System Sensor Smoke Alarm Smoke Detector Spacing on Level Ceilings with Beams and Joists User Manual

White Paper  
September 1, 2006  
Smoke Detector Spacing on Level Ceilings  
with Beams and Joists  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Smoke Detector Spacing on Level Ceilings with Beams and Joists  
and Vision Systems Ltd. using Fire Dynamics Simulator and Smokeview Version  
41 (developed by the National Institute of Science and Technology). The results of  
this research were published in a report entitled, “Smoke Detector Performance  
for Level Ceilings with Deep Beams and Deep Beam Pocket Configurations.”2 The  
report was issued March 28, 2006 and was the basis for recommended changes to  
NFPA 72.  
Based on a variety of modeled flaming fire scenarios, the results of this  
study indicate:  
• There is no technical basis for the NFPA 72 2002 edition requirement  
for placing smoke detectors in every beam pocket when ceilings are  
greater than 12 feet in height and/or beams are greater than 12 inches  
in depth.  
• The smooth ceiling 30-foot spacing guideline of NFPA 72, with permitted  
increases for narrow space geometry, allows smoke detectors to extend  
to approximately 41 feet on-center and along a corridor. For ceilings up to  
24 feet in height, the deep-beam configurations do not negatively affect  
expected performance. This means that for corridor conditions, spot  
smoke detectors can be effectively used with deep beams at spacings for  
smooth ceilings.  
A recent analysis shows  
no basis for many of the  
spacing requirements in the  
2002 edition.  
• Standard 900-square-foot smoke detector spacing is adequate for waffle  
or pan type ceilings up to 24 feet in height and for beams up to 24 inches  
in depth that are spaced no greater than 12 feet on center.  
• Spot smoke detectors may be placed on the bottom of the beams or in  
the beam pocket without any significant difference in performance.  
• The concern about mounting smoke detectors a minimum of 12 inches  
from a ceiling-beam corner, per NFPA 72, is unsubstantiated. The CFD  
modeling showed no stagnant areas in the beam pockets that would  
preclude smoke detector activation. Although the modeling results  
showed no stagnant zones, it does not suggest that spot detectors can  
be installed in close proximity or contact to the wall or ceiling surface.  
The research report notes that such close mounting may impact the  
airflow characteristics into and around the detector housing, which  
could have a negative impact on how smoke flows into a detector’s  
sensing chamber.  
1 The CFD software is available free of charge from the NIST web site: www.fire.nist.gov/fds.  
2 The full report is available on the National Fire Protection Association web site: www.nfpa.org.  
System Sensor. Advanced Ideas. Advanced Solutions.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Smoke Detector Spacing on Level Ceilings with Beams and Joists  
Recommendations  
Based on these findings, the report authors proposed language for addition to the body and annex of NFPA 72.  
The language clarifies how smoke detectors shall be placed on ceilings with beams and joists. These changes  
are expected to be incorporated into the 2007 edition of NFPA 72, which will be released in late 2006, to quell  
some of the debate surrounding the current requirements for smoke detectors on beam ceilings.  
Conclusion  
As a part of the National Fire Protection Association’s mission to “reduce the worldwide burden of fire” by  
continually updating their consensus codes based on the latest research available, NFPA commissioned this study  
of smoke detector spacing. The results of this study and accompanying code changes are expected to reduce the  
overall cost of fire protection systems in beam ceiling applications while not comprising occupant safety.  
Acknowledgement  
This document was written with guidance from Schirmer Engineering Corporation.  
For more information regarding Smoke Detector Spacing, please contact:  
System Sensor  
3825 Ohio Avenue  
St. Charles, Illinois 60174  
1-800-sensor2  
A05-0408-000 • 9/06 • #1703  
System Sensor. Advanced Ideas. Advanced Solutions.  
4
©2006 System Sensor  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Server Technology Switch CDUCW 24V4 User Manual
Sharp Calculator EL 240S User Manual
Sharp Projection Television PG C20X User Manual
Sony Camcorder Accessories CCD FX310 User Manual
Sony Cell Phone LT26i User Manual
Sony Computer Drive VRD MC6 User Manual
Speco Technologies Security Camera CVC 340LC W User Manual
Speco Technologies Security Camera CVC 1705 User Manual
State Industries Water Heater SBD100400NE A User Manual
State Industries Water Heater STGPG 0303 User Manual