Instruction Manual
resIdentIal Gas water heaters
Gas Models power vent Gs675YrvIt and Gs675hrvIt
wIth hot surface IGnItIon
www.statewaterheaters.com
Thank you for buying this energy efficient water heater. We
appreciate your confidence in our products.
You should thoroughly read this manual before installation and/
or operation of this water heater. Please pay particular attention
to the important safety and operating instructions as well as the
WARNINGS and CAUTIONS.
• for Your safety •
AN ODORANT IS ADDED TO THE GAS USED
BY THIS WATER HEATER.
all technIcal and warrantY questIons: SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS
PURCHASED. IF YOU ARE UNSUCCESSFUL, PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER.
Keep thIs Manual In the pocKet on heater for future reference
whenever MaIntenance adjustMent or servIce Is requIred.
PRINTED IN THE U.S.A 0708
197218-002
Download from Www.Somanuals.com. All Manuals Search And Download.
General safetY
3
Download from Www.Somanuals.com. All Manuals Search And Download.
General safetY
4
Download from Www.Somanuals.com. All Manuals Search And Download.
taBle of contents
SAFE INSTALLATION, USE AND SERVICE.................................. 2
Installation of Vent System...............................................18-21
Vent Pipe Preparation......................................................21-22
LIGHTING & OPERATING LABEL...............................................23
TEMPERATURE REGULATION ..................................................24
FOR YOUR INFORMATION.........................................................25
Start Up Conditions
GENERAL SAFETY.....................................................................3-4
TABLE OF CONTENTS.................................................................. 5
INTRODUCTION............................................................................ 5
Preparing for the Installation................................................... 5
INSTALLATION REQUIREMENTS FOR THE
COMMONWEALTH OF MASSACHUSETTS................................. 6
TYPICAL INSTALLATION............................................................7-8
LOCATING THE NEW WATER HEATER.................................. 9-11
Facts to Consider About Location......................................9-10
Insulation Blankets................................................................ 10
Combustion Air and Ventilation for Appliances
Smoke/Odor..................................................................25
Thermal Expansion .......................................................25
Strange Sounds ............................................................25
Operational Conditions .........................................................25
Smelly Water.................................................................25
“Air” in Hot Water Faucets.............................................25
High Temperature Shut Off System...............................25
PERIODIC MAINTENANCE....................................................26-28
Venting System Inspection....................................................26
Burner Operation and Inspection..........................................26
Burner Cleaning....................................................................26
Housekeeping..................................................................26-27
Anode Rod Inspection...........................................................27
Temperature-Pressure Relief Valve Operation .....................27
Draining.................................................................................27
Service..................................................................................28
LEAKAGE CHECKPOINTS..........................................................28
REPAIR PARTS............................................................................29
TROUBLESHOOTING ............................................................30-32
WARRANTY.................................................................................35
Located in Unconfined Spaces............................................. 10
Combustion Air and Ventilation for Appliances
Located in Confined Spaces............................................ 10-11
INSTALLING THE WATER HEATER.......................................12-22
Chemical Vapor Corrosion.................................................... 12
Water Piping ....................................................................12-13
Temperature-Pressure Relief Valve ...................................... 13
Gas Piping ............................................................................ 14
Sediment Traps..................................................................... 15
Filling the Water Heater ........................................................ 15
Venting.................................................................................. 15
Vent Pipe Termination......................................................15-16
Planning the Vent System................................................16-17
Condensate........................................................................... 17
Blower Assembly Installation ...........................................17-18
IntroductIon
thank You for purchasing this water heater. Properly installed and
maintained, it should give you years of trouble free service.
installations should comply with the National Fuel Gas Code (ANSI
Z223.1/NFPA 54) and the National Electrical Code (NFPA 70).
These publications are available from The National Fire Protection
Association, 1 Batterymarch Park, Quincy, MA 02269.
Abbreviations Found In This Instruction Manual:
• ANSI - American National Standards Institute
• NFPA - National Fire Protection Association
• ASME - American Society of Mechanical Engineers
• GAMA - Gas Appliance Manufacturer’s Association
• UL - Underwriters Laboratories Inc.
3. The water heater when installed must be grounded in accordance
with the local codes, or in the absence of local codes: the National
Electrical Code (NFPA 70).
4. If after reading this manual you have any questions or do not
understand any portion of the instructions, call the local gas utility
or the manufacturer whose name appears on the rating plate.
This gas-fired water heater is design certified by Underwriters
Laboratories Inc. under American National Standard for Gas Water
Heaters ANSI Z21.10.3 (current edition).
5. Carefully plan the place where you are going to put the water
heater. Correct combustion, vent action, and vent pipe installation
are very important in preventing death from possible carbon
monoxide poisoning and fires, see Figures 1 and 2.
preparInG for the InstallatIon
Examine the location to ensure the water heater complies with
the “Locating the New Water Heater” section in this manual.
1. Read the “General Safety” section, page 3 and 4 of this manual
first and then the entire manual carefully. If you don’t follow the
safety rules, the water heater will not operate properly. It could cause
DEATH, SERIOUS BODILY INJURY AND/OR PROPERTY DAMAGE.
6. For California installation this water heater must be braced,
anchored, or strapped to avoid falling or moving during an
earthquake. See instructions for correct installation procedures.
Instructions may be obtained from California Office of the State
Architect, 400 P Street, Sacramento, CA 95814.
This manual contains instructions for the installation, operation,
and maintenance of the gas-fired water heater. It also contains warnings
throughout the manual that you must read and be aware of.All warnings
and all instructions are essential to the proper operation of the water
heater and your safety. Since we cannot put everything on the first few
pages, read the entIre Manual Before atteMptInG
to Install or operate the water heater.
7. Massachusetts Code requires this water heater to be installed in
accordance with Massachusetts 248-CMR 2.00: State Plumbing
Code and 248-CMR 5.00. For more information see next page.
2. The installation must conform with these instructions and the local
code authority having jurisdiction. In the absence of local codes,
8. Complies with SCAQMD rule #1146 and districts having equivalent
NOx requirements.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
InstallatIon requIreMents for the coMMonwealth of Massachusetts
For all side wall terminated, horizontally vented power vent, direct vent, and power direct vent gas fueled water heaters installed
in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by
the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the
area of the venting, including but not limited to decks and porches, the following requirements should be satisfied:
InstallatIon of carBon MonoXIde detectors At the time of installation of the side wall horizontal vented gas fu-
eled equipment, the installing plumber or gasfitter should observe that a hard wired carbon monoxide detector with an alarm
and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber
or gasfitter should observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each
additional level of the dwelling, building or structure served by the sidewall horizontal vented gas fueled equipment. It should
be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard
wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired
carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner should
have a period of thirty (30) days to comply with the above requirements provided that during said thirty (30) day period, a bat-
tery operated carbon monoxide detector with an alarm should be installed.
approved carBon MonoXIde detectors Each carbon monoxide detector as required in accordance with the above
provisions should comply with NFPA 720 and be ANSI/UL 2034 listed and CSA certified.
sIGnaGe A metal or plastic identification plate should be permanently mounted to the exterior of the building at a minimum
height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating
appliance or equipment. The sign should read, in print size no less than one-half (1/2) inch in size, “Gas vent dIrectlY
Below. Keep clear of all oBstructIons.”
InspectIon The state or local gas inspector of the side wall horizontally vented gas fueled equipment should not approve
the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance
with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
eXeMptIons: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54
as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the
dwelling, building, or structure used in whole or in part for residential purposes.
Manufacturer requIreMents - Gas equIpMent ventInG sYsteM provIded When the manufacturer of Product
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with
the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system should
include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
Manufacturer requIreMents - Gas equIpMent ventInG sYsteM not provIded When the manufacturer of
a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases,
but identifies “special venting systems,” the following requirements should be satisfied by the manufacturer:
1. The referenced “special venting system” instructions should be included with the appliance or equipment installation
instructions; and
2. The “special venting systems” should be Product Approved by the Board, and the instructions for that system should include
a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting
instructions, all parts lists for venting instructions, and/or all venting design instructions should remain with the appliance or
equipment at the completion of the installation.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
tYpIcal InstallatIon
(a) vent pIpe
(o) Inlet dIp tuBe
(p) teMperature and
pressure relIef valve
(q) ratInG plate
(r) InsulatIon
(s) vent terMInal
(t) draIn valve
(u) IGnIter and MaIn
Burner
replaceMent parts and delIMInG products
(B) anode
(c) hot water outlet
(d) outlet (120 vac)
(e) flue Baffle
(f) Gas supplY
(G) MaIn Manual Gas
shut off valve
(h) Ground joInt unIon
(j) dIrt leG
(K) outer door
(l) unIon
Replacement parts and recommended delimer may be ordered
through authorized servicers or distributors. Refer to the Yellow
Pages for where to call or contact the water heater manufacturer
at, 500 Tennessee Waltz Parkway, Ashland City, TN 37015. When
ordering parts, provide complete model and serial numbers (see rating
plate), quantity and name of part desired, see Figure 1. Standard
hardware items may be purchased locally.
(v) flue
(w) Metal draIn pan
(X) control
(M) Inlet water shut
off valve
(n) cold water Inlet
(Y) control harness*
(Z) Motor & Blower
(aa) condensate fIttInG
vacuuM relIef valve
*Install per local
codes
Install therMal eXpansIon
tanK If water heater Is
Installed In a closed
water sYsteM.
teMperature IndIcators
teMperature adjustMent Buttons
(u) natural Gas MaIn Burner
wIth IGnIter asseMBlY
(u) propane Gas MaIn Burner
wIth IGnIter asseMBlY
(sIde vIew)
fIGure 1.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
tYpIcal InstallatIon
MIXInG valve usaGe
fIGure 2.
This appliance has been design certified as complying withAmerican
National Standard for water heaters and is considered suitable for:
HOTTER WATER CAN SCALD:
Water heaters are intended to produce hot water. Water heated to a
temperature which will satisfy space heating, clothes washing, dish
washing, and other sanitizing needs can scald and permanently injure
you upon contact. Some people are more likely to be permanently
injured by hot water than others. These include the elderly, children,
the infirm, or physically/mentally handicapped. If anyone using hot
water in your home fits into one of these groups or if there is a local
code or state law requiring a certain temperature water at the hot
water tap, then you must take special precautions. In addition to
using the lowest possible temperature setting that satisfies your
hot water needs, a means such as a Mixing Valve should be used
at the hot water taps used by these people or at the water heater.
Mixing valves are available at plumbing supply or hardware stores.
Consult a Qualified Installer or Service Agency. Follow mixing valve
manufacturer’s instructions for installation of the valves. Before
changing the factory setting on the thermostat, read the “Temperature
Regulation” section in this manual, see Figure 21.
water (potable) heating and space heating: All models are
considered suitable for water (potable) heating and space heating.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
locatInG the new water heater
facts to consIder aBout the locatIon
Carefully choose an indoor location for the new water heater, because
the placement is a very important consideration for the safety of the
occupants in the building and for the most economical use of the
appliance. this water heater is not for use in manufactured
(mobile) homes or outdoor installation.
Whether replacing an old water heater or putting the water heater in
a new location, the following critical points must be observed:
1. Select a location indoors as close as practical to the vent terminal or
locationtowhichthewaterheaterventpipingisgoingtobeconnected,
and as centralized with the water piping system as possible.
2. Selected location must provide adequate clearances for servicing
and proper operation of the water heater.
Installation of the water heater must be accomplished in such a manner
that if the tank or any connections should leak, the flow will not cause
damage to the structure. For this reason, it is not advisable to install
the water heater in an attic or upper floor. When such locations cannot
be avoided, a suitable metal drain pan should be installed under the
water heater. Drain pans are available at your local hardware store.
Such a drain pan must have a clearance of at least 1.0” (2.5cm)
greater than any point on the water heater’s outer jacket and must
be piped to an adequate drain. The pan must not restrict combustion
air flow. For example, if a circular pan is used, it must be a minimum
of 27” (69cm) in diameter, see Figure 1.
Water heater life depends upon water quality, water pressure and
the environmentinwhichthewaterheaterisinstalled.Waterheatersare
sometimes installed in locations where leakage may result in property
damage, even with the use of a drain pan piped to a drain. However,
unanticipated damage can be reduced or prevented by a leak detector or
water shut-off device used in conjunction with a piped drain pan.These
devices are available from some plumbing supply wholesalers and
retailers, and detect and react to leakage in various ways:
• Sensors mounted in the drain pan that trigger an alarm or turn off the
incoming water to the water heater when leakage is detected.
• Sensors mounted in the drain pan that turn off the water supply to
the entire home when water is detected in the drain pan.
• Water supply shut-off devices that activate based on the water
pressure differential between the cold water and hot water pipes
connected to the water heater.
• Devices that will turn off the gas supply to a gas water heater while
at the same time shutting off its water supply.
INSTALLATIONS IN AREAS WHERE FLAMMABLE LIQUIDS
(VAPORS) ARE LIKELY TO BE PRESENT OR STORED
(GARAGES, STORAGE AND UTILITY AREAS, ETC.): Flammable
liquids (such as gasoline, solvents, propane (LP or butane, etc.) and
other substances (such as adhesives, etc.) emit flammable vapors
which can be ignited by a gas water heater’s hot surface igniter or
main burner. The resulting flashback and fire can cause death or
serious burns to anyone in the area.
This water heater must not be installed directly on carpeting. Carpeting
must be protected by metal or wood panel beneath appliance extending
beyond full width and depth of appliance by at least 3” (7.6 cm) in any direction,
or if appliance is installed in an alcove or closet, entire floor must be covered
by the panel. Failure to heed this warning may result in a fire hazard.
Also, the water heater must be located and/or protected so it is not
subject to physical damage by a moving vehicle.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Propellants of aerosol sprays and volatile compounds (cleaners,
chlorine based chemicals, refrigerants, etc.), in addition to being highly
flammable in many cases, will also react to form corrosive hydrochloric
acid when exposed to the combustion products of the water heater.
The results can be hazardous, and can also cause product failure.
InsulatIon BlanKets
Insulation blankets are available to the general public for external use
on gas water heaters but are not necessary with these products. The
purpose of an insulation blanket is to reduce the standby heat loss
encountered with storage tank heaters. Your water heater meets or
exceeds the Energy Policy Act standards with respect to insulation and
standby loss requirements, making an insulation blanket unnecessary.
Minimum clearances between the water heater and combustible
construction are 0 inch at the sides and rear, 5.5” (14.0 cm) from the
front and 12” (30.5 cm) from the top (standard clearance). If clearances
stated on the heater differ from standard clearances, install water
heater according to clearances stated on the heater.
Should you choose to apply an insulation blanket to this heater, you
should follow these instructions (for identification of components
mentioned below, see Figure 1). Failure to follow these instructions
can restrict the air flow required for proper combustion, potentially
resulting in fire, asphyxiation, serious personal injury, or death.
Adequate clearance 24” (61.0 cm) for servicing this appliance should
be considered before installation, such as changing the anodes, etc.
A minimum clearance of 5.5” (14.0 cm) must be allowed for access to
replaceable parts such as the thermostats, drain valve and relief valve.
When installing the heater, consideration must be given to proper
location. Location selected should be as close to the wall as practicable
and as centralized with the water piping system as possible.
• Do not apply insulation to the top of the water heater, as this will
interfere with safe operation of the blower assembly.
• Do not cover outer door, thermostat or temperature & pressure relief valve.
• Do not allow insulation to come within 2” (5.1 cm) of the floor to
prevent blockage of combustion air flow to the burner.
• Do not cover the instruction manual. Keep it on the side of the
water heater or nearby for future reference.
• Do obtain new warning and instruction labels from the manufacturer
for placement on the blanket directly over the existing labels.
• Do inspect the insulation blanket frequently to make certain it
does not sag, thereby obstructing combustion air flow.
fIGure 3.
fIGure 4.
Agas water heater cannot operate properly without the correct amount
of air for combustion. Do not install in a confined area such as a closet,
unless you provide air as shown in the “Locating The New Water
Heater” section. Never obstruct the flow of ventilation air. If you have
any doubts or questions at all, call your gas supplier. Failure to provide
the proper amount of combustion air can result in a fire or explosion
and cause death, serious bodily injury, or property damage.
coMBustIon aIr and ventIlatIon for
applIances located In unconfIned spaces
unconfIned space is space whose volume is not less than
50 cubic feet per 1,000 Btu per hour (4.8 cubic meters per kW) of the aggregate
input rating of all appliances installed in that space. Rooms communicating
directly with the space in which the appliances are installed, through openings
not furnished with doors, are considered a part of the unconfined space.
In unconfined spaces in buildings, infiltration may be adequate to
provide air for combustion, ventilation and dilution of flue gases.
However, in buildings of tight construction (for example, weather
stripping, heavily insulated, caulked, vapor barrier, etc.), additional air
may need to be provided using the methods described in “Combustion
Air and Ventilation for Appliances Located in Confined Spaces.”
coMBustIon aIr and ventIlatIon for
applIances located In confIned spaces
confIned space is a space whose volume is less than 50 cubic
feet per 1,000 Btu per hour (4.8 cm per kW) of the aggregate input
rating of all appliances installed in that space.
When drawing combustion air from inside a conventionally
constructed building to a confined space, such a space should be
provided with two permanent openings. ONE WITHIN 12 INCHES
(30 cm) OF THE ENCLOSURE TOPAND ONE WITHIN 12 INCHES
(30 cm) OFTHE ENCLOSURE BOTTOM. Each opening should have
a free area of one square inch per 1000 Btu/hr (22 cm2/kW) of the
total input of all appliances in the enclosure, but not less than 100
square inches (645 cm2). If the confined space is within a building of
tight construction, air for combustion and ventilation must be obtained
from outdoors. When directly communicating with the outdoors or
communicating through vertical ducts, two permanent openings,
fIGure 5.
If this water heater will be used in beauty shops, barber shops, cleaning
establishments, or self-service laundries with dry cleaning equipment, it
is imperative that the water heater or water heaters be installed so that
combustion and ventilation air be taken from outside these areas.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
located in the above manner, should be provided. Each opening
should have a free area of not less than one square inch per 4000
Btu/hr (5.5 cm2/kW) of total input of all appliances in the enclosure.
If horizontal ducts are used, each opening should have a free area
of not less than one square inch per 2000 Btu/hr (11cm2/kW) of the
total input of all appliances in the enclosure.
a. all aIr froM InsIde BuIldInGs: (See Figure 5 and 6)
The confined space should be provided with two permanent openings
communicating directly with an additional room(s) of sufficient volume
so that the combined volume of all spaces meets the criteria for an
unconfinedspace.Thetotalinputofallgasutilizationequipmentinstalled
inthecombinedspaceshouldbeconsideredinmakingthisdetermination.
Each opening should have a minimum free area of one square inch
per 1,000 Btu per hour (22 cm2/kW) of the total input rating of all gas
utilizationequipmentintheconfinedspace,butnotlessthan100square
inches (645 cm2). One opening should commence within 12 inches
(30 cm) of the top and one commencing within 12 inches (30 cm)
of the bottom of the enclosures.
fIGure 8.
fIGure 8B.
5. Alternatively a single permanent opening may be used when
communicating directly with the outdoors, or with spaces that freely
communicate with the outdoors. The opening shall have a minimum free
area of 1 square inch per 3,000 BTU per hour (8.3 cm2/kW) of total input
rating of all equipment in the enclosure. See Figure 8B.
fIGure 6.
B. all aIr froM outdoors: (See Figures 7, 8 and 9)
The confined space should be provided with two permanent openings,
one commencing within 12 inches (30 cm) of the top and one
commencing within 12 inches (30 cm) from the bottom of the enclosure.
Theopeningsshouldcommunicatedirectly,orbyducts,withtheoutdoors
or spaces (crawl or attic) that freely communicate with the outdoors.
4. When ducts are used, they should be of the same cross-sectional
area as the free area of the openings to which they connect. The
minimum short side dimension of rectangular air ducts should not
be less than 3 inches (7.6 cm), see Figure 9.
1. Whendirectlycommunicatingwiththeoutdoors, eachopeningshould
have a minimum free area of 1 square inch per 4,000 Btu per hour
(5.5 cm2/kW) of total input rating of all equipment in the enclosure,
see Figure 7.
fIGure 9.
5. Louvers and Grilles: In calculating free area, consideration should
be given to the blocking effect of louvers, grilles or screens protecting
openings. Screensusedshould notbesmallerthan1/4inch(6.4mm)
mesh. If the free area through a design of louver or grille is known, it
should be used in calculating the size opening required to provide the
free area specified. If the design and free area is not known, it may be
assumed that wood louvers will be 20-25 percent free area and metal
louversandgrilleswillhave60-75percentfreearea.Louversandgrilles
should be fixed in the open position or interlocked with the equipment
so that they are opened automatically during equipment operation.
fIGure 7.
2. When communicating with the outdoors through vertical ducts,
each opening should have a minimum free area of 1 square inch
per 4,000 Btu per hour (5.5 cm2/kW) of total input rating of all
equipment in the enclosure, see Figure 8.
3. When communicating with the outdoors through horizontal ducts,
each opening should have a minimum free area of 1 square inch
per 2,000 Btu per hour (11 cm2/kW)) of total input rating of all
equipment in the enclosure, see Figure 9.
6. SpecialConditionsCreatedbyMechanicalExhaustingorFireplaces:
operation of exhaust fans, ventilation systems, clothes dryers or
fireplaces may create conditions requiring special attention to avoid
unsatisfactory operation of installed gas utilization equipment.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
InstallInG the new water heater
As water is heated, it expands (thermal expansion). In a closed
cheMIcal vapor corrosIon
system, the volume of water will grow. As the volume of water
grows, there will be a corresponding increase in water pressure due
to thermal expansion. Thermal expansion can cause premature
tank failure (leakage). This type of failure is not covered under the
limited warranty. Thermal expansion can also cause intermittent
temperature-pressure relief valve operation: water discharged from
the valve due to excessive pressure build up. The temperature-
pressure relief valve is not intended for the constant relief of
thermal expansion. This condition is not covered under the limited
warranty.
CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY OCCUR IF
AIRFORCOMBUSTIONCONTAINSCERTAINCHEMICALVAPORS.SUCH
CORROSION MAY RESULT IN FAILURE AND RISK OF ASPHYXIATION.
Spray can propellants, cleaning solvents, refrigerator and air
conditioning refrigerants, swimming pool chemicals, calcium and
sodium chloride (water softener salt), waxes, and process chemicals
are typical compounds which are potentially corrosive.
Do not store products of this sort near the heater. Also, air which is
brought in contact with the heater should not contain any of these
chemicals. If necessary, uncontaminated air should be obtained from
remote or outside sources. The limited warranty is voided when failure
of water heater is due to a corrosive atmosphere (see limited warranty
for complete terms and conditions).
A properly-sized thermal expansion tank should be installed
on all closed systems to control the harmful effects of thermal
expansion. Contact a local plumbing service agency to have a
thermal expansion tank installed..
water pIpInG
note: to protect against untimely corrosion of hot and cold
water fittings, it is strongly recommended that di-electric
unions or couplings be installed on this water heater when
connected to copper pipe.
All gas piping must comply with local codes and ordinances or with
the National Fuel Gas Code (ANSI Z223.1/ NFPA-54). Copper and
brass tubing and fittings (except tin lined copper tubing) should
not be used.
HOTTER WATER CAN SCALD:
Water heaters are intended to produce hot water. Water heated to a
temperature which will satisfy space heating, clothes washing, dish
washing, cleaning and other sanitizing needs can scald and permanently
injure you upon contact. Some people are more likely to be permanently
injured by hot water than others. These include the elderly, children, the
infirm, or physically/mentally handicapped. If anyone using hot water in
your home fits into one of these groups or if there is a local code or state
law requiring a certain temperature water at the hot water tap, then you
must take special precautions. In addition to using the lowest possible
temperature setting that satisfies your hot water needs, a means such
as a *mixing valve should be used at the hot water taps used by these
people or at the water heater, see Figure 2. Valves for reducing point of
use temperature by mixing cold and hot water are also available.
Consult a Qualified Installer or ServiceAgency. Follow manufacturer’s
instructions for installation of the valves. Before changing the factory
setting on the thermostat, read the “Temperature Regulation” section
in this manual.
This water heater should not be connected to any heating systems or
component(s) used with a non-potable water heating appliance.
All piping components connected to this unit for space heating
applications should be suitable for use with potable water.
Toxic chemicals such as those used for boiler treatment, should not be
introduced into this system.
When the system requires water for space heating at temperatures higher
than required for domestic water purposes, a tempering valve must be
installed. Please refer to Figure 2 for suggested piping arrangement.
fIGure 10.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 10 shows the typical attachment of the water piping to the The valve must be marked with a maximum set pressure not to
water heater. The water heater is equipped with 3/4 inch NPT water
connections.
exceed the marked hydrostatic working pressure of the water heater
(150 psi = 1,035 kPa) and a discharge capacity not less than the water
heater input rate as shown on the model rating plate.
note: If using copper tubing, solder tubing to an adapter before
attaching the adapter to the water heater connections. do not
solder the water lines directly to the water heater connections.
It will harm the dip tube and damage the tank.
For safe operation of the water heater, the relief valve must not be
removed from its designated opening nor plugged.
The temperature-pressure relief valve must be installed directly into
the fitting of the water heater designed for the relief valve. Position
the valve downward and provide tubing so that any discharge will
exit only within 6 inches (15.2 cm) above, or at any distance below
the structural floor. Be certain that no contact is made with any live
electrical part. The discharge opening must not be blocked or reduced
in size under any circumstances. Excessive length, over 30 feet (9.14
m), or use of more than four elbows can cause restriction and reduce
the discharge capacity of the valve, see Figures 10 or 14.
t & p valve and pipe Insulation (if supplied)
Remove insulation for T &P valve and pipe connections from carton.
No valve or other obstruction is to be placed between the relief valve
and the tank. Do not connect tubing directly to discharge drain unless
a 6” (15.2 cm) air gap is provided. To prevent bodily injury, hazard to
life, or property damage, the relief valve must be allowed to discharge
water in quantities should circumstances demand. If the discharge
pipe is not connected to a drain or other suitable means, the water
flow may cause property damage.
fIGure 11.
Fit pipe insulation over the incoming cold water line and the hot water
line. Make sure that the insulation is against the top cover of the heater.
Fit T & P valve insulation over valve. Make sure that the insulation
does not interfere with the lever of the T & P valve.
Secure all insulation using tape.
teMperature-pressure relIef valve
The Discharge Pipe:
• Should not be smaller in size than the outlet pipe size of the valve, or
have any reducing couplings or other restrictions.
• Should not be plugged or blocked.
• Should be of material listed for hot water distribution.
• Should be installed so as to allow complete drainage of both the
temperature-pressure relief valve, and the discharge pipe.
• Should terminate at an adequate drain.
• Should not have any valve between the relief valve and tank.
This heater is provided with a properly certified combination
temperature - pressure relief valve by the manufacturer.
The valve is certified by a nationally recognized testing laboratory
that maintains periodic inspection of production of listed equipment
of materials as meeting the requirements for Relief Valves for Hot
Water Supply Systems, ANSI Z21.22 and the code requirements
of ASME.
The temperature-pressure relief valve must be manually operated at least
once a year. Caution should be taken to ensure that (1) no one is in front
of or around the outlet of the temperature-pressure relief valve discharge
line, and(2)thewatermanuallydischargedwillnotcauseanybodilyinjury
or property damage because the water may be extremely hot.
If after manually operating the valve, it fails to completely reset and
continues to release water, immediately close the cold water inlet
to the water heater, follow the draining instructions, and replace the
temperature-pressure relief valve with a new one.
If replaced, the valve must meet the requirements of local codes,
but not less than a combination temperature and pressure relief
valve certified as indicated in the above paragraph.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
When installed at elevations above 7,700 feet (2,347 meters), input
rating should be reduced at the rate of 4 percent for each 1,000
feet (305 meters) above sea level which requires replacement
of the burner orifice in accordance with National Fuel Gas Code
(ANSI Z223.1/NFPA 54). Contact your local gas supplier for
further information.
Gas pIpInG
Failure to replace the standard orifice with a high altitude orifice
when installed could result in improper and inefficient operation of
the appliance, producing carbon monoxide gas in excess of safe
limits, which could result in serious injury or death. Contact your
gas supplier for any specific changes which may be required in
your area.
Make sure the gas supplied is the same type listed on the model rating
plate. The inlet gas pressure must not exceed 14 inch water column (3.5
kPa) for natural and propane gas (L.P.). The minimum inlet gas pressure
shown on the rating plate is that which will permit firing at rated input.
All gas piping must comply with local codes and ordinances or with the
National Fuel Gas Code (ANSI Z223.1/ NFPA-54). Copper or brass
tubing and fittings (except tin lined copper tubing) should not be
used.
Use pipe joint compound or teflon tape marked as being resistant
to the action of petroleum [Propane (L.P.)] gases.
If the gas control valve is subjected to pressures exceeding 1/2 psi
(3.5 kPa), the damage to the gas control valve could result in a fire
or explosion from leaking gas.
The appliance and its gas connection must be leak tested before
placing the appliance in operation.
If the main gas line shut-off serving all gas appliances is used,
also turn “off” the gas at each appliance. Leave all gas appliances
shut “off” until the water heater installation is complete.
The appliance and its individual shut-off valve should be disconnected
from the gas supply piping system during any pressure testing of
that system at test pressures in excess of 1/2 pound per square inch
(3.5 kPa). It should be isolated from the gas supply piping system
by closing its individual manual shut-off valve during any pressure
testing of the gas supply piping system at test pressures equal to
or less than 1/2 pound per square inch (3.5 kPa).
A gas line of sufficient size must be run to the water heater. Consult
the current edition of National Fuel Gas Code (ANSI Z223.1/NFPA
54) and your gas supplier concerning pipe size.
There must be:
Connectingthegaspipingtothegascontrolvalveofthewaterheatercanbe
accomplished by either of the two methods shown in Figures 12 and 13.
• A readily accessible manual shut off valve in the gas supply line
serving the water heater, and
• Adripleg(sedimenttrap)aheadofthegascontrolvalvetohelpprevent
dirt and foreign materials from entering the gas control valve.
• A flexible gas connector or a ground joint union between the shut
off valve and control valve to permit servicing of the unit.
Be sure to check all the gas piping for leaks before lighting the water
heater. Use a soapy water solution, not a match or open flame.
Rinse off soapy solution and wipe dry.
fIGure 12. Gas pIpInG wIth
fleXIBle connector.
fIGure 13. Gas pIpInG wIth all
BlacK Iron pIpe to Gas control.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Never use this water heater unless it is completely full of water.
To prevent damage to the tank, the tank must be filled with water.
Water must flow from the hot water faucet before turning “ON” gas
to the water heater.
sedIMent traps
To fill the water heater with water:
1. Close the water heater drain valve by turning the handle to the
right (clockwise). The drain valve is on the lower front of the
water heater.
2. Open the cold water supply valve to the water heater.
note: the cold water supply valve must be left open when
the water heater is in use.
3. To insure complete filling of the tank, allow air to exit by opening the
nearest hot water faucet. Allow water to run until a constant flow is
obtained. This will let air out of the water heater and the piping.
A sediment trap should be installed as close to the inlet of the water
heater as practical at the time of water heater installation. The
sediment trap should be either a tee fitting with a capped nipple in
the bottom outlet or other device recognized as an effective sediment
trap. If a tee fitting is used, it should be installed in conformance with
one of the methods of installation shown in Figures 12 and 13.
4. Check all water piping and connections for leaks. Repair as
needed.
ventInG
Contaminants in the gas lines may cause improper operation of the
gas control valve that may result in fire or explosion. Before attaching
the gas line be sure that all gas pipe is clean on the inside. To trap any
dirt or foreign material in the gas supply line, a drip leg (sometimes
called a sediment trap) must be incorporated in the piping. The drip
leg must be readily accessible. Install in accordance with the “Gas
Piping” section. Refer to the current edition of the National Fuel Gas
Code (ANSI Z223.1/NFPA 54).
vent pIpe terMInatIon
The first step is to determine where the vent pipe will terminate, see
Figures 15, 19 and 20. The vent may terminate through the roof as
shown in Figure 20 or through a sidewall as shown in Figure 19.
fIGure 14.
fIllInG the water heater
IMportant
The vent system must terminate so that proper clearances are
maintained as cited in local codes or the current edition of the
National Fuel Gas Code, ANSI Z223.1.
For your convenience instructions on proper installation through a
sidewall are provided in Figure 15 and the numbered points below:
1. The exit terminals of a mechanical vent system should be not
less than 7 feet above grade when located adjacent to public
walkways.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
u.s. horIZontal vent clearances
warnInG
vent hood(s) MaY Be
eXtreMelY hot
durInG operatIon.
fIGure 15.
2. A venting system should terminate at least 3 feet above any
forced air inlet located within 10 feet.
2. This water heater is capable of venting the flue gases the
equivalent of thirty (30) feet of 3 inch pipe or one-hundred (100)
feet of 4 inch pipe as listed in Table 1.
3. The venting system should terminate at least 4 feet below, 4 feet
horizontally from or, 1 foot above any door, window or gravity air
inlet into any building.
taBle 1.
number of
90° elbows
3” Maximum
pipe (feet)
4” Maximum
pipe feet
ONE (1)
TWO (2)
THREE(3)
FOUR (4)
FIVE (5)
25
20
92
84
76
68
60
4. The manufacturer also recommends that the vent system
termination not be installed closer than 18” from an inside
corner of an L shaped structure and not be less than 1 foot
above grade. The vent should terminate a minimum of 12’’
above expected snowfall level to prevent blockage of vent
termination.
15
10
- - -
Minimum of one (1) elbow and 2 feet of straight pipe must be
installed for 3” and 4” pipe.
5. The vent termination should not be mounted directly above or
within 3 feet horizontally from an oil tank vent or gas meter to
avoid potential freeze-up from condensation.
note: The equivalent feet of pipe listed above are exclusive
of the “45° Elbow” termination. That is, the termination “45°
Elbow”, with installed screen, is assumed to be in the system
and the remainder of the system must not exceed the thirty (30)
equivalent feet of 3 inch pipe or one-hundred (100) equivalent
feet of 4 inch pipe.
Plan the vent system layout so that proper clearances are maintained
from plumbing and wiring.
3. The blower discharge adapter is made to accept only straight
sections of 3” pipe. To start a minimum of 2 inches of 3” pipe
must be attached to the blower discharge. See Figure 6.
Vent pipes serving power vented appliances are classified by
building codes as “vent connectors”. Required clearances from
combustible materials must be provided in accordance with
information in this manual under LOCATION OF HEATER and
INSTALLATION OF VENT SYSTEM, and with the National Fuel
Gas Code and local codes.
If using 3 inch vent pipe:
A minimum of 2 inches, maximum of 4 feet of 3” pipe must be
attached to the blower before the first 3-inch elbow. After the first
elbow add the additional venting required for the installation. The
total system cannot exceed 30 equivalent feet of venting, where
each elbow is equal to 5 feet of straight pipe.
plannInG the vent sYsteM
If using 4 inch vent pipe:
Plan the route of the vent system from the discharge of the blower
to the planned location of the vent terminal.
Two inches of 3” pipe must be attached to the blower discharge.
A 4” x 3” reducer is added and then up to maximum 4 feet of
4 inch pipe added before the first elbow. An additional 4” x 3”
reducer and (1) foot of 3” pipe must be added to the end of the
vent system before terminating into the 3” 45° elbow. The total
system cannot exceed 100 equivalent feet of 4” venting, where
each elbow is equal to 8 feet of straight pipe.
1. Layout the total vent system to use a minimum of vent pipe and
elbows. Take into consideration that an elbow will be necessary
to make the first vent pipe connection to the power venter outlet,
see Figure 6.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
note: This unit can be vented using only the following
materials: PVC (Cellular Core; ASTM-F891), PVC (DWV;ASTM
D2665 or CSA B181.2), PVC (Sch 40, 80, 120; ASTM D1785 or
CSAB137.3), PVC (SDR Series; ASTM-D2241 or CSAB137.3),
CPVC (CPVC 41; ASTM-D2846 or CSA B137.6), CPVC
(Sch 40, 80; ASTM-F441 or CSA B137.6), CPVC (SDR Series;
ASTM-F442), ABS (Sch 40 DWV;ASTM D2661 or CSAB181.1),
ABS (Sch 40 DWV cellular core;ASTM-F628). The fittings, other
than the TERMINATION should be equivalent to PVC-DWV
fittings meeting ASTM D-2665 (Use CPVC fittings, ASTM F-438
for CPVC pipe and ABS fittings, ASTM D-2661/3311 for ABS
pipe). If CPVC or ABS pipe and fittings are used, then the proper
cement must be used for all joints, including joining the pipe to
the Termination (PVC Material). If local codes do not allow the
use of the PVC termination when a material other than PVC is
used for venting, then an equivalent fitting of that material may
be substituted if the screen in the PVC terminal is removed and
inserted into the new fitting.
PVC Materials should use ASTM D-2564 Grade Cement; CPVC
Materials should use ASTM F-493 Grade Cement and ABS
Materials should use ASTM D-2235 Grade Cement.
Blower asseMBlY InstallatIon
If the water heater is being installed as a replacement for an
existing power vented heater in pre-existing venting, a thorough
inspection of the existing venting system must be performed prior
to any installation work. Verify that the correct material as detailed
above has been used, and that the minimum or maximum vent
lengths and terminal location as detailed in this manual have been
met. Carefully inspect the entire venting system for any signs of
cracks or fractures, particularly at the joints between elbows and
other fittings and the straight runs of vent pipe. Check the system
for signs of sagging or other stresses in the joints as a result of
misalignment of any components in the system. If any of these
conditions are found, they must be corrected in accordance with
the venting instructions in this manual before completing the
installation and putting the water heater into service.
1. Check to make sure that the wire harness is attached to the gas
valve and blower control box.
note: a. For water heaters in locations with high ambient
temperatures (above 100°F) it is recommended that CPVC or
ABS pipe and fittings be used. B. A 22.5 degree elbow (2” vent
pipe) or a 45 degree elbow (3” and 4” vent pipe) with an installed
screen VENT TERMINAL must be used in all cases.
2. Make sure no material is still attached to the outside or inside
of blower assembly.
condensate
Condensate formation does not occur in all installations of power
vented water heaters, but should be protected against on installations
where it can form in the venting system. Condensation in the venting
system of power vented water heaters is dependent upon installation
conditions including, but not limited to ambient temperature and
humidity of installation location, ambient temperature and humidity
of venting space, vent discharge and slope, and product usage. In
certain conditions, installations in unconditioned space or having
long horizontal or vertical vent runs may accumulate condensate.
In these conditions, the vent pipe should be sloped downward
away from the blower assembly (not less than 1/8” (3.2 mm) nor
greater than 1/2” (12.7 mm) per foot maximum). If the vent piping
is vented level or sloped upwards away from the blower assembly,
then adequate means for draining and disposing of the condensate
needs to be made by the installer (if condensate is detected). If you
have condensate, then a 3/8” drain hose can be connected to the
built-in drain port of the rubber boot on the blower assembly. For
your convenience, the rubber boot is supplied with a removable cap
on the built-in drain port. Prior to operating the water heater, make
sure the removable cap is installed on the drain port (if a drain hose
is not needed).
fIGure 16. Blower asseMBlY
3. Make sure that plastic tubing is still attached to the pressure
switch and fan housing. Also make sure that wiring connector
from motor to control box is securely attached.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Do not plug in power cord until vent system is completely installed.
The Power Vent operates on 120 Vac, therefore a grounded outlet
must be within reach of the 6 foot flexible power cord supplied
with the vent. The power cord supplied may be used on unit
only where local codes permit. If local codes do not permit use
of flexible power supply cord:
vent terMInal InstallatIon, sIdewall
1. Install the vent terminal by using the cover plate as a template to
mark the hole for the vent pipe to pass through the wall. BEWARE
OF CONCEALED WIRING AND PIPING INSIDE THE WALL.
2. If the Vent Terminal is being installed on the outside of a finished
wall, it may be easier to mark both the inside and outside wall.
Align the holes by drilling a hole through the center of the template
from the inside through to the outside. The template can now be
positioned on the outside wall using the drilled hole as a centering
point for the template.
A. Remove screws that hold cover plate on control box and
remove plate.
B. Cut flexible power cord on inside of control box, as close to
inside wall as possible.
3. A) MASONRY SIDE WALLS
C. If flexible cord and strain relief are removed, then opening
in box must be covered by a plastic cap on the front side of
the control box.
Chisel an opening approximately one half inch (1.3 cm) larger
than the marked circle.
B) WOODEN SIDE WALLS
D. Remove plastic cap on the right side of control box and install
suitable conduit fitting in enclosure.
Drill a pilot hole approximately one quarter inch (0.64 cm) outside
of the marked circle. This pilot hole is used as a starting point
for a saws-all or sabre saw blade. Cut around the marked circle
staying approximately one quarter inch (0.64 cm) outside of the
line. (This will allow the vent to easily slide through the opening.
The resulting gap will be covered up by the Vent Terminal cover
plate.) Repeat this step on inside wall if necessary.
E. Splice field wiring into existing wiring using code authorized
method (wire nuts, etc.).
F. Be certain that neutral and line connections are not reversed
when making these connections.
SEQUENCE OF INSTALLATIONS, FIGURE 17
G. Ground heater properly. This water heater must be grounded
in accordance with the National Electrical Code ANSI/
NFPA70 and/or local codes. These must be followed in all
cases.
Cut a length of PVC pipe about 3.5 inches (8.9 cm) longer than the
wall thickness at the opening. Glue the vent terminal to this section
of pipe. Slide the wall plate over the pipe to stop against the vent
terminal. Place a bead of caulking (not supplied) around the gap
between the pipe and cover plate. Apply enough to fill some of the
gap between the pipe and wall. Place some of the caulking on the
back of the plate to hold it against the wall after installation. If the
vent pipe is installed up to the wall, with a coupling on the end against
the wall opening, the pipe with the vent terminal can be prepared
for gluing before inserting through the wall. Slide the pipe through
the wall and insert into the coupling on the other side of the wall,
making sure that the vent terminal ends up pointed in the correct
position, see Figure 17.
The water heater must be connected to a grounded metal,
permanent wiring system; or an equipment grounding
conductor must be run with the circuit conductors and
connected to the equipment grounding terminal or lead on
the water heater, see Figure 19.
H. Replace cover plate and secure with two screws.
5. The blower discharge boot is made to accept only straight
sections of 3” pipe. To start off with an elbow, a short section
of the furnished pipe, a minimum of 2 inches, must be cut and
glued into the end of the elbow that will mount on the discharge
boot (see figure 16).
InstallatIon of vent sYsteM
Before beginning installation of piping system thoroughly read the
section of this manual VENT PIPE PREPARATION.
If you are installing your system so that it vents through the roof, please
refer to section titled INSTALLATION OF VERTICAL VENT SYSTEM.
fIGure 17. vent terMInatIon
18
Download from Www.Somanuals.com. All Manuals Search And Download.
cautIon
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN
CAUSE IMPROPER AND DANGEROUS OPERATION. VERIFY PROPER OPERATION AFTER SERVICING.
fIGure 18. power vent wIrInG scheMatIc.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Provide support for all pipe protruding through the roof. All piping
should be properly secured. The vent system piping should be
supported every 5 feet (1.5 m) of vertical run and every 3 feet (91 cm)
of horizontal run. All piping and fittings must be joined by the proper
procedures as described under: VENT PIPE PREPARATION.
InstallatIon of vent sYsteM, sIdewall
With the route of the venting system and selection of materials completed,
as discussed in the section of this manual titled PLANNING THE VENT
SYSTEM, the through the wall vent terminal in place and the first section
of piping, up to first elbow, installed at the blower it is time to complete the
installation of the venting system for the sidewall installation.
fIGure 19.
fIGure 20.
Before completing the installation of the venting system be sure to read
the sections of this manual discussing the proper method of cutting and
cementing PVC pipe and fittings: VENT PIPE PREPARATION.
IMportant
The vent system must terminate so that proper clearances are
maintained as cited in local codes or the current edition of the
National Fuel Gas Code (ANSI Z223.1) and as listed below:
It is recommended that the completion of the venting system start at
the blower assembly and run to the coupling on the inside wall of the
vent terminal, see Figure17.
1. VentTermination must extend a minimum of 18 inches (46 cm) above
roof or 18 inches (46 cm) above the anticipated snow level to prevent
blockage of the vent termination, as shown in Figures 19 and 20.
The vent system piping should be supported every 5 feet (1.5 m)
of vertical run and every 3 feet (91 cm) of horizontal run. All piping
and fittings must be joined by the proper procedures as described
under: VENT PIPE PREPARATION.
2. The venting system should terminate at least four (4) feet (1.2 m)
from or one (1) foot (30 cm) above any gable, dormer or other roof
structure with building interior access; i.e., vent, window, etc.
InstallatIon of vertIcal vent sYsteM
A proper flashing or “BOOT” should be used to seal the pipe where it
exits the roof. The total vent system should not exceed the equivalent
feet of pipe as listed in Table 1.
3. The venting system should terminate three (3) feet (91 cm)
above any forced air inlet located within ten feet (3.0 m).
20
Download from Www.Somanuals.com. All Manuals Search And Download.
prIMer
vent pIpe preparatIon
It is recommended that Tetrahydrofuran (THF) be used to prepare the
surfaces of pipe and fittings for solvent welding. Do not use water,
rags, gasoline or any other substitutes for cleaning PVC or CPVC
surfaces. A chemical cleaner such as MEK may be used.
1. InItIal preparatIon
A. Make sure the solvent cement you are planning to use is
designed for the specific application you are attempting.
ceMent
B. Know the physical and chemical characteristics and limitations of
the PVC and CPVC piping materials that you are about to use.
The cement should be a bodied cement of approximately 500 to
1600 centipoise viscosity containing 10-20% (by weight) virgin PVC
material solvated with tetrahydrofuran (THF). Small quantities of
dimethyl formamide (DMF) may be included to act as a retarding
agent to extend curing time. Select the proper cement; Schedule 40
cement should be used for Schedule 40 pipe. Never use all-purpose
cements, commercial glues and adhesives or ABS cement to join
PVC or CPVC pipe and fittings.
C. Know the reputation of your manufacturer and their products.
D. Know your own qualifications or those of your contractor. The
solvent welding technique of joining PVC and CPVC pipe is a
specialized skill just as any other pipe fitting technique.
E. Closely supervise the installation and inspect the finished
job before start-up.
F. Contact the manufacturer, supplier, or competent consulting
agency if you have any questions about the application or
installation of PVC and CPVC pipe.
G. Take the time and effort to do a professional job. Shortcuts
will only cause you problems and delays in start-up. By far,
the majority of failures in PVC and CPVC systems are the
result of shortcuts and/or improper joining techniques.
applIcators
2. selectIon of MaterIals
Select a suitable pure bristle type paint brush. Use a proper width
brush or roller to apply the primer and cement (see chart below).
Speedy application of cement is important due to its fast drying
characteristics. IMPORTANT NOTE:Adauber type applicator should
only be used on pipe sizes 2” and below. For larger diameter pipe,
a brush or roller must be used.
•
•
•
•
•
•
Cutting Device - Saw or Pipe Cutter
Deburring Tool, Knife, File, or Beveling Machine (2” and above)
Brush - Pure Bristle
Rag - Cotton (Not Synthetic)
recoMMended Brush* sIZe for prIMer
Primer and Cleaner
and ceMent applIcatIons
nominal pipe
size Brush width
Solvent Cement - PVC for PVC Components and CPVC for
CPVC Components
(Ips)
2
3
1.5” (3.8 cm)
1.5” - 2.5” (3.8 cm - 6.4 cm)
•
Containers - Metal or Glass to hold Primer and Cement. Select
the type of PVC or CPVC materials to be used on the basis of
their application with respect to chemical resistance, pressure
rating, temperature characteristics, etc.
*use onlY natural BrIstle
•
Insertion Tool - Helpful for larger diameter pipe and fittings 6
inches (15.2 cm) and above.
3. MaKInG the joInt
a. cutting
Pipe must be squarely cut to allow for the proper interfacing of the
pipe end and the fitting socket bottom. This can be accomplished
with a miter box saw or wheel type cutter. Wheel type cutters are
not generally recommended for larger diameters since they tend
to flare the corner of the pipe end. If this type of cutter is used,
the flare on the end must be completely removed.
NOTE: Power saws should be specifically designed to cut plastic pipe.
step a
21
Download from Www.Somanuals.com. All Manuals Search And Download.
B. deburring
Use a knife, plastic pipe deburring tool, or file to remove burrs from the
endofsmalldiameterpipe. Besuretoremoveallburrsfromaroundthe
insideaswellastheoutsideofthepipe.Aslightchamfer(bevel)ofabout
10°-15° should be added to the end to permit easier insertion of the pipe
into the end of the fitting. Failure to chamfer the edge of the pipe may
remove cement from the fitting socket, causing the joint to leak.
step e
f. joint assembly
Working quickly, insert the pipe into the fitting socket bottom and
give the pipe or fitting a 1/4 turn to evenly distribute the cement.
Do not continue to rotate the pipe after it has hit the bottom of the
fitting socket. A good joint will have sufficient cement to make a
bead all the way around the outside of the fitting hub. The fitting
will have a tendency to slide back while the cement is still wet
so hold the joint together for about 15 seconds.
step B
C. Test dry fit of the joint
Tapered fitting sockets are designed so that an interfaced fit should
occur when the pipe is inserted about 1/3 to 2/3 of the way into the
socket.Occasionally,whenpipefittingdimensionsareatthetolerance
extremes, it will be possible to fully insert dry pipe to the bottom of
the fitting socket. When this happens, a sufficient quantity of cement
must be applied to the joint to fill the gap between the pipe and fitting.
The gap must be filled to obtain a strong, leak-free joint.
d. Inspection, cleaning, priming
Visuallyinspecttheinsideofthepipeandfittingsocketsandremove
all dirt, grease or moisture with a clean dry rag. If wiping fails to clean
the surfaces, a chemical cleaner must be used. Check for possible
damage such as splits or cracks and replace if necessary.
depth-of-entry
Marking the depth of entry is a way to check if the pipe has
reached the bottom of the fitting socket in Step F. Measure the
fitting depth and mark this distance on the pipe O.D. You may want
to add several inches to the distance and make a second mark as
the primer and cement will most likely destroy your first one.
step f
G. cleanup and joint movement
Remove all excess cement from around the pipe and fitting with a
dry cotton rag. This must be done while the cement is still soft.
Apply primer to the surface of the pipe and fitting socket with
a natural bristle brush. This process softens and prepares the
PVC or CPVC for the solvent cementing step. Move quickly and
without hesitation to the cementing procedure while the surfaces
are still wet with primer.
The joint should not be disturbed immediately after the cementing
procedure, and sufficient time should be allowed for proper curing
of the joint. Exact drying time is difficult to predict because it
depends on variables such as temperature, humidity and cement
integrity. For more specific information, you should contact your
solvent cement manufacturer.
e. application of solvent cement
• Apply the solvent cement evenly and quickly around the outside of the
pipe at a width a little greater than the depth of the fitting socket.
• Apply a light coat of cement evenly around the inside of the
fitting socket. Avoid puddling.
• Apply a second coat of cement to the pipe end.
step G
22
Download from Www.Somanuals.com. All Manuals Search And Download.
for Your safetY read Before operatInG
warnInG: If you do not follow these instructions exactly, a fire or
explosion may result causing property damage, personal injury or loss of
life.
Before operatInG: entIre sYsteM Must Be fIlled wIth water and aIr purGed froM all lInes.
A. This appliance does not have a pilot. It is equipped with
an ignition device which automatically lights the burner.
do not try to light the burner by hand.
B. Before operatInG smell all around the appliance
area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the floor.
what to do If You sMell Gas:
•
If you cannot reach your gas supplier, call the fire
department.
C. Use only your hand to push in the gas control buttons.
Never use tools. If the control buttons will not push in, don’t
trytorepairthem,callaqualifiedservicetechnician.Force
or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under
water. Immediately contact a qualified installer or service
agencytoreplaceafloodedwaterheater. Donotattempt
to repair the unit! It must be replaced!
•
•
Do not try to light any appliance.
Do not touch any electric switch;
Do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
•
operatInG InstructIons
4. This appliance is equipped with a device which
automatically lights the burner.
do not trY to lIGht the Burner BY hand.
5. Wait five (5) minutes to
If you then smell gas,
clear out any gas.
STOP! Follow “B” in
the safety information above on this label. If you don’t
smell gas, go to the next step.
6. Turn on all electrical power to the appliance.
7. Set thermostat to desired setting by first pressing the
COOLER
and HOTTER
buttons together and
holding for 1 second. Then press the HOTTER
button.
8. If the appliance will not operate, follow the instructions
“TO TURN OFF GAS TO APPLIANCE” and call your
technician or gas supplier.
1.
STOP! Read the safety information above,
on this label.
9. WATER TEMPERATURE ADJUSTMENT
is approximately 120°F.
2. Set the thermostat to the lowest setting by first pressing
the COOLER and HOTTER buttons together
cautIon: hotter water increases the risk
of scald injury. consult the instruction
manual before changing temperature.
and holding for 1 second. Then press the COOLER
button until the WARM indicator light appears.
3. Set the “ON/OFF” switch on the blower control box to
the “OFF” position.
warnInG: turn off all electrIc
power Before servIcInG
to turn off Gas to applIance
1. Set the thermostat to the lowest setting by first pressing the COOLER
and HOTTER
buttons together and
holding for 1 second. Then press the COOLER button until the WARM indicator light appears.
2. Set the ON/OFF switch on the blower control box to the “OFF” position.
3. Turn off all electric power to the appliance if service is to be performed.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
teMperature reGulatIon
Any water heater’s intended purpose is to heat water. Hot water is
The water temperature setting was factory set at the lowest temperature;
neededforcleansing, cleaning, andsanitizing(bodies, dishes, clothing).
Untempered hot water can present a scald hazard. Depending on the
time element, and the people involved (adults, children, elderly, infirm,
etc.) scalding may occur at different temperatures.
Pressing the “COOLER”
pressing the “HOTTER”
button decreases temperature and
button increases the temperature.
Setting the water heater temperature at 120°F (49°C) (Approx. “
” mark on temperature setting of gas valve) will reduce the
risks of scalds. Some states require settings at specific lower
temperatures.
It is recommended that lower water temperatures be used to avoid
the risk of scalding. It is further recommended, in all cases, that the
water temperature be set for the lowest temperature which satisfies
your hot water needs. This will also provide the most energy efficient
operation of the water heater.
To avoid any unintentional changes in water temperature settings, the
control has a tamper resistant feature for changing the temperature
setting. To change the temperature setting follow these instructions:
Figure 21shows the approximate water temperatures produced
at various thermostat settings. Short repeated heating cycles
caused by small hot water uses can cause temperatures at the
point of use to exceed the thermostat setting by up to 30°F (17°C).
If you experience this type of use you should consider using lower
temperature settings to reduce scald hazards.
1. “Wake Up” the temperature indicators by holding down both
“COOLER” and “HOTTER” temperature adjustment buttons at
the same time for one second, see Figure 21. One or two of the
temperature indicators will light up. These indicators will only
remain on for 30 seconds if no further buttons are pressed. After
30 seconds the control will go back to “Sleep” mode.
Valves for reducing the point-of-use temperature by mixing cold and
hot water are available, see Figure 2. Also available are inexpensive
devices that attach to faucets to limit hot water temperatures.
Contact a licensed plumber or the local plumbing authority.
2. Release both of the temperature adjustment buttons.
a. To decrease the temperature press and release the “COOLER”
button until the desired setting is reached.
b. To increase the temperature press and release the “HOTTER”
button until the desired setting is reached.
NOTE: Holding down the button will not continue to lower or raise
the temperature setting. The button must be pressed and released
for each temperature change desired.
Should overheating occur or the gas supply fail to shut off, turn off
the manual gas control valve to the appliance.
HOT WATER CAN SCALD: Water heaters are intended to produce
hot water. Water heated to a temperature which will satisfy space
heating, clothes washing, dish washing, and other sanitizing needs
can scald and permanently injure you upon contact. Some people
are more likely to be permanently injured by hot water than others.
These include the elderly, children, the infirm, or physically/mentally
handicapped. If anyone using hot water in your home fits into one of
these groups or if there is a local code or state law requiring a certain
temperature water at the hot water tap, then you must take special
precautions. In addition to using the lowest possible temperature
setting that satisfies your hot water needs, a means such as a mixing
valve, should be used at the hot water taps used by these people or
at the water heater. Mixing valves are available at plumbing supply
or hardware stores, see Figure 2. Follow manufacturer’s instructions
for installation of the valves. Before changing the factory setting on
the thermostat, read the “Temperature Regulation” section in this
manual, see Figure 21.
Time to Produce
Display
A B C
2nd and 3rd Degree
Burns on Adult Skin
About 1/2 seconds
About 1-1/2 seconds
Less than 5 seconds
About 30 seconds
More than 5 minutes
- - - - - - - - - - - - -
Temperature Setting
C-Flashing = approx. 160°F (71°C)
C = approx. 150°F (66°C)
B = approx. 140°F (60°C)
A = approx. 130°F (54°C)
= approx. 120°F (49°C)
Never allow small children to use a hot water tap, or to draw their own
bath water. Never leave a child or handicapped person unattended
in a bathtub or shower.
The water heater should be located in an area where the general
public does not have access. If a suitable area is not available, a cover
should be installed over the thermostat to prevent tampering.
WARM = approx. 80°F (27°C)
fIGure 21.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
for Your InforMatIon
of a “rotten egg smell” in the hot water. The smell is a result of four
start up condItIons
factors which must all be present for the odor to develop:
sMoKe/odor
a. A concentration of sulfate in the supply water.
b. Little or no dissolved oxygen in the water.
c. A sulfate reducing bacteria which has accumulated within the
water heater (this harmless bacteria is nontoxic to humans).
d. An excess of active hydrogen in the tank. This is caused by the
corrosion protective action of the anode.
It is not uncommon to experience a small amount of smoke and odor
during the initial start-up. This is due to burning off of oil from metal
parts, and will disappear in a short while.
therMal eXpansIon
Smellywatermaybeeliminatedorreducedinsomewaterheatermodels
by replacing the anode(s) with one of less active material, and then
chlorinating the water heater tank and all water lines. Contact the local
water heater supplier or service agency for further information concerning
an Anode Replacement Kit and this chlorination treatment.
If the smelly water persists after the anode replacement and chlorination
treatment, we can only suggest that chlorination or aeration of the water
supply be considered to eliminate the water problem.
do not remove the anode leaving the tank unprotected. By doing
As water is heated, it expands (thermal expansion). In a closed
system, the volume of water will grow. As the volume of water
grows, there will be a corresponding increase in water pressure
due to thermal expansion. Thermal expansion can cause
premature tank failure (leakage). This type of failure is not
covered under the limited warranty. Thermal expansion can also
cause intermittent temperature-pressure relief valve operation:
water discharged from the valve due to excessive pressure build
up. The temperature-pressure relief valve is not intended for the
constant relief of thermal expansion. This condition is not covered
under the limited warranty.
so, all warranty on the water heater tank is voided.
“aIr” In hot water faucets
A properly-sized thermal expansion tank should be installed
on all closed systems to control the harmful effects of thermal
expansion. Contact a local plumbing service agency to have a
thermal expansion tank installed.
HYDROGEN GAS: Hydrogen gas can be produced in a hot water
system that has not been used for a long period of time (generally
two weeks or more). Hydrogen gas is extremely flammable and
explosive. To prevent the possibility of injury under these conditions,
we recommend the hot water faucet, located farthest away, be
opened for several minutes before any electrical appliances
which are connected to the hot water system are used (such as a
dishwasher or washing machine). If hydrogen gas is present, there
will probably be an unusual sound similar to air escaping through the
pipe as the hot water faucet is opened. There must be no smoking
or open flame near the faucet at the time it is open.
stranGe sounds
Possible noises due to expansion and contraction of some metal
parts during periods of heat-up and cool-down do not necessarily
represent harmful or dangerous conditions.
Condensation causes sizzling and popping within the burner area
during heating and cooling periods and should be considered normal.
See “Condensate” in this section.
operatIonal condItIons
hIGh water teMperature shut off sYsteM
This water heater is equipped with an automatic gas shut-off system.
This system works when high water temperatures are present. Turn
“OFF” the entire gas supply to the water heater. The high temperature
shut-off is built into the gas control valve. It is non-resettable. If the
high temperature shut-off activates, the gas control valve must be
replaced. Contact your gas supplier or service agency.
sMellY water
In each water heater there is installed at least one anode rod (see
parts section) for corrosion protection of the tank. Certain water
conditions will cause a reaction between this rod and the water.
The most common complaint associated with the anode rod is one
25
Download from Www.Somanuals.com. All Manuals Search And Download.
perIodIc MaIntenance
ports. If the proper flame characteristics are not evident, see Figure
ventInG sYsteM InspectIon
22, make sure that the flow of combustion and ventilation air is not
blocked.
You should also check for sooting. Soot is not normal and will impair
proper combustion. A visual inspection of the main burner and HSI
igniter assembly should also be done at least once a year, see
Figure 22.
Soot build-up indicates a problem that requires correction before
further use. Turn “OFF” gas to water heater and leave off until
repairs are made, because failure to correct the cause of the
sooting can result in a fire causing death, serious injury, or
property damage.
At least once a year a visual inspection should be made of the venting
system. You should look for:
1. Obstructions which could cause improper venting. The
combustion and ventilation air flow must not be obstructed.
2. Damage or deterioration which could cause improper venting or
leakage of combustion products.
fIGure 22.
Be sure the vent piping is properly connected to prevent escape of
dangerous flue gasses which could cause deadly asphyxiation.
Burner cleanInG
Obstructions and deteriorated vent systems may present serious
health risk or asphyxiation.
In the event your burner or burner air openings require cleaning, turn
the blower switch to the “OFF” position and allow the burner to cool.
Call a service agency to remove and clean the burner and correct
the problem that required the burner to be cleaned.
Chemical vapor corrosion of the flue and vent system may occur
if air for combustion contains certain chemical vapors. Spray can
propellants, cleaning solvents, refrigerator and air conditioner
refrigerants, swimming pool chemicals, calcium and sodium chloride,
waxes, bleach and process chemicals are typical compounds which
are potentially corrosive.
houseKeepInG
Vacuum around base of water heater for dust, dirt, and lint on a
regular basis.
If after inspection of the vent system you found sooting or
deterioration, something is wrong. Call the local gas utility to
correct the problem and clean or replace the flue and venting before
resuming operation of the water heater.
Burner operatIon and InspectIon
Flood damage to a water heater may not be readily visible or
immediately detectable. However, over a period of time a flooded
water heater will create dangerous conditions which can cause
DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.
Contact a qualified installer or service agency to replace a
flooded water heater. Do not attempt to repair the unit! It must be
replaced!
At least once a year a visual inspection should be made of the
main burner and the hot surface igniter assembly for proper flame
characteristics and ignition sequences. This can be done by removing
the Outer Door and viewing the main burner operation through the
Viewport on the Inner Door, see Figure 1. The main burner should
provide complete combustion of gas, ignite rapidly, give reasonably
quiet operation, and cause no excessive flame lifting from the burner
26
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLED IN SUITABLE AREA: To insure sufficient ventilation
and combustion air supply, proper clearances from the water heater
must be maintained. See “Locating the New Water Heater” section.
Combustible materials such as clothing, cleaning materials, or
flammable liquids, etc. must not be placed against or adjacent to
the water heater which can cause a fire.
When checking the temperature-pressure relief valve operation,
make sure that (1) no one is in front of or around the outlet of the
temperature-pressure relief valve discharge line, and (2) that the
water discharge will not cause any property damage, as the water
may be extremely hot, see Figure 23.
If after manually operating the valve, it fails to completely reset and
continues to release water, immediately close the cold water inlet
to the water heater, follow the draining instructions, and replace the
temperature-pressure relief valve with a new one.
anode rod InspectIon
If the temperature-pressure relief valve on the appliance weeps or
discharges periodically, this may be due to thermal expansion. You
may have a check valve installed in the water line or a water meter
with a check valve. Consult your local water supplier or service
agency for further information. Do not plug the temperature-
pressure relief valve.
The anode rod is used to protect the tank from corrosion. Most hot
water tanks are equipped with an anode rod. The submerged rod
sacrifices itself to protect the tank. Instead of corroding the tank,
water ions attack and eat away the anode rod. This does not affect
the water’s taste or color. The rod must be maintained to keep the
tank in operating condition.
draInInG
Anode deterioration depends on water conductivity, not necessarily
water condition. A corroded or pitted anode rod indicates high water
conductivity and should be checked and/or replaced more often than
an anode rod that appears to be intact. Replacement of a depleted
anode rod can extend the life of your water heater. Inspection should
be conducted by a qualified technician, and at a minimum should be
checked annually after the warranty period.
teMperature-pressure
relIef valve operatIon
The water heater should be drained if being shut down during
freezing temperatures. Also periodic draining and cleaning of
sediment from the tank may be necessary.
1. Set the blower switch to the “OFF” position.
2. CLOSE the cold water inlet valve to the water heater.
3. OPEN a nearby hot water faucet and leave open to allow for
draining.
4. Connect a hose to the drain valve and terminate to an adequate
drain.
The temperature-pressure relief valve must be manually operated
at least once a year.
5. OPEN the water heater drain valve to allow for tank draining.
note: If the water heater is going to be shut down and
drained for an extended period, the drain valve should be
left open with hose connected allowing water to terminate
to an adequate drain.
6. CLOSE the drain valve.
7. Follow instructions in the “Filling The Water Heater” section.
8. Follow the lighting instructions on the label or see “Lighting
Instructions” in this manual to restart the water heater.
fIGure 23.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
servIce
If you are not thoroughly familiar with gas codes, your water heater,
and safety practices, contact your gas supplier or qualified installer
If a condition persists or you are uncertain about the operation of
the water heater contact a service agency.
to check the water heater.
Read this manual first. Then before checking the water heater make
sure the gas supply has been turned “OFF”, and never turn the gas
“ON” before the tank is completely full of water.
Use this guide to check a “Leaking” water heater. Many suspected
“Leakers” are not leaking tanks. Often the source of the water can
be found and corrected.
leaKaGe checKpoInts
Never use this water heater unless it is completely filled with water.
To prevent damage to the tank, the tank must be filled with water.
Water must flow from the hot water faucet before turning “ON” gas
to the water heater.
B
A *Condensation may be seen on pipes in humid weather or pipe
connections may be leaking.
d
B. *The anode rod fitting may be leaking.
c
C. Small amounts of water from temperature-pressure relief valve
may be due to thermal expansion or high water pressure in your
area.
D. *The temperature-pressure relief valve may be leaking at the
tank fitting.
E. Water from a drain valve may be due to the valve being slightly
opened.
F. *The drain valve may be leaking at the tank fitting.
G. Combustion products contain water vapor which can condense
on the cooler surfaces of the tank. Droplets form and drip onto
the burner or run on the floor. This is common at the time of
start-up after installation and when incoming water is cold.
f
G
e
H. Water in the water heater bottom or on the floor may be
from condensation, loose connections, or the relief valve.
DO NOT replace the water heater until a full inspection of
all possible water sources is made and necessary corrective
steps taken.
Leakage from other appliances, water lines, or ground seepage
should also be checked.
*
To check where threaded portion enters tank, insert cotton
swab between jacket opening and fitting. If cotton is wet, follow
“Draining” instructions in the “Periodic Maintenance” section and
then remove fitting. Put pipe dope or teflon tape on the threads
and replace. Then follow “Filling the Water Heater” instructions
in the “Installing the New Water Heater” section.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
repaIr parts lIst
8
16
Key no.
1
part description
7
pipe nipple
9
2
stamped steel Burner
cast Iron Burner
2a
3
1
Burner tube (stamped Burner)
Burner tube (cast Iron Burner)
Orifice (Stamped Steel Burner)
Orifice (Cast Iron Burner)
3a
4
4A
5
Ignitor/flame sensor (stamped steel Burner)
Ignitor/flame sensor (cast Iron Burner)
Ignitor Bracket (cast Iron Burner)
Blower assembly
Inlet tube, closed end
Flue Baffle Assembly
anode rod
5a
5B
6
7
8
12
9
10
11
12
13
14
15
16
17
Inner door
outer door
thermostat
t&p relief valve
drain valve
wire harness
flue restrictor
vent Kit
10
14
11
* not shown.
** optional
17
6
15
13
propane Burner asseMBlY
natural Gas Burner
asseMBlY
Now that you have purchased this water heater, should a need ever exist for
repair parts or service, simply contact the company it was purchased from or
direct from the manufacturer listed on the rating plate on the water heater.
WHEN ORDERING REPAIR PARTS, ALWAYS GIVE THE
FOLLOWING INFORMATION:
•
•
•
•
MODEL NUMBER
TYPE GAS (NATURAL OR PROPANE (L.P.)
SERIAL NUMBER
Be sure to provide all pertinent facts when you call or visit.
selling prices will be furnished on request or parts will be
shipped at prevailing prices and you will be billed accordingly.
PART DESCRIPTION
The model number of your Gas Water Heater will be found on the
rating place located above the gas control valve.
thIs Is a repaIr parts lIst, not a pacKInG lIst. parts
are not drawn to scale.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
trouBleshootInG GuIdelInes
trouBle shootInG
Please check guidelines below. For your safety, water heater service should be performed only by a qualified service technician.
Read the GENERAL SAFETY INFORMATION section first.
INTELLI-VENT TROUBLESHOOTING CHART - RESIDENTIAL CONTROL
#
led status
proBleM
solutIon
a B
c
Inadequate or no earth ground
sensed by the Intelli-Vent™
control.
1. Ensure the wall outlet is properly grounded.
1
2. Ensure all ground connections/wires on the
water heater are secure.
Power supply to Intelli-Vent™
control has reversed polarity or a
high resistance to earth ground.
1. Ensure the wall outlet is properly wired.
a B
c
2
2. Ensure all internal 120 VAC wiring connections and
wiring harness have no reversed wires. 120 VAC
“hot” wire must connect to the on/off switch.
3. Ensure the wall outlet is properly grounded.
4. Ensure all ground connections/wires on the water
heater are secure.
Pressure switch circuit remaining
closed for more than 5 seconds
after heating cycle begins.
Blower does not start.
1. Ensure air pressure switch circuit wiring is correct
and the air pressure switch is not jumpered.
a B
c
3
2. Secure power to water heater, check continuity of air
pressure switch contacts with wires disconnected.
service note:
Disconnect power - disconnect one
wire from the air pressure switch
or the vent temperature limit
switch. Turn power back on -
blower should start.
A If pressure switch contacts show continuity (closed
circuit) replace the pressure switch.
B If pressure switch contacts are open and all wiring
is correct - turn the power off for 10-20 seconds
then on again to clear the error code - if the error
code persists replace the Intelli-Vent™ control.
Pressure switch circuit remains open
longer than 5 seconds after the blower
is energized.
1. Ensure the blower is running - check for 120 VAC to
the blower when the heating cycle begins, check the
wiring. If the control does not energize the blower -
replace the Intelli-Vent™ control. If the blower fails to
start when energized -replace the blower assembly.
4
a B c
Blower may run continuously in
this condition.
2. Ensure the air pressure switch sensing tube is properly
connected - not kinked or damaged.
3. Check continuity of vent temperature limit switch - replace
switch if contacts remain open under 160ºF (71°C).
4. Ensure the correct size of vent pipe (2”, 3”, 4”) was used
per installation manual for vent length. Ensure maximum
number of elbows or equivalent feet of vent pipe has not
exceeded maximum limits.
service note:
To learn more about performing Air
Pressure Switch tests visit our web
technical bulletin A-023-06 Air Pressure
Switches.
5. Ensure there are no obstructions in the vent pipe.
6. Check air pressure switch performance - check pressure
with a digital manometer - check continuity of contacts.
(see service note in left column) If the switch proves
defective - replace the air pressure switch and or the
blower assembly as required.
7. If air pressure switch performance test results prove
the air pressure switch is working properly and error
code 4 persists - replace the Intelli-Vent™ control.
The Intelli-Vent™ control has detected
an open ignitor circuit.
1. Check wiring to the hot surface ignitor - replace ignitor
assembly if wiring is damaged or worn.
5
a B
c
service note:
2. Check ignitor assembly plug and the socket on the
Intelli-Vent™ body for good connection. Replace
ignitor assembly and/or control if necessary.
The resistance (ohms) of a hot surface
ignitor will increase over time. If the
resistance at room temperature is near
18.8 ohms - consider replacing the ignitor 3. Check resistance of ignitor at room temperature 77ºF
as a preventative measure.
(25°C) at the plug end. Replace ignitor if resistance
is not within 11.5 and 18.8 ohms at room temperature.
4. If results from the above tests were good and error
code 5 persists - replace the Intelli-Vent™ control.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
trouBleshootInG GuIdelInes
trouBle shootInG
Please check guidelines below. For your safety, water heater service should be performed only by a qualified service technician.
Read the GENERAL SAFETY INFORMATION section first.
INTELLI-VENT TROUBLESHOOTING CHART - RESIDENTIAL CONTROL
#
led status
proBleM
solutIon
Ignition/flame failure.
1. Gas supply is turned off - pressure too low. Ensure
supply and manifold gas pressures are within
requirements in the installation manual. Manifold gas
pressure is non-adjustable if pressure is off by more
a B
c
6
The water heater has reached the
maximum number of retries and is
currently locked out for one hour.
than 0.3” W.C. (75 Pa) replace the Intelli-Vent™ control.
Cycle the power to the water heater
off and on to reset.
2. Low supply voltage - should be 115 -125 VAC.
3. Ensure flame sensor is making good contact with the
burner flame, ensure flame is steady see #8 below.
service note:
The resistance (ohms) of a hot surface
ignitor will increase over time. If the
resistance at room temperature is near
18.8 ohms - consider replacing the ignitor
as a preventative measure.
4. Ensure the flame sensor is clean - use ultra fine steel
wool or Scotch-Brite™ pad to clean flame sensor.
5. Ensure the hot surface ignitor is positioned to provide
consistent ignition.
6. Check for any cracks in ignitor assembly ceramic
insulators - replace ignitor assembly if damaged.
7. Check resistance of ignitor at room temperature (77ºF)
(25°C) at the plug end. Replace ignitor if resistance is
not within 11.5 and 18.8 ohms at room temperature.
8. Ensure the correct size of vent pipe (2”, 3”, 4”) was
used per installation manual for vent length. Using larger
pipe than required may cause excessive air turbulance
in the combustion chamber.
Self diagnostic tests have found a problem
with the gas valve driver circuit, internal
microprocessor, or other internal circuits.
1. Turn the power off for 10-20 seconds then on again to
clear these error codes.
a
a
B
B
c
c
7
8
2. If any of these error codes persist or cannot be cleared-
replace the Intelli-Vent™ control.
a
a
B c
9
Flame signal has been sensed out of
proper sequence.
1. Turn the power off for 10-20 seconds and then on again
again to clear this error code.
B
c
10
2. Replace the Intelli-Vent™ control if this error code persists.
Water temperature in the tank has
exceeded 195°F (91°C) and has
activated the ECO.
1. Turn the power off for 10-20 seconds then on again
to clear this error code.
a B
c
c
c
11
12
2. Replace the Intelli-Vent™ if the error code persists.
The self diagnostic check detected one
or both of the temperature adjust buttons
are stuck.
1. Press and release temperature adjust buttons. If the
above action does not clear the error, the control will
continue to regulate water temperature at the last setting.
However, settings will no longer be adjustable - the
control should be replaced.
a
B
The self diagnostic test has detected the
water temperature sensor (thermistor) is
either open or shorted.
1. Turn the power off for 10-20 seconds then on again
to clear this error code.
13
a B
2. Replace the Intelli-Vent™ control if this error code persist.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
trouBleshootInG GuIdelInes
These guidelines should be utilized by a qualified service agent.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
notes:
33
Download from Www.Somanuals.com. All Manuals Search And Download.
notes:
34
Download from Www.Somanuals.com. All Manuals Search And Download.
lIMIted resIdentIal Gas warrantY
state of California where such charges are the manufacturer’s
responsibility.
c. All cost necessary or incidental for handling and administrative charges,
and for any materials and/or permits required for installation of the
replacement heater or part.
THIS WARRANTY IS APPLICABLE TO THE ORIGINAL OWNER ONLY.
If the glass lined tank in this water heater should prove upon examination
by the State Water Heaters (warrantor) to have leaked during the warranty
period in normal residential use, due to natural corrosion from potable water
therein, thewarrantorwillfurnishtheORIGINALOWNERareplacementwater
heater of equivalent size and current model, or a replacement part for any
component part which fails in normal use, in accordance with the warranty
terms and conditions specified below. THE REPLACEMENT MODEL OR
PARTWILLBE WARRANTED FOR ONLYTHE UNEXPIRED PORTION OF
THE ORIGINAL WARRANTY. The warranty period will be determined by
the original installation date of the water heater. PROOF-OF-PURCHASE
AND PROOF-OF-INSTALLATION ARE NECESSARY TO VALIDATE THIS
WARRANTY. This warranty is not transferable and applies to models listed
in Table 1 which are produced after December 31, 1996.
lIMItatIon on IMplIed warrantIes
Implied warranties, including any warranty of merchantability imposed on
the sale of this heater under state law are limited to one year duration for the
heater or any of its parts. Some states do not allow limitations on how long
an implied warranty lasts, so the above limitations may not apply to you.
claIM procedure
Any claim under this warranty should be initiated with the dealer who sold
the heater, or with any other dealer handling the warrantor’s products. If
this is not practical, the owner should contact: State Water Heaters, 500
Tennessee Waltz Parkway; Ashland City, TN 37015.
TABLE 1
WARRANTY PERIOD
MODEL
GS675YRVIT
GS675HRVIT
TANK1
PARTS2
6 YEARS
6 YEARS
The warrantor will only honor replacement with identical or similar water
heater or parts thereof which are manufactured or distributed by the
warrantor.
6 YEARS
6 YEARS
When the water heater has been used for other than single family residential
application: 1. The tank warranty should be reduced to 1 year. 2. The parts
warranty should be reduced to one year for all models. Returned parts which
meet any of the following conditions are not covered by this warranty: 1)
improper installation or removal, 2) damaged by other than normal wear, 3)
replaced for cosmetic purposes, or 4) returned with defaced date codes.
Dealer replacements are made subject to in-warranty validation by warrantor.
PROOF-OF-PURCHASE AND PROOF-OF-INSTALLATION DATES
ARE REQUIRED TO SUPPORT WARRANTY FOR CLAIM FROM
ORIGINAL OWNER. THIS FORM DOES NOT CONSTITUTE PROOF-
OF-PURCHASE OR PROOF-OF-INSTALLATION.
condItIons and eXceptIons
dIsclaIMers
This warranty should apply only when the water heater is installed and
operated in accordance with 1) all local fire codes and plumbing codes,
ordinances and regulations, 2) the printed instructions provided with it, 3)
good industry practices, and 4) proper safety practices such as but not
limited to a properly sized drain pan if installed in an area where leakage
from connections of the tank would result in damage to the area adjacent
NO EXPRESS WARRANTY HAS BEEN OR WILL BE MADE IN BEHALF
OF THE WARRANTOR WITH RESPECT TO THE MERCHANTABILITY
OF THE HEATER OR THE INSTALLATION, OPERATION, REPAIR OR
REPLACEMENTOFTHEHEATERORPARTS. THEWARRANTORShould
NOT BE RESPONSIBLE FOR WATER DAMAGE, LOSS OF USE OF THE
to the heater. In addition, a new temperature and pressure relief valve, UNIT,INCONVENIENCE,LOSSORDAMAGETOPERSONALPROPERTY,
certified toANSI Z21.22/CSA4.4 and the code requirements ofASME must
have been properly installed and piped to the nearest drain.
OR OTHER CONSEQUENTIAL DAMAGE. THE WARRANTOR Should
NOT BE LIABLE BY VIRTUE OF THIS WARRANTY OR OTHERWISE FOR
DAMAGE TO ANY PERSONS OR PROPERTY, WHETHER DIRECT OR
INDIRECT, AND WHETHER ARISING IN CONTRACT OR IN TORT.
This warranty should apply only when the heater is:
• owned by the original purchaser;
• used at temperatures not exceeding the maximum calibrated setting of
its thermostat;
Somestatesdonotallowthelimitationorexclusionofincidentalorconsequential
damages, so the above limitation or exclusion may not apply to you.
• not subjected to excessive water pressure fluctuations and not subject
to an operating pressure greater than 150 P.S.I.;
• filled with potable water, free to circulate at all times and with the tank
free of damaging water sediment or scale deposits;
• used in a non-corrosive and non-contaminated atmosphere;
• used with factory approved anode(s) installed;
• in its original installation location;
• in the United States, its territories or possessions, and Canada;
• sized in accordance with proper sizing techniques for residential water
heaters;
This warranty gives you specific legal rights, and you may also have other
rights which vary from state to state.
This warranty gives you specific legal rights, and you may also have other
rights which vary from state to state. Should governmental regulations or
industry standards prohibit the Manufacturer from furnishing a comparable
model replacement under this warranty, the Owner will be furnished with
the closest comparable water heater meeting the current governmental
regulations and industry standards.Asupplementary fee may be assessed
to cover the additional cost associated with the changes made to meet
applicable regulations and standards.
• bearing a rating plate which has not been altered, defaced or removed
except as required by the warrantor;
• used in an open system or in a closed system with a properly sized and
installed thermal expansion tank;
Fill out and keep with water heater.
• fired at the factory rated input using the fuel stated in the face of the
rating plate;
• operated with the inner and outer combustion chamber doors in place;
• maintained in accordance with the instructions printed in the manual
included with the heater.
IMportant InforMatIon
Model Number__________________________________________
Serial Number__________________________________________
Installation Information:
Any accident to the water heater or any part thereof (including freezing,
fire, floods, or lightning), any misuse, abuse or alteration of it, any operation
of it in a modified form, or any attempt to repair tank leaks or parts, will
void this warranty.
Date Installed __________________________________________
Company’s Name _______________________________________
Street or P.O. Box ______________________________________
City, State, and Zip Code _________________________________
Phone Number _________________________________________
Plumber’s Name ________________________________________
servIce and laBor responsIBIlItY
UNDER THIS LIMITED WARRANTY, THE WARRANTOR WILLPROVIDE
ONLY A REPLACEMENT WATER HEATER OR PART THEREOF. THE
OWNER IS RESPONSIBLE FOR ALL OTHER COSTS. Such costs may
include but are not limited to:
a. Labor charges for service, removal, or reinstallation of the water heater
or part thereof.
b. Shipping and delivery charges for forwarding the new water heater
or replacement part from the nearest distributor and returning the
claimed defective heater or part to such distributor except in the
Download from Www.Somanuals.com. All Manuals Search And Download.
500 tennessee waltz parkway,
ashland city, tn 37015
www.statewaterheaters.com
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Sennheiser Satellite Radio EK 2000 User Manual
Sharp Stereo System MD M2H User Manual
Silvercrest Waffle Iron SDW 1200 A1 User Manual
Singer Sewing Machine 114W100 User Manual
Sony Computer Drive CRX1750MU User Manual
Sony Computer Monitor GDM 20OPS User Manual
Sony MP3 Player AZ HS1 User Manual
Sony Personal Computer PCV L640 User Manual
Sony Portable CD Player MHC W550 User Manual
Sony Speaker SRS A201 User Manual