Therma Stor Products Group Ventilation Hood Quiet Vent Ventilation System User Manual |
Quiet-Vent
TS-174E
Owner’s Manual — Quiet-Vent Ventilation System
Installation, Operation & Service Instructions
Read and Save These Instructions
Quiet-Vent is a central exhaust ventilation system that replaces noisy, low output and
unreliable bath fans. With today’s tight homes, Quiet-Vent presents one of the best ways
to eliminate pollutants (i.e. normal household chemicals, outgasing from construction
materials, furniture and carpeting) by exhausting them out of the home. Quiet-Vent
also reduces humidity levels that otherwise lead to mildew in closets, condensation on
windows, insulation and walls which, over just a few years can cause costly damage.
Specifications subject to change without notice.
11/06
Toll-Free ꢀ-800-533-7533
ꢀ
Download from Www.Somanuals.com. All Manuals Search And Download.
be positioned in the home to minimize the amount of
duct and wire required for installation. The unit should
be mounted and oriented to allow periodic blower oiling,
cleaning of the internal blower screen via the side
mounted clean-out port, and adjustment of the 7-day timer
(the timer can be remote mounted away from the Quiet-
Vent (see paragraph F). In cold climates the unit should be
located in a heated space to prevent condensation from
forming inside the cabinet. A basement or utility room is
an ideal location.
14.5”
11” Hanger Strap
(4 supplied)
Oil Port
6”
Inlet
Electrical
Box Cover
13.125”
If the Quiet-Vent and its ducting must be located in a
unheated space in a cold climate, they must be insulated
to prevent condensation from forming in the system.
13.5”
7-Day Timer
If the Quiet-Vent is used to correct a moisture problem in
an existing house, a 6” duct should be run from near the
ceiling in the center of the house to the Quiet-Vent (see
Fig. 3). This will provide adequate ventilation.
Figure 1
11” Hanger St
rap
(4 supplied)
2.3 Fresh Air Inlets
The “FRESH 80” fresh air inlets are recommended to
provide fresh air to the bedrooms and prevent excessive
depressurization. These fresh air inlets should be located
on an exterior wall near the ceiling in any isolated rooms
that are occupied for extended periods of time with the
door closed. These vents have an adjustable opening, a
filter and a shut off valve. One air inlet is recommended in
each bedroom.
6”
4”
Inlet
Inlet
4”
Inlet
4”
Inlet
Figure 2
Figure 3
Toll-Free ꢀ-800-533-7533
3
Download from Www.Somanuals.com. All Manuals Search And Download.
2.4 Hanging the Quiet-Vent
Circuit to next timer in bath or kitchen
Timer switch ground
The Quiet-Vent has four vibration absorbing straps for
hanging from joists, rafters, or trusses (See Fig. ꢀ & 3)
and use (4) ꢀ/4” diameter lag bolts or the equivalent.
Locate the unit to minimize the ducting from the baths and
kitchen to the Quiet-Vent inlets and from the Quiet-Vent
outlet to the outside. Because the oiling system depends
on gravity, the unit must be oriented with the hanger bolts
on the top.
Timer switch
ground
115 Volt circuit/ground from
Quite-Vent to bath or kitchen
10-15 AMP 115 Volt
circuit with ground from
main electrical service
2.5 Ducting to and from the Quiet-Vent
Alternative Electrical
Layouts
All flexible ducting connected to the unit should be UL
listed. The preferred method of ducting the exhaust air
from the rooms is to use 4” round duct from 4” x 6”
register heads located in the wall cavities or the ceiling.
For routing through 3.5” stud cavities, flatten the 4”
round duct to 3.ꢁ5”. If a 4” duct length from a full bath
or kitchen exceeds 50’, two 4” ducts or a 6” duct is
recommended. The 4” duct can be either metal or flexible
and can be routed to the Quiet-Vent 4” inlet or manifolded
to a 6” duct. If more than four 4” ducts are connected to
the Quiet-Vent, use a 6” manifold on the Quiet-Vent’s 6”
inlet.
DO NOT locate the register head connecting the kitchen duct to
the Quiet-Vent in the area designated in Fig. 5.
To exhaust the stale air, connect a six inch insulated
flexible duct from the outlet of the Quiet-Vent to a
dampered six inch wall cap. If the length of the exhaust
duct exceeds 50 ft., an 8” duct should be used. All the
ducts must be insulated when they are located in non-
heated space in a cold climate. Flexible duct can be
spliced by threading the ends of the ducts into each
other 3 turns. To reduce leakage, all the duct couplings
should be taped with 3 turns of duct tape. Several ducting
alternatives are illustrated in Fig. 3.
2.6 Wiring the Quiet-Vent
NOTE: All electrical connections must be installed by a qualified
electrician. All wiring must conform to the local electric codes
and/or the National Electrical Code.
Figure 4
Quiet-Vent uses a ꢀꢀ5 volt, ꢀ0 amp circuit which is
connected to the black and white wires in the electrical
cabinet (see Fig. 4). Spring wound one hour remote timers
or humidity controllers located in the baths and kitchen
are wired in parallel to the two blue wires. These remote
controls activate the high speed of the exhaust fan. These
controls are to be UL listed with minimum electrical ratings
of ꢁ amps inductive load at ꢀꢁ5 VAC.
Cooking Area
Do Not Install Above or Inside
This Area
The prewired 7 day timer located on the Quiet-Vent
activates the low speed of the exhaust fan. The timer can
be mounted remote from the Quiet-Vent. This requires a
double gang electrical box and 3 conductors plus ground
to extend connections to the timer from the Quiet-Vent.
45°
45°
Floor
Cooking
Equipment
A 4” junction box cover is used to cover the timer opening
on the Quiet-Vent.
Figure 5
Toll-Free ꢀ-800-533-7533
4
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING: To reduce the risk of fire, electric shock, or injury to
persons, observe the following:
A. Use this unit only in the manner intended by the manufacturer.
If you have questions, contact the manufacturer.
B. Before servicing or cleaning unit, switch power off at service
panel and lock service disconnecting means to prevent power
from being switched on accidentally. When the service disconnect-
ing means cannot be locked, securely fasten a prominent warning
device, such as a tag, to the service panel.
CAUTION: For general ventilating use only. Do not use to exhaust
hazardous or explosive materials and vapors.
3 Operation
Figure 6
3.1 Using the Timers
1. Setting The 7-Day Timer
Rotate the timer dial until the white pointer indicates
the correct time of day. Each segment moved toward the
dial center represents ꢁ hours of low speed exhaust fan
operation. Typically, the timer is set to operate during the
time of occupancy. If additional ventilation is required to
control moisture and odors, additional spades can be
moved in. If the home becomes too dry, decrease the
hours of low speed operation.
4 Maintenance
4.1 Lubricating the Blower Motor
Although the motor is factory lubricated for many years of
normal operation, additional oiling will extend motor life.
To facilitate motor oiling, tubing from the motor extends
outside the Quiet-Vent cabinet (See Fig. ꢀ). Five to ten
drops of SAE ꢁ0 Non-Detergent oil is recommended every
six months.
3.2. Using Remote Timers
Estimate the ventilation time required and set it on the
timer. Activate the timer whenever moisture or odors are
generated in the room. If timers are not available locally,
they may be ordered with the Quiet-Vent.
4.2 Cleaning the Blower Screen
WARNING: Disconnect the appliance from the power supply before
cleaning the blower screen.
3.2 Adjusting the Amount of Ventilation
A coarse screen covers the blower inlet port located
inside the Quiet-Vent cabinet. Vacuuming the screen is
recommended every six months. Remove the 4” x 4” cover
on the side of the Quiet-Vent cabinet for access (See Fig.
ꢁ).
The amount of air removed from the home depends on the
restrictions in the duct system and the amount of time the
system operates. If more or less ventilation is required
the 7-day timer can be set for more or less low speed
operation. The air flow can be reduced by installing a duct
damper in the exhaust duct of the Quiet-Vent.
By partially closing the damper, the CFM of stale air
removed from the house can be reduced. Figure 6
indicates air flow and power consumption versus static
duct pressure.
Toll-Free ꢀ-800-533-7533
5
Download from Www.Somanuals.com. All Manuals Search And Download.
5.4 Fan Motor
If the blower motor fails to operate when voltage is present
at its leads, the motor is defective and the blower must be
replaced.
5 Service
CAUTION: Requires a qualified service person because electrical
shock hazard is present.
5.5 Warranty
The Quiet-Vent is guaranteed for two years from the date of
installation against all manufacturing defects provided the
Quiet-Vent has been installed, operated, and maintained
as stated in this manual. This warranty is limited to the
repair or replacement of the equipment, F.O.B. MADISON,
WI. Call the factory at ꢀ-800-533-7533.
5.1 Circuit Breaker Trips
Check For Short In Wiring:
Turn off the 7-day timer by moving all the spades out. Turn
off all the remote timers and the dehumidistat (if used). If
the circuit breaker trips, locate a short in the wiring. If the
circuit breaker does not trip, activate the 7-day timer. If the
circuit breaker then trips, check the blower motor.
6 Service Parts
Item
Part Number
Qty
Description
5.2 Blower Operates on One Speed Only
Operates On Low Speed Only:
ꢀ
40ꢁꢁ036
ꢀ
Blower, w/ Capacitor, ꢀꢀ5V
(Fasco p/n 7090-ꢀ806)
If the blower operates only on low speed, deactivate the
7-day timer so that unit is not running. Activate one of
the optional controls and then check for voltage to the
relay coil (terminals 7 and 8). See Figure 4. If voltage is
not present, check for a loose wire or a defective optional
control. If voltage is present, check for voltage between
relay terminal 4 and ground. If there is no voltage, the relay
is defective. If there is voltage at terminal 4 and the motor
does not operate, the high speed winding of the blower
motor is defective. Replace the blower.
ꢁ
3
4
40ꢀ978ꢁ
40ꢀ9649
40ꢀ9648
4
ꢀ
ꢀ
Mounting Strap, Rubber
Relay, DPDT, ꢀꢁ0V, ꢀ0A
Timer, 7-Day (Diehl TA-4073,
Model 880)
5
40ꢀ964ꢀ
40ꢀ964ꢁ
40ꢀ9643
40ꢀ9644
40ꢀ9645
40ꢀ9654
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
Wire Harness, Lꢀ
Wire Harness, Lꢁ
Wire Harness, Blue
Wire Assembly, Red
Wire Assembly, Green
Wiring Diagram
6
7
8
9
ꢀ0
Operates On High Speed Only:
High speed operation of the blower has priority over low
speed. Verify that all the optional controls are in the off
position. If the blower operates on high speed constantly,
check for voltage between relay terminals 7 and 8. If
voltage is present, one of the optional controls is not
opening and is defective.
If the blower operates only on high speed (when the
optional controls are activated) and is off the rest of the
time, check that the segments on the 7-day timer are
moved to the center of the dial, thus calling for low speed
ventilation. If the blower does not run with the segments
in and the optional controls off, check for voltage between
timer terminal 5 and ground. If terminal 5 does not have
voltage, the timer is defective. If terminal 5 has voltage
and relay terminal 5 does not have voltage, the relay is
defective. If relay terminal 5 has voltage, the low speed
winding of the blower motor is defective.
5.3 7-Day Timer Does Not Advance
Check for voltage between timer terminals ꢀ and ꢁ. If
voltage is present and the timer does not advance, the
timer motor is defective and the timer must be replaced.
Specifications subject to change without notice.
Toll-Free ꢀ-800-533-7533
6
Download from Www.Somanuals.com. All Manuals Search And Download.
QUIET-VENT Ventilating System Limited Warranty
Warrantor:
Therma-Stor LLC
PO Box 8680
Madison, WI 53708
Telephone: ꢀ-800-533-7533
Who Is Covered: This warranty extends only to the original residential end-user of the Quiet-Vent
Ventilating System, and may not be assigned or transferred.
Warranty: Therma-Stor LLC warrants that, for two (ꢁ) years from the date of installation, the Quiet-
Vent Ventilating System will operate free from any defects in materials and workmanship, provided
the Quiet-Vent has been installed, operated, and maintained as stated in the installation and
operation manual. This warranty is limited to the repair or replacement of the equipment F.O.B.
Madison, WI. Call the factory at ꢀ-800-533-7533.
Limitation and Exclusions: If any Quiet-Vent Ventilating System part is repaired or replaced, the new
part shall be warranted for only the remainder of the original warranty period applicable thereto
(but all warranty periods will be extended by the period of time, if any, that the QUIET-VENT is out of
service while awaiting covered warranty service).
UPON THE EXPIRATION OF THE WRITTEN WARRANTY APPLICABLE TO THE QUIET-VENT VENTILATING
SYSTEM OR ANY PART THEREOF, ALL OTHER WARRANTIES IMPLIED BY LAW, INCLUDING
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, SHALL ALSO EXPIRE. ALL
WARRANTIES MADE BY THERMA-STOR LLC ARE SET FORTH HEREIN, AND NO CLAIM MAY BE MADE
AGAINST THERMA-STOR LLC BASED ON ANY ORAL WARRANTY. IN NO EVENT SHALL THERMA-STOR
LLC, IN CONNECTION WITH THE SALE, INSTALLATION, USE, REPAIR OR REPLACEMENT OF ANY QUIET-
VENT VENTILATING SYSTEM OR PART THEREOF BE LIABLE UNDER ANY LEGAL THEORY FOR ANY
SPECIAL, INDIRECT OR CONSEQUENTIAL DAMAGES (THE END-USER SHOULD TAKE PRECAUTIONS
AGAINST SAME), OR LOSS OF USE OR DAMAGE TO ANY REAL OR PERSONAL PROPERTY.
Some states do not allow limitations on how long an implied warranty lasts, and some do not allow
the exclusion or limitation of incidental or consequential damages, so one or both of these limitation
may not apply to you.
Legal Rights: This warranty gives you specific legal rights, and you may also have other rights which
vary from state to state.
TS-ꢁ84-ꢀꢁ03
Toll-Free ꢀ-800-533-7533
7
Download from Www.Somanuals.com. All Manuals Search And Download.
|