System Sensor Smoke Alarm 2100D User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS  
2100D and 2100TD Photoelectronic  
Smoke Detectors  
A Division of Pittway  
3825 Ohio Avenue, St. Charles, Illinois 60174  
1-800-SENSOR2, FAX: 630-377-6495  
Specifications  
Diameter:  
5.5 inches (140 mm)  
Height (including mounting bracket):  
Weight:  
1.7 inches (43 mm)  
5.3 oz. (150 g)  
Operating Temperature Range:  
Model 2100D: 32° to 120°F (0° to 50°C)  
Model 2100TD: 32° to 100°F (0° to 39°C)  
Operating Humidity Range:  
Latching Alarm:  
10% to 93% Relative Humidity, Noncondensing  
Reset by momentary power interruption  
Heat Sensor (Model 2100TD only):  
Electrical Ratings  
135°F Fixed Temperature Electronic Thermistor  
System Voltage –  
Nominal:  
Minimum:  
Maximum:  
12 or 24 VDC  
8.5 VDC  
35 VDC  
Maximum Ripple Voltage:  
Start-up Capacitance:  
Standby Current:  
30% of nom. Voltage (peak to peak)  
0.02 µF maximum  
50 µA maximum  
Alarm Ratings:  
4.2 VDC minimum at 10 mA.  
6.6 VDC maximum at 100 mA.  
(Alarm current must be limited to 100 mA maximum by the control panel. If  
used, the RA400Z Remote Annunciator operates within the specified detector  
alarm currents.)  
Reset Voltage:  
Reset Time:  
2.5 VDC minimum  
0.3 seconds maximum  
Start-up Time:  
30 seconds maximum (after 60 second reset)  
Before Installing  
Please thoroughly read System Sensor manual I56-407, Installation of these detectors is simplified by the use of a  
Guide for Proper Use of System Smoke Detectors, which mounting bracket and a plug-in screw terminal block that  
provides detailed information on detector spacing, place- can be prewired to the system, allowing the detector to be  
ment, zoning, wiring, and special applications. Copies of easily installed or removed for cleaning. The detector’s  
this manual are available at no charge from System Sensor. sensitivity can be tested in place using the MOD400R Test  
Module. An LED on the detector provides a local visual  
NOTICE: This manual should be left with the owner/user indication of the detector’s status. If power is applied to  
of this equipment.  
the detector, and it is functioning normally in standby, the  
status LED blinks every ten seconds. The LED also latches  
IMPORTANT: This detector must be tested and maintained on in alarm.  
regularly following NFPA 72 requirements. The detector  
should be cleaned at least once a year.  
Models 2100D and 2100TD feature a visual indication that  
maintenance is required – if the sensing chamber drifts out  
of its sensitivity limits, the LED ceases to blink.  
General Description  
Model 2100D is a 2-wire photoelectronic smoke detector  
that uses a state-of-the-art optical sensing chamber. This The detectors also include an output that allows an optional  
detector is designed to provide open area protection and Model RA400Z Remote Annunciator to be connected.  
to be used with compatible UL-listed panels only. Model  
2100TD features a restorable, built-in, fixed-temperature  
(135°F) thermal detector.  
D200-54-00  
1
I56-710-09  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 3. Wiring diagram for the 2100D and 2100TD detector:  
+
EOL RESISTOR  
SPECIFIED BY  
PANEL  
INITIATING  
LOOP  
MANUFACTURER  
+
+
+
+
+
+
+
UL LISTED  
COMPATIBLE  
CONTROL  
PANEL  
+
RA400Z  
REMOTE  
ANNUNCIATOR  
RA400Z  
REMOTE  
ANNUNCIATOR  
OPTIONAL CLASS A WIRING  
A78-2331-02  
or analog voltmeter to check the detector sensitivity as  
described in the test module’s manual.  
C. Smoke Entry Test  
CAUTION  
Dust covers are an effective way to limit the entry of dust  
into smoke detector sensing chambers. However, they may  
not completely prevent airborne dust particles from en-  
tering the detector. Therefore, System Sensor recommends  
the removal of detectors before beginning construction or  
other dust producing activity. Be sure to remove dust covers  
from any sensors that were left in place during construction  
as part of returning the system to service.  
Hold a smoldering punk stick or cotton wick at the side  
of the detector and gently blow smoke through the de-  
tector until the unit alarms.  
D. Direct Heat Method (Model 2100TD only – Hair dryer of  
1000-1500 watts).  
Direct the heat toward either of the side thermistors.  
Hold the heat source about 12 inches from the detector  
in order to avoid damage to the plastic. The detector will  
reset only after it has had sufficient time to cool and the  
power source has been momentarily interrupted.  
Both smoke and heat detection testing are recommended  
for verifying system protection capability.  
Testing  
NOTE: Before testing, notify the proper authorities that the  
smoke detector system is undergoing maintenance  
and will temporarily be out of service. Disable the  
zone or system undergoing maintenance to prevent  
unwanted alarms.  
Detectors must be tested after installation and following  
periodic maintenance. Test the 2100D as follows:  
A. Test Switch  
A detector that fails to activate with any of the above tests  
should first be cleaned as outlined in the MAINTENANCE  
section which follows. If the detector still fails to activate, it  
should be returned for repair.  
1. A recessed test switch is located on the detector hous-  
ing (See Figure 4).  
2. Push and hold the recessed test switch with a 0.18  
inch maximum diameter tool such as an allen wrench  
or small screwdriver.  
Notify the proper authorities the system is back on line.  
Maintenance  
NOTE: Before removing the detector, notify the proper  
authorities that the smoke detector system is un-  
dergoing maintenance and will temporarily be out  
of service. Disable the zone or system undergoing  
maintenance to prevent unwanted alarms.  
3. The detector’s LED should light within 5 seconds.  
B. Test Module (System Sensor Model No. MOD400R).  
The MOD400R test module can be used with a DMM  
Figure 4. Top and side views showing position of test switch:  
LED  
TEST MODULE  
SOCKET  
PUSH RECESSED  
SWITCH WITH A  
RECESSED TEST  
SWITCH  
0.18MAX. DIAMETER TOOL  
D200-54-00  
3
I56-710-09  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: (Model 2100TD only) Before removing the de-  
tector cover, note the position of the thermistors.  
Make sure the thermistors are not bent over when  
the housing is replaced.  
Gently press the housing until it locks in place. Check  
to make sure that the thermistors are in the upright po-  
sition (2100TD).  
9. Reinstall the detector.  
1. Remove detector housing by gently prying the four hous- 10. Notify the proper authorities the system is back in op-  
ing tabs on the bottom of the base with a small-bladed  
screwdriver and pull the housing from the base. Use cau-  
tion to avoid damaging the thermistors (2100TD only).  
2. Vacuum the screen carefully without removing it.  
3. Remove screen assembly, pulling straight out (see Figure  
5).  
eration.  
Figure 5. Removal of cover and screen for cleaning:  
REMOVABLE  
HOUSING  
4. Remove the sensing chamber cover.  
5. Clean the sensing chamber by vacuuming or blowing out  
dust and particles.  
REMOVABLE  
SCREEN  
6. Replace the sensing chamber cover, aligning the arrow  
on the cover top with the arrow on the printed circuit  
board.  
7. Replace the screen by placing the screen assembly over  
the sensing chamber cover and twisting until it snaps  
into place.  
SENSING CHAMBER  
COVER  
SENSING  
CHAMBER  
8. Replace the housing by aligning the three triangular  
slots on the base with their counterparts on the housing.  
BASE  
A78-2565-02  
WARNING  
The Limitations of Property Protection Smoke Detectors  
This smoke detector is designed to activate and initiate emergency ac-  
tion, but will do so only when it is used in conjunction with an authorized  
fire alarm system. This detector must be installed in accordance with  
NFPA standard 72.  
Smoke detectors will not work without power. AC or DC powered  
smoke detectors will not work if the power supply is cut off.  
pability but they are somewhat better at detecting fast flaming fires than  
slow smoldering fires. Photoelectric detectors sense smoldering fires bet-  
ter than flaming fires which have little, if any, visible smoke. Because fires  
develop in different ways and are often unpredictable in their growth, nei-  
ther type of detector is always best, and a given detector may not always  
provide early warning of a specific type of fire.  
Smoke detectors will not sense fires which start where smoke does  
not reach the detectors. Smoldering fires typically do not generate a lot  
of heat which is needed to drive the smoke up to the ceiling where the  
smoke detector is usually located. For this reason, there may be large de-  
lays in detecting a smoldering fire with either an ionization type detector  
or a photoelectric type detector. Either one of them may alarm only after  
flaming has initiated which will generate the heat needed to drive the  
smoke to the ceiling.  
Smoke from fires in chimneys, in walls, on roofs or on the other side of a  
closed door(s) may not reach the smoke detector and alarm it. A detector  
cannot detect a fire developing on another level of a building quickly or  
at all. For these reasons, detectors shall be located on every level and in  
every bedroom within a building.  
In general, detectors cannot be expected to provide warnings for fires  
resulting from inadequate fire protection practices, violent explosions,  
escaping gases which ignite, improper storage of flammable liquids like  
cleaning solvents which ignite, other similar safety hazards, arson, smok-  
ing in bed, children playing with matches or lighters, etc. Smoke detectors  
used in high air velocity conditions may have a delay in alarm due to  
dilution of smoke densities created by frequent and rapid air exchanges.  
Additionally, high air velocity environments may create increased dust  
contamination, demanding more frequent maintenance.  
To keep your equipment in excellent working order, ongoing maintenance  
is required per the manufacturer’s recommendations and UL and NFPA  
standards. At a minimum, the requirements of Chapter 7 of NFPA 72, the  
National Fire Alarm Code, shall be followed. A preventative maintenance  
agreement should be arranged through the local manufacturer’s represent-  
ative. Though smoke detectors are designed for long life, they may fail at  
any time. Any smoke detector, fire alarm equipment, or any component of  
that system which fails shall be repaired or replaced as soon as possible.  
Smoke detectors have sensing limitations, too. Ionization detectors and  
photoelectric detectors are required to pass fire tests of the flaming and  
smoldering type. This is to ensure that both can detect a wide range of  
types of fires. Ionization detectors offer a broad range of fire sensing ca-  
Three-Year Limited Warranty  
System Sensor warrants its enclosed smoke detector to be free from de-  
fects in materials and workmanship under normal use and service for a  
period of three years from date of manufacture. System Sensor makes no  
other express warranty for this smoke detector. No agent, representative,  
dealer, or employee of the Company has the authority to increase or alter  
the obligations or limitations of this Warranty. The Company’s obliga-  
tion of this Warranty shall be limited to the repair or replacement of any  
part of the smoke detector which is found to be defective in materials or  
workmanship under normal use and service during the three year period  
commencing with the date of manufacture. After phoning System Sensor’s  
toll free number 800-SENSOR2 (736-7672) for a Return Authorization  
number, send defective units postage prepaid to: System Sensor, Repair  
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174.  
Please include a note describing the malfunction and suspected cause  
of failure. The Company shall not be obligated to repair or replace units  
which are found to be defective because of damage, unreasonable use,  
modifications, or alterations occurring after the date of manufacture. In no  
case shall the Company be liable for any consequential or incidental dam-  
ages for breach of this or any other Warranty, expressed or implied what-  
soever, even if the loss or damage is caused by the Company’s negligence  
or fault. Some states do not allow the exclusion or limitation of incidental  
or consequential damages, so the above limitation or exclusion may not  
apply to you. This Warranty gives you specific legal rights, and you may  
also have other rights which vary from state to state.  
D200-54-00  
4
I56-710-09  
© System Sensor 1997  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Snapper Snow Blower 1690771 User Manual
Sony Camera Lens HG0737X User Manual
Sony Car Stereo System CDX GT20W User Manual
Sony Computer Drive PEGA UC50 User Manual
Sony Cordless Telephone SPP ID970 User Manual
Spectra Laser Level LL300 User Manual
Subaru Automobile Premium Outback Sport User Manual
Sunbeam Mixer 2556 User Manual
SUPER MICRO Computer Server H8QM8 2 User Manual
Targus Computer Drive 400 0084 001A User Manual