SUBMITTAL SHEET
AIRCONDITIONING PRODUCTS
SYSTEM
24XS32A
INDOOR/OUTDOOR
XS2432/C24 32
322A
CEILING RECESSED (4-WAY) AIR CONDITIONER
2
SS24XS32- 2
PERFORMANCE DATA @ ARI STANDARD CONDITIONS (230/208V)
GENERAL DATA
V/PH/HZ
(AT 230V)
COOLING
POWER
230/208/1/60
30
30
Total Capacity
Sensible Capacity
Latent Capacity
SEER
(BTU/H)
(BTU/H)
(BTU/H)
24,000/23,400
13,740/13,300
10,360/10,100
10.0/10.2
Circuit Ampacity, Min. (A)
Fuse size, Max.
(A)
COMPRESSOR
No. used
R.L. Amps - L.R. Amps (A)
Crankcase Heater
Rotary-Hermetic
1
10.1-66.0
-
Dehumidification
Amps
(Pints/H)
(A)
7.1/6.9
11.6/12.2
Power Inputs
Outdoor Sound Rating(bels)
(W)
2,440/2,380
7.6
OUTDOOR FAN - TYPE
Dia. (in.) - No. used
Type Drive - No. speeds
No. Poles - RPM (High)
No. Motors - HP
Propeller
18-3/32 - 1
Direct – 3 (AUTO)
6 - 879
1 - 1/7
1,900
FEATURE
Controls
Microprocessor
LCD Wireless type
IC Thermostat
ON/OFF, 24 hours
Built-In
Remote Controller
Temperature Control
Timer
Night Setback
Air Louver
CFM (High)
F.L. Amps. (A)
1.2
OUTDOOR COIL - TYPE
Fin Type - Pipe Type
Rows - F.P.I.
Face Area (sq.ft.)
Tube Size (in.)
Aluminum Fin & Copper Pipe
Slit Plate - Inner Riffled
2 - 14.1
6.63
3/8
(Horizontal)
(Vertical)
-
Automatic
Built-In
N/A
Power Failure Automatic Restart
Self Diagnosis
INDOOR FAN - TYPE
Dia. & Length (in.) - No. used 19-9/32 -1
Turbo
OPTION
No. speeds
3 & Auto
6-451
1 - 1/25
540/460/360
0.6
Refrigerant Line Set
AP2710BH
AP2715BH
(30 ft)
(50 ft)
No. Poles -RPM (High)
No. Motors - HP
CFM (HI/MED/LOW)
F.L. Amps (A)
Low Ambient Control
Fresh Air Intake
Available
CMB-GSJ80T
Available
Available
N/A
Available
RCS5PS4B
RCS-102WD/RCS-302WD
Central Remote ON-OFF Control
Airduct Extension
Indoor Frame Extension
Condensate Drain Pump
Non-Removable Remo-con Bracket
Wired Remote Controller
INDOOR COIL - TYPE
Fin Type - Pipe type
Rows - F.P.I.
Face Area (sq. ft.)
Tube Size (in.)
Aluminum Fin & Copper Pipe
CorrugatedPlate - Inner Riffled
2 - 14.9
3.18
3/8
Drain Connection Size (in.)
1-1/4
OPERATING RANGE
REFRIGERANT
Lbs. - R22 (O.D. Unit)
Control
R22
5.5
Capillary Tube
Cooling
Indoor Air
Outdoor Air
Intake Temp.
115F DB
Intake Temp.
95F DB/71F WB
67F DB/57F WB
Connection
Line Length, Max (ft.)
Lift difference, Max (ft.)
Flare
132
82
Maximum
Minimum
67F DB
Line Size - in. O.D. Discharge 1/4
Line Size - in. O.D. Suction
3/4
CERTIFICATION
DIMENSIONS (in.)
H
x
W
x
D
Indoor Unit -Uncrated 12-29/32 x 33-27/32 x 33-27/32
-Crated
11-6/32 x 32-14/32 x 32-25/32 (Indoor unit)
4-3/32 x 38-2/32 x 39-11/32 (Indoor Grille)
Outdoor Unit –Uncrate 28-15/16 x 37
x 13-3/8
-Crated
32-17/32 x 40
x 16-12/32
WEIGHT
Net
INDOOR
60.0
OUTDOOR
152.0
24XS3 2 A
(lbs.)
Shipping (lbs.)
57.0/18.0(Grille)
168.0
Shipping Volume (cu.ft.) 6.9/ 3.5 (Grille)
12.3
Download from Www.Somanuals.com. All Manuals Search And Download.