Sub Zero Blower 808331 User Manual

Page 1  
MODEL 808331  
IN-LINE BLOWER  
For use with models CTWH30, CTWH36, IH4227,  
W302418, W302718, W362210-482210  
READ AND SAVE THESE INSTRUCTIONS  
!
!
FOR DOMESTIC COOKING ONLY  
WARNING  
WARNING  
TO REDUCETHE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY  
TO PERSONS, OBSERVE THE FOLLOWING:  
4. Use an extinguisher ONLY if:  
A. You know you have a Class ABC extinguisher and you already  
1. Use this unit only in the manner intended by the manufacturer. If  
know how to operate it.  
you have questions, contact the manufacturer or your distributor.  
B. The fire is small and contained in the area where it started.  
C. The fire department is being called.  
D. You can fight the fire with your back to an exit.  
* Based on “Kitchen Fire Safety Tips” published by NFPA.  
2. Before servicing or cleaning unit, switch power off at service panel  
and lock the service disconnecting means to prevent power from  
being switched on accidentally.When the service disconnecting  
means cannot be locked, securely fasten a prominent warning  
device, such as a tag, to the service panel.  
3. Installation work and electrical wiring must be done by a qualified  
person(s) in accordance with all applicable codes and standards,  
including fire-rated construction codes and standards.  
4. Sufficient air is needed for proper combustion and exhausting of  
gases through the flue (chimney) of fuel burning equipment to pre-  
vent backdrafting. Follow the heating equipment manufacturer’s  
guideline and safety standards such as those published by the  
National Fire Protection Association (NFPA), and the American  
Society for Heating, Refrigeration andAir Conditioning Engineers  
(ASHRAE), and the local code authorities.  
!
CAUTION  
1. For general ventilating use only.Do not use to exhaust hazardous  
or explosive materials and vapors.  
2. To avoid motor bearing damage and noisy and/or unbalanced  
impellers, keep drywall spray, construction dust, etc. off power  
unit.  
3. If ventilator is installed in an unconditioned space (such  
as an attic): Surround the ventilator with thermal insulation - to  
minimize possible condensation.  
5. When cutting or drilling into wall or ceiling, do not damage electri-  
4. Please read specification label on product for further information  
cal wiring and other hidden utilities.  
and requirements.  
6. Ducted fans must always be vented to the outdoors.  
7. To reduce the risk of fire, use only steel ductwork.  
8. If this unit is to be installed over a tub or shower, it must be marked  
as appropriate for the application and be connected to a GFCI  
(Ground Fault Interrupter) - protected branch circuit.  
TABLE OF CONTENTS  
This manual is divided into sections as follows:  
9. Never place a switch where it can be reached from a tub or  
shower.  
“TYPICAL INSTALLATION”  
This section shows a common installation.  
- Mounting (New Frame Construction)  
- Mounting (Existing Frame Construction)  
- Mounting Using Hanger Kit (included)  
- Ducting (Horizontal blower discharge)  
- Wiring  
10. This unit must be grounded.  
TO REDUCE THE RISK OF A RANGE TOP GREASE FIRE:  
1. Never leave surface units unattended at high settings. Boilovers  
cause smoking and greasy spillovers that may ignite. Heat oils  
slowly on low or medium settings.  
2. Always turn hood ON when cooking at high heat or when flambe-  
ing food (i.e. Crepes Suzette, Cherries Jubilee, Peppercorn Beef  
Flambe’).  
“MOUNTING OPTIONS”  
“WIRING PLATE POSITION”  
3. Clean ventilating fans frequently. Grease should not be allowed  
to accumulate on fan or filter.  
“DUCTING OPTIONS”  
4. Use proper pan size. Always use cookware appropriate for the  
size of the surface element.  
TO REDUCETHE RISK OF INJURYTO PERSONS INTHE EVENT  
OFA RANGETOP GREASE FIRE, OBSERVETHE FOLLOWING:*  
1. SMOTHER FLAMES with a close-fitting lid, cookie sheet, or  
metal tray, then turn off the burner. BE CAREFUL TO PREVENT  
BURNS.If the flames do not go out immediately, EVACUATEAND  
CALL THE FIRE DEPARTMENT.  
- Blower Discharge Positions  
- Ducting (Vertical blower discharge)  
ATTACH POWER CORD TO HOOD”  
“USE AND CARE”  
2. NEVER PICK UP A FLAMING PAN - You may be burned.  
Installer: Leave this manual with  
the homeowner.  
3. DO NOT USEWATER, including wet dishcloths or towels - violent  
steam explosion will result.  
Homeowner: Use and Care  
information on page 4.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 3  
WIRING  
WIRING PLATE POSITION  
BLACK  
TO  
TOP / BACK  
OF HOUSING  
BLACK  
VERTICAL  
POWER CABLE  
CONNECTION  
GROUND TO  
WIRING PLATE  
WIRING  
PLATE  
HORIZONTAL POWER  
CABLE CONNECTION  
120 VAC  
LINE IN  
(from  
WHITE  
TO  
WHITE  
Wiring plate mounts to side or top of housing.  
range  
hood)  
Ventilator can be wired from outside of housing.  
Use UL approved connectors to wire per local codes.  
DUCTING OPTIONS  
MOUNTING OPTIONS  
BLOWER DISCHARGE POSITIONS  
¼-20 hex nuts secure mounting brackets to housing. Loosen and  
re-tighten or remove and replace nuts as necessary for desired  
mounting bracket position.  
DUCT CONNECTOR  
DUCT CONNECTOR  
1½"  
to  
2½"  
11/8  
MAX.  
"
Change  
blower  
& duct  
21½"  
21½"  
connector  
positions  
for vertical  
discharge.  
Mounting brackets in  
Mounting brackets flipped  
factory-shipped position. over and mounted to outlet  
(Outlet parallel to joists.)  
sides of housing.  
(New construction)  
(Outlet parallel to joists.)  
(Existing construction)  
BLOWER  
BLOWER  
11/2  
to  
"
Blower and duct connec-  
tor in horizontal discharge  
position. (Factory shipped)  
Blower and duct connec-  
tor in vertical discharge  
position.  
21/2  
"
12¼"  
21½"  
Mounting brackets mounted  
to outlet sides of housing.  
(Outlet perpendicular to joists.)  
(New construction)  
Mounting brackets flipped  
over to give approx. 1”  
DUCTING (Vertical blower discharge)  
more clearance.  
(Outlet parallel to joists.)  
(New construction)  
ROOF CAP  
4½” X 18½”  
10”  
10 3/4" to  
11 3/4"  
91/2" to  
TO 10” ROUND  
ROUND  
101/2  
"
TRANSITION  
DUCT  
21½"  
21½"  
Mounting brackets flipped  
Mounting brackets mounted  
over and mounted to top of  
to top of sides of housing.  
(Outlet parallel to joists.)  
sides of housing.  
(Outlet parallel to joists.)  
(New or existing construction)  
(New or existing construction)  
Typical ductwork connection to a ventilator converted to  
vertical discharge.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 4  
ATTACH POWER CORD TO  
HOOD  
Follow wiring instructions packed with range hood, and adhere to  
all local and state codes, and the National Electrical Code.  
USE AND CARE  
To clean blower assembly: Remove access panel, unplug blower  
from housing, remove blower mounting nuts, and carefully remove  
blower from housing. Use appropriate vacuum attachment or a soft  
cloth and mild soap or detergent to clean blower discharge area and  
wheel. DO NOT ALLOW WATER TO ENTER MOTOR. Make sure  
blower assembly is completely dry before reinstalling.  
WARNING: To reduce the risk of electric shock,  
disconnect from power supply before servicing.  
Motor is permanently lubricated. Do not oil or disassemble motor.  
Some hoods require the use of a separate power cord and strain  
relief bushing (included), for proper wiring of in-line blowers. Please  
refer to the hood manual for proper installation instructions.  
99043889B  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 1  
MODEL 808332  
IN-LINE BLOWER  
For use with models CTWH30, CTWH36, IH4227, DD30R, DD36R, DD45R,  
W30-662418, W30-662718, L28-582212, I36-663418  
READ AND SAVE THESE INSTRUCTIONS  
!
!
FOR DOMESTIC COOKING ONLY  
WARNING  
WARNING  
TO REDUCETHE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY  
TO PERSONS, OBSERVE THE FOLLOWING:  
4. Use an extinguisher ONLY if:  
A. You know you have a Class ABC extinguisher and you already  
1. Use this unit only in the manner intended by the manufacturer. If  
know how to operate it.  
you have questions, contact the manufacturer or your distributor.  
B. The fire is small and contained in the area where it started.  
C. The fire department is being called.  
D. You can fight the fire with your back to an exit.  
* Based on “Kitchen Fire Safety Tips” published by NFPA.  
2. Before servicing or cleaning unit, switch power off at service panel  
and lock the service disconnecting means to prevent power from  
being switched on accidentally.When the service disconnecting  
means cannot be locked, securely fasten a prominent warning  
device, such as a tag, to the service panel.  
3. Installation work and electrical wiring must be done by a qualified  
person(s) in accordance with all applicable codes and standards,  
including fire-rated construction codes and standards.  
4. Sufficient air is needed for proper combustion and exhausting of  
gases through the flue (chimney) of fuel burning equipment to pre-  
vent backdrafting. Follow the heating equipment manufacturer’s  
guideline and safety standards such as those published by the  
National Fire Protection Association (NFPA), and the American  
Society for Heating, Refrigeration andAir Conditioning Engineers  
(ASHRAE), and the local code authorities.  
!
CAUTION  
1. For general ventilating use only.Do not use to exhaust hazardous  
or explosive materials and vapors.  
2. To avoid motor bearing damage and noisy and/or unbalanced  
impellers, keep drywall spray, construction dust, etc. off power  
unit.  
3. If ventilator is installed in an unconditioned space (such  
as an attic): Surround the ventilator with thermal insulation - to  
minimize possible condensation.  
5. When cutting or drilling into wall or ceiling, do not damage electri-  
4. Please read specification label on product for further information  
cal wiring and other hidden utilities.  
and requirements.  
6. Ducted fans must always be vented to the outdoors.  
7. To reduce the risk of fire, use only steel ductwork.  
8. If this unit is to be installed over a tub or shower, it must be marked  
as appropriate for the application and be connected to a GFCI  
(Ground Fault Interrupter) - protected branch circuit.  
TABLE OF CONTENTS  
This manual is divided into sections as follows:  
9. Never place a switch where it can be reached from a tub or  
“TYPICAL INSTALLATION”  
This section shows a common installation.  
- Mounting (New Frame Construction)  
- Mounting (Existing Frame Construction)  
- Mounting Using Hanger Kit (included)  
- Ducting (Horizontal blower discharge)  
- Wiring  
shower.  
10. This unit must be grounded.  
TO REDUCE THE RISK OF A RANGE TOP GREASE FIRE:  
1. Never leave surface units unattended at high settings. Boilovers  
cause smoking and greasy spillovers that may ignite. Heat oils  
slowly on low or medium settings.  
2. Always turn hood ON when cooking at high heat or when flambe-  
ing food (i.e. Crepes Suzette, Cherries Jubilee, Peppercorn Beef  
Flambe’).  
“MOUNTING OPTIONS”  
“WIRING PLATE POSITION”  
3. Clean ventilating fans frequently. Grease should not be allowed  
“DUCTING OPTIONS”  
to accumulate on fan or filter.  
- Blower Discharge Positions  
- Ducting (Vertical blower discharge)  
4. Use proper pan size. Always use cookware appropriate for the  
size of the surface element.  
TO REDUCETHE RISK OF INJURYTO PERSONS INTHE EVENT  
OFA RANGETOP GREASE FIRE, OBSERVETHE FOLLOWING:*  
ATTACH POWER CORD TO HOOD”  
“USE AND CARE”  
1. SMOTHER FLAMES with a close-fitting lid, cookie sheet, or  
metal tray, then turn off the burner. BE CAREFUL TO PREVENT  
BURNS.If the flames do not go out immediately, EVACUATEAND  
CALL THE FIRE DEPARTMENT.  
Installer: Leave this manual with  
the homeowner.  
Homeowner: Use and Care  
information on page 4.  
2. NEVER PICK UP A FLAMING PAN - You may be burned.  
3. DO NOT USEWATER, including wet dishcloths or towels - violent  
steam explosion will result.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 2  
TYPICAL INSTALLATION  
MOUNTING (New Frame Construction)  
TYPICAL INSTALLATION  
MOUNTING USING HANGER KIT (included)  
10” ROUND DUCT  
(OUTLET)  
8” X 12” TO  
10” ROUND  
TRANSITION  
(FEMALE)  
8” X 12” TO  
8” X 12” TO  
10” ROUND  
TRANSITION  
(MALE)  
HANGER  
KIT BOLT  
& WASHER  
10” ROUND  
TRANSITION  
(FEMALE)  
EXTENSION  
SPRING  
10” ROUND  
DUCT  
(INTAKE)  
HANGER  
KIT CHAIN  
10” ROUND  
DUCT (INTAKE)  
HANGER KIT  
EYE-BOLT  
GRILLE NUT  
(Install into square  
holes in housing)  
8” X 12” TO  
10” ROUND  
TRANSITION  
(MALE)  
HANGER  
KIT NUT &  
WASHER  
MOUNTING  
BRACKETS  
Ventilator  
factory-shipped  
in straight-through  
discharge position.  
CEILING  
MOUNTING  
BRACKET  
JOIST  
(24” centers  
shown)  
ACCESS  
PANEL  
SCREW  
GRILLE NUT  
(Install into  
square holes in  
housing)  
ACCESS PANEL  
10” ROUND  
DUCT  
(OUTLET)  
Factory-shipped unit installed in new construction.  
MOUNTING (Existing Frame Construction)  
ACCESS  
ACCESS  
PANEL  
PANEL SCREW  
10” ROUND  
DUCT (INTAKE)  
8” X 12” TO 10” ROUND  
TRANSITION (FEMALE)  
Blower factory-shipped in straight-through  
discharge position.  
8” X 12” TO  
10” ROUND  
TRANSITION  
(MALE)  
MOUNTING  
BRACKETS  
DUCTING (Horizontal blower discharge)  
10” ROUND  
DUCT  
ROOF CAP  
(OUTLET)  
10”  
ROUND  
MOUNTING  
SCREWS  
DUCT  
8” X 12” TO  
10” ROUND  
TRANSITION  
GRILLE NUT  
(Install into  
square  
holes in hous-  
ing)  
(MALE)  
10”  
CEILING  
JOIST  
ROUND  
DUCT  
(24” cen-  
ters  
shown)  
ACCESS  
PANEL  
Ventilator factory-shipped  
in straight-through  
ACCESS  
PANEL SCREW  
discharge position.  
WALL  
CAP  
8” X 12” TO 10” ROUND  
TRANSITION (FEMALE)  
Factory-shipped unit installed in existing construction.  
10” ROUND  
ELBOW  
Two ways to connect ductwork to a factory-shipped unit.  
IMPORTANT: Remove shipping tape from damper  
Remove the shipping tape from the damper flap and make sure that  
damper flap opens and closes freely inside the ductwork. Use duct  
tape to make ductwork connections secure and air-tight.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 3  
WIRING  
WIRING PLATE POSITION  
BLACK  
TO  
BLACK  
EDGE  
OF HOUSING  
GROUND TO  
WIRING PLATE  
VERTICAL  
POWER CABLE  
CONNECTION  
WIRING  
PLATE  
HORIZONTAL POWER  
CABLE CONNECTION  
WHITE  
TO  
WHITE  
Wiring plate mounts to side or top of housing.  
120 VAC LINE IN  
(from range hood)  
DUCTING OPTIONS  
BLOWER DISCHARGE POSITIONS  
Ventilator can be wired from outside of housing.  
Use UL approved connectors to wire per local codes.  
DUCT  
CONNECTOR  
(outlet)  
DUCT  
CONNECTOR  
(outlet)  
Housing  
MOVABLE  
PANEL  
rotated & mov-  
able panel cov-  
ers previous  
open side.  
MOUNTING OPTIONS  
¼-20 hex nuts secure mounting brackets to housing. Loosen and  
re-tighten or remove and replace nuts as necessary for desired  
mounting bracket position.  
Factory-Shipped  
Straight-Through  
11/8"  
MAX.  
MOVABLE  
PANEL  
(Change to this  
location)  
1½"  
to  
2½"  
Factory-Shipped  
Straight-Through  
Discharge  
Discharge  
DUCT  
CONNECTOR  
(intake)  
DUCT  
CONNECTOR  
(intake)  
22"  
18"  
Ventilator shown in  
straight-through discharge  
position. (Factory shipped)  
Ventilator shown in right-  
angle discharge position.  
(Change movable panel to  
new location as shown.)  
Mounting brackets in  
Mounting brackets flipped  
factory-shipped position -  
over and mounted to ad-  
mounted directly to joists.  
(Outlet parallel to joists.)  
(New construction)  
ditional framing.  
(Outlet perpendicular to joists.)  
(New or Existing construction)  
DUCTING (Vertical blower discharge)  
8” X 12” TO  
ROOF CAP  
Housing Con-  
10” ROUND  
verted to Right-  
TRANSITION  
Angle Discharge  
1½"  
to  
2½"  
10” ROUND  
DUCT  
Factory-Shipped  
Straight-Through  
Discharge  
(MALE)  
8” X 12” TO 10”  
ROUND  
TRANSITION  
(FEMALE)  
22"  
18"  
Mounting brackets flipped  
Mounting brackets flipped  
over and mounted to top of  
housing. Housing secured  
10” ROUND  
DUCT  
over and mounted to ad-  
ditional framing.  
(Outlet vertical.)  
with cables.  
(New or Existing construction)  
Typical ductwork connection to a ventilator converted to  
right-angle discharge.  
(Outlet parallel to joists.)  
(New or Existing construction)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 4  
ATTACH POWER CORD TO  
HOOD  
Follow wiring instructions packed with range hood, and adhere to  
all local and state codes, and the National Electrical Code.  
USE AND CARE  
To clean blower assembly: Remove access panel, unplug blower  
from housing, remove blower mounting nuts, and carefully remove  
blower from housing. Use appropriate vacuum attachment or a soft  
cloth and mild soap or detergent to clean blower discharge area and  
wheel. DO NOT ALLOW WATER TO ENTER MOTOR. Make sure  
blower assembly is completely dry before reinstalling.  
WARNING: To reduce the risk of electric shock,  
disconnect from power supply before servicing.  
Motor is permanently lubricated. Do not oil or disassemble motor.  
Some hoods require the use of a separate power cord and strain  
relief bushing (included), for proper wiring of in-line blowers. Please  
refer to the hood manual for proper installation instructions.  
99043890C  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Sharp MiniDisc Player MD R2 User Manual
Snapper Network Card Z Series User Manual
Sonos Speaker System PLAY3US1 User Manual
Sony Cassette Player MJ User Manual
Sony DVD Player DVP K86P User Manual
Sony Portable Speaker SA WFT7 User Manual
Steren Laptop Talking Notebook User Manual
Stiga Lawn Mower 12 1203 22 User Manual
Sylvania TV VCR Combo SSC090 User Manual
System Sensor Smoke Alarm DH500ACDC User Manual