Preface  
This manual is a reference to the hardware components, configuration and operation of  
the Hot Standby CPU Redundancy system for the Series 90 -70 Programmable Logic  
Controller. This redundancy system is one of several redundancy alternatives that may  
be incorporated into a Series 90-70 Programmable Logic Controller system (see  
AppendixA).  
The information in this manual is intended to supplement the information contained in  
the system installation, programming, and configuration information found in the  
manuals listed below under ”Related Publications”.  
Content of this Manual  
Chapter 1. Introduction: describes the basic system features of the Hot Standby CPU  
Redundancy system Control Strategy, and provides an overview of system components,  
configuration, and operation.  
Chapter 2. Components: describes the hardware components for the Hot Standby CPU  
Redundancy system.  
Chapter 3. Configuration: describes the special configuration requirements of a Hot  
Standby CPU Redundancy system and provides an example of system configuration.  
Chapter 4. Operation: describes the operation of a Hot Standby CPU Redundancy  
system, fault detection and actions taken, and the on-line repair of a failed component.  
Appendix A. Redundancy Alternatives: describes the redundancy alternatives for the  
Series 90-70 Programmable Logic Controller for those readers not familiar with those  
alternatives.  
Related Publications  
For more information, refer to these publications:  
Genius I/O System Users Manual (GEK-90486-1). Reference manual for system  
designers, programmers, and others involved in integrating Genius I/ O products in a  
PLC or host computer environment. This book provides a system overview, and  
describes the types of systems that can be created using Genius products. Datagrams,  
Global Data, and data formats are defined.  
Genius Discreteand AnalogBlocks Users Manual (GEK-90486-2). Reference manual for  
system designers, operators, maintenance personnel, and others using Genius discrete  
and analog I/ O blocks. This book contains a detailed description, specifications,  
installation instructions, and configuration instructions for discrete and analog blocks.  
Series 90-70PLCInstallation Manual (GFK-0262). This book describes the hardware  
components in a Series 90-70 PLC system, and provides the details of system installation.  
Logicmaster 90-70ProgrammingSoftwareUsers Manual (GFK-0263). A programming  
software user s manual for system operators and others using the Logicmaster 90-70  
software to program, configure, monitor, or control a Series 90-70 PLC system.  
iii  
GFK-0827  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Preface  
Series90-70 PLC ReferenceManual (GFK-0265). Reference manual which describes  
operation, fault handling, and Logicmaster 90-70 programming instructions for the  
Series 90-70 PLC.  
Series 90-70RemoteI/O Scanner Users Manual (GFK-0579). Reference manual for the  
Remote I/ O Scanner, which interfaces a drop containing Series 90-70 modules to a  
Genius bus. Any CPU capable of controlling the bus can be used as the host. This book  
describes the Remote I/ O Scanner features, configuration, and operation.  
Series 90-70Bus ControllerUsers Manual (GFK-0398). Reference manual for the bus  
controller, which interfaces a Genius bus to a Series 90-70 PLC. This manual describes  
the installation and operation of the Bus Controller. It also contains the programming  
information needed to interface Genius I/ O devices to a Series 90-70 PLC.  
We Welcome Your Comments and Suggestions  
At GE Fanuc automation, we strive to produce quality technical documentation. After  
you have used this manual, please take a few moments to complete and return the  
Reader s Comment Card located on the next page.  
Henry A. Konat  
Senior Technical Writer  
GFK-0827  
iv  
Hot Standby CPU Redundancy Users Manual - December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Chapter 1  
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1
Hot Standby CPU Redundancy Product . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Features of the Hot Standby CPU Redundancy Product . . . . . . . . . . . . .  
Benefits of the Hot Standby CPU Redundancy Product . . . . . . . . . . . . .  
I/ O Systems for Hot Standby CPU Redundancy Systems . . . . . . . . . . . .  
Genius I/ O System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
LocalI/ O System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Cable Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Control Strategy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Basic Hot Standby Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Redundancy CPU Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Redundancy Communications Module . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Bumpless Switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Synchronized CPUs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Effect on Scan Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Fail Wait Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Switch to Backup Unit Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Configurable Backup Data Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
On-Line Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
On-Line Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Programming Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Configuration Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Definition of Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Commonly Used Acronyms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1
3
3
4
4
4
4
5
5
7
7
8
8
8
8
8
9
9
9
10  
10  
11  
12  
GFK–0827  
Series 90–70 Hot Standby CPU Redundancy Users Guide – December 1993  
v
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Chapter 2  
System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
13  
Redundancy CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
CPU Architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
CPU Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
13  
14  
15  
CPU Mode Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16  
Memory Protect Keyswitch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
CPU Status LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Battery Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Serial Port Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18  
Expansion Memory Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18  
Redundancy Communications Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
RCM Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
19  
19  
RCM System Status LEDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20  
Unit Selection Pushbutton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21  
RCM Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21  
Bus Transmitter Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
22  
LED Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
BTM Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
Bus Receiver Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
23  
I/ O Bus SignalTermination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24  
LED Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24  
BRM Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24  
Genius Bus Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
24  
Genius Bus Controller User Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
LED Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
GBC Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26  
Racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
26  
GFK–0827  
Series 90–70 Hot Standby CPU Redundancy Users Guide – December 1993  
vi  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Chapter 3  
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
27  
Configuring a Hot Standby CPU Redundancy System . . . . . . . . . . . . . . . . .  
Redundancy System Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Basic Redundancy System Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Logicmaster 90 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
I/ O System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Screens for Fault Category Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Handling Folders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Configuration with Logicmaster 90-70 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Configuration of a Redundancy CPU Module . . . . . . . . . . . . . . . . . . . . . . . . .  
Redundant CPU Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
27  
28  
28  
28  
28  
29  
30  
30  
31  
33  
Redund Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
Background Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
Normal Sweep Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
Constant Window Sweep Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
Constant Sweep Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
Ctrl Strgy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36  
Fail Wait . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36  
SharedI/ O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36  
Configuring a CPU Expansion Memory Board . . . . . . . . . . . . . . . . . . . . .  
Configuration of a Redundancy Communications Module . . . . . . . . . . . . . .  
Configuration of a Genius Bus Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Paired GBC Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Configuring a Primary Redundant PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Select the Redundancy CPU Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Select an Expansion Memory Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Configure the Redundant Communications Module . . . . . . . . . . . . . . . .  
Configure a Genius Bus Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Configure Genius I/ O Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Configure the Bus Transmitter Module . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Configuring a Secondary Redundant PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Change Redund Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
39  
40  
42  
42  
44  
45  
46  
47  
48  
50  
51  
52  
53  
GFK–0827  
Series 90–70 Hot Standby CPU Redundancy Users Guide – December 1993  
vii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Chapter 4  
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Section 1: System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
55  
55  
Power-Up Sequence of a Redundant CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Incompatible Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Resynchronization of the Redundant CPU . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Hot-Standby Redundancy Control Strategy . . . . . . . . . . . . . . . . . . . . . . . . . .  
Synchronous Scan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
First Data Transfer %I, %AI and Synchronization . . . . . . . . . . . . . . . . . . .  
55  
56  
57  
58  
59  
59  
Data Transfer from Backup Unit to Active Unit . . . . . . . . . . . . . . . . . . . . . 60  
Second Data Transfer %Q, %AQ, %R, and %M . . . . . . . . . . . . . . . . . . . . .  
Switching Control to Backup Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
61  
61  
Role Switch SVCREQ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62  
%S References for CPU Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Redundancy CPU Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Features not Available with CPU 780 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
63  
64  
64  
I/ OInterrupts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64  
Timed Interrupts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64  
VME Integrator Racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64  
STOP/ IOSCAN Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64  
Flash Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64  
Differences in Operation for CPU 780 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
65  
RUN Disabled Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65  
Configuration of Fault Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67  
STOP to RUN Mode Transition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68  
Background Window Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68  
Background User Checksum and Background Window  
Timing Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69  
Miscellaneous Operation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
70  
Timer and PID Function Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70  
Timed Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70  
OVR_PRE %S Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70  
Genius Bus Controller Switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71  
GFK–0827  
Series 90–70 Hot Standby CPU Redundancy Users Guide – December 1993  
viii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Section 2: Fault Detection and Control Actions . . . . . . . . . . . . . . .  
72  
Fault Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Fault Categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Changing Fault Category Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
PLC Fault Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Faulting RCMs, Losing Links, and Terminating Communications . . . . .  
Fault Actions in a CPU Redundancy System . . . . . . . . . . . . . . . . . . . . . . .  
On-Line Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Maintaining Parallel Bus Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
On-Line Repair Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Central Processor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Redundancy Communications Module and Cables . . . . . . . . . . . . . . . . .  
Redundancy Communications Link Failures . . . . . . . . . . . . . . . . . . . . . . .  
Bus Transmitter Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Genius Bus Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Genius Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Genius Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
72  
72  
73  
74  
75  
77  
80  
80  
80  
81  
81  
81  
81  
82  
82  
82  
83  
83  
Appendix A Redundancy Alternatives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
85  
Redundancy Alternatives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Series 90-70 Redundancy Through Application Logic . . . . . . . . . . . . . . . . . .  
85  
88  
GFK–0827  
Series 90–70 Hot Standby CPU Redundancy Users Guide – December 1993  
ix  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Figure 1. Example of a Local I/ O Configuration with Expansion Racks in a  
Hot Standby CPU Redundancy System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
5
6
Figure 2. Synchronized Hot Standby CPU Redundancy System Configuration . . . . . . . . . . . . .  
Figure 3. CPU 780 Locations in a Hot Standby CPU Redundancy System . . . . . . . . . . . . . . . . . .  
Figure 4. Redundancy CPU - IC697CPU 780 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 5. Redundancy Communications Module - IC697RCM711 . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 6. Example of RCM Location in a Hot Standby CPU Redundancy System . . . . . . . . . . .  
Figure 7. Example of Multiple Genius Busses in a Hot Standby CPU Redundancy System . . .  
Figure 8. Active and Backup Sweeps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Figure 9. Guide to Selection of Redundancy Option Key for Table 1 (Redundancy Options) . .  
14  
15  
19  
20  
26  
59  
86  
GFK–0827  
Series 90–70 Hot Standby CPU Redundancy Users Guide – December 1993  
x
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Table 1. Capacities for Redundancy CPU, IC697CPU780 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Table 2. Valid Operating Mode Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Table 3. Expansion Memory Boards for CPU 780 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Table 4. Shared I/ O Data Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Table 5. Shared I/ O Reference Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Table 6. Transfer Data Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Table 7. Definition for% S Reference for Redundancy Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Table 8. Fault Zoom Help Text for Redundancy Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Table 9. Maskable Fault Group Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Table 10. Maskable Fault Group Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Table 11. Non-Maskable Fault Group Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Table 12. Non-Maskable Fault Action Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Table 13. Redundancy Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
14  
16  
18  
37  
37  
38  
63  
74  
77  
78  
79  
79  
87  
GFK–0827  
Series 90–70 Hot Standby CPU Redundancy Users Guide – December 1993  
xi  
Download from Www.Somanuals.com. All Manuals Search And Download.  
restart lowapp ARestart oddapp: ARestarts for autonumbers that do not restart in  
each chapter. figure bi level 1, reset table_big level 1, reset chap_big level 1, reset1  
Lowapp Alwbox restart evenap:A1app_big level 1, resetA figure_ap level 1, reset  
table_ap level 1, reset figure level 1, reset Figure 1. table level 1, reset Table 1.  
these restarts oddbox reset: 1evenbox reset: 1must be in the header frame of  
chapter 1. a:ebx, l 1 resetA a:obx:l 1, resetA a:bigbx level 1 resetA a:ftr level 1 resetA  
c:ebx, l 1 reset1 c:obx:l 1, reset1 c:bigbx level 1 reset1 c:ftr level 1 reset1  
Reminders for autonumbers that need to be restarted manually (first instance will  
always be 4) let_in level 1: A. B. C. letter level 1:A.B.C. num level 1: 1. 2. 3.  
num_in level 1: 1. 2. 3. rom_in level 1: I. II. III. roman level 1: I. II. III. steps level 1:  
1. 2. 3.  
Chapter 1 Introduction  
section level 1 1  
figure bi level 1  
table_big level 1  
1
This chapter is an introduction to a method of CPU Redundancy for the Series 90-70  
Programmable Logic Controller which is referred to as the Hot Standby CPU  
Redundancy product.  
The contents of this chapter provide:  
a basic description of what Hot Standby CPU Redundancy is;  
tells what it does for you - the user;  
provides a basic description of the components of the Hot Standby CPU  
Redundancy system;  
provides a basic description of how a system is configured using the Logicmaster  
90-70 programming software configurator function;  
lists certain restrictions that you must be aware of;  
and defines terminology unique to this product.  
Note  
For those who are not familiar with the various redundancy alternatives  
which may be applied to a Series 90-70 PLC system, please refer to  
Appendix A before proceeding with this chapter. For those who are familiar  
with those redundancy alternatives please proceed with the dicussion of the ’Hot  
Standby CPU Redundancy Product” below.  
Hot Standby CPU RedundancyProduct  
CPU Redundancy for the Series 90-70 Programmable Logic Controller provides a  
method of allowing a critical application or process to continue operating if a failure  
occurs in any single component. The CPU Redundancy system described in this guide  
is the Hot Standby CPU Redundancy product. A Hot Standby CPU Redundancy system  
consists of two CPUs connected to one or more Genius I/ O buses. Each PLC is  
configured as either Primary or Secondary. The Primary PLC is the preferred PLC and  
1
GFK-0827  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1
contains all redundant Genius Bus Controllers at Serial Bus Address 31; the Secondary  
PLC contains all redundant Genius Bus Controllers at Serial Bus Address 30. The CPU  
that currently controls the system is called the active unit, the other CPU is the standby  
unit.  
If certain system failures are detected in the active unit, control is switched to the  
standby unit. Control can also be switched by depressing a pushbutton on the  
Redundancy Communications Module, or through the user s logic program. When a  
switch of control occurs, the units switch roles; the active unit becomes the standby unit  
and the standby unit becomes the active unit.  
Each PLC must have a Redundancy CPU module (catalog number IC697CPU780) and a  
Redundancy Communications module (IC697RCM711) which provides the synchronization  
link between the two units, (and a Bus Transmitter Module (IC697BEM713)). The  
scanning process of both CPUs is synchronized to keep active and standby units in  
lockstep to minimize ”bumps” or upsets to the process when switching from the active  
to the standby unit. The effect of this action is a bumpless switch.  
The Series 90-70 CPU Redundancy system runs synchronously with a transfer of all  
control data that defines machine status and any internal data needed to keep the two  
CPUs operating in sync, and is capable of executing the same program and obtaining the  
same results. The transfer of data from the active unit to the standby unit occurs once  
per sweep. These CPU to CPU transfers are checked for data integrity.  
GFK-0827  
2
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1
Features of the Hot Standby CPU RedundancyProduct  
Bumpless switching  
Synchronized CPUs  
20 millisecond scan extension (nominal). This figure is variable, depending on  
amount of data transferred.  
One scan switching (in most cases)  
Configurable backup data size  
No single point of failure (excludingGeniusI/ O)  
Redundant backup communications  
On–line repair of failed component  
On–line programming  
Same or different programs in Primary and Secondary units  
Redundancy CPU has a 16 MHz microprocessor, configurable memory and  
configurable addressing capacity  
Redundancy Communications Module  
Manual pushbutton switch for switching control between active and backup  
CPUs  
Five Status LEDs  
– Board OK  
– Local System Ready  
– Local System Active  
– Remote System Ready  
– Remote System Active  
Status Bits (%S) reflect redundancy status of Primary/ Secondary units  
Program control switching  
Memory parity and checksums  
Common I/ O on Genius bus  
Background Diagnostics  
– Processor test  
– PLC CPU EPROM CRC Validation  
– User program checksumming  
– Time-of-Day/ ElapsedTime Clock test  
Memory Protect Keyswitch  
Benefits of the Hot Standby CPU RedundancyProduct  
Implementation of the Hot Standby CPU Redundancy product provides you with a  
method of ensuring that a critical control system or process is uninterrupted in the event  
of a failure of any single component (excluding I/ O) of the PLC system.  
GFK-0827  
Chapter 1 Introduction  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1
I/O Systems for Hot Standby CPU Redundancy Systems  
Both Series 90-70 Local I/ O and Genius I/ O systems can be present in a Hot Standby  
CPU Redundancy control system. The two units are not required to have matching I/ O  
systems. They may have different numbers of I/ O racks, and different local I/ O or  
option modules.  
Genius I/O System  
A Genius I/ O system is the I/ O system that is included in the redundancy system as  
shown below. The system can have multiple Genius I/ O buses. Any Genius device can  
be placed on the bus (Genius blocks, Remote I/ O Scanner, etc.). The Genius devices are  
under control of the active unit in the Redundancy system. The Genius Bus Controller  
in the Primary Unit has a Serial bus Address of 31; the Genius Bus Controller in the  
Secondary Unit has a Serial Bus Address of 30. Data from Serial Bus Address 31 is the  
preferred data when data is being sent from both units to devices on the Genius bus.  
Local I/O System  
Local I/ O can be configured in the overall PLC system; however, it is not part of the Hot  
Standby CPU Redundancy system. Control of Local I/ O is done normally through the  
user s logic program. The user may choose to transfer or not transfer this data. A failure  
in the Local I/ O system will affect the system as described in GFK-0265, the Series 90-70  
Programmable Controller Reference Manual.  
CableConnections  
The I/ O system is configured ”normally” except as described below (see the following  
figure). That is, a Bus Transmitter Module configured in rack 0 is connected through a  
parallel I/ O cable to a Bus Receiver Module in the next rack. The link is continued from  
this Bus Receiver Module to the Bus Receiver Module in the next rack. This link is  
continued with a maximum of six expansion racks. Then, the last Bus Receiver is  
connected via an I/ O cable with built-in termination (catalog IC697CBL811 (10 feet (3m))  
or IC697CBL826 (25 feet (7.5m)). The last module in the parallel I/ O bus link must be a  
Redundancy Communications Module (RCM). This terminated I/ O cable allows  
replacement of the RCM without interrupting the running system. If no expansion  
racks are used, the terminated I/ O cable is connected directly from the Bus Transmitter  
Module to the Redundancy Communications Module.  
Note  
The exception to a normally configured system is that Rack 7, which  
normally can contain I/ O modules is not available for physical I/ O  
modules in a Hot Standby CPU Redundancy system.  
GFK-0827  
4
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1
a47000  
PRIMARY UNIT  
RACK 0  
SECONDARY UNIT  
RACK 0  
C
P
S
P
S
B
T
M
R
C
M
G
B
C
I
O
I
O
I
O
I
O
I
O
B
T
M
G
B
C
C
P
U
R
C
M
I
O
I
O
I
I
I
O
O O  
P
U
30  
31  
TERMINATED I/O CABLE  
*
REMOTE DROP  
B
L
O
C
K
B
L
O
C
K
B
L
O
C
K
S
C
A
N
N
E
I
O
I
O
I
O
I
O
I
O
I
O
I
O
I
O
P
S
LOCAL I/0  
CAN BE IN  
R
RACKS  
0 - 6  
RACK 1  
I
O
I
O
I
O
I
O
I
O
I
O
I
O
I
O
P
S
B
R
M
Y
Y
RACK 6  
I
I
O
I
O
I
O
I
O
I
O
I
O
I
O
P
S
B
R
M
O
I/O CABLE WITH BUILT-IN TERMINATION  
IC697CBL811 (10 FEET (3m))  
*
IC697CBL826 (25 FEET (7.5m)  
TERMINATED I/O CABLE  
*
Figure 1. Example of a Local I/O Configuration with Expansion Racks in a  
Hot Standby CPU Redundancy System  
Control Strategy  
Control strategy refers to the type of redundancy alternative that may be used. For the  
Hot Standby CPU Redundancy product, the control strategy is referred to as Genius Hot  
Standby (GHS). The control strategy must be selected when configuring the system with  
the Logicmaster 90-70 programming Software Configurator function.  
Basic Hot Standby Operation  
In a basic Genius Hot Standby CPU Redundancy system, Genius blocks receive outputs  
from two PLCs (Primary PLC and Secondary PLC), but they are normally controlled  
directly by the Genius Bus Controller at serial bus address 31 (Genius Bus Controller in  
the Primary PLC). If no output data is available from bus address 31 (the preferred data)  
GFK-0827  
Chapter 1 Introduction  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1
for three consecutive Genius I/ O bus scans, the outputs are then controlled by the  
Genius Bus Controller at serial bus address 30 (Genius Bus Controller in the Secondary  
PLC).  
If output data is not available from either bus address 31 or 30, the outputs go to their  
configured default (OFF or hold last state). The PLC at serial bus address 31 always has  
priority, therefore when the PLC with serial bus address 31 is On-line, it always has  
control of the outputs.  
The redundancy system configuration is shown in the following figure. This example  
configuration shows only the redundancy system components. As described previously,  
a system can also contain Local I/ O which is not a part of the redundancy scheme.  
PRIMARY UNIT  
SECONDARY UNIT  
a47001  
P
S
C
P
U
P C B  
P T  
U M M C  
R
C
G
B
B
T
R
C
G
B
S
M M C  
30  
31  
TERMINATED I/O CABLE  
TERMINATED I/O CABLE  
*
*
other Genius devices  
REMOTE DROP  
B
L
O
C
K
B
L
O
C
K
B
L
O
C
K
S
C
A
N
N
E
R
I
I
I
I
I
I
I
I
O
P
S
O O O O O O O  
Legend  
PS.................... Power Supply.............................................. IC697PWRXXX  
CPU................. Central ProcessorUnit.............................. IC697CPU780  
BTM................. Bus TransmitterModule............................. IC697BEM713  
RCM................ Redundancy Communications Module..... IC697RCM711  
GBC................ Genius Bus Controller................................ IC697BEM731  
BLOCK........... GeniusI/OBlock........................................ IC660XXXYYY  
SCANNER....... Remote I/O Scanner.................................... IC697BEM733  
*...................... TerminatedI/OCable................................. IC697CBL811/826  
Figure 2. Synchronized Hot Standby CPU Redundancy System Configuration  
GFK-0827  
6
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1
Redundancy CPU Module  
The same model of CPU must be installed in both the Primary and Secondary PLCs.  
This CPU, which is the only CPU that currently supports synchronized Hot Standby  
CPU redundancy, is the CPU 780 (catalog number IC697CPU780). This CPU is similar to  
the existing IC697CPU782 CPU in that it has an 80386DX microprocessor which operates  
at a speed of 16 MHz, supports floating point calculations, and requires an expansion  
memory board which can be 128 KBytes, 256 Kbytes with 256 KBytes of non-volatile  
flash memory, 256 KBytes or 512 KBytes.  
NOTE  
It is important to note that the following features available with other  
Series 90-70 CPUs arenot supported by the CPU 780: I/ O interrupts,  
timed interrupts, the VME Integrator Racks (IC697CHS782 and  
IC697CHS783), Flash memory operation, and STOP/ IOSCAN mode. In  
addition, the operation of several other features is changed. For more  
detailed information on these features, please see Chapter 4.  
As with the other Series 90-70 CPUs, the CPU 780 must be installed in slot 1 of rack 0  
(CPU rack). The Primary unit and the Secondary unit must each have a Redundancy  
CPU installed in slot 1 of rack 0 with one CPU configured as the Primary CPU and the  
other CPU configured as the Secondary CPU. Configuration of the CPU 780 in the  
Primary unit and the CPU 780 in the Secondary unit must be done separately (see  
Chapter 3 for details of configuration with the Logicmaster 90-70 configurator function).  
Redundancy Communications Module  
The Redundancy Communications Module (RCM), catalog number IC697RCM711,  
provides a path (see Figure 1) for sharing data between the two CPUs in the redundant  
system. The RCM has five LEDS:  
BOARD OK  
LOCALSYSTEM READY  
LOCALSYSTEM ACTIVE  
REMOTE SYSTEM READY  
REMOTE SYSTEM ACTIVE.  
These LEDs report the status of the health of the RCM and the control status of the Hot  
Standby CPU Redundancy system. The status provided by these LEDs is also provided  
in an area of %S memory (%S33 through %S39) which is accessible from the user logic  
program but cannot be altered or overridden.  
The module has a momentary pushbutton switch which when depressed for 1 second  
and released allows you to manually switch control from the active unit to the standby  
unit. The switch between units can also be controlled through user logic  
implementation of a SVC_REQ function that is activated by a discrete input point. Both  
of these switch requests may only be made every 10 seconds.  
In a synchronized system, I/ O data is controlled by only one unit (the active unit) but is  
shared between both units (active and backup units). The RCM provides the path for a  
synchronizing message from the active to the backup unit which is used to synchronize  
GFK-0827  
Chapter 1 Introduction  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1
the two CPUs and provides the communications path for the transfer of I/ O data  
between the two units. An RCM must be configured in both the Primary PLC and the  
Secondary PLC. The RCM must reside in the CPU rack (rack 0) in a system and there  
can be no empty slot between the RCM and the CPU (there can be other modules).  
Bumpless Switching  
Bumpless switching occurs when the active unit fails and system control is transferred to  
the backup unit without affecting the operation of the process under control.  
SynchronizedCPUs  
For bumpless switching to occur, the CPU in the active and backup units must operate in a  
synchronous fashion, that is, the operation of both units must occur at the same time (or as  
close to the same time as possible). There are two synchronization points in the sweep: one  
immediately after the input scan and the other immediately before the output scan.  
Synchronization data is passed from the active to the backup unit at the first  
synchronization point, which occurs after the input scan. Specifically, after the inputs are  
scanned, the inputs that were just read (%I and %AI) are sent from the active to the backup  
unit and the synchronization message is passed after the input data.  
The second synchronization point occurs immediately after the end of the logic solution  
before the output scan begins. During this time, all remaining control data, including the  
%Q, %AQ, %M and %R memories is transferred from the active unit to the backup unit.  
Effect on Scan Time  
When a system is operating normally (no faults exist in the system) redundancy adds about  
21 ms (includes 5 ms default background window setting) per PLC scan. The effect on scan  
time depends on the system configuration. The following number of data points and  
registers is considered the base configuration on which the 21 ms was calculated.  
512  
256  
2048  
%I, 512 %Q, 512 %M  
%AI, 256 %AQ  
%R  
Each additional 1K %I, %Q, or %M data points adds about 1.8 ms to the scan impact  
(add 25% for each %I or %Q reference if point faults enabled) and each additional 1K of  
%R, %AI, or %AQ registers adds about 5 ms to the scan impact (add 50% for each %AI  
or %AQ reference if point faults enabled).  
Fail Wait Time  
When the active CPU has a failure, the backup CPU will wait for a specified time (in  
milliseconds) before assuming that the link has failed. This time is referred to as the Fail  
Wait time. The duration of this time must be specified during configuration of both the  
Primary and Secondary units and can range from 60 ms to 400 ms (in increments of 10  
ms), with the default value being 60 ms.  
Switch to Backup Unit Time  
The amount of time it takes to switch control from the active unit to the backup unit  
depends on what caused the switch to take place.  
GFK-0827  
8
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1
If the switch occurs due to a controlled condition such as toggling the unit selection  
switch on the Redundancy Communications Module or forcing a switch in the user logic  
program with a SVC_REQ, or because of a fault detected by the PLC CPU, then the  
switch-over will occur at the beginning of the next sweep. The delay will be up to 1  
sweep with the possibility of an input and an output scan after failure detection.  
If the switch occurs due to a failure of the PLC CPU (including loss of power), then the  
switch will occur after the backup unit determines that the active unit has failed to  
rendezvous at the synchronization point. Failure to rendezvous may take up to 2 failwait  
timeouts (1 for each link) to determine that a failure has occurred. Control will not  
transfer, in this case, until both links have been tried unsuccessfully.  
Configurable Backup Data Size  
The maximum size of the backup data (Shared I/ O) is 20 KBytes of Input data and 28  
KBytes of Output data. The shared I/ O data configuration must be the same in both the  
Primary and Secondary units. This shared I/ O data is transferred from the active CPU to  
the backup CPU during the CPU sweep process. A total of up to 56 KBytes of user  
memory is consumed by this data transfer. A maximum of 48 KBytes of the 56 KBytes is  
the total Shared I/ O (20 KBytes %I, %AI; 28 KBytes %Q, %M, %AQ, and %R), while the  
remainder (8 KBytes) is used by the system for internal data transfers, including  
synchronizing data.  
On-Line Programming  
On-line changes to the user logic program are permitted in both the active unit and the  
backup unit. The programming device must be connected to the system in which  
changes are to be made in order to make any on-line changes. Note that all precautions  
regarding power source and grounding for connecting the programming device must be  
followed in accordance with instructions in the Series 90-70 Programmable Controller  
Installation Manual, GFK-0262.  
A connection and disconnection of the parallel programmer cable should only be made  
with the programmer properly grounded, and Logicmaster 90 software properly booted  
up and in OFF-LINE mode. For more information, refer to the Series 90-70 Installation  
manual, GFK–0262.  
On-Line Repair  
A Hot Standby CPU Redundancy system allows you to do on-line repair of failed  
components without disrupting the process under control. Control status of both the  
Primary and the Secondary units can be monitored by the LEDS on the Redundancy  
Communications Modules in each system. When a component of the active unit fails,  
control is switched to the backup unit. The failed component can then be replaced by  
removing power from the rack in which it is installed.  
After replacing the failed component and returning power to the rack, the backup unit  
will resynchronize with the currently active unit. The unit which had failed and was  
previously the active unit will determine its role in the system as part of the  
resynchronization process. If it is the Primary unit (with Serial Bus Address 31) it will  
once again become the active unit, the unit with Serial Bus Address 30 (Secondary unit)  
will again become the backup unit. For more detailed information on replacing failed  
components and resynchronization, see Chapter 4, ”System Operation”.  
GFK-0827  
Chapter 1 Introduction  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1
Programming Considerations  
There are several features in the operation of the Redundancy CPU which are not  
supported or are different then operation of other CPUs. These features are listed below  
and are described in detail in Chapter 4, ”System Operation”.  
The following features are not available with the Redundancy CPU (CPU 780):  
I/ OInterrupts  
Timed Interrupts  
VME Integrator Rack  
STOP/ IOSCAN mode  
Flash memory operation  
The operation of the following features is different with the CPU 780 than with other  
Series 90-70 CPUs:  
RUN/ DISABLEDmode  
Configuration of fault actions  
STOP to RUN mode  
Default Background Window Time  
ConfigurationRequirements  
The Redundancy CPU and the Redundancy Communications Module must be  
configured into the redundancy system. There are several additional parameters (other  
than the normal CPU parameters) that must be configured with the Logicmaster 90-70  
Configurator function which are unique to the Hot Standby CPU Redundancy system.  
The following items require configuration when specifying the CPU 780 (the  
Redundancy CPU) as the CPU for configuration:  
Configuration  
Parameter  
Description  
Fail-wait (60 ms to 400 ms) The time to wait on a failed active PLC before switching to  
the backup CPU. The default value is 60 ms.  
Control Strategy  
Shared I/O References  
Redund Type  
The control strategy for the current configuration. Config-  
ured as a three-character identifier (GHS for Hot Standby  
CPU Redundancy). The default value is GHS (currently  
the only value that is valid).  
The references within the control of the Redundancy sys-  
tem; up to 20 KBytes of Input data and 28 KBytes of Out-  
put data is transferred. The references which may be used  
as shared I/ O are %I, %Q, %AI, %AQ, %R, and %M.  
Whether the CPU being configured is the Primary or Sec-  
ondary CPU in the Redundancy system. Redund Type  
has three possible values: PRIMARY, SECONDARY, or  
SIMPLEX. SIMPLEX (not supported in this release of the  
product) indicates a non–redundant system. The default  
value is PRIMARY.  
GFK-0827  
10  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1
The Primary Unit and the Secondary Unit must be configured separately. That is, the  
programming device should be connected directly to either the Primary or the  
Secondary Unit to configure that unit. When you have completed configuring that unit,  
disconnect the programmer from the configured unit and move it to the other unit and  
proceed with configuration of the second unit. Refer to Chapter 3, ”System  
Configuration” for details of configuring a Redundancy system  
Definition of Terms  
Several new or unfamiliar terms are used throughout this manual which are relevant to  
the discussions of CPU Redundancy. These terms are defined in the following table.  
Ter m  
Definition  
ActiveUnit  
Backup Unit  
CPURedundancy  
The unit that is actively controlling the process.  
That unit that is synchronized with the active unit and able to take over the process.  
A system with two PLC CPU units cooperating to control the same process.  
CriticalComponent A component whose failure causes the PLC (either active or backup) in which it resides to  
stop.  
Hot Standby  
A feature of Genius blocks whereby the block prefers output data from the  
Bus Controller at Serial Bus Address 31. When inputs from that Bus Controller are not  
available,the block takes output data from the Bus Controller at Serial Bus Address30.  
If inputs from neither Controller are available, the block places its outputs in the  
designated defaultstate.  
LocalUnit  
The RCM LEDs and %S status bits refer to the PLC in which they reside as  
the”LocalUnit”.  
Primary Unit  
Redundancy  
The unit in which the Genius Bus Controller s Serial Bus Address is 31.  
A system feature that has multiple elements controlling the same process to provide alter-  
nate functional channels in case of failure.  
RemoteUnit  
The RCM LEDs and status bits refer to the other PLC as the ”Remote Unit”.  
For example, the Primary Unit is the Remote Unit to the Secondary Unit and likewise  
the Secondary Unit is the Remote Unit to the Primary Unit.  
Secondary Unit  
Synchronized  
The unit in which the Genius Bus Controller s Serial Bus Address is 30.  
A unit is considered to be synchronized when it has received the latest status information  
from the Active unit and is running the PLC program in parallel.  
GFK-0827  
Chapter 1 Introduction  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1
CommonlyUsed Acronyms  
A list of acronyms used in this manual are defined for your convenience in the following  
table.  
Acronym  
Definition  
BRM  
BSM  
BTM  
CPU  
EPROM  
GBC  
GHS  
GMR  
HHM  
LED  
BusReceiver Module  
Bus Switching Module  
Bus TransmitterModule  
Central ProcessorUnit  
ErasableProgrammable Read Only Memory  
Genius Bus Controller  
Genius Hot Standby Redundancy  
GeniusModularRedundancy  
Hand Held Monitor  
Light Emitting Diode  
OI  
Operator Interface  
PLC  
ProgrammableLogicController  
Programmable Read–Only Memory  
Random AccessMemory  
RedundancyCommunicationsModule  
RelayLadderDiagram  
PROM  
RAM  
RCM  
PLD  
SBA  
Serial Bus Address  
SNP  
Series 90 Protocol  
VME  
VersaModule Europe:the backplane standard  
used by the Series 90-70 PLC system  
GFK-0827  
12  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 2 SystemComponents  
section level 1 1  
figure bi level 1  
table_big level 1  
2
This chapter describes the hardware components for a Hot Standby CPU Redundancy  
system. It describes the modules required for the system and provides catalog numbers  
of the components. For detailed installation instructions for the Series 90-70 PLC, refer  
to GFK-0262, the Series 90-70 Programmable Controller Installation Manual.  
Redundancy CPU  
The IC697CPU780 Central Processing Unit (CPU) has been designed specifically for  
Series 90-70 Hot Standby CPU Redundancy applications. This is the only Series 90-70 CPU  
that currently supports CPU redundancy .  
Note  
It is important to note that the following features available with other  
Series 90-70 CPUs arenot supported by the CPU 780: I/ O interrupts,  
timed interrupts, the VME Integrator Racks (IC697CHS782 and  
IC697CHS783), Flash Memory operation, and STOP/ IOSCAN mode. In  
addition, the operation of several other features is changed. For more  
detailed information on these features, please see Chapter 4.  
The CPU 780 supports floating point calculations, offers remote programmer keyswitch  
memory protection, and has four status LEDs. Operation of this module may be  
controlled by the three-position RUN/ STOP switch on the module, or remotely by an  
attached programmer and Logicmaster 90-70 Programming Software. Program and  
configuration data can be locked through software passwords or manually by the  
memory protect keyswitch. When the key is in the ”protected” position, program and  
configuration data can only be changed by a programmer connected for parallel  
communications (that is, to the Bus Transmitter Module).  
As with the other Series 90-70 CPUs, the CPU 780 must be installed in slot 1 of rack 0  
(CPU rack). In a Hot Standby CPU Redundancy system, the Primary unit and the  
Secondary unit must each have a Redundancy CPU installed in slot 1 of rack 0. One  
CPU is configured as the Primary CPU and the other CPU is configured as the  
Secondary CPU. Configuration of the CPU 780 in the Primary unit and the CPU 780 in  
the Secondary unit must be done separately (see Chapter 3 for details of configuration  
with the Logicmaster 90-70 configurator function). The following figure shows the CPU  
location in a Hot Standby CPU Redundancy system.  
13  
GFK-0827  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2
PRIMARY UNIT  
SECONDARY UNIT  
a47002  
P
S
C
P
U
P C B  
P T  
U M M C  
R
C
G
B
B
T
R G  
C B  
S
M M C  
30  
31  
RedundancyCommunicationsLink  
RedundancyCommunicationsLink  
CPU 780  
Genius Bus  
Figure 3. CPU 780 Locations in a Hot Standby CPU Redundancy System  
The capacities for the CPU 780 are as listed in the following table.  
Table 1. Capacities for Redundancy CPU, IC697CPU780  
Speed  
(MHz)  
Input  
Points  
Output  
Points  
On-Board  
UserMemory  
FloatingPoint  
Math  
Expansion Memory  
(KBytes)  
Processor  
16  
80386DX  
12288  
12288  
notavailable  
128/ 256/ 512  
Ye s  
The total number of Input points and Output points on the model 780 CPU cannot exceed 12288.  
CPU Architecture  
The CPU 780 has an 80386DX microprocessor as the main processing element, on-board  
memory, a dedicated VLSI processor for performing boolean operations and interfaces  
to a serial port and the system bus. The microprocessor provides all fundamental sweep  
and operation control, plus execution of non-boolean functions. Boolean functions are  
handled by a dedicated, VLSI, Boolean Coprocessor (BCP) designed by GE Fanuc.  
Program and data memory on the CPU 780 is available by the attachment of an  
expansion memory board with either 128 Kbytes, 256 Kbytes or 512 Kbytes of  
battery-backed CMOS RAM, or 256 Kbytes with 256 Kbytes of non-volatile flash  
memory.  
When the CPU board is in storage, disconnect the lithium battery if there is no  
application program stored in memory. If a program is stored in memory, do not  
disconnect the battery; otherwise the data will be lost.  
Caution  
If a Low Battery Warning occurs, replace the battery beforeremoving  
power from the rack. Otherwise there is the possibility that data will  
be corrupted or the program will be cleared from memory.  
Watchdog Timer  
The CPU provides a watchdog timer to catch certain failure conditions. The value of this  
timer is controlled by the user from the programmer. The valid range of the watchdog  
GFK-0827  
14  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2
timer is 10 milliseconds to 1000 milliseconds. The default value for the watchdog timer is  
200 milliseconds. The watchdog timer resets at the beginning of each sweep. The fail  
wait time is included in the watchdog check. The watchdog timer should be set to allow  
for the expected scan plus two fail wait times.  
CPU Features  
The CPU must reside in Slot 1 in rack 0, the main (CPU) rack. An illustration of the CPU  
780 is shown in the following figure, followed by a description of the CPU features.  
a47003  
MEMORY  
PROTECT  
KEY  
SWITCH  
OK  
RUN  
CPU  
STATUS  
ENABLED  
LEDS  
B
A
T
T
E
R
CPU MODE  
SWITCH  
MEM PROTECT  
CPU 780  
OPEN  
TOP  
CENTRAL  
PROCESSOR  
UNIT  
REPLACEMENT  
BATTERY  
CONNECTOR  
Y
OFF  
ON  
REMOTE PROGRAMMER  
MEMORY PROTECT  
KEY POSITION  
CURRENTLY  
INSTALLED  
BATTERY  
FRONT  
MODULE OK  
RUN  
CONNECTOR  
OUTPUTS  
ENABLED  
MEMORY PROTECT  
REMOTE  
PROGRAMMER  
ONLY  
ON = OK, ENABLED  
PROTECTED  
RUN WITH  
OUTPUTS  
ENABLED  
RUN WITH  
OUTPUTS  
DISABLED  
STOP  
EXPANSION  
MEMORY  
BATTERY  
CONNECTORS  
BOARD  
INSTALL NEW  
IC697MEM731  
IC697MEM732  
IC697MEM733  
IC697MEM735  
BATTERY BEFORE  
UNPLUGGING OLD  
BATTERY. USE  
IC697ACC701  
MODULE FUNCTION  
16MHz 32 BIT CENTRAL  
PROCESSING UNIT  
WITH FLOATING POINT  
MATH COPROCESSOR  
FOR HOT STANDBY  
CPU APPLICATIONS  
RS-485  
COMPATIBLE  
SERIAL PORT  
SERIAL PORT  
RS-485  
COMPATIBLE  
USE THIS MODULE  
IN SLOT 1 ONLY  
MODULE  
IC697CPU 780  
LABEL  
44A726758-130R03  
Figure 4. Redundancy CPU - IC697CPU 780  
GFK-0827  
Chapter 2 System Components  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2
CPU Mode Switch  
A three-position toggle switch is mounted near the top of the CPU board. This switch  
selects one of three operating modes for the CPU: RUN/ENABLED,RUN/DISABLED, or  
STOP. Although the mode of operation for the CPU can be controlled from both the  
switch and the programmer, the switch position restricts the ability of the programmer  
to put the CPU into certain modes.  
The following table shows the modes that can be selected by the programmer based  
upon the position of the CPU mode switch.  
Table 2. Valid Operating Mode Selection  
CPU Mode Switch  
Position  
Allowable Programmer  
Mode Command  
STOP  
RUN/ OUTPUTSENABLED  
RUN/ DISABLED  
RUN/ ENABLED  
STOP  
RUN/ OUTPUTSDISABLED  
STOP  
RUN/ DISABLED  
STOP  
Run/Outputs Enabled  
The top position of the switch is Run with Outputs Enabled. With the switch in this  
position, the CPU executes all portions of the sweep normally.  
Run/Outputs Disabled  
The middle position of the switch is Run with Outputs Disabled. When the switch is in  
this position, the CPU executes all portions of the sweep normally, but physical outputs  
are held in their default state, and therefore remain unchanged. Refer to Chapter 4,  
page 65 for important information on the Run/ Disabled mode in a Hot Standby CPU  
Redundancy system.  
STOP  
NOTE  
TheSTOP/ IOSCAN mode is not a valid mode in a redundancy system.  
Refer to Chapter 4 for detailed information.  
The bottom position of the switch is labeled STOP. With the switch in this position, the  
CPU communicates only with the programmer and devices connected to the serial port,  
and recovers faulted modules. Any of the values in the I/ O tables can be changed using  
the programming computer.  
GFK-0827  
16  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2
Memor y Protect Keyswitch  
The Memory Protect keyswitch is located at the top of the module and has two  
positions: ON and OFF. This keyswitch is used to manually lock program and  
configuration data. When the key is in the ”protected” (ON) position, program and  
configuration data can only be changed by a programmer connected for parallel  
communications with the CPU 780 (that is, to the Bus Transmitter Module).  
CPU Status LEDs  
There are four LEDs mounted at the top of the CPU board which indicate the current  
state of the CPU. The normal state of these LEDs when the CPU is running is ON. They  
are OFF or flashing to indicate special or failure conditions.  
OK  
The top LED, labeled OK is an indicator of the health of the CPU. It is ON when the CPU  
is functioning properly. The LED blinks when the CPU executes the power-up  
diagnostics, when the system has failed, and when the remote unit is powered-up.  
However, when in this state, the CPU can still communicate with the programmer (the  
CPU cannot communicate with the programmer during power-up diagnostics) . The  
LED is OFF when the system has failed and the CPU cannot communicate with the  
programmer.  
RUN  
The middle LED, labeled RUN is an indicator of the RUN/ STOP status of the CPU. It is  
ON when the CPU is in the RUN/ ENABLE or RUN/ DISABLE mode. When the CPU is in  
the STOP mode, the LED is OFF.  
ENABLED  
The bottom LED, labeled ENABLED indicates the state of the outputs. This LED is ON  
when the outputs are enabled, and OFF when the outputs are disabled.  
MEM PROTECT  
This LED indicates the status of the memory protect keyswitch. When the keyswitch is  
in the OFF position the LED is OFF, and the CPU can be programmed (if connected for  
parallel communications, the CPU can be programmed regardless of the keyswitch  
position). After the program has been verified, the toggle switch for mode selection can  
be moved to the appropriate mode position. When the memory protect keyswitch is in  
the ON position, the LED will be ON.  
Battery Connectors  
Directly below the mode switch are two identical battery connectors. The connector  
wired to the lithium backup battery cable plugs into one of these connectors to connect  
the battery to the CMOS memory devices. Two connectors are provided for use when  
the battery requires replacement. The battery currently installed can remain connected  
until the new battery is connected, thus minimizing the possibility of losing data.  
GFK-0827  
Chapter 2 System Components  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2
Serial Port Connector  
The 15-pin D-connector at the bottom of the module provides the connection to an  
RS-422/ RS-485 serial port. Its port provides a serial connection to the Work Station  
Interface (WSI) board installed in the programming computer. For applications  
requiring RS-232 communications, an RS-232 to RS-422 converter (IC690ACC900) or  
RS-232 to RS422 miniconverter (IC690ACC901) is available.  
Note  
An RS-422 Isolated Repeater/ RS-232 Converter (IC655CCM590) is  
available for applications requiring ground isolation where a common  
ground cannot be established between components.  
A standard serial COM port version of Logicmaster 90-70 programming software  
provides logic programming and configuration for the Series 90-70 PLC using the COM1  
or COM2 serial port of the programming device (a Work Station Interface board is not  
needed). Connections for this configuration are made from the programmer s COM1 or  
COM2 serial port to the converter to the serial port on the Series 90-70 CPU.  
Expansion Memory Board  
The CPU 780 requires an expansion memory board (see GFK-0837 and GFK-0531C, or  
later versions), for more information. The expansion memory board uses battery-backed  
CMOS RAM memory devices for program and data storage. These expansion memory  
boards are arranged in a 32-bit memory configuration and can only be used on the  
models 780, 781 and 782 CPUs. Error checking is provided by a CPU checksum routine.  
Logic program memory is continually error-checked by the CPU as a background task.  
Memory parity errors are reported to the CPU when they occur.  
These expansion memory boards are not compatible with the expansion memory boards  
used with the models 771 and 772 CPUs or the Programmable Coprocessor Module.  
Four versions of the 32-bit memory expansion board are available as listed in the table  
below. These expansion memory boards are installed on the CPU 780 module by  
mounting them on a connector provided for that purpose. The CMOS RAM memory on  
the expansion memory boards is backed-up by the Lithium battery mounted on the CPU  
module on which the boards are installed.  
Table 3. Expansion Memory Boards for CPU 780  
Catalog Number  
Memory Size  
IC697MEM731  
IC697MEM732  
IC697MEM733  
IC697MEM735  
128KBytes  
256KBytesw/ 256KBytesNon-VolatileFlash Memory  
256KBytes  
512KBytes  
Note that the current version of the expansion memory boards must be used with the  
CPU 780. consult your local PLC Distributor or PLC sales office for more  
information.  
GFK-0827  
18  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2
Redundancy Communications Module  
The Redundancy Communications Module (RCM), catalog number IC697RCM711, provides  
a communications path for sharing data between the two CPUs in the redundant system.  
In a synchronized system, I/O data is controlled by one unit (the active unit) but is shared  
between both units (active and backup units). The RCM provides the communications path  
between the two units. An RCM must be configured in both the Primary PLC and the  
Secondary PLC. The RCM must reside in rack 0 and there can be no empty slot between  
the RCM and the CPU (there can be other modules).  
RCM Features  
The following figure shows the features of the RCM module.  
a47004  
OK  
LOCAL READY  
LOCAL ACTIVE  
REMOTE READY  
REMOTE ACTIVE  
RCM 711  
BOARD OK  
REDUNDANCY  
COMMUNICATIONS  
LOCAL SYSTEM  
READY  
LOCAL SYSTEM  
ACTIVE  
MODULE  
REMOTE SYSTEM  
READY  
REMOTE SYSTEM  
ACTIVE  
ON = TRUE  
DEPRESS 1 SEC.  
TO SWITCH ACTIVE  
CPU (MIN 10 SECS  
BETWEEN SWITCHES)  
MODULE FUNCTION  
REDUNDANCY  
COMMUNICATIONS  
MODULE.  
HIGH SPEED INTERFACE  
BETWEEN HOT.  
STANDBY REDUNDANCY  
SUPPORTED CPUs.  
CONNECT TO END  
OF EXPANSION BUS  
EXPANSION  
PORT IN  
(TOWARDS CPU)  
TO BEM711  
OR BEM713  
(USE TERMINATED  
CABLE CBL811  
OR CBL826)  
50 FT. MAXIMUM  
CABLE LENGTH FROM  
BEM 713 TO TO RCM711  
UNUSED PORT  
DO NOT INSTALL  
CABLE OR  
TERMINATOR  
MODULE  
IC697RCM711  
LABEL:  
44A726758–136R02  
Figure 5. Redundancy Communications Module - IC697RCM711  
Chapter 2 System Components  
GFK-0827  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2
a47005  
PRIMARY UNIT  
( RACK 0 )  
SECONDARY UNIT  
( RACK 0 )  
C
P
U
G
B
C
P
S
B
T
M
R
C
M
G
B
C
P
S
B
T
M
R
C
M
C
P
U
30  
31  
Redundancy Communications Link  
Redundancy Communications Link  
Figure 6. Example of RCM Location in a Hot Standby CPU Redundancy System  
RCM System Status LEDS  
A Hot Standby CPU Redundancy system has two RCM modules, each with five LEDs  
and a momentary pushbutton switch for manually switching between the active and the  
backup units. The LEDs will always be updated by the appropriate system. The RCM  
has two internal timers that will automatically turn off four of the LEDs (not the board  
OK LED) if the LEDs have not been updated within a specified time period. The two  
remote LEDs and the two local LEDs have separate timers since they are controlled from  
different systems.  
The RCM has five LEDS:  
BOARD OK  
LOCALSYSTEM READY  
LOCALSYSTEM ACTIVE  
REMOTE SYSTEM READY  
REMOTE SYSTEM ACTIVE.  
These LEDs report the status of the health of the RCM and the control status of the Hot  
Standby CPU Redundancy system. The status provided by these LEDs is also provided  
in an area of %S memory (%S33 - %S39) which is accessible from the user logic program  
but cannot be altered or overridden. The LEDs have the following meanings and uses.  
Note that the term Local Unit when associated with a particular RCM refers to that unit  
in which the RCM resides. Remote Unit refers to that unit in which the RCM is  
configured by the system for addressing as being in rack 7, slot 1. Each RCM will have  
an associated local and remote unit.  
BOARDOK  
This LED will come on when the diagnostics are complete and the RCM has been  
determined to be operating normally. It will remain on unless the RCM fails.  
LOCALSYSTEM READY  
Indicates whether the local unit is ready to become the active unit in a redundant PLC  
configuration. If the LED is on, the local unit has been configured for redundancy, is in  
RUN mode, and has performed sufficient initialization, diagnostics, and hand–shaking  
to take control of the redundant system if selected as the active unit. It is the  
responsibility of the local unit to set the state of this LED at least once during each  
sweep; if the local unit is unable to set (or fails to set) the state of the LED, the hardware  
will force the LED to off after the timer has timed out.  
GFK-0827  
20  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2
LOCALSYSTEM ACTIVE  
Indicates whether the local unit is the controlling (or active) unit in a redundancy  
system. It is the responsibility of the local unit to set the state of this LED at least once  
during each sweep; if the local unit is unable to set (or fails to set) the state of the LED,  
the hardware will force the LED to off after the timer has timed out.  
REMOTESYSTEM READY  
Indicates whether the remote unit is ready to become the active unit in a redundant PLC  
configuration. If the LED is on, the remote unit has been configured for redundancy, is  
in RUN mode, and has performed sufficient initialization, diagnostics, and  
hand–shaking to take control of the redundant system if selected as the active unit. It is  
the responsibility of the remote unit to set the state of this LED at least once during each  
sweep; if the remote unit is unable to set (or fails to set) the state of the LED, the  
hardware will force the LED to off after the timer has timed out.  
REMOTESYSTEM ACTIVE  
Indicates whether the remote unit is the controlling (or active) unit in a redundancy  
scheme. It is the responsibility of the remote unit to set the state of this LED at least once  
during each sweep; if the remote unit is unable to set (or fails to set) the state of the LED,  
the hardware will force the LED to off after the timer has timed out.  
Unit Selection Pushbutton  
The module has a momentary pushbutton switch which when depressed for 1 second  
and released allows you to manually switch control from the active unit to the backup unit  
if the backup unit is READY. The status of each pushbutton is checked by the PLC CPU  
software. The switch between units can also be controlled through user logic  
implementation of a SVC_REQ function that is activated by user logic. After a switch  
has been requested, you must wait 10 seconds before requesting another switch.  
RCM Connectors  
The RCM has two connectors mounted on the front of the board. The top connector is the  
only one used. It is connected via an I/ O cable with built-in termination to the last rack of  
the other PLC system. If no expansion rack is used, it is connected to the lower connector  
on the Bus Transmitter Module of the other system. The I/ O cable with built-in  
termination is available in two lengths:  
IC697CBL811, 10 feet (3 meters)  
IC697CBL826, 25 feet (7.5 meters)  
GFK-0827  
Chapter 2 System Components  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2
Bus Transmitter Module  
A Bus Transmitter Module (BTM), catalog number IC697BEM713, is required in both the  
Primary PLC CPU rack (rack 0) and the Secondary PLC CPU rack (rack 0) in a Hot  
Standby CPU Redundancy system. The BTM provides a path for Redundancy  
communications when connected to the Redundancy Communications Module (RCM).  
Each PLC system (Primary and Secondary) has a BTM and an RCM in rack 0. The BTM  
in one unit connects to the RCM in the other unit (or through a series or BRMs if  
expansion racks are in a system).  
PRIMARY UNIT  
( RACK 0 )  
SECONDARY UNIT  
( RACK 0 )  
a47006  
P
S
B
T
M
R
C
M
G
B
C
C
P
U
P
S
B
T
M
R
C
M
G
B
C
C
P
U
30  
31  
Redundancy Communications Link  
Redundancy Communications Link  
When included as a bus communications module in an I/ O  
a42986  
expansion system, the BTM is a high speed parallel interface which  
propagates the I/ O bus signals through a cable to a Bus Receiver  
Module located in the first I/ O expansion rack. The BTM also  
provides a high speed parallel connection to the programmer  
through the Work Station Interface board installed in the  
programmer.  
MODEL 70  
BEM 713  
MODULE OK  
PROGRAMMER  
PORT ENABLED  
LED Status Indicators  
EXPANSION  
PORT ENABLED  
ON = OK, ENABLED  
There are three LEDs located at the top of the BTM. The LEDs are  
labeled: OK, PGMR ACTIVE and BUS ACTIVE. As with all other  
Series 90-70 PLC LEDs, they are visible through the clear plastic lens  
at the top of the modules cover. The function of each LED is  
described below.  
MODULE FUNCTION  
SERIES 90–70  
BUS TRANSMITTER  
HIGH SPEED  
PARALLEL  
INTERFACE TO  
PROGRAMMER AND  
90–70 EXPANSION  
RACKS.  
PARALLEL  
PORT  
Module OK  
PROGRAMMER  
ONLY  
The top LED is the MODULE OK LED and is ON when the CPU  
software completes its power-up configuration of the BTM, and has  
polled (or attempted to poll) each expansion rack in the system. It is  
OFF when any of these conditions are not met.  
50 FT. MAXIMUM  
CABLE LENGTH  
EXPANSION  
PORT  
TO BEM 711  
(7 DROPS  
MAXIMUM)  
Programmer Port Enabled  
The middle LED is the Programming Port Active LED. This LED is  
either blinking or ON when the programmer and the PLC are  
communicating. It is OFF when they are not communicating.  
50 FT. MAXIMUM TOTAL  
CABLE LENGTH TO  
LAST BEM 711  
MODULE  
IC697BEM713  
LABEL  
Expansion Port Enabled  
44A726758–103  
The bottom LED provides the status of the expansion bus.  
This LED is either blinking or ON when the BTM is communicating  
with the Bus Receiver Modules connected to it through the parallel  
I/ O bus link. It is OFF when they are not communicating.  
BUS TRANSMITTERMODULE  
GFK-0827  
22  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2
BTM Connectors  
There are two connectors on the front of the BTM board. The top one provides a parallel  
connection to a Work Station Interface (WSI) board installed in the programmer for the  
Series 90-70 PLC. Serial connection to Workmaster II is through a programmer cable  
(IC647CBL703) 10 feet (3 meters) in length (parallel connection to Workmaster is through a  
parallel I/O cable, IC600WD005A). Standard parallel I/O cables are used to connect the  
BTM’s lower connector to a Redundancy Communications Module in the other  
Redundancy unit, or to a Bus Receiver Module in the first expansion rack. These connectors  
are 37-pin connectors. The top one is a male connector, while the lower one is female.  
Note  
The programmer running Logicmaster 90 Software must be connected to the  
same power ground as the PLC, unless special isolated drivers are used. The  
parallel programmer cable should only be connected/ disconnected when the  
programmer is powered-up and offline. Do not power the parallel programmer  
up or down while connected to a PLC that is running.  
a42987  
Bus Receiver Module  
The Bus Receiver Module is required if expansion racks are used in  
the overall redundancy system.  
MODEL 70  
BEM 711  
RACK  
The Bus Receiver Module (BRM), catalog number IC697BEM711,  
which must be installed in slot 1 of each expansion rack in a system,  
is the expansion rack interface to the I/ O bus. It provides the link to  
the I/ O bus for I/ O modules installed in its rack. The BRM in the first  
expansion rack connects to the BTM in the CPU rack through a  
parallelI/ O bus cable.  
CONFIGURED  
TERMINATION  
INSTALLED  
EXPANSION  
PORT ENABLED  
ON = OK, ENABLED  
MODULE FUNCTION  
SERIES 90–70  
BUS RECEIVER  
HIGH SPEED  
INTERFACE FROM  
90–70 EXPANSION  
RACKS TO 90–70  
MAIN RACK  
This cable is connected to the bottom connector on the BTM, and to  
the top connector on the BRM. The next rack to be included in the  
I/ O bus is connected to the lower connector on the BRM in the first  
expansion rack and the top connector of the BRM in the next rack.  
EXPANSION  
PORT IN  
(TOWARDS CPU)  
TO BEM 711  
OR BEM 713  
Connection of expansion racks on the I/ O bus is continued in this  
manner until the maximum of 6 expansion racks is connected. The  
bottom connector in the last expansion rack is connected to the top  
connector of the RCM in the remote unit. Note that the last bus  
connection is to an RCM module (instead of a BRM).  
50 FT. MAX.TOTAL  
CABLE LENGTH  
FROM BEM 713 TO  
LAST BEM 711  
EXPANSION  
PORT OUT  
(AWAY FROM CPU)  
TO BEM 711  
INSTALL  
Note  
TERMINATOR  
PLUG IN LAST  
RACK IN CHAIN  
USE IC697ACC702  
The total cable length of all connecting cables between racks  
on the I/ O bus cannot exceed 50 feet (15 meters).  
USE THIS MODULE  
IN FIRST SLOT ONLY  
MODULE  
IC697BEM711  
LABEL  
44A726758–201  
BUS RECEIVER MODULE  
GFK-0827  
Chapter 2 System Components  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2
I/O Bus Signal Termination  
The I/ O bus signals must be terminated at the end of the bus. In a standard PLC system  
this is done by installing a resistor pack, located inside of a terminator plug (catalog  
number IC697ACC702) on the bottom connector of the BRM module that is installed in  
the last I/ O expansion rack in the system. In a Hot Standby CPU Redundancy system a  
special I/ O cable with built-in termination is used. Do not use the resistor plug with the  
terminated cable.  
LED Status Indicators  
There are three LEDs located at the top of the BRM. The LEDs are labeled: OK, LAST  
RACK, and BUS ACTIVE. The LEDs are visible through the clear plastic lens at the top  
of the modules cover. The function of each LED is described below.  
Board OK  
The top LED, the Board OK LED, is ON when the CPU software completes its power-up  
configuration of the expansion rack and at least one module in that rack responds to the  
CPU requests for information. It is OFF when any of these conditions are not met.  
Last Rack  
The middle LED is the Last Rack LED. This LED is ON when the I/ O bus terminator  
plug is installed in the bottom connector of this BRM, and is Off when it is not installed.  
The terminator plug is to be installed only on the BRM that is at the end of the expansion  
rack I/ O bus. All BRMs are shipped from the factory with a terminator plug installed.  
These terminator plugs must be removed from any expansion rack located between the  
CPU rack and the last expansion rack.  
Expansion Bus Active  
The bottom LED provides the status of the expansion bus. This LED is ON when the  
BRM has detected that there has been activity on the expansion bus in the last 500 ms,  
otherwise it is off. When this LED is OFF, the BRM is holding the Series 90-70 I/ O  
modules in its rack in their default state.  
BRM Connectors  
The BRM has two connectors mounted on the front of the board. The top connector is  
for the I/ O cable connection to either the lower connector on a BTM in the CPU rack, or  
to the lower connector on another BRM. The lower connector is for an I/ O cable  
connection to the upper connector of a BRM in the next expansion rack on the I/ O bus or  
to the top connector on an RCM. The I/ O cable is an 18 twisted-pair cable with a ground  
shield. The total maximum cable length from the CPU rack to the most distant  
expansion rack (at the same ground potential) is 50 feet. Standard parallel I/ O bus cables  
that meet this specification are available in lengths of 5, 10, 25, and 50 feet.  
Genius Bus Controller  
The Genius Bus Controller (GBC), catalog number IC697BEM731, for the Series 90-70  
PLC is the interface for the Series 90-70 PLC to a Genius I/ O communications system.  
Configuration of the GBC is simple through use of Logicmaster 90 Configurator  
software. Genius I/ O blocks are scanned asynchronously by the GBC and I/ O data is  
transferred to the CPU once per scan over the backplane of the Series 90-70 PLC rack.  
GFK-0827  
24  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2
The Hot Standby CPU Redundancy system uses a single Genius bus and requires one GBC  
module in the Primary PLC and one in the Secondary PLC; however there can be multiple  
Genius busses configured in this manner in a system. The GBCs in the Primary PLC are  
assigned SBA 31, and the GBCs in the Secondary PLC are assigned SBA 30. Data from SBA  
31 in the Primary PLC is the ”preferred” data. The Primary PLC is normally the active unit  
in the redundancy system.  
In a redundancy system the GBCs must be configured for ”RED CTRLredundancy. All of  
the Genius devices on the Genius bus must also be configured for ”Redundancy”  
The bus can have up to 30 Genius devices connected to it, with one of the SBAs reserved for  
the Hand-Held Monitor. Any type of Genius I/O block may be connected to this bus. A  
Genius I/O device will use the output data received from SBA 31 in preference to data from  
SBA 30. If the active and backup units switch roles, the GBC will then use the output data  
from SBA 30.  
As a safety feature, a watchdog timer protects each Genius I/ O link. This timer is  
periodically reset by the GBC software, Should it ever expire, the microcontroller on the  
board ceases functioning and the Channel OK LED turns off. If this happens in a CPU  
Redundancy system, the other GBC will then drive the Genius I/ O blocks The cause of  
the link failure must be determined to re-establish communications.  
a42985  
Genius Bus Controller User Features  
A Genius Bus Controller can be installed in any slot in rack 0, except  
for slot 1 which is reserved for the CPU module. It can be installed  
MODEL 70  
BEM 731  
in any slot in an expansion rack, except slot 1 which must contain a  
Bus Receiver Module.  
MODULE OK  
CHANNEL 1 OK  
NOT USED  
ON = OK  
HAND HELD  
MONITOR  
CHANNEL  
1
LED Status Indicators  
MODULE FUNCTION  
SERIES 90–70  
GENIUS BUS  
CONTROLLER  
( 1 CHANNEL )  
The GBC has three LEDs located at the top of the board: one as an  
indicator of the state of the board, and one to indicate the state of  
the Genius I/ O link. When the board is functionally properly, the  
top two LEDs are ON (third LED currently not used). They are  
either blinking or OFF to indicate special or failure conditions. If,  
after the power-up diagnostics routine has been completed, all LEDs  
are OFF, this is an indication that a board failure has been detected  
and the board must be replaced.  
Removal of terminal  
block breaks bus if  
external jumpers are  
not applied as shown  
CHANNEL  
1
SER 1  
SER 1  
SER 2  
SER 2  
SHIELD  
OUT  
SHIELD  
IN  
N
C
N
C
Module OK  
N
C
N
C
N
C
N
C
The top LED, labeled OK, indicates the health of the GBC. It is ON  
when the board has successfully completed the power-up  
diagnostics. If the power-up diagnostics detects a failure or if the  
board fails during operation, the LED will be OFF. The LED blinks  
during the power-up diagnostics and when the GBC is installed in  
a slot different from the slot specified by the configuration  
information downloaded from the programmer.  
MODULE  
IC697BEM731C  
LABEL  
44A726758–11  
GENIUS BUS CONTROLLER  
GFK-0827  
Chapter 2 System Components  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2
CH 1 OK  
The CH 1 OK LED is the middle LED. It operates identical to the Module OK LED in that it  
is ON after the board has successfully completed the power-up diagnostics and OFF if a  
failure has been detected during the power-up diagnostics, or if its bus or bus controller fails  
while the CPU is running (even in the STOP mode). If the failure is a bus controller failure,  
the LED will remain permanently off. If it is a bus failure, such as a broken wire or excessive  
bus errors, the LED remains off until the failure condition is corrected.  
GBCConnectors  
A GBC has two connectors. Directly below the LED is a dedicated nine-pin connector for  
connection to the Hand-Held Monitor. The actual bus connections are made through a 12  
point removable terminal board. Six of these terminals are used for connection to the  
Genius I/O channel. The GBC may be located on either end or in the middle of the bus.  
a47007  
PRIMARY UNIT  
SECONDARY UNIT  
P
S
C
P
U
P
S
C B R G  
P T C B  
U M M C  
G
B
C
B
T
R
C
G
B
G
B
C
G
B
C
G
B
C
M M C  
30  
30  
30  
31  
31  
31  
Genius Bus  
Genius Bus  
Genius Devices  
Genius Devices  
Genius Devices  
Genius Bus  
Figure 7. Example of Multiple Genius Busses in a Hot Standby CPU Redundancy System  
Racks  
The standard series 90-70 I/ O racks may be used to contain the modules in a Hot  
Standby CPU Redundancy System.. These racks include the following:  
IC697CHS750, 5-slot rear mount;  
IC697CHS790, 9-slot rear mount;  
IC697CHS791, 9-slot front mount.  
Note  
Please note that he Series 90-70 VME Integrator racks (IC697CHS782  
and IC697CHS783) are not supported by this release of the Hot Standby  
CPU Redundancy product.  
For detailed information on the Series 90-70 I/ O racks, refer to GFK–0262, the Series  
90-70 Programmable Controller Installation Manual.  
GFK-0827  
26  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 3 Configuration  
section level 1 1  
figure bi level 1  
table_big level 1  
3
This chapter describes how to configure a Series 90-70 PLC system for Hot Standby CPU  
Redundancy. Several parameters in addition to the normally configured CPU  
parameters must be configured for the Redundancy CPU 780. A description of all of the  
parameters for a redundancy system is provided first, followed by an example of a  
Primary system configuration and a Secondary system configuration.  
Configuringa Hot Standby CPU Redundancy System  
Asdiscussed previously, when configuring a system for Hot Standby CPU Redundancy,  
the following parameters require configuration in addition to the CPU configuration  
parameters that are done for any other CPU78X CPU.  
Configuration  
Parameter  
Description  
Fail-wait  
The time one PLC will wait on one RCM link for the other  
PLC to respond before faulting that link. The CPU will try  
both links before continuing its scan. Once the RCM links are  
marked as failed, one unit or the other must be power cycled  
to recover them. Range is 60 ms to 400 ms, with the default  
value being 60 ms.  
Control Strategy  
Shared I/O References  
Redund Type  
The control strategy for the current configuration. Config-  
ured as a three-character identifier (GHS for Hot Standby  
CPU Redundancy). The default value is GHS (currently the  
only value that is valid).  
The references within the control of the Redundancy system;  
limited to total of 20 KBytes for Inputs and 28 Kbytes for Out-  
puts. The references which may be used as shared I/ O are  
%I, %Q, %AI, %AQ, %R, and %M. .  
Whether the CPU being configured is the Primary or Second-  
ary CPU in the Redundancy system. Redund Type has three  
possible values: PRIMARY, SECONDARY, or SIMPLEX. SIM-  
PLEX indicates a non-redundant system. The default value is  
PRIMARY. SIMPLEX is not a currently supported Redund Type  
for the CPU 780.  
27  
GFK-0827  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
Redundancy System Requirements  
For a redundant CPU configuration using the Hot-Standby Redundancy scheme to be  
valid, the following requirements must be true in both the Primary Unit and the  
Secondary Unit in the redundancy system.  
One configuration must be set to Primary; the other to Secondary.  
The control strategy configurable parameter must be set to ”GHS”.  
An RCM must be configured in rack 0 of each system. There can be no empty slots  
between the RCM and the CPU. For a given unit, the Local RCM is the one  
configured in that unit; the Remote RCM is not configured by the user, but is  
automatically configured by the system to be in slot 1 of rack 7.  
All Genius Bus Controllers in the system must be configured for RED CTRL  
Redundancy with the redundant pair set for EXTERNAL, or they must be  
configured for no redundancy.  
If a Genius Bus Controller is set to redundant in a redundant CPU configuration, all of  
its bus blocks must also be set redundant; if a Genius Bus Controller is set  
non-redundant in a redundant CPU configuration, all of its bus blocks must also be set  
non-redundant.  
If the primary/ secondary configurable item is set to PRIMARY, all Genius Bus  
Controllers configured for RED CTRL redundancy must have Serial Bus Address 31.  
If the primary/ secondary configurable item is set to SECONDARY, all Genius Bus  
Controllers configured for RED CTRL redundancy must have Serial Bus Address 30.  
The Shared I/O selections must match exactly between Primary and Secondary PLCs.  
Basic Redundancy System Setup  
Assemble each PLC system and cable the last rack of each system to the RCM of the  
other PLC using the terminated I/ O cable. If there are no expansion racks in the  
system, cable each BTM to the RCM in the other PLC.  
Logicmaster 90 Configuration  
Set the primary CPU to PRIMARY.  
Set the secondary CPU to SECNDARY.  
Forboth Primary and Secondary CPUs, do the Following:  
Select Data Transfer (SHARED I/ O) parameters (up to 20 Kbytes Input data, up to 28  
Kbytes Output data).  
Configure the SBA for all Redundancy Genius Bus Controllers (SBA 31 for the  
Primary; SBA 30 for the Secondary), and Redund Mode to ”RED CTRL.  
Select fail-wait time. The default value of 60 ms should suffice for most applications.  
Select watchdog timer. Allow for worst case scan time plus data transfer time plus  
two fail-wait times (plus a generous margin). Setting this value too small could  
cause the standby unit to time out during a failure of the active unit.  
Select the programmer window. Set to about 10% of the normal scan time (if scan  
time is unknown, use default time (do not exceed the fail wait time).  
Select Fault Actions.  
I/O System Configuration  
Configure your I/ O system as required for your application.  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GFK-0827  
28  
 
3
Screens for Fault CategoryConfiguration  
A new Fault Category Configuration screen is displayed for the CPU 780. This new  
screen has two columns of fault actions for the configurable fault groups/ categories. The  
following sample screens show the Fault Category Configuration screens as they appear  
in Logicmaster 90-70. To access this screen, select the F2 softkey (CPU Configuration)  
from the Configuration Software main menu. The CPU Configuration menu will be  
displayed. From this menu select the F5 softkey (Fault Category).  
The screen shown below is the Fault Category screen for a redundant system when in  
the OFFLINE mode  
The screen shown below is the Fault Category screen for a redundant system when in  
MONITOR or ONLINE mode  
GFK-0827  
Chapter 3 Configuration  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
The Fault Type is shown at the left. The first column under Fault Category (CFG) shows  
which faults are FATAL and which faults are DIAGNOSTIC for this CPU, when it is the  
only running CPU (i.e., stand-alone with no backup available). This column can be  
edited for each fault group/ category to select FATALor DIAGNOSTIC so that a safe  
shutdown or fault tolerant operation can be selected for when a failure occurs with no  
backup ready. The column next to it (PLC) shows the value (F or D) currently stored to  
the PLC or the defaults if it is not stored.  
The next column shows the Synchronized PLC values. These values are either F (FATAL  
- which causes a transition to STOP mode), or D (DIAGNOSTIC - which maintains the  
current state of the PLC) for this CPU, when it is synchronized. This column cannot be  
edited.  
Handling Folders  
It is very desirable from a maintenance standpoint to keep the applications programs  
identical between PLCs. The best way to handle this is to maintain different folders for  
each configuration and use the same logic folder for both PLCs. By using this scheme,  
you would have three folders for the redundant system.  
1. Folder”A - configuration for the Primary unit.  
2. Folder B” - configuration for the Secondary unit.  
3. Folder ”C” - logic and reference tables for both systems.  
It is recommended that for a new system, you should STORE the configuration first,  
then the logic.  
Functionally, it is not necessary to keep the same ladder in both PLCs but it is difficult to  
maintain such a system. Any ladder changes made in one system would have to be  
evaluated and hand-keyed in to the other folder. Other than visual inspection, there would  
be no way to tell if changes made in one system were appropriately made in the other.  
Note  
When entering either the Programmer Package or the Configuration  
Package while ONLINE and EQUAL, the folder containing the logic  
program will be automatically selected.  
Configuration with Logicmaster 90-70  
To configure the Hot Standby CPU Redundancy system, connect the programmer to  
either the Bus Transmitter Module for parallel communications or to the RS-485 serial  
port on the CPU 780 module for serial communications. For detailed information on  
installation procedures refer to GFK-0262, the Series 90-70 Programmable Controller  
Installation Manual. For detailed information on running Logicmaster 90-70  
Programming Software, refer to GFK-0263, the Logicmaster 90-70 Programming Software  
User’s Manual.  
Any computer running Logicmaster 90 interfacing with the PLC must be connected to  
the same power ground as the PLC unless special isolated drivers are used. The parallel  
GFK-0827  
30  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
cable connecting the PLC to the programmer should only be plugged and unplugged  
when the programmer is powered up and offline. Avoid powering the parallel programmer  
up or down while connected to a running PLC.  
Configuration of a Redundancy CPU Module  
The redundancy CPU module, IC697CPU 780 must be configured as a rack module in  
rack 0, slot 1. The procedure for configuring a CPU 780 in a rack is described below.  
While in the Logicmaster 90 main menu, select the Logicmaster 90 Configuration  
Package by pressing the F2 softkey. You will then be prompted to enter a folder name or  
select an existing folder. When you have done this, press the Enter key and the Series  
90-70 Configuration software main menu will appear.  
While in the Configuration Software main menu, select the I/O softkey (F1) for I/ O  
Configuration. The default I/ O Configuration Rack screen is displayed.  
To configure the CPU 780 module position the cursor on rack 0, slot 1, then press the  
zoom softkey (F10).  
GFK-0827  
Chapter 3 Configuration  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
The detail screen of the currently configured CPU module is displayed. The following  
screen shows the CPU module detail screen for the currently displayed module.  
To select the CPU 780 Redundancy CPU module, press the cpu softkey (F1). A list of the  
available CPU modules is displayed with the currently selected CPU module highlighted  
in reverse video. Move the cursor to the line for the Redundant CPU (catalog number  
IC697CPU 780), as shown below, and press Enter.  
If the existing CPU configuration requires any modification for the redundant CPU  
configuration, an informative message will be displayed.  
Note  
The message area can show messages for all possible types of  
configuration modifications; any number of these messages could be  
displayed at any one time.  
GFK-0827  
32  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3
If the existing configuration does not require any modification to suit the redundant  
CPU configuration, the prompt ”REPLACE displayed module ? (Y/ N)will be displayed  
beneath the softkey strip instead of the message box.  
If you answer ”Y”, page 1 of the detail screen for the redundant CPU (IC697CPU 780) is  
displayed, If you were to answer ”N”, the previous CPU is displayed. For the  
redundant CPU configuration example, the answer is ”Y”.  
The differences between screen page 1 of the redundant CPU and non-redundant CPU  
are described below.  
Redundant CPU Requirements  
The I/ O configuration of a redundant CPU has the following restrictions, which are:  
1. In a redundant CPU system, rack I/ O module interrupts MUST be disabled.  
2. The SBAs of redundant GBCs in a Primary redundant CPU system must be 31; the  
SBAs of redundant GBCs in a Secondary redundant CPU system must be 30.  
GFK-0827  
Chapter 3 Configuration  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
3. In a redundant CPU system, RCMs cannot be configured in expansion racks.  
4. Rack 7 cannot be seen nor edited.  
Redund Type  
This parameter specifies whether the CPU is configured as the primary controller or the  
secondary controller. The Redund Type has three possible choices: PRIMARY,  
SECNDARY, or SIMPLEX. The default value is PRIMARY.  
When this configuration item is set PRIMARY, all configured redundant Genius Bus  
Controller(GBC) Serial Bus Addresses (SBA) must be 31. If any one of the SBAs is not 31,  
the message ”SBAs of all redundant GBCs in a primary system must be 31: modify (Y/N) ?.  
Answering ”Y” automatically changes all SBAs to 31. Answering ”N” leaves this field  
unchanged.  
When this configuration item is set to SECNDARY, all configured redundant Genius Bus  
Controller(GBC) Serial Bus Addresses (SBA) must be 30. If any one of the SBAs is not 30,  
the message ”SBAs of all redundant GBCs in a secondary system must be 30: modify  
(Y/ N)?.” Answering ”Y” automatically changes all SBAs to 30. Answering ”N” leaves  
this field unchanged.  
The third choice is SIMPLEX, which is currently not a valid mode for the CPU 780. You  
can configure the Redund Type for SIMPLEX, but the choice will be rejected when you  
attempt to STORE the configuration.  
BackgroundWindow  
The default for this parameter for CPU redundancy systems is 5 ms (limited Window  
mode). The background window runs several diagnostic tests which can be disabled by  
setting the the background window time to 0. These tests are run in Constant Window  
and Constant Sweep mode only if the window/ sweep time is large enough.  
Normal Sweep Mode  
The Sweep Mode for the redundant CPU has to be selected. Below is the detail screen  
(page 2) of a redundant CPU configured for NORMAL sweep mode.  
GFK-0827  
34  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
Constant Window Sweep Mode  
To change the Sweep Mode, move the cursor to the Sweep Mode field and press the Tab  
key until the desired mode is displayed. Below is the detail screen (page 2) of a  
redundant CPU configured for CNST WND (constant window) sweep mode.  
When a Series 90-70 redundant CPU is configured for CNST WND (constant window)  
mode, the window value will automatically be set to 10 msec.  
Constant Sweep Mode  
Below is the detail screen (page 2) of a redundant CPU configured for CNST SWP  
(constant sweep) mode.  
When a Series 90-70 redundant CPU is configured for CNST SWP (constant sweep)  
mode, its Sweep Timer value will automatically be set to 100 msec.  
The screen shown below is the detail screen (page 3) of a redundant CPU module. This  
screen will not appear for non-redundant CPU modules, or when the redundant CPU is  
GFK-0827  
Chapter 3 Configuration  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
set for SIMPLEX mode. The parameters on this screen are Ctrl Strgy (Control Strategy),  
Fail Wait and SHARED I/ O.  
Ctrl Strgy  
This parameter specifies which type of control strategy is selected for a redundancy  
system. The valid entry is three ASCII characters (A...Z). The only value that is  
supported at this time is Genius Hot Standby (GHS). If this parameter is set to any other  
value, the configuration will be considered valid, but any attempt to STORE the  
configuration will be rejected by the PLC. The default value is GHS.  
Fail Wait  
This parameter specifies the time one PLC will wait on one RCM link for the other PLC  
to respond before faulting that link. The Fail Wait range is 60 msec to 400 msec  
(measured in multiples of 10 msec) with the default value being 60 msec. The following  
table lists the two parameters described above.  
Parameter  
Description  
Valid Values  
Default Value  
Fail Wait  
Wait time  
60 to 400 milliseconds in  
10millisecond increments  
60  
ControlStrategy  
Three character control  
strategyidentifier  
A......Z  
GHS  
Shared I/O  
The Shared I/ O values are the reference addresses and ranges for the I/ O references  
included in the 20 KBytes of Input data (%I, %AI) and 28 KBytes of Output data (%Q,  
%AQ, %M, %R) which is shared between the Primary and the Secondary units in the  
Hot Standby CPU Redundancy control system. The Shared I/ O data is transferred from  
the active CPU to the backup CPU each sweep (refer to Chapter 4, ”Synchronous Scan”,  
for details). The valid entries for these parameters are described in the following tables.  
GFK-0827  
36  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
Table 4. Shared I/O Data Parameters  
I/O Parameter  
Description and Valid Entries  
%I Ref Adr  
Starting address for redundant %I data region. Range is %I00001...%I12288. The starting  
address is bit aligned. Default value is %I00001.  
%I LENGTH  
%Q Ref Adr  
The bit length of the redundant %I data region. Range is 0...12288. Default value is 0.  
Starting address for redundant %Q data region. Range is %Q00001...%Q12288. The  
starting address is byte aligned. Default value is %Q00001.  
%Q LENGTH  
%M Ref Adr  
The bit length of the redundant %Q data region. Range is 0...12288. Default value is 0.  
Starting address for redundant %M data region. Range is %M00001...%M12288. The  
starting address is byte aligned. Default value is %M00001.  
%M LENGTH  
%R Ref Adr  
The bit length of the redundant %M data region. Range is 0...12288. Default value is 0.  
Starting address for redundant %R data region. Range is %R00001...%R configured limit or  
8K, whichever is smaller (since only 28 Kbytes can be transferred). The %R memory limit  
for the CPU 780 is configurable in the PLC memory configuration screen. The maximum  
limit depends on the available CPU memory. See ”Memory Configuration” later in this  
chapter. The default value is %R00001.  
%R LENGTH  
%AI Ref Adr  
The word length of the redundant %R data region. Range is 0...%R configured limit. The  
default value is 0.  
Starting address for redundant %AI data region. Range is %AI00000...%AI configured  
limit. The %AI memory limit for the is configurable in the PLC memory configuration screen.  
The maximum limit depends on the available CPU memory. The default value is %AI00001.  
%AILENGTH  
%AQ Ref Adr  
The word length of the redundant %AI data region. Range is 0...%AI configured limit.  
The default value is 0.  
Starting address for redundant %AQ data region. Range is %AQ00000...%AQ configured limit.  
The %AQ memory limit for the is configurable in the PLC memory configuration screen. The  
maximum limit depends on the available CPU memory. The default value is %AQ00001.  
%AQ  
LENGTH  
The word length of the redundant %AQ data region. Range is 0...%AQ configured limit.  
Default value is 0.  
Table 5. Shared I/O Reference Values  
Parameter  
Valid Values  
DefaultValues  
%I Ref Adr  
%I Length  
%I00001...%I12288  
%I00001  
0...12288  
0
%Q Ref Adr  
%Q Length  
%M Ref Adr  
%M Length  
%R Ref Adr  
%Q00001...%Q12288  
0...12288  
%Q00001  
0
%M00001...%M12288  
0...12288  
%M00001  
0
%R0001..configuredlimits  
%R00001  
%R Length  
0...PLC memory limits  
%AI0001..configuredlimits  
0...configuredlimits  
0
%AI Ref Adr  
%AI Length  
%AQ Ref Adr  
%AQ Length  
%AI00001  
0
%AQ0001..configuredlimits  
0...configuredlimits  
%AQ00001  
0
Transfer Data Size  
The following table shows the amount of Shared I/ O data transferred for each reference  
type. No more than 20 Kbytes of Input data and 28 Kbytes of Output data can be  
transferred (an additional 8 Kbytes is reserved for resynchronization transfers).  
GFK-0827  
Chapter 3 Configuration  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
Note that the memory for the Shared I/ O data that is stored at configuration must be  
subtracted from the amount of memory on the configured expansion memory module.  
The calculation for the size of the memory for Shared I/ O data is (bytes of Input data  
transfer plus bytes of Output data transfer plus 8 Kbytes for synchronization  
information).  
For example if the selected expansion memory is 512 Kbytes, and the Shared I/ O data is  
10 Kbytes of Input data transfer and 20 Kbytes of Output data transfer, then 10K + 20K  
+ 8K Bytes = 38 KBytes is reserved for data transfers. This is subtracted from the 512  
KBytes of available user memory (512K – 38K = 474K Bytes, which means that 474  
KBytes is available for the user s control program.  
Table 6. Transfer Data Size  
Reference Type Reference Size  
Calculation for Number of Bytes  
If point faults are DISABLED usethefollowingcalculations.  
%I  
Bit  
(%Ireferences x 4bits/ reference)÷ 8bits/ byte  
(%AIreferencesx2bytes/ reference)  
%AI  
%Q  
%M  
%AQ  
%R  
Word  
Bit  
(%Q references x 4bits/ reference)÷ 8bits/ byte  
(%M references x 4bits/ reference)÷ 8bits/ byte  
(%AQ references x2bytes/ reference)  
Bit  
Word  
Word  
(%Rreferences x2bytes/ reference)  
If point faults areENABLED usethefollowingcalculations.  
%I  
Bit  
(%Ireferences x 5bits/ reference)÷ 8bits/ byte  
(%AIreferencesx3bytes/ reference)  
%AI  
%Q  
%M  
Word  
Bit  
(%Q references x 5bits/ reference)÷ 8bits/ byte  
(%M references x 4bits/ reference)÷ 8bits/ byte  
Bit  
%AQ  
%R  
Word  
Word  
(%AQ references x3bytes/ reference)  
(%Rreferences x2bytes/ reference)  
Interrupts  
Interrupts cannot be ENABLED for Input Modules or VME modules when the  
configured CPU is a CPU 780. The current configuration will be checked to ensure that  
there are no modules that have interrupts ENABLED. If modules do exist in the current  
configuration that have interrupts ENABLED and you configure a CPU 780, a prompt  
will appear asking whether or not all module interrupts should be DISABLED  
automatically. You cannot configure a Redundant CPU (CPU 780) until all module  
interrupts are DISABLED.  
GFK-0827  
38  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
Configuringa CPU Expansion Memory Board  
To configure a CPU expansion memory board for the CPU 780, press the expbd softkey  
(F9) and then the memory softkey (F1). Position the cursor on the desired expansion  
memory board and press Enter to select that board. The detail screen for the expansion  
memory board and the displayed catalog list for the available CPU expansion memory  
boards is shown below.  
Press the Esc key twice to return to the Rack level display. The selected memory size is  
shown below the CPU model (CPU 780).  
GFK-0827  
Chapter 3 Configuration  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
Configuration of a Redundancy Communications Module  
Asdescribed previously, one Redundancy Communications Module (the Local unit)  
must be configured in rack 0 (can be in slots 2 to 9). There must not be an empty slot  
between the CPU 780 module and the RCM module. If there is an empty slot, the  
configuration will be invalid. The following example screens show an RCM configured  
in slot 2 in rack 0. While in the I/ O Configuration rack screen, cursor to slot 2 (currently  
empty) as shown below.  
Select the bem softkey (f3) from the I/ O Configuration rack screen, the following screen  
will be displayed:  
GFK-0827  
40  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
To display the RCM catalog list, press the rcm softkey (F3). The RCM catalog list is then  
displayed as shown below.  
Next, press the Enter key, the following screen is displayed to confirm that you have  
selected the RCM catalog entry.  
You have just configured the Local RCM in rack 0. The system automatically configures  
the RCM in the Secondary unit as being in slot 1 of rack 7 (in relation to the RCM you  
have just configured in the Primary unit).  
GFK-0827  
Chapter 3 Configuration  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3
Configurationof a Genius Bus Controller  
For this example, assume that a Genius Bus Controller has been configured in slot 3 of  
rack 0. In a Hot Standby CPU Redundancy system, the Redundancy parameter  
(Redund Mode) of a Genius Bus Controller can only be NONE or RED CTRL; any other  
value is not valid. The following screen is the GBC screen when the Redund Mode  
parameter is set to NONE.  
To change the Redund Mode, move the cursor to the Redund Mode field and press the  
Tab key until the desired mode is selected. When the Redund Mode parameter for the  
GBC is set to RED CTRL, the following screen is displayed:  
Paired GBC Parameter  
When the GBC redundancy mode, Redund Mode is set to RED CTRL, the Paired GBC  
configuration parameter MUST be set to EXTERNAL. This is automatically done by the  
system.  
GFK-0827  
42  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
Serial Bus Address  
Allredundant GBCs in the Primary CPU redundant system MUST be configured at SBA  
31. In the sample screen on the previous page, the rack level GBC is configured at SBA  
31. The Bus level GBC is automatically configured at SBA 30.  
All redundant GBCs in the Secondary CPU redundant system MUST be configured at  
SBA 30. In our example, the rack level GBC is configured at SBA 30. The Bus level GBC  
is automatically configured at SBA 31  
All of the Genius I/ O blocks on the bus of a redundant GBC in a Hot Standby CPU  
Redundancy system MUST be set Redundant.  
Note  
For fastest switching, all Genius Bus Controllers in the Hot Standby CPU  
Redundancy system should be in the main rack, or in a rack driven by  
the main racks power supply. This will cause the Genius Bus Controller  
to lose power at the same time that the CPU loses power and allow the  
backup unit to gain full control of the I/ O as soon as possible.  
GFK-0827  
Chapter 3 Configuration  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
Configuring a Primary Redundant PLC  
The steps required for configuring a Primary Redundant PLC are described below. The  
Primary PLC and the Secondary PLC must be configured separately. An example of the  
configuration screens for each system is provided on the following pages. The  
programmer must be connected to the CPU in the Primary PLC to configure the Primary PLC and  
then moved to the CPU in the Secondary PLC to configure the Secondary PLC. First, the  
Primary PLC will be configured.  
While in the Configuration Software main menu, select I/ O (F1). The default  
configuration for the I/ O Configuration Rack screen is displayed.  
Position the cursor on rack 0, slot 1 and press the zoom softkey (F10) to zoom into the  
CPU module currently configured in slot 1. Press the cpu softkey (F1) to have a catalog  
list of the available CPU modules displayed. The currently selected CPU is highlighted  
in reverse video.  
GFK-0827  
44  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
Select the Redundancy CPU Module  
Move the cursor to the line for the Redundant CPU, IC697CPU 780, and press the Enter  
key. A message is displayed beneath the softkey selection strip: ”REPLACEdisplayed  
module ?(Y/ N)”. Press the Y key to replace the currently displayed CPU with the CPU  
780. The detail screen (page 1) for the redundancy CPU module is displayed.  
Press the PgDn (page down) key to go to the next page of the CPU module. The default  
screen for page 2 is as follows:  
GFK-0827  
Chapter 3 Configuration  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
Press the PgDn key again to go to the next page of the CPU module. The default screen  
for page 3 of the CPU detail screen appears as shown below:  
Select an Expansion Memory Board  
To configure a CPU expansion memory board for the CPU 780, press the expnd softkey  
(F9), then the memory softkey (f1). The detail screen for selection of the expansion  
memory board with the catalog list of the CPU expansion memory modules appears as  
follows: Position the cursor on the desired memory board and press Enter.  
GFK-0827  
46  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
Press the Esc key twice to return to the rack level display, which now appears as shown  
below.  
Configure the Redundant Communications Module  
To configure an RCM in rack 0, slot 2, move the cursor to slot 2 and press the bem  
softkey (F3). The configuration screen for bus communication modules will appear.  
From this screen press the rcm softkey (F3). The catalog list screen for the RCM module  
will be displayed. Press the Enter key to select the RCM module, IC697RCM711. The  
RCM module detail screen appears as follows:  
Press the Esc key to return to the rack level screen.  
GFK-0827  
Chapter 3 Configuration  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
Configure a Genius Bus Controller  
To configure a Genius Bus Controller module in rack 0, slot 3, position the cursor on slot  
3 and press the genius softkey (F2). To display the catalog list for the Genius Bus  
Controller, press the gbc softkey (F1). Press the Enter key to select the Genius Bus  
Controller module. The Genius Bus Controller detail screen will then be displayed as  
shown below.  
To change the Genius bus redundancy mode for redundancy, move the cursor to  
Redund Mode: Press the Tab key until the value for the field changes to RED CTRL.  
Note that in a Hot Standby CPU Redundancy system, the only values that are valid for  
this parameter are NONE or RED CTRL.  
GFK-0827  
48  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
Press the Esc key to return to the rack level screen. From the rack level screen press the  
zoom softkey (F10). The following bus level screen is displayed:  
To view the Genius Bus Controller (block level) at SBA 30, position the cursor on BUS  
ADR 30 and press the zoom softkey. The Genius Bus Controller s detail screen will  
appear as shown below.  
GFK-0827  
Chapter 3 Configuration  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3
At this point, Press the Esc key and the bus screen will appear as shown below.  
Configure Genius I/O Blocks  
We will now configure a block for Bus Address 29. Move the cursor to block 29 and  
configure a bus block (Discrete Input block IC660BBD110 for this example) by selecting  
the F1 function key (d in), then Enter. The bus blocks detail screen will appear as shown  
below.  
The Redundancy? parameter at the middle right of the screen is based on the Redund  
Mode that was selected for the Genius Bus Controller. At this point, you may configure  
the required type and number of blocks on the Genius bus.  
GFK-0827  
50  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
When you have completed configuring Genius blocks, press the Esc key to go from the  
block level display back to the bus level display. The bus display will now appear as  
shown below.  
Configure the Bus Transmitter Module  
Press the Esc key to return to the rack level display. A message will be displayed  
reminding you to configure a Bus Transmitter Module for this rack (since it had not been  
configured earlier). Press Esc again. Move the cursor to slot 4, press the bem softkey  
(F1), then press the btm softkey (F1) to select the Bus Transmitter Module, and press  
Enter. The detail screen for the Bus Transmitter Module will appear.  
Press the Esc key which will return you to the rack level display. At this point you have  
completed the necessary configuration steps for the Primary PLC and can proceed to  
configuring the Secondary PLC.  
GFK-0827  
Chapter 3 Configuration  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
Configuring a Secondary Redundant PLC  
This section describes the steps for configuration of a Secondary PLC. The programmer  
for Logicmaster 90-70 software must be connected to the Secondary PLC in order to  
configure the Secondary PLC. There are several ways to configure a Secondary PLC in a  
Hot Standby CPU Redundancy system. One method is shown here.  
Create a new folder for the Secondary PLC system. Copy the data from the Primary  
PLC system to the Secondary PLC system folder. This process will save time since you  
will not need to re-enter the configuration parameters that are common to the two  
redundancy systems.  
This example shows how to change the Primary PLC redundancy configuration  
described on the previous pages to a Secondary PLC redundancy.  
Enter the I/ O Configuration software by pressing the I/O softkey (F1). The configuration  
for rack 0 appears as shown below (note that this is the configuration that you had  
selected for the Primary PLC)  
GFK-0827  
52  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
Position the cursor on rack 0, slot 1. Press the zoom softkey (F10) to zoom into the CPU  
module configured in slot 1. The detail screen (page 1) for the CPU module appears as  
shown below:  
Change Redund Type  
Change the Redund Type: parameter value from PRIMARY to SECNDARY by pressing  
the Tab key then the Enter key. The message ”SBAs of all redundant GBCs in a secondary  
system must be 30: modify (Y/N) ? will be displayed Press ”Y” at the prompt. At this time,  
the SBAs of all redundant rack level GBCs will be changed to 30 and the SBAs of their  
corresponding bus level GBCs will be changed to 31. After the changes have been made,  
the screen will appear as follows:  
GFK-0827  
Chapter 3 Configuration  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3
Press the Esc key twice to save the changes you have just made. This completes the  
process of converting a Primary PLC redundancy system configuration to a Secondary  
PLC redundancy system configuration. The differences between the Primary system  
and the Secondary system are:  
1. The CPU module parameter Redund Type in a Primary system is PRIMARY and in a  
Secondary system is SECNDARY.  
2. The Serial Bus Address (SBA) of a redundant GBC in a Primary system MUST be 31  
and in a Secondary system MUST be 30.  
The Genius Bus Controller bus level display in a Secondary PLC redundancy system is as  
shown below.  
GFK-0827  
54  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4 Operation  
section level 1 1  
figure bi level 1  
table_big level 1  
4
This chapter discusses:  
the normal operation of a Hot Standby CPU Redundancy PLC system;  
what happens when a fault is detected and the system does not operate normally;  
how to restore the system to normal operation;  
on-line repair procedures.  
Section 1 describes normal system operation of a Series 90-70 Hot Standby CPU  
Redundancy system, Section 2 describes what happens when a system failure is  
detected, the actions taken by the system in response to detected faults and how to  
restore the system to normal operation.  
Section 5: System Operation  
Power-Up Sequence of a Redundant CPU  
When a CPU is powered up, it will perform a complete hardware diagnostic check and a  
complete check of the user program and configuration parameters. This will cause the  
power up time of a redundant CPU to be significantly longer than the normal power up  
time of a simplex (non-redundant) Series 90-70 CPU. If the Primary and Secondary  
systems are powering up together each CPU must recognize this fact so that the Primary  
system will become the active and the Secondary system the backup.  
The following sequence outlines each step in the power-up process. The only difference  
in this sequence as compared to the power-up sequence of existing CPUs is that full  
power-up tests are always performed instead of conditionally depending on whether STOP  
mode is selected, and the detection of the other CPU along with initialization of each  
RCM followed by synchronization.  
1. Power-up self-test is performed.  
2. CPU operating system is initialized and PLC memory is validated.  
3. Diagnostics called for ”Full” power-up tests performed.  
55  
GFK-0827  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
4. System Configuration verified.  
5. System interrogated and initialized.  
6. Presence of other CPU detected and RCMs initialized.  
7. Complete user program verification.  
8. Synchronize with the Redundant CPU.  
When powering up the unit configured as the Secondary Unit in a Redundant system  
and no remote unit (the Primary Unit) is detected, the Secondary Unit will wait up to 15  
seconds to see if the remote unit will also power up. If after 15 seconds, the remote unit  
has not completed its power up sequence, then the Secondary Unit will assume that no  
remote unit is present. If at this time, the Secondary Unit transitions to RUN mode, it  
will do so as a stand-alone unit.  
If the unit configured as the Primary Unit completes its power-up sequence before the  
remote unit (the Secondary Unit) the Primary Unit does not wait for the remote unit to  
complete its power-up sequence. If the Primary Unit is setup to transition to RUN on  
power-up (that is, was powered-down in RUN mode), it will transition to a stand-alone  
unit without waiting for the remote unit. When the remote unit completes its power-up  
sequence, it will attempt to establish communications with the Primary Unit and will  
synchronize if also transitioning to RUN mode.  
In either case, if one CPU fails to notify the other CPU that it is either present or  
powering up, this CPU will proceed to power-up as a stand-alone CPU and will become  
the active CPU. The other CPU will resynchronize once the power-up sequence is  
complete.  
Note  
In applications where it is desired to have a fully redundant system  
upon power-up, the Secondary Unit must complete power-up first but  
no more than 15 seconds before the Primary Unit. The way to be sure  
that this happens is to apply power to the Secondary Unit first.  
Incompatible Configurations  
When two units have incompatible configurations stored (for example, both units  
configured for PRIMARY or differing blocks for data transfer), then only one of the units  
can go to RUN mode. If the other unit attempts to go to RUN mode or both units  
attempt to go to RUN mode at the same time, a FATAL incompatible configuration fault  
will be logged.  
If one unit is configured for CPU Redundancy and the other has no configuration, then  
both units may go to RUN mode at the same time but they will not be synchronized and  
only the unit that has been configured will drive outputs.  
GFK-0827  
56  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
Resynchronization of the Redundant CPU  
Whenever a CPU is attempting to get back in synchronization with the currently active  
CPU, a resynchronization process will occur. This resynchronization process will occur  
any time a CPU performs a STOP to RUN mode transition. This process will start by  
determining which role each CPU is to play. The Primary Unit (with Serial Bus Address  
31) is always preferred and a switch will occur from the Secondary Unit anytime the  
primary CPU performs a resynchronization. However, until the resynchronization is  
complete, the primary CPU will play the role of the backup. The Primary unit will  
switch to active just prior to logic execution. Outputs will be driven that sweep by the  
primary unit.  
If both systems are transitioning at the same time, then the primary CPU will become  
the active CPU and the secondary will become the backup.  
During the resynchronization process, data is exchanged between the CPUs regarding  
roles and configuration. If the transitioning CPU detects that the role or configuration is  
not in agreement, then that CPU will not be permitted to go to RUN mode. If both  
CPUs are transitioning, then neither CPU will be permitted to go to RUN mode. The  
following items must be in agreement:  
1. One CPU must be configured as Primary, the other as Secondary.  
2. Both CPUs must be configured for the same redundancy scheme; but not necessarily  
the same release.  
3. Both CPUs must have the same Shared I/ O redundancy points configured.  
4. Point fault configuration must match. If point faults are configured on one CPU,  
they must also be configured on the other if %I, %Q, %AI, or %AQ data is  
transferred.  
At this point, the active unit is the one that has been in control and the backup unit is the  
one that is resynchronizing. The transfer of all configured control data from the active  
unit to the backup will occur provided both units are not transitioning at the same time  
(the transfer always goes from the running unit to the resynching unit. In addition to  
the configured control data, the FST_SCN and FST_EXE %S references as well as  
internal timer information for each common (that is, present in both CPUs) sub-block are  
transferred from active to backup. Only the internal timers and FST_EXE references for  
program blocks with the same name will be transferred from the active to the backup  
CPU. The result of this is that if one CPU is already on-line and the other is transitioning  
to RUN mode, its FST_SCN and matching FST_EXE bits will not be set on its first scan.  
These bits are considered system bits and will only be set if one unit comes up alone, or if  
both units come up together.  
No transfer of data occurs at this point if both units are transitioning. Instead, the  
normal clearing of non-retentive data will happen and the FST_SCN and FST_EXE  
references will be set as in the non-redundant simplex CPU models.  
The timer information and the FST_EXE %S reference bits will not be continuously  
transferred. The timer information and FST_EXE references will be transferred only at  
resynchronization time and the timer information will be calculated each sweep from  
the universal ”Start of Sweep Time” that is transferred every sweep.  
GFK-0827  
Chapter 4 Operation  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
Hot-Standby Redundancy Control Strategy  
In the Hot-Standby Redundancy Control Strategy, the primary CPU (designated by all  
GBCs addressed at bus address 31), is always the preferred CPU. The secondary CPU  
(designated by all GBCs addressed at bus address 30) will have the outputs enabled to its  
GBCs at all times whether it is in control or not. This is necessary to prevent glitching of  
the outputs when a switch is made. The primary CPU on the other hand must disable  
its outputs whenever control is manually switched to the backup CPU and then  
re-enable them if it is again selected as the active unit. Glitching of the outputs will not  
occur on a switch from the secondary to the primary CPU when it is done manually but  
may occur if the switch is made automatically due to a failure in the secondary CPU.  
For this reason, the primary CPU should normally be selected as the active unit. Anytime the  
primary CPU performs a STOP to RUN mode transition, the primary CPU will assume  
control from the secondary CPU after a resynchronization has occurred. This will be  
done automatically by the control strategy firmware in the PLC CPU.  
The primary unit in the hot-standby control strategy will become a functioning backup if  
control is manually switched to the secondary unit. The system will remain with the  
secondary unit as the active unit and the primary unit as the backup until either another  
manual switch is commanded or either unit performs a STOP to RUN mode transition.  
A STOP to RUN mode transition always occurs when the unit is power cycled and  
proceeds directly to RUN mode or when commanded to transition by either the  
programmer or the toggle switch. A failure of the secondary unit while it is active may  
result in a glitch in the outputs.  
To further clarify the above operation – when a resynchronization occurs for any  
reason, the primary unit will become active. However, in order for resynchronization to  
occur, one of the units must go to STOP mode and then back to RUN. If the secondary  
unit goes to STOP, the primary unit will then become the active unit.  
The control strategy is selected during configuration of the Redundant CPU. The  
Control Strategy parameter is indicated by a three ASCII character identifier. For Hot  
Standby CPU Redundancy this identifier is GHS. Although other values may be selected  
and considered valid, any attempts to STORE them to the PLC will be rejected since  
GHS is currently the only valid Control Strategy. GHS is the default value for the  
Control Strategy parameter. For more information on selecting Redundancy CPU  
parameters, refer to Chapter 3, Redundancy System Configuration.  
GFK-0827  
58  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
SynchronousScan  
The figure below shows the sweep components for the active and the backup CPUs. It  
shows the two communication points in the sweep. The first communication point is  
immediately after the inputs are scanned. At this point in the sweep the newly read  
inputs are sent from the active CPU to the backup CPU and synchronization information  
is passed. In the second communication point, the rest of the data (outputs, internal  
references, registers) is sent from the active PLC to the backup.  
a47008  
ACTIVE CPU  
BACKUP CPU  
Housekeeping  
Housekeeping  
Input Scan  
Input Scan  
1
2
Send Inputs  
and  
Synchronize  
Receive Inputs  
and  
Synchronize  
D
D
A
A
T
T
A
A
Logic Solution  
Logic Solution  
Send Outputs  
and  
Other Data  
Receive Outputs  
and  
Other Data  
Output Scan  
Output Scan  
Windows  
and  
Windows  
and  
Run-Time Diagnostics  
Run-Time Diagnostics  
1
First Data Transfer Occurs: %I, %AI and Synchronization  
Second Data Transfer Occurs: %Q, %AQ, %R, %M  
2
Figure 8. Active and Backup Sweeps  
First Data Transfer %I, %AI and Synchronization  
There are two points in the sweep where the active CPU will transfer data to the backup  
unit. The first data transfer will occur immediately after the Input Scan has occurred.  
The active unit will send all of the configured input data, both discrete (%I) and analog  
(%AI), to the backup unit. For discrete data, the status, override, and transition  
information is all transferred; if point faults are configured, point fault data is also sent.  
This data will overwrite the current input data in the backup unit.  
In addition to the input data transfer, a synchronizing message containing the ”Start of  
Sweep Time” will be sent from the active unit to the backup unit as soon as the input  
data has been transferred. The CPUs will stay in synchronization because the active  
unit will wait on the backup CPU to respond to the synchronizing message before  
starting its sweep.  
GFK-0827  
Chapter 4 Operation  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
The transfer of the redundancy data during each sweep will be in blocks with each block  
checked for data integrity. The transferred data will be held in a temporary area by the  
backup CPU until all data has been received and verified from the active unit. Then the  
backup CPU will copy that data from the temporary area to the actual PLC memories.  
The transfer is capable of being performed on either RCM link. If one RCM link fails  
then the transfer will switch to the other RCM without causing a loss of synchronization  
in the system. If at any time during a transfer the active unit fails or the full transfer fails  
to complete properly (both RCMs fail) then the backup unit will disregard the data that  
has been transferred to the temporary area and proceed with the values it already  
obtained during its input scan.  
The last part of the input data transfer is the synchronizing message containing the  
”Start of Sweep Time”. The ”Start of Sweep Time” is the universal start of sweep time  
for the redundancy system. Normally each PLC CPU operates its elapsed time clock on  
which timers are based independently and the clocks are always started over from zero  
on a power cycle. Two independent clocks would cause time discontinuity at switch  
over time. In addition the clocks will tend to drift from each other over time. The  
redundancy system corrects for this by keeping a single elapsed time value for the entire  
redundancy system. The time will be continuous as long as one of the two systems  
continue to run and the active unit will continuously pass the time to backup unit to  
correct for any natural drift in the clocks. When a switch over occurs, the same time will  
continue to be kept in the new active unit.  
Data Transfer from Backup Unit to Active Unit  
Eight bytes (4 registers) of data can be transferred from the backup unit to the active unit  
during the input data transfer before the logic solution. To initiate this transfer, the  
backup unit executes SVCREQ #27 (Write to Reverse Transfer Area) to copy eight bytes  
of data from the reference specified by PARM to a temporary buffer (SVCREQ #27 on  
the active unit will have no effect). This transferred data will be stored in a temporary  
buffer on the active unit.  
In the active unit, SVCREQ #28 (Read from Reverse Transfer Area) is then executed to  
copy the eight bytes of data from the temporary buffer to the reference specified by  
PARM (SVCREQ #28 will have no effect on the backup unit).  
Note  
There is always a one sweep delay between sending data to the active  
unit using SVCREQ #27 and reading the data using SVCREQ #28 on  
the active unit.  
This data copied from the buffer is not valid  
during the first scan after either unit has transitioned to RUN;  
while the backup unit is in STOP mode;  
if the remote unit does not issue a service request to the sending unit.  
An example of this data transfer is described below.  
This data should not be used if REM_RDY is off or if REM_RDY is transitioning to on.  
If the following two rungs are placed in the program logic of both units, the backup unit  
will send %P0001 through %P0004 to the active unit. The active unit will read the data  
into %P0005 through %P0008. %P0001 through %P0004 on the active unit and %P0005  
GFK-0827  
60  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
through %P0008 on the backup unit will not change. %T0002 will be set whenever the  
operation is successful and the data can be used.  
|REM_RDY  
%T00001  
|——||—————————————————————————————————————————————————————————————————————( )—  
|
|
_____  
|REM_ACT |  
|
%M00001  
|——| |———| SVC_|———————————————————————————————————————————————————————————( )—  
|
|
| REQ |  
|
|
| CONST —|FNC |  
| 00027 |  
|
|
|
|
|%P00001—|PARM |  
|
|_____|  
|
|
|
_____  
|%T00001  
REM_RDY LOC_ACT  
|
|
%T00002  
|——| |————————| |——————| |——————| SVC_|————————————————————————————————————( )—  
/
|
|
|
|
|
|
|
|
|
| REQ |  
|
|
CONST —|FNC |  
00028 |  
|
%P00005—|PARM |  
|_____|  
|
|
Second Data Transfer %Q, %AQ, %R, and %M  
Both CPUs will then proceed independently until the end of the logic solution before the  
output scan begins. At this time the second data transfer will take place. In this data  
transfer, all remaining control data (as configured) will be transferred from the active  
unit to the backup unit. This includes the %Q, %AQ, %R, and %M memories, and point  
fault data that has been configured. As with the input data, the backup unit will hold all  
data until it is all received and verified before transferring it to the actual PLC memories.  
After this second data transfer has been completed, both the active and the backup CPU  
will then proceed to perform their output scans and run their programmer and system  
communication windows independently of each other. Any remaining time for the  
background window will also be run and then the sweep housekeeping and input scans  
will be performed before synchronizing again at the start of the next sweep.  
Switching Control to Backup Unit  
The amount of time required for a switch in control from the active unit to the backup  
unit is dependent on the nature of the switch. A switch from the active unit to the  
backup unit will occur if:  
1. the active unit has a failure;  
2. the pushbutton switch on the RCM is depressed;  
3. commanded by activating a Service Request (SVCREQ #26).  
If the switch occurs due to a failure of the PLC CPU (including loss of power), then the  
switch will occur after the backup unit determines that the active unit has failed to  
rendezvous at the synchronization point. Failure to rendezvous may take up to 2  
failwait timeouts (one for each link) to determine. Control will not transfer, in this case,  
until both links have been tried unsuccessfully.  
GFK-0827  
Chapter 4 Operation  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
If the switch occurs due to a controlled condition such as toggling the RCM unit selection  
switch, forcing a switch in the user logic program, or because of a fault detected by the  
PLC CPU, then the switch-over will occur at the beginning of the subsequent sweep.  
The delay will be up to 1 sweep with the possibility of an input and an output scan after  
failure detection.  
Role Switch SVCREQ  
The role switch SVCREQ (SVCREQ #26) will cause the units to switch roles (active to  
backup and backup to active) on the next sweep if the units are synchronized and the  
timing requirements of the role switch request are met. That is, a manual role switch  
may not occur within 10 seconds of a previous manual role switch. Role switches due to  
failures or resynchronization are always allowed (the 10 second limitation does not  
apply). Power flow from SVCREQ #26 indicates that a role switch will be attempted on  
the next sweep. Note that power flow does not indicate that a role switch has occurred or  
even that a role switch will occur on the next sweep. For example, the units could fall  
out of synchronization due to a link timeout before the next sweep which would  
prevent the role switch from occurring.  
An example of the SVCREQ #26 function block is shown below. SVCREQ #26 function  
has three input parameters and one output parameter. When SVCREQ #26 receives  
power flow to its enable input, the PLC is requested to perform a role switch. The three  
input parameters are the enable input, the service number FNC, and PARM, which is the  
beginning reference for the function parameters. An output coil will be set ON if the  
operation succeeds.  
|
_____  
|%I00001 |  
|
%M00001  
|——||———| SVC_| —————————————————————————————————————————————————————————( )—  
|
|
| REQ |  
|
|
| CONST —|FNC |  
| 00026 |  
|
|
|
|
|%R00001—|PARM |  
|
|
|_____|  
A typical application can be to have a switch on a control console wired to %I0001, which  
is the input to the SVCREQ #26 function block. When closed, the switch will activate  
the SVCREQ #26, causing a role switch between units.  
Note that the 10 second limitation allows these SVC_REQs to be in both units so that  
only a single switch occurs if the input is seen by both units.  
GFK-0827  
62  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
%S References for CPU Redundancy  
There are seven special %S references which reflect the status of the Redundancy units:  
%S33 through %S39. The definition of these LEDs is shown in the following table.  
Table 7. Definition for% S Reference for Redundancy Status  
%S Bit  
Definition  
Primary Unit  
Nickname  
Description  
LED  
%S33  
PRI_UNT  
Bit will be set if the local unit is configured as the primary unit: other-  
wise; it is cleared. For any given local unit, if PRI_UNT is set, then  
SEC_UNT cannot be set.  
no  
%S34  
Secondary Unit  
SEC_UNT  
Bit will be set if the local unit is configured as the secondary unit:  
otherwise; it is cleared. For any given local unit, if SEC_UNT is set,  
then PRI_UNT cannot be set.  
no  
%S35  
%S36  
Local Unit Ready  
Local Unit Active  
LOC_RDY  
LOC_ACT  
Bit will be set if local unit is ready to become the active unit; otherwise  
it is cleared.  
yes  
yes  
Bit will be set if local unit is currently the active unit; otherwise it is  
cleared. For any given local unit, if LOC_ACT is set, then REM_ACT  
cannot be set.  
%S37  
%S38  
Remote Unit Ready  
Remote Unit Active  
REM_RDY  
REM_ACT  
Bit will be set if remote unit is ready to become the active unit; other-  
wise it is cleared.  
yes  
yes  
Bit will be set if remote unit is currently the active unit; otherwise it is  
cleared. For any given local unit, if REM_ACT is set, then LOC_ACT  
cannot be set.  
%S39  
LogicEqual  
LOGIC=  
Bit will be set if the logic program for both units in the redundant sys-  
tem is the same; otherwise the bit is cleared.  
no  
no  
%SB18 Redundant Informa-  
tional Message, Fault  
Logged  
RDN_MSG Bit will be set if a redundant informationalmessage was logged.  
It can be cleared in reference tables or logic (you may want to do this  
if logic will be monitoring the bit).  
These bits can be accessed from the users logic program, but cannot be altered or  
overridden. These references are always OFF when no configuration has been stored.  
Once you have completed configuration of the Redundancy system and STORED the  
configuration, the state of these %S references is set and is maintained whether in STOP or  
RUN mode. Four of these references %S35, %S36, %S37, and %S38 are displayed on LEDs  
on the Redundancy Communications Module, as long as that module is not faulted.  
If desired, external indicators other than those on the RCM could be used as status  
indicators to monitor the status of %S35 through %S38 (Local Ready/Active, Remote  
Ready/Active) by programming in ladder logic. These four bits in %S memory can be  
copied to other points from the ladder logic. An example of the expected status of these %S  
references for each unit (Primary and Secondary) in a Redundancy system is as follows:  
Description  
Primary Unit  
Secondary Unit  
Primary Unit  
Secondary Unit  
LocalReady  
ON  
OFF  
ON  
ON  
ON  
OFF  
ON  
OFF  
ON  
ON  
OFF  
ON  
ON  
ON  
LocalActive  
RemoteReady  
RemoteActive  
LogicEqual  
GFK-0827  
Chapter 4 Operation  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
RedundancyCPU Considerations  
The Redundancy CPU (CPU 780) has several restrictions and differences in operation as  
compared to other Series 90-70 CPUs. The following features are not available with the  
CPU 780:  
I/O Interrupts  
Timed Interrupts  
VME Integrator Racks.  
Stop I/O Scan mode  
Flash operation  
Features not Available with CPU 780  
I/O Interrupts  
I/O Interrupts are not supported by the Redundancy CPU (CPU 780). This includes the single  
edge triggered interrupts from the discrete input modules, the high alarm and low alarm  
interrupts from the analog input modules, and interrupts from foreign VME modules, all of  
which can be used to trigger a ladder diagram program block. In order to prevent I/O  
interrupts from changing the data being transferred from one CPU to another, interrupts  
would have to be disabled for the entire transfer time. Programs which declare I/O  
Interrupt triggers cannot be stored to the CPU 780 (the program will be rejected causing an  
abort of the store). In addition, any configuration containing an enabled I/O interrupt for a  
discrete or analog input module will cause a fatal system configuration mismatch fault.  
Timed Interrupts  
Timed Interrupts are not supported by the Redundancy CPU (CPU 780). Timed Interrupts  
would have the same interrupt latency problem as the I/ O Interrupts. Programs which  
declare Timed Interrupt triggers cannot be stored.  
VME Integrator Racks  
The VME Integrator Racks (IC697CHS782 and IC697CHS783) that support half size  
modules are not supported with this release of the Hot Standby CPU Redundancy  
product.  
STOP/IOSCAN Mode  
TheSTOP/ IOSCAN mode is not valid in a redundant system. If an attempt is made to  
place the PLC in this mode, the PLC will reject the selection and return an error. A  
message will be displayed on the programmer with this information.  
Flash Operation  
Flash memory operation is not supported in this release of the CPU 780.  
GFK-0827  
64  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
Differences in Operation for CPU 780  
The following features operate differently with the CPU 780 than they do with other  
Series 90-70 CPUs:  
RUN/ DISABLEDmode  
Configuration of Fault Actions  
STOP to RUN mode transition  
Background Window Time (default is different)  
RUN Disabled Mode  
RUN/ DISABLEDmode causes all physical outputs to go to their default state in that  
PLC. Inputs are still scanned and logic is solved. A CPU in RUN/ DISABLED mode may  
be the active unit.  
There are several guidelines that you should be aware of regarding the use of the  
RUN/ DISABLEDmode.  
1. If a unit is in RUN/ DISABLED mode, its LOC_RDY %S reference and the remote  
units REM_RDY %S reference will not be set and the corresponding LEDs on the  
RCMs will not be ON. This indicates that the unit (with LOC_RDY reference off) is  
not available to drive outputs.  
2. You cannot command a role switch from an active unit that is in RUN/ ENABLED  
mode to a unit that is in RUN/ DISABLED mode. The RCM role switch pushbuttons  
and SVCREQ #26 will be ignored if a role switch is attempted in this situation.  
3. If the units are transitioned when the primary unit is active with outputs disabled  
and the secondary unit is backup with outputs enabled, the primary unit will  
continue to solve logic and transfer outputs to the backup, and the backup unit will  
drive the transferred outputs.  
4. If units are transitioned in any manner where the secondary unit is active with  
outputs disabled and the primary unit is backup with outputs enabled, then the  
units will automatically role switch so that the primary unit becomes active in  
RUN/ ENABLEDmode.  
5. If a unit is in RUN/ ENABLED and the other unit is in RUN/ DISABLED, the unit in  
RUN/ ENABLED will not use its synchronized fault action table. Instead, it will use  
the user-configurable fault actions since there is no backup available to drive  
outputs.  
Note  
If the backup unit is in RUN/ DISABLED mode, then the backup unit will  
continue to NOT drive outputs upon failure of the active unit and  
therefore is not a true backup.  
GFK-0827  
Chapter 4 Operation  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
Following are several examples that illustrate the above guidelines. Each example gives  
the role of each unit, its current operating mode, and the state of the LEDs on the RCMs.  
An X indicates that the corresponding LED and %S bit is ON.  
A. Role switches allowed on both units.  
Primary Unit  
Active  
Secondary Unit  
Backup  
RUN/ ENABLED  
RUN/ ENABLED  
X OK  
X OK  
X LOC_RDY  
X LOC_ACT  
X REM_RDY  
REM_ACT  
X LOC_RDY  
LOC_ACT  
X REM_RDY  
X REM_ACT  
B. Role switches allowed on both units.  
Primary Unit  
Active  
Secondary Unit  
Backup  
RUN/ DISABLED  
RUN/ ENABLED  
X OK  
X OK  
LOC_RDY  
X LOC_ACT  
X REM_RDY  
REM_ACT  
X LOC_RDY  
LOC_ACT  
REM_RDY  
X REM_ACT  
Note that the Secondary unit drives the outputs in this case.  
C. Role switches are not allowed on either unit.  
Primary Unit  
Active  
Secondary Unit  
Backup  
RUN/ ENABLED  
RUN/ DISABLED  
X OK  
X OK  
X LOC_RDY  
X LOC_ACT  
REM_RDY  
REM_ACT  
LOC_RDY  
LOC_ACT  
X REM_RDY  
X REM_ACT  
D. Role switches are allowed on both units.  
Primary Unit  
Active  
Secondary Unit  
Backup  
RUN/ DISABLED  
RUN/ DISABLED  
X OK  
X OK  
LOC_RDY  
X LOC_ACT  
REM_RDY  
REM_ACT  
LOC_RDY  
LOC_ACT  
REM_RDY  
X REM_ACT  
GFK-0827  
66  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
E. Role switches are allowed on both units.  
Primary Unit  
Backup  
RUN/ ENABLED  
Secondary Unit  
Active (see NOTE below)  
RUN/ ENABLED  
X OK  
X OK  
X LOC_RDY  
LOC_ACT  
X REM_RDY  
X REM_ACT  
X LOC_RDY  
X LOC_ACT  
X REM_RDY  
REM_ACT  
F. Role switches are not allowed on either unit.  
Primary Unit  
Backup  
RUN/ DISABLED  
Secondary Unit  
Active (see NOTE below)  
RUN/ ENABLED  
X OK  
X OK  
LOC_RDY  
LOC_ACT  
X REM_RDY  
X REM_ACT  
X LOC_RDY  
X LOC_ACT  
REM_RDY  
REM_ACT  
G. Role switches allowed on both units.  
Primary Unit  
Backup  
RUN/ DISABLED  
Secondary Unit  
Active (see NOTE below)  
RUN/ DISABLED  
X OK  
X OK  
LOC_RDY  
LOC_ACT  
REM_RDY  
X REM_ACT  
LOC_RDY  
X LOC_ACT  
REM_RDY  
REM_ACT  
H. The following situation is not valid. If detected, the units will switch roles  
automatically and behave as in (C) above.  
Primary Unit  
Backup  
RUN/ ENABLED  
Secondary Unit  
Active (see NOTE below)  
RUN/ DISABLED  
Note  
* Secondary unit active is not a recommended mode of operation.  
Configuration of Fault Actions  
With the Redundancy CPU, you cannot select to configure certain faults to be FATAL  
(causing the CPU to STOP). Whenever the system is in redundancy mode with a backup  
unit available, the decision as to which faults are FATAL and therefore will cause a  
switch to the backup CPU are made by the operating system and are not configurable.  
GFK-0827  
Chapter 4 Operation  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
Specific fault actions are described in Section 2 of this Chapter. However, you can  
configure whether or not a stand-alone CPU (after failure of the other CPU) will stop if  
another fault occurs.  
You can select the fault actions (either diagnostic or fatal) for when a given CPU is  
operating without a backup available. This will allow you to choose between fault  
tolerant operation and a safety system where a shutdown is preferred.  
If you do choose to set these fault actions to be diagnostic when the system is running,  
but not synchronized, the unit may remain the active unit even after the backup unit has  
been placed in RUN mode. Also, a unit with the fault actions set to diagnostic may be  
placed in RUN mode and become the active unit even though it may have a diagnostic  
fault which would be logged as fatal in a synchronized system.  
For example, if you were to configure ”Loss of or Missing Rack” failures as diagnostic,  
then the following conditions would apply:  
If an expansion rack fails when the units are synchronized, the unit with the rack  
failure will transition to STOP/ FAULT mode and the other unit will become a  
stand-alone unit.  
If an expansion rack fails after a unit becomes a stand-alone unit, a diagnostic fault  
will be logged on that unit but the unit will stay in RUN mode and continue to  
control the process.  
If after the above situation occurs, the other unit transitions to RUN, the unit with  
the failed expansion rack will stay in RUN mode and may, depending on the  
configuration, remain in control of the process. With this situation, you may want to  
include logic to shut down the faulted unit if this is an undesired operation.  
If an expansion rack fails while in STOP mode or while transitioning to RUN mode,  
a diagnostic fault is logged; however, the unit will still transition to RUN and may,  
depending on configuration, become the active unit. You may want to include logic  
to shut down the faulted unit if this is an undesired operation.  
STOP to RUN Mode Transition  
A resynchronization will occur at all STOP to RUN mode transitions. The time to  
perform this resynchronization may be very large and will exceed the current transition.  
The STOP to RUN mode transition has two separate paths.  
1. If the CPU performing the transition is doing so alone or both CPUs are  
transitioning at the same time, then a normal STOP to RUN mode transition is  
performed (clear non-retentive memory and initialize FST_SCN and FST_EXE).  
2. If the other CPU is active when this CPU performs a STOP to RUN mode transition,  
then non-retentive references will be cleared followed by a resynchronization with  
the active CPU.  
Background Window Time  
In a redundancy system, this value may be set to zero. Unlike other CPU models which  
have a default of 0 ms, the default value for the CPU 780 is 5 ms.  
GFK-0827  
68  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
BackgroundUser Checksum and Background Window  
Timing Instructions  
The following information is provided to allow you to guarantee full coverage of the  
number of program words verified by the User Program Checksum per sweep and the  
Background Window Diagnostics within a certain amount of time. It is important to  
understand that the more checksums performed and the larger the background  
window, the longer the sweep will take. For example setting the number of words to  
checksum to 176 will add 2.8 ms to each sweep.  
First, you should determine the number of words to checksum per sweep.  
(program size ÷ 2) x (sweep time) x maximum completion time  
Words per Sweep =  
[max. completion time – (program size x F)] x max. completion time – C) – (C x F x program size)  
Where:  
Words per Sweep: The number of words to set in the PLC Configuration to be  
checksumed each sweep. This number must be a multiple of 8.  
Program Size: The size of the user program in bytes. You can get this from the  
Logicmaster 90 PLC Memory Usage screen, which is accessed by pressing the status  
softkey (F3) from the Programmer Main menu, then the plcmem softkey (F5). Add  
the ”USER PROGRAM” size on this screen to 10566 (this accounts for internal  
memory usage not added to the user program memory.  
Sweep Time: The sweep time in milliseconds of the user program with checksums and  
background window turned off. You can get this from the Logicmaster 90 status line  
on any screen.  
Maximum Completion Time: The amount of time in milliseconds that you want to have  
full coverage of background diagnostics.  
F: A constant that represents milliseconds per byte of user program checksumed.  
This constant is dependent on the type of CPU module (that is CPUs with 80386  
microprocessors are faster than CPUs with 80186 microprocessors). This constant is  
0.008 ms/ byte for the CPU 780.  
C: A constant with units in milliseconds, which is also dependent on the type of  
CPU. For the CPU 780 it is 4480 ms.  
Following is an example of calculating the Words per Sweep, using the following data:  
User program Size = 89434 bytes  
Program Size =User program Size + 10566 = 89434 + 10566 = 100000 bytes  
Sweep Time = 100 ms  
Max. Completion Time = 120000 ms (2 minutes)  
100000 ÷ 2 x 100 x 120000  
Words per Sweep =  
[120000 – 100000 x 0.008] x (120000 – 4480) – (4480 x 0.008 x 100000)  
Words per Sweep = 174  
You should round this answer (174) up to the nearest number divisible by 8 (8, 16, 24,  
etc.) which is 176 since Logicmaster 90 only accepts numbers divisible by 8. Next use this  
number in the following formula to determine how long to set the background window  
time.  
C x (sweep time + words per sweep x F x 2)  
Background Window Time =  
(maximum completion time – C)  
GFK-0827  
Chapter 4 Operation  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
Where the Background Window Time is the time in milliseconds that you should set the  
background window timer. The other elements in the formula are described above in  
the calculation for words per sweep. The constants (F and C) are for the CPU 780.  
448 0 x (100 + 176 x 0.0008 x 2)  
BackgroundWindow Time =  
(120000 – 4480)  
3.9 rounded up to 4 ms  
Background Window Time =  
Miscellaneous Operation Information  
Timer and PID FunctionBlocks  
These function blocks will remain in lock step between the two synchronized units  
provided:  
A. Enabling logic is identical on both units. This includes power flow, frequency of  
calling sub-block, etc..  
B. The sub-block in which the function block occurs has the same name in both  
units. Note that __MAIN is always common.  
C. Reference registers (3 for timers, 40 for PID) and reset references are copied  
from the unit that was in stand-alone to the unit that just transitioned to RUN  
for each timer and PID function block. This copy does not need to be performed  
if both units transition to RUN in the same sweep.  
For example, if the following ladder logic is identical in sub-blocks on both units,  
then %M100, %R250, %R251, and %R252 must all be transferred on  
resynchronization to keep both units running timers synchronously:  
%M100  
%M100  
–––––––––––––––––––( )  
––––] / [––––––––––– TMR  
1.00s  
%L10 – PV  
CV  
– %L20  
%R250  
Timed Contacts  
When both systems are synchronized, timed contacts will have exactly the same value in  
both units. That is, whenever T_SEC is on in one unit, it will also be on in the other unit  
as long as both units are synchronized.  
OVR_PRE %S Reference  
The OVR_PRE %S reference which indicates whether one or more overrides is active is  
not supported by the CPU 780. This reference should not be used in a redundancy  
system.  
GFK-0827  
70  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
Genius Bus Controller Switching  
Genius Bus Controllers will stop sending outputs to blocks when no data has been  
received from the PLC CPU for a period equal to two times the configured watchdog  
timeout.  
If the CPU on the active unit becomes inoperative in an uncontrolled fashion (for  
example, because of a power failure), the Genius Bus Controllers will detect this within  
twice the watchdog setting, and stop sending outputs to the Genius blocks. After three  
Genius I/ O bus scans of not receiving data from the Genius Bus Controllers, the Genius  
blocks will start driving data from Serial bus Address 30 (that is, the backup unit). If no  
data is available from SBA 30, the blocks revert to default or hold last state (as  
configured).  
For example, if the system has a 200 ms watchdog timeout and 5 ms Genius bus scan  
time, then if the active unit loses power, the Genius Bus Controllers on expansion racks  
will wait 400 ms and then stop updating outputs on Genius blocks. 15 ms later, the  
blocks will begin driving outputs based on data from the backup unit. Note that any  
Genius Bus Controllers in the main rack would stop driving outputs immediately since  
they would also lose power. Genius blocks on these busses would begin driving data  
from the backup unit within 15 ms.  
Note  
For fastest switching, all Genius Bus Controllers in the Hot Standby CPU  
Redundancy system should be in the main rack, or in a rack driven by  
the main racks power supply. This will cause the Genius Bus Controller  
to lose power at the same time that the CPU loses power and allow the  
backup unit to gain full control of the I/ O as soon as possible.  
GFK-0827  
Chapter 4 Operation  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
Section 6: Fault Detection and Control Actions  
This section describes how faults are handled in a Redundancy system. It discusses how  
faults affect the operation of the Redundancy system, describes categories of faults,  
describes how faults are detected, describes the actions taken when faults are detected,  
and discusses on-line repair of individual components.  
Fault Detection  
The Hot Standby CPU Redundancy system requires that faults or failures in all critical  
components be detected and reported so that appropriate control actions may be taken.  
All components that are involved in the acquisition and distribution of I/ O data or are  
involved in the execution of the control logic solution are considered to be critical  
components.  
In a Redundancy system, fault actions are not configurable as they are in a  
non-redundancy (Simplex) system. A FATAL fault will cause a switch from the active to  
the backup unit; a DIAGNOSTIC fault will allow the currently active system to continue  
operating as the active system.  
Faults within the PLC may be such that (1) the PLC has a controlled shutdown, (2) the  
PLC has an uncontrolled shutdown, or (3) the PLC continues to operate. If the PLC has  
detected an internal fault and has a controlled shutdown, a fault will be logged in the  
fault table, the backup system will be notified of the fault and the PLC will go to stop  
mode and stop driving outputs. This does not normally occur until the top of the sweep  
following the failure. The exception is when the failure occurs during the input scan.  
Upon notification, the backup system will immediately take over and start driving  
outputs.  
If the PLC has an uncontrolled shutdown the PLC will log a fault if it can and proceed as  
described above. If the backup PLC detects that the active PLC has failed to  
synchronize, it will assume the active unit has failed after timing out all (both) available  
links. The backup will then start driving outputs and controlling the process. If a fault  
exists within the PLC, but has not been detected, the system will eventually detect the  
fault through the background diagnostic procedure. When the fault is detected, the PLC  
will proceed with the orderly shutdown process if it can.  
If the two PLCs fail to synchronize, because the timeout is set too short, then the two  
systems will begin to act independently. A fault will be logged at the time  
synchronization failure occurs.  
Fault Categories  
The detection of faults and failures falls into three basic categories:  
1. faults and failures that are detected immediately;  
2. faults and failures that are detected as soon as possible, but not necessarily within  
the current sweep;  
GFK-0827  
72  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
3. faults and failures that are detected in the background.  
Faults and failures that are detected immediately are those that are identified within the  
current sweep. These faults include I/ O data corruption, single bit RAM failures, power  
supply failures, processor failures, VME bus failures, and no response from an addressed  
module.  
Faults and failures that are detected as soon as possible, but not necessarily within the  
current sweep, include a group of faults that are detected asynchronously to the PLC  
sweep (Genius faults) or those faults that require a timeout larger than one sweep time  
to detect the failure. These faults are typically detected within one second and include  
all Genius faults (circuit faults, loss of block, etc.)  
Faults and failures that are detected in the background can be detected within 30  
seconds. These faults include address or data line failures, multiple bit RAM failures,  
EPROM failures, and communication device failures.  
ChangingFault Category Actions  
Fault category actions can be changed for both non-redundant systems and redundant  
systems that are not synchronized. When the redundant system is synchronized, the  
fault category actions cannot be changed.  
GFK-0827  
Chapter 4 Operation  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
PLC Fault Table  
The following table lists fault zoom Help text and messages for error codes associated  
with the redundancy fault group.  
Table 8. Fault Zoom Help Text for Redundancy Error Codes  
Error  
Code  
Message  
Fault Description  
Corrective Action  
1
2
3
Primary Unit is Active and  
Secondary Unit is Backup.  
The primary and secondary units have  
switched roles.  
None required.  
None required.  
Secondary Unit is Active and  
Primary Unit is Backup.  
The secondary and primary units have  
switched roles.  
Primary Unit is Active;  
No Backup Unit Available.  
The primary unit has transitioned to RUN  
mode and is running as a stand-alone unit.  
Secondary unit MUST be placed in RUN mode with a  
comparable configuration  
in order to have a synchronized system.  
4
5
Secondary Unit is Active;  
No Backup Unit Available.  
The secondary unit has transitioned to RUN  
mode and is running as a stand-alone unit.  
Primary unit MUST be placed in RUN mode with a  
comparable configuration  
in order to have a synchronized system.  
Primary Unit Has Failed;  
Secondary Unit is Active w/o  
Backup.  
Primary unit has recorded a fatal fault, has  
been powered down, or has lost  
ability to communicate with the secondary  
unit while acting as the active or backup unit.  
Secondary unit will continue running as a  
stand-alone unit.  
If primary unit has also logged the fault ”Secondary  
Unit Has Failed: Primary Unit is Activew/ oBackup”,  
then communications has been broken between the  
two units and must be repaired. If a fatal fault has  
been logged in the primary unit, the indicated fault  
must be repaired. Power may have to be cycled on one  
of the units in order to re-establish communications  
and return to a synchronized system.  
6
Secondary Unit Has Failed;  
Primary Unit is Active w/o  
Backup.  
Secondary unit has recorded a fatal fault, has  
been powered down, or has lost ability to  
communicate with the primary unit while  
acting as the active or backup unit. The pri-  
mary unit will continue running as a stand-  
alone unit.  
If secondary unit has also logged the fault ”Primary  
Unit Has Failed: Secondary Unit is Activew/ oBackup”,  
then communications has been broken between the  
two units and must be repaired. If a fatal fault has  
been logged in the secondary unit, the indicated fault  
must be repaired. Power may have to be cycled on one  
of the units in order to re-establish communications  
and return to a synchronized system.  
7
Synchronization Failure; Both  
Units are Active.  
A communications failure between  
the two units has caused each unit to become  
stand-alone units. Communications has since  
been restored.  
One of the units should be power cycled to return to a  
synchronized system. NOTE: The Genius blocks will  
respond to the unit that is using Serial Bus Address 31.  
8
9
Unable to Switch Redundancy  
Roles  
An attempt to switch redundancy roles was  
made when it was not possible to perform the  
switch.  
None required.  
Primary and Secondary Units  
areIncompatible  
The local unit cannot be placed in RUN mode  
when its redundancy configuration is incom-  
patible with the remote unit. This error is  
logged when (1) Store of an incompatible con-  
fig is attempted and (2) going to RUN with an  
incompatible config.  
Modify the configuration.  
10  
CPU to CPU communications  
terminated  
Synchronization protocol has been violated.  
If this fault is also accompanied by an RCM failed fault,  
replace the failed RCM: otherwise power cycle the CPU  
or CPUs.  
11  
Redundant Link has timed out  
The RCM has timed out while waiting on com-  
munications from the other unit.  
Power cycle the back-up CPU (CPU not  
controlling the process); increase the fail wait time.  
>11  
CPU Redundancy Status has  
Changed  
A change in the status of the system has oc-  
curred. Press Ctrl-F to determine the error  
code.  
Corrective action to be taken depends on the error  
code.  
57  
Redundant link hard  
failure occurred.  
The RCM has been faulted due to an error  
while accessing memory.  
Power cycle the rack with the faulted RCM. If the  
RCM’s BOARD OK LED is on, replace the cable be-  
tween the RCM and the BTM. If the RCM’s BOARD  
OK LED is off, replace the RCM.  
GFK-0827  
74  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
Faulting RCMs, Losing Links, and Terminating Communications  
There are distinct differences between losing a redundant communications link, faulting  
an RCM, and terminating communications.  
Faulting the RCM module occurs only when a hardware related failure occurs such as a  
parity error or VME bus error.  
Action taken when a board is faulted:  
Module Failed fault is logged in the PLC Fault Table.  
All LEDs on the RCM module are turned OFF. The LEDs on the other RCM will  
continue to be updated as long as that RCM is OK.  
The module fault contact is set.  
The corresponding communications link is no longer used. If the other link is still  
operating, then that link will be used for all further data transfer and units can  
remain in synchronization.  
If no other communications link is available, then the unit functions as a stand-alone  
unit when in RUN mode.  
A power cycle, after replacement of the faulted RCM, is required to restore the RCM  
to service.  
Losing a Link occurs when a link timeout occurs (that is, no data received in the expected  
time period). Since the system is not certain that a lost link is due to a hardware failure,  
the RCM is not faulted. Some possible causes for a link timeout are:  
1. Remote unit has failed and is unable to communicate.  
2. Configured fail-wait timeout is too short and a long sweep or communications  
window has resulted in a link timeout. Normally the other link will continue to  
function in this case and the systems remain synchronized. If the condition  
continues, the remaining communications link will timeout in a subsequent sweep.  
3. A hardware problem is present that prevents data from being transferred but is not  
detectable by error checking mechanisms such as parity errors (there are no known  
problems in this category).  
Action taken when a link has timed out.  
Link Timeout fault is logged in the PLC Fault Table.  
The OK and Local LEDs on the RCM in the RCM to BTM link that failed will  
continue to be maintained (that is, they will stay ON and the Local LEDs will reflect  
the state of the Local unit) but the Remote LEDS will be turned OFF. The LEDs on  
the other RCM will continue to be updated as long as that RCM is OK.  
The module fault contact is set.  
The corresponding communications link is no longer used. If the other link is still  
operating, then that link will be used for all further data transfer and units can  
remain in synchronization.  
If no other communications link is available, then the unit functions as a stand-alone  
unit when in RUN mode.  
A power cycle of either unit is required to restore the link to service.  
GFK-0827  
Chapter 4 Operation  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
In this case, if the RCM is at fault, it will need to be replaced before power is  
restored.  
Terminating Communications occurs when the two units get out of synchronization.  
The action taken when communications is terminated is the same as when a link has  
timed out, except that actions are taken on both links and the Communications  
Terminated fault is logged rather than Link Timeout.  
GFK-0827  
76  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
Fault Actions in a CPU Redundancy System  
Fault actions in the Hot Standby CPU Redundancy System are handled differently than  
those in a non-redundancy (Simplex) system. Whenever there is a ”ready” backup unit  
configured in the system, the fault actions in the active unit will not be those normally  
specified by the user. For an active unit with a ready backup, any fault which will cause  
a degradation in performance, or loss of control of I/ O which does not cause a similar  
degradation of performance or loss of control of I/ O in the backup will be considered a  
FATAL fault in the active unit and cause the active unit to transition to STOP mode.  
The configurable fault actions will be applied whenever the system is running in  
stand-alone mode in case you prefer fault tolerance (availability) versus safety  
(depending on the application). The following tables (1) define the Fault Groups and (2)  
show the fault groups and their fault action defaults. There are three fault actions  
shown in Table 11: Fatal, Non-Fatal, and Conditionally Fatal. Fatal always stops the PLC,  
Non-Fatal never stops the PLC and Conditionally Fatal stops the PLC depending on  
other information in the fault.  
Table 9. Maskable Fault Group Descriptions  
Table  
Type  
Fault Group  
Description  
LOSS_RACK  
CPU  
I/ O  
Lossof or Missing Rack  
Loss of or Missing IOC  
LOSS_IOC  
LOSS_IO_MOD  
LOSS_OTHR_MOD  
ADD_RCK  
I/ O  
Lossofor Missing I/ O Module  
Loss of or Missing Option Module  
Addition ofor Extra Rack  
CPU  
CPU  
I/ O  
ADD_IOC  
Addition of or Extra IOC  
ADD_IO_MOD  
ADD_OTHR_MOD  
IOC_FAULT  
I/ O  
Addition ofor Extra I/ O Module  
Addition of, Reset of, or Extra Option Module  
IOC or I/ O Bus Fault  
CPU  
I/ O  
IO_MOD_FAULT  
CNFG_MIS_MTCH  
SYS_BUS_ERROR  
CPU_HARDWR  
MOD_HARDWR  
IOC_SOFTWR  
I/ O  
I/ O Module Fault  
Both  
CPU  
CPU  
CPU  
I/ O  
System ConfigurationMismatch  
System Bus Error  
CPU Hardware Failure  
ModuleHardwareFailure (e.g. Serial Port Failure on PCM)  
IOC Software Failure  
MOD_OTHR SOFTWR  
PRG_BLK_CHKSUM  
LOW_BATTERY  
CNST_SW_EXCD  
PLC_FTBL_FULL  
IO_FTBL_FULL  
APPLICATION_FLT  
CPU  
CPU  
CPU  
CPU  
CPU  
CPU  
CPU  
Option Module Software Failure  
Program BlockChecksum Mismatch  
Low Battery in the System  
Constant Sweep Exceeded  
PLC System Fault Table Full  
I/ OFault Table Full  
UserApplication Fault  
GFK-0827  
Chapter 4 Operation  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
Table 10. Maskable Fault Group Actions  
Fault Action  
SimplexMode  
RedundantMode  
Fault Group  
User Configurable  
LOSS_RACK  
Non-Fatal  
Non-Fatal  
Non-Fatal  
Non-Fatal  
Non-Fatal  
Non-Fatal  
Non-Fatal  
Non-Fatal  
Non-Fatal  
Non-Fatal  
Fatal  
Fatal  
Fatal  
Ye s  
Ye s  
Ye s  
Ye s  
No  
No  
No  
No  
Ye s  
No  
Ye s  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
LOSS_IOC  
LOSS_IO_MOD  
LOSS_OTHR_MOD  
ADD_RCK  
Non-Fatal  
Non-Fatal  
Non-Fatal  
Non-Fatal  
Non-Fatal  
Non-Fatal  
ConditionallyFatal  
Non-Fatal  
Fatal  
ADD_IOC  
ADD_IO_MOD  
ADD_OTHR_MOD  
IOC_FAULT  
IO_MOD_FAULT  
CNFG_MIS_MTCH  
SYS_BUS_ERROR  
CPU_HARDWR  
MOD_HARDWR  
IOC_SOFTWR  
Fatal  
Fatal  
Fatal  
Fatal  
Non-Fatal  
Fatal  
Non-Fatal  
Conditionallyfatal  
Non-Fatal  
Fatal  
MOD_OTHR SOFTWR  
PRG_BLK_CHKSUM  
LOW_BATTERY  
CNST_SW_EXCD  
PLC_FTBL_FULL  
IO_FTBL_FULL  
APPLICATION_FLT  
Non-Fatal  
Fatal  
Non-Fatal  
Non-Fatal  
Non-Fatal  
Non-Fatal  
Non-Fatal  
Non-Fatal  
Non-Fatal  
Non-Fatal  
Non-Fatal  
Non-Fatal  
The two fault groups IOC_FAULT and IOC_SOFTWR faults are Conditionally Fatal to  
the system (forces the PLC to STOP FAULT mode) whenever the fault that is logged is  
Fatal to the Genius Bus Controller that logged the fault. When a module logs a fault it  
notifies the PLC whether or not it can continue by placing Fatal or Diagnostic in the fault  
action of the fault entry. The PLC will shut the Genius Bus Controller down on all Fatal  
faults.  
Note  
In a CPU redundancy system a Fatal fault from a GBC will cause the  
active unit to transition to STOP FAULT mode. All Diagnosticfaults will  
allow the CPU to continue to operate.  
GFK-0827  
78  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
Table 11. Non-Maskable Fault Group Descriptions  
Table  
Type  
Fault Group  
Description  
SYS_BUS_FAIL  
NO_USER_PRG  
BAD_USER_RAM  
CPU  
CPU  
CPU  
System bus failure.  
No User s Program on Power-up.  
Corrupted User RAM detected on Power-up.  
WIND_CMPL_FAIL CPU  
Window Completion Failure in Constant Sweep Mode (i.e., all  
windows failed to receive their allotted time).  
PASSWD_FAIL  
CPU  
CPU  
CPU  
CPU  
PasswordAccess Failure.  
NULL_SYS_CNFG  
CPU_SOFTWR  
NULLSystem Configuration for RUN Mode.  
PLC CPU Software Failure.  
TOO_MANY_IOCS  
More than the allowable number ofI/ O Bus Controllers were  
found in the system.  
SEQ_STORE_FAIL  
CPU  
Communicationfailure during a store operation by the program-  
mer. This fault results when the start-of-store sequence was  
received but not an end-of-storesequence.  
Table 12. Non-Maskable Fault Action Descriptions  
Fault Actions  
Fault Group  
SimplexMode  
Redundant Mode  
SYS_BUS_FAIL  
Fatal  
Non-Fatal  
Fatal  
Fatal  
Non-Fatal  
Fatal  
NO_USER_PRG  
BAD_USER_RAM  
WIND_CMPL_FAIL  
PASSWD_FAIL  
Non-Fatal  
Non-Fatal  
Non-Fatal  
Fatal  
Non-Fatal  
Non-Fatal  
Non-Fatal  
Fatal  
NULL_SYS_CNFG  
CPU_SOFTWR  
TOO_MANY_IOCS  
SEQ_STORE_FAIL  
Fatal  
Fatal  
Fatal  
fatal  
GFK-0827  
Chapter 4 Operation  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
On-Line Repair  
With a Hot Standby CPU Redundancy system most system component failures can be  
repaired by replacing the failed component while the system is on-line. These on-line  
repair procedures are possible because of the role switching capability of the units in the  
system. Status of the Primary and Secondary units is determined by observing the  
LEDs on the Redundancy Communications Module. There are two basic situations  
regarding the active and backup units that you should be aware of when a component  
needs to be replaced.  
1. If the failure is in the active system, control will switch to the backup system. Power can  
then be removed from the rack containing the failed component  
2.  
Note  
If maintenance is to be performed on a unit when that unit is the active  
unit in a synchronized system, then control should be switched to the  
other unit before powering down. This will allow for an orderly transfer  
of control.  
After repairing a defective unit:  
1. Power-up the CPU rack in STOP mode.  
2. Verify that the Remote Ready and Remote Active LEDS are on while in STOP mode.  
3. Verify that the Local Ready and Local Active LEDs are on in the Active unit.  
4. Put the repaired unit in RUN mode.  
Maintaining Parallel Bus Termination  
It is important when doing on-line repair to maintain parallel bus termination on the  
active unit. This is the reason that the terminated parallel cable (IC697CBL811 or  
IC697CBL826) is used, and why the RCM must be the last device on the parallel bus. The  
terminated end of the cable may be safely removed from a de-energized RCM. These  
terminated cables should be considered an integral part of the unit it terminates.  
On-Line Repair Recommendations  
It is advised when doing on-line repair to power-off the entire PLC system (of the  
suspect unit), including ALL RACKS. Change the suspect part, and power-up in STOP  
mode. Verify that the links are operational before switching to RUN (%S bits and RCM  
LEDs update in STOP mode).  
GFK-0827  
80  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
Power Supply  
The power supply has adequate internal fault detection which will cause it to  
automatically shut down if there is a failure. In an orderly shut down, the power supply  
will first assert the ACFAIL signal before it asserts the SYSREST signal. This will give the  
active PLC time to notify the backup PLC that it can no longer control the process.  
In the event of a power supply failure, the backup CPU takes control of the system. The  
power supply can be replaced with power removed from its rack without interruption to  
the application being controlled. When the power supply is replaced, power can be  
returned to the rack and the CPU will then obtain synchronization with the active  
system and either take control or become the backup CPU.  
Racks  
The only detectable rack failure is bad data across the backplane. This bad data can take  
the form of a bad control line as well as a bad data or address line. In most cases bad data  
lines will be detected by the data integrity checks associated with the data transfers. If  
these occur the system will be faulted and control transferred to the backup unit. An  
indication will be given that a data transfer error has occurred.  
There is no single indication that a rack failure has occurred. The rack is a very reliable  
component in the system and rack failures are extremely rare. A rack failure (other than  
a catastrophic rack failure) will only be correctly diagnosed by process of elimination.  
In the unlikely event that a rack failure does occur and is correctly diagnosed, the rack  
can be replaced with power removed from the system. When the rack is replaced and  
power restored to the system, the CPU will then obtain synchronization with the active  
system and either take control or become the backup CPU.  
Central Processor Unit  
If the CPU 780 fails, the OK light on the CPU will be out or blinking. In addition, fault  
information will be available in the Fault Table of one or both CPUs.  
In the event of a CPU failure control is transferred to the backup system. CPU  
replacement can be accomplished by removing power from the rack and replacing the  
CPU. When power is returned to the system, the program can be loaded into the CPU  
and the CPU started. It will then obtain synchronization with the active system and  
either take control or become the backup CPU.  
Redundancy Communications Module and Cables  
If a fault is detected in a single RCM or in its terminated I/ O cable, the backup RCM will  
be used. Control will not transfer to the backup CPU. An RCM fault will be logged in the  
PLC Fault Tables of both PLCs. The loss of an RCM is not fatal. If there are expansion racks  
within a system, and the cable fault is such that the system can no longer communicate  
to the expansion racks, then the fault is fatal and the PLC will be halted. Control will  
then transfer to the backup PLC.  
GFK-0827  
Chapter 4 Operation  
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
If an RCM fault is detected, proceed as follows:  
STOP the unit with the suspected bad RCM.  
Turn power off at that rack.  
Unplug the terminated cable from the RCM and replace the module.  
Reconnect the terminated cable.  
Power-up the rack (mode switch is still in STOP).  
Verify that the REMOTE ACTIVE and REMOTE READY LEDs are on, or look at the  
%S bits in the stopped unit. Note that the RCM LEDs only update if the board is not  
faulted.  
Switch the repaired unit to RUN.  
RedundancyCommunications Link Failures  
There are two types of Redundancy Communications Link failures; a ”Link Timeout”  
and a ”Hard Link Failure”. When a Link Timeout occurs, the RCM BOARD OK LED will  
remain ON and the LOCALREADY and LOCALACTIVE LEDs will continue to reflect  
the status of the Local unit. The REMOTE ACTIVE and REMOTE READY LEDs will not  
be updated by the Remote unit until the link is reinitialized by storing a configuration or  
power cycling either unit. When a Hard Link Failure occurs, all five RCM LEDs will be  
OFF. A power cycle of the Local unit is required to attempt to reinitialize the failed link.  
Bus Transmitter Module  
A fault in the BTM is treated just like a fault in the RCM. It is only fatal if the fault  
prevents communications to any expansion racks within the system.  
Failure of the BTM module may not easily be distinguished from an RCM cable failure or  
even an RCM failure. However, most failure modes of the BTM can be isolated to the  
BTM. When a BTM fails, the system will respond as described for the RCM and cable  
failure, it will only fault the active PLC if the active PLC has expansion racks with critical  
components installed.  
The BTM can be replaced by removing power from the rack and replacing the BTM.  
When power is restored to the CPU, the CPU will obtain synchronization with the active  
system and either take control or become the backup CPU.  
Genius Bus Controller  
In a synchronized Hot Standby CPU Redundancy system, all GBC faults are considered  
fatal. The failure of a Genius bus controller will be detected and isolated by the PLC. If a  
GBC fails in the active PLC, the active PLC will fail and the backup will assume control.  
The GBC can be replaced by removing power from the rack and replacing the GBC.  
When power is restored to the CPU, the CPU will obtain synchronization with the active  
system and either take control or become the backup CPU.  
GFK-0827  
82  
Series 90-70 Hot Standby CPU Redundancy Users Guide – December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4
GeniusBus  
Genius bus faults are not fatal to the PLC. However, if a bus fault exists, it exists for both  
systems. There may be situations where one controller can communicate to more blocks  
than the other controller can. Since both controllers are running with the same outputs  
and shared inputs, and both controllers are still synchronized, the blocks will choose  
which controller to respond to, if either can be heard.  
The Genius bus can be repaired without disturbing power to either system and thus  
without disturbing which PLC is in control of the process. Replacement of a bus can be  
done on line but is not recommended because all devices on that bus will be lost until  
the bus is repaired.  
GeniusBlocks  
The failure of a single block is not fatal to the PLC.  
GFK-0827  
Chapter 4 Operation  
83  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Appendix A RedundancyAlternatives  
section level 1 1  
figure_ap level 1  
table_ap level 1  
A
Redundancy Alternatives  
There are several redundancy alternatives for the Series 90-70 Programmable Logic  
Controller. These redundancy options consist of implementation of the redundancy  
feature through a user logic program or through a redundancy product which consists of  
both hardware and software. The type of redundancy product alternative that is used is  
also referred to as the Control Strategy, which must be defined for configuration  
purposes. Redundancy alternatives are:  
Hot Standby Application Logic;  
Hot Standby Product plus Application Logic;  
Hot Standby Product (described in this manual);  
ESD (Emergency Shutdown System) Duplex Application Logic;  
ESD Duplex and Triplex GMR (Genius Modular Redundancy) (see GFK-0787, Genius  
Modular Redundancy Users Manual).  
For your information the following Redundancy Selection Guide is provided which lists the  
features desired through implementation of a redundancy system followed by a table  
which further describes these redundancy options.  
Note  
Note that the redundancy option described in this  
manual is the Hot Standby Product.  
85  
GFK-0827  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
A
a47009  
START  
Fault  
Tolerant  
No  
Yes  
ESD  
SYSTEM  
FAILURE  
STRATEGY  
TRIPLEX  
CPUS  
HOT STANDBY  
(2 CPUS) OPTIONS  
Fail Safe  
Redundancy  
Option Key  
(see Table 1)  
1, 2, 3  
5B  
SINGLE  
BUS  
OPTIONS  
REDUNDANT  
BUS  
DUPLEX  
CPUS  
1, 2  
4
APPLICATION  
LOGIC  
LOW COST  
1B  
DUPLEX  
CPUS  
5A  
LOWEST COST  
1D  
PRODUCT  
I/O COUNT  
1A-C, 2, 3  
>512 IN/512 OUT  
VME  
1A-C, 2, 3  
1A-C, 2, 3  
ISO/ETHERNET  
THERMOCOUPLE/  
RTD  
1C, 3C  
1A, 3A  
HIGH DENSITY  
ANALOG IN  
Use This Guide to Select the  
Redundancy Option Key for the  
Available Redundancy Options  
Figure 9. Guide to Selection of Redundancy Option Key for Table 1 (RedundancyOptions)  
GFK-0827  
86  
Series 90-70 Hot Standby CPU Redundancy Users Guide - December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
A
Table 13. RedundancyOptions  
Output  
Selection  
Method  
Option  
PLC  
Scan  
Sync  
Data  
Sync  
I/O System  
Redund. Redund.  
SelectionGuide  
Key  
Bus  
I/O  
290-70s  
no  
Application  
Logic  
90-70  
(I/ OScanner)  
Hot  
Standby  
yes - 2  
no  
Higher Density Analog Inputs  
MorecompetitiveI/ O  
1A  
Hot Standby  
290-70s  
290-70s  
no  
no  
Application  
Logic  
90-30  
(GCM+)  
Hot  
Standby  
yes - 2  
yes - 2  
no  
no  
1B  
1C  
Application  
Application  
Logic  
GeniusI/ O  
Hot  
Standby  
Highly distributable with diagnos-  
tics. Thermocouple. RTD  
290-70s  
290-70s  
no  
Application  
Logic  
90-30  
(GCM+)  
Hot  
Standby  
yes - 2  
yes - 2  
no  
no  
Least expensive. Limited to  
512 Inputs, 512 Outputs  
1D  
2
Hot Standby  
Product plus  
yes  
Operating  
System  
90-30  
(GCM+)  
Hot  
Standby  
Redundant Bus Applications.  
MorecompetitiveI/ O.  
Application Logic  
Function  
290-70s  
290-70s  
290-70s  
290-70s  
290-70s  
390-70s  
yes  
yes  
yes  
no  
Operating  
System  
90-70  
(I/ OScanner)  
Hot  
Standby  
no  
no  
no  
no  
Higher Density Analog Inputs  
MorecompetitiveI/ O.  
3A  
3B  
3C  
4
Hot Standby Product  
Operating  
System  
90-30  
(GCM+)  
Hot  
Standby  
Operating  
System  
GeniusI/ O  
GeniusI/ O  
GeniusI/ O  
GeniusI/ O  
Hot  
Standby  
no  
no  
Highly Distributable with diagnos-  
tics. Thermocouple. RTD.  
ESD Duplex  
Application Logic  
no  
no  
no  
Duplex  
yes - 2  
yes  
yes  
yes  
For Fail-Safe ESD applications.  
ESD Duplex  
GMR Product  
no  
GMR  
yes - 2  
or 3  
For Fail–Safe or fault tolerant ESD  
applications.  
5A  
5B  
ESD Triplex  
GMR Product  
no  
GMR  
yes - 3  
For fault tolerant ESD applications.  
See list of restrictions below.  
Explanation of terms used in the above Table of Redundancy Options.  
Hot Standby Redundancy  
Two CPUs are connected to one or more I/ O. One CPU is active; the other is in standby. If the active  
unit fails, the standby unit takes control of the process (Hot Standby Redundancy is sometimes  
known as Hot Backup Redundancy).  
Scan Synchronization  
Scan mechanisms may be synchronized to keep active and standby units in lockstep to minimize  
”bumps” or upsets to the process when switching from active to standby unit.  
Data Synchronization  
Keeps standby unit refreshed with the current state of the active unit to minimize ”bumps” or upsets  
to the process when switching from active to standby unit.  
Emergency Shutdown System (ESD)  
Two or three unsynchronized CPUs solve logic asynchronously based on common inputs. Output  
state is voted on by the output devices. The inputs and outputs are normally energized and do not  
change state. DUPLEX ESD is Failsafe while TRIPLEX ESD is fault tolerant.  
Application Logic-Based Solutions  
ProductSolutions  
Has many restrictions (see the list of restrictions on page 13).  
Has functions built into the operating system that make the system easier to engineer and more  
robust. Product solutions are preferable to application solutions from a support perspective.  
Output Selection Method  
Refers to the algorithm in the I/ O device, such as Hot Standby, Duplex, or No Redundancy Modes.  
These modes may refer to existing GeniusI/ O terminology. GMR (Genius Modular Redundancy)  
mode is a voting algorithm available in Genius I/ O DC blocks.  
FailSafe  
An ESD system will fail such that the process under supervision will be shutdown.  
In an ESD system any single failure will not disrupt the process under supervision.  
Fault Tolerant  
GFK-0827  
Appendix A Redundancy Alternatives  
87  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
A
Series 90-70 Redundancy Through Application Logic  
The following restrictions apply using the current Series 90-70 for redundancy  
applications requiring synchronization (these restrictions do not apply to the Hot Standby  
CPU Redundancy product).  
Do not use transitional contacts or coils since this information cannot be transferred  
across the link.  
Avoid using timers, counters or PID in program blocks which are not called every  
sweep otherwise timer durations may not match up when control is transferred.  
Since PID keeps the actual real time clock in its data structure, you cannot simply  
execute it all the time while updating its entire data structure. You must omit the  
clock portion of the data structure when you do the transfer. Another safer method  
would be to keep the backup unit in manual mode while forcing the manual register  
to the output of the master. When the switch-over occurs, put the PID in auto.  
The time of day clock cannot be shared between PLCs, therefore it cannot be used to  
make program decisions.  
Do not use MCRs since the internal value of the MCR cannot be transferred  
between systems.  
Do not expect information that comes in to the system from an external  
communications device to be the same in both systems. The communications can  
change data in one system before it is updated in another.  
Avoid using fault contacts and fault table information to base critical program  
decisions, some of the information is not available to be passed between systems.  
Avoid using the timed contacts since the internal PLCs real time clocks will not  
match.  
Local program block memory (%L) cannot be transferred between the PLCs,  
therefore data that must be shared should be restricted to the transferred memories.  
GFK-0827  
88  
Series 90-70 Hot Standby CPU Redundancy Users Guide - December 1993  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Index  
A
C
Acronyms, list of, 12  
Cable, programmer connection, connect-  
Active and backup sweeps, 59  
Calculations, background user checksum,  
Appendix A, redundancy alternatives, 85  
ASCII identifier for control strategy, 58  
Checksum, program memory, 18  
Communications module, redundancy, 7  
Communications, terminating, 76  
B
Background window, 69  
Configurable backup data size, 9  
Configuration  
expansion memory board, 39  
genius bus controller, 42  
paired gbc parameter, 42  
Battery, backup, 18  
parameters for cpu redundancy, 27  
parameters, list of for redundancy, 10  
configure remote communications  
configurable backup data size, 9  
select expansion memory board, 46  
switch to backup unit time, 8  
Bus controller,geniusI/ O, 4 , 5 , 24  
Bus receiver module  
Configuring a hot standby cpu redundan-  
Bus,I/ O termination of, 24  
89  
GFK-0827  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
F
Connectors, battery, 17  
Fault actions  
configuration of, 67  
Constant window sweep mode configura-  
Control strategy, 5 , 58  
table of, 77  
CPU  
module for redundancy, 7  
serial port connector, 18  
watchdog timer, 14  
Fault group descriptions, non-maskable,  
CPU requirements for redundancy, 33  
Fault zoom help text, redundancy error  
D
Data parameters, shared I/ O, 37  
Data size, backup, 9  
Data transfer  
%Q, %AQ, %R, %M, 61  
G
Data transfer example, backup to active  
Genius bus controller, 4 , 5  
configuration example, 48  
configuration of, 42  
Data transfer, backup to active unit, 60  
Definition of terms, 11  
description of, 24  
E
Expansion memory, 7 , 18 , 38  
Expansion memory board, 39  
GFK-0827  
90  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Index  
GeniusI/ O, bus controller, 24  
Grounding, programmer, 9  
Guidelines for run disabled mode, 66  
H
M
Help text, redundancy error codes, 74  
Memory protect keyswitch, 17  
Memory, flash, 64  
Hot standby CPU redundancy, 85  
Hot standby cpu redundancy  
basic description of, 1  
benefits of, 3  
features of, 3  
I/ Osystems  
geniusI/ O, 4  
localI/ O, 4  
Hot standby redundancy control strategy,  
N
Non-maskable fault group descriptions,  
I
I/ O bus signaltermination, 24  
O
K
On-line repair, 9 , 80  
Keyswitch, memory protect, 17  
genius bus controller, 82  
power supply, 81  
L
LEDs for redundancy communications  
redundancy communications module,  
Operating mode, selection of, 16  
Lithium battery for memory backup, 18  
Local I/ O configuration,example of, 5  
Operating modes, valid  
91  
GFK-0827  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
local system ready, 20  
remote system ready, 21  
Operation of a cpu redundancy system,  
Redundancy cpu considerations  
I/ Ointerrupts, 64  
timed interrupts, 64  
P
Parallel bus termination, 80  
catalog number, IC697CPU780, 13  
description of, 13  
PLC fault table, redundancy error codes,  
expansion memory board, 18  
features of, 15  
illustration of, 15  
installation information, 13  
memory protect keyswitch, 17  
serial port connector, 18  
watchdog timer, 14  
R
Redundancy option key, 86  
Racks  
Redundancy options, table of, 87  
Redundant cpu module, resynchroniza-  
Redund type, configuration of, 34  
Reference values, shared I/ O, 37  
Reference, OVR_PRE, 70  
Redundancy  
alternatives  
hot standby product plus application  
References, %S, definition of, 63  
Redundancy communications module  
description of, 19  
illustration of, 19  
GFK-0827  
92  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
Sweep mode  
constant window, 35  
S
Sweeps, active and backup, 59  
Switch to backup unit time, 8  
Switching control to backup unit  
Screens for fault category, 29  
Sequence, power-up, 55  
Serial port connector, 18  
System components for redundancy, 13  
System operation, normal, 55  
SharedI/ O, 9  
T
Status references for redundancy systems,  
Terms, definitions of, 11  
STOP/ IOSCAN mode, 16  
Time to switch to backup unit, 8  
Transition, stop to run mode, 68  
SVCREQ #26 example, 62  
W
93  
GFK-0827  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Sharp Car Satellite TV System LC 32LE155X User Manual
Sony Camcorder BMC 110 User Manual
Sony CD Player XA C30 User Manual
Sony MiniDisc Player MZ EP11 User Manual
Sony Portable Speaker SS FCRW115 User Manual
Spalding Fitness Equipment M890001 User Manual
Speco Technologies Computer Monitor VM TV19LCD User Manual
StarTechcom Stereo Receiver VGA2HD2 User Manual
SUPER MICRO Computer Network Card P4SCT+ User Manual
Sylvania DVD VCR Combo DVC865G User Manual