A P P L I C A T I O N S
G U I D E
System
Smoke Detectors
Download from Www.Somanuals.com. All Manuals Search And Download.
A
P
P
L
I
C
A
T
I
O
N
S
G
U
I
D
E
:
S
Y
S
T
E
M
S
M
O
K
E
D
E
T
E
C
T
O
R
S
The purpose of this guide is installers should find the contents both educational and
to provide information con- informative.
Introduction
cerning the proper application of smoke detectors used in
conjunction with fire alarm systems. It outlines basic prin- Though this information is based upon industry expertise
ciples that should be considered in the application of early and many years of experience, it is intended to be used
warning fire and smoke detection devices. Operating char- only as a technical guide. The requirements of applicable
acteristics of detectors and environmental factors, which codes and standards, as well as directives of the Authorities
may aid, delay or prevent their operation, are presented.
Having Jurisdiction (AHJ’s) should be followed. In partic-
ular, the most current version of NFPA 72 for installation
Fire protection engineers, mechanical and electrical engi- and testing of systems is a key element in the effectiveness
neers, fire service personnel, fire alarm designers and of smoke detection systems.
Section 1
ICBO’s Uniform Building Code is generally used through-
out the West and Southwest regions of the United States.
NFPA Codes and
Standards
NFPA publishes standards for
the proper application, instal-
Standards That
Apply
Southern Building Code Congress International (SBCCI)
900 Montclair Road, Birmingham, Alabama 35213-1206
SBCCI’s Standard Building Code is generally used in the
South and Southeast regions of the United States.
lation, and maintenance of automatic smoke detectors. The
principal codes and standards that should be reviewed
before specifying or installing automatic smoke detectors
are listed below:
International Code Council, Inc. (International Building
Code/International Fire Code)
5360 Workman Mill Road, Whittier, California 90601-
2298
The organizations listed above have formed an umbrella
organization known as the International Code Council
(ICC), for the purpose of combining the codes produced by
the above three organizations into a single set of model
building and fire codes. ICC’s International Building Code
and International Fire Code were first published in 2000
and have been adopted by some states.
National Fire Protection Association (NFPA)
Batterymarch Park, Quincy, Massachusetts 02269-9101
NFPA publishes codes and standards concerning all phas-
es of fire protection. Among those which directly concern
automatic smoke detectors are:
NFPA 70: National Electrical Code
NFPA 72: National Fire Alarm Code
NFPA 72 covers minimum performance, location, mount-
ing, testing, and maintenance requirements of automatic
fire detectors.
Testing Laboratories
Testing laboratories test smoke detectors, control panels
and other components of fire alarm systems to verify con-
formance with NFPA requirements and their own stan-
dards. Equipment that passes their tests are identified by a
label and/or listing.
NFPA 90A: Standard for the Installation of Air
Conditioning and Ventilating Systems
NFPA 92A: Smoke Control Systems in Malls, Atria, and
Large Areas
NFPA 90A and 92A provide information for the use of
smoke detectors in ducts of HVAC systems and smoke con-
trol systems.
Underwriters Laboratories, Inc. (UL)
333 Pfingsten Road, Northbrook, Illinois 60062
1655 Scott Boulevard, Santa Clara, California 95050
1285 Walt Whitman Road, Melville, New York 11747
12 Laboratory Drive, P.O. Box 13995, Research Triangle
Park, North Carolina
NFPA 101: Life Safety Code
NFPA 101 specifies the requirements for smoke detection in
both new and existing buildings depending on the type of
occupancy.
UL publishes an annual directory listing fire protection
equipment which bear the UL label. Its standards which
apply to smoke detectors are:
Building and Fire Codes
There are three independent regional organizations which
write model building and fire codes which become law
when adopted by local and state governments. These codes
specify smoke detector requirements based on building
type and occupancy. The organizations are:
UL 217: Single and Multiple Station Smoke Detectors
UL 268: Smoke Detectors for Fire Protection Signaling
Systems
UL 268A: Smoke Detectors for Duct Applications
UL 864: Standard for Control Units for Fire Protective
Signaling Systems
Building Officials and Code Administrators (BOCA)
4051 West Flossmoor Road, Country Club Hills, Illinois
60478-5795
BOCA’s National Building Code is generally used through-
out the northeast and midwest regions of the United States.
Factory Mutual Research (FM)
1151 Boston-Providence Turnpike, P.O. Box 9102,
Norwood, Massachusetts 02062
International Conference of Building Officials (ICBO)
5360 Workman Mill Road, Whittier, California 90601-
2298
FM publishes an annual report listing fire protection equip-
ment which bears its label.
2
Download from Www.Somanuals.com. All Manuals Search And Download.
S
Y
S
T
E
M
S
E
N
S
O
R
Industry Publications
Manufacturer’s Publications
NEMA Guide for Proper Use of Smoke Detectors in Duct
Applications
The manufacturer of the smoke detectors being used
should be contacted for any published information on their
products.
NEMA Training Manual on Fire Alarm Systems
NEMA Guide to Code Requirements for Fire Protective
Signaling and Detection Systems
NEMA Guide for proper Use of System Smoke Detectors
Section 2
There are two basic types of Electronic circuitry monitors both chambers and compares
smoke detectors in use today; their outputs. If the humidity or the atmospheric pressure
ionization and photoelectric. changes, both chambers’ outputs are affected equally and
The sensing chambers of these cancel each other. When combustion particles enter the
How Smoke
Detectors Work
detectors use different principles of operation to sense the sensing chamber, its current decreases while the current of
visible or invisible particles of combustion given off in the reference chamber remains unchanged. The resulting
developing fires.
current imbalance is detected by the electronic circuitry.
(See Figure 5.) There are a number of conditions that can
affect dual-chamber ionization sensors; dust, excessive
humidity (condensation), significant air currents, and tiny
insects can be misread as particles of combustion by the
electronic circuitry monitoring the sensors.
Ionization Smoke Detector Operation
A typical ionization chamber consists of two electrically
charged plates and
a
radioactive source (typically
Americium 241) for ionizing the air between the plates.
(See Figure 1.) The radioactive source emits particles that
collide with the air molecules and dislodge their electrons.
As molecules lose electrons, they become positively
charged ions. As other molecules gain electrons, they
become negatively charged ions. Equal numbers of positive
and negative ions are created. The positively charged ions
are attracted to the negatively charged electrical plate,
while the negatively charged ions are attracted to the pos-
itively charged plate. (See Figure 2.) This creates a small
ionization current that can be measured by electronic cir-
cuitry connected to the plates (“normal” condition in the
detector).
Figure 2: Ion Distribution
Figure 1: Particle Radiation Pattern
Particles of combustion are much larger than the ionized
air molecules. As particles of combustion enter an ioniza-
tion chamber, ionized air molecules collide and combine
with them. (See Figure 3.) Some particles become posi-
tively charged and some become negatively charged. As
these relatively large particles continue to combine with
many other ions, they become recombination centers, and
the total number of ionized particles in the chamber is
reduced. This reduction in the ionized particles results in a
decrease in the chamber current that is sensed by elec-
tronic circuitry monitoring the chamber. When the current
is reduced by a predetermined amount, a threshold is
crossed and “alarm” condition is established.
Figure 3: Ion and Particles of Combustion Distribution
Changes in humidity and atmospheric pressure affect the
chamber current and create an effect similar to the effect of
particles of combustion entering the sensing chamber. To
compensate for the possible effects of humidity and pressure
changes, the dual ionization chamber was developed and
has become commonplace in the smoke detector market.
Sensing Chamber
(Current Decreasing)
Sensing Chamber
Source
A dual-chamber detector utilizes two ionization chambers;
one is a sensing chamber that is open to the outside air.
(See Figure 4). The sensing chamber is affected by partic-
ulate matter, humidity, and atmospheric pressure. The
other is a reference chamber that is partially closed to out-
side air and affected only by humidity and atmospheric
pressure, because its tiny openings block the entry of larg-
er particulate matter including particles of combustion.
Reference
Chamber
(Current Stable)
Reference Chamber
(Current Stable)
Figure 5: Dual Chamber with
Particles of Combustion
Figure 4: Dual Chamber
3
Download from Www.Somanuals.com. All Manuals Search And Download.
A
P
P
L
I
C
A
T
I
O
N
S
G
U
I
D
E
:
S
Y
S
T
E
M
S
M
O
K
E
D
E
T
E
C
T
O
R
S
Photoelectric Light Obscuration Smoke Detector
Photoelectric Smoke Detector Operation
Another type of photoelectric detector, the light obscura-
tion detector, employs a light source and a photosensitive
receiving device, such as a photodiode (see Figure 8).
When smoke particles partially block the light beam
(Figure 9), the reduction in light reaching the photosensi-
tive device alters its output. The change in output is sensed
by the detector’s circuitry, and when the threshold is
crossed, an alarm is initiated. Obscuration type detectors
are usually of the projected beam type where the light
source spans the area to be protected.
Smoke produced by a fire affects the intensity of a light
beam passing through air. The smoke can block or obscure
the beam. It can also cause the light to scatter due to reflec-
tion off the smoke particles. Photoelectric smoke detectors
are designed to sense smoke by utilizing these effects of
smoke on light.
Photoelectric Light Scattering Smoke Detector
Most photoelectric smoke detectors are of the spot type and
operate on the light scattering principle. A light-emitting
diode (LED) is beamed into an area not normally “seen” by
a photosensitive element, generally a photodiode. (See
Figure 6.) When smoke particles enter the light path, light
strikes the particles (Figure 7) and is reflected onto the pho-
tosensitive device causing the detector to respond.
Light Source
Light Sensitive Device
Light Source
Light Sensitive Device
Light Sensitive Device
Figure 6: Light Scattering Detector
Figure 7: Light Scattering Detector with Smoke
Light Source
Light Sensitive Device
Light Source
Figure 8: Light Obscuration Detector
Figure 9: Light Obscuration Detector with Smoke
Smoke Detector Design Considerations
Considerations in Selecting Detectors
Smoke detectors are based on simple concepts, but certain The characteristics of an ionization detector make it more
design considerations need to be observed. They should suitable for detection of fast flaming fires that are charac-
produce an alarm signal when smoke is detected, but terized by combustion particles in the 0.01 to 0.4 micron
should minimize the impact of an unwanted signal which size range. Photoelectric smoke detectors are better suited
can arise from a variety of causes. In an ionization detec- to detect slow smoldering fires that are characterized by
tor, dust and dirt can accumulate on the radioactive source particulates in the 0.4 to 10.0 micron size range. Each type
and cause it to become more sensitive. In a photoelectric of detector can detect both types of fires, but their respec-
detector, light from the light source may be reflected off the tive response times will vary, depending on the type of fire.
walls of the sensing chamber and be seen by the photo-
sensitive device when no smoke is present. The entrance of Because the protected buildings normally contain a variety
insects, dirt, drywall dust, and other forms of contamina- of combustibles, it is often very difficult to predict what
tion into the sensing chamber can also reflect light from size particulate matter will be produced by a developing
the light source onto the photosensitive device.
fire. The fact that different ignition sources can have dif-
ferent effects on a given combustible further complicates
Electrical transients and some kinds of radiated energy can the selection. A lighted cigarette, for example, will usually
affect the circuitry of both ionization and photoelectric produce a slow smoldering fire if it is dropped on a sofa or
smoke detectors and be interpreted by the electronic cir- bed. However, if the cigarette happens to fall upon a news-
cuitry to be smoke, resulting in nuisance alarms.
paper on top of a sofa or bed, the resulting fire may be
characterized more by flames than by smoldering smoke.
The allowable sensitivity ranges for both types of detectors
are established by Underwriters Laboratories, Inc. and all The innumerable combustion profiles possible with vari-
are verified by their performance in fire tests. Regardless of ous fire loads and possible ignition sources make it difficult
their principle of operation all smoke detectors are required to select the type of detector best suited for a particular
to respond to the same test fires.
application.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
S
Y
S
T
E
M
S
E
N
S
O
R
For more information, see NFPA 72-1999, paragraphs A-2- save more in the future. Nevertheless, smoke detectors do
3.6.1.2, A-2-3.6.1.1, A-2-3.6.1.2(a), and A-2-3.6.1.2(b).
have limitations. They may not provide early warning of a
fire developing on another level of a building. A first floor
NFPA 72 requirements also dictate that alarm notification detector, for example, may not detect a second floor fire.
appliances (including smoke detectors with built-in For this reason, detectors should be located on every level
sounders) produce the 3-pulse temporal pattern fire alarm of a building. In addition, detectors may not sense a fire
evacuation signal described in ANSI S3.41. (Audible developing on the other side of a closed door. In areas
Emergency Evacuation Signals)
where doors are usually closed, detectors should be locat-
ed on both sides of the door.
Situations Where Other Types of Detectors May Be Used
In certain circumstances where standard smoke detectors
are unsuitable, special-purpose detectors, such as flame
detectors, heat detectors, and other detection devices may
be used.
As already indicated, detectors have sensing limitations.
Ionization detectors are better at detecting fast, flaming
fires than slow, smoldering fires. Photoelectric smoke
detectors sense smoldering fires better than flaming fires.
Because fires develop in different ways and are often
unpredictable in their growth, neither type of detector is
always best. A given detector may not always provide sig-
nificant advance warning of fires when fire protection prac-
tices are inadequate, nor when caused by violent explo-
sions, escaping gas, improper storage of flammable liquids
such as cleaning solvents, etc.
The application of these special types of detectors should
be based on an engineering survey and used in accordance
with the manufacturer’s installation instructions provided.
Smoke Detectors Have Limitations
Smoke detectors offer the earliest possible warning of fire.
They have saved thousands of lives in the past and will
Section 3
Wiring Supervision
Class B Circuits
Typical System
Layout
The initiating circuits that con- Class B circuits differentiate between short circuits across
nect smoke detectors to a con- the loop (alarm) and opens on the loop (trouble).
trol panel should be super- Supervision of this circuit is accomplished by passing a low
vised so that a fault (trouble) condition that could interfere current through the installation wiring and an end-of-line
with the proper operation of the circuit will be detected resistor. Increases or decreases in this supervisory current
and annunciated.
are monitored by the fire alarm control panel and will
cause alarm or trouble conditions, respectively, to be indi-
Smoke detectors are generally categorized as either 2-wire cated. A single open in a Class B circuit disables all devices
or 4-wire detectors. Two-wire detectors derive their power electrically beyond the open.
directly from the same fire alarm control panel alarm initi-
ating device circuit over which they report an alarm.
Because of their dependency on the initiating circuit, 2-wire
END OF LINE
RESISTOR
detectors must be tested and listed for compatibility with
the control panel to be used, to ensure proper operation.
Four-wire detectors are powered from a separate pair of
wires, and, like the 2-wire detector, apply an electrical
short across the associated alarm initiating device circuit to
transmit an alarm (Figure 10). Because they do not derive
power from the alarm initiating device circuit, electrical
compatibility is predicated upon the operating parameters
TYPICAL
INITIATING
DEVICES
of the power supply to which the detectors are connected
and not the initiating circuit. Supervision of the power to
4-wire detectors is mandated through the use of an end-of-
line power supervision relay. When power is on, the relay
contacts of the end-of-line relay are closed and connected
in series with the end-of-line resistor beyond the last initi-
ating device. Loss of power at any point in the power sup-
ply circuit will cause the relay to de-energize and a trouble
condition to occur on the initiating circuit.
INITIATING DEVICE
CIRCUIT
ZONE 1
TROUBLE
ALARM
NOTE*: Refer to the fire alarm control panel manufacturer’s
operating manual to determine the ability of a specific initi-
ating circuit to react in a “Class B” or “Class A” fashion.
FIRE ALARM CONTROL UNIT
PRIMARY
POWER
SUPPLY
*NFPA 72 now classifies initiating device circuits by “Style” and “Class”. Style B
is an example of a Class B circuit; Style D is an example of a Class A circuit.
Figure 10: Two-Wire Detector Circuit
5
Download from Www.Somanuals.com. All Manuals Search And Download.
A
P
P
L
I
C
A
T
I
O
N
S
G
U
I
D
E
:
S
Y
S
T
E
M
S
M
O
K
E
D
E
T
E
C
T
O
R
S
Class A Circuits
Class A circuits also differentiate between short circuits
across the loop and opens on the loop. Supervision is
accomplished by monitoring the level of current passing
through the installation wiring and the end-of-line resistor,
which in a Class A circuit is an integral part of the fire
alarm control panel. Class A wiring must return to and be
terminated in the control panel. This technique requires a
minimum of four conductors to be terminated at the panel,
and further requires that the fire alarm control panel is
designed to monitor Class A circuits. The additional cir-
cuitry necessary for Class A supervision enables the con-
trol panel to “condition” the initiating circuit to monitor
the initiating circuit from both ends when in a trouble
mode due to an open fault on the loop. This “conditioning”
ensures that all devices are capable of responding and
reporting an alarm despite a single open or non-simultane-
ous single ground fault on a circuit conductor.
TYPICAL
INITIATING
DEVICES
INITIATING DEVICE
CIRCUIT
INITIATING DEVICE
CIRCUIT RETURN
ZONE 1
TROUBLE
ALARM
The compatibility considerations of smoke detectors that
were detailed in Class B circuits apply with Class A as well
(Figure 11).
FIRE ALARM CONTROL UNIT
PRIMARY
POWER
SUPPLY
Figure 11: 2-Wire Detectors – Style D (Class A) Circuit
Wireless Circuits
Fire Safety Functions
Wireless detectors and their internal transmitters derive Often smoke detectors are utilized to control ancillary
their operating power from their internal battery or batter- equipment. Most detectors used in releasing service have
ies and are listed by Underwriters Laboratories, Inc. in auxiliary relay contacts which are directly connected to the
accordance with requirements of NFPA 72. Supervision of system or device to be controlled. Care should be taken to
the internal battery power source is incorporated within ensure that detectors utilized in such a manner are
the smoke detector circuitry. If the battery power source approved for releasing service. A few of the typical appli-
depletes to the threshold specified by Underwriters cations are as follows:
Laboratories, the smoke detector will sound a local alert
and initiate a trouble signal once each hour for a minimum
of seven days or until the battery or batteries are replaced.
• To control the flow of smoke in air handling and air
conditioning systems.
• To release doors to contain smoke in a fire situation.
• To release locks to allow exit in a fire situation.
• To capture and recall elevators in a fire situation.
• To activate a suppression system.
The wireless initiating devices are supervised for tamper
and/or removal by initiating a distinct trouble signal. Each
wireless device also initiates a test transmission every hour
to verify the reliability of the communication circuit. Any Spacing and placement requirements for detectors used in
device failing to communicate is identified on the control releasing service may be different from detectors used in
panel no less than every four hours.
conventional open area applications. It is recommended
that 4-wire detectors be used in these situations because
depending on the control panel and detectors used, more
than one detector relay on a circuit may not receive enough
power from the 2-wire circuit to operate during alarm.
General Zoning Guidelines
The faster the source of an alarm can be pinpointed, the
faster action can be taken. Although formal rules for zon-
ing are not given in fire protection codes, except for wire-
less devices where each smoke detector must be individu- Smoke Detector Installation
ally identified, it is always sensible to zone any system that Wiring Installation Guidelines
contains more than
a
small number of detectors. All fire alarm system installation wiring should be installed
Experienced detector installers and system designers rec- in compliance with Article 760 of NFPA 70, the National
ommend the following:
Electrical Code (NEC), the manufacturer’s instructions and
the requirements of the authority having jurisdiction.
• Establish at least one zone on every protected floor.
• Zone natural subdivisions of a large building, such as
separate wings on a single floor.
Typical Wiring Techniques
• Minimize the number of detectors in each zone. Fewer The primary rule of installation wiring is:
detectors on a zone will speed up locating the fire and
simplify troubleshooting.
“Follow the Manufacturer’s Instructions”
This rule cannot be overemphasized. The requirement for
• Install duct detectors in different zones than open-area electrical supervision of the installation wires and their
detectors for troubleshooting and locating purposes.
connections to initiating devices makes fire alarm system
installation wiring very different than general wiring.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
S
Y
S
T
E
M
S
E
N
S
O
R
A manufacturer’s installation wiring drawing routes wires
and shows connections in a certain manner to accommo-
date supervision requirements. Any variance from the
manufacturer’s drawings might cause a portion of a circuit
to be unsupervised and, if an open or short circuit fault
occurred, it could prevent the circuit from being able to
perform its intended function without giving the required
trouble indication.
Smoke Detector “A”
The rules of supervision are not very complex. However,
unless an installer is experienced in fire alarm system instal-
lations, he or she would not likely be familiar with them.
Smoke detector manufacturer’s installation drawings will
show how their detectors are to be connected into a system.
However, a manufacturer’s drawings may not show how
devices located on the same floor, but served by a different
riser (vertical wiring run), should be connected. The dia-
grams on the following page should be considered as typi-
cal initiating device circuits utilizing smoke detectors. They
are offered to illustrate proper and improper installation
wiring and termination techniques. Since there are always
exceptions to typical installation drawings, experienced
installers use the primary rule of installation wiring: Follow
the manufacturer’s instructions, and meet the local codes.
Smoke Detector
Smoke Detector
Figure 12: Incorrect Wiring Method
Smoke Detector
Figure 12 illustrates improper wiring of smoke detector “A”.
This wiring method is referred to as “T-tapping.” This com-
mon installation error is often made in riser wiring as well
as single floor wiring. The smoke detector may operate
properly under alarm conditions. If it becomes disconnect-
ed from the installation wiring loop beyond the “T-tap”,
however, the detector would not function, and no “trou-
ble” condition would occur.
NOTE: “T-tapping” may be permitted with some
“intelligent” fire alarm systems. Refer to manufacturer’s
recommendations.
Smoke Detector
Smoke Detector
Figure 13: Correct Wiring Method
Figure 13 illustrates the correct installation wiring method
for smoke detectors. None of the connections can be bro-
ken without opening the circuit, causing loss of supervi-
sion, and the fire alarm control panel to indicate trouble.
Smoke detectors should be connected to supervised instal-
lation wiring in a manner that ensures electrical supervision
of the device. Removal of a detector from its associated ini-
tiating circuit should cause the loop to open, resulting in a
trouble condition. The required termination at the smoke
detector may involve either screw terminals or wire pigtails.
Regardless of the method utilized, removal of the smoke
detector or a single installation wire must open the initiat-
ing circuit and result in a trouble signal at the control panel.
Figure 14: Proper Termination
Screw termination of either side of the initiating circuit may
require only one or two screws. Figure 14 is an example of
proper termination when one screw terminal is used. Note
that the installation conductor has been cut before termina-
tion. This assures full supervision of the smoke detector.
Figure 15 details common connection errors. In both exam-
ples, removal of the smoke detector wire does not open the
initiating circuit. The fire alarm control panel will not rec-
ognize a trouble condition, and the detector that has been
deliberately or inadvertently disconnected will be disabled.
Figure 15: Improper Termination
7
Download from Www.Somanuals.com. All Manuals Search And Download.
A
P
P
L
I
C
A
T
I
O
N
S
G
U
I
D
E
:
S
Y
S
T
E
M
S
M
O
K
E
D
E
T
E
C
T
O
R
S
Figure 16 is an example of properly connected
smoke detectors provided with pigtails. This
method of termination supervises all wiring to
the point at which it connects to the detector.
may require more power than the initiating device cir-
cuit can supply. This could result in the inability of the
relay to control auxiliary equipment to which it is con-
nected.
Wire Nut
• When using wireless detectors, follow the manufactur-
er’s installation instructions to assure proper radio
communication between the smoke detector and the
control panel.
• Observe polarity when required.
• Protect detectors against contamination during con-
struction or renovation.
Smoke
Detector
Figure 17 shows an incorrect pigtail connec-
tion. This is a form of “T-tapping” discussed
earlier. Note that the conductor between the
wire nut (or splice) and the detector is unsu-
pervised, and could be cut or disconnected
without resulting in a trouble signal.
Figure 16: Pigtail Connections –
Correct Wiring Method
• Carefully follow the manufacturer’s installation
instructions.
Wireless Systems
Wireless smoke detectors do not require any
field wiring as the power for the initiating
devices is contained and incorporated within
the device. Removal of a wireless smoke detec-
tor initiates a distinct tamper or trouble signal.
Follow the instructions in the manufacturer’s
installation manual for wireless systems.
Wire Nut
Don’t:
• “T-tap” smoke detectors or circuit conductors, except
when specifically permitted by the manufacturer as
part of an intelligent/addressable system.
• Loop uncut installation conductors around screw ter-
minations.
• Exceed the maximum resistance permitted for the ini-
tiating device system.
• Exceed the number of 2-wire detectors allowed on a 2-
wire initiating circuit (specified by UL).
Installation Do’s and Don’ts
Do:
Smoke
Detector
• Verify that 2-wire smoke detectors to be
used have been tested and UL listed for
compatibility with the equipment to
which they are connected. If necessary,
contact the manufacturer for this informa-
tion.
• Locate any end-of-line devices electrically
at the end of the circuit, beyond all initi-
ating devices (not at the control unit,
except in a Class A installation).
• Use caution when utilizing 2-wire detec-
tors with integral relays, because they
Wiring and System Checkout
As required for all installation wiring of fire alarm systems,
check the detector loop wiring for grounds, short circuits,
and open faults before the system is placed into operation.
Each detector should be tested in accordance with the
manufacturer’s instructions.
Figure 17: Pigtail Connections –
Incorrect Wiring Method
When using wireless detectors, verify the radio signal trans-
mission strength in accordance with the installation manual.
Section 4
After all detectors have been Some codes or ordinances have minimum objectives such
installed, test the complete as capturing elevators or preventing circulation of smoke
system to ensure that no through the HVAC systems instead of early detection of fire.
wiring faults exist, and that all
parts of the system operate as A user should weigh the costs against the benefits of
intended. A complete system installing a complete fire detection system when any detec-
Proper Detector
Applications,
Placement and
Spacing*
checkout consists of testing each detector at its installed tion system is being installed. The location, quantity and
location and following the panel manufacturer’s instruc- zoning of detectors should be determined by what objec-
tions for system checkout. Also, refer to NFPA 72 for addi- tives are desired rather than the minimum requirements of
tional information.
any local codes or ordinances.
“Total coverage”, as defined in NFPA 72, is the definition
of a complete fire detection system. In some of the speci-
fied areas of coverage, such as attics, closets, under open
loading docks or platforms, a heat detector may be more
appropriate than a smoke detector. Careful consideration
should be given to the detector manufacturer’s instructions
and the following recommendations in this guide.
Where to Place Detectors
Detector placement is critical to early warning functions.
To provide effective early warning of a developing fire sit-
uation, smoke detectors should be installed in all areas of
the protected premises. Total coverage as defined by NFPA
72 should include all rooms, halls, storage areas, base-
ments, attics, lofts, and spaces above suspended ceilings
including plenum areas utilized as part of the HVAC sys-
tem. In addition, this should include all closets, elevator
shafts, enclosed stairways, dumbwaiter shafts, chutes and
other subdivisions and accessible spaces.
In general, when only one detector is required in a room or
space, the detector should be placed as close to the center
of the ceiling as possible. Central location of the detector is
best for sensing fires in any part of the room. If a center
location is not possible, it may be placed no closer than 4
inches from the wall, or if listed for wall mounting, it may
Fire detection systems installed to meet local codes or ordi-
nances may not be adequate for early warning of fire.
*The guidelines in this section of the guide are adapted from Standards published by the National Fire Protection Association, Quincy,
Massachusetts, USA. These standards include NFPA 72, National Fire Alarm Code; NFPA 70, “National Electrical Code”, Article 760; and NFPA
90A, “Installation of Air Conditioning and Ventilating Systems”.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
S
Y
S
T
E
M
S
E
N
S
O
R
be mounted on the wall. Wall-mounted detectors should be
located not less than 4 inches nor more than 12 inches
from the ceiling to the top of the detector, and at least 4
inches (10 cm) from any corner wall junction. (See Figure
18.)
4 in. (10 cm)
Ceiling
When air supply and/or air return ducts are present in a
room or space, the detector(s) should not be placed in the
path of the air flow supply or return duct (NFPA 72, 1999
Edition).
Smoke tests are helpful in determining proper placement.
Special attention should be given to smoke travel directions
and velocity, since either can affect detector performance.
Never Here
Acceptable Here
Placement of detectors near air conditioning or incoming
air vents can also cause excessive accumulation of dust
and dirt on the detectors. This dirt can cause detectors to
malfunction and cause unwanted alarms. Detectors should
not be located closer than 3 feet from an air supply diffuser
or an air return vent.
Top of Detector Acceptable Here
Spot type detectors, in properly engineered systems, may
also be placed in return air ducts, or in approved duct
detector housings designed for this application. Although
duct detectors are not a substitute for open area detectors,
they can provide an effective method of initiating building
control functions to prevent smoke from being transported
from the fire area to other parts of a building. (See Duct
Smoke Detector Applications Guide.)
Note: Measurements shown are to the
closest edge of the detector.
Side Wall
Figure 18: Wall Mounted Detector – Placement
• Extreme Cold or Hot Environments
Where Not To Place Detectors
Avoid very cold or very hot environments, or unheat-
ed buildings or rooms where the temperature can fall
below or exceed the operating temperature range of
the detector. At temperatures above or below the oper-
ating range of the detector*, its internal components
may not function properly.
See Table A-2-3.6.1.2A in NFPA 72-1999.
One of the major causes of unwanted alarms is improper
placement of detectors. The best way to avoid unwanted
alarms is not to install detectors in environments that can
cause them to malfunction, or to install detectors specially
designed for those environments. Examples follow:
• Excessively Dusty or Dirty Areas
*Manufacturers’ specifications should list acceptable
temperatures in these ranges.
• Areas with Combustion Particles
In excessively dusty or dirty areas consider using the
Filtrex™ smoke detector. This detector incorporates a
microprocessor-controlled air intake fan and filter that
allows the unit to be installed in areas where ordinary
detectors cannot be used. Filtrex is an intelligent
smoke detector that removes airborne particles before
they reach the sensing chamber. It is ideal for textile
mills, dusty manufacturing facilities, paper mills, and
recycling centers. For more information see System
Sensor’s Filtrex™ Applications Guide.
Avoid areas where particles of combustion are nor-
mally present, such as in kitchens or other areas with
ovens and burners; in garages, where particles of com-
bustion are present in vehicle exhausts. When a detec-
tor must be located in or adjacent to such an area, a
heat detector may be appropriate.
• Manufacturing Areas
Avoid manufacturing areas, battery rooms, or other
areas where substantial quantities of vapors, gases, or
fumes may be present. Strong vapors can make detec-
tors overly sensitive or less sensitive than normal. In
very large concentrations, gases heavier than air, such
as carbon dioxide, may make detectors more sensitive,
while gases lighter than air, such as helium, may make
them less sensitive. Aerosol particles may collect on
detector chamber surfaces and cause nuisance alarms.
• Fluorescent Light Fixtures
• Outdoors
Avoid using detectors outdoors, in open storage sheds,
or other open structures affected by dust, air currents,
or excessive humidity and temperature extremes.
• Wet or Excessively Humid Areas
Avoid damp, wet or excessively humid areas, or next
to bathrooms with showers.
• Elevator Lobbies
Avoid placement near fluorescent light fixtures.
Electrical noise generated by fluorescent light fixtures
may cause unwanted alarms. Install detectors at least
1 foot (0.3 m) away from such light fixtures.
Do not place over ashtrays or where people will smoke
while waiting for the elevator.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
A
P
P
L
I
C
A
T
I
O
N
S
G
U
I
D
E
:
S
Y
S
T
E
M
S
M
O
K
E
D
E
T
E
C
T
O
R
S
to use system detectors and manual fire alarm stations in
the hallways and common areas of the complex and resi-
dential single station type smoke detectors and heat detec-
tors in the individual apartments. The system detectors,
manual stations and heat detectors would be connected to
a control panel, sound a general alarm and automatically
notify the proper authorities that a fire condition exists.
The residential smoke detectors located in the apartments
would be interconnected only within the individual living
quarters of each apartment. These residential units would
sound an alarm only in the apartment where a fire started.
Special Application Detectors
The guidelines in this document generally apply to stan-
dard open-area smoke detectors. System Sensor has a num-
ber of advanced technology detectors that are optimized
for specific environments and should be considered.
Pinnacle™ Laser technology smoke detector is designed for
use in areas that require extremely early warning of fire. It
is designed to detect the earliest particles of combustion
making it ideal for clean rooms, computer rooms or
telecommunication centers — any area where any damage
is too much. As Pinnacle is ultra-sensitive to smoke — as
much as 100 times more sensitive than standard detectors
— care and judgement of application is needed to prevent
unwanted alarms. See System Sensor’s Pinnacle™
Applications Guide.
Detector Spacing
General Spacing Guidelines
Some fire protection codes specify detector spacing on a
given center-to-center distance between detectors under
ideal conditions. These distances are based on rooms with
smooth ceilings with no physical obstructions between the
contents being protected and the detectors. Moreover, they
are also based on a maximum ceiling height, and on the
assumption that the value and the combustible nature of
the contents of the room to be protected do not warrant
greater protection or closer spacing.
For environments classified as hazardous, System Sensor
offers Intrinsically Safe Detectors designed to provide
detection for high-risk areas such as oil production facili-
ties, refineries and chemical plants. These units operate on
low energy levels and are used with a safety barrier. See
our Guide for Proper Use of Intrinsically Safe Fire
Protection Devices.
If we assume a typical center distance spacing guideline is
30 feet (90 meters), how do we determine whether a given
room or space can be protected by a single detector? Figure
19 shows four detectors spaced horizontally and vertically
30 feet (9 meters) apart. Detectors B and D, however, are
more than 30 feet apart. Clearly, in this example detector
spacing can exceed the given 30 foot spacing and still com-
ply with the code if any source of combustion is within
21.2 feet (6.4 meters) of the horizontal projection of a
detector, and if no more than 900 square feet (82.8 square
meters) are being protected by one detector.
Standards for Smoke Detectors
Underwriters Laboratories (UL) has three standards for
smoke detectors: one for duct detectors, UL 268A; one for
single and multiple station smoke alarms, UL 217; and one
for systems type detectors, UL 268. Detectors should only
be used for the applications for which they are specifically
listed.
The 2000 NFPA 101 Life Safety Code notes in Section
9.6.2.10.4 that single station smoke alarms shall sound an
alarm only within an individual living unit, suite of rooms,
or similar area and shall not actuate the building fire alarm
system unless otherwise permitted by the authority having
jurisdiction. Section 9.6.1.5 states, “All systems and com-
ponents shall be approved for the purpose for which
installed.”
To determine what coverage patterns are permissible with-
in the 30 foot spacing, start by tracing a circle with a radius
of 21.2 feet. Keeping in mind the fact that most rooms and
areas to be protected are rectangular or square in shape, any
square or rectangle that fits within the circumference of the
circle may be protected by one detector. (See Figure 20.)
In addition to possible code noncompliance, the following
deficiencies would exist in a series of residential smoke
detectors, connected in a system mode:
A
B
• Since the system is not supervised, vandals or others
could disconnect a detector or the entire system, leav-
ing a building without protection. The residents would
be unaware of this serious life threatening condition.
• Residential smoke alarms do not latch in alarm. In
other words, the smoke alarm self-resets. One smoke
alarm in alarm will sound all the smoke alarms con-
nected together. It would be difficult to identify or
locate a specific smoke alarm that initially put the sys-
tem into alarm after the alarm condition was cleared.
30 ft. (9.1 m)
6.4 m)
21.2 ft. (
F
System detectors latch in alarm. They do not reset until
power is momentarily disconnected. This makes it conven-
ient to identify the location of a detector that caused the
control panel to alarm. In addition, system detectors are
specifically designed to connect to a panel. Two-wire detec-
tors require a UL compatibility review to verify that the
detector and panel operate together. A typical life safety
fire protection system for an apartment complex would be
D
C
Figure 19: Typical Detector Spacing
10
Download from Www.Somanuals.com. All Manuals Search And Download.
S
Y
S
T
E
M
S
E
N
S
O
R
In other words, if a diagonal through the center of the room
is no greater than the diameter of the circle, or 42.4 feet
(12.8 meters), one detector can be used under ideal condi-
tions. Figure 21 shows how a length of hallway can be pro-
tected by only two detectors under ideal conditions.
Rectangles
A 10 ft. × 41 ft. = 410 sq. ft.
B 15 ft. × 39 ft. = 585 sq. ft.
C 20 ft. × 37 ft. = 740 sq. ft.
D 25 ft. × 34 ft. = 850 sq. ft.
E 30 ft. × 30 ft. = 900 sq. ft.
Special Spacing Problems
The ideal conditions upon which code guidelines are based
do not exist in the majority of buildings. Detector installers
usually have to deal with a variety of problems, such as
uneven ceilings or ceilings crossed by beams and joists;
storage racks and partitions that obstruct the path of smoke
toward detectors; air stratification due to uninsulated roofs,
peaked or sloped ceilings, or localized heating or cooling
from heating, ventilating, and air conditioning systems;
and extensive variability in the value and combustion char-
acteristics of building contents. The following are suggest-
ed techniques for dealing with some of the special detector
spacing problems:
Figure 20: Detector Coverage Patterns
10 ft.
• Solid joist and beam construction. Per NFPA 72-1996,
solid joists are to be considered equivalent to beams
for smoke detector spacing guidelines. For ceiling
heights of 12 ft. (3.66 m) or lower and beam depths of
1 ft. (0.3 m) or less, smooth ceiling spacing running in
the direction parallel to the run of the beams is to be
used, and 1/2 the smooth ceiling spacing is to be used
in the direction perpendicular to the run of the beams.
Spot-type detectors may be located either on the ceil-
ing or on the bottom of the beams. For beam depths
exceeding 1 ft. (0.3 m) or for ceiling heights exceeding
12 ft. (3.66 m), detectors are to be located on the ceil-
ing in every beam pocket. If the beamed ceiling is also
sloped, use the spacing determined for flat beamed
ceilings. Use the average height over the slope as the
ceiling height in such cases. Note that, by definition in
NFPA 72, ceilings are to be considered smooth unless
the beams or joists are more than 4 in. (0.1 m) in
depth.
20.5 ft.
41 ft.
82 ft.
20.5 ft.
Figure 21: Detector Placement in Hallways
lating, or air conditioning (HVAC) system creates arti-
ficial hot or cold air layers in a room, the layers may
affect the flow of smoke to the detectors.
• Uninsulated Roofs. Uninsulated roofs present special
placement problems. Air movement toward ceiling
detectors is not impeded when the outside tempera-
ture is cool, but stratification can occur when outside
temperature is warm or hot, or when the roof is heat-
ed by the sun on bright, sunny days. Although true
thermal barriers are not present in many installations,
smoke tests should be run in factories or warehouses
with metal roofs on warm sunny days to determine
whether such a thermal barrier exists.
• High storage racks. Multi-level storage racks present
special problems for early fire detection. Developing
fires, especially smoldering fires, on the lower levels of
the racks may not be sensed rapidly by ceiling mount-
ed detectors. Upward convection of smoke can be
slowed or blocked by goods stored on the upper levels
of the racks. Multi-level fire detection is required.
Detectors should be installed on the ceiling above each
aisle and on intermediate levels of the racks adjacent
to alternate pallet sections, shown in NFPA 72-1999,
A-2-3.6.5. A consultant’s judgement may be required
for specific installations.
• Partitions. Partitions and many types of large, tall
equipment standing on the floor can block the flow of
smoke toward detectors. Any partition or similar
obstruction that is less than 18 inches (45 cm) from
the ceiling should be treated as a side wall dividing the
area protected.
• Peaked or Sloped Ceilings. Peaked or sloped ceilings
can foster air stratification. Codes may specify spacing
detectors by using horizontal spacing from the peak of
the roof or ceiling. For instance, if the specified dis-
tance from the peak is 3 feet (1 m), the dis-
tance is measured on the base of the
right triangle formed by a vertical line
dropped from the peak of the roof,
with the roof incline as the
Detector may be placed
anywhere in shaded area.
hypotenuse. Additional detec-
tors are installed on the
3 ft.
3 ft.
selected spacing, using
the horizontal distance,
not the distance
along the incline of
the ceiling. (See
Figure 22.)
• Air Stratification. Air stratification in a room may keep
air containing smoke from reaching ceiling-mounted
detectors. Three conditions are known to accentuate
air stratification: when a layer of hot air exists under a
poorly insulated roof heated by the sun, cooler air will
stratify the hot air layer at the ceiling; when a layer of
cold air exists under a poorly insulated roof cooled
from the outside by cold air, the heated air is cooled as
it reaches the cold air layer; or when a heating, venti-
S/2
S
S
S/2
S = Detector Spacing
Figure 22: Detector Spacing Layout – Sloped Ceilings (peaked type)
11
Download from Www.Somanuals.com. All Manuals Search And Download.
A
P
P
L
I
C
A
T
I
O
N
S
G
U
I
D
E
:
S
Y
S
T
E
M
S
M
O
K
E
D
E
T
E
C
T
O
R
S
• Alternate Detector Mounting. Mounting alternate
detectors up to 3 feet (1 m) below the ceiling can
increase detection of small or smoldering fires when
the possibility of air stratification exists. Figure 23
illustrates such an installation. Specific designs for
such an alternate detection should be based upon an
engineering survey.
• Heating, Ventilating and Air Conditioning (HVAC)
effects on air flow and air stratification should be
determined and considered when planning detector
placement. In rooms where forced-air ventilation is
present, detectors should not be located where air
from supply diffusers could dilute smoke before it
reaches the detector. This may require additional
detectors, because placing detectors only near return
air openings may leave the balance of the area with
inadequate protection, especially when the Heating,
Ventilating and Air Conditioning (HVAC) system is not
operating.
• Detectors placed in an above-ceiling air handling space
should not be used as a substitute for open area pro-
tection, because smoke may not be drawn into the air
handling space when the ventilating system is shut
down. The detector will be less responsive to a fire
condition in the room below than a detector located on
the ceiling of the room below due to dilution and fil-
tering of the air in the air handling space before the
smoke reaches a detector. (See the discussion of detec-
tor placement in Section 4: Where To Place Detectors).
• Burn characteristics and the value of assets being pro-
tected influence the spacing of detectors and the
amount of protection provided in a specific room or
area. Refer to NFPA 72-1999, Section 2-3.6 for more
detailed information on spacing of detectors under
special applications. Likewise, if the contents are espe-
cially valuable, for example, sophisticated and expen-
sive machinery or irreplaceable records, detectors
should be placed closer together.
Detectors in Air Handling and Air Conditioning
Systems
See NEMA Guide for Proper Use of Smoke Detectors in
Duct Applications and NFPA 72, National Fire Alarm Code
for more specific information.
Detectors in Above-Ceiling Plenum Areas
Including Plenums Utilized as Part of the HVAC
System
Detectors should be placed in plenum areas (above ceiling
air handling space) in addition to the open area detectors
installed in the open areas below and duct detectors
installed in the ducts. Plenum detectors are required to be
listed or tested and approved for the air velocities within
the environment in which they are to be installed.
Detectors placed in plenums MAY NOT be used as a sub-
stitute for open area protection, because smoke may not be
drawn into the plenum when the ventilating system is shut
down. When the system is operating, the detector may be
less responsive to a fire condition in the room below than
will a detector located on the ceiling of the room below.
This may be due to blockage, dilution, and filtering of the
air prior to its arrival at the detector location in the plenum
area.
Since the air circulating through the plenums is usually at
higher velocities than would be prevalent in the room
below, detector spacing should be reduced.
Also, the dilution of the smoke in plenum spaces is an
important consideration when utilizing smoke detectors
rated for higher velocities. Therefore, plenum detectors
should be utilized to detect fire in the plenum but should
never be utilized as a substitute for duct detectors and
open area detectors.
Maintenance requirements of detectors exposed to unusu-
al velocities (above 300 fpm) are generally increased due to
the excessive dirt buildup and contamination present in
these environments.
A
A
3 ft. Minimum
Smoke Detectors at Ceiling
Smoke Detectors below Ceiling
Figure 23: High Ceiling Area
12
Download from Www.Somanuals.com. All Manuals Search And Download.
S
Y
S
T
E
M
S
E
N
S
O
R
Smoke detectors are designed
to be as maintenance free as
possible. However, dust, dirt,
and other foreign matter can
accumulate inside a detector’s
sensing elements and change
its sensitivity. They can
Section 5
If a detector’s sensitivity is within specifications, nothing
further needs to be done to the detector. If the detector’s
sensitivity is outside specifications, clean the detector and
retest. If that does not place the sensitivity within the unit
specified range then follow the manufacturer’s recom-
mended procedure.
Testing,
Maintenance
and Service of
Detectors
become either more sensitive, which may cause unwanted
alarms, or less sensitive, which could reduce the amount of
warning time given in case of a fire. Both are undesirable.
Therefore, detectors should be tested periodically and
maintained at regular intervals. Follow closely the manu-
facturer’s specific recommended practices for maintenance
and testing. Also refer to Appendix B of NFPA 90A and
NFPA 72, Chapter 7.
Restore zone or system at the completion of testing.
Notify the proper authorities that testing has been com-
pleted and the system is again operational.
Refer to paragraph 7-4.1 of NFPA 72 for additional infor-
mation.
To assure that each smoke detector is within its listed and
marked sensitivity range it should be tested using either:
• A calibrated test method, or
• The manufacturer’s calibrated sensitivity test instru-
ment, or
• Listed control equipment arranged for the purpose, or
• Other calibrated sensitivity test method acceptable to
the authority having jurisdiction.
Caution
Smoke detectors are sophisticated electronic devices that
need periodic testing and maintenance. To maintain the
integrity of any fire alarm system, it is important to have a
qualified person periodically test the system.
Typical Inspection, Test and Maintenance
Practices
Detectors should be given a visual inspection at installation
and at least twice a year thereafter. This ensures that each
detector remains in good physical condition and that there
are no changes that would affect detector performance,
such as building modifications, occupancy hazards, and
environmental effects.
Detectors found to have a sensitivity of 0.25 percent/ft.
obscuration or more outside the listed and marked sensi-
tivity range should be cleaned and recalibrated or replaced.
Exception: Detectors listed as field adjustable may be
either adjusted within the listed and marked sensitivity
range, cleaned and recalibrated, or replaced.
Restore the zone or system at the completion of testing.
Notify the proper authorities that the smoke detector is
undergoing maintenance, and therefore the system will
temporarily be out of service. NOTE: Disable the zone or
system undergoing maintenance to prevent unwanted
alarms and possible dispatch of the fire department.
Notify all the persons contacted at the beginning of the test
that testing has been completed and the system is again
operational.
Some individuals rely on an aerosol chemical spray to test
the sensitivity of a detector. This can give unsatisfactory
results since an aerosol chemical spray does not accurate-
ly test detector sensitivity. NFPA 72-1999, Chapter 7,
Section 7-3.2.1 notes that, “The detector sensitivity shall
not be tested or measured using any device that adminis-
ters an unmeasured concentration of smoke or other
aerosol into the detector.” The duration of spray, distance
between the detector and the aerosol container, angle of
discharge, and different environmental conditions can pro-
duce random results. In addition, many aerosols leave an
oily residue. Over a period of time, this oily residue can
attract dust or dirt, which can make a detector more sensi-
tive and result in nuisance alarms.
Use a high power vacuum cleaner and remove dust from
the detector by placing the nozzle as close as possible to
the openings in the outside housing. A nozzle with a brush
attachment will assist in dust removal. Some detector’s
sensing chambers can be removed for more thorough
cleaning; refer to the manufacturer’s recommended proce-
dure for details.
Test each detector’s sensitivity per the manufacturer’s rec-
ommended procedure within one year after installation
and every alternate year thereafter.
Test each detector functionally in place annually, as
detailed in NFPA 72 1999 (Chapter 7).
Be sure to follow the manufacturer’s recommendation on
test gas, aerosol or smoke.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
A
P
P
L
I
C
A
T
I
O
N
S
G
U
I
D
E
:
S
Y
S
T
E
M
S
M
O
K
E
D
E
T
E
C
T
O
R
S
Section 6
Make sure that all the detectors in the zone or pinpointed
device(s) that show an alarm are checked before deciding
that it is a false alarm. If a fire does exist, more than one
detector may be in the alarm state, although no signs of fire
may be evident in the vicinity of the first activated detec-
tor. The fire could be overlooked.
What to Do About
Unwanted Alarms
Troubleshooting
Techniques
No detection system is imper-
vious to unwanted alarms.
Statistically, as the system size and the total number of
detectors increases, the total number of nuisance alarms
per year tends to increase. Historical experience in a given
installation or data on similar sized buildings with similar
utilization patterns can provide a basis for a rough indica-
tion of how many nuisance alarms are probable during a
12 month span; however, no two installations are identical.
Maintain an Alarm Log
The next step for all alarms should be entry of a report into
an Alarm Log. A typical Alarm Log is shown in Appendix
2 (page 19). Such a log serves immediate and long-term
purposes.
In small- to moderate-sized detection systems protecting
relatively combustion-free environments, like office build-
ings, more than one or two unwanted alarms per year
would be unusual. In more adverse environments, such as
laboratory or manufacturing facilities where combustion
processes are present, more frequent alarms can be antici-
pated. In very adverse environments, one alarm per month
might not be considered excessive.
The Alarm Log indicates which individuals responded to
the alarm and whether or not they took appropriate action.
Periodic review of the cumulative Alarm Log can help those
responsible for the detection system discern patterns in the
reported alarms. Generally, several months (or even years)
of data may be necessary before patterns begin to emerge.
In a worst case example, a pattern of repeated alarms or
small fires in a particular area may indicate a serious defi-
ciency in safety practices that should be promptly correct-
ed. In less obvious cases, patterns are indicated by repeat-
ed alarms in the same or adjacent zones with similar prob-
able causes, or repeated alarms in the same zone that
occur at about the same time of day, or time of year.
After the first few months, which serve as a shakedown
period, it should be possible to arrive at some reasonable
expectation for probable unwanted alarms from the sys-
tem. After that, any unexpected change in frequency or dis-
tribution indicates a problem that should be investigated.
The best way to monitor alarm frequency and distribution
is to maintain an alarm log.
Effects of Location or Environment
Reasons for Unwanted Alarms
Check for the effects of location and environment. Review
the information in this guide Where To Place Detectors and
Where NOT to Place Detectors to determine whether the
detector’s location or its environment is potentially causing
the unwanted alarms. Also, refer to the installation manu-
al for further information.
Unwanted alarms can result from a wide variety of causes,
including:
• Improper locations are environments where they will
not operate properly because of temperature extremes;
excessive dust, dirt, or humidity, excessive air flow
rates, or the normal presence of combustion particles
in the air streams surrounding the detectors.
• Improper installation can occur when detectors and
their wiring are not protected from interference from
induced currents and noise in adjacent wiring systems,
radio-frequency transmissions, and other types of elec-
tromagnetic effects.
• Inadequate maintenance can result in the accumula-
tion of dust and dirt on the detector’s sensing cham-
bers over a period of time.
• Seasonal effects such as the reactivation of a building
heating system after an extended summer shutdown
can cause alarms.
One often overlooked source of problems is the placement
of detectors where air streams carry smoke or chemical
fumes from some areas of an installation past detectors in
other areas unrelated to the source of the contaminants.
Diagnosing problems of this kind requires that air move-
ments into the problem area, especially near the ceiling, be
carefully checked and their sources be determined.
Experienced heating, ventilating, and air conditioning
(HVAC) engineers or contractors usually have the training
and specialized equipment (flow meters, etc.) to conduct
such a study. In very difficult cases, a full-scale smoke test
may be required to solve the problem.
• Building maintenance issues, such as accidental trig-
gering of a detector’s magnetic test switch, or the
introduction of plaster dust from drywall repairs into a
detector’s sensing chamber can cause unwanted
alarms.
Conversely, strong air streams near air inlet or supply
ducts, etc. can also prevent a detector from signaling an
alarm when a fire is present by blowing smoke away from
the detector heads.
• Induced current effects from lightning storms can
cause alarms.
• Infestation from insects small enough to enter the
detector’s sensing chamber.
• Vandalism or mischievous acts — detectors set off as a
prank have been found to be a problem in dormitories.
Inspect Detector for Dirt and Review Maintenance
If the Alarm Log indicated that after several months or a
year with a fairly stable alarm rate, there is a gradual
increase in the frequency of unwanted alarms, this is usu-
ally an indication that the detectors in the system should
be cleaned.
If an alarm occurs and a fire does not exist, the alarm
should be silenced, the problem unit located, and the
alarm system controls reset so that the effectiveness of the
detection system is restored.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
S
Y
S
T
E
M
S
E
N
S
O
R
NFPA standards require and smoke detector manufacturers or other dust-producing operations in the vicinity of the
recommend that all detectors be visually inspected twice detector heads to prevent false alarms due to the dust get-
a year.
ting into the detector sensing chambers. In new construc-
tion applications drywall dust contamination affects all
Clean the detectors at least once a year, or more frequent- types of smoke detectors. To help overcome this problem, it
ly if environmental conditions warrant it. See the section is strongly recommended that installation of detector heads
on Detector Testing and Maintenance in this guide for more be delayed until after drywall installation is completed or to
details.
protect detector heads from dust contamination.
In cases where the probable cause of a number of alarms
appears to be dust or dirt on the detectors, detector main- If alarms occur whenever the heating system is turned on
tenance schedules should be reviewed to determine the after an extended shutdown, due to the accumulated dust
dates when the detectors were last cleaned and tested. If burning off as the system components heat, the detector
the detectors are due or overdue for maintenance, schedul- system can be turned off for a short period while the heat-
ing and performing the recommended cleaning and testing ing system is activated and checked out, or the start-up of
should eliminate the problem.
the heating system can be scheduled for an evening, week-
end or other off-hours period to minimize the effects of
If the problem resulted from a temporary overall increase alarms on regular daytime activities.
in airborne dust due to nearby construction, scheduling a
one-time special cleaning for all the detectors in the system Not all unwanted alarms are caused by dirt, interference or
should alleviate the problem. If the problem is confined to other effects on the detectors. If the control panel shows an
one or two zones and is the result of higher dust levels in alarm but no detectors in the zone are indicating an alarm
a particular area, scheduling the detectors in those areas condition, the possibility of interference or a failure of a
for more frequent maintenance and cleaning may prevent control panel component should also be investigated.
the development of similar alarm problems in the future.
Responsibilities of Detector Owners and
Installers
Effects of Other Systems on Alarm System
In checking for the effects of other systems on the alarm
system wiring the Alarm Log may be very valuable in help-
ing to pinpoint relationships among apparently causeless
alarms. One important fact that can be obtained from an
Alarm Log is the beginning date for a rash of apparently
causeless alarms that may or may not be grouped around
one particular zone. The sudden onset of such a group of
alarms may result when an addition or change in the alarm
system or in another electrical or electromechanical system
in the building affects the detectors or the alarm system
circuitry.
The owners of smoke detector-equipped fire alarm systems
are responsible for maintaining the integrity of the detec-
tion system. This can be accomplished by:
• Maintaining an Alarm Log and training appropriate
personnel to properly maintain the system as
described above in the section titled What To Do When
Unwanted Alarms Occur.
• Maintaining a Detector Maintenance Log that records
inspection, testing and cleaning data for each detector
in the system. (Refer to Section 6 of this manual –
Testing, Maintenance and Service of Detectors for
information on recommended testing and maintenance
intervals and procedures, and a sample Detector
Maintenance Log page.)
• Maintaining a complete file of information on the
alarm system in a readily accessible location. This file
should include specifications and installation instruc-
tions for the detectors, control panel, and auxiliary
devices, wiring diagrams and wire location informa-
tion, and the manufacturer’s recommendations for iso-
lating the detection system wiring from other electrical
wiring to prevent interference and unwanted alarms.
• Making certain that maintenance personnel or con-
tractors working on the building’s electrical systems
are given copies of the alarm system wiring layout and
locations so that potential interference from other
wiring systems can be prevented by proper insulation
and spacing during installation.
Systems that can affect the alarm system include: other
security systems; walkie-talkie; mobile telephones; heat-
ing, ventilating, and air conditioning controls; elevator call
systems; remote control equipment (door closers, etc.);
and even the installation of microwave antenna. If the
alarm pattern supports the possibility of some kind of
interference with a fairly definite initiation date, all equip-
ment changes made in the building immediately prior to or
concurrent with the beginning of the development of the
alarm pattern should be reviewed. In addition, the wiring
layouts of the alarm system and any recent building or sys-
tem modifications should be compared to make sure that
the spacing and/or shielding required to protect the alarm
system wiring from other potentially interfering electrical
systems was maintained.
Miscellaneous Causes of Unwanted Alarms
Isolated alarm causes such as a maintenance person acci-
dentally triggering an alarm by touching a detector with a
magnetic screwdriver can be ignored, except to periodical-
ly remind maintenance personnel to be careful when work-
ing around detectors.
• Keeping accurate records of installation and modifica-
tions to all other building electromechanical systems
that could cause interference with the alarm system,
including updating schematics, wiring layouts, and
wiring location information whenever changes are
made, so that problems can be promptly found and
eliminated.
Steps should also be taken to protect detectors from dust
whenever maintenance requires sawing, sanding, drilling,
• Making a record of everything done during investiga-
tion of a series of alarms, indicating a problem exists.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
A
P
P
L
I
C
A
T
I
O
N
S
G
U
I
D
E
:
S
Y
S
T
E
M
S
M
O
K
E
D
E
T
E
C
T
O
R
S
If assistance must be sought from the installer or man-
ufacturer, there will be an indication of the tests that
have already been done by the owner’s personnel.
• Helping the owner set up appropriate Detector
Maintenance and Alarm Logs for the system.
• Providing initial instruction and training to the
owner’s personnel or outside organization which will
be monitoring and maintaining the system.
• Providing troubleshooting assistance if nuisance alarm
problems cannot be solved satisfactorily by the
owner’s personnel or outside organization.
These services can be provided by qualified outside
organizations.
The installers of smoke detector equipped alarm systems
are responsible for providing the owners with the neces-
sary information and training so that their personnel can
maintain the integrity of the alarm system. These respon-
sibilities should include:
• Providing copies of the specifications and installation
instructions for the detectors, control panel, and auxil-
iary devices; wiring diagrams and wire location infor-
mation; and the manufacturer’s recommendations for
isolating the detection system wiring from other elec-
trical wiring to prevent interference and unwanted
alarms.
Where to Get Help if the Source of Unwanted
Alarms Can’t be Found
In the event a series of unexplained unwanted alarms
and/or a review of the Alarm Log indicates that a problem
situation exists, the owner should conduct the initial inves-
tigation to find a solution. If the owner’s personnel are
unable to determine the cause for the alarms, the installer
or representative of the manufacturer should be contacted
to help pinpoint the problem.
• Verifying that the alarm system installation meets all
applicable code requirements.
• Completely testing a newly installed, expanded, or
modified alarm system to ensure that all components
are working properly.
• Providing troubleshooting assistance to the owners for
a specified break-in period after installation in case
problems develop.
Manufacturers can be contacted by phone for additional
suggestions. If factory assistance is needed, a factory engi-
neer may be able to explain the source of the problem with
data from your Alarm Log, complete description of your
alarm system including detector model numbers, make and
model number of the control panel and other components,
and a complete summary of all aspects of the problem that
have already been checked.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
S
Y
S
T
E
M
S
E
N
S
O
R
Appendix 1
Addressable System Smoke End of Line Relay
Detector Device used to supervise power (for four-wire smoke
System smoke detectors, detectors) and installed after the last device on the loop.
Glossary of Terms
which, in addition to providing alarm and trouble indica-
tions to a control unit, are capable of communicating a
unique identification (address).
False Alarms
An unwanted alarm caused by non-smoke contaminants
such as dust or insects.
Air Sampling-type Detector
Fire
A sampling-type detector consists of piping or tubing distri-
bution from the detector unit to the area(s) to be protected.
An air pump draws air from the protected area back to the
detector through the air sampling ports and piping or tub-
ing. At the detector, the air is analyzed for fire particulate.
A chemical reaction between oxygen and a combustible
material where rapid oxidation results in the release of
heat, light, flame and/or smoke.
Flame Detector
A device that detects the infrared, ultraviolet, or visible
radiation produced by a fire.
Alarm (Signal) Notification Appliance
An electromechanical appliance that converts energy into
audible or visible signal for perception as an alarm signal.
Four-wire Smoke Detector
A smoke detector which initiates an alarm condition on
two separate wires (initiating loop) apart from the two
power leads.
Alarm Signal
A signal indicating an emergency requiring immediate
action, such as an alarm for fire from a manual box, a
waterflow alarm, or an alarm from an automatic fire alarm
system, or other emergency signal.
Heat Detector
A device that detects abnormally high temperature or rate-
of-temperature rise.
Alarm Verification Feature
Initiating Circuit
A feature of automatic fire detection and alarm systems to
reduce unwanted alarms, wherein automatic fire detectors
must report alarm conditions for a minimum period of time
or confirm alarm conditions within a given time period,
after being reset, to be accepted as a valid alarm initiation
signal.
A circuit which transmits an alarm signal initiated manu-
ally or automatically, such as a fire alarm box, smoke, heat,
or flame sensing device, sprinkler waterflow alarm switch
or similar device or equipment to a control panel or any
similar device or equipment which, when activated, caus-
es an alarm to be indicated or retransmitted. An Initiating
Device Circuit (Loop) is a circuit to which automatic or
manual signal initiating devices are connected where the
signal received does not identify the individual device
Annunciation
A visible and/or audible indication of system status.
Automatic Fire Alarm System
A system of controls, initiating devices and alarm signals in operated.
which all or some of the initiating circuits are activated by
Initiating Device
Any manually operated or automatically operated equip-
ment which, when activated, initiates an alarm through an
automatic devices such as smoke detectors.
Class A Circuit (Loop)
An arrangement of supervised initiating device, signaling alarm signaling device.
line, or indicating appliance circuits that prevents a single
Intelligent (Analog, Smart) System Smoke Detector
open or ground on the installation wiring of these circuits
from causing loss of the system’s intended function.
A system smoke detector capable of communicating infor-
mation about smoke conditions at its location to a control
unit. This type of detector typically communicates a
Class B Circuit (Loop)
An arrangement of supervised initiating device, signaling unique identification (address) along with an analog (data)
line, or indicating appliance circuits, which does not pre- signal, which indicates the level of smoke at its location.
vent a single open or ground on the installation wiring of
these circuits from causing loss of the system’s intended
An ionization smoke detector has a small amount of
function.
Ionization Smoke Detector
radioactive material that ionizes the air in the sensing
Combination Smoke Detector
chamber, thus rendering it conductive and permitting a
A smoke detector that combines two or more smoke or fire current to flow between two charged electrodes. This gives
sensing technologies.
the sensing chamber an effective electrical conductance.
When particles of combustion enter the ionization area,
they decrease the conductance of the air by attaching
themselves to the ions, causing a reduction in mobility.
When the conductance is less than a predetermined level,
the detector responds in a fire alarm condition.
Detector Coverage
The recommended maximum distance between adjacent
detectors or the area that a detector is designated to protect.
Drift Compensation
The capability of a detector to automatically adjust its
alarm sensitivity to compensate for any changes over time
in the factory settings for smoke and/or fire detection. In
analog systems, this may be done by the panel.
Light Scattering
The action of light being reflected and/or refracted by
smoke particles for detection by a photoelectric smoke
detector. The action of light being refracted or reflected.
End of Line
Listed
A device such as a resistor or diode placed at the end of a
Class B wire loop to maintain supervision.
Equipment or materials included in a list published by an
organization (e.g., Underwriters Laboratories) acceptable
to the “authority having jurisdiction” and concerned with
17
Download from Www.Somanuals.com. All Manuals Search And Download.
A
P
P
L
I
C
A
T
I
O
N
S
G
U
I
D
E
:
S
Y
S
T
E
M
S
M
O
K
E
D
E
T
E
C
T
O
R
S
product evaluation, that maintains periodic inspection of Smoothing Algorithms
listed equipment or materials and whose listing states A method of “smoothing out” a detector’s interpretation of
either that the equipment or material meets appropriate sudden, short-duration increases in obscuration within the
standards or has been tested and found suitable for use in sensing chamber, intended to reduce the occurrence of nui-
a specified manner.
sance alarms.
Note: The means for identifying listed equipment may vary
for each organization concerned with product evaluation,
some of which do not recognize equipment as listed unless
it is also labeled.
Spot (Point) Detector
A device whose detecting element is concentrated at a par-
ticular location. Typical examples are bimetallic detectors,
fusible alloy detectors, certain pneumatic rate-of-rise detec-
tors, most smoke detectors and thermoelectric detectors.
Maintenance Condition
Method of providing annunciation of a smoke detector that
it is out of its listed sensitivity range.
Stratification
An effect that occurs when air containing smoke particles
or gaseous combustion products is heated by smoldering
or burning material and, becoming less dense than the sur-
rounding cooler air, rises until it reaches a level at which
there is no longer a difference in temperature between it
and the surrounding air. Stratification can also be caused
by forced ventilation.
National Fire Protection Association (NFPA)
An organization that administers the development and
publishing of codes, standards, and other materials con-
cerning all phases of fire safety.
Nuisance Alarm
An unwanted alarm caused by smoke from cooking or cig-
arettes.
Trouble Supervision
The ability of a fire alarm control unit (FACU) to detect a
fault condition in the installation wiring, which would pre-
vent normal operation of the fire alarm system.
Obscuration
A reduction in the atmospheric transparency caused by
smoke usually expressed in percent per foot.
Thermal Lag
Particles of Combustion
When a fixed temperature device operates, the temperature
of the surrounding air will always be higher than the oper-
ating temperature of the device itself. This difference
between the operating temperature of the device and the
actual air temperature is commonly spoken of as thermal
lag, and is proportional to the rate at which the tempera-
ture is rising.
Substances (products that either remain at the site of burn-
ing such as ash, or scatter as volatile products) resulting
from the chemical process of a fire.
Photoelectric Smoke Detector
In a photoelectric light scattering smoke detector, a light
source and a photosensitive sensor are so arranged that the
rays from the light source do not normally fall on the pho-
tosensitive sensor. When smoke particles enter the light
path, some of the light is scattered by reflection and refrac-
tion onto the sensor, causing the detector to respond.
Two-wire Compatibility
Per NFPA 72, 1999 edition: “All fire detection devices that
receive their power from the initiating device circuit or use
a signaling line circuit of a fire alarm control unit shall be
listed for use with the control unit.”
Projected Beam Smoke Detector
In a projected beam detector the amount of light transmit-
ted between a light source and a photosensitive sensor is
monitored. When smoke particles are introduced into the
light path, some of the light is scattered and some
absorbed, thereby reducing the light reaching the receiver,
causing the detector to respond.
Two-wire Smoke Detector
A smoke detector which initiates an alarm condition on the
same two wires that also supply power to the detector.
Unwanted Alarm
Any false alarm or nuisance alarm.
Wireless Smoke Detector
Rate-of-rise Heat Detector
A smoke detector which contains an internal battery or
batteries that supply power to both the smoke detector and
integral radio frequency transmitter. The internal power
source is supervised and degradation of the power source
is communicated to the control panel. On stimuli, the
detector transmits a radio signal to a repeater or Fire Alarm
Control Unit (FACU) that in turn generates a signal or sta-
tus condition.
A device which will respond when the temperature rises at
a rate exceeding a predetermined amount, usually 15° per
minute.
Remote Maintenance Condition
NFPA 72 listed method of providing annunciation at the
control unit that the smoke detector is outside of its listed
sensitivity.
Smoke Detector
A device that detects the visible or invisible particles of
combustion.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
S
Y
S
T
E
M
S
E
N
S
O
R
Appendix 2
Fire Alarm Log
Customer Name:
Installation Date:
Installing Contractor:
Inspection and Test Date:
Inspection and Test Performed By:
Check one
Fire
Location
Action Taken By
Name and Date
Date
Time
Recorded By
Trouble
(Bldg, Zone, Det #)
Probable Cause
Action Taken
19
Download from Www.Somanuals.com. All Manuals Search And Download.
©2002 System Sensor. The company reserves the right to change specifications at any time.
A05-1003-002
Download from Www.Somanuals.com. All Manuals Search And Download.
|