Sterling Power Products
England Tel. 01905 453999
Fax 01905 458836
Download from Www.Somanuals.com. All Manuals Search And Download.
General:
ꢀ
“ 3 in 1” It is a powerful pure sine wave inverter, a sophisticated battery
charger that features adaptive charge technology and a high-speed AC
transfer switch in a single compact enclosure.
ꢀ
Besides all this functions ,however, the “3 in 1” has several advanced
features that provides a range of new applications as outlined bellow:
In the event of a grid failure ,or shore or generator power being
disconnected, the inverter within the “3 in 1” is automatically In less than 20
milliseconds activated and takes over supply to the connected loads.
Allowed them to continue to operate without disruption. The “3 in 1” is very
powerful battery charger. It will therefore draw a lot of current from the
generator or shore side supply.
ꢀ
ꢁ INVERTER:
ꢀ
ꢀ
ꢀ
Pure Sine Wave AC output.
Very low total harmonic distortion (< 2 % )
High surge capacity and soft-start design for heavy inductive loads such as air
conditioning
ꢀ
ꢀ
Load detection system for “power saving” mode
Extremely high efficiency.
ꢁ Battery Charger :
ꢀ
The “3 in 1” series is built around a bi-directional converter , that operates as
an inverter or as a battery charger high capacity three-stage Battery charger
Equalization mode conditions Battery for longer life
Multistage charger-power factor corrected for superior
Charging temperature sensitive charging for optional
Care of all batteries ( temperature sensor optional ) Built in solar charge
regulator.
ꢀ
ꢀ
ꢀ
ꢁ Bypass Function:
ꢀ
Automatic 60 A (3000W ) / 30 A ( 1500W ) transfer relay turns inverter and
charger on / off.
ꢀ
Fast ( UPS ) mode or delay mode of the Bypass switch.
Power sharing prevent tripping of shore power breaker.
ꢁ Basic Remote Control:
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
Power output on / off
Function mode select
Programming Battery charging voltage
Error message display
Programming auxiliary relay (x2 )
Programming input current limit for power share
Download from Www.Somanuals.com. All Manuals Search And Download.
-1-
A. General Information
Operating instructions
This manual is a part of the delivery package of every inverter-charger. It serves as
Guidelines for safe and efficient operation of the unit. The instructions are only
valid for use with the following models and accessories.
ꢁ
ꢁ
ꢁ
ꢁ
DAI-1500C-12xx / DAI-3000C-12xx
DAI-1500C-24xx / DAI-1500C-24xx
BTS-A-15 (m)
Temperature
Remote controller
RCC-A-03 (3m) / RCC-A-15 (15m)
Any personnel who install the unit and / or works with it must be fully familiar with
the contents of this manual and must follow exactly all the warnings and safety
instructions. A qualified and trained personnel must carry out installation of , or any
work on the unit . Installation and application must comply with the respective local
installations codes and safety regulations.
Download from Www.Somanuals.com. All Manuals Search And Download.
-2-
B. Warranty
During production and assembling, all Sterling Inverter / Chargers go through
many testing procedures. Every Sterling has its own serial number, which helps to
refer back to its original data in the event of controls or repairs. That is why you
should never remove the identification plate showing the serial number and must
ensure you return your warranty card as soon as possible.
The warranty period for your Sterling is 2 years.
Sterling Warranty Terms and Conditions
Sterling warrants this product against defects in material or workmanship, to the
original purchaser only for an initial period of 60 days from date of purchase, when
in normal use and service. The warranty period will be extended to a total of one (1)
year if a completed warranty card is received within 60 days of purchase. No
warranty will be provided on units which have not been paid for in full.
Some models may have the option of purchasing an extended warranty period,
see elsewhere in this manual for details. This manufacturers warranty is in addition
to your consumer rights under local trade practices act.
This warranty does not extend to products which have been opened, altered or
repaired by persons other than authorized by Sterling or to products which
become defective due to acts of God, fire, sabotage, vandalism, contaminated
fluids, negligence or failure to operate, house and maintain the product in
accordance with instructions provided in this manual. It is extremely important
that all installation instructions contained within this manual are strictly
adhered to , failure to do so will void your warranty. Except for the foregoing
expressed warranty Sterling makes no warranty, expressed or implied,
including but not limited to, the warranty of merchantability or fitness for a particular
purpose.
Sterling will repair or replace the defective product in accordance with its best
judgment, For service under warranty, , if the product is found to be defective,
within the terms of the warranty. Repair or replacement of any unit does not extend
the original warranty terms in any way.
This warranty does not cover repairs made necessary due to the product coming in
contact with dirt, abrasives, moisture, rust, corrosion, varnish or other similar, or
failure due to poor quality or poor condition batteries.
Download from Www.Somanuals.com. All Manuals Search And Download.
-3-
Sterling reserve the right with some models to supply an accredited installer with
replacement parts, this may allow the unit to become operable much quicker. In
this case Sterling are not responsible for any costs of the installer’s time or
traveling expenses. Replacement parts are sent at Sterling's discretion.
Sterling will in no way be held responsible for any losses incurred
due to the malfunctioning or failure of a product.
Suitably qualified personnel must carry out wiring, failure to do so will void
warranty.
If you have any questions about this warranty please do not hesitate
to contact us.
Caution: Even when a unit has been completely disconnected, there can
Still be deadly voltages present at the OUTPUT. To remove these voltages you
must switch the unit ON with the ON/OFF switch. After one minute the
electronics are discharged and any work can now be safely carried out.
Caution: In normal use lead-acid and lead-gel batteries give out explosive gases.
Never smoke or allow a spark or flame in the vicinity of batteries. The batteries
must always be stored or placed in a well ventilated area, they should be placed in
such a way that there is no danger of short circuiting through carelessness. Never
charge frozen batteries.
This unit is not to be used or sold for life support equipment or applications.
B.1 Special Precautions
While working on batteries there should always be a second person close to you or
within your voice range, in case help is needed.
Plenty of fresh water and soap must be ready at hand so that in case of acid
coming in contact with skin, eyes and clothes, the areas in question can be
thoroughly washed.
If acid enters the eyes, you must thoroughly wash the eyes with cold running water
for at least 15 minutes. It is recommended that you immediately consult a medical
doctor.
Baking powder neutralizes battery acid electrolyte. Always keep some at hand.
Special care must be taken when working with metal tools near or on the batteries.
With tools such as screwdrivers, spanners etc. short-circuits can result. Sparks
produced by the short-circuit can cause an explosion.
When working on batteries all personal metal items such as rings, necklaces and
bracelets must be removed. Batteries are so powerful that short-circuit with these
items can melt them and thus cause severe burns. Always follow the battery
manufacturers instructions.
Under certain conditions this unit or a connected generator can start
automatically. While working on an electrical installation you must ensure that
these appliances are disconnected before commencing any work.
Download from Www.Somanuals.com. All Manuals Search And Download.
-4-
C. Introduction
C.1 Basic schematic
This unit is a a sine wave inverter with integrated battery charger and AC Bypass
switch with many additional functions.
DC BUS
AC BUS
PV Array
Solar Controller
Bidirectional Inverter
(Inverter / Charger)
BATTERY
Home / Boat / Motohome
AC Load
C.1.1 The Inverter
The sinewave-inverter section of your Combi generates a sinewave AC voltage
with an exceptionally precise voltage and stabilized frequency, In order to start
large electric motors, the user has the possibility to employ a short-start-power
which is 3-times the nominal power of the Combi
The inverter is protected against overload and short-circuit. A power-stage with the
latest MOS-FET power transistors, a toroidal transformer, and a fast regulating
system make-up a robust and reliable inverter with very high efficiency. A load
detection system serves to provide the smallest energy consumption and ensures a
long life for the battery.
C.1.2 The Bypass switch
This unit can be connected to an AC input source. For example a stand-by motor
generator or the AC grid, such as shore power or a caravan park. With the
transfer system, on one side you have AC voltage which is used to run the load,
on the other side the batteries are being charged. The distribution of energy
between the AC loads and battery charger is automatic.
Download from Www.Somanuals.com. All Manuals Search And Download.
-5-
C.1.3 The Battery charger
The built-in battery charger is capable of charging the batteries quickly and
completely. A microprocessor controlled, 3 to 4 Step charging process ensures
the optimum charging of the batteries. The desired charging current can be set.
The battery charger can be used for lead-acid or gel batteries. Thanks to the
floating charge ability of this unit, the batteries can remain continuously connected.
C.1.4 The solar charge regulator (opetional)
With the built-in solar regulator, the unit is a complete solar-power-center. In a
solar installation this regulator ensures that the batteries are charged correctly.
With the unit, batteries can be charged with a generator and with the solar
modules at the same time. The charging of batteries with both energy sources is
carried out fully automatically.
C.1.5 Remote control
As an option, a remote control can be connected to this unit. The
remote control is supplied with a 3m long cable. This cable can be up to 15m long.
(RS-485 interface) On the remote control output current and charging current are
also shown.
C.2 Battery connections
Lead-acid batteries are normally available in blocks of 2V, 6V or 12V. In most
cases, to generate the necessary operating voltage and the capacity of the
batteries for the unit many batteries have to be connected together in parallel
and or in series. Following three examples are shown:
Download from Www.Somanuals.com. All Manuals Search And Download.
-6-
C.2.1 Parallel Connection:
C.2.2 Series Connection:
Download from Www.Somanuals.com. All Manuals Search And Download.
-7-
C.2.3 Parallel-Series Connection:
Download from Www.Somanuals.com. All Manuals Search And Download.
-8-
D. Installation
D.1 Location
The location of the Combi must be chosen by the following criteria:
Protection from unauthorized handling.
Dry dust free room, no condensation, no rodents.
Never install directly over the battery and never in a cabinet together
with the batteries.
Keep ventilation holes free. The ventilation of the Combi is designed in such a
way that it will work most efficiently when mounted vertically.
In mobile installation it is important to keep vibrations to a minimum.
D.2 Rear Panel
Connections
A Battery +/-
Battery cables.
B SOLAR +/-
C AUX1 contact
D AUX2 contact
Connections for Solar modules.
Connecting terminal for Auxiliary contact 1.
Connecting terminal for Auxiliary contact 2.
E BTS (Battery temp. sensor) Connecting terminal for Temperature sensor.
F EXT AC IN
G AC OUT
Connecting terminal for AC input.
Connecting terminal for AC output.
Download from Www.Somanuals.com. All Manuals Search And Download.
-9-
D.3 Cabling / wiring
When making connections to the unit you must ensure that all connections
are carried out in a clean and correct manner and under no circumstances that a
cable is connected to a wrong terminal.
Connecting the unit must be carried out in the following order.
D.3.1 Connection to battery
Prepare the batteries for connection. Prepare battery cables, if necessary press
on cable tabs/shoes. Connect the red cable to the Battery positive fuse/circuit
breaker and the black cable to battery Minus (-) Take care when connecting the
second cable to the battery, as a spark is produced, this is caused for a short time
due to high current flowing in the unit to charge the capacitors. This is another
reason to install a battery fuse/circuit breaker. For this reason follow strictly the
safety measures described in this manual.
DO NOT INSERT THE BATTERY FUSE AT THIS STAGE.
D.3.2 Connection to the AC OUTPUT.
The AC output must be connected to the screw terminal AC OUTPUT. For this,
use a 3-core cable with a conductor cross section of 2,5mm². Connections are
marked as follows “OUT / N”=Neutral, “GND”=Earth, “OUT / L”=Live or Active.
Caution: High voltage can be at the AC output, ensure the unit is not
connected when making AC connections.
D.3.3 Connection to the AC INPUT
The AC input supply from the electricity grid or from a generator must be
connected to the screw terminals AC INPUT. For this use a 3-core cable with a
conductor cross section of 2,5mm². Connections are marked as follows
“IN / N”=Neutral, “GND”=Earth, “IN / L”=Live or Active.
Download from Www.Somanuals.com. All Manuals Search And Download.
-10-
D.3.4 Connect the Solar modules: SOLAR IN +/-
Solar modules are connected on these terminals. Under no circumstances should
any other energy source i.e. wind generator be connected to these terminals.
Depending on the power of the modules, the cable cross section should be 2.5 up
to 6mm². Before connecting it is necessary to check with a Voltmeter that the
voltage of the Module meets the following values:
Invertek DAI -1500C -12xx / DAI - 3000C -12xx 17-25V / 30A
Invertek DAI -1500C -24xx / DAI - 3000C - 24xx 34-45V / 30A.
D.3.5 Connection to Aux1 & AUX2:
On these three terminals is a potential free change-over contact capable of
switching a maximum current and voltage of 16A/250V ac. The “ multi-display “
on the front of Combi can show the status of these contacts.
D.3.6 Connection to Remote control unit ( optional ):
The Remote control unit RCC-A is connected in the “Remote control” of front
panel with a RJ11 / 6 connector. The Remote Control can be plugged IN at any
time. Push in the connector, without forcing it, until you hear the ”click:, now the
connector is locked in place. The same applies to the plug at the Remote control
unit. The length of the cable for the Remote control should not exceed 15m, is
comes standard with 3m cable.
Download from Www.Somanuals.com. All Manuals Search And Download.
-11-
E. Operating
E.1 Front Panel Display And Operating Description
Sterling Power Products
2
1
3
4
8
10
12
6
5
7
9
11
PB1
PB2
PB3
PB4
PB5 PB7
PB6
E.2 Push buttons
Push buttons
PB1
Name
Description
RUN/STOP key
k Operation mode select key.
RUN/STOP
FUNC
PB2
PB3
AUX
Auxiliary contract (aux1, aux2) Manual / Active change. And Function
programming key
PB4
PB5
DSPL
Multi-display select key
UP(△ )
△ Increment key.
PB6
PB7
DOWN (▽ ) ▽ Decrement key.
ENTER Data write key.
Download from Www.Somanuals.com. All Manuals Search And Download.
-12-
E.3 LED INDICATOR:
LED
1
Name
AC IN
L ED ON
LED Blink
LED OFF
1. Input voltage normal, and
position ”transfer
Has input power, but
voltage or frequency is not
in the allowance range.
No input power
Voltage Level”
(150VAC~240VAC)
2. Input voltage frequency
range in between(45~60Hz)
Green : Battery charger is
working.
2
3
CHARGER
Green Blink : Battery
charger is standby.
Orange Blink : Battery
charger is disable.
--------------
SOLAR PANEL Solar module is delivering
energy.
1. Solar module
aren’t connect
or
2. Day or Night /
(cloudy day)
Solar charger is
disabled.
-----------------------------
------------------------------
4
5
6
SOLAR
CHARGER
Solar charger is working.
AC OUT
There is voltage at the “AC OUT” No voltage at the “AC
terminal.
OUT” terminal.
-------------
INVERTER
Green : Inverter is working.
Green Blink : Inverter is
standby
Orange Blink : Inverter is --------------
disable.
7
EQUALIZE
In Equalize charging
Process
Disable Equalize
charging function
------------------------------
8
9
BATTERY
BYPASS
Approx state of charge or discharge of Battery.
Green : BYPASS switch is active Green Blink :BYPASS
AC IN voltage is being sent
directly to AC OUT terminal
switch standby.
Orange Blink : BYPASS ---------------
switch disable
10 RUN/STOP
Green : Invertek turn on.
Red : Invertek turn off.
Red Blink : Auto-Restart
is in use
---------------
Download from Www.Somanuals.com. All Manuals Search And Download.
-13-
11
MULTI-DISPLAY
LED In Inverter Mode
9.1 Battery Voltage
9.2 Output Voltage
9.3 Output Frequency
9.4 AC output current
In Charger Mode
Battery Voltage
Input Voltage
Charging Phase
Battery charging current
LED 9.1
LED 9.4
LED 9.5
LED 9.6
LED 9.2
LED 9.3
Display
monitoring
values or set
values of each
parameter.
9.5 Indicator of parameter setting or modify or monitor.
9.6 Indicator of error message
:Battery under voltage trip.
:Battery over voltage trip.
:AC out overload trip.
:Heatersink overtemperature trip.
12
POWER
MONITOR
Displays the value of the output power in % of max continuous
power (in Inverter Mode) and the charge current in Amps. (in
Charger Mode) In this mode the 200% LED indicate that power
sharing is in use.
Download from Www.Somanuals.com. All Manuals Search And Download.
System Adjustments
To adjust any of the unit’s preset parameters (factory/default settings are highlighted in dark blue in each function box) the unit must be in STOP mode! Select the
function you wish to change from the list of light blue boxes below. Select the parameter in the box you wish to change. For example, if you wish to switch the power saver
function off, you find that the power saver function is attached to Fn02 (function 2) and that selection 2 means “off”. To select this desired option go to the main key pad on the
front of the unit. Push the pad marked FUNC (function) for 2 seconds and use up/down keys to scroll through the functions. (The display will show Fn00 up to Fn09.) Stop at
the function you require. (For power saver stop at Fn02.) With Fn02 on the screen push ENT (”enter”) on the keypad and use the up/down arrows to select the parameter
required. The display will show from 00 to 06 (depending on which parameter you wish to change). Then select the parameter number you wish (in this case the power saver
off function which is 2), by using the up/down keys and push the ENT key to enter that selection. After the selection has been made the display will show End and this will
complete the parameter change. Then press DSPL to return to the function heading (one level upwards). Either continue to adjusting the next function or press DSPL again to
return to the voltage display mode. The unit will also automatically return to the voltage display after about 20 seconds if left alone. Don’t forget to return to RUN mode!
Fn00
Fn01
Fn02
Fn03
Fn04
Fn05
Fn06
Fn07
Fn08
Fno9
Battery type
0= Open lead acid
1= Gel ( exide ) setting
2= Gel u.s.a setting
3= Agm sealed
low voltage cut out
0) 10.0 v
1) 10.5 v
2) 11.0 v
3) 11.5 v
4) 12.0 v
DSPL FUNC
AUX
ENT
inverter voltage
0) 200 v 50 hz
1) 220 v 50 hz
2) 230 v 50 hz
3) 240 v 50 hz
solor charger
1) on
2) off
screen example Fn09
charging current reduction
0) 25% reduction
1) 50% reduction
2) 75% reduction
3) full current
power saver mode
1) power saver on
2) power saver off
system fuctions
0) all functions normal
1) inverter off, charger and bypass on
2)charger and bypass off, inverter on
3) inverter and charger off, bypass on
input current limit setup
0) 25 % power 4 amps
1) 50% power 7 amps
2) 75% power 11 amps
3) 100% power 15 amps
aux 1 setup
aux 2 setup
0) on when charger on
1) on when charger off
2) on when inverter on
3) on when inverter off
0) on when charger on
1) on when charger off
2) on when inverter on
3) on when inverter off
Download from Www.Somanuals.com. All Manuals Search And Download.
-15-
E.7.1 The Inverter
The Inverter section of the unit produces a high quality Sinewave output, the
quality of this output is compatible with any appliance, Thanks to the generous
dimensioning of the unit , you can operate appliances requiring higher power
than the nominal power of the unit for a short time. The unit provide up to
3-times the nominal power to start motors etc.
E.7.2 Power saving function (Fn02)
In order to avoid unnecessary discharge of the battery, the inverter switches OFF
automatically if no AC power is being used. The unit switches ON
automatically again if an AC load is switched ON. The AC Out LED blinks if the
inverter is in “Power Saving-Mode”.
If the “Power Saving-Mode” is not wanted, set the Fn02 "DISABLE" function.
This will keep the unit running continuously, but will also discharge your
batteries quicker.
E.7.3 Overload
If the unit is overloaded for too long or too heavily, it switches off. The
“Multi-display” will show “
” and the “RUN/STOP” LED will RED Blink. After
approximately 10 seconds the Inverter switches on automatically. If the unit is
overloaded four times in quick succession, then it no longer switches back on
automatically. The “RUN/STOP” LED remains lit, and the multi-display show “
Press the push button 1(PB1) ”RUN/STOP” in order to switch the unit back ON.
”.
E.7.4 Overheating (Over Temp)
If the Inverter has been overload for a long time or it has been working in a high
ambient temperature, it will switch OFF. The “Multi-display” will show “
” and
the “RUN/STOP”LED RED blinks. After cooling down, the inverter switches back on
automatically. One minute before the inverter switches off due to high temperature
a buzzer will be heard. If the Auxiliary Contact has been programmed for “Over
Temp” then the contact will be active when the buzzer sounds. This could be used
for example to start an emergency back up generator, creating a no break energy
supply.
Download from Www.Somanuals.com. All Manuals Search And Download.
-16-
E.7.5 Battery Condition
Deep discharging of batteries leads to high losses in capacity and early aging.
That is why the unit will constantly monitor the battery condition. When battery
voltage gets too low the Invertek switches OFF. The multi-display will show
“
” or ”
” (Low voltage cut out P-12) the “RUN/STOP” LED RED blinks.
When the battery voltage returns to 12.1V resp..24.2V, the inverter switches ON
automatically. One minute before the Inverter switches OFF due to low voltage a
buzzer will be heard.
The low voltage is set to 11.8V resp. 23.6V. These settings are standard for
most batteries. The voltage levels are maintained by the built-in
Battery-Management-System of the Invertek which looks at the load and battery
condition and adjusts to suit.
This setting is comparable with the levels of 10.8V resp. 21.6V, which are given
for most batteries on nominal load.
Absorption Stage
Equalization Charging
Download from Www.Somanuals.com. All Manuals Search And Download.
-17-
F. Disabling Functions (Fn05)
Each different function, charger, inverter and transfer can be disabled. This is
useful for specific applications which are required to disable some of these three
functions. If you press the “FUNC” button for more than 2 seconds you can
have access to the different possibilities shown in the following diagram,.
In programming mode the display only shows the different types of program with
the “Charger”, Transfer” and “Inverter” functions. To change the type of
programming press the “△ or ▽ ” button until the LED corresponding to the
desired function is lit, in to the table below, After 10 seconds or press “DSPL”
button the Invertek will exit the programming mode and function with the new
programming,. In normal user mode, the disabled functions are displayed by a
orange blinking LED.
Download from Www.Somanuals.com. All Manuals Search And Download.
-18-
F.1 Diagram of the different mode
Indicates an off LED
Indicates a orange blinking LED
Indicates a lit green LED
All the functions are enabled. This is factory setting.
The inverter ins disabled. Only the Bypass switch and charger will
work normally.
Charger and Bypass switch are disabled. The inverter will work
continuously even if there is a correct AC voltage at the input.
Inverter and charger are both disabled. Only the Bypass switch
function is enabled in input and frequency is OK.
Download from Www.Somanuals.com. All Manuals Search And Download.
-19-
G. Charger Information
G.1.1 Charging Cycle
The fully automatic battery charger can be adjusted so that most major battery
types can be charged to the maximum,
As soon as the minimum AC voltage is available at the AC input (“AC IN” LED is
lit),the Battery Charger is switched on automatically (“CHARGER” LED is lit). The
battery is automatically charged to match the pre adjusted voltage levels and
charge current. Thanks to the sophisticated and intelligent Floating Charge
System, the batteries can be left in charge mode for unlimited time.
During the charging cycle, the AC loads are continually supplied with power from
the incoming AC voltage source. (“AC OUT” LED is lit).
G.1.3 Input current repartition (Power sharing Fn06)
To manage the power available on the AC INPUT the unit is equipped with a
system usually called “Power sharing” or INPUT power distribution. With this
feature it is possible to limit the AC INPUT current assigned to the charger. The
more current used by the AC load, the less power is given to the charger. Priority
for the AC Loads. When power sharing is used the red 200% LED on the power
monitor is lit to show that the battery charging is being limited.
G.1.4 Set the charging current (Fn07):
The maximum charging current or the battery can be adjusted by function Fn07.
The charging current should be set to approximately 10-15% of the battery
capacity (at C10). This means that the charging current for a battery with 300Ah
should be set between 30-45A. The charging current is displayed on the
“multi-display” or “CURRENT MONITOR” on the front panel
G.1.5 Battery Condition:
The built in microprocessor features a specially developed algorithm (formulae)
which calculates the actual state of charge (SOC) of the battery and displays it on
LED-8. The Equalize LED-7 is lit when the system is performing an equalization
charge. The SOC displayed should be used as a guide only, for batteries which
are not sealed, use a hydrometer to determine the exact SOC.
For safety reasons:
Make sure that the setting of the charger matches your battery type! The correct
charging levels are critical for safe functioning and long life of the battery.
Download from Www.Somanuals.com. All Manuals Search And Download.
-20-
G.2 The Transfer system
When an AC voltage is present at the AC IN of the unit , the “AC IN” LED is lit.
When this voltage matches the Parameter P-06 value set, and the frequency is
between 44Hz and 65Hz, then this power is transferred directly to the AC load and
the battery charger section . The “TRANSFER” LED is lit to indicate
this has happened. The inverter is then switched off and the battery charger
switched on. This process is automatic and should not be noticed by the load, at
worst a slight flicker may be seen in lights.
The maximum current of the Bypass switch is 60A (CUxx3500) resp.
30A (CUxx1700). That means through this system AC loads of up to a
maximum of 7000 W (CUxx3500) or 3500W (CUxx1700) can be operated.
When the Battery Charger is working, part of this power is used for the charging
according to the power sharing settings.
The Transfer system is protected against overload with an automatic breaker
on the AC Input side of the unit . If the system has been overloaded
the Input breaker will pop-out. To put the automatic safety system back in
to operating you must push this breaker for reset.
Note: In inverter operation the unit generates a pure sinewave and quartz
stabilized output voltage. However, when the unit is transferring power from
the grid or a generator the voltage and quality of the power running the AC load
will be the same as that coming from the grid or generator. The unit cannot
modify the incoming AC supply.
G.3 The solar charge regulator
The unit has a built-in solar charge regulator. To charge the batteries
solar modules can be connected to the terminal SOLAR IN +/-. The
built-in regulator is a shunt regulator with a maximum input current of 30A for all
series products. The operating voltage of solar modules to be connected must
match the actual operating voltage of the unit and never exceed the max. rated
value.
Under no circumstances should any other charging sources such as a
wind-generator be connected at the input of the solar charge regulator.
The Solar Charge Regulator works automatically and is always in operation. As
soon as the energy is delivered from the solar charge regulator, the “SOLAR
CHARGE” LED is lit and the batteries are being charged, The solar charge
regulator works even when the battery charger is functioning. The method of
operation is a 3 or 4 step charging process, the same as the battery charger. The
function is described in the section on battery charger. The programming and the
adjustments are carried out in accordance with the section on battery charger.
The programming and the adjustments are carried out in accordance with the
same conditions. Check with your battery supplier which adjustments must be
carried out for your battery.
Download from Www.Somanuals.com. All Manuals Search And Download.
-21-
I. Auxiliary Contacts
In the unit there are two built-in programmable power relays (AUX1, AUX2). The
potential-free change-over contact of this power relay is connected to the screw
terminals (AUX1 NO-NC-COM, AUX2 NO-NC-COM)
Maximum Contact load: -230Vac / 5Amp-30Vdc/7Amp
In the factory we program this output to be active when one these situations are
detected:
ꢁ
ꢁ
ꢁ
ꢁ
Over temperature
Overload
Over or under voltage of batteries
Unit is turned off manually or with a fault, “RUN/STOP” LED RED lit
over / under voltage of batteries.
AC output overload.
over temperature.
J. The Remote control unit
As an option, a Remote control unit can be connected to the unit . All operating
controls and displays are available on the Remote control unit, The Remote control
is supplied with a 3m long cable. It can be lengthened to 15m The Remote control
is suitable for surface mounting on the wall or on to a switch board. It is fixed with 2
screws. The unit can also be programmed with the Remote control. The output
currents and the charging currents are displayed on the Remote control.
J.1 The Temperature sensor
Charging voltages of lead-acid batteries can change depending on temperature.
To correct the operating voltages according to the actual temperatures, a
temperature sensor can be connected to the unit .
The compensation through the sensor is -3mv/℃/Cell.
Download from Www.Somanuals.com. All Manuals Search And Download.
-22-
L. Programming Aux Contacts (AUX1, AUX2)
L.1.1 Principle
The Auxiliary unit can be basically programmed for any operating situation of
the unit which is indicated with a LED. The programming is possible for one or
more operating situations. If the contact is programmed for many situations, it is
activated as soon as the unit finds itself in any one of the programmed
situations.
L.1.2 Example
L.1.2.1 Auxiliary contact as generator starter
When in the programming of the Auxiliary Contact, the State of Charge (SOC)
LED`s (LED 8) can be used as a condition, then you must take note of the
following requirements.
If you have to start an emergency back-up supply with a battery having a certain
SOC, then two SOC levels must be programmed. The first (i.e. Battery 25% LED)
for the starting or activating the Auxiliary Contact and the second (i.e. Battery
100% LED ) for stopping or deactivating the Auxiliary Contact. By programming
in this way the Auxiliary Contact starts with the lowest set condition and stops
when it has reached the highest programmed condition through charging.
L.1.2.2 Auxiliary Contact as Twilight Switch (With solar charger option)
The Auxiliary Contact can also be used as a twilight switch , i.e. for
automatically operating exterior lighting. Solar modules connected to the unit
will measure the light intensity. If the unit is operating without solar modules
and a twilight-switching function is desired, you can connect small solar cells with
the nominal voltage of the unit to the SOLAR terminals for the purpose of
measuring the light intensity. To function as a twilight-switch the Auxiliary Contact
must be programmed so that the condition “SOLAR CHARGE” LED is active.
Programming must be carried out in steps and in accordance with the description
for the programming of the Auxiliary Contact.
L.1.3.3 Manual operating of Auxiliary Contact:
The Auxiliary Contact can be operated manually at any time by pressing the
) to indicate that the
Contact is manually operated. By pushing the “AUX CONTACT” button again ,the
“AUX” button. The “Multi-display show
(
(
). By pushing it a third time,
Contact is deactivated. Multi-display show
automatic functions are restored and Multi-display show
(
).
Download from Www.Somanuals.com. All Manuals Search And Download.
-23-
M. Maintenance
Periodic maintenance is important to avoid potential problems. Every six months
disconnect all power in and out from the system. Thoroughly clean and check all
battery connections within the battery bank and to the unit . Ensure all
connections to the unit are tight. Ensure the vents at the top and bottom of the
unit are clear of any debris, such as mud wasps, severe dust build ups etc.
Other than this, you should enjoy years of trouble free operation form your
unit.
Download from Www.Somanuals.com. All Manuals Search And Download.
-24-
N. Specifications
MODEL
DAI-1500C-12xx
DAI-1500C-24xx
DAI-3000C-12xx
DAI-3000C-24xx
1.
Inverter Section
Nominal battery voltage
Input voltage range
12V / 24V
9.5-16V / 19-32V
12V / 24V
9.5-16V / 19-32V
Output voltage
200~240Vac / 100~120Vac
Output frequency
50Hz / 60Hz
< 2%
Total Harmonic Distortion output THD
Dynamic behavior 0→100%
Nominal power (W)
Maximum power 30 min (W)
Maximum power 3 min (W)
Maximum power 5 sec (W)
Maximum load
0.5 ms
1500W
1700W
2300W
3000W
3000W
3500W
4500W
6000W
Up to short circuit
Asymmetrical load max.
Overload and short circuit protection
Overheating temperature protection
Power factor range
Power saving function
Maximum efficiency
Up to nominal output power
Automatic disconnection with 5 time restart attempt
Acoustic warning before shut-off. Automatic restart
0.1-1
(disable / enable)
85-90%
2. Battery Charger Section
Maximum input voltage
Minimum input voltage
265 Vac, 350 V peak
Adjustable 150-230Vac
45~63Hz
Input Frequency range
Charging current adjustable
Setting of AC INPUT current POWER
SHARING
0-50A / 0-35A
100A / 0-70A
0 to 15A
3. Solar Charge Regulator-Floating
Maximum Poen Circuit Voltage
Maximum charging current
25V
30A
45V
30A
4. Battery Charge Montitoring (25℃)
*Low battery disconnection voltage
*Low voltage
*End of charge cycle voltage
*Equalization voltage every 25 cycles
*Floating voltage
10.8V / 21.6V
10.8V~12.0V (11.6V) / 21.6V~24.0V (23.2V)
14.2V~15.0V (14.4V) / 28.4V~30.0V (28.8V )
15.1V~15.5V (15.3V) / 30.2V~31.8V (30.6V)
13.3V~13.7V (13.5V) / 26.6V~27.4V (27.0V)
0~4h (2h)
*Absorption charge time
Temperature compensation (Option)
3mV / ℃ cell
5. General date
AC By pass time (UPS-Mode)
Potential free Multifunction contact
Max Current at Transfer relay
Operating temperature
20ms max
5A-250Vac / 7A-60V dc x 2
30A / AC 220V
60A / AC220V
-20℃to +55℃
Fan forced ventilation
From 45℃ / over 75℃ will be trip
Protection index IP
Weight
IP20
15kg
22kg
Dimension H*W*L (mm)
350x285x185
510x285x185
Remark:* ( ) Factory settings