System Sensor Smoke Alarm BS5839 User Manual

SYSTEM SENSOR EUROPE  
guide to intelligent  
fire systems  
Advanced Ideas. Advanced Solutions  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. CALL POINTS..............................................................................................28  
INDOOR................................................................................................................................................................................28  
OUTDOOR.............................................................................................................................................................................28  
WATERPROOF.......................................................................................................................................................................28  
SWITCHES............................................................................................................................................................................28  
ACCESSORIES......................................................................................................................................................................28  
6. AUDIO VISUAL PRODUCTS ..........................................................................29  
SOUNDERS...........................................................................................................................................................................29  
DETECTOR BASE SOUNDERS................................................................................................................................................29  
STROBES..............................................................................................................................................................................29  
SOUNDER STROBES .............................................................................................................................................................29  
BASES..................................................................................................................................................................................29  
7. OTHER INFORMATION .................................................................................30  
7.1. STANDARDS..................................................................................................................................................................30  
7.2. APPROVAL BODIES FOR FIRE DETECTION PRODUCTS................................................................................................... 31  
Note: This document is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire d
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.2. INTELLIGENT SYSTEM TYPES  
1. INTELLIGENT FIRE ALARM  
SYSTEMS  
There are two methods commonly used for implementing  
intelligent fire systems:  
1.1. INTRODUCTION  
The most common type of system is “Analogue”. In this  
case the detector (or sensor) returns a value to the panel  
representing the current state of its sensing element(s). The  
control panel compares this value with the alarm threshold  
in order to make the decision as to whether a fire is present.  
Note that the term analogue, used to describe these systems  
does not refer to the communication method (indeed many  
“analogue” fire systems use digital communications) but to  
the variable nature of the response from the detector to the  
control panel.  
Conventional fire alarm systems provide an adequate and  
cost effective fire alarm system for many small buildings. In  
larger, more complex buildings however, more sophisticated  
‘intelligent’ fire alarm systems tend to be used. These  
systems offer benefits in speed of detection, identification  
of the location of a fire and easier maintenance. Intelligent  
systems also offer tolerance to faults in the system wiring,  
which allows a single pair of wires to be used to connect up  
to 198 devices to the system, allowing cost savings in the  
wiring of large systems. In larger installations, the benefits  
of improved maintenance and reduced cabling cost are  
overwhelming. Currently, the point at which an intelligent  
system becomes economical is around 6 zones in the UK.  
In “Addressable” type intelligent systems, mainly used to meet  
the requirements of the French market, detector sensitivity is  
programmed to each device by the control panel or is preset  
in the factory. The detector compares its current sensor value  
with the configured threshold to make the alarm decision,  
which is then transmitted to the panel when the sensor is  
interrogated.  
This guide is intended as an introduction to the technology  
used in intelligent fire alarm systems. For more information  
on conventional systems, refer to System Sensor’s ‘Guide to  
Conventional Fire Systems’.  
In many systems the features offered by the two detection  
techniques are so similar that it is not particularly relevant  
which technique is used to make the alarm decision. It is  
better to select a system based on the features offered by the  
system as a whole.  
ISOLATOR  
FIRE ALARM SYSTEM OK  
28 January 2004  
14:01  
SYSTEM OK  
FIRE ALARM  
FAULT  
CONTROL  
SYSTEM RESET  
MODULE  
1.3. COMMUNICATION PROTOCOL  
CONVENTIONAL  
ALARM ZONE  
INTELLIGENT  
FIRE ALARM  
CONTROL  
PANEL  
Intelligent systems use the same pair of wires both to supply  
power to the loop, and to communicate with devices on the  
loop. The communication language, or protocol used varies  
from manufacturer to manufacturer, but generally comprises  
switching of the 24V supply voltage to other voltage levels to  
achieve communication.  
ISOLATOR  
MONITOR  
MODULE  
CONTACT  
(E.G. SPRINKLER  
SWITCH  
ISOLATOR  
+24V  
Panel to detector  
Detector Response  
Sensor Other Info  
Figure 1.1.1 Intelligent Fire Alarm Systems  
Device  
Type  
Detector  
Address  
Control  
Value  
e.g. drift  
status  
Figure 1.1.1 demonstrates an example of a single loop  
intelligent fire system layout. The wiring is looped, and  
connects to the control panel at each end. All detectors, call  
points, sounders and interface modules are wired directly  
to the loop, each having its own address. The control panel  
communicates with each device on the loop, and if an alarm or  
fault condition is signalled, or if communications are lost with  
one or more detectors, the appropriate response is triggered.  
The loop can be powered from each end so that if the loop is  
broken at any point, no devices are lost. In addition the use of  
short circuit isolators minimises the area of coverage lost in  
the case of a short circuit.  
Figure 1.3.1 Typical Protocol Configuration  
A typical basic protocol comprises two main parts (See  
Fig 1.3.1): A query or poll of a device by the control panel  
including the device address and control information, and  
a response from the device giving its status and other  
information. Precise details of the information transferred will  
depend on the manufacturer, but normally will include:  
Poll: Control Panel to device:  
• Device address  
• Control of device LED - blink to indicate polling, switch  
on when device is in alarm  
• Control of device self-test  
• Control of module output  
• Error detection for example parity bit or checksum  
Response: Device to Control Panel  
• Device type (e.g. optical detector, heat detector, multi-  
sensor detector, module)  
• Analogue Signal - i.e. the current sensor value  
ent is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire detection systems.  
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
only from one end. If the loop is broken (See figure 1.5.1.),  
the panel will detect the loss of communications with the  
detectors beyond the break, signal a fault, and switch to drive  
the loop from both ends. The system therefore remains fully  
operational, and can possibly even indicate the area of the  
break.  
• Alarm Signal if appropriate  
• Status of module output  
• Remote test status  
• Manufacturer code  
Most commonly, each device on the loop will be polled in turn,  
however to increase speed around a loop, some protocols  
allow polling of groups of devices on a single communication.  
In order to give tolerance against short circuits on the loop,  
short circuit isolators are placed at intervals on the loop.  
Should a short circuit occur on the loop (Figure 1.5.2.) the  
isolators directly on either side of the fault will isolate that  
section. The panel will detect the loss of the devices, signal  
a fault and drive the loop from both ends, thereby enabling  
the remainder of the loop to operate correctly and ensuring  
minimum loss of coverage.  
Note that since different manufacturers have their own  
protocols, it is important to ensure compatibility between  
the detectors and control panel you intend to use. Some  
detector manufacturers produce intelligent detectors  
with different communication protocols for different  
customers, so two detectors which look virtually  
identical in appearance may not be compatible. Always  
check with the manufacturer of the control panel.  
Short circuit isolators are available as separate modules and  
incorporated into a detector base.  
1.4. ADDRESSING METHODS  
Some products, for example System Sensor’s M200 Series  
modules, have isolators built into each of the loop devices.  
With this configuration, since only the section of wiring  
between the two adjacent devices is isolated there will be no  
loss of coverage should a short circuit occur.  
Different manufacturers of intelligent systems use a number  
of different methods of setting the address of a device,  
including:  
• 7-bit binary or hexadecimal DIL switch  
• Dedicated address programmer  
24V  
• Automatic, according to physical position on the loop  
• Binary ‘address card’ fitted in the detector base  
• Decimal address switches  
Line break  
SYSTEM FAULT: OPEN CIRCUIT:  
Zone 2 Module 01  
FIRST FLOOR CANTEEN  
Panel detects the loss of  
devices after the break,  
signals a fault and powers  
from both ends of the loop  
SYSTEM OK  
FIRE ALARM  
FAULT  
to retain full coverage.  
SYSTEM RESET  
System Sensor’s Series 200 plus range of intelligent devices  
uses decimal address switches to define a device’s address  
between 00 and 99 (See Figure 1.4.1). This is a simple  
intuitive method, not requiring knowledge of binary or  
purchase of specialised equipment to set addresses.  
INTELLIGENT  
FIRE ALARM  
CONTROL PANEL  
24V  
Figure 1.5.1. Open Circuit Fault  
4
0
5
9
4
0
5
9
Isolating  
Impedance  
6
8
6
8
3
3
7
7
2
2
24V  
Isolators on either side of  
the short circuit switch an  
impedance onto the line  
to isolate it.  
SYSTEM FAULT: SHORT CIRCUIT:  
Zone 2 DETECTOR 03  
FIRST FLOOR CANTEEN  
1
1
SYSTEM OK  
Devices between the two  
isolators are lost,  
FIRE ALARM  
FAULT  
however the remainder of  
the circuit still operates  
correctly.  
Short Circuit  
SYSTEM RESET  
TENS  
UNITS  
INTELLIGENT  
FIRE ALARM  
CONTROL  
Isolators automatically  
reset the line when the  
short circuit is removed  
Figure 1.4.1 System Sensor decade address switches  
-Address 03 selected  
PANEL  
24V  
Isolating  
Impedance  
Differences in the protocol between detectors and modules  
allow them to have the same address without interfering  
with each other, and normally address 00 (the factory default  
setting) is not used within a system so that the panel can  
identify if a device address has not been set: Hence a total of  
up to 198 devices - 99 detectors and 99 modules (including  
call points, sounders, input and output modules) may be  
connected to a loop.  
Figure 1.5.2. Short Circuit Fault  
1.5. SYSTEM FAULT TOLERANCE  
Due to the looped wiring method used for analogue systems,  
they are more tolerant to open and short circuit wiring faults  
than conventional systems.  
Under normal conditions, the loop will typically be driven  
Note: This document is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire d
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
use control modules to operate additional electrical equipment  
such as air conditioning units and door releases to prevent the  
spread of smoke and fire.  
1.6. DRIFT COMPENSATION AND MAINTENANCE ALARM  
The sensitivity of a smoke detector tends to change as it  
becomes contaminated with dirt or dust (see figure 1.6.1). As  
contamination builds up, it usually becomes more sensitive,  
leading to the risk of a false alarm, but in some cases can  
become less sensitive, so delaying the alarm if a fire is  
detected. To counter this, if a detector drifts outside its  
specification, a maintenance signal may be sent to the panel  
warning that the detector needs cleaning.  
The alarm signals can either be a zone of conventional  
sounders and strobes activated via control modules on the  
loop or directly from the control panel, or addressable loop  
powered devices connected on the same loop as the detectors  
and activated by direct command from the panel. Loop  
powered sounders tend to have lower wiring costs, however  
the number permissible on the loop may be restricted by  
current limitations.  
To further increase the maintenance interval, many systems  
incorporate a “drift compensation” function, included in either  
the detector or the control panel algorithms. These functions  
use algorithms that monitor the sensitivity of a detector, and  
modify its response to compensate for a build up of dust in  
the chamber over time. Once the detector reaches the “drift  
limit” when the dirt build up can no longer be compensated  
for, a fault can be signalled. Some systems also incorporate  
a warning to signal that a detector is approaching its  
compensation limit and requires cleaning.  
On larger sites, it may be desirable to use zoned alarms. This  
allows a phased evacuation to be carried out, with areas  
at most immediate risk being evacuated first, then less  
endangered areas later.  
1.9. FIRE SYSTEM ZONES  
Conventional fire alarm systems group detectors into  
‘zones’ for faster location of a fire, with all the detectors in  
a particular zone being connected on one circuit. Although  
intelligent systems allow the precise device that initiated an  
alarm to be identified, zones are still used in order to make  
programming the system and interpreting the location of a fire  
easier. The control panel will have individual fire indicators  
for each zone on the system, and the control panel response  
to an alarm is often programmed according to the zone of the  
device in alarm rather than its individual address.  
Threshold  
increased to  
compensate for  
increased chamber  
clean air value.  
Smoke required to  
reach alarm  
threshold reduces -  
Detector sensitivity  
increases  
Whilst the division of a loop into zones is achieved within the  
panel software, BS5839 part 1 recommends that a single  
wiring fault in one zone should not affect the operation  
of the system in other zones of the building. To meet this  
recommendation, a short circuit isolator should be placed on  
each boundary between zones (figure 1.9.1). In this instance,  
a short circuit in one zone would cause the isolators on either  
side of the zone to open, thereby disabling that zone. Any  
devices in neighbouring zones would be protected by the short  
circuit isolators and remain operational.  
Time  
Clean Air  
Value  
Uncompensated  
Alarm Threshold  
Uncompensated  
Chamber Value  
Compensated  
Threshold  
Figure 1.6.1 Chamber Contamination and Drift  
Compensation  
1.7. PRE-ALARM FACILITY  
One advantage of intelligent type systems is that since the  
data sent by a detector to the panel varies with the local  
environment, it can be used to detect when the device is  
approaching an alarm condition. This “Pre-Alarm” can be  
signalled at the panel and can therefore be investigated to  
check if there is a real fire, or if it is caused by other signals,  
for example steam or dust from building work. This can  
avoid the inconvenience and expense of evacuating a building  
or calling out the fire brigade unnecessarily because of a  
nuisance alarm. The Pre-Alarm Threshold is typically set at  
80% of the alarm threshold.  
ISOLATOR  
FIRE ALARM SYSTEM OK  
28 January 2003  
12:15 pm  
SYSTEM OK  
FIRE ALARM  
FAULT  
Zone 1  
SYSTEM RESET  
INTELLIGENT  
FIRE ALARM  
CONTROL  
PANEL  
Zone 2  
Zone 3  
ISOLATOR  
1.8. FIRE ALARMS  
Zone 4  
When a fire is detected, the control panel indicates an alarm  
by activating the fire indicator for the relevant zone on the  
control panel, sending a command to the relevant detector  
to illuminate its LED and activate alarm signals to start  
evacuation. Most intelligent fire system control panels include  
alphanumeric displays enabling them to show information  
on the source of the alarm. This may simply be a zone and  
detector address, or could be more descriptive for example  
“Smoke Detector, Bedroom 234”. The control panel may also  
ISOLATOR  
Figure 1.9.1 Intelligent System Fire Zones  
ent is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire detection systems.  
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.10. REMOTE LEDS  
1.13. ADVANTAGES OF INTELLIGENT SYSTEMS  
Most system smoke detectors are equipped with a terminal to  
allow the connection of a remote LED. Remote LEDs are often  
used outside bedroom doors in hotels so that in case of a fire,  
it is easy for the fire brigade to identify the location of the fire  
without the need to enter every room in the building. They  
may also be used where a detector is concealed in loft space,  
for example, to provide a visual indication that the detector is  
in an alarm state.  
• The wiring cost of a system can be reduced by the use  
of a single pair of wires for up to 198 devices including  
smoke and heat detectors, call points, beam detectors,  
input and output modules.  
• Intelligent Systems allow the location of a fire to be  
precisely located from the control panel  
• The use of looped wiring allows the system to function  
normally even with an open circuit in the loop wiring  
1.11. INTERFACE MODULES  
• The use of short circuit isolators allows correct  
operation of most, if not all of the system even with a  
short circuit in the loop wiring  
Input and Output modules can be used to provide an interface  
between a fire loop and a variety of types of electrical  
equipment. Output or control modules can be used to operate  
sounders or shut down electrical equipment by command  
from the panel in case of a fire. Input or monitor modules are  
used to monitor volt-free switch contacts, for example from a  
sprinkler supervisory switch or an existing conventional fire  
panel. Conventional zone monitor modules are also available,  
providing an interface between a zone of conventional  
detectors and an analogue fire detection loop, and are often  
used when existing conventional systems are upgraded.  
• Detectors are constantly monitored for correct  
operation  
• The use of a ‘pre-alarm’ feature alerts staff to check  
whether a fire condition exists before the alarm is raised  
• Different detector sensitivities can be used for diverse  
applications  
• The use of addressable loop-powered sounders allows  
the same wiring to be used for sensors, call points and  
sounders  
1.12. PROGRAMMING OF INTELLIGENT FIRE ALARM  
PANELS  
• The use of monitor modules allows contacts from  
sprinkler switches, existing fire alarm systems, fire  
dampers etc. to be monitored using detector loop wiring  
Most small intelligent systems can be programmed with  
ease without the need for any specialised equipment. The  
control panel has an alphanumeric keypad, which is used to  
enter data into the system. Typically a password is required  
to set the panel to ‘engineering mode’, allowing the panel to  
be programmed. Many control panels have an ‘auto-learn’  
facility, whereby the control panel polls every address on the  
system, and detects which addresses have been used, and  
what type of detector or module has been connected to each  
address. As a default, the panel will usually programme all  
the devices on the loop into the same zone. The user can  
then customise the system by entering how the zones are  
configured. The panel may give the user an option of how  
modules are to be configured - for example whether an input  
module should trigger an alarm or a fault when operated and  
whether the wiring is to be monitored for open circuit faults.  
• The use of control modules allows sounder lines, air  
conditioning systems, lifts etc. to be controlled or shut  
down using detector loop wiring  
Other optional features may also be programmed using the  
keypad. The sensitivity of each detector on the system can  
be configured for high sensitivity if the detector is installed  
in a clean smoke-free area, or for low sensitivity if the area  
is subject to cigarette smoke, for example. The pre-alarm  
facility may be enabled or disabled.  
Complex intelligent systems offer many user-programmable  
features that can be time-consuming to enter manually  
using the keypad. In this case, many panels have the facility  
to connect a portable PC by means of a serial data link.  
The user is supplied with a specialised piece of software,  
which enables the entire configuration of the system to be  
programmed into the PC, away from site if necessary. It is  
then a simple matter of temporarily connecting the PC to the  
control panel and downloading the system configuration to  
the panel. Once the information has been downloaded, it is  
permanently stored in the control panel, and the PC can be  
removed.  
Note: This document is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire d
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. DETECTOR APPLICATION GUIDE  
2.1. FIRE SYSTEM CATEGORIES.  
Before a fire protection system can be designed, it is necessary to define the main objectives of the system. This is normally  
determined by a fire risk assessment, and should be provided as part of the fire system specification. BS5839 Part 1: 2002  
defines three basic categories of fire detection system.  
2.1.1.  
Category M Systems  
Category M systems rely on human intervention, and use only  
manually operated fire detection such as break glass call  
points. A category M system should only be employed if no  
one will be sleeping in the building, and if a fire is likely to be  
detected by people before any escape routes are affected.  
Any alarm signals given in a category M system must be  
sufficient to ensure that every person within the alarm area is  
warned of a fire condition.  
Kitchen  
Canteen  
Pantry  
Paper  
Store  
Office  
Office  
2.1.2.  
Category L Systems  
Category L systems are automatic fire detection systems  
intended to protect life. The category is further subdivided as  
follows:  
Category L5: In a category L5 system certain areas within  
a building, defined by the fire system specification, are  
protected by automatic fire detection in order to reduce the  
risk to life. This category of system may also include manual  
fire protection.  
Kitchen  
Canteen  
Pantry  
Paper  
Store  
Office  
Office  
Example L5 System: L4 protection plus areas of high risk  
Category L4: Designed to offer protection to the escape  
routes from a building. The system should comprise Category  
M plus smoke detectors in corridors and stairways  
Kitchen  
Pantry  
Canteen  
Paper  
Store  
Office  
Office  
Category L3: Intended to offer early enough notification of a  
fire to allow evacuation before escape routes become smoke  
logged. Protection should be as for category L4 with the  
addition of smoke or heat detectors in rooms opening onto  
escape routes.  
Canteen  
Pantry  
Kitchen  
Paper  
Store  
Office  
Office  
ent is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire detection systems.  
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Kitchen  
Category L2: Objectives are similar to category L3, however  
additional protection is provided for rooms at higher risk.  
Protection should be as for category L3 plus smoke detectors  
in specified rooms at high risk  
Canteen  
Pantry  
Paper  
Store  
Office  
Office  
Category L1: The highest category for the protection of life.  
Intended to give the earliest possible notification of a fire in  
order to allow maximum time for evacuation. Automatic and  
manual fire detection installed throughout all areas of the  
building. Smoke detectors should be employed wherever  
possible to protect rooms in which people can be expected to  
be present.  
Kitchen  
Canteen  
Pantry  
Paper  
Store  
Office  
Office  
Similarly to class M systems, all alarm signals given in  
a category L system must be sufficient to warn all those  
people for whom the alarm is intended to allow for a timely  
evacuation.  
2.1.3.  
Category P Systems  
Category P systems are automatic fire detection systems  
whose primary objective is to protect property. The category  
is subdivided as follows:  
Category P2: Intended to provide early warning of fire  
in areas of high hazard, or to protect high-risk property.  
Automatic fire detection should be installed in defined areas  
of a building.  
Materials  
Storage  
Electric Plant  
Computer  
Equipment  
Materials  
Storage  
Electrical Plant  
Category P1: The objective of a category P1 system is to  
reduce to a minimum the time from the ignition of a fire to  
the arrival of the fire brigade. In a P1 system, fire detectors  
should be installed throughout a building.  
In a category P system, unless combined with category M, it  
may be adequate for alarm signals simply to allow fire fighting  
action to be taken, for example a signal to alert a responsible  
person to call the fire brigade.  
Computer  
Equipment  
Note: This document is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire d
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.2. MANUAL CALL POINTS  
People can often still detect a fire long before automatic  
fire detectors; hence manual call points are important  
components of fire detection systems in occupied buildings  
to ensure timely evacuation in the case of fire. All call points  
should be approved to EN54-11, and should be of type A, that  
is once the frangible element is broken or displaced the alarm  
condition is automatic.  
Manual call points should be mounted on all escape routes,  
and at all exit points from the floors of a building and to  
clear air. It should not be possible to leave the floor of a  
building without passing a manual call point, nor should it  
be necessary to deviate from any escape route in order to  
operate a manual call point. Call points mounted at the exits  
from a floor may be mounted within the accommodation or  
on the stairwell. In multiple storey buildings where phased  
evacuation is to be used call points should be mounted within  
the accommodation to avoid activation of call points on lower  
levels by people leaving the building.  
In order to provide easy access, call points should be mounted  
between 1.2 and 1.6m from the floor, and should be clearly  
visible and identifiable. The maximum distance anyone  
should have to travel in order to activate a manual call point  
is 45m, unless the building is occupied by people having  
limited mobility, or a rapid fire development is likely, in which  
case the maximum travel distance should be reduced to 20m.  
Call points should also be sited in close proximity to specific  
hazards, for example kitchens or paint spray booths.  
Pantry  
Kitchen  
Canteen  
MAX DISTANCE 45M  
1.2 to 1.6m  
Office  
Office  
Figure 2.2.1. Manual Call Point Positioning  
ent is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire detection systems.  
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
heat sensors, which can give a response to fast flaming  
fires similar to that of ionisation detectors. Other sensor  
combinations are also available.  
2.3. SELECTION OF AUTOMATIC FIRE DETECTORS  
Smoke detectors are the most sensitive automatic means of  
detecting a fire and should be used wherever conditions allow.  
Multi-Criteria  
Alarm  
2.3.1. Ionisation smoke detectors  
Optical  
Alarm  
Ionisation smoke detectors use a weak radioactive source to  
ionise the air between two electrodes, creating positive and  
negative ions and so allowing a small current to flow across  
the chamber. Smoke particles attract these ionised particles,  
and allow positive and negative ions to recombine, thus  
reducing the number of ions and hence the current flow.  
Chamber  
Response  
Alarm  
Threshold  
Environmental regulations concerning the radioactive source  
used in ion detectors means that they are now becoming  
obsolete, and most major manufacturers are no longer  
including ionisation detectors in new ranges.  
Heat  
Response  
Time  
2.3.2.  
Photoelectric smoke detectors  
Figure 2.3.2. Photo-Thermal Detector Response  
Photoelectric or optical smoke detectors work by generating  
pulses of infra red light and measuring any diffracted light.  
If smoke is present in the sensing chamber, the light is  
diffracted by the smoke particles onto a photodiode, which  
senses the presence of the smoke (see figure 2.3.1). They  
are now largely replacing ionisation detectors as a general  
purpose detector.  
2.3.4.  
CO Detectors  
A recent addition to BS5839 is CO detectors. These generally  
use an electro-chemical sensor to detect carbon monoxide  
given off by incomplete combustion. They provide reliable  
detection of incipient fires whilst giving good assurance  
against nuisance alarms. However the chemical cells used  
in these detectors have a limited life span, and they cannot  
detect fast burning fires due to the low CO levels produced.  
2.3.5.  
Heat Detectors  
Heat detectors are normally used in environments where a  
smoke detector might generate false alarms, for example  
kitchens or shower rooms.  
Rate of Rise heat detectors will alarm if the temperature  
rises very quickly, or if the temperature reaches a set  
threshold. This type of detector would be the first choice in an  
environment where a smoke detector could not be used.  
Without Smoke: Chamber is designed so  
that light from the IR-LED does not reach  
the receiver  
In some environments, such as boiler rooms, fast rates of  
rise of temperature can be expected normally, meaning that  
there would be a risk of false alarms when using a rate-of-rise  
device. In this case a fixed temperature detector would be  
suitable. As their name implies, fixed temperature detectors  
give an alarm once the temperature has reached a preset  
threshold, most commonly 58°C or 78°C for EN54-5 Class AS  
or BS respectively.  
Smoke Present : Light from the IR-LED is  
reflected off the smoke particles onto the  
receiver, triggering an alarm signal.  
2.3.6.  
Optical Beam Detectors  
Optical beam detectors work on the principle of projecting a  
beam of light across a room, which is attenuated when smoke  
is present thus allowing an alarm to be given (Figure 2.3.3).  
There are two forms of beam detector: emitter and receiver  
separate (single path), requiring separate wiring both to the  
emitter and receiver, and reflective in which the emitter and  
receiver are mounted in the same box, and the beam is shone  
onto a reflective material at the far side of the room (dual  
path).  
Figure 2.3.1. - Operation of Optical Chamber  
Photoelectric smoke detectors are tested across the complete  
range of EN54 fires, however they are most sensitive to smoke  
containing large particles from around 0.4 to 10 microns,  
such as that given off by smouldering fires. A photoelectric  
detector would therefore be a good choice in an environment  
where a slow burning fire could be expected, such as a room  
containing modern fabrics and furnishings.  
2.3.3.  
Multi-criteria Detectors  
Since an optical beam detector senses smoke across the  
entire smoke plume, it tends to be less affected by smoke  
dilution as the ceiling height increases than point type smoke  
detectors. In addition, a single beam detector can protect a  
large area; hence they are particularly suitable for protecting  
large high rooms such as sports arenas, warehouses and  
shopping malls.  
Multi-criteria detectors comprise two or more sensors within  
the same housing, integrated by the detector electronics or  
software to give a rapid response to a broader range of fires  
and greater immunity to nuisance alarms. The most common  
type at present is a combination of optical and rate of rise  
Note: This document is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire d
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Up to 100M  
Beam  
attenuated by  
smoke plume  
Reflector  
Combined  
Emitter /  
Receiver Unit  
Figure 2.3.3. Operation of Reflective Type Optical Beam  
Smoke Detector  
Beam detectors are more complex to install than ordinary  
point smoke detectors and it is advisable to consult an  
application guide for the use of projected beam smoke  
detectors before considering the use of these detectors.  
Detector type  
Application  
General purpose smoke detector – better Areas subject to smoke, steam, dust or  
for fast flaming fires dirt during normal use  
General purpose smoke detector – better Areas subject to smoke, steam, dust or  
Not suitable for  
Ionisation smoke detector  
Optical smoke detector  
for smouldering fires  
dirt during normal use  
Photo-thermal multi-criteria detector  
Optical beam smoke detector  
Rate of rise heat detector  
General purpose detector – good for  
smouldering and fast flaming fires  
Areas subject to smoke, steam, dust or  
dirt during normal use  
Large and high rooms  
Areas subject to smoke, steam, dust or  
dirt during normal use  
Areas subject to smoke, steam, dust or  
dirt during normal use  
Areas subject to rapid changes of  
temperature or temperatures over 43°C  
Fixed temperature detector (58°C)  
Areas subject to smoke, steam, dust or  
dirt and rapid changes of temperature  
during normal use  
Areas subject to temperatures over 43°C  
High temperature fixed detector (78°C)  
Areas subject to smoke, steam, dust or  
dirt and temperatures over 43°C during  
normal use  
Areas subject to temperatures over 65°C  
Figure 2.3.1. Selection of Fire Detectors  
ent is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire detection systems.  
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.4. LOCATION AND SPACING OF AUTOMATIC FIRE  
DETECTORS  
2.4.2.  
Ceiling Height  
Smoke or heat detectors can only detect fires once a certain  
amount of smoke or heat has reached the sensor. As the  
height of a ceiling increases, the time taken for smoke or heat  
to reach a sensor will increase, and it will become diluted  
with clean, cool air. As a result, maximum ceiling heights are  
limited as indicated in table 2.4.1 below.  
It is important to consult applicable local and national  
standards when choosing the spacing and location of fire  
detectors. The following information is intended only as  
a guide to the location and spacing of detectors. There is  
currently no European standard available; hence this guide is  
based on BS5839 part 1, 2002.  
Detector type  
Maximum ceiling height  
10.5m  
2.4.1.  
Location and Spacing of Point Fire Detectors on  
Point smoke detector conforming  
to EN54–7  
Flat Ceilings  
On a flat ceiling with no obstructions, the radius of protection  
of fire detectors is 7.5m for a smoke detector and 5.3m for a  
heat detector, and detectors should be mounted a minimum  
of 0.5m from a wall. Some analogue multi-criteria detectors  
have a heat sensor only function, switched by the control  
panel, typically used to reduce the possibility of false alarms  
during daytime when a building is occupied, reverting to multi-  
sensor operation at night time. If this type of operation is  
employed, the radius of protection for a heat sensor should be  
used. Figure 2.4.1 gives a simple spacing plan based on these  
figures, however it should be noted that this might not be the  
most efficient layout for a given site; for example in larger  
areas, it is also possible to use a staggered layout, see figure  
2.4.2, which may reduce the number of detectors required. In  
practice, the layout of the room must be considered to obtain  
the most efficient detector layout.  
Heat detector conforming to  
EN54–5 Class A1 (threshold 58°C) 9m  
High temperature heat detector  
conforming to EN54–5 Class B  
(threshold 78°C)  
6m  
Optical beam detectors  
25m  
Table 2.4.1: Maximum ceiling height for different types of  
detector  
Often, a boundary layer can form close to the ceiling, which is  
free of smoke and remains cool. To avoid this, and maximise  
the probability of detection, smoke detectors should normally  
be mounted with their smoke entry 25mm-600mm below the  
ceiling, and heat detectors should be mounted with their heat  
element 25mm-150mm below the ceiling. Detector design  
normally ensures that the minimum requirement is met,  
but care needs to be taken if the detectors are to be stood  
away from the roof, for example mounting on an open lattice  
suspended ceiling.  
5.3m  
7.5m  
Another problem that should be considered is the possibility  
of stratification of the air in a room into hot and cold layers,  
causing the smoke or heat to stop at the boundaries. This  
particularly affects high rooms or atria, where beam detectors  
are often used. Stratification is very difficult to predict,  
and can vary, even within the same room as environmental  
conditions change.  
3.7m  
7.5m  
10.5m  
5.3m  
Standard Heat Detector  
Spacing  
Standard Smoke Detector Spacing  
Figure 2.4.1: Simple spacing plans for smoke and heat  
detectors  
2.4.3.  
Ceiling Obstructions  
Ceiling obstructions such as beams greater than 10% of the  
ceiling height should be treated as a wall, and will thus divide  
a room. Detectors should not be mounted within 500mm of  
such an obstruction.  
13m  
If the depth an obstruction such as a beam is less than 10% of  
the height of the ceiling, but greater than 250mm deep, then  
detectors should not be mounted any closer than 500mm to  
the obstruction.  
Where an obstruction such as a beam or a light fitting is less  
than 250mm in depth, detectors should not be mounted any  
closer to the obstruction than twice its depth (see figure 2.4.3  
below)  
60 °  
60 °  
Where a ceiling comprises a series of small cells, for example  
a honeycomb ceiling, or a series of closely spaced beams, for  
example floor of ceiling joists, the recommended spacing and  
siting of detectors changes further, dependant on the ceiling  
height and the depth and spacing of the beams. Reference  
should be made to relevant standards for details (in the UK  
BS5839 Part 1: 2002, 22.3.k Tables 1 and 2).  
Figure 2.4.2: Alternate smoke detector spacing plan for  
protecting large areas  
Note: This document is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire d
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
however along the roof apex spacing the lesser of the two  
figures should be used, in this example 10.5m +18%. Where  
the slope finishes within the adjusted detection radius, the  
standard distance to the next row of detectors, 10.5m, should  
be used. Care must be taken when placing the next row that  
no gaps are left in detection coverage.  
>10% of Ceiling Height  
Treat as separate room  
Minimum  
500mm  
>250mm  
<10% of Ceiling Height  
Max 600mm  
Minimum  
500mm  
15m  
40°  
18°  
Normal Detector Spacing, eg. 10.5m max  
for “simple” layout.  
9.35m  
Height < 250mm  
= 7.5 + 25%  
7.5m  
Minimum 2 x  
height  
Normal Detector Spacing, eg. 10.5m max  
for “simple” layout.  
Figure 2.4.3: Detector Spacing around isolated ceiling  
obstructions  
2.4.4.  
Partitions and Racking  
Where the gap between the top of a partition or section of  
racking and the ceiling is greater than 300mm, it may be  
ignored. If the gap is less than 300mm it should be treated as  
a wall.  
8.85m  
=7.5 + 18%  
To maintain a free flow of smoke and heat to the detector, a  
clear space should be maintained for 500mm in all directions  
below the detector.  
Figure 2.4.5. Spacing of Smoke Detectors under a  
Pitched Roof  
2.4.6.  
Corridors  
In corridors less than 2m wide, detectors should be spaced  
at a distance of 15m for smoke detectors and 10.6m for heat  
detectors, with the maximum dimension to a wall at the end of  
the corridor being 7.5m and 5.3m respectively.  
>300mm : No effect  
<300mm :Treat as wall  
Minimum  
500mm  
Clear  
In narrow rooms and corridors greater than 2m wide, due to  
the way that the coverage radii of detectors intersect with  
the walls of the corridor, the spacing between detectors  
will increase. Figure 2.4.6 shows how, for a room 6m wide,  
the spacing for smoke detectors can be increased from the  
standard 10.5m.  
Racking /  
Shelving  
Figure 2.4.4. Partitions  
6.88m  
13.75m  
2.4.5.  
Sloping Ceilings  
Where the ceiling is pitched or sloping, the slope of the  
roof tends to speed the rise of smoke or heat to the apex,  
hence reducing the delay before the detectors are triggered.  
For sloped roofs with a pitch height greater than 600mm  
for smoke detectors, or 150mm for heat detectors, a row  
of detectors should be placed within a maximum vertical  
distance of 600mm or 150mm for smoke or heat detectors  
respectively from the roof apex. Sloped roofs rising less than  
600mm for smoke detectors or 150mm for heat detectors may  
be treated as a flat ceiling.  
7.5m  
Note: Detectors are mounted in the centre line of the room  
Figure 2.4.6. Smoke detector spacing in corridors greater  
than 2m wide  
Since the smoke or heat tends to rise faster up the slope, it is  
permissible to use a greater spacing for the row of detectors  
mounted in the apex of the roof: For each degree of slope  
of the roof, the spacing may be increased by 1% up to a  
maximum of 25%. Where, as in figure 2.4.5, the roof slopes  
are unequal the spacing down the slopes can be unequal,  
ent is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire detection systems.  
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Where they are installed into voids, a detector's sensing  
element should be mounted either in the top 10% or the top  
125mm of the void space whichever is greater. Although it  
can be difficult to install detectors the correct way up in void  
spaces, care should be taken as incorrect orientation of a  
detector can lead to increased ingress of dirt and dust, leading  
to reduced maintenance intervals, and possible nuisance  
alarms.  
2.4.7. Stairwells and Lift Shafts  
Internal stairwells and lift shafts and other vertical service  
ducts through a building provide a clear path for smoke to  
pass between floors of a building as if they were chimneys.  
It is therefore important to protect these, preferably using  
smoke detectors.  
All vertical shafts through a building must be protected by  
a smoke or heat detector at the top of the shaft, and by a  
detector within 1.5m of each opening onto the shaft.  
Detectors above a false ceiling may be used to protect the  
area below it, if the false ceiling is perforated uniformly across  
the complete area of the ceiling, with the holes making up  
over 40% of the ceiling surface area, having a minimum size  
of 10mm and the false ceiling having a thickness of less than  
three times the dimensions of the perforations.  
In internal stairways, a detector should be mounted on each  
main landing (Figure 2.4.7). In addition, if the detectors on  
the landings are separated by more than 10.5m, intermediate  
detectors should be mounted on the underside of the stairs.  
Detectors should also be fitted into any room opening directly  
onto a stairway other than a WC cubicle.  
In all other cases, the areas above and below a false ceiling  
should be treated as separate, and thus should be protected  
separately with detectors below the ceiling, and if necessary  
in the void above the ceiling.  
2.4.9.  
Lantern Lights  
A detector should be mounted in any lantern light used  
for ventilation or having a height exceeding 800mm. The  
temperature in lantern lights can change rapidly owing to  
heating by sunlight, which means that rate-of-rise heat  
detectors should not be used and heat detectors should be  
protected from direct sunlight.  
2.4.10. Location and Spacing of Optical Beam Detectors  
Generally, for an optical beam detector mounted within  
600mm of a ceiling, the fire detection coverage is up to 7.5m  
either side of the beam (Figure 2.4.9). The beam of the  
detector should not be closer than 500mm to any obstruction.  
Similar recommendations to above apply to the application  
of beam detectors with sloped ceilings, voids, false ceilings,  
walls and partitions and ceiling obstructions.  
Figure 2.4.7. Detector in Stairwells  
Maximum 100m  
Maximum  
7.5m  
Minimum  
500mm  
Transmitter or  
Transmitter/Receiver  
Receiver or  
Reflector  
1.5M  
Maximum  
15m  
1.5M  
Transmitter or  
Transmitter/Receiver  
Receiver or  
Reflector  
Figure 2.4.9: Standard Beam Detector Layout  
Where it is likely that people will be present in an area  
protected by beam detectors, the detectors must be mounted  
at a minimum height of 2.7m, and consideration must also be  
given to the possibility of other temporary obstructions to the  
beam such as forklift trucks.  
Figure 2.4.8. Protection of Vertical Shafts  
2.4.8.  
Voids and False Ceilings  
For further information on the use and mounting of beam  
detectors, see System Sensor Europe's Guide to Projected  
Beam Detectors.  
Detectors need not normally be installed in voids less than  
800mm deep, unless on the basis of a fire risk assessment it  
is thought that fire or smoke could spread extensively through  
the voids before detection, or unless the fire risk in the void  
is such as to warrant protection. Use of heat and smoke  
detectors in voids greater than 800mm high is dependant on  
the protection category, and fire risk assessment.  
Note: This document is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire d
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Where it is not possible to place a sounder within a room,  
there will be a loss of approximately 20dB(A) through a  
standard door, and 30dB(A) through a fire door.  
2.5. ALARM SIGNALS  
2.5.1.  
Audible Alarm Signals  
Audible fire alarm signals must provide a clear warning of a  
fire to all those for whom the signal is intended. For category  
M and L systems this would normally imply all occupants  
of a building, however in some sites this may not apply, for  
example in hospitals or rest homes, residents might need  
assistance to evacuate, in which case it may be sufficient to  
alert staff.  
Fire Door  
Reduces by  
30dB(A)  
Standard Door  
Reduces by  
20dB(A)  
Sounder  
Volume  
115dB(A)  
115 - 30 =  
85dB(A)  
85 - 20 =  
65dB(A)  
The general requirement for the volume of audible alarm  
signals is that they should provide a Sound Pressure Level  
(SPL) of at least 65dB(A), but not more than 120dB(A)  
throughout all accessible areas of a building. See figure 2.5.1.  
Warning: Volumes greater than 120dB(A) will cause  
damage to hearing.  
SOUND REDUCTION AGAINST DISTANCE  
Based on a sounder rated at 1m  
Minimum  
65dB(A)  
0
-5  
dB(A) Reduction  
Minimum  
65dB(A)  
Minimum  
65dB(A)  
-10  
-15  
-20  
-25  
-30  
Minimum  
65dB(A)  
Minimum  
65dB(A)  
Minimum  
65dB(A)  
0
5
10  
15  
20  
Distance (Metres)  
Stairwell  
Min 60dB(A)  
In open space, as the distance from a sounder doubles, the  
sound level will be reduced by 6dB(A), as shown.  
Figure 2.5.1. General Fire Alarm Sound Pressure Levels  
It is preferable to use multiple quieter sounders to achieve  
the required sound level, rather than a smaller number of  
loud devices. This is to prevent points of excessive volume,  
which may lead to disorientation or damage to hearing. Two  
sounders providing equal sound levels will combine to add  
3dB(A) to the SPL.  
Exceptions to this general rule are as follows:  
• In stairways the SPL may be reduced to 60dB(A)  
• Enclosures less than 60m² may be reduced to 60dB(A)  
• There is no minimum for enclosed areas less than 1m²  
At specific points of limited extent the SPL may be  
reduced to 60dB(A)  
2.5.2.  
Visual Alarm Signals  
25m  
Where a continuous background noise level greater than  
60dB(A) is present the fire alarm signal should be 5dB above  
the ambient, but not greater than 120dB(A).  
-16dB  
-23dB  
69dB(A)  
Sounder  
Minimum  
85dB(A)  
63 + 3  
= 66dB(A)  
85dB(A)  
0dB  
Machinery  
Generating  
80dB(A)  
62 + 3  
= 65dB(A)  
69dB(A)  
-16dB  
Note: dB(A) figures are for example only.  
Left side represents attenuation; right side  
indicates typical sound pressure level  
Where the alarm is intended to wake people, an SPL of  
75dB(A) is required at the bed head. Generally this will  
require a sounder to be placed within the room.  
Visual alarms are normally used only as a supplement to  
audible alarms where they are likely to be ineffective, for  
example in areas of high background noise levels where  
hearing protection is likely to be worn. They can however  
be used alone where audible warnings are undesirable for  
example operating theatres and recording studios.  
Volume at  
Bed Head  
75dB(A)  
Visual alarms should be clearly distinguishable from other  
warning lights, preferably red and should flash at a rate of 30  
to 130 flashes per minute. The recommended mounting height  
is above 2.1m, however they should not be mounted closer  
than 150mm from the ceiling. They should be positioned so  
that any alarm is clearly visible from all locations within the  
area protected.  
ent is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire detection systems.  
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.6 MAINTENANCE OF FIRE DETECTORS  
2.7 ROUTINE FUNCTIONAL TESTING OF FIRE DETECTORS  
Caution: Prior to carrying out any maintenance or testing  
on a fire alarm system, the relevant authorities and staff  
should be notified.  
BS5839 Part 1: 2002 gives a range of recommendations  
regarding routine testing of a fire detection system.  
A weekly test should be carried out on a fire detection system  
by activating a manual call point to ensure that all fire alarm  
signals operate correctly, and that the appropriate alarm  
signals are clearly received. This test should be carried out at  
approximately the same time each week, using a different call  
point in rotation.  
Over time, the sensitivity of a smoke detector can change  
owing to a build-up of dirt in the detector chamber. In most  
modern detectors this effect is slowed by the inclusion of drift  
compensation functions, however the build up can still lead to  
a risk of false alarms or change in the detector sensitivity.  
The frequency of maintenance requirements on a detector will In order to comply with BS5839 Part 1: 2002, periodic  
depend on site conditions, obviously the dirtier the site the  
more frequent maintenance will be required. The optimum  
frequency for a given site should be determined over a period  
of time after the commissioning of the fire system.  
inspections, servicing and functional tests of the fire alarm  
system should be carried out at intervals determined by  
an assessment of the site and type of system installed, not  
normally greater than six months.  
All System Sensor detectors (smoke, heat, or multi-criteria)  
are designed such that they can be easily dismantled for  
maintenance. Instructions are given for maintenance in the  
instruction manual supplied with each detector. Normally it  
is sufficient to use compressed air or a vacuum cleaner to  
remove dust from the detector chamber.  
It is recommended to perform regular functional tests on all  
fire detectors annually. These annual tests may be carried  
out over the course of two or more service visits during the  
twelve-month period.  
System Sensor detectors include various means of testing the  
system without using smoke, dependent on the detector range  
being tested, including magnet switches and laser test tools.  
Once maintenance on a fire detection system has been  
completed, it should be re-tested.  
Codes and standards (in the UK BS5839 Part 1:2002, Section  
6) now require functional tests to introduce smoke through  
the smoke detector vents and into the sensing chamber. It also  
calls for heat detectors to be tested by means of a suitable  
heat source, and not by a live flame. CO fire detectors now  
also need to be functionally tested by a method that confirms  
that carbon monoxide can enter the chamber.  
Many installers use a set of equipment that consists of a  
complete range of test tools that locate on the end of the pole  
such as those available from No Climb Products Ltd. (www.  
noclimb.com) in order to aid compliance with codes. Tools  
exist for testing smoke, heat, and CO fire detectors, whilst  
also enabling them to be accessed and removed at heights up  
to 9 meters from the ground.  
Using functional test equipment, along with those  
maintenance tools available from System Sensor, should  
ensure that the system remains at its optimum operation for  
many years.  
Note: This document is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire d
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERIES 200 PLUS ANALOGUE ADDRESSABLE DETECTOR RANGE  
INTRODUCTION  
System Sensor’s Series 200 plus range of plug in smoke detectors are a family of analogue addressable smoke detectors  
combining state of the art design with micro-processor control and sophisticated processing circuitry to provide fast, efficient  
fire detection in a wide range of applications.  
All Series 200 plus detectors have two integral LEDs, which provide local visual indication of the sensor status. These LEDs  
provide a dual function. In the event of an alarm, they are switched ON continuously, and can also be programmed to either  
blink when polled by the panel or remain off during normal conditions. In addition to their integral LEDs, Series 200 plus  
detectors can be connected to a remote LED indicator.  
The individual loop address of each Series 200 plus detector can be easily set and read, using the rotary decade address  
switches located on the rear of each sensor. The use of decimal address codes significantly reduces the potential for incorrect  
address selection.  
Each sensor base includes a tamper resistant option which, when activated, prevents the removal of the sensor from its base  
without the use of a tool.  
Full circuit functionality can be easily confirmed on site by use of the sensor test switch. This comprises a switch operated by  
a magnet near the side of the detector. Operation of this magnetic switch simulates the effect of smoke or heat on the detector,  
and will generate an alarm response to the fire alarm control panel, making system testing both convenient and simple.  
SERIES 200 PLUS FEATURES  
GENERAL SPECIFICATIONS  
Electrical  
Microprocessor precision control  
Automatic drift compensation.  
Enhanced signal processing for improved stability.  
Extended Temperature Range  
Voltage Range:  
Standby Current:  
Alarm Current:  
15 to 32VDC  
200µA at 24VDC (No communications)  
7mA at 24VDC  
Twin LED indicators providing 360° visibility  
Rotary Decade Address Switches  
Stable communication with high noise immunity  
Tamper-Resistant (standard feature)  
Built in test switch  
Environmental  
Temperature Range:  
Humidity:  
-20°C to 60°C  
10% to 93% Relative Humidity  
(Non-condensing)  
Mechanical:  
Diameter:  
Maximum Wire Gauge: 2.5mm²  
102mm  
Third party certified to the latest EN54 standards with  
multiple alarm thresholds  
Colour:  
Material:  
Pantone Warm Grey 1C  
Bayblend FR110  
ent is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire detection systems.  
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2251EM PHOTOELECTRIC SMOKE SENSOR  
The 2251EM photoelectric smoke detector combines a state  
of the art sensing chamber with microprocessor control  
and sophisticated processing to eliminate transient noise  
conditions thereby giving reliable fire detection whilst  
minimising unwanted alarms. It is approved to a range of  
sensitivities, permitting the detector to be configured to match  
he application environment.  
The 2251EM includes algorithms, which compensate for  
a slow build up of contamination such as dust, within  
he sensing chamber. Once the detector has reached its  
maximum compensation level, a signal can be sent to the  
control panel to indicate the need for maintenance.  
Tested and approved to EN54-7: 2000 by LPCB  
Specifications  
Height:  
Weight:  
45mm in B501 Base  
102g excluding base  
2251TEM PHOTO–THERMAL SENSOR  
The 2251TEM multi-criteria fire sensor incorporates an optical  
smoke-sensing chamber and thermal-sensing elements  
combined with microprocessor control and sophisticated  
processing to eliminate transient noise conditions thereby  
giving reliable fire detection whilst minimising unwanted  
alarms. It can respond either as a smoke detector, or a rate of  
ise heat detector or, using special algorithms combining both  
elements to provide improved reliability of detection.  
The 2251TEM is an environmentally friendly replacement  
or an ionisation detector, providing rapid detection of  
fast, flaming fires without incurring the significant end-  
of-life disposal costs associated with products containing  
radioactive material.  
The 2251TEM is approved to a number of sensitivity settings:  
Three Photo-Thermal and two Auto-Adjusting, which slowly  
adjust the detector’s sensitivity to match short term changes  
in its environment, thus reducing the potential for nuisance  
alarms. In addition, it is possible to detect an alarm from heat  
only, for day/night operation for example.  
Similarly to the 2251EM, the 2251TEM includes algorithms,  
which compensate for a slow build up of contamination,  
such as dust, within its optical sensing chamber. Once the  
detector has reached its maximum compensation level, a  
signal can be sent to the control panel to indicate a the need  
for maintenance.  
Tested and approved to CEA 4021, EN54-7: 2000 and EN54-5:  
2000 (Class A1R) by LPCB  
Specifications  
Height:  
Weight:  
45mm in B501 Base  
115g excluding base  
Note: This document is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire d
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DRIFT COMPENSATION AND SMOOTHING  
Effects of Drift Compensation  
Drift Compensation and Smoothing eliminate nuisance  
alarms and provide a consistent progressive alarm sensitivity  
threshold throughout the period between service intervals.  
Adjusted thresholds  
Maintenance levels  
In many instances this will result in an improved economic  
performance through savings in the cost of maintenance by  
extending the detector cleaning interval.  
Analogue sensor value  
Low fault threshold  
Intelligent sensors incorporate enhanced digital signal  
processing, eliminating spurious peaks.  
Time: years  
Processed versus Unprocessed Signals  
Processed  
Unprocessed  
Time: hours  
5251REM, 5251EM AND 5251HTEM HEAT SENSORS  
The 5251 range of static element and “rate of rise”  
temperature sensors provide solutions for a wide range of  
applications.  
The 5251EM and 5251HTEM are fixed temperature analogue  
addressable sensors employing low mass thermistors and  
microprocessor technology for fast response and linear  
temperature sensing. Their linear response allows these  
sensors to be used to signal temperatures over the range of  
58°C (Class A1S) to 78°C (Class BS).  
The 5251REM uses the same thermistor and microprocessor  
technology to provide an alarm when the rate of rise  
in temperature exceeds 10°C/minute (typical) or if the  
temperature exceeds a threshold of 58°C (Response Class  
A1R).  
5251REM is approved to EN54-5: 2000 Class A1R  
5251EM is approved to EN54-5: 2000 Class A1S  
5251HTEM is approved to EN54-5: 2000 Class BS  
Specifications  
Height:  
Weight:  
51mm in B501 Base  
102g excluding base  
ent is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire detection systems.  
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6500 AND 6500S BEAM DETECTOR  
The 6500S and 6500 are addressable reflector- type linear  
optical beam smoke detectors that can be directly connected  
o an analogue loop circuit as a component of an intelligent  
fire alarm system. The detectors have a range of 5m to 70m,  
extending to 100m with a long-range reflector kit.  
The 6500S and 6500 detectors are combined transmitter/  
eceiver units. The Infrared transmitter generates a beam of  
ight towards a high efficiency reflector. The reflector returns  
he beam to the receiver where an analysis of the received  
signal is made. The change in the strength of the received  
signal is used to determine the alarm condition.  
The 6500S features a unique remote test capability that fully  
tests both the optics and the electronics of the device. An  
optical filter is automatically introduced in front of the optics,  
attenuating the returned beam and causing the unit to go into  
alarm.  
Both versions incorporate automatic drift compensation,  
whereby the detector will adjust its detection thresholds in  
line with any long-term signal reduction of the beam caused  
by contamination of the optical surface.  
The 6500 and 6500S also include built in short circuit isolators  
(which may be wired out if required), reducing the number of  
isolators required in the detection circuit.  
Tested and approved to EN54-12: 2002  
Specifications  
Voltage Range:  
15 to 32VDC,  
or 15 to 28.5VDC if isolators used.  
2mA at 24VDC (no communications)  
8mA  
Standby Current:  
Max Alarm Current:  
Temperature Range: -30°C to 55°C  
Humidity:  
IP Rating:  
0 to 95% RH (Non-Condensing)  
IP54  
Detector Dimensions: 254mm x 190mm x 84mm (h x w x d)  
Reflector Dimensions: 200mm x 230mm (for 5-70m)  
Weight:  
1770g  
REMOTE TEST SWITCH  
In the conventional version of the beam detector, an  
optical filter is activated from ground level by a hard-wired  
connection; in the addressable model it is initiated by a  
command from the fire control panel to the servo motor.  
The filter attenuates the beam, causing the unit to go into  
alarm. This test process provides a complete check of every  
component in the alarm path without the need for access at  
high level.  
Note: This document is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire d
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7251 LASER DETECTOR  
The Pinnacle high sensitivity laser based intelligent smoke  
sensor is a unique offering from System Sensor that provides  
extremely high sensitivity to fire conditions, by detecting the  
earliest particles of combustion. This is achieved by combining  
a patented optical chamber with the latest in laser diode and  
precision optics technology, which enhances the sensitivity  
of the device. The chamber is also linked to sophisticated  
processing circuitry that incorporates smoothing filters to help  
eliminate transient environmental noise conditions, which  
can be the cause of unwanted alarms. The result is a very  
sensitive but stable sensor that can achieve sensitivities of  
0.006% to 0.6% per metre obscuration and provides up to 100  
times more sensitivity than a standard photoelectric smoke  
sensor. With its quick response and pinpoint accuracy, this  
unique sensor is ideally suited to environmental applications  
where there is substantial cost for downtime or a significant  
investment in installed equipment has been made (e.g.  
Electronics Manufacturer Clean Rooms, Telecommunication  
Rooms, Computer Rooms etc.).  
The sensor’s performance is improved even further by the  
inclusion of special drift compensation algorithms, which  
compensate for the build up of contamination in the sensing  
chamber. There are three stages of drift compensation, ‘low  
level alert’, ‘high level alert’ and ‘maintenance urgent’. The  
‘low and high level alert’ signals are used to identify that  
the Pinnacle sensor has accumulated significant amounts  
of airborne particles and requires maintenance, whilst the  
‘maintenance urgent’ signal indicates that the sensor has  
reached the end of its compensation range.  
Tested and approved to EN54-7: 2000  
Specifications  
Operating Voltage:  
15 to 32VDC  
Max Standby Current: 230µA at 24VDC (No communications)  
Operating Temperature:-10°C to 55°C  
Weight:  
142g  
ent is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire detection systems.  
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2251EIS INTRINSICALLY SAFE DETECTOR AND IST200  
INTERFACE  
The 2251EIS analogue addressable photoelectric sensor is a  
plug in Intrinsically Safe smoke sensor combining an optical  
sensing chamber with analogue addressable communications.  
As an Intrinsically Safe sensor, the 2251EIS has been designed  
specifically to provide fire protection for most hazardous  
environments, and has therefore been engineered so that it  
cannot become a source of ignition in areas where potentially  
explosive atmospheres are likely to arise.  
The IST200 translator module serves as an interface between  
the control panel and up to a maximum of 15 x 2251EIS smoke  
sensors. The IST200 must be used in conjunction with a  
Y72221 custom galvanic isolator barrier.  
Tested and approved to EN54-7 and by BASEEFA (2001) to  
EEx ia IIB T5 for use in Zone 0 hazardous areas.  
Specifications  
Note that there are limitations of capacitance, inductance and  
nductance/resistance ratio connected within the hazardous  
area. Reference must therefore be made to product data  
before installation of these devices.  
Voltage:  
Max. standby current: 330µA  
(One communication every 5s  
17 to 24VDC  
with LED blink enabled)  
4.2mA at 24VDC  
102g  
Max. alarm current:  
Weight:  
ST200  
nput Voltage:  
Output Voltage:  
Supply Current:  
Dimensions:  
Weight:  
15 to 32VDC  
20 to 24VDC  
14mA at 24VDC  
70mm x 70mm x 32mm (h x w x d)  
142g  
Note: This document is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire d
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B500 SERIES BASES  
A range of detector bases and accessories are available  
for use with Series 200 plus plug in detectors to suit the  
requirements of varying applications. All bases are 102mm in  
diameter.  
B501 Standard Base:  
For normal applications.  
Height:  
Weight:  
20mm  
53g  
B501DG Deep Base:  
For use when cabling in surface mounted conduit.  
Height:  
Weight:  
26mm  
57g  
B524HTR Heater Base:  
Includes an anti-condensation heater for use in cold  
applications where condensation may be expected. The  
B524HTR uses heater resistors to provide an element of  
heating to reduce condensation.  
Height:  
36mm  
Weight:  
92g  
Power supply:  
Temperature:  
Up to 125mA; up to 32VDC  
-30°C to 60°C  
B524RTE Relay Base:  
Relay base which follows alarm status of detector, used to  
control external devices such as fire shutters.  
Height:  
36mm  
Weight:  
100g  
Contact Rating:  
Temperature:  
2A at 30VDC no/nc  
-10°C to 60°C  
B524IEFT-1 ISOLATOR BASE  
The B524IEFT-1 isolator base monitors the loop on either  
side of the base, and if it detects a short circuit, it isolates  
that side. As a result, when used in conjunction with other  
isolator bases or modules, short circuits can be isolated  
from the remainder of the loop, thus minimising the effect of  
the fault. Once the short circuit is removed, the isolator will  
automatically restore the loop.  
Height:  
26mm  
Operating Temperature:-30°C to 70°C  
Standby Current:  
100µA  
Max ON resistance:  
0.2 Ohms at 24V  
ent is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire detection systems.  
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WB1 Wet Base:  
For use in conjunction with the B501, increases the IP rating  
of the detector from IP40 to IP42, providing protection from  
water dripping from above.  
Diameter:  
Height:  
Weight:  
110mm  
69mm  
102g  
RMK400 Recess Mounting Kit:  
Used to recess Series 200 plus detectors into suspended  
ceilings, reducing the detector height by approximately 20mm.  
nterior diameter:  
Exterior diameter:  
Depth:  
102mm  
144mm  
31mm  
100g  
Weight:  
Note: This document is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire d
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
M200 SERIES MODULE RANGE  
INTRODUCTION  
The family of input/output modules form part of System Sensor Europe’s Series 200 plus family. Single and multi-way models  
are available within the same mechanical package, reducing both the cost of installation and the mounting space required.  
Their unique mechanical design allows each module to be mounted in either a wall box, on a DIN rail or within any type of  
enclosure. Irrespective of the mounting method chosen, the address switches and indicator LED’s are visible and accessible.  
To help engineers in the maintenance and fault-finding process, the LEDs, are multi-colour, providing diagnostic information  
regarding the status of each individual input/output.  
Each module has built-in short circuit protection for the communications loop; however, to increase application flexibility, the  
isolators can be selected/deselected on an individual module basis.  
For ease of installation, testing and maintenance, the field wiring terminals are of plug-in design.  
Specifications  
Operating Voltage:  
15 to 30VDC  
Operating Temperature:-20C to 60°C  
Humidity Range:  
Dimensions:  
0 to 95% Relative Humidity  
23mm x 93mm x 94mm (h x w x d)  
(including terminal block)  
Maximum Wire Gauge: 2.5mm²  
M200-SMB Surface Mount Box  
Dimensions:  
134mm x 139mm x 40mm (h x w x d)  
M200XE SHORT CIRCUIT ISOLATOR MODULE  
The M200XE Isolator Module monitors the loop on either side  
of the module, and if it detects a short circuit will isolate  
that side. As a result, when used in conjunction with other  
isolator bases or modules, short circuits can be isolated  
from the remainder of the loop, thus minimising the effect of  
the fault. Once the short circuit is removed, the isolator will  
automatically restore the loop.  
Specifications  
Max standby current: 200µA at 24VDC  
Max ON resistance:  
0.13 Ohms at 15V  
M210E SINGLE CHANNEL INPUT MODULE, M220E DUAL  
CHANNEL INPUT MODULE AND M221E DUAL CHANNEL  
INPUT, SINGLE CHANNEL OUTPUT MODULE  
The M210E and M220E provide supervision of one or two  
input circuits from external devices; the M221E also provides  
an un-monitored single pole volt-free changeover contact  
for external devices. Input channels are capable of both  
latched and analogue supervision: There are three separate  
latched states, normal, open circuit and combined alarm/  
short. The analogue supervision continuously monitors the  
supervised circuit, returning a signal proportional to the circuit  
resistance.  
Specifications  
M210E  
Max Standby current 310µA at 24VDC (No communications)  
M220E  
Max Standby Current: 340µA at 24VDC (No communications)  
M221E  
Max Standby Current: 340µA at 24VDC (No communications)  
Output Relay Rating: 2A at 30VDC, resistive load.  
ent is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire detection systems.  
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
M201E OUTPUT MODULE  
The M201E optionally supervises the wiring to the load  
devices and, upon command from the control panel, switches  
an external power supply to operate these devices. It also has  
built-in short circuit isolation capability. In normal supervised  
mode, the device switches out the load supervision and  
switches in the external power supply through a double pole  
elay. The external power supply is monitored and raises an  
unlatched fault condition if the voltage falls below the fixed  
hreshold. In the unsupervised mode, the device provides  
neither load nor power supply supervision and can be used to  
switch a single form C set of changeover contacts.  
ld selectable DIL switch allows the module to be used  
lly meet the VdS 2489 requirements (subject to panel  
port). Note: selecting this option imposes an additional  
riction on the load that can be switched.  
cifications  
Standby Current: 310µA at 24VDC (No communications)  
y Contact Ratings: Unsupervised form C: 2A at 30VDC  
Supervised form C: 1.5A at 30VDC  
01E-240 AND M201E-240-DIN 240VAC RELAY MODULES  
M201E-240 is a loop-powered device controlling an  
supervised double pole (one normally open, one normally  
sed) output suitable for managing 240VAC loads. The  
tput relay is a bi-stable device, latching in the on or off state  
command from the control panel. The module is supplied  
a wall-mounting box as standard with a grounding terminal  
ovided.  
The M201E-240-DIN has the same features and capabilities  
as the M201E-240 but is designed to mount directly on to a  
standard 35mm ‘Top Hat’ DIN rail. The module is supplied  
unboxed for installation in a suitable enclosure.  
Specifications  
Max Standby Current: 275µA at 24VDC (No communications)  
Relay Contact Ratings: 5A at 250VAC  
Temperature Range: -20C to 60°C  
Humidity Range:  
0 to 95% Relative Humidity  
M210E-CZ CONVENTIONAL ZONE MODULE  
The M210E-CZ provides an interface between a zone of  
conventional detectors and an intelligent signalling loop. The  
module monitors the convention zone and transmits the zone  
state (normal, open or short fault and alarm) to the panel.  
Specficaions  
urrent, externally powered zone:  
288µA at 24VDC (No communications)  
500µA at 24VDC  
(One communication every 5s)  
urrent, loop powered zone:  
1.5mA at 24VDC  
(One communication every 5s)  
vailable for Detectors:  
1.5mA additional to above  
Note: This document is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire d
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. CALL POINTS  
KAC’s range of Call Points comprise indoor, outdoor and  
special environment products suitable for all applications.  
They are available in a variety of colour and marking options  
for a wide range of applications, including red for use in fire  
systems.  
An extensive range of adaptor trays is available, allowing easy  
installation anywhere in the world.  
The majority of the KAC product range is certified to EN54 Part  
11, and other approvals are available.  
INDOOR  
KAC Indoor Call Points are available to satisfy all system types  
from conventional switch only manual systems, through to  
intelligent addressable systems.  
Products are surface mounted using the fixings in the rear  
enclosure. The back-box is supplied punched with centres to  
assist drilling of cable entries.  
Indoor products are generally rated at IP24D.  
OUTDOOR  
KAC Outdoor Call Points are available to satisfy all system  
types from conventional switch only manual systems, through  
to intelligent addressable systems.  
Products are surface mounted using the fixings in the rear  
enclosure. The back-box is supplied punched with centres to  
assist drilling of cable entries.  
Outdoor products are generally rated at IP55.  
WATERPROOF  
KAC Waterproof Call Points are available to satisfy all system  
types from conventional switch only manual systems, through  
to intelligent addressable systems. Waterproof products are  
rated at IP67.  
Waterproof products for Marine Applications are certified with  
Lloyds Register.  
Products of this type are available which are certified for use  
in Hazardous Areas.  
SWITCHES  
KAC Call Point Switching Devices provide alternative methods  
of manual activation of systems, rather than the traditional  
break glass principle. There are both indoor and outdoor  
models available in the familiar KAC housings.  
A variety of different colours and switch types can be chosen,  
key-switches and push buttons being the most popular. There  
is also a large choice of text markings to identify the purpose  
of the device.  
ACCESSORIES  
An extensive range of accessories supports KAC calls points,  
including a number of mounting accessories, allowing easy  
installation throughout the world.  
More information about call points and their accessories is  
available on the KAC website.  
ent is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire detection systems.  
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
majority of back box formats.  
6. AUDIO VISUAL PRODUCTS  
A deeper profile base with knockouts and marked drilling  
positions for rear and side entry allows for an IP55 rating,  
when used with appropriate glands.  
KAC Sounders and Strobes from simple tone set conventional  
products to fully featured fourteen-tone intelligent units, a  
range of sounders, strobes and combined sounder-strobe  
products suitable for all applications.  
The IP66 base has the same features as the IP55, but includes  
a sealing kit to increase the protection rating.  
The range meets the requirements of EN54 Part 3; key  
products are LPCB and VdS Approved. All are fully tested  
under simulated climatic conditions to ensure “real-world”  
conformance to the published specifications.  
SOUNDERS  
KAC Sounders are available in four or fourteen-tone versions.  
They operate at 9-33VDC, optimised for use at 12 and 24 volts.  
Four tone sounders have a high, medium and low volume  
selection, whilst the fourteen tone sounder has a volume  
control.  
The sounders have a distinctive, acoustically efficient low  
profile shape, producing high sound output at low current  
levels. The shape provides a wide-angle uniform sound  
distribution providing good audibility in all directions.  
The sounders are of rugged construction with solid-state  
electronics providing high reliability and stable performance.  
Three bases are available: low profile IP44, IP55 or IP66.  
DETECTOR BASE SOUNDERS  
KAC Detector Base Sounders are for use either underneath  
smoke detectors or fitted with a red or white lid as a low  
profile wall mounted sounder. They are available in four or  
fourteen tone versions. They operate at 9-33VDC (nominally  
12 and 24 volt). Four tone sounders have a high, medium and  
low volume selection, whilst the fourteen tone sounder has a  
volume control.  
The package is acoustically very efficient, producing omni-  
directional high sound output with low current levels. The  
detector base sounder can be used under any smoke detector  
with 60mm mounting centres and an external diameter of up  
to 102mm.  
STROBES  
The KAC Range of stand-alone Strobes is designed to provide  
visual signalling for use in a wide range of applications. There  
are both standard and high intensity output strobes available.  
A variety of different coloured strobe lenses are available.  
This variety of colours provides a range of products for  
different applications.  
SOUNDER STROBES  
The KAC Sounder Strobe combines a full feature fourteen-tone  
sounder with an integral strobe mounted on the horn. The  
design provides an efficient combination of audible and visual  
warning, in a package taking up no more surface area than a  
standard sounder.  
A variety of different coloured strobe lenses are available and  
the product housing is available in either red or white.  
BASES  
Three bases are available for KAC Sounders and Sounder  
Strobes. The standard base is an IP44 rated low profile unit.  
The base has rear and side cable access suitable for use with  
standard trunking and has mounting holes suitable for the  
Note: This document is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire d
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. OTHER INFORMATION  
7.1.  
STANDARDS  
To ensure that a fire alarm system provides adequate  
protection, it is advisable to ensure that it meets all  
relevant standards. The system should be designed in  
accordance with relevant national and local standards.  
Useful standards and references include:  
British Standard Code of Practice for fire detection  
systems BS 5839 part 1: 2002  
European Standard for Fire Detection and Alarm Systems:  
Control and Indicating Equipment  
BS EN54 part 2: 1998  
Sounders  
BS EN54 part 3: 2001  
Point Heat Detectors  
BS EN54 part 5: 2001  
Point Smoke Detectors  
BS EN54 part 7: 2001  
Manual Call Points  
BS EN54 part 11: 2001  
Optical Beam Detectors  
BS EN54 part 12: 2002  
These are all available from:  
British Standards Institution  
389 Chiswick High Road  
London  
W4 4AL  
ent is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire detection systems.  
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.2. APPROVAL BODIES FOR FIRE DETECTION  
PRODUCTS  
All components of the fire alarm system should be certified  
to a European standard by an independent certification  
body that specialise in the certification of fire and security  
systems. These include:  
BRE - LPCB  
Building 3,  
Bucknalls Lane,  
Garston,  
Watford,  
WD25 9XX,  
England  
Tel: (+44) (0) 1923 66400  
VdS  
Amsterdamerstrasse 174,  
50732 Köln,  
Germany  
Tel: +49 221 77 66 00  
ANPI  
Parc Scientific Fleming,  
1348 Louvain-la Neuve Sud,  
Belgium  
Tel: +32 10 47 52 73  
CNMIS  
16 Avenue Hoch,  
75008 Paris, France  
Tel: +33 1 53 89 00 40  
DIFT  
Jernholmen 12,  
DK-2650 Hvidovre,  
Denmark  
Tel: +45 36 349 000  
Note: This document is based on the recommendations of BS5839 Part 1: 2002. It is intended only as a guide to the application of fire d
Reference must be made to relevant national and local standards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYSTEM SENSOR EUROPE  
15 – 19 Trescott Road  
Trafford Park  
Smallwood  
Redditch  
B98 7AH  
United Kingdom  
Telephone: + 44 (0)1527 406700  
Fax: + 44 (0)1527 406699  
manufacturing and support centres  
RUSSIA  
System Sensor Fire Detectors  
Volochaevskaya Str 40, Bld 2  
Moscow 109033  
INDIA  
System Sensor India  
Pace city 2, Sector 36  
Gurgaon -122004  
Haryana, India  
ITALY  
System Sensor Europe  
Via Caboto 19/3  
34147 Trieste  
Italy  
Russia  
Telephone: + 7 (095) 937-7982  
Fax: + 7 (095) 937-7983  
Telephone: + 91 124 6371770  
Fax: + 91 124 6373118  
Telephone: + 39 040 9490111  
Fax: + 39 040 382137  
Other operations in Australia, Canada, China, Hong Kong, Mexico and United States of America  
WORLD HEADQUARTERS  
System Sensor  
3825 Ohio Avenue  
St. Charles  
IL-60174  
United States of America  
Telephone: + 1 630 377 6580  
Fax: + 1 630 377 6495  
Advanced ideas. Advanced Solutions  
November 2004  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Sennheiser Microphone 518 User Manual
Sennheiser Wireless Office Headset SD Pro 1 User Manual
ShelterLogic Gas Grill VS14032 User Manual
Sony Camcorder PJ10 User Manual
Sony Computer Monitor CPD 15SF2 User Manual
Sony MiniDisc Player MZ B10 User Manual
Sony Portable Speaker SA WFT7 User Manual
Sony Speaker SA VE367T User Manual
Southern Pride Smoker BBR 700 FL User Manual
Stow Webcam SMC3PB User Manual