Quick Start Guide - ATV312
S1A1094202
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•
•
Read and understand this quick start guide before performing any procedure with this drive.
The user is responsible for compliance with all international and national electrical code requirements with respect to grounding of all
equipment.
•
•
•
•
Many parts of this drive, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically insulated tools.
DO NOT touch unshielded components or terminal strip screw connections with voltage present.
DO NOT short across terminals PA/+ and PC/- or across the DC bus capacitors.
Before servicing the drive:
-
-
-
-
-
-
Disconnect all power, including external control power that may be present.
Place a "DO NOT TURN ON" label on all power disconnects.
Lock all power disconnects in the open position.
WAIT 15 MINUTES to allow the DC bus capacitors to discharge.
Measure the voltage of the DC bus between the PA/+ and PC/- terminals to ensure that the voltage is less than 42 Vdc.
If the DC bus capacitors do not discharge completely, contact your local Schneider Electric representative. Do not repair or operate
the drive
•
Install and close all covers before applying power or starting and stopping the drive.
Failure to follow these instructions will result in death or serious injury.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider
Electric for any consequences arising out of the use of this product.
Information below is designed to use single drive connected to single motor with a motor cable length less than 50 meters (164 ft).
In any other case, consult the ATV312 installation manual (BBV46391) and programming manual (BBV46385) on www.schneider-electric.com.
1
Check the delivery of the drive
•
•
Remove ATV312 from the packaging and check that it has not been damaged.
WARNING
DAMAGED DRIVE EQUIPMENT
Do not operate or install any drive or drive accessory that appears damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Check that the drive reference printed on the label matches the delivery note and corresponding purchase order.
Write the drive Model Reference: _____________ ___________and Serial Number: ____________________________
2
Check the line voltage compatibility
•
Check that the line voltage is compatible with the supply range of the drive.
8B0917121134
Line voltage _______ Volts
/
Drive voltage range _______ Volts
Drive range: ATV312 M2 = 200/240 V single phase / ATV312 M3=200/240 V three-phase
ATV312 N4 = 380/500 V three-phase / ATV312 S6 = 525/600 V three-phase
3
Mount the drive vertically
For a surrounding air temperature up to 50 °C (122 °F)
(a)
(a)
(b)
(a) 50 mm (2 in.)
(b) 10 mm (0.4 in.)
1/4
Download from Www.Somanuals.com. All Manuals Search And Download.
7
(continued)
Set motor parameters
•
Set tUn parameter to YES.
Customer
setting
Menu
Code
Description
Factory setting
drC-
[MOTOR CONTROL]
[Auto Tunning]:
tUn
nO
Auto-Tunning for UnS, FrS, nCr, nSP, nPr and COS
DANGER
DANGER
HAZARD OF ELECTRIC SHOCK OR ARC FLASH
UNINTENDED EQUIPMENT OPERATION
•
The Nominal Motor Parameters UnS, FrS, nCr, nSP, nPr and
COS must be correctly configured before starting auto-tuning.
If one or more of these parameters is modified after auto-tuning has
been performed, tUn will return to nO and the procedure must be
repeated.
•
•
During auto-tuning, the motor operates at rated
current.
Do not service the motor during auto-tuning.
•
Failure to follow these instructions will result in death
or serious injury.
Failure to follow these instructions will result in death or serious injury.
8
Set basic parameters
Customer
Factory setting
Menu
Code
Description
setting
[Acceleration]:
Acceleration time (s)
[Deceleration]:
Deceleration time (s)
[Low speed]:
Motor frequency at minimum reference (Hz)
[High speed]:
ACC
3.0
3.0
0.0
dEC
LSP
HSP
ItH
rrS
PS2
PS4
SA2
SEt-
[SETTINGS]
50.0
drive rating
LI2
Motor frequency at maximum reference (Hz)
[Mot. therm. current]:
Nominal current on motor nameplate (A)
[Reverse assign.]:
I-O-
[INPUTS / OUTPUTS CFG]
Reverse assignment
[2 preset speeds]:
LI3
Preset speeds
Fun-> PSS-
[PRESET SPEEDS]
[4 preset speeds]:
Preset speeds
[Summing ref. 2]
Analog input
LI4
Fun-> SAI-
[SUMMING INPUTS]
AI2
9
Set control choice
Menu
CtL-
[COMMAND]
I-O-
[INPUTS / OUTPUTS CFG]
Code
Description
[Ref.1 channel]:
Reference control
[2/3 wire control]:
Command control
5.1 [REMOTE configuration]
Al1 (factory setting),
Al2, Al3
2C: 2-wire (factory setting)
3C: 3-wire
5.2 [LOCAL configuration]
Customer Setting
Fr1
AlU1
tCC
LOC
[REMOTE configuration]
[LOCAL configuration]
9.1
9.2
(Factory setting)
MODE
3s
Factory settings of parameters:
Fr1 = AI1
rdY
LOC
tCC = 2C
Factory settings of parameters:
Fr1 = AIU1
tCC = LOC
rrS = LI2
35.1
PS2 = LI3
PS4 = LI4
[Output frequency] (Hz)
10
Start the motor
3/4
S1A10942 - 02/2012
Download from Www.Somanuals.com. All Manuals Search And Download.
Menus structure
MODE
= ENT
ESC
3s
LOC
rEN
2s
rdY
rdY
These 3 parameters are
only visible at first power up
of the drive.
MODE
ESC
ENT
3s
bFr
Settings can be changed
subsequently in menu:
drC- for bFr
CtL- for Fr1
I-O- for tCC.
[Output frequency] (Hz)
35.
Fr1
tCC
MODE
rEF-
[SPEED REFERENCE]
[SETTINGS]
SEt-
drC-
[MOTOR CONTROL]
I-O-
CtL-
FUn-
FLt-
COM-
SUP-
[INPUTS / OUTPUTS CFG]
[COMMAND]
[APPLICATION FUNCT.]
[FAULT MANAGEMENT]
[COMMUNICATION]
[MONITORING]
Parameter selection
= ENT
ESC
ESC
15.
SEt-
ACC
Refer to the programming manual (BBV46385) for comprehensive menu descriptions.
ENT
ESC
ENT
A dash appears after menu codes to differentiate them from parameter codes.
26.
dEC
Example:
ENT
[SETTINGS] (SEt-), ACC parameter.
26.
SFr
1 flash
(save)
4/4