Upright Hot Oil
Temperature Control Units
Part Number: 682.88107.00
Bulletin Number: SC1-660.3
Effective: 10/22/2009
Write Down Your Serial Numbers Here For Future Reference:
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
We are committed to a continuing program of product improvement.
Specifications, appearance, and dimensions described in this manual are subject to change without notice.
DCN No. ____________
© Copyright 2009
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
CHAPTER 1: SAFETY ................................................................5
1-1
How to Use This Manual .............................................................................................5
Safety Symbols Used in this Manual.....................................................................5
Warnings and Precautions ..........................................................................................6
Responsibility ..............................................................................................................7
General Responsibility...........................................................................................7
Operator Responsibility.........................................................................................8
Maintenance Responsibility...................................................................................9
Reporting a Safety Defect .....................................................................................9
1-2
1-3
CHAPTER 2: FUNCTIONAL DESCRIPTION............................10
2-1
2-2
2-3
Models Covered in This Manual................................................................................10
General Description...................................................................................................10
Standard Features.....................................................................................................10
Mechanical Features...........................................................................................10
Electrical Features...............................................................................................11
Controller Features..............................................................................................11
Options......................................................................................................................11
Feature Descriptions .................................................................................................12
Immersion Heaters..............................................................................................12
Heater Tank.........................................................................................................12
Pump...................................................................................................................12
Ful-Flo Valve .......................................................................................................12
Connection Lines.................................................................................................13
Electrical System Controls...................................................................................13
Electrical Panel and System Components ..........................................................13
Air Purge .............................................................................................................14
Pressure Switch ..................................................................................................14
Safety Thermostat...............................................................................................14
Reservoir Tank....................................................................................................14
Cooling (Optional) ...............................................................................................15
Safety Devices and Interlocks...................................................................................15
2-4
2-5
2-6
CHAPTER 3: INSTALLATION ...................................................17
3-1
3-2
Uncrating the Equipment...........................................................................................17
Rigging and Placing the TCU....................................................................................17
Installation Location Considerations....................................................................17
Electrical Connections...............................................................................................18
Setup Procedures......................................................................................................19
Connecting Piping ...............................................................................................19
Connecting Process Piping .................................................................................20
Initial Start-up ............................................................................................................22
Starting the Hot Oil TCU......................................................................................22
3-3
3-4
3-5
CHAPTER 4: OPERATION .......................................................24
Upright Portable Hot Oil TCUs
Chapter 1: Safety
iii
Download from Www.Somanuals.com. All Manuals Search And Download.
4-1
4-2
Start-up......................................................................................................................24
Controller Description & Operation............................................................................24
Identifying Control Panel Switches......................................................................25
Identifying System Status Board Indicators.........................................................26
Status Indicator Lights.........................................................................................27
Mode Indicator Lights..........................................................................................27
Fault Indicator Lights...........................................................................................27
Returning Fluid to the Tank.......................................................................................28
Shutting Down the Hot Oil TCU.................................................................................28
4-3
4-4
CHAPTER 5: MAINTENANCE..................................................30
5-1
5-2
Maintenance Schedule..............................................................................................30
Preventative Maintenance.........................................................................................31
Routine Servicing ................................................................................................31
Draining the Unit for Storage...............................................................................31
Preventative Pump Maintenance.........................................................................31
Corrective Maintenance ............................................................................................32
Pumps and Seals ................................................................................................32
Maintaining the Pump..........................................................................................33
Thrust Bearing Adjustment..................................................................................35
Installation of Carbon Graphite Bushings............................................................35
5-3
CHAPTER 6: TROUBLESHOOTING.........................................36
6-1
Introduction................................................................................................................36
CHAPTER 7: APPENDIX ..........................................................39
7-1
7-2
Optional Components................................................................................................39
Technical Specifications............................................................................................40
Annex B Information............................................................................................40
Drawings and Diagrams............................................................................................42
Spare Parts List.........................................................................................................45
Returned Material Policy ...........................................................................................48
Credit Returns .....................................................................................................48
Warranty Returns ................................................................................................48
Safety Tag Information..............................................................................................48
TCU Safety Tags.................................................................................................48
TCU Identification (Serial Number) Tag ....................................................................49
Technical Assistance.................................................................................................49
Parts Department ................................................................................................49
Service Department.............................................................................................49
Sales Department................................................................................................49
Contract Department...........................................................................................49
7-3
7-4
7-5
7-6
7-7
7-8
Upright Portable Hot Oil TCUs
Chapter 1: Safety
iv
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 1: Safety
1-1 How to Use This Manual
Use this manual as a guide and reference for installing, operating, and maintaining your
portable hot oil temperature control unit (TCU). The purpose is to assist you in applying
efficient, proven techniques that enhance equipment productivity.
This manual covers only light corrective maintenance. No other maintenance should be
undertaken without first contacting a service engineer.
The Functional Description section outlines models covered, standard features, and safety
features. Additional sections within the manual provide instructions for installation, pre-
operational procedures, operation, preventive maintenance, and corrective maintenance.
The Installation chapter includes required data for receiving, unpacking, inspecting, and setup
of the portable hot oil TCU. We can also provide the assistance of a factory-trained
technician to help train your operator(s) for a nominal charge. This section includes
instructions, checks, and adjustments that should be followed before commencing with
operation of the portable hot oil TCU. These instructions are intended to supplement
standard shop procedures performed at shift, daily, and weekly intervals.
The Operation chapter includes a description of electrical and mechanical controls, in
addition to information for operating the portable hot oil TCU safely and efficiently.
The Maintenance chapter is intended to serve as a source of detailed assembly and
disassembly instructions for those areas of the equipment requiring service. Preventive
maintenance sections are included to ensure that your portable hot oil TCU provides
excellent, long service.
The Troubleshooting chapter serves as a guide for identification of most common problems.
Potential problems are listed, along with possible causes and related solutions.
The Appendix contains technical specifications, drawings, schematics, parts lists, and
available options. A spare parts list with part numbers specific to your machine is provided
with your shipping paperwork package. Refer to this section for a listing of spare parts for
purchase. Have your serial number and model number ready when ordering.
Safety Symbols Used in this Manual
The following safety alert symbols are used to alert you to potential personal injury hazards.
Obey all safety messages that follow these symbols to avoid possible injury or death.
DANGER! DANGER indicates an imminently hazardous situation that, if not avoided,
will result in death or serious injury.
WARNING! WARNING indicates a potentially hazardous situation or practice that, if
not avoided, could result in death or serious injury.
Caution!
CAUTION indicates a potentially hazardous situation or practice that, if
not avoided, may result in minor or moderate injury or in property damage.
Upright Portable Hot Oil TCUs
Chapter 1: Safety
5
Download from Www.Somanuals.com. All Manuals Search And Download.
1-2 Warnings and Precautions
Our equipment is designed to provide safe and reliable operation when installed and operated
within design specifications, following national and local safety codes. This may include, but
is not limited to OSHA, NEC, CSA, SPI, and any other local, national and international
regulations.
To avoid possible personal injury or equipment damage when installing, operating, or
maintaining this equipment, use good judgment and follow these safe practices:
; Read and follow these operation and installation instructions when installing,
operating, and maintaining this equipment. If these instructions become damaged or
unreadable, additional copies are available from the manufacturer.
; Follow all SAFETY CODES.
; Wear SAFETY GLASSES and WORK GLOVES.
; Work only with approved tools and devices.
; Disconnect and/or lock out power before servicing or maintaining the equipment.
; Use care when LOADING, UNLOADING, RIGGING, or MOVING this
equipment.
; Operate this equipment within design specifications.
; OPEN, TAG, and LOCK ALL DISCONNECTS before working on equipment.
You should remove the fuses and carry them with you.
; Make sure the equipment and components are properly GROUNDED before you
switch on power.
; When welding or brazing in or around this equipment, make sure VENTILATION is
ADEQUATE. PROTECT adjacent materials from flame or sparks by shielding with
sheet metal. An approved FIRE EXTINGUISHER should be close at hand and
ready for use if needed.
; Do not restore power until you remove all tools, test equipment, etc., and the
equipment and related components are fully reassembled.
; Only PROPERLY TRAINED personnel familiar with the information in this
manual should work on this equipment.
We have long recognized the importance of safety and have designed and manufactured our
equipment with operator safety as a prime consideration. We expect you, as a user, to abide
by the foregoing recommendations in order to make operator safety a reality.
Upright Portable Hot Oil TCUs
Chapter 1: Safety
6
Download from Www.Somanuals.com. All Manuals Search And Download.
1-3 Responsibility
These machines are constructed for maximum operator safety when used under standard
operating conditions and when recommended instructions are followed in the maintenance
and operation of the machine.
All personnel engaged in the use of the machine should become familiar with its operation as
described in this manual.
Proper operation of the machine promotes safety for the operator and all workers in its
vicinity.
Each individual must take responsibility for observing the prescribed safety rules as outlined.
All warning and danger signs must be observed and obeyed. All actual or potential danger
areas must be reported to your immediate supervisor.
General Responsibility
No mater who you are, safety is important. Owners, operators and maintenance personnel
must realize that every day, safety is a vital part of their jobs.
If your main concern is loss of productivity, remember that production is always affected in a
negative way following an accident. The following are some of the ways that accidents can
affect your production:
• Loss of a skilled operator (temporarily or permanently)
• Breakdown of shop morale
• Costly damage to equipment
• Downtime
An effective safety program is responsible and economically sound.
Organize a safety committee or group, and hold regular meetings. Promote this group from
the management level. Through this group, the safety program can be continually reviewed,
maintained, and improved. Keep minutes or a record of the meetings.
Hold daily equipment inspections in addition to regular maintenance checks. You will keep
your equipment safe for production and exhibit your commitment to safety.
Please read and use this manual as a guide to equipment safety. This manual contains safety
warnings throughout, specific to each function and point of operation.
Upright Portable Hot Oil TCUs
Chapter 1: Safety
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Operator Responsibility
The operator’s responsibility does not end with efficient production. The operator usually has
the most daily contact with the equipment and intimately knows its capabilities and
limitations.
Plant and personnel safety is sometimes forgotten in the desire to meet incentive rates, or
through a casual attitude toward machinery formed over a period of months or years. Your
employer probably has established a set of safety rules in your workplace. Those rules, this
manual, or any other safety information will not keep you from being injured while operating
your equipment.
Learn and always use safe operation procedures. Cooperate with co-workers to promote safe
practices. Immediately report any potentially dangerous situation to your supervisor or
appropriate person.
REMEMBER:
• NEVER place your hands or any part of your body in any dangerous location.
• NEVER operate, service, or adjust the temperature control unit without appropriate
training and first reading and understanding this manual.
• Before you start the temperature control unit check the following:
• Remove all tools from the tcu;
• Be sure no objects (tools, nuts, bolts, clamps, bars) are laying in the
TCUs operating area;
• If your TCU has been inoperative or unattended, check all settings before starting the
unit.
• At the beginning of your shift and after breaks, verify that the controls and other
auxiliary equipment are functioning properly.
• Keep all safety guards in place and in good repair. NEVER attempt to bypass, modify,
or remove safety guards. Such alteration is not only unsafe, but will void the warranty
on your equipment.
• When changing control settings to perform a different mode of operation, be sure
selector switches are correctly positioned. Locking selector switches should only be
adjusted by authorized personnel and the keys removed after setting.
• Report the following occurrences IMMEDIATELY:
• unsafe operation or condition
• unusual temperature control unit action
• leakage
• improper maintenance
• NEVER stand or sit where you could slip or stumble into the
temperature control unit while working on it.
• DO NOT wear loose clothing or jewelry, which can be caught while working on a tcu.
In addition, cover or tie back long hair.
Upright Portable Hot Oil TCUs
Chapter 1: Safety
8
Download from Www.Somanuals.com. All Manuals Search And Download.
• Clean the tcu and surrounding area DAILY, and inspect the machine for loose, missing
or broken parts.
• Shut off power to the tcu when it is not in use. Turn the switch to the OFF position, or
unplug it from the power source.
Maintenance Responsibility
Proper maintenance is essential to safety. If you are a maintenance worker, you must make
safety a priority to effectively repair and maintain equipment.
Before removing, adjusting, or replacing parts on a machine, remember to turn off all electric
supplies and all accessory equipment at the machine, and disconnect and lockout electrical
power. Attach warning tags to the disconnect switch.
When you need to perform maintenance or repair work on equipment above floor level, use a
solid platform or a hydraulic elevator. If there is a permanently installed catwalk on your
equipment, use it. The work platform should have secure footing and a place for tools and
parts. DO NOT climb on equipment, machines, or work from ladders.
If you need to repair a large component, use appropriate handling equipment. Before you use
handling equipment (portable “A” frames, electric boom trucks, fork trucks, overhead cranes)
be sure the load does not exceed the capacity of the handling equipment or cause it to become
unstable.
Carefully test the condition of lifting cables, chains, ropes, slings, and hooks before using
them to lift a load.
Be sure that all non-current carrying parts are correctly connected to earth ground with an
electrical conductor that complies with current codes. Install in accordance with national and
local codes.
When you have completed the repair or maintenance procedure, check your work and remove
your tools, rigging, and handling equipment.
Do not restore power to the equipment until all persons are clear of the area. DO NOT start
and run the machine until you are sure all parts are functioning correctly.
BEFORE you turn the machine over to the operator for production, verify all equipment
enclosure panels, guards and safety devices are in place and functioning properly.
Reporting a Safety Defect
If you believe that your equipment has a defect that could cause injury, you should
immediately discontinue its use and inform the manufacturer.
The principle factors that can result in injury are failure to follow proper operating procedures
(i.e. lockout/tagout), or failure to maintain a clean and safe working environment.
Upright Portable Hot Oil TCUs
Chapter 1: Safety
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 2: Functional Description
2-1 Models Covered in This Manual
This manual provides operation, installation, and maintenance instructions for portable hot oil
temperature control units. Model numbers are listed on the serial tag. Make sure you know
the model and serial number of your equipment before contacting the manufacturer for parts
or service.
Your portable hot oil temperature control unit circulates thermal transfer-type oil through
your process and precisely, automatically, and reliably maintains it at a temperature you can
select. Portable hot oil temperature control units are sized to meet the specific requirements
stated by the Customer at the time of purchase.
2-2 General Description
The operating range of your temperature control unit is from 100°F to 550°F (38°C to
288°C). The unit is best suited for use with a specially formulated Heat Transfer Fluid. A
recommended list of commercially available heat transfer fluids can be obtained through
Customer Service.
Rapid recirculation of the relatively small amount of fluid provides a close and uniform
temperature relationship between the TO PROCESS and FROM PROCESS lines. This does,
of course, depend on the configuration of your process, and any restrictions within the mold.
This recirculation, combined with the immersion heater and optional cooling capability, gives
fast and accurate response to bring the fluid up to temperature, or to changes in the settings
when needed.
Performance is assured through matching the unique controllers to the high temperature
system. The two systems are fully integrated to achieve accurate control, along with efficient
use of water and electricity.
2-3 Standard Features
Mechanical Features
• Dual stage immersion heater with IEC contactors
• 550°F (288ºC) maximum operating temperature {400°F (244°C) maximum operating
temperature for 6 kW heaters}
• Manual bypass
• Pressure switch for low pump pressure shut-down
• To Process pressure gauge
• Independent safety thermostat
• Y strainer on From Process line
• Automatic venting sequence
• Positive displacement pumps capable of reversing to evacuate the process
• Easily removable panels for quick access to internal components
• 1 year warranty on parts and labor (Labor at factory)
Upright Portable Hot Oil TCUs
Chapter 2: Functional Description
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical Features
• Non-fused lockable rotary disconnect
• Branch circuit fusing
• NEMA 12 electrical enclosure
• UL listed subpanel
Controller Features
• M2B+ microprocessor controller with fuzzy logic; includes diagnostic features with
indicator and warning status lights
• System status graphic display
• Low level alarm for reservoir
• Audible alarm
• 5 year warranty on controller
2-4 Options
Options marked with “*” indicate options that can be factory installed or retrofitted in the
field.
• Drain valve
• Hour meter; measures total pump run time hours
• General fault visual alarm
• Autovent sequence; deducts available
• Low level alarm; deducts available
• High level indicator light
• Manual bypass; deducts available
• M2B+ microprocessor controller options include:
• 4-20 mA remote set point and retransmission
• SPI protocol, RS-485
• General protocols, types RS-232, -485
• Remote sensor; 10 Ft. (3m)
• Heat exchanger options of 3.9 sq. ft. (0.3627 sq. m) and 6.7 sq. ft. (0.6231 sq. m)
• Remote controller
• Lexan cover
• Optional operating voltages of 208/3/60, 230/3/60, 575/3/60, 380/3/50, and 415/3/50
Upright Portable Hot Oil TCUs
Chapter 2: Functional Description
11
Download from Www.Somanuals.com. All Manuals Search And Download.
2-5 Feature Descriptions
Immersion Heaters
The fluid is heated by the specially designed three-phase low watt density electrical
immersion heater, and regulated by the controller. The standard heater has a steel sheath for
low watt density and good heat transfer.
These models can be supplied with 6, 12, 18, or 24 kW low watt density immersion heaters,
depending upon the heating needs of the process. The 18 and 24 kW models are built to
provide full or partial heat as required by the process and determined by the controller, to
provide more precise control.
Heater Tank
The Upright features a single pass heater tank. The tank is designed to maintain an optimum
balance of fluid velocity versus watt density, and turbulence for excellent heat transfer, and
minimal pressure drop. The high fluid velocity will greatly prolong the life of the heater and
fluid.
Pump
The pump is a mechanical seal, positive displacement pump. It features a nearly maintenance
free design, and was selected after extensive testing to provide superior performance,
flexibility, and low maintenance. It is well suited for use with a variety of commercially
available heat transfer fluids. The pump has only two internal moving parts, and a specially
designed seal to give years of trouble free service, even at high temperatures. The only
routine maintenance required is the monthly greasing and occasional head space adjustment;
see Section 5-3 on Page 40 for more information.
The pump is capable of running in either direction. Thus, the pump reverse feature can be
used to draw fluids back from the process. It is not necessary to install a service air line to
purge lines before changing molds. Since the pump is capable of achieving extremely high
pressures, it is necessary to regulate the pressure through use of a regulating bypass line (Ful-
Flo valve). Because the pump is a positive displacement pump, it will supply the process with
rated flow at or below the rated pressure.
The flow is constant until the pressure reaches the rated pressure. The pressure however is a
function of frictional losses through the process that it is attached to. Systems with large
process connections, ports, and piping will operate at low pressures. While systems with
small process connections, ports, and piping will operate at higher pressures. Once pressure
requirements exceed the rated pressure, the Ful-Flow valve will open and bypass the
necessary fluid to prevent high pressures.
Ful-Flo Valve
A regulating bypass line featuring a Ful-Flo valve is standard in all units. This is a safety
device to prevent excessive pressure in the event that the delivery line is obstructed. Each
Ful-Flo valve is factory preset to limit system pressure as specified by the customer. It must
not be tampered with in any way.
In the event of an obstruction in the line, the Ful-Flo valve will open and divert fluid from the
delivery TO PROCESS line to the return FROM PROCESS line. A constant flow of fluid is
maintained through the heater tank to prevent damage to the heating elements and fluid.
Upright Portable Hot Oil TCUs
Chapter 2: Functional Description
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Connection Lines
Connections for TO PROCESS and FROM PROCESS lines are 1" NPT (25.4 mm). Water
connections for COOLING WATER SUPPLY and COOLING WATER DRAIN are ¾” NPT
(19.1 mm); see Section 3-4 on Page 20 for more information. The customer is responsible for
conversions to metric standards.
The manufacturer stocks many lengths of flexible metal hose; the part number is 572-16969.
State the length of hose you want when ordering.
WARNING! Component failure may result in high-temperature oil spray, causing serious injury or
death. Make sure hoses, valves, and other components installed in your process can
withstand maximum temperature and pressure of the Upright unit; check unit
nameplate for specific capacities. All components must be carefully inspected for
condition before installing. Make sure you have factory components if you have any
doubt.
Electrical System Controls
The electrical controls of your Upright unit are specially engineered for reliability, safety, and
simplicity of operation. Switch functions are clearly labeled. Your Upright unit has a system
status board so you can evaluate the status and performance of the unit at a glance. Pilot
lights are provided to indicate key unit functions.
An audible alarm is standard with your unit. The alarm will sound in the event of the
following conditions:
• motor overload
• safety thermostat trip (over temperature)
• low fluid pressure
• low fluid level
• high fluid level (optional)
Push the ALARM SILENCE button to silence the alarm. See Section 4-2 on Page 25 for
more information on control functions.
Electrical Panel and System Components
The pump motor and immersion heater operate on three-phase, 50/60 cycle, nominal voltage
with the control circuit at 115 V single phase. The control circuit voltage is provided by a
single phase machine tool transformer with primary fuse protection and a grounded
secondary. A main power disconnect is included for ease of service. The electrical panel is
UL listed and complies with N.F.P.A. 79 provisions.
All components are IEC rated for long life and reduced maintenance. The heater elements are
branch fused, and protected from contactor welding by a separate primary voltage contactor.
The pump motor is controlled by a full voltage magnetic reversing starter, with fused branch
circuit overcurrent and thermal overload protection. Many additional features are available as
options.
A NEMA 12 enclosure is standard, with NEMA 4 available as an option.
Upright Portable Hot Oil TCUs
Chapter 2: Functional Description
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Air Purge
Upon initial start-up and mold/process change-out, you’ll need to purge all air and water from
the system. The Upright unit has appropriate valving to ensure complete purging. Procedures
are covered in Section 3-5 on Page 23.
WARNING! Failure to purge the system of air before heating may result in serious injury or critical
system and equipment damage. Make sure you properly purge the system of air before
starting the heater cycle.
Pressure Switch
A pressure switch is built into each unit to guard against heater damage. This feature prevents
the heater elements from being energized unless the pump is running and fluid is in the
system. After a preset time, the pump shuts down if the fluid pressure is not re-established.
The pressure switch is preset at the factory; do not tamper with it.
Safety Thermostat
The safety thermostat is a J-thermocouple sensing, adjustable fail-safe device located in the
heater tank. This is to guard against the unlikely event of “runaway” heating. If over-heating
does occur, the safety thermostat shuts down the heater outputs and sounds an audible alarm.
A red pilot light on the status board also illuminates. The unit continues to pump fluid
through the system to prevent heater damage. Auxiliary factory installed alarms such as
beacons and klaxons are available as options.
All controller functions are locked out until the main supply power is disconnected. Resetting
the alarm condition is initiated by depressing the red pump stop button. The reset button is
located inside the electrical enclosure, mounted on the left wall of the enclosure. It is
imperative that a qualified maintenance technician determine and correct the cause of the
fault before resuming operation.
Reservoir Tank
A reservoir tank with sight gauge is standard; usable capacity is seven (7) gallons (26.5
liters). The tank permits thermal expansion of the heat transfer fluid, and provides makeup
fluid.
WARNING! The reservoir tank may cause serious injury if it ruptures from not being properly
vented. Make sure that the reservoir tank is always properly vented to prevent tank
rupture.
The reservoir tank drain is extended beyond the base of the unit for ease of draining. Optional
ball valves are available to further simplify draining.
Upright Portable Hot Oil TCUs
Chapter 2: Functional Description
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Cooling (Optional)
The manufacturer-designed shell and tube heat exchanger is provided as optional equipment
in this unit. The design features U-tube construction and copper-nickel tubes for durability
and optimal heat transfer.
The modular construction (unique to our units) allows the tube bundle to be easily removed
for periodic cleaning. Additionally, check valves are installed on the water supply and drain
lines to prevent water from back flowing into the heat exchanger from a closed drain or into
the water supply piping.
The controller automatically regulates cooling by opening and closing the cooling solenoid.
This allows the proper amount of cooling water to pass through the tubes of the heat
exchanger and out the drain. A water supply of 75 psi (517.1 kPa/5.2 bars) maximum is
required for connection to the heat exchanger.
2-6 Safety Devices and Interlocks
This section includes information on safety devices and procedures that are inherent to the
portable hot oil tcu. This manual is not intended to supersede or alter safety standards
established by the user of this equipment. Instead, the material contained in this section is
recommended to supplement these procedures in order to provide a safer working
environment.
At the completion of this section, the operator and maintenance personnel will be able to do
the following:
•
•
•
Identify and locate specific safety devices.
Understand the proper use of the safety devices provided.
Describe the function of the safety device.
Safety Circuit Standards
Safety circuits used in industrial systems protect the operator and maintenance personnel
from dangerous energy. They also provide a means of locking out or isolating the energy for
servicing equipment.
Various agencies have contributed to the establishment of safety standards that apply to the
design and manufacture of automated equipment. The Occupational Safety and Health
Administration (OSHA) and the Joint Industrial council (JIC) are just a few of the
organizations that have joined with the plastics industry to develop safety standards.
Every effort has been made to incorporate these standards into the design of the portable hot
oil tcu; however, it is the responsibility of the personnel operating and maintaining the
equipment to familiarize themselves with the safety procedures and the proper use of any
safety devices.
Upright Portable Hot Oil TCUs
Chapter 2: Functional Description
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Fail Safe Operation
If a safety device or circuit should fail, the design must be such that the failure causes a
“Safe” condition. As an example, a safety switch must be a normally open switch. The switch
must be held closed with the device it is to protect. If the switch fails, it will go to the open
condition, tripping out the safety circuit.
At no time should the safety device fail and allow the operation to continue. For example, if
a safety switch is guarding a motor, and the safety switch fails, the motor should not be able
to run.
Safety Device Lock-Outs
Some safety devices disconnect electrical energy from a circuit. The safety devices that are
used on these temperature control units are primarily concerned with electrical power
disconnection and the disabling of moving parts that may need to be accessed during the
normal operation of the machine.
Some of the safety devices utilize a manual activator. This is the method of initiating the
safety lock out. This may be in the form of a plug, lever or a handle. Within this lockable
handle, there may be a location for a padlock. Personnel servicing the equipment should
place a padlock in the lockout handle.
In addition to the safety devices listed above, these temperature control units are equipped
with a line cord plug. This allows the operator or maintenance personnel to unplug the tcu
from its power source and tag it out. The plug can then be tagged with any number of
approved electrical lockout tags available at most electrical supply stores.
WARNING! Always disconnect and lockout all electrical power and pneumatic (i.e. compressed air)
sources prior to servicing or cleaning the temperature control unit. Failure to do so
may result in serious injury. No one but the person who installed the lockout may
remove it.
Upright Portable Hot Oil TCUs
Chapter 2: Functional Description
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 3: Installation
3-1 Uncrating the Equipment
Portable hot oil temperature control units are shipped mounted on a skid, enclosed in a plastic
wrapper, and contained in a cardboard box.
1. Pry the crating away from the skid.
Note: Remove the nails holding the box to the skid and lift the box off carefully;
avoiding staples in the 1’ x 4’ wood supports. Cut the steel banding.
2. Use a pry bar to remove the blocks securing the unit to the skid.
3. Lift unit from sides. Use a pry bar if necessary to carefully remove the
skid from the unit.
4. Lower slowly.
3-2 Rigging and Placing the TCU
Make sure that you meet the following requirements when installing and operating your
Upright hot oil temperature control unit.
Installation Location Considerations
Locate the Upright unit as close as possible to the process for proper circulation and
temperature control. Take care when selecting a location. The area surrounding the unit must
be free of obstructions to ensure proper ventilation of internal components. Allow a minimum
clearance of at least 30 inches (76 cm).
Make sure that the unit location is not in a confined space to ensure proper air circulation.
Special air circulation/ventilation is required for units operating at temperatures exceeding
500ºF (260ºC). Vapors can escape from areas such as the reservoir tank during high
temperature operation.
Caution!
Harmful vapors may be generated from thermal fluid during high
temperature operation. Prolonged or repeated exposure of these heat-
generated vapors may result in eye and respiratory tract irritation.
Avoid contact or inhaling harmful amounts or material. Consult the
Material Safety Data Sheet (MSDS) for precautions and instructions for
the thermal fluid you are using.
Note: Before storing your Upright temperature control unit, make sure you remove
all residual water with compressed air to avoid a potential freezing hazard.
See Section 5-2 on Page 39 for more information.
Note the following table of ambient temperature ranges permitted for storage and operation:
Ambient storage range
Ambient operation range
ºF
ºC
ºF
ºC
-40ºF to 185ºF
-40ºC to 85ºC
-4ºF to 120ºF
-20ºC to 49ºC
You should preheat the process heat transfer fluid first if you want to start the unit below an
ambient temperature of 30ºF (-1ºC).
Upright Portable Hot Oil TCUs
Chapter 3: Installation
17
Download from Www.Somanuals.com. All Manuals Search And Download.
3-3 Electrical Connections
These units are designed for three-phase voltage operation. Refer to the unit nameplate for
proper voltage and amperage requirements, and make sure your electrical service conforms.
Check the unit nameplate for correct voltage and amperage before making electrical
connections!
Caution!
1. Provide a correctly sized and protected power supply to the unit.
2. If an electrical supply disconnect is not installed as a factory option, the customer
is responsible to properly size and install a suitable disconnect.
3. Refer to National Electric Code (NEC) 430-24-26 for proper feed conductor and
supply disconnect sizing.
4. Voltages must be within plus or minus ten percent (±10%) of the nameplate rating.
5. Maintain a safe ground and disconnect the power supply before servicing the unit.
A qualified electrician should make electrical connections and disconnect the
electricity when service calls are needed.
• Locate disconnects in an easily accessible location. Operators should
not have to squeeze around the Upright unit to reach disconnects,
especially in case of emergency.
• When running conduit whips to the Upright unit, make sure that whips
are routed away from hot piping.
DANGER! Improper electrical connections can cause damage to the unit and
cause serious operator injury or death! Make sure that ALL electrical
connections are made by a qualified electrician, and that ALL
connections are tight.
Make all electrical supply connections at the front of the unit. An access panel covers all
electrical connections. Run electrical connections to the supply terminals from either side of
the unit. Make sure that all three phases are wired correctly. The pump runs backwards if not
wired properly.
Upright Portable Hot Oil TCUs
Chapter 3: Installation
18
Download from Www.Somanuals.com. All Manuals Search And Download.
3-4 Setup Procedures
This section provides the procedures necessary for configuring your portable hot oil
temperature control unit.
Configuration of your TCU includes connecting cooling, process and vent piping. We
recommend that you carry out these procedures in the order given here.
Note: Before carrying out these procedures, install all equipment as described in
this section.
Connecting Piping
Make sure that all external piping is properly sized to reduce external pressure drop as much
as possible. Do not install process or water supply/drain piping smaller than the fittings on the
unit. If the water supply piping is larger than unit fittings, reduce the pipe size at the unit.
The following table lists recommended Upright TCU pipe sizes.
Size diameter
Connection
inches NPT
mm (approx.) c
To Process
From Process
Cooling Water Supply
Cooling Water Drain
Oil Drain
1”
1”
¾”
¾”
½”
1”
25.4
25.4
19.1
19.1
12.7
25.4
Fill Port
c Customer is responsible for converting to metric.
Note: Always use a backup wrench to support Upright unit piping when making
connections. Make sure all external piping is supported independently of the
Upright unit.
The manufacturer recommends that you have strainers installed on the
cooling water inlets and customer-supplied shut-off valves on all piping
connections. Use common black welded pipe for permanent installations.
The Upright is designed to operate with an open, unrestricted drain line.
Steam rapidly expands within the heat exchanger, so any overpressure
condition from backpressure or standing columns of water against the drain
must be avoided.
If you must use a pipe joint compound, use a compound that can withstand the high
temperatures and pressures of your Upright unit. Always insulate all piping to prevent burn
hazards and to retain heat. Make sure insulation is properly rated for maximum operating
temperatures of your Upright unit.
Piping Considerations for Mobile Installations
Because your Upright unit is fitted with casters, its portability is well suited for multiple
applications. You can purchase high-quality flexible metal hose from the manufacturer to
enhance the mobility of your Upright unit; state the length you want when ordering.
Although they cause a drop in pressure, you can also install quick disconnects to your
Upright unit. However, do not install check valves with quick disconnects unless absolutely
necessary!
Upright Portable Hot Oil TCUs
Chapter 3: Installation
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Connecting Process Piping
When connecting process piping, ensure that the Cautions listed below are observed and
followed:
Caution!
• Hoses, valves and other components in your process must be able to withstand
Upright unit maximum temperatures and pressures.
• Maximum temperatures and pressures are listed on the unit nameplate.
• Carefully inspect all components before installation.
• If in doubt about component suitability, obtain factory components.
• Fix all leaks! Fluid can be a potential fire and slip hazard.
Connecting Cooling Water Piping
You must provide cooling water at 25 psi to 75 psi (172.4 kPa to 517.1 kPa/1.7 bars to 5.2
bars) for proper operation. Untreated water can foul or corrode the heat transfer surfaces,
slowing water flow and causing fluid temperature control problems. The manufacturer sells a
complete line of water treatment equipment that can reduce downtime and maintenance costs.
Run properly-sized cooling water lines—never smaller than the outlets on the Upright unit. If
external piping is larger than Upright unit connections, reduce the size of the piping at the
unit.
Connecting Vent Piping
You must leave the vent connection open to the atmosphere at all times. The vent connection
is located on top of the reservoir. On systems with piping above the reservoir level, you must
run vent piping to a minimum height of one foot (1’ / 31 cm) above the highest point in the
system. Run the piping down into an auxiliary vented overflow chamber, such as a vented,
covered 55-gallon (208-liter) drum. This practice ensures that overflow will not create a
hazard to personnel.
Note: All external piping must be supported independently of the Upright unit.
Caution!
The reservoir tank must be vented to prevent pressurization. A pressurized
reservoir could rupture, allowing hot fluid to escape and become a
potential fire and slip hazard.
Note: Heat transfer fluids expand when heated. Expansion rates vary, depending
on fluid types and temperatures. For more information on expansion rates,
refer to specification information for the heat transfer fluid you select.
Generally, most heat transfer fluids expand at the rate of 2.5% for every
increase of 50°F/°C from temperatures above 60°F (16°C).
Upright Portable Hot Oil TCUs
Chapter 3: Installation
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 1: Upright Unit Piping Setup
Connect the TO PROCESS hookup to the entrance of the process and the FROM PROCESS
hookup to the exit of the process. Connect the COOLING WATER SUPPLY to your plant
water supply. Connect the COOLING WATER DRAIN line to an open drain, or to the return
line of your central water system. If returning to a central water system, use a
condensate/return tank to avoid a standing water column on the heat exchanger drain line.
Caution!
If you are routing the drain line to an open drain, make sure that the line is
directed away from personnel to avoid scalding.
Carefully select connecting lines and connectors between the Upright unit
and the process to best meet the needs and requirements of your
application.
Make sure lines and connectors have a service rating of at least 100 psig
(689.5 kPa/6.9 bars), and a temperature rating at least equal to the
maximum operating temperature of your Upright unit.
Note: To prevent debris from fouling reservoir fluid, the Upright unit is equipped
with an internal vent on the reservoir tank. Use the plug provided to close off
the external fill port after filling the unit with heat transfer fluid.
Upright Portable Hot Oil TCUs
Chapter 3: Installation
21
Download from Www.Somanuals.com. All Manuals Search And Download.
3-5 Initial Start-up
Starting the Hot Oil TCU
Before you begin your heating process, perform the following startup procedures. Doing so
ensures that all air is vented from the system to prevent fluid degradation and damage to the
heater.
1. Add recommended heat transfer fluid to the reservoir tank until the level is near the
top of the sight glass.
2. If so equipped, open the manual vent valve on the back of the unit.
3. Push the PUMP START button to start the pump, then check motor rotation by
observing the pressure gauge.
If the gauge indicates positive pressure, rotation is correct. If not, disconnect power
and reverse the incoming power leads.
4. As fluid is drawn out of the reservoir tank to fill the process, the fluid level falls in
the tank. Continue to add fluid to maintain the level about four inches (4”/10 cm)
from the bottom of the sight glass.
Air and thermal fluid vent through the vent solenoid or the manual vent valve and
into the reservoir tank.
Caution!
You must purge the system of air before the heating cycle. Personal injury
and system damage can occur from a pressurized system.
Make sure that the reservoir tank vent port is not plugged. The reservoir
tank must never be pressurized!
5. When the unit has built at least five (5) psi (34.5 kPa) of pressure, wait two (2)
minutes, then select a set point of 100°F (38ºC) and switch the unit into AUTO mode.
As the oil warms up, viscosity decreases and pressure falls.
6. Increase the set point to 150ºF, then 200ºF (65ºC, then 93ºC) at two-minute intervals.
7. Any water present in the system must boil off before continuing operation. Select a
set point of 215ºF (102ºC) and observe the reservoir tank vent for any signs of
escaping steam.
Continue to run at this set point temperature until no more steam appears and
pressure stabilizes.
8. When fluid level stabilizes and the air and water are purged from the system, allow
the vent timer to run out.
- or -
If so equipped, close the vent valve. Do not open the vent valve at temperatures
exceeding 250ºF (121ºC).
With the system properly purged, only four to six inches (4” to 6” / 10 cm to 15 cm) of fluid
should be visible in the sight glass. This lets the fluid expand as it heats, also permitting
process fluid additional capacity when the pump reverses and fluid is withdrawn from the
mold.
Upright Portable Hot Oil TCUs
Chapter 3: Installation
22
Download from Www.Somanuals.com. All Manuals Search And Download.
The Upright unit is now ready for use. All that is now required, is to select a process set point
on the controller.
Note: If all traces of water are not removed from the system, severe cavitation may
occur at elevated temperatures. Indications are a rough-sounding pump,
fluctuating or dropping pressure, or a rapidly rising fluid level in the
expansion tank. Repeat Step 3 if this occurs.
Upright Portable Hot Oil TCUs
Chapter 3: Installation
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 4: Operation
4-1 Start-up
1. Push the PUMP START button to start the pump.
2. When the unit has built at least five (5) psi (34.5 kPa) of pressure, wait two (2)
minutes, then select a set point of 100°F (38ºC) and switch the unit into AUTO mode.
As the oil warms up, viscosity decreases and pressure falls.
3. Four to six inches (4” to 6” / 10 cm to 15 cm) of fluid should be visible in the sight
glass.
4. Select a process set point on the controller.
4-2 Controller Description & Operation
The M2B+ controller is an easy-to-operate microprocessor-based PID control device. When
the process reaches the set point, the PID control cycles the cooling valve and/or immersion
heater to maintain the proper leaving temperature.
The controller has been fully factory tested. Set the desired process temperature set point and
the controller does the rest.
Built-in range of operation on the controller is -4°F to 120°F (-20ºC to 49ºC).
Refer to the M2B+ Owner’s Manual supplied with your unit for specific operation
instructions.
Upright Portable Hot Oil TCUs
Chapter 4: Operation
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Identifying Control Panel Switches
This section lists the descriptions and functions of the control panel switches. These switches
control the operation of the unit.
Figure 4: Control Panel Switches
Pump Start. Press the START button to start the pump in the normal forward direction.
Pump Stop. Press the STOP button to stop the pump and de-energize the controller.
Caution!
Always press the Pump Stop button and allow the pump to come to a
complete stop before pressing the Pump Reverse button.
Failure to let the pump stop before reversing may damage the pump and
drive.
Pump Reverse. Press the REVERSE button to start the pump in the reverse direction. Use
this feature to purge oil from the mold.
Vent Cycle Start. Press the VENT button to start the vent cycle timer. Use this feature to
purge air and water from the unit and process.
Upright Portable Hot Oil TCUs
Chapter 4: Operation
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Mode Select. With the pump running, you can select the AUTO position or the Maintained
(manual cooling) position with the Mode Select switch. Select AUTO mode to energize the
controller, permitting it to monitor and control the process. The switch automatically returns
to the Center Default position when in AUTO mode. The switch stays in the Maintained
position in Manual Cooling mode.
Caution!
Always let the pump run for at least one (1) minute before switching to
AUTO mode.
Never switch to AUTO mode when filling or venting the unit, except as
described in the Unit Startup. Improper switching can seriously damage
the heater, as it could become energized with air in the system.
Alarm Silence. Press the ALARM SILENCE button to silence the audible alarm on the
console.
Caution!
After you silence the alarm, make sure you locate and correct the alarm
condition before continuing with unit operation.
Identifying System Status Board Indicators
The system status board is located next to the controller panel. It displays indicator lights to
show current operation status, letting you analyze system performance.
Figure 5: System Status Board Indicators
Use the status board to optimize unit performance. For example, if you observe a rapid
cycling of the Heater and Cool Solenoid indicators, the unit is operating with a process
inefficiency; see the Troubleshooting section for more information.
What follows is a description of system status board indicators.
Upright Portable Hot Oil TCUs
Chapter 4: Operation
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Status Indicator Lights
Pump Reverse Indicator Light. The Pump Reverse indicator light illuminates when the
unit pump runs in reverse.
Pump Forward Indicator Light. The Pump Forward indicator light illuminates when the
unit pump runs in the normal forward direction. This indicator typically illuminates
continuously during normal operation.
Heater On Indicator Light. The Heater On indicator illuminates when the heater energizes.
Cool Solenoid Indicator Light. The Cool Solenoid indicator illuminates when the cooling
solenoid energizes. It is used only on the optional heat exchanger.
Vent Solenoid Indicator Light. The Vent Solenoid indicator illuminates when the venting
solenoid energizes during venting sequences.
Mode Indicator Lights
Select the unit operating mode by using the selection switch.
Power On Mode Indicator Light. The Power On mode indicator light illuminates to
indicate that the control circuit is energized in the unit.
Auto Mode Indicator Light. The Auto mode indicator light indicates that the Auto mode is
active and the controller is monitoring the system and controlling the process.
If the Auto light is off and the Cool Solenoid indicator light is illuminated, the controller is
disabled and the cooling solenoid is open, permitting maximum cooling.
If the Auto and Cool Solenoid indicator lights are off, the unit is in standby.
Fault Indicator Lights
Pump Overload Indicator Light. The Pump Overload indicator light illuminates when the
pump is overloaded. This is an alarm condition, so the audible alarm activates to notify you
of the pump overload fault, and the unit shuts down.
Note: Always correct the alarm condition before returning to normal
operation!
Low Pressure Indicator Light. The Low Pressure indicator light illuminates when the unit
has low heat transfer fluid pressure. This is an alarm condition, so the audible alarm activates
to notify you of the low pressure fault, and disables controller outputs, permitting the pump to
continue to circulate fluid to avoid damage. If low pressure continues past five minutes
elapsed time, the pump shuts off.
Note: Always correct the alarm condition before returning to normal
operation!
Safety Thermo Indicator Light. The Safety Thermo indicator light illuminates when the
unit is overheating. This is an alarm condition, so the audible alarm activates to notify you of
the safety thermo fault, and disables controller outputs, permitting the pump to continue to
circulate fluid to avoid damage.
Note: Always correct this alarm condition before returning to normal
operation!
Upright Portable Hot Oil TCUs
Chapter 4: Operation
27
Download from Www.Somanuals.com. All Manuals Search And Download.
High Level Indicator Light (Optional). The High Level indicator light illuminates when
the heat transfer fluid level in the reservoir tank is too high. Carefully remove just enough
fluid so this indicator light shuts off.
Low Level Indicator Light. The Low Level indicator light illuminates when the heat
transfer fluid level in the system is too low. This is an alarm condition, so the audible alarm
activates to notify you of the low fluid level fault, and the controller outputs are disabled.
Note: Always correct the alarm condition before returning to normal
operation!
4-3 Returning Fluid to the Tank
If you want to move the unit from one process to another (like mold changes), perform the
following steps to drain the mold and process lines.
Note: This procedure is just the opposite of the unit startup/air purge procedure.
1. Cool the heat transfer fluid to no more than 100°F (38ºC).
2. If so equipped, open the manual vent valve to add air into the pipes.
3. Press the PUMP STOP button.
4. Press and hold the PUMP REVERSE button.
The pump runs in reverse, drawing fluid from the mold and lines, then drains the
fluid into the reservoir tank.
5. Watch the sight glass to prevent overflow of the reservoir tank.
Caution!
The reservoir tank may not have adequate volume to contain the total
system capacity of fluid.
An overflowing reservoir allows hot fluid to escape and become a potential
fire and slip hazard.
The total capacity of the tank is 7 gallons (26.5 liters).
If it appears that the tank may overfill, connect a line from the FILL port of the reservoir tank
to a clean auxiliary container.
4-4 Shutting Down the Hot Oil TCU
1. Cool down the unit by switching the CONTROL MODE switch to the MAN. COOL
(manual cooling) position.
This step disables the heaters (prevents the controller from turning them on) and, if so
equipped, opens the Cool solenoid.
2. You can monitor fluid temperature on the controller display during cool-down.
Upright Portable Hot Oil TCUs
Chapter 4: Operation
28
Download from Www.Somanuals.com. All Manuals Search And Download.
When fluid temperature dips below 120ºF (49ºC), press the PUMP STOP button to
turn off the unit.
Upright Portable Hot Oil TCUs
Chapter 4: Operation
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 5: Maintenance
5-1 Maintenance Schedule
The checklist below contains a list of items which should be inspected and/or replaced to
keep your Portable Hot Oil TCU operating at peak efficiency. Perform each inspection at the
regular intervals listed below.
System model #
Serial #
Date/ Date/ Date/ Date/ Date/ Date/ Date/ Date/ Date/ Date/ Date/ Date/ Date/
Every week
By
By
By
By
By
By
By
By
By
By
By
By
By
Check fluid level.
add fluid as needed
Check connecting
lines, hoses, &
conectors for wear
or damage.
Every month Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Check for leaks at
pump seal,
gaskets, etc.
Check pump drive
V belt for wear.
Check reservoir
tank vent for
obstructions.
Next scheduled
inspection
Actual inspection
Date/By
Next scheduled
inspection
Actual inspection
Date/By
Every Quarter
Check the heat transfer
fluid for deterioration.
Do a routine check of the
fluid every 1,000 hours of
operation or every three (3)
months, whichever comes
first. Contact the Service
Department for information
on fluid testing
Next scheduled
inspection
Actual inspection
Date/By
Next scheduled
inspection
Actual inspection
Date/By
Every Six Months
Inspect electrical
connections for secure, tight
terminations and ground
connections. Inspect the
power cable at the entrance
point to the electrical
enclosure.
Check the mounting bolts on
the pump, the motor, and
the heater flange for
tightness
Remove the heat exchanger
tube bundle and check it for
lime and mineral deposits.
Carefully clean the bundle
as needed.
- Photocopy this page for your maintenance records -
Upright Portable Hot Oil TCUs
Chapter 5: Maintenance
30
Download from Www.Somanuals.com. All Manuals Search And Download.
5-2 Preventative Maintenance
WARNING! Make sure that your maintenance technicians comply with lock-out/tag-out procedures
during any servicing or maintenance of this unit and related equipment, per OSHA
article ART 1910.147.
Before you begin servicing this unit, disconnect all power to it, let the unit cool down
completely, and turn off the water.
Failure to follow these directives can result in serious injury or death!
Routine Servicing
Your hot oil temperature control unit requires little in preventive maintenance and servicing.
To keep it in good, reliable working order, make sure you follow the following scheduled
preventive maintenance procedures.
Keep surfaces clean and free of any excessive accumulations of dirt, oil, or debris. This is
especially true for the pump. It relies on free air circulation for proper cooling.
Check the motor air intake screen for any accumulation of dirt; clean it as needed.
Servicing the Unit Monthly or Every 500 Hours
• Lubricate the pump at the grease fittings with a high-quality lithium
grease rated at 400ºF (204ºC) or higher. Use only Dow-Corning #44 or
a high temperature grease rated at 400ºF or higher that is compatible
with Dow-Corning #44. Do not over-lubricate.
• Adjust the pump drive belt tension. Make sure that the motor pulley is
properly aligned with the pump pulley; use a straightedge to check.
Tighten motor mounting bolts after realignment.
• Inspect the screen in the Y strainer for accumulations of debris. Clean
as needed.
Servicing the Unit Every Three Months
Remove and clean the screen in the Y-strainer. Replace the screen if it is damaged.
Draining the Unit for Storage
You should thoroughly flush and drain the Upright unit if you need to take it out of service
for a long time, or if you expect it to become exposed to freezing temperatures. The
manufacturer recommends using a flushing fluid or equivalent for flushing your Upright unit;
follow unit flushing instructions that comes with the flushing fluid.
Drain plugs are provided at the base of the heater tank, reservoir tank, and on the pump. You
should also remove, drain, and reinstall the heat exchanger tube bundle before storage.
Preventative Pump Maintenance
You can extend the life of your pump and reduce the cost per gallon pumped if you perform a
few preventive maintenance procedures.
Lubricating the Pump
Using #2 ball bearing grease and a hand-operated grease gun, gently lubricate all grease
fittings after every 500 hours of operation or after 60 days, whichever comes first. If pump
service occurs in severe conditions, lubricate more frequently. Use an appropriate type of
grease for hot or cold applications.
Upright Portable Hot Oil TCUs
Chapter 5: Maintenance
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Adjusting End Clearance
After long periods of service, the running clearance between the end of the rotor teeth and
head may be increased from wear. The pump may lose some capacity of pressure as a result.
If you reset the end clearance, pump performance should improve.
Examining Internal Parts
Remove the head occasionally and examine the idler, bushing, head and pin for wear.
Replace the idler bushing and idler pin after moderate wear to avoid replacing more
expensive parts later.
Note: Make sure the idler doesn’t slide off the idler pin during head removal to avoid
damage and personal injury.
Cleaning the Pump
A clean pump is easier to inspect, lubricate, and adjust; it runs better and looks better!
5-3 Corrective Maintenance
Pumps and Seals
Each Upright unit is completely tested and calibrated before leaving the factory. The unit is
then cooled, drained, and packed for shipment.
If the unit stands idle for a long time before being installed in your factory, gaskets can dry
out and possibly leak when you start the unit. In most cases, these gaskets soon swell and
form a tight seal. If not, you may need to tighten the bolts to stop the leak.
Similarly, rough handling in shipping may sometimes cause minor leaks upon startup; you
may need to re-tighten bolts or fittings to stop the leak.
You should expect to periodically replace the pump seal. If the pump is properly lubricated
and used at moderate temperatures, the seal should last several years. The following section
describes the proper procedures for replacing the seal (Mechanical seal, part no. 162-00030-
160). Periodic replacement of the pump drive V-belt is also to be expected.
Note: If the pump motor wiring is disconnected for removal from the unit, you
must check the actual direction of rotation when the motor is rewired to the
unit. Consult Elementary Diagrams provided in unit for additional
information.
Upright Portable Hot Oil TCUs
Chapter 5: Maintenance
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintaining the Pump
Disassembling the Pump
WARNING! Before opening the pump chamber:
• Make sure that any pressure in the chamber has been completely
vented!
• Make sure that the motor cannot be inadvertently started while you
work on the pump!
Failure to follow these precautions may result in serious injury or death!
1. Mark the head and casing before disassembly to insure proper reassembly. The idler
pin, which is offset in the pump head, must be positioned toward and equal distance
between port connections to allow for proper flow of liquid through the pump.
2. Remove the head from the pump. Do not allow the idler to fall from the idler pin. To
prevent this from happening, tilt the top of the head back when removing. Avoid
damaging the head gasket.
3. Remove the idler and the bushing assembly.
4. Insert a length of hardwood or brass through the port opening between the rotor teeth
to keep the shaft from turning. Bend up the lockwasher tang with a spanner wrench.
Remove the locknut and lockwasher from the shaft.
5. Loosen Allen head setscrews in the face of the thrust bearing assembly. Remove the
thrust bearing assembly by threading out of the bracket.
6. Loosen the radial setscrews in the thrust bearing assembly and remove the end cap
using the spanner wrench.
7. Remove the bearing spacer collars and the ball bearing.
8. Using snap ring pliers, remove snap ring from shaft.
9. Remove two nuts holding seal gland plate and seal gland in place. Slide seal gland
off of the shaft being careful not to damage the lip seal.
10. Using a soft headed hammer, gently tap on the end of the rotor shaft until the rotor
and shaft assembly can be completely removed from the pump. Note the mechanical
seal may stick to the shaft causing initial resistance when the shaft is removed.
11. Remove the mechanical seal parts from the bracket.
12. Clean all parts thoroughly and examine for wear and damage. Check lip seals, ball
bearing, bushings and idler pin and replace if necessary. Check all other parts for
nicks, burrs, excessive wear and replace if necessary.
13. Wash bearings in clean solvent. Blow out bearings with compressed air. Do not allow
bearings to spin; turn them slowly by hand. Spinning bearings will damage race and
balls. Make sure bearings are clean, then lubricate with non-detergent SAE 30 weight
oil and check for roughness. Roughness can be determined by turning outer race by
hand.
14. Casing can be checked for wear or damage while mounted on bracket.
Upright Portable Hot Oil TCUs
Chapter 5: Maintenance
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Pump Assembly
The seal used in this pump is simple to install. If you take care during installation, good
performance will result.
The principle of the mechanical seal is to make contact between the rotary and stationary
members. These parts are lapped to a high finish, and their sealing effectiveness depends on
complete contact. When requesting special seal information, make sure that you give the
pump model number and serial number.
1. Install bracket bushing if required. If bracket bushing has a lubrication groove, install
bushing with groove at 6:00 o’clock position in bracket. If carbon graphite, Refer to
Installation of Carbon Graphite Bushings, page 43.
2. Coat shaft of rotor shaft assembly with non-detergent SAE 30 weight oil. Start end of
shaft in bracket bushing turning from right to left, slowly pushing rotor in casing.
3. Coat idler pin with non-detergent SAE 30 weight oil and place idler and bushing on
idler pin in head. If replacing with carbon graphite bushing, Refer to Installation of
Carbon Graphite Bushings, page 43.
4. Using a .010 to .015 inch head gasket, install head and idler assembly on pump.
Pump head and casing were marked before disassembly to insure proper reassembly.
If not, be sure idler pin, which is offset in pump head, is positioned toward and equal
distance between port connections to allow for proper flow of liquid through pump.
Tighten head capscrews evenly.
5. Place the mechanical seal installation tapered half rings over the shaft and apply P-80
oil supplied with the replacement seal, grease is not recommended on the sleeve and
rotor shaft. Slide the rotating portion of the mechanical seal on the shaft until it
bottoms on the shaft step. See FIGURE 7 in Appendix. Remove the seal installation
tapered half rings. It is important when using the rings to make sure the thin edge is
facing the direction of the shaft end, and that the thick end is facing the rotor.
6. Apply lubricant to the seal seat o-ring and push it in the bracket. Note the shinny
side of the seat goes towards the carbon graphite seal face.
7. Apply Dow Corning #44 high temperature silicon grease to the lip seal area in the
seal gland and install on the shaft. Install the seal gland plate and secure with two
nuts.
8. Pack ball bearing with Dow Corning #44 high temperature silicon grease and install
in the thrust bearing housing. Place bearing spacer collars inside the lip seals.
Thread the end cap into the bearing housing and tighten with a spanner wrench.
Tighten the radial set screws that lock the end cap in place.
9. Using the snap ring pliers, install the snap ring onto the shaft.
10. Thread the thrust bearing assembly into the bracket. Turn in until hand tight. This
forces the rotor against the head.
11. Put lockwasher and locknut on shaft. Insert length of hardwood or brass through port
opening between rotor teeth to keep shaft from turning. Tighten locknut to 50 – 70
ft.-lbs. torque and bend one tang of lockwasher into slot.
12. Adjust pump end clearance. Refer to section on Thrust Bearing Adjustment.
13. Lubricate all grease fittings with Dow Corning #44 high temperature silicon grease.
Upright Portable Hot Oil TCUs
Chapter 5: Maintenance
34
Download from Www.Somanuals.com. All Manuals Search And Download.
Thrust Bearing Adjustment
1. Loosen axial setscrews in face of end cap on the thrust bearing assembly. If rotor
shaft cannot be turned by hand, back off the thrust bearing assembly until there is a
noticeable drag of the shaft. Note mechanical seal will provide some drag and this is
a normal condition. The thrust bearing assembly must be turned in until it can just be
turned over by hand. This ensures the rotor is against the head and a zero end
clearance condition exists.
2. Make a mark on the OD of the bearing housing and a corresponding mark on the
bracket. Back off thrust bearing housing the required number of marks or distance on
the OD as shown below.
3. Tighten the axial setscrews in the face of the thrust bearing assembly. Make sure the
rotor shaft turns freely. If it does not, repeat steps 1 and 2.
PUMP
SIZE
Turn Outer End Cap C.C.W.
No. of Notches*
or Length on O.D., Inches
G
HL, HV
KK
-
0.75"
1"
6
10
1.38"
*Each small notch on outer end cap represents .001 inch end clearance.
WARNING! Before starting the pump, make sure that all drive equipment guards are in place!
Failure to properly install the guards may result in serious injury or death!
Installation of Carbon Graphite Bushings
When installing carbon graphite bushings, extreme care must be taken to prevent breaking.
Carbon graphite is a brittle material and easily cracked. If cracked, the bushing will quickly
disintegrate. Using a lubricant and adding a chamfer on the bushing and the mating part will
help in installation. The additional precautions listed below must be followed for proper
installation:
1. A press must be used for installation.
2. Be certain bushing is started straight.
3. Do not stop pressing operation until bushing is in proper position. Starting and
stopping will result in a cracked bushing.
4. Check bushing for cracks after installation.
Carbon graphite bushings with extra interference fits are frequently furnished for high
temperature operation. These bushings must be installed by a shrink fit.
1. Heat bracket or idler to 750°F.
2. Install cool bushings with a press.
3. If facilities are not available to reach 750°F. temperature, it is possible to install with
450°F. temperature; however, the lower the temperature, the greater the possibility of
cracking the bushing.
Upright Portable Hot Oil TCUs
Chapter 5: Maintenance
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 6: Troubleshooting
6-1 Introduction
The utmost in safety precautions should be observed at all times when working on or around
the machine and the electrical components. All normal trouble-shooting must be
accomplished with the power off, line fuses removed, and with the machine tagged as out of
service.
The use of good quality test equipment cannot be over-emphasized when troubleshooting is
indicated. Use a good ammeter that can measure at least twice the AC and DC current that
can be encountered for the machine. Be sure that the voltmeter has at least minimum
impedance of 5,000 OHMS-per-volt on AC and 20,000 OHMS-per-volt on DC scales.
Popular combination meters, VOM and VTVM can be selected to provide the necessary
functions.
Before making haphazard substitutions and repairs when defective electrical components are
malfunctioning, we recommend that you check the associated circuitry and assemblies for
other defective devices. It is common to replace the obviously damaged component without
actually locating the real cause of the trouble. Such hasty substitutions will only destroy the
new component. Refer to wiring diagrams and schematics.
Locating mechanical problems, should they occur, is relatively straightforward. When
necessary, refer to the parts catalog section.
Problem
Possible cause
Corrective action
Increase size of connectors/
water lines.
Undersized connectors/lines.
Long connecting lines between
unit and mold.
Move the unit closer to the mold
and shorten connecting lines.
Connect lines for parallel flow
instead of series flow.
Check mold for metal chips or
deposits. Clean mold.
Remove and replace fitting or
valve.
Serpentine flow through mold.
Blocked line in mold.
Temperature fluctuations/rapid
cycling from hot to cold.
Quick disconnect fitting with
check valve.
Carbon build-up in unit piping
or fittings.
Clean or replace affected piping.
Replace fluid.
Check unit by opening the
manual bypass to determine if
the TCU contols the set point
temperature.
Faulty TCU.
Switch Return and Delivery
probes.
Reversed probes.
Upright Portable Hot Oil TCUs
Chapter 6: Troubleshooting
36
Download from Www.Somanuals.com. All Manuals Search And Download.
Problem
Possible cause
Corrective action
Check all lines/connections/
fittings.
Loss of fluid in process.
Allow vent timer to run out; or,
check valve operation when unit
is cold by opening the fill port.
Switch to Manual Cool mode
several times to flush valve. If
Vent valve open.
Unit does not heat properly/can
not achieve set point.
Faulty/dirty solenoid valve;
usually detected when there is a the leak continues, disconnect
steady stream or trickle of water the power to the unit, turn off
out of the drain line.
the water supply, and clean or
replace the solenoid.
Degraded fluid.
Drain and replace fluid.
Visual inspection of coil and
contacts. Repair/replace
Defective heater contactor.
defective contactors.
Check resistance on all three (3)
legs of heater with an ohmmeter.
If not all equal, contact factory
for replacement heater.
Check heater tank for scorched/
discolored paint. Check
resistance on all three (3) legs of
heater with an ohmmeter.
Replace heater as needed.
Check the heater output with an
ohmmeter to ground. It should
read in the mega-ohm range.
Infinite or zero readings indicate
a defective output.
Defective immersion heater.
Heater burnout.
Unit does not heat.
Controller heater output open.
Clogged Y strainer.
Water supply to unit is turned
OFF.
Clean Y strainer.
Open water supply.
Water drain is plugged or
excessive back pressure in drain
line.
Clear drain line or eliminate
back pressure condition.
Unit overheats/unable to cool.
Heat exchanger tubes plugged
by lime deposits.
Remove tube bundles; clean/
replace as required.
Test solenoid valve by switching
to Manual Cool mode and listen
for valve operation. Replace if
faulty.
Faulty solenoid valve.
Upright Portable Hot Oil TCUs
Chapter 6: Troubleshooting
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Problem
Possible cause
Corrective action
Inspect/replace faulty line or
connection.
Leaks in connecting lines.
Perform venting sequence in
Chapter 3.
Air in circulating lines.
Check fluid level in sight glass.
Add fluid if required.
See Chapter 3.
Low fluid.
Defective Ful-Flo valve.
Drain water from low point in
piping (see Chapter 3), or boil
water off.
Allow vent timer to run out; or,
check valve operation when unit
is cold by opening the fill port.
Check motor; rewire if
necessary. See electrical
diagrams.
Water in fluid.
Rapid drop in pressure/no
pressure.
Vent solenoid open.
Pump running in reverse.
Adjust head spacing or replace
worn pump components.
Replace as required.
Pump repair/adjustment needed.
V belt broken/worn.
Drain water from low point in
piping (see Chapter 3), or boil
water off.
Water in fluid.
Noisy pump.
Drain and flush system. Replace
fluid.
Severely degraded fluid.
Upright Portable Hot Oil TCUs
Chapter 6: Troubleshooting
38
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 7: Appendix
7-1 Optional Components
The following is a list of options which your portable hot oil tcu may have been equipped
with:
• Drain valve
• Hour meter; measures total pump run time hours
• General fault visual alarm
• Autovent sequence; deducts available
• Low level alarm; deducts available
• High level indicator light
• Manual bypass; deducts available
• M2B+ microprocessor controller options include:
• 4-20 mA remote set point and retransmission
• SPI protocol, RS-485
• General protocols, types RS-232, -485
• Remote sensor; 10 Ft. (3m)
• Heat exchanger options of 3.9 sq. ft. (0.3627 sq. m) and 6.7 sq. ft. (0.6231 sq. m)
• Remote controller
• Lexan cover
• Optional operating voltages of 208/3/60, 230/3/60, 575/3/60, 380/3/50, and 415/3/50
Upright Portable Hot Oil TCUs
Chapter 7: Appendix
39
Download from Www.Somanuals.com. All Manuals Search And Download.
7-2 Technical Specifications
Annex B Information
The following design information is provided for your reference:
1. No modifications are allowed to this equipment that could alter the CE compliance
2. Ambient temperature:
3. Humidity range:
4. Altitude:
40 degrees Celsius – Maximum (104 degrees Fahrenheit)
50% relative humidity
Sea level
5. Environment:
6. Radiation:
Clean, dust-free and non-explosive
None
7. Vibration:
Minimal, i.e. machine mounting
8. Allowable voltage fluctuation:
9. Allowable frequency fluctuation:
10. Intermittent
+/- 10%
Continuous
+/- 2%
+/- 1%
11. Nominal supply voltage:
460/3/60 (Verify on serial number tag)
12. Earth ground type:
protective conductor)
TN (system has one point directly earthed through a
13. Power supply should include a ground connection.
14. Over-current protection is supplied in the tcu, but additional protection should be
supplied by the user.
15. The door-mounted disconnect serves as the electrical disconnect device.
16. Tcu is not equipped with local lighting.
17. Functional identification
18. Tcu is equipped with a CE mark
19. Tcu is supplied with an operating manual in the language of the destination country.
20. Cable support may be required for power cord, depending on final installation.
21. No one is required to be in the interior of the electrical enclosure during the normal
operation of the unit. Only skilled electricians should be inside the enclosure for
maintenance.
22. Doors can be opened with a screwdriver, but no keys are required.
23. Two-hand control is not required or provided.
24. All tcus should be moved around and set in a place with a lift truck or equivalent.
25. There are no frequent repetitive cycles that require manual control⎯repetitive
functions are automatic while the tcu is operating.
26. An inspection report detailing the functional test is included with the tcu.
27. The machine is not equipped with cableless controls.
28. Color-coded (harmonized) power cord is sufficient for proper installation.
Upright Portable Hot Oil TCUs
Chapter 7: Appendix
40
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 6: Upright Series Hot Oil Portable Temperature Control Unit
Upright Series Temperature Control Unit Specifications
Model number
Upright-
1.5
1
2
3
Full load amps; 460/3/60 VAC
12 kW heater
18 kW heater
24 kW heater
36 kW heater
48 kW heater
17
25
32
47
62
18
26
33
48
63
19
27
34
49
64
20
28
35
50
65
Reservoir capacity in gallons / liters
TEFC pump
17 gallons each zone c
hp (kW)
Flow
1 (0.75)
1.5 (1.1)
2 (1.5)
24
3 (2.2)
50
227
50
5.4
1.5”
gpm
lpm
psig
bar
18
68
91
Pressure
30
2
50
3.4
1”
30/50
2/5.4
Connection size in inches
Dimensions in inches / (mm)
Shipping weight in lbs. / Kg
Height
Width
Depth
62 (1,575)
24 (610)
34 (864) < 24 kW
44 (1,118) > 24 KW
700
850
< 24 kW
950
1,050
> 24 KW
c
Each zone requires 15 gallons minimum to run properly.
Upright Portable Hot Oil TCUs
Chapter 7: Appendix
41
Download from Www.Somanuals.com. All Manuals Search And Download.
7-3 Drawings and Diagrams
Figure 7: 18-24 GPM Pump Construction 075-00370-02
Upright Portable Hot Oil TCUs
Chapter 7: Appendix
42
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 8: Thrust Bearing Assembly
Upright Portable Hot Oil TCUs
Chapter 7: Appendix
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 9: Belt Tensioning Instructions
Upright Portable Hot Oil TCUs
Chapter 7: Appendix
44
Download from Www.Somanuals.com. All Manuals Search And Download.
7-4 Spare Parts List
Immersion Heaters
Part number
Description
722-00138-07 HTR, IMM, 12 KW, 208 V, 3”, 6 ELE
722-00138-08 HTR, IMM, 12 KW, 240 V, 3”, 6 ELE
722-00138-09 HTR, IMM, 12 KW, 380 V, 3”, 6 ELE
722-00138-10 HTR, IMM, 12 KW, 415 V, 3”, 6 ELE
722-00138-11 HTR, IMM, 12 KW, 480 V, 3”, 6 ELE
722-00138-12 HTR, IMM, 12 KW, 600 V, 3”, 6 ELE
Note: 6KW heaters are modified 12 kW heaters; jumpers are remove from one leg.
Heater Gasket
Part number
542-00007-08 GASKET, FLANGE, 3
Description
Description
Description
Heater Tank
Part number
572-87548-00 TANK, HEATER, Upright, 3½
Manual Reset Safety Thermostat
Part number
724-00041-00 THERMOSTAT, 200ºF — 550ºF
Note: Please give model and serial numbers when ordering parts. Prices are subject to change without
notice.
Pressure Gauge
Part number
Description
037-00119-00 GAUGE, PRESSURE, 0 — 100 PSI
Optional Heat Exchangers; Tube Bundle Only
Ass’y. part no. Tube bundle only part no.
Description
106-00267-00
106-00268-00
162-00047-10
162-00047-11
3.9 SQ. FT. Upright 550°F
6.7 SQ. FT. Upright 550°F
Pilot Lights
Part number
Description
715-10074-00 PILOT, LED, 120 V, RED, N-12, 36”, LEAD
715-10075-00 PILOT, LED, 120 V, AMBER, N-12, 36”, LEAD
715-10076-00 PILOT, LED, 120 V, GREEN, N-12, 36”, LEAD
Casters
Part number
Description
042-00016-00 CASTER, SWIVEL, 3”
042-00017-00 CASTER, STATIONARY, 3”
Upright Portable Hot Oil TCUs
Chapter 7: Appendix
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Manual Reset Safety Thermostat
Part number
724-00041-00 THERMOSTAT, 200ºF — 550ºF
Description
Description
Sight Glass Assembly
Part number
037-00046-00 GLASS, SIGHT, 15¾
Note: Please give model and serial numbers when ordering parts. Prices are subject to change without
notice.
Controllers
Part number
601-00521-06 CONTROLLER, M2B, 550ºF
724-00589-01 CONTROLLER, STERLCO 4000
Description
Description
Selector Switches and Push Buttons
Part number
721-01028-00 PUMP STOP
721-01027-00 PUMP START
721-01026-00 ALARM SILENCE
717-01016-00 MODE SELECT
721-01026-00 VENT
721-01029-00 PUMP REVERSE
717-10055-00 HALF-FULL HEAT, LOCAL-REMOTE (OPTIONAL)
Pressure Switches
Part number
733-00029-00 SWITCH, PRESSURE
Description
Description
Pump
Part number
075-00370-01 MECH. SEAL, VIKING HL4125 (0-30 GPM)
Motors
Part number
Description
720-09240-00 MOTOR, 1 HP 3/60/208, 230, 460 V
720-09242-00 MOTOR, 1½ HP 3/60/208, 230, 460 V
720-09218-00 MOTOR, 2 HP 3/60/208, 230, 460 V
Note: Please give model and serial numbers when ordering parts. Prices are subject to change without
notice.
Upright Portable Hot Oil TCUs
Chapter 7: Appendix
46
Download from Www.Somanuals.com. All Manuals Search And Download.
Solenoid Valves
Part number
Description
732-00007-03 ¼” VALVE, 115 V COIL (0-125 PSI, 300°F)
732-00013-01 ¾” VALVE, 115 V COIL (0-125 PSI, 300°F)
Sensing Probe Equipment
Part number
Description
692-07369-05 HEAT & COOL, M2B
701-00003-00 TYPE ‘I’ THERMOCOUPLE
Disconnect Switches
Part number
Description
728-00153-00 SWITCH, DISCONNECT, 45 AMP
728-00168-00 SWITCH, DISCONNECT, 100 AMP
Heater Tank Insulation
Part number
Description
542-88062-00 INSULATION, TANK, HEATER
Ful-Flo Relief Valves
Part number
Description
044-00239-00 VALVE, RELIEF, FUL-FLO, 1”
Breather Cap
Part number
Description
161-00072-00 CAP, BREATHER, 1”
Note: Please give model and serial numbers when ordering parts. Prices are subject to change without
notice.
Upright Portable Hot Oil TCUs
Chapter 7: Appendix
47
Download from Www.Somanuals.com. All Manuals Search And Download.
7-5 Returned Material Policy
Credit Returns
Prior to the return of any material authorization must be given by the manufacturer. A
RMA number will be assigned for the equipment to be returned.
Reason for requesting the return must be given.
ALL returned material purchased from the manufacturer returned is subject to 15% ($75.00
minimum) restocking charge.
ALL returns are to be shipped prepaid.
The invoice number and date or purchase order number and date must be supplied.
No credit will be issued for material that is not within the manufacturer’s warranty period
and/or in new and unused condition, suitable for resale.
Warranty Returns
Prior to the return of any material, authorization must be given by the manufacturer. A
RMA number will be assigned for the equipment to be returned.
Reason for requesting the return must be given.
All returns are to be shipped prepaid.
The invoice number and date or purchase order number and date must be supplied.
After inspecting the material, a replacement or credit will be given, at the manufacturer’s
discretion. If the item is found to be defective in materials or workmanship, and it was
manufactured by our company, purchased components are covered under their specific
warranty terms.
7-6 Safety Tag Information
TCU Safety Tags
Hot!
Read Operation
and Installation
Manual
High Voltage
Earth Ground
Inside Enclosure
PE Protected Earth
Ground
Lifting Point
Upright Portable Hot Oil TCUs
Chapter 7: Appendix
48
Download from Www.Somanuals.com. All Manuals Search And Download.
7-7 TCU Identification (Serial Number) Tag
(Located on back of TCU)
Company Logo
XXX Series TCU
Model Number XXX-030
Max Heating/Cooling Capacity HR
460V
1Ǿ
Serial Number 060701R
Date of Manufacture 06/2003
4.5A
Over-current Protection Device (s) 4.5A Total
Frequency 50/60Hz
Compressed air supply None
TCU Mass 400 lbs/(180 KG)
Electrical Diagrams &
Pneumatic Diagram
Street Address
City, State Zip Code
Telephone Number
7-8 Technical Assistance
Parts Department
[
]
[262]
Call toll-free 7am–5pm CST 800 423-3183 or call 641-8610, Fax [262] 641-8653
The ACS Customer Service Group will provide your company with genuine OEM quality parts
manufactured to engineering design specifications, which will maximize your equipment’s performance
and efficiency. To assist in expediting your phone or fax order, please have the model and serial
number of your unit when you contact us. A customer replacement parts list is included in this manual
for your convenience. ACS welcomes inquiries on all your parts needs and is dedicated to providing
excellent customer service.
Service Department
[
]
[
] 641-8610
Call toll-free 8am–5pm CST 800 423-3183 or call 262
[
]
Emergencies after 5pm CST, call 847 439-5655
We have a qualified service department ready to help. Service contracts are available for most of our
products.
Sales Department
[
] 641-8610
Call 262
Monday–Friday, 8am–5pm CST
Our products are sold by a world-wide network of independent sales representatives. Contact our Sales
Department for the name of the sales representative nearest you.
Contract Department
[
] 641-8610
Call 262
Monday–Friday, 8am–5pm CST
Let us install your system. The Contract Department offers any or all of these services: project planning;
system packages including drawings; equipment, labor, and construction materials; and union or non-
union installations.
Upright Portable Hot Oil TCUs
Chapter 7: Appendix
49
Download from Www.Somanuals.com. All Manuals Search And Download.
|