HOW THEY WORK
When power is applied to the magnetic lock, it turns on the unit's powerful built-
in electromagnet. This electromagnet is attracted to the steel armature plate
which is mounted on a door, holding the door fast against unauthorized entry.
When power to the magnetic lock is turned off, the electromagnet releases the
armature plate, allowing the door to open.
SPECIFICATIONS
E-941SA-600
12VDC/24VDC
E-941SA-300
12VDC
E-941SA-1200
12VDC/24VDC
Power
Magnet Size
97/8 x 11/16 x 15/8 in.
(250 x 27 x 42 mm)
71/4 x 1/2 x 11/2 in.
(185 x 12 x 38 mm)
600 lb. (272kg)
500mA @ 12VDC
250mA @ 24VDC
± 10%
63/4 x 15/16 x 11/4 in.
(170 x 23 x 32 mm)
6 x 3/8 x 11/4 in.
10½ x 15/8 x 25/8 in.
(268 x 42 x 67 mm)
71/4 x 5/8 x 23/8 in.
(185 x 16 x 61 mm)
1200 lb. (545kg)
500mA @ 12VDC
250mA @ 24VDC
Armature Size
(152 x 10 x 32 mm)
300 lb. (136kg)
315mA @ 12VDC
Holding Force
Current Drain
Voltage Tolerance ± 10%
± 10%
Housing
Aluminum
Aluminum
Aluminum
Temperature
14° ~ 131°F
(-10° ~ 55°C)
11 lb. (5.0kg)
UL, CUL, CE
14° ~ 131°F
14° ~ 131°F
(-10° ~ 55°C)
2 lb. 13.5oz. (1.29kg.)
CE
(-10° ~ 55°C)
4 lb. 6oz. (2.0kg.)
UL, CUL, CE
Weight
Certifications
Download from Www.Somanuals.com. All Manuals Search And Download.
ELECTROMAGNETIC LOCK Installation Manual
FIG.
1
For Inswing Doors
Filler
Plate*
Standard
Mounting
*Note: may require more
than one filler plate.
"Z"
Bracket
"L" Bracket
(Z/L brackets are not available for E-941SA-300.)
Steel and
Steel and
Rubber
washers
(as
Steel and
Rubber washers
(as needed)
FIG.
2
Rubber washers
(as needed)
Sexnut tube
Armature
needed)
Sexnut
bolt
Armature
Screw
Sexnut
bolt
Armature
Screw
Armature Screw
Armature
Drill a 8mm
hole thru door
Armature
This side drill
16mm only
Drill 12.7mm
(1/2")
Drill a 8mm
hole thru door
Tap M8 x 1.25 Thread
HOLLOW METAL DOOR
SOLID CORE DOOR
REINFORCED DOOR
Drill an 8mm hole thru door. From sexnut
bolt side only, enlarge the 8mm hole to
16mm.
Drill an 8mm hole thru door. From sexnut
bolt side of door, drill 12.7mm (1/2") hole,
25mm (1") in depth.
Drill a 6.8mm dia. hole and tap for
M8 x 1.25 thread.
(E-941SA-600 &
E-941SA-1200 only)
FIG. 3
Power Cable
Voltage Selection
12VDC
Magnet set for 12VDC
operation as supplied
from factory.
To Magnet
-
E-941SA-600
+
ENFORCER
Control
Device
24VDC
Position a jumper over the
two middle pins for 24VDC
operation.
Power
Supply
+
-
R E C R O E N F
Power Cable
To Magnet
E-941SA-1200
Voltage Selection
12VDC
Magnet set for 12VDC
operation as supplied
from factory.
Control
Device
+ Power
INPUT
POWER
Supply
-
24VDC
Position a jumper over the
two middle pins for 24VDC
operation.
+
-
Important note:
Check jumper settings before connecting the
lock to the 24VDC input power. Damage to the
lock may result from incorrect jumper settings.
Page 3
Download from Www.Somanuals.com. All Manuals Search And Download.
ELECTROMAGNETIC LOCK Installation Manual
TROUBLESHOOTING
Problem:
Possible cause: Solutions:
Door does not lock
No power
• Check to make sure the wires are
securely tightened to the terminal block
• Check that the power supply is connected
and operating
• Make sure the lock switch is wired
correctly
Door locks, but can be
easily forced open
Poor contact between
electromagnet and
armature plate
• Make sure the electromagnet and
armature plate are properly aligned
• Make sure the contact surfaces of the
electromagnet and armature plate are
clean and free from rust
Incorrect voltage
setting
• Check the power leads with a meter, and
make sure 12VDC or 24VDC is present
Delay in door releasing
A secondary diode was • The electromagnet is fitted with a metal
installed across the
electromagnet
oxide varistor to prevent interference, so
do not install a secondary diode
REGULAR MAINTENANCE
• Clean the contact surfaces of the electromagnet or armature plate with a soft cloth and non-
abrasive, non-corrosive cleaner.
• Apply a light coat of a silicon lubricant to prevent rust. Wipe away the excess.
• Check that the armature plate is securely attached to the door, yet can pivot slightly around the
armature screw.
• Check that the electromagnet is securely attached to the door frame.
UL CERTIFICATION
E-941SA-600 and E-941SA-1200 electromagnetic locks conform to UL/10B “Fire Tests of Door
Assemblies” and UL/10C “Positive Pressure Fire Tests of Door Assemblies” for swinging door
assemblies. They are also classified in accordance with the Uniform Building Code standard 7-2.
WARRANTY: ENFORCER Electromagnetic Locks are warranted against defects in
material and workmanship while used in normal service for a period of one (1) year from the
date of sale to the original customer. Our obligation is limited to the repair or replacement of any
defective part if the unit is returned, transportation pre-paid, to SECO-LARM.
NOTICE
The information and specifications printed in this manual are current at the time of publication.
However, the SECO-LARM policy is one of continual development and improvement. For this reason,
SECO-LARM reserves the right to change specifications without notice. SECO-LARM is also not
responsible for misprints or typographical errors.
Copyright © 2003 SECO-LARM U.S.A., Inc. All rights reserved. This material may not be reproduced
or copied, in whole or in part, without the written permission of SECO-LARM.
SECO-LARM® U.S.A., Inc.
16842 Millikan Avenue, Irvine, CA 92606
Tel: 800-662-0800 / 949-261-2999 Fax: 949-261-7326
®
E-mail: sales seco-larm.com
PITGW1
E-941SAd.pmd
@
Page 4
SECO-LARM U.S.A., Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
ELECTROMAGNETIC LOCK Installation Manual
Page 5
Download from Www.Somanuals.com. All Manuals Search And Download.
|