Rheem Water Heater Commercial Power Direct Vent Water heater User Guide |
Commercial Power Direct Vent Water heater
USE & CARE mANUAl
WiTh iNSTAllATiON iNSTRUCTiONS FORThE CONTRACTOR
mUlTi-FlUE COmmERCiAl mODElS
S
I
G
N
D
R
T
E
I
®
CERTIFIED
R
Recognize this symbol as an indication of important
Do Not Destroy this manual. Please read carefully and
!
!
!
Safety information!
keep in a safe place for Future Reference.
NOTiCE:This water heater is designed for use in a commercial application and the installation and maintenance of it should be per-
formed by a qualified, licensed service personnel. if the foregoing assumption is not appropriate, then we recommend that you obtain
and retain our Residential Use & Care manual.
CAliFORNiA PROPOSiTiON 65WARNiNg:This product contains chemicals known to the State of California to cause cancer, birth
defects or other reproductive harm.
!
WARNiNg: if the information in these instructions are not followed exactly, a fire or explosion may result
causing property damage, personal injury or death.
!
!
immediately call your gas supplier from a neighbor's
FORYOUR SAFETY!
•
•
•
phone. Follow the gas supplier's instructions.
— Do not store or use gasoline or other flammable
vapors or liquids or other combustible materials in
the vicinity of this or any other appliance. To do so
may result in an explosion or fire.
if you cannot reach your gas supplier, call the fire
department.
Do not return to your building until authorized by
the gas supplier or fire department.
— WhATTO DO iFYOU SmEll gAS
— improper installation, adjustment, alteration, service
or maintenance can cause injury, property dam-
age or death. Refer to this manual. installation and
service must be performed by a qualified installer,
service agency or the gas supplier.
Do not try to light any appliance.
•
•
Do not touch any electrical switch; do not use any
phone in your building.
AP13463-3 (02/07)
Printed in USA
Download from Www.Somanuals.com. All Manuals Search And Download.
!
general Safety Precautions
To meet commercial water use needs, the thermostat on this water
heater is adjustable up to 180°F. however, water temperatures over
125°F. can cause severe burns instantly or death from scalds.This
is the preferred starting point for setting the control for supplying
general purpose hot water.
The following chart details the relationship of water temperature
and time with regard to scald injury and may be used as a guide in
determining the safest water temperature for your applications.
Temperature
120° F
125° F
130° F
135° F
140° F
145° F
150° F
155° F
Time to Produce Serious Burn
More than 5 minutes
11/2 to 2 minutes
Safety and energy conservation are factors to be considered when
setting the water temperature on the thermostat. The most energy
efficient operation will result when the temperature setting is the
lowest that satisfies the needs consistent with the application.
About 30 seconds
About 10 seconds
Less than 5 seconds
Less than 3 seconds
About 11/2 seconds
About 1 second
Table courtesy of Shriners Burn Institute
!
D A N G E R
TimE / TEmPERATURE RElATiONShiPS iN SCAlDS
The temperature of the water in the heater can be regulated by
setting the temperature dial on front of the thermostat.To comply
with safety regulations the thermostat was set at its lowest setting
before water heater was shipped from the factory.The illustration
below illustrates the thermostat and how to adjust the water tem-
perature.
HOT
BURN
F
To adjust the water temperature, insert a small straight
screwdriver into slotted screw in hole in front of ther-
mostat and turn wheel to desired setting. Thermostat
is adjustable up to 180º F.
Water temperature over 125°F can
cause severe burns instantly or
death from scalds.
CAUTiON!! - hotter water increases the risk of SCAlDiNg!
Children, disabled and elderly are
at highest risk of being scalded.
THERMOSTAT
See instruction manual before
setting temperature at water
heater.
White-Rodgers
honeywell
NOTiCE: Each water heater will contain one (1) of the above ther-
mostats. Refer to actual unit to determine which one.
Feel water before bathing or
showering.
DANGER
Temperature limiting valves are
available, see manual.
hotter water increases the Potential for hotWater SCAlDS.
NOTiCE: mixing valves are available for reducing point of use
water temperature by mixing and cold water in branch water lines
Contact a licensed plumber or the local plumbing authority for
further information.
maximum water temperatures occur just after burner has shut off.
To find hot water temperature being delivered, turn on a hot water
faucet and place a thermometer in the hot water stream and read
the thermometer.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
general Safety Precautions
!
Be sure to read and understand the entire Use & Care Manual before attempting to install or operate this water heater. Pay particular attention
to the following General Safety Precautions. Failure to follow these warnings could result in a fire or explosion, causing property damage, bodily
injury or death . Should you have any problems understanding the instructions in this manual, STOP, and get help from a qualified installer or
service technician or the gas supplier.
DANGER
WARNING
!
liQUEFiED PETROlEUm mODElS — Propane, or lP gas,
gasoline, as well as other flammable materials and liquids
(adhesives, solvents, etc.), and the vapors they produce,
are extremely dangerous. DO NOT handle, use or store
gasoline or other flammable or combustible materials any-
where near or in the vicinity of a water heater. Be sure to
read and follow the warning label pictured below and other
labels on the water heater, as well as the warnings printed
in this manual. Failure to do so can result in property dam-
age, bodily injury, or death.
must be used with great caution.
• it is heavier than air and will collect first in lower areas
making it hard to detect at nose level.
•
make sure to look and smell for lP leaks before
attempting to light appliance. Use a soapy solution to
check all gas fittings and connections. Bubbling at a
connection indicates a leak that must be corrected.
When smelling to detect an lP leak, be sure to sniff
near the floor too.
• gas detectors are recommended in lP applications
and their installation should be in accordance with the
manufacturer's recommendations and/or local laws,
rules, regulations or customs.
DANGER
• it is recommended that more than one method be used
to detect leaks in lP applications.
Failure to properly vent the water heater to the outdoors
as outlined in the Venting Section of this manual can result
in unsafe operation of the water heater. To avoid the risk
of fire, explosion, or asphyxiation from carbon monoxide,
never operate this water heater unless it is properly vented
and has an adequate air supply for proper operation. Be
sure to inspect the vent system for proper installation at
initial start-up; and at least annually thereafter. Refer to
maintenance section of this manual for more information
regarding vent system inspections.
iF lP gAS iS PRESENT OR SUSPECTED:
• DO NOT attempt to find the cause yourself;
• DO NOT try to light any appliance;
• DO NOT touch any electrical switch;
• DO NOT use any phone in your building.
• leave the house immediately and make sure your fam-
ily and pets leave also.
• leave the doors open for ventilation and contact the
gas supplier, a qualified service agency or the fire
department.
• Keep the area clear until the service call has been
made, the leak is corrected, and a qualified agency has
determined the area to be safe.
!
D A N G E R
WARNING
!
Both lP and natural gas have an odorant added to help
detection. Some people may not physically be able to
smell or recognize this odorant. if unsure or unfamiliar
about the smell associated with lP or natural gas, ask the
gas supplier. Other conditions, such as "Odorant Fade",
which causes the odorant to "fade", or diminish in inten-
sity can also hide or camouflage a gas leak.
FLAMMABLES
FlammableVapors
!
Vapors from flammable
liquids will explode and
catch fire causing death or
severe burns.
Do not use or store flammable
products such as gasoline,
solvents or adhesives in the
same room or area near the
water heater.
Water heater has a main
burner and pilot flame.
The pilot flame:
1. which can come on at
any time and
DANGER
2. will ignite flammable
vapors.
Water heaters utilizing liquefied Petroleum gas (lP) are
different from natural gas models. A natural gas heater will
not function safely on lP gas and vice versa. No attempt
should ever be made to convert a heater from natural gas
to lP gas. To avoid possible equipment damage, personal
injury or fire: DO NOT connect this water heater to a fuel
type not in accordance with unit data plate. Propane for
propane units. Natural gas for natural gas units. These
units are not certified for any other type fuel.
Vapors:
1. cannot be seen,
2. are heavier than air,
3. go a long way on the
floor and
Keep flammable products:
1. far away from heater,
2. in approved containers,
3. tightly closed and
4. can be carried from
other rooms to the pilot
flame by air currents.
4. out of children's reach.
Installation:
are at least 18" above the
floor.This will reduce, but not
eliminate, the risk of vapors
being ignited by the main
burner or pilot flame.
Do not install water heater
where flammable products will
be stored or used unless the
main burner and pilot flames
WARNING
!
lP appliances should not be installed below-grade (for
example, in a basement) if such installation is prohibited
by federal, state and/or local laws, rules, regulations or cus-
toms.
Read and follow water heater warnings and instructions.If owners
manual is missing,contact the retailer or manufacturer.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
introduction
C. All models are certified for installation on combustible floors and in
WARNING
!
alcoves. The minimum side and top clearance to walls and ceiling for
providing protection of combustible materials are shown on the water
heater’s rating label. A front clearance of 18 inches (46 cm) should be
provided for adequate inspection and servicing.
Read and Review this entire manual with special emphasis
on the Venting Sections (Pages 8-12) and Operation Section
(Pages 14-17) prior to any installation work.
LOCAL INSTALLATION REGULATIONS
If the water heater must be installed on carpeting, place a metal or
wood panel beneath water heater extending beyond its full width and
depth at least 3 inches (7.6 cm) in all directions. If the water heater is
installed in an alcove, the entire floor must be covered by the panel.
The water heater should not be located in an area where leakage of
the tank or connections will result in damage to the area adjacent
This water heater must be installed in accordance with these instructions,
local codes, utility company requirements and/or, in the absence of local
codes, the latest edition of the National Fuel Gas Code, ANSI Z223.1 in
the United States, or CGA/CAN B149 Installation Codes in Canada.
LOCATION
A. This water heater is of the direct vent design. All air for combustion
and all products of combustion are routed through the venting system,
directly from and to the outside of the building.
CAUTION
to it or to lower floors of the structure.When such areas cannot be
avoided, it is recommended that a suitable catch pan, adequately
drained, be installed under the water heater. The pan mUST NOT
restrict the flow of combustion air flow to bottom of water heater.
The water heater should be installed in a clean, dry location as close
as practical to the gas vent terminals. Long hot water lines should be
insulated to conserve water and energy. The water heater and water
lines should be protected from exposure to freezing temperatures.
NOTICE: Auxiliary catch pan installation MUST conform to the ap-
plicable local codes.
B. A gas fired water heater should not be installed in a space where liquids
which give off flammable vapors are to be used or stored. Such liquids
include gasoline, LP gas (butane and propane), paint or adhesives and
their thinners, solvents or removers. Because of natural air movement
in a room or other enclosed space, flammable vapors can be carried
some distance from where their liquids are being used or stored. The
open flame of the water heater’s intermittent pilot or main burner can
ignite these vapors causing an explosion or fire which may result in
severe burns or death to those in range, as well as property damage.
For these reasons, installation of a gas fired water heater in a garage
is not desirable.
D. RESTAURANTS — If the water heater is to be installed in a restau-
rant or other location where the floor is frequently cleaned, it must be
elevated to provide at least six inches (15 cm) of clearance from the
floor to comply with NSF International recommendations.
E. CORROSIVE ATMOSPHERES — The heater should not be installed
near an air supply containing halogenated hydrocarbons. For example,
the air in beauty shops, dry cleaning establishments, photo processing
labs, and storage areas for liquid and powdered bleaches or swim pool
chemicals often contain such hydrocarbons.The air there may be safe
to breathe, but when it passes through a gas flame, corrosive elements
are released that will shorten the life of any gas burning appliance.
Propellants from common spray cans or gas leaks from refrigeration
equipment are highly corrosive after passing through a flame.The lim-
ited warranty is voided when failure of water heater is due to a corrosive
atmosphere. (Refer to the Certificate of Limited Warranty for complete
terms and conditions.)
WARNING
!
if a location in a garage is the only alternative, the gas water heater
should be installed so that the open flame of the pilot and main
burner are no less than 18 inches above the garage floor.The water
heater must be located or protected so it is not subject to physical
damage by moving vehicles or area flooding. Raising the gas fired
water heater will reduce BUT NOT eliminate the possibility of light-
ing the vapor of any flammable liquids which may be improperly
stored or accidentally spilled.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
installation
heater. If special instructions are required for any specific water heater,
they will be included in the bag.
WARNING
!
Cap or plug unused connections. Use only clean, new galvanized steel,
copper or approved plastic pipe for water connections. Local codes
or regulations shall govern the exact type of material to be used. The
installation of unions on the inlet and outlet water lines and a shut-off
valve in at least the cold water inlet line is recommended, so the water
heater may be easily disconnected for servicing. Dielectric unions are
not required for protection of water heater.
The manufacturer’s warranty does not cover any damage or defect
caused by installation, or attachment, or use of any special attach-
ment such as energy saving devices (other than those authorized
by the manufacturer) into, onto, or in conjunction with the water
heater. The use of such unauthorized devices may shorten the
life of the water heater and may endanger life and property. The
manufacturer disclaims any responsibility for such loss or injury
resulting from the use of such unauthorized devices.
When this water heater is supplying general purpose hot water require-
ments for use by individuals, a thermostatically controlled mixing valve
is recommended to reduce the risk of scald injury. Contact a licensed
plumber or the local plumbing authority for further information.
1. INSPECT SHIPMENT — for possible damage. The manufacturer’s
responsibility ceases upon delivery of goods to the carrier in good
condition. Any claims for damage, shortage in shipments, or non de-
livery must be filed immediately against carrier by consignee.
Thermometer(s) should be installed so that they indicate the tempera-
ture of the water at or near the outlet of the water heater and storage
tank(s) if provided. See Fig. 4 on page 7.
2. THERMAL EXPANSION — Determine if a check valve exists in the
inlet water line. It may have been installed in the cold water line as a
separate back flow preventer, or it may be part of a pressure reduc-
ing valve, water meter or water softener. A check valve located in
the cold water inlet line can cause what is referred to as a ”closed
water system”. A cold water inlet line with no check valve or back
flow prevention device is referred to as an ”open” water system.
3. RELIEF VALVE — A new factory installed combination pressure and
temperature relief valve, complying with the Standard for Relief Valves
and Automatic Gas Shutoff Devices for Hot Water Supply Systems,
ANSI Z21.22, or Standard CAN1-4.4, Temperature, Pressure, Tempera-
ture and Pressure Relief Valves and Vacuum Relief Valves is provided
with the water heater. No valve is to be placed between the relief valve
and the water heater. For a circulating tank installation, the separate
storage tank(s) must have similar protection.The pressure rating of the
relief valve must not exceed 150 psi (160 psi for ASME models), the
maximum working pressure as marked on front of the water heater.
As water is heated, it expands in volume and creates an increase
in the pressure within the water system. This action is referred to as
”thermal expansion”. In an ”open” water system, expanding water
which exceeds the capacity of the water heater flows back into the
city main where the pressure is easily dissipated.
The Btu/h rating of the relief valve must equal or exceed the Btu/h input
of the water heater as marked on its rating plate.
A ”closed water system”, however, prevents the expanding water
from flowing back into the main supply line, and the result of ”thermal
expansion” can create a rapid, and dangerous pressure increase in
the water heater and system piping.This rapid pressure increase can
quickly reach the safety setting of the relief valve, causing it to oper-
ate during each heating cycle. Thermal expansion, and the resulting
rapid, and repeated expansion and contraction of components in the
water heater and piping system can cause premature failure of the
relief valve, and possibly the heater itself. Replacing the relief valve
will not correct the problem!
Connect the outlet of the relief valve to a suitable open drain. The
discharge line must pitch downward from the valve to allow complete
draining (by gravity) of the relief valve and discharge line, and be no
smaller than the outlet of the valve. The end of the discharge line
should not be threaded or concealed and should be protected from
freezing. No valve of any type, restriction or reducer coupling should be
installed in the discharge line. Local codes shall govern the installation
of relief valves.
4. GAS SUPPLY — The inlet gas pressure to the water heater must not
exceed 10.5” w.c. (2.6 kPa) for Natural gas. For purposes of input adjust-
ment, the minimum inlet gas pressure (with main burner on) is shown on
the rating plate. Check to see if high or low gas pressure is present and
then contact the gas company for correction.
The suggested method of controlling thermal expansion is to install an
expansion tank in the cold water line between the water heater and the
check valve.The expansion tank is designed with an air cushion built in
that compresses as the system pressure increases, thereby relieving
the over pressure condition and eliminating the repeated operation of
the relief valve. Other methods of controlling thermal expansion are also
available. Contact your installing contractor, water supplier, or plumbing
inspector for additional information regarding this subject.
The gas line should be of adequate size to prevent undue pressure
drop. Sizing based upon Table 1 (on pg. 13) is recommended. No ad-
ditional allowance is necessary for an ordinary number of fittings.
A ground joint union and manual shutoff valve should be installed in
the gas line near the water heater so that the burner assembly may
be easily removed. The shut-off valve must be readily accessible for
turning on or off. See Fig. 4 on page 7.
If a recirculation line is installed, the return connection should be made
to a tee close to the inlet connection on the water heater. A check valve
should always be installed in the recirculation line to prevent cold water
from entering.
A sediment trap must be installed at the bottom of the gas line. See
Fig. 4 on page 7.
WATER CONNECTIONS — This water heater may be connected indi-
vidually, in multiples with others, or with an external hot water storage
tank.
LEAK TESTING — The water heater and its gas connections MUST
be leak tested at normal operating pressure before it is placed in op-
eration. Turn ON the manual gas shut-off valve near the water heater.
Use a soapy water solution to test for gas leaks at all connections and
fittings. Bubbles indicate a gas leak that must be corrected.The water
heater factory connections to the gas valve should also be leak tested
after placing the water heater in operation.
Inlet water connections are made to the lower coupling on the heater,
and outlet water connections are made to the upper coupling.
Each water heater is supplied with the necessary components (Diffuser
tubes) to make the water connections that will ensure proper perfor-
mance. The components are supplied in a bag attached to the water
6
Download from Www.Somanuals.com. All Manuals Search And Download.
installation
7
Download from Www.Somanuals.com. All Manuals Search And Download.
installation
The unit may be vented horizontally through a wall or vertically through
WARNING
!
the roof. Pipe runs must be adequately supported along both vertical
and horizontal runs. Maximum unsupported span is recommended to
be no more than 4 feet. It is imperative that the first hanger be located
on the horizontal run immediately adjacent to the first 90-degree elbow
from the vertical rise or at the blower outlet in the case of a horizontal
blower position. Support method used should isolate the vent pipe from
floor joists or other structural members to help prevent the transmission
of noise and vibration. Do not support, pin or otherwise secure the vent-
ing system in a way that restricts the normal thermal expansion and
contraction of the chosen venting material.
NEVER use open flame to test for gas leaks, as bodily injury or
property damage could result.
PRESSURE TESTING THE GAS SUPPLY SYSTEM — The water
heater and its manual gas shut-off valve MUST be disconnect-
ed from the gas supply piping system during any high pressure
testing of that system at pressures in excess of 1/2 psi
(14” w.c. / 3.5 kPa).
The water heater MUST be isolated from the gas piping system
by closing the manual gas shut-off valve during any pressure test-
ing of the gas supply piping at pressures equal to or less than
1/2 psi (14” w.c. / 3.5 kPa).
If the water heater is being installed as a replacement for an existing
power vented water heater, a thorough inspection of the existing venting
system must be performed prior to any installation work. Verify that the
correct materials, as detailed above have been used, and that the mini-
mum or maximum vent length and terminal locations as detailed in this
manual have been met. Carefully inspect the entire venting system for
any signs of cracks or fractures, particularly at the joints between elbows
or other fittings and the straight runs of vent pipe. Check the system for
signs of sagging or other stresses in the joints as a result of misalignment
of any components in the system. If any of these conditions are found,
they must be corrected in accordance with the venting instructions in this
manual before completing the installation and putting the water heater
into service.
5. VENTING —
WARNING
!
The water heater must be vented to the outdoors as described
in these instructions. DO NOT connect this water heater to an
existing Vent or Chimney it must be vented separately from all
other appliances.
VENT PIPE CONNECTION —
WARNING
!
Outlet
Vent Connection
Failure to properly vent the water heater to the outdoors as outlined
above and in the following section can result in unsafe operation of
the water heater causing bodily injury, explosion, fire or death.
Inlet
Vent Connection
WARNING
!
To avoid the risk of fire, explosion or asphyxiation from carbon
monoxide, NEVER operate this water heater unless it is properly
vented and has an adequate air supply for proper operation. The
vent pipe must overlap a minimum of ½" on each connection. it is
important that the vent pipe engages fully into any pipe fitting and
be kept in that position until the adhesive has fully cured. DO NOT
drill or punch holes in the plastic pipe or fittings.
Figure 5.
—
Vent Pipe Connection locations
The blower assembly is preinstalled at the factory, so all that is required
for connecting the vent system is attaching the vent pipe to the blower
and the PVC Tee. Before starting the vent installation, careful planning
should be given to the routing and termination of the vent pipe.The length
of the vent pipe (inlet and outlet) should be kept to a minimum. Also, see
page 10 & 12 for vent terminal placement.The GP100-150 & GP100-200
model can be vented using either 3 inch or 4 inch Schedule 40 PVC pipe
and fittings.
NOTICE: This unit can be vented using only the following
recommended pipe material. Use only 3- or 4-inch diameter pipe.
PVC (Schedule 40, ASTM D-1785)
CPVC (Schedule 40, ASTM F-441)
ABS (Schedule 40, ASTM D-2661)
To use 3 inch PVC, you can connect directly to the blower outlet (rubber
coupling provided for outlet connection) and PVC Tee. Make sure that
clamps on rubber coupling are tight, after the pipe is installed. The inlet
vent pipe should be cemented into the PVC Tee.
The fittings, other than the VENT TERMINAL, should be equiva-
lent to the following:
PVC (Schedule 40 DWV, ASTM D-2665)
CPVC (Schedule 40 DWV, ASTM F-438)
ABS (Schedule 40 DWV, ASTM D-2661)
If 4 inch PVC pipe is going to be used, then it will be necessary to have
a short piece ( at least 3 inches long ) of 3 inch PVC pipe to join into the
coupling and tee. Then a 4 X 3 reducer would need to be joined to the
short piece of pipe, so that the 4 inch pipe could be used.The 4 inch pipe
will then need to be stepped back down, using a 4 X 3 reducer, to 3 inch
PVC. To install the vent terminals, a short length of 3 inch (maximum of
16 inches long) pipe will need to be used. (Refer to Figure 9b on page
10.)
The GP100-250 model can only be vented using 4 inch Schedule 40 PVC
pipe and fittings. The 4 inch pipe can be connected directly to the blower
coupling and 4 inch tee.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
miNimUm AND mAximUm VENT lENgThS
Charts are for installation from 0 - 2000 ft. elevation ONLY. (Please see supplement sheet for installations above 2000 feet.)
NOTICE: Be sure to mount inlet vent terminal 6 inches higher than the outlet vent terminal. Vent terminals need to be a minimum of 7 inches
(center to center) horizontally apart and a maximum of 24 inches apart.
gP100-250
Venting Information for 4” Vents
gP100-150 & gP100-200
Venting Information for 3” Vents
Number of 90º Elbows with
Vent Terminal
Minimum Pipe Maximum
Length Required Pipe Length
Number of 90º Elbows with
Vent Terminal
Minimum Pipe Maximum
Length equired Pipe Length
Number of
45º Elbows
Number of
45º Elbows
(Ft)
10.0
7.5
5.0
2.5
5.0
2.5
5.0
2.5
(Ft)
Inlet Vent
Outlet Vent
One (1)
(Ft)
5.0
2.5
5.0
2.5
5.0
2.5
5.0
2.5
(Ft)
Inlet Vent
Outlet Vent
One (1)
One (1)
One (1)
Two (2)
None
One (1)
None
45.0
42.5
40.0
37.5
35.0
32.5
30.0
27.5
One (1)
One (1)
Two (2)
None
One (1)
None
40.0
37.5
35.0
32.5
30.0
27.5
25.0
22.5
One (1)
Two (2)
One (1)
Two (2)
Two (2)
Two (2)
One (1)
None
Two (2)
Two (2)
One (1)
None
Three (3)
Three (3)
Four (4)
Four (4)
Three (3)
Three (3)
Four (4)
Four (4)
Three (3)
Three (3)
Four (4)
Four (4)
Three (3)
Three (3)
Four (4)
Four (4)
One (1)
None
One (1)
None
One (1)
Vent lengths for the inlet and the outlet pipes should not have a
difference of more than five (5) equivalent feet.
One (1)
Vent lengths for the inlet and the outlet pipes should not have a dif-
ference of more than five (5) equivalent feet.
GP100-250 can only be vented with four (4) inch PVC pipe and fit-
tings. Use only the vent terminals supplied withthe water heater
Venting Information for 4” Vents
HORIZONTAL VENT TERMINAL LOCATION - The location of the
vent terminal depends on the minimum clearances and consider-
ations shown in the charts on pages 11 and 12..
Number of 90º Elbows with
Vent Terminal
Minimum Pipe Maximum
Length Required Pipe Length
Number of
45º Elbows
(Ft)
10.0
9.5
5.0
2.5
5.0
2.5
5.0
2.5
(Ft)
Inlet Vent
One (1)
Outlet Vent
One (1)
None
One (1)
None
50.0
47.5
45.0
42.5
40.0
37.5
35.0
32.5
One (1)
Two (2)
One (1)
Two (2)
Two (2)
Two (2)
One (1)
None
Three (3)
Three (3)
Four (4)
Four (4)
Three (3)
Three (3)
Four (4)
Four (4)
One (1)
None
One (1)
Vent lengths for the inlet and the outlet pipes should not have a differ-
ence of more than five (5) equivalent feet.
NOTICE: 3” and 4” vent pipe should not be mixed, other than
to reduce the 4” vent for the 3” PVC Vent Terminal. This unit
is supplied with two (2) 3-inch Schedule 40 PVC 45º vent
terminals.
The 4” vent pipe can use up to 16 inches of 3” PVC, preceding
the vent terminal. This unit uses the same vent terminals (sup-
plied with the unit) for both 3” and 4” pipe. A 4” to 3” reducer
will be required to go from 4” to 3” pipe.
ꢀ
Download from Www.Somanuals.com. All Manuals Search And Download.
installation
gP100-150 & gP100-200
Additional Considerations (See Figure 9)
Sheet Metal Shield on Brick or
Masonry Walls
1. Do Not install vent terminal under any patio or deck.
§
Mortar or
Silicone Caulk
§
§
2. To help prevent moisture from freezing on walls and
under eaves, do not locate vent terminal on the side of a
building with prevailing winter winds.
3” Pipe
Coupling
3”Vent
Pipe
Vent Terminal with 1/2
Mesh Protective
Screen Inside
"
§
§
3. Do Not terminate vent pipe directly on brick or masonry
surfaces. Use a rust-resistant sheet metal backing plate
behind vent. (See Figure 9.)
3”Vent
Pipe
3” Pipe
Coupling
4. Do Not locate vent terminal too close to shrubbery,
since flue gases may damage them.
§
§
Outside of
Building Wall
From Water
Heater
5. Caulk all cracks, seams and joints within six (6) feet of
vent terminal.
Figure ꢀa – Typical horizontal 3”Vent installation
6. All painted surfaces should be primed to lessen the
chance of physical damage. Painted surfaces will require
maintenance.
Sheet Metal Shield on Brick or
Masonry Walls
§
Mortar or
Silicone Caulk
§
§
4x3 Reducer
7. Insulate vent pipe exposed to cold conditions (attics,
crawl spaces, etc.) to help prevent moisture from accu-
mulating in vent pipe.
Coupling
4”Vent
Pipe
§
Vent Terminal with 1/2
Mesh Protective
Screen Inside
"
§
4x3 Reducer
Coupling
3”Vent
Pipe
WARNING
!
From
moisture in the flue gas will condense as it leaves the
vent terminal. in cold weather this condensate can
freeze on the exterior wall, under the eaves and on
surrounding objects. Some discoloration to the
exterior of the building is to be expected. however,
improper location or installation can result in se-
vere damage to the structure or exterior finish of the
building.
Water
Heater
§
§
Outside of
Building Wall
Figure ꢀb – Typical horizontal 4”Vent installation
gP100-250
Sheet Metal Shield on Brick or
Masonry Walls
§
Mortar or
Silicone Caulk
§
§
Inlet
4” Pipe
Coupling
Inlet Min. 6”
above
outlet
Short Piece of Vent Pipe
4”Vent
Pipe
Vent Terminal with 1/2
Mesh Protective
Screen Inside
"
§
§
Outlet
4”Vent
Pipe
4” Pipe
Coupling
§
§
Outside of
Building Wall
From Water
Heater
Min. 12" Above Roof
Vent Pipe
Through Roof
Min. 12" Above Anticipated
Snow Level.
Figure ꢀc – Typical horizontal 4”Vent installation
Max. 24" Above Roof
Elbows
(Without Additional Support)
Figure 8 – Vertical Vent Terminal location
HORIZONTAL VENT INSTALLATION – Once the vent terminal
location has been determined, make a hole through the exterior wall to
accommodate the vent pipe.Vent pipe must exit exterior wall horizontally
only. (See Figures 9a and 9b.)
Min. 7”
Max. 24”
Insert a small length of vent pipe through the wall and connect the
coupling as shown in Figure 9. Connect terminal as shown to the vent
pipe on the exterior of the building. Seal any opening around the vent
pipe or fittings with mortar or silicone caulk as shown in Figures 9a and
9b.
Complete the rest of the vent pipe installation to the water
heater’s vent connector fitting on the blower outlet. If
necessary support horizontal run as previously mentioned.
Inlet
Outlet
6” above outlet
Figure 6
10
Download from Www.Somanuals.com. All Manuals Search And Download.
installation
VERTICAL VENT INSTALLATION – Once the vent termi-
3. Maximum twenty-four (24) inches above roof level without
additional support for vent pipe.
nal location has been determined, make a hole through the
roof and interior ceiling to accommodate the vent pipe. Com-
plete the vent pipe installation to the water heater’s vent
connector fitting on the blower outlet. Support vertical or
horizontal runs as previously mentioned.
4. Four (4) feet from any gable, dormer or other roof structure with
building interior access (i.e., vent, window, etc.).
5. Ten (10) feet from any forced air inlet to the building. Any
fresh or make-up air inlet such as a dryer or furnace area is
considered to be a forced air inlet.
Install adequate flashing where the vent pipe passes through the
roof. Determine the vent terminal height and cut vent pipe ac-
cordingly. Refer to Fig. 8 for proper vent terminal height. Connect
vent elbow onto vertical pipe through roof. Connect short piece
6. The inlet is a minimum of six (6) inches vertically above the outlet.
of vent pipe (approximately 3
to the short piece of vent pipe.
"
long) to elbow, then join terminal
7. Terminals are a minimum of seven (7) inches horizontally apart with
a maximum of twenty-four (24) inches.
VERTICAL VENT TERMINAL LOCATION – The location of
vertical vent terminal depends on the following considerations
(see Figure 8):
VENT INSTALLATION – Before proceeding, make certain you
understand the procedure and cautions covered in the section
“Joining Pipes and Fittings.”
1. Minimum twelve (12) inches above roof.
2. Minimum twelve (12) inches above anticipated snow level.
AREA WHERE TERMINAL IS NOT PERMITTED
AIR SUPPLY INLET
VENT TERMINAL
X
V
Horizontal Vent Terminal Location
The following information should be used for determining the proper location of the vent terminal
for direct vent water heaters.
1
2
Canadian Installations
US Installations
A= Clearance above grade, veranda,
porch, deck or balcony.
12 inches (30 cm) above anticipated
snow level.
12 inches (30 cm) above anticipated
snow level.
B= Clearance to window or door that may 6 inches (15 cm) for appliances < 10,000
6 inches (15 cm) for appliances < 10,000
be opened.
Btuh (3 kW), 12 inches (30 cm) for appli- Btuh (3 kW), 9 inches (23 cm) for appli-
ances > 10,000 Btuh (3kW) and < 100,000 ances > 10,000 Btuh (3 kW) and
Btuh (30kW), 36 inches (91 cm) for appli- < 50,000 Btuh (15 kW), 12 inches
ances > 100,000 Btuh (30kW).
(30 cm) for appliances > 50,000 Btuh
(15 kW).
C= Clearance to permanently closed
window.
*
*
D= Vertical Clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (61 cm)
from the center line of the terminal.
3 feet (91 cm)
3 feet (91 cm)
E= Clearance to unventilated soffit.
F= Clearance to outside corner.
G= Clearance to inside corner.
*
*
*
*
18 inches (46 cm)
18 inches (46 cm)
Figure 9 - Horizontal Vent Terminal Location
11
Download from Www.Somanuals.com. All Manuals Search And Download.
1
2
Canadian Installations
US Installations
H = Clearance to each side of center line
extended meter/regulator assembly.
above
3 feet (91 cm) within a height 15 feet (4.57
m) above the meter/regulator assembly.
*
I = Clearance to service regulator vent
outlet.
3 feet (91 cm)
*
J = Clearance to nonmechanical air supply 6 inches (15 cm) for appliances < 10,000
4 feet (1.2 m) below or to side of opening;
Btuh (3 kW), 12 inches (30 cm) for appli- 1 foot (300 mm) above opening.
ances > 10,000 Btuh (3kW) and
< 100,000 Btuh (30kW), 36 inches (91 cm)
inlet to the combustion air inlet to any
building or other appliance.
for appliances > 100,000 Btuh (30kW).
6 feet (1.83 m)
7 feet (2.13 m)
3 feet (91 cm) above if within 10 feet
(3 m) horizontally.
K = Clearance to mechanical air supply
inlet.
L = Clearance above paved side walk or
paved driveway located on public
property.
7 feet (2.13 m)
M = Clearance under veranda, porch, deck
or balcony.
Not Allowed
Not Allowed
1 In accordance with current CAN/CGA-B149 Installation Codes.
2 In accordance with current ANSI Z223.1/ NFPA 54 National Fuel Gas Code.
+ A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
* If clearances are not specified then follow local installation codes and the requirement of the gas supplier.
DRAINING THE CONDENSATE – In certain conditions,
installations in unconditioned space or having long horizontal or vertical
runs may accumulate condensate. In order to prevent condensate from
draining back into the blower, we recommend that it be drained. This
unit is provided with a special fitting on the blower that allows for the
draining of condensate formed in the vent. The drain hose should have
two (2) loops formed, to act as traps. Before operation of the water
heater, both loops should have water placed in them. Support the traps
so that they remain horizontal. Condensate is known to be acidic; refer
to local, state or federal codes for proper handling methods.
PVC materials should use ASTM D-2564 grade cement.
CPVC materials should use ASTM F-493 grade cement.
ABS materials should use ASTM D-2235 grade cement.
Cleaner-Primer and Medium Body Solvent Cement
1. Cut pipe end square, remove jagged edges and burrs. Cham-
fer end of pipe, then clean fitting socket and pipe joint area
of all dirt, grease or moisture.
2. After checking pipe and socket for proper fit, wipe
socket and pipe with cleaner-primer. Apply a liberal coat of
primer to inside surface of socket and outside of pipe. Do not
allow primer to dry before applying cement.
3. Apply a thin coat of cement evenly in the socket. Quickly
apply a heavy coat of cement to the pipe end and in-
sert pipe into fitting with a slight twisting motion until it
bottoms out.
NOTICE: Cement must be fluid; if not, recoat.
Figure 10 - Draining the Condensate
4. Hold the pipe fitting for 30 seconds to prevent the tapered
socket from pushing the pipe out of the fitting.
JOINING PIPES AND FITTINGS – All pipe, fittings, solvent
cement, primers and procedures must conform to Ameri-
can National Standards Institute and American Society for
Testing and Materials (ANSI/ASTM) standards.
5. Wipe all excess cement from the joint with a rag. Allow 15
minutes before handling. Cure time will vary according to fit,
temperature and humidity.
NOTICE: Stir the solvent cement frequently while using. Use
a natural bristle brush or the dauber supplied with the can.
The proper brush size is one inch.
CEMENTING JOINTS – All joints in the vent piping must
be properly sealed and we recommend using the following mate-
rial:
12
Download from Www.Somanuals.com. All Manuals Search And Download.
FOR PROPER iNSTAllATiON:
Avoid skin or eye contact. Observe all cautions
and warnings on material containers.
CAUTION
6. WIRING — A polarized 120V 50/60 Hz power supply, with suitable
disconnect means, must be connected to the black and white leads
provided. The current draw by the Power Direct Vent unit is 1.5 Amps.
The water heater, when installed, must be electrically grounded in ac-
cordance with local codes, or, in the absence of local codes, with the
National Electrical Code, ANSI/NFPA 70 in the United States; or CSA
C22.1 Electrical Code, in Canada. Refer to Fig. 14 on page 26 & 27
of this manual for water heater internal wiring diagrams.
• DO NOT use solvent cement that has become
curdled, lumpy or thickened.
• DO NOT thin solvent cement. Observe shelf
precautions printed on the containers.
• For applications below 32°F use only low
temperature type solvent cement.
• Appropriate solvent and cleaner must be used for
the type of vent pipe used (PVC, CPVC or ABS).
NOTICE: DO NOT use in conjunction with a GFCI.
WARNING
!
DANgER OF FiRE OR BODilY iNJURY – Solvent
cements and primers are highly flammable. Pro-
vide adequate ventilation and do not assemble
near heat source or open flame. Do not smoke.
installation Check list
C. Gas Supply
A. Water Heater Location
❑ Close to area of vent.
❑ Gas line equipped with shut-off valve, union, and sediment
trap/drip leg.
❑ Indoors and protected from freezing temperatures.
❑ Approved pipe joint compound used.
❑ Proper clearance from combustible surfaces observed and
water heater not installed on carpeted floor.
❑ Soap and water solution used to check all connections and
fittings for possible gas leak.
❑ Air supply free of corrosive elements and flammable vapors.
❑ Provisions made to protect area from water damage.
❑ Sufficient room to service heater.
❑ Gas Company inspected installation (if required).
D. Relief Valve
❑ Discharge line run to open drain.
B. Water Supply
❑ Discharge line protected from freezing.
❑ Water heater completely filled with water.
E. Venting
❑ Water heater and piping air vented.
❑ All pipe connections are secure (at blower, vent terminals and for
each pipe joint connection)
❑ Water connections tight and free of leaks.
❑ Vent terminals mounted properly and in correct location.
❑ Condensate tube has water in both loops.
TABlE 1
maximum Capacity of Pipe in Cubic Feet of gas per hour for gas Pressures of
--------0.5 psig or less and a Pressure Drop of 0.3 inch Water Column
Based on a 0.60 Specific gravity Natural gas; if 1.5 Specific gravity l.P. gas is used, multiply capacity by 0.63
Nominal
internal
Diameter
inches
.622
.824
1.04ꢀ
1.380
1.610
2.067
2.46ꢀ
Length of Pipe, Feet
iron Pipe Size,
inches
1/2
3/4
1
1 1/4
1 1/2
2
10
132
278
20
ꢀ2
1ꢀ0
350
730
1,100
2,100 1,650
3,300 2,700
5,ꢀ00 4,700
30
73
152
285
5ꢀ0
8ꢀ0
40
63
130
245
500
760
1,450 1,270
2,300 2,000
4,100 3,600
8,300 7,400
50
56
115
215
440
670
60
50
70
46
80
43
ꢀ0
40
84
160
320
4ꢀ0
ꢀ30
100
38
125
34
150
31
175
28
200
26
105
1ꢀ5
400
610
ꢀ6
ꢀ0
170
350
530
ꢀꢀ0
7ꢀ
72
64
5ꢀ
55
520
180
370
560
150
305
460
870
1,400 1,250
2,500 2,200
5,100 4,500
130
275
410
780
120
250
380
710
1,130
2,000
4,100
110
225
350
650
1,050
1,850
3,800
100
210
320
610
ꢀ80
1,700
3,500
1,050
1,600
3,050
4,800
8,500
1,150 1,050
2 1/2
3
1,850 1,700 1,600 1,500
3,250 3,000 2,800 2,600
6,800 6,200 5,800 5,400
3.068
4.026
4
17,500 12,000 ꢀ,700
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Before operating this water heater, be sure to read and follow the instructions on the label pictured below and all other labels on the water
heater, as well as the warnings printed in this manual. Failure to do so can result in unsafe operation of the water heater resulting in prop-
erty damage, bodily injury, or death. Should you have any problems reading or following the instructions in this manual, STOP, and get
help from a qualified person.
1. LIGHTING PROCEDURE - Lighting procedures are outlined on the label pictured below. This label is also located on the water heater near the thermostat.
NOTICE: The Gas Valve supplied with this water heater may vary from the one pictured on the label below, but the Lighting Instructions are the same for all
types of valves supplied with this model water heater.
FORYOURSAFETYREADBEFOREOPERATING
WARNING: Ifyoudonotfollowtheseinstructionsexactly, afireorexplosionmay
resultcausingpropertydamage,personalinjuryorlossoflife
A. This appliance is equipped with an ignition
device which automatically lights the pilot. DO
NOT try to light the pilot by hand.
B. BEFORE OPERATI NG smell all around the
appliance area for gas. Be sure to smell next to
the floor because some gas is heavier than air
and will settle on the floor.
• If you cannot reach your gas supplier, call
the fire department.
C .Use only your hand to turn the gas control knob.
Never use tools. If the knob will not turn by hand,
don't try to repair it, call a qualified service
technician. Force or attempt to repair may result
in a fire or explosion.
D.Do not use this appliance if any part has been
under water. Immediately call a qualified ser-
vice technician to inspect the appliance and to
replace any part of the control system and any
gas control which has been under water.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions.
OPERATINGINSTRUCTIONS
1. STOP! READ THE SAFETY INFORMATI ON
ABOVE ON THIS LABEL.
5. TURN THE "GAS COCK KNOB" CLOCKWISE
TO "OFF."
2.
USING A SLOTTED SCREW DRIVER — INSERT
INTO TEMPERATURE ADJUSTMENT OPEN-
ING. TURN SCREW CLOCKWISE
LOWEST SETTING
6. WAIT FIVE (5) MINUTES TO CLEAR OUT
ANY GAS. IF YOU THEN SMELL GAS, STOP!
FOLLOW "B" IN THE SAFETY INFORMATI ON
ABOVE ON THIS LABEL. IF YOU DON'T
SMELL GAS, GO TO NEXT STEP.
TO THE
7. TURN "GAS COCK KNOB" COUNTER-
CLOCKWISE
TO "ON".
THERMOSTAT
ON
OFF
8. TURN ON ALL ELECTRIC POWER TO THE
APPLIANCE.
INDEX
GAS COCK
KNOB
TEMPERATURE
ADJUSTMENT
SCREW
GAS VALVE
9. SET THERMOSTAT TO DESIRED SETTING
10. IF THE APPLIANCE WILL NOT OPERATE ,
FOLLOW THE INSTRUCTIONS "TO TURN
OFF GAS TO APPLIANCE" AND CALL YOUR
SERVICE TECHNICIAN OR GAS SUPPLIER.
3. TURN OFF ALL ELECTRIC POWER TO THE
APPLIANCE.
4. THIS APPLIANCE IS EQUIPPED WITH AN IGNITION
DEVICE WHICH AUTOMATICALLY LIGHTS THE
PILOT.DO NOT TRY TO LIGHT THE PILOT BY HAND.
TOTURNOFFGASTOAPPLIANCE
1. SET THE THERMOSTAT TO LOWEST SETTING. 3. TURN THE "GAS COCK KNOB" CLOCKWISE
TO "OFF".
2. TURN OFF ALL ELECTRIC POWER TO THE
APPLIANCE IF SERVICE IS TO BE PERFORMED.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Before operating this water heater, be sure to read and follow the instructions on the label pictured below and all other labels on the water
heater, as well as the warnings printed in this manual. Failure to do so can result in unsafe operation of the water heater resulting in prop-
erty damage, bodily injury, or death. Should you have any problems reading or following the instructions in this manual, STOP, and get
help from a qualified person.
1. LIGHTING PROCEDURE - Lighting procedures are outlined on the label pictured below. This label is also located on the water heater near the thermostat.
NOTICE: The Gas Valve supplied with this water heater may vary from the one pictured on the label below, but the Lighting Instructions are the same for all
types of valves supplied with this model water heater.
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING: If youdonot followthese instructionsexactly, a fire or explosion
may result causing propertydamage, personal injury or loss of life.
A. This appliance is equipped with an ignition
device which automatically lights the pilot. DO
NOT try to light the pilot by hand.
• If you cannot reach your gas supplier, call
the fire department.
B. BEFORE OPERATING smell all around the
appliance area for gas. Be sure to smell next to
the floor because some gas is heavier than air
and will settle on the floor.
C. Use only your handtoturnthe gas controlknob.
Never use tools. If theknobwill not turnbyhand,
don'ttry to repair it, call a qualified service
technician. Force or attemptedrepair may result
in a fire or explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified ser -
vice technician to inspect the appliance and to
replace any part of the control system and any
gas control which has been under water.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance
• Do not touch any electric switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions.
OPERATING INSTRUCTIONS
STOP! READ THE SAFETY INFORMATION
ABOVE ON THIS LABEL.
1.
TURN THE "GAS CONTROL KNOB" CLOCK-
5.
WISE
TO " OFF".
2. REMOVE OUTER COVER. USING A SLOTTED
SCREWDRIVER - INSERT INTO SLOT IN CENTER
OF DIAL. TURN DIAL COUNTERCLOCKWISE
6. WAIT FIVE (5) MINUTES TO CLEAR OUT ANY
GAS. IF YOU THEN SMELL GAS, STOP! FOL-
LOW "B" IN THE SAFETY INFORMATION
ABOVE ON THIS LABEL. IF YOU DON'T SMEL L
TO THE LOWEST SETTING .
THERMOST AT
Honeywell
GAS,
GO TO NEXT STEP.
7. TURN THE "GAS CONTROL KNOB" COUNTER-
CLOCKWISE TO "ON".
TEMPERATURE
ADJUSTMENT
DIAL
Index
NOTE: Thermostat
shown with cover
removed .
8. TURN ONALL ELECTRIC POWER TO THE
APPLIANCE.
Ga s C ock
Knob
GAS VA LV E
9. SET THERMOSTAT TO D ESIRED SETTING.
INSTAL L OUTER COVER.
3. TURN OFF ALL ELECTRIC POWER TO TH E
APPLIANCE.
4. THIS APPLIANCE IS EQUIPPED WITH AN
IGNITION DEVICE WHICH AUTOMATICALLY
LIGHTS THE PILOT. DO NOT TRY TO LIGHT THE
10. IF THE APPLIANCE WILL NOTOPERATE, FOL-
LOW THE INSTRUCTIONS "TO TURN OFF GAS
TO APPLIANCE" AND CALL YOUR SERVICE
PILOT
BY HAND.
TECHNICIAN
OR GAS SUPPLIER.
TO TURN OFF GAS TO APPLIANCE
1. TURN OFF ALL ELECTRIC POWER TO THE 3. TURN THE "GAS CONTROL KNOB" CLOCK-
APPLIANCE IF SERVICE IS TO BE PERFORMED.
2. SET THE THERMOSTA T TO LOWEST SETTING.
WISE TO "OFF" .
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
SAFETY PRECAUTIONS
A. Do turn off manual gas shut-off valve if water heater has been sub-
E. Do not allow combustible materials such as newspaper, rags or
mops to accumulate near water heater.
jected to over heating, fire, flood, physical damage or if gas supply
fails to shut off.
F. If there is any difficulty in understanding or following the OPERA-
TION or MAINTENANCE instructions, it is recommended that a
qualified person or serviceman perform the work.
B. Do Not turn on water heater unless it is filled with water.
C. Do Not turn on water heater if cold water supply shut-off valve is
closed.
CAUTION
hydrogen gas can be produced in a hot water system served by
this water heater that has not been used for a long period of time
(generally two weeks or more). hYDROgEN gAS iS ExTREmElY
FlAmmABlE!!To dissipate such gas and to reduce risk of injury,
it is recommended that the hot water faucet be opened for several
minutes at the kitchen sink before using any electrical appliance
connected to the hot water system. if hydrogen is present, there
will probably be an unusual sound such as air escaping through
the pipe as the water begins to flow. Do not smoke or use an
open flame near the faucet at the time it is open.
D. Do Not store or use gasoline or other flammable vapors and liquids,
such as adhesives or paint thinner, in vicinity of this or any other
appliance. If such flammables must be used, open doors and win-
dows for ventilation, and all gas burning appliances in vicinity should
be shut off, including their pilot lights, to avoid vapors igniting.
NOTICE: Flammable vapors may be drawn by air currents from sur-
rounding areas to the water heater.
2. TEMPERATURE SETTINGS — The thermostat is adjusted to its lowest
temperature position when shipped from the factory. To meet com-
mercial water use needs, it is adjustable up to 180°F (82°C). How-
ever, water temperatures over 125°F (52°C) can cause severe burns
instantly or death from scalds. This is the preferred starting point for
setting the control for supplying general purpose hot water.
WARNING
!
When this water heater is supplying general purpose hot water
requirements for individuals, a thermostatically controlled mixing
valve for reducing point of use water temperature is recommend-
ed. Contact a licensed plumber or the local plumbing authority for
further information.
Safety and energy conservation are factors to be considered when
setting the water temperature on the thermostat. The most energy ef-
ficient operation will result when the temperature setting is the lowest
that satisfies the needs consistent with the application.
Outlet water temperature will vary during normal operating cycles. Reli-
able temperature readings should be taken shortly after main burner
cycles off during a period of little or no use.
hotter water increases the Potential for hotWater SCAlDS.
3. GAS MANIFOLD PRESSURE — With the gas valve supplied with this
water heater, main burner ignition occurs at a low or step manifold
pressure, which will then automatically build up to its normal operat-
ing level .The rated operating manifold pressure is listed on the water
heater rating plate. For purposes of input adjustment, the minimum inlet
gas pressure(with main burner on) is also shown on the rating plate.
A 1/8” NPT tapping is provided on the outlet side of the gas valve for
connecting a manometer to check this pressure. If necessary, adjust
the pressure to the proper value by turning regulator adjustment screw
clockwise to increase pressure or counterclockwise to decrease pres-
sure.
DANGER
4. CHECK INPUT — Consult the local Gas Company to determine the
heating value of the gas supplied. Check input by clocking gas meter with
all other gas appliances turned off. Use the following formula:
F
To adjust the water temperature, insert a small straight
screwdriver into slotted screw in hole in front of ther-
mostat and turn wheel to desired setting. Thermostat
is adjustable up to 180º F.
(3,600) x (Heating Value) x (Number of Cubic Feet Timed)
INPUT (btu/h) =
Seconds Clocked
WARNING
!
CAUTiON!! - hotter water increases the risk of SCAlDiNg!
THERMOSTAT
DO NOT exceed input shown on the water heater's rating plate!
White-Rodgers
honeywell
Figure 11. —Thermostat adjustment
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
To insure accuracy for rating, clock enough cubic feet of gas so that
7. EMERGENCY SHUTDOWN —
the clocked time is at least 60 seconds.
Small adjustments can be made by varying the manifold pressure from
the designated settings mentioned above.
WARNING
!
Should overheating occur or the gas supply fail to shut off, turn off
the manual gas control valve to the appliance.
5. INTERMITTENT PILOT FLAME ADJUSTMENT — No adjustment is
required with normal inlet gas pressures. The pilot flame adjustment
valve is pre-set, and does not normally require re-adjustment.
WARNING
!
6. HIGH ALTITUDE — Ratings of gas appliances are based on installation
and operation at sea level of elevations of 2000 feet.
DO NOT use this appliance if any part has been under water. imme-
diately call a qualified service technician to inspect the appliance
and to replace any part of the control system and any gas control
which has been under water.
Factory prepared high altitude models are available and are specifically
rated for installation at elevation up to 8000 feet. Refer to rating plate
on the front of the water heater for number and altitude specifications.
Also refer to the supplement sheet for information on venting high
altitude models.
If the water heater has been subjected to fire or physical damage, turn
off gas at the manual gas control (shut-off) valve. Do not operate the
water heater again until it has been checked out by a qualified service
technician.
maintenance
Properly maintained, this water heater will provide years of dependable,
trouble free service. It is strongly suggested that a regular routine main-
tenance program be established and followed by the owner. It is further
recommended that a periodic inspection of the blower, thermostat, burner,
relief valve, internal flueway, draft hood / damper assembly and venting
system should be made by service technicians qualified in gas appliance
repair.
TO REMOVE BURNERTRAY:
1. Turn off manual gas shut-off valve.
2. Disconnect gas pipe union and wiring to gas valve and pilot.
3. Remove retaining screws from plate on the same side as the gas
valve.
4. Slide burner tray assembly out. When reinstalling the burner tray
assembly, make certain it is pushed in all the way so that the plate
lines up with the holes in the plenum side.Then reinstall the retain-
ing screws.
1. ROUTINE PREVENTIVE MAINTENANCE
A. BURNERS — Visually inspect the main burner flame and the pilot flame
at least every three months. Refer to Figures 12 and 13 for normal
flame pattern. Fallen scale can usually be dislodged from the tops of
the burners with a thin rod, then vacuumed or brushed from the bottom
of the burner box. If a more thorough cleaning is deemed necessary
to restore a normal flame pattern, the burner tray assembly should be
removed and the burners cleaned individually.
5. Reconnect gas pipe union and wiring to gas valve and pilot, turn
on manual gas shut-off valve and test for gas leak.
B. VENTING SYSTEM — Inspect venting system at least yearly to make
certain the passageways are free and unobstructed, and that the vent
connector from the water heater’s blower assembly is properly posi-
tioned and securely attached. Remove any obstructions in vent con-
nector or vent terminal.
CAUTION
C. CONTROLS — The manifold pressure and controls should be checked
at least yearly by a qualified service technician.
For your safety, removal and cleaning of burner tray and individual
burners should be performed ONlY by a qualified service techni-
cian, as it involves disconnection of gas piping and leak testing.
Figure 13. — Pilot & main Burner Flame Pattern
Figure 12. — Pilot Flame Pattern
17
Download from Www.Somanuals.com. All Manuals Search And Download.
maintenance
D. BLOWER — Clean the blower periodically to remove any buildup of
lint or dirt. Remove the inlet plate and blow out any lint or dirt on the
wheel and on the screen of the inlet plate. Before operation, re-install
the inlet plate to the blower.
A wet-dry shop vac with a nozzle fashioned from 1” and/or 3/4” poly-
ethylene pipe makes a good tool for scraping and removing scale.
TO CLEAN OR INSPECT TANK:
1. Shut off gas valve and drain tank.
E. PRESSURE SWITCH — Inspect the inlet to the pressure switch and
the tubing for debris or blockage. Clean out the tubing periodically to
prevent buildup of debris.
2. Remove tank clean-out cover on jacket and with pocket knife cut
and remove a circular plug of insulation the full size of jacket open-
ing.
F. EMERGENCY CUT-OFF — This water heater is equipped with a com-
bination thermostat/temperature limiting device (ECO) that should be
checked annually by qualified service personnel.
3. Loosen nut on seal plate assembly enough to twist yoke sideways.
Hold assembly securely and push inward, then remove from tank.
G. THERMAL CUTOFF SWITCH — Some units are equipped with a
thermal cutoff switch which will shut down the unit if the flue gas tem-
perature is above permissible limits. The switch is a manual reset
type.
4. Remove as much built-up scale from flue tubes and tank bottom as
practical. Do not attempt to clean so thoroughly that the tool used
damages the glass lining.
CAUTION
5. Clean the seal plate and install a new gasket. Wipe clean the inte-
rior surface of the tank that contacts the gasket. Reinstall the seal
plate and tighten in position. Fill tank with water and check for leaks.
If no leaks are found, install insulation plug and clean-out cover on
jacket and re-light the water heater.
label all wires prior to disconnection when servicing controls.Wir-
ing errors can cause improper and dangerous operation.
VERiFY PROPER OPERATiON AFTER SERViCiNg!
If chemical lime dissolving cleaners are preferred, cautiously follow
the instructions supplied with the cleaner. DO NOT use a muriatic or
hydrochloric acid (HCl) base cleaner.
G. RELIEF VALVE — The Temperature and Pressure Relief Valve must
be free to operate properly. Check (at least once a year) by lifting the
handle fully and allowing several gallons of water to flush through the
discharge line. Make certain the discharged water is directed to a
suitable drain.
2. ANODE INSPECTION — The water supply in certain areas contains
very aggressive elements. In these areas, periodic inspection of the
anode is recommended to determine if replacement is necessary.The
anode(s) supplied in this water heater is slowly consumed , thereby
eliminating or minimizing corrosion and protecting the glass lined tank.
The anode(s) should be replaced when more than 6 inches (15 cm) of
core wire is exposed at either end.
DANGER
Before manually operating the relief valve, make certain no one
will be exposed to the danger of coming in contact with the hot
water released by this valve.The water may be hot enough to cre-
ate a SCAlD hazard. The water released should be directed to a
suitable drain to prevent injury or damage.
3. SEASONAL OPERATION — If the water heater is to remain idle for an
extended period (60 days or more) the heater should be turned off.The
water heater and piping should be drained if they might be subjected
to freezing temperatures. It is recommended that the water heater’s
operation is thoroughly checked (by a qualified service technician)
before it is placed back in service. NOTICE: Refer to Hydrogen Gas
caution notation on page 16.
NOTICE: If the temperature and pressure relief valve on the water
heater discharges periodically, this may be due to thermal expansion
in a “closed” water system. Contact the water supplier or local plumbing
inspector on how to correct this. DO NOT plug the relief valve outlet.
H. TANK— Good maintenance requires that the tank be cleaned of de-
posits. Unless the water supply is soft (0 to 5 grains hardness), scale
or lime deposits will accumulate in the tank. Hard water scale is de-
posited at an increasingly high rate in proportion to increased water
temperature. Accumulation of these deposits may reduce efficiency,
and shorten the life of the water heater.
Any new installation should have a tank inspection program set up
initially for frequent inspection. The first inspection should be within a
six month period. Once the scaling tendencies have been established,
the inspection program can be modified to suit the water conditions.
Cleaning should be performed if the scale has accumulated above the
drain valve opening.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
“System Sentinel” Diagnostic System
The “System Sentinel” Diagnostic system on this water heater provides the user or service technician with a visual representation of the
operational status of the various sections of the water heater’s control system. A quick glance at the System Sentinel panel on the front of
the heater will give an indication of where to begin trouble shooting of a non operational heater.
The LED’s (light emitting diodes) on the panel are arranged from top to bottom based on their function in the normal sequence of operation,
and their function is explained as follows:
POWER
When illuminated, this green LED indicates that 120VAC power is
being supplied to the heater, the ON/OFF switch is functioning and
the 24V transformer is functioning properly.
(Refer to Section 1 of Troubleshooting Guide)
THERMOSTAT
When illuminated, this red LED indicates that the ther-
mostat is functioning(calling for heat) and 24VAC power
is being supplied to the relay (to turn on the blower) and
the N/C terminal of the pressure switch with N/C and N/O
terminals.
SYSTEMSENTINEL
(Refer to Section 2 of Troubleshooting Guide)
POWER
IGNITION
THERMOSTAT
IGNITION
When illuminated, this red LED indicates that 24 VAC
power is being supplied to the Ignition Control Module,
and the ignition sequence has begun.The N/O side of the
pressure switch with N/C and N/O terminals closes
(Refer to Section 3 of Troubleshooting Guide)
PILOT VALVE
ECO
PILOT VALVE
When illuminated, this red LED indicates that the Ignition
Control Module is supplying 24 VAC power to the ECO
(Energy Cut Off device), or High Limit.
MAIN VALVE
(Refer to Section 4 of Troubleshooting Guide)
®
ECO
When illuminated, this red LED indicates that the ECO
(Energy Cut Off device), or High Limit is closed, and 24
VAC power is being supplied to the PV (Pilot Valve) ter-
minal on the Gas Control Valve.
(Refer to Section 5 of Troubleshooting Guide)
MAIN VALVE
When illuminated, this red LED indicates that the Ignition Control
Module is supplying 24 VAC power to the MV (Main Valve) terminal
on the Gas Control Valve.
(Refer to Section 6 of Troubleshooting Guide)
1ꢀ
Download from Www.Somanuals.com. All Manuals Search And Download.
“System Sentinel”Troubleshooting guide
Section 1... the“POWER”lED
is the“POWER”lED illuminated?
YES
NO
is the“ON/OFF”Switch in the
Turn switch to ON position. is the
Power is
YES
NO
“ON”position?
Power lED now illuminated?
being supplied to the heater,
the ON/OFF Switch is func-
tioning, and the 24V AC
Transformer is functioning.
YES
NO
is 120 VAC power present at the
Check circuit breaker or fuse and field connec-
tion of branch circuit wiring to leads of switch.
Repair or replace as required. is “POWER” lED
now illuminated?
NO
branch circuit connections to Black
wire of the switch and White wire of
the transformer ?
YES
YES
NO
Replace Switch, then verify that
power is present. is “POWER” lED
now illuminated?
is 120 VAC power present between
the Black and White wires to the
transformer ?
YES
NO
NO
YES
Replace Transformer, then verify
that power is present. is “POWER”
lED now illuminated?
is 24 VAC power present between
the Yellow and gray wires from the
transformer ?
NO
YES
YES
NO
The System Senti-
nel Panel is defective and must be
replaced.
CAUTION
!
label all wires prior to disconnection when servicing controls.Wiring errors can cause improper and dangerous operation. VERiFY PROP-
ER OPERATiON AFTER SERViCiNg!
20
Download from Www.Somanuals.com. All Manuals Search And Download.
“System Sentinel”Troubleshooting guide
Section 2... the“ThERmOSTAT”lED
NO
YES
is the “ThERmOSTAT” lED illuminated?
Ensure that power is being supplied to
the water heater. Refer to “Section 1...the
POWER lED”in thisTroubleshooting guide,
and correct if necessary. is the “ThERmO-
STAT lED”now illuminated.
Thermostat is calling for
heat, and 24VAC power.
YES
YES
NO
is Thermostat set at a tempera-
Adjust
ture higher than the water tem-
Thermostat to a higher setting.
is Thermostat lED now illumi-
nated?
NO
perature in tank?
YES
NO
Ensure that power is being supplied to
the water heater. Refer to “Section 1...the
POWER lED”in thisTroubleshooting guide,
and correct if necessary. is the “ThERmO-
STAT lED”now illuminated.
is 24 VAC
power present at Yellow Wire
Terminal insideThermostat?
NO
YES
YES
NO
is 24 VAC power present at
Blue Wire Terminal inside Ther-
mostat?
YES
NO
Thermostat is
defective or out of calibration
and must be replaced.
CAUTION
!
label all wires prior to disconnection when servicing controls.Wiring errors can cause improper and dangerous operation. VERiFY PROP-
ER OPERATiON AFTER SERViCiNg!
21
Download from Www.Somanuals.com. All Manuals Search And Download.
“System Sentinel”Troubleshooting guide
Section 3... the“igNiTiON”lED
YES
is the ignition lED illuminated?
NO
The Thermostat has called for
heat, the Blower is running, and
24VAC power is being supplied to
the ignition Control module and
the ignition sequence will begin.
is Spark ignitor operating?
is the Blower Operating?
YES
(Can sparking be heard?)
NO
YES
NO
is there 120 VAC
across Black wire
and White wire of
blower?
The System Sentinel Panel is
defective and must be replaced.
NO
is 24 VAC present between the
gray ground wire and the Red
24 V wire connected to the igni-
tion Control module?
is there 24 VAC present
NO
YES
between the common and
Normally open terminal of
pressure switch 1?
is there 120
VAC between
the black wire at
the relay and the
whitewireonthe
transformer?
Blower is
defective
and must be
replaced.
YES
YES
NO
1. Remove ignition Cable and check for
good continuity, replace if necessary.
2. Check ignitor Electrode(s) gap for proper
spacing (1/8” to 5/32”). Correct if neces-
sary.
3. Examine Ceramic insulator on Pilot
Assembly for cracks. Replace if cracks
are evident.
NO
YES
Check Con-
tinuity of the
Red wire from
the ignition
module to
the Pressure
Switch.
Check con-
Check continuity
of black wire to
relay.
tinuity of
yellow wires
to pressure
s w i t c h e s
and between
switches.
Check continuity
of black wire from
relay to blower
motor and white
wire to motor.
YES
if all of the above components check okay,
replace ignition Control module.
is continuity
is continuity
good?
good?
is continuity
good?
Pressure Switch
is defective and
must be replaced.
is continuity
good?
C h e c k
wire con-
nections.
NO
YES
YES
W i r e
NO
NO
YES
is defec-
tive and
must be
replaced.
is there 120 VAC between the
black wire on the relay (power
going to blower) and the white
wire of the transformer?
Wiring harness is defec-
tive and must be replaced.
YES
NO
Recheck all connections,
P o w e r
should be
at 24 VAC
of ignition
module.
Relay is
d e fe c t i v e
and must be
replaced.
is 24
should have power at blower motor.
VAC present
across coil
of relay?
YES
Review pressure switch circuit
on this page.
NO
CAUTION
!
label all wires prior to disconnection when servicing controls.Wiring errors can cause improper and dangerous operation. VERiFY PROP-
ER OPERATiON AFTER SERViCiNg!
22
Download from Www.Somanuals.com. All Manuals Search And Download.
“System Sentinel”Troubleshooting guide
Section 4... the“PilOTVAlVE”lED
is the“PilOTVAlVE”lED illuminated?
NO
YES
The ignition Control module is in
the ignition sequence, and is pro-
viding 24 VAC power to the ECO
(Energy Cut-Off Device) inside of
theThermostat
is the Spark ignitor operating?
(Can sparking be heard?)
YES
is the Pilot Flame burning?
YES
NO
NO
The System Sentinel Panel is
defective and must be replaced.
1. Remove ignition Cable and check for good conti-
nuity, replace if necessary.
2. Check ignitor Electrode gap for proper spacing
(1/8”to 5/32”). Correct if necessary.
3. Examine Ceramic insulator on Pilot Assembly
for cracks. Replace if cracks are evident.
is 24 VAC present between the Brown wire on “PV”
Terminal and White wire on “PV/mV” Terminal on
the gas ControlValve?
YES
YES
is 24 VAC present between the Brown wire on “PV”
Terminal and gray ground wire on ignition Control
module?
YES
NO
i s
the inlet gas pres-
sure at or below the
maximum as speci-
fied on the rating
plate?
gas Control Valve
is inoperable and must
be replaced
NO
is the“igNiTiON”lED illuminated?
is the “ECO” lED
illuminated?
YES
NO
NO
YES
Check continuity of Brown wire
between ECO Device (inside of Ther-
mostat), and “PV” Terminal on gas
ControlValve. Repair or replace wire as
needed to restore power to“PV”Termi-
nal on gas valve.
ignition Control module
is inoperable and must be
replaced.
Refer to Section 3...the“igNi-
TiON”lED in theTroubleshooting guide
Refer to Section 5...the“ECO”lED in
theTroubleshooting guide
CAUTION
!
label all wires prior to disconnection when servicing controls.Wiring errors can cause improper and dangerous operation. VERiFY PROP-
ER OPERATiON AFTER SERViCiNg!
23
Download from Www.Somanuals.com. All Manuals Search And Download.
“System Sentinel”Troubleshooting guide
Section 5... the“ECO”lED
NO
YES
is the "ECO" lED illuinated?
ECO is “open”. Allow tank to cool,
and reset. if ECO again trips, the
Thermostat/high limit is defective.
Replace as required.
T h e
ECO (Energy Cut-Off device) is
not tripped (open) and power is
being supplied to the “PV” termi-
nal on the gas ControlValve.
YES
is“ECO lED now illuminated?
NO
The System Sentinel Panel is
defective and must be replaced.
YES
is the Pilot Flame burning?
NO
Refer to
Section 3...the “igNiTiON”lED; and Section
4...the “PilOT VAlVE”lED of Troubleshoot-
ing guide. Repair or replace components as
required.
Section 6... the“mAiNVAlVE”lED
is the“mAiNVAlVE”lED illuminated?
NO
YES
The ignition Control module is
providing 24 VAC between the
“mV” and “mV/PV” terminals on
gas ControlValve, and main Burn-
er should be operating
is main Burner on?
is the Pilot Flame burning?
YES
YES
NO
NO
is 24 VAC present between Blue wire on
“mV Terminal and White wire on “mV/PV”
terminal on the ignition Control module?
The System Sentinel Panel is
defective and must be replaced.
is the Spark ignitor operating?
(Can sparking be heard?)
is the inlet gas pressure at or below the
maximum as specified on the rating plate?
YES
NO
NO
is 24 VAC present between Blue
wire on “mV Terminal and White
wire on “mV/PV” terminal on gas
valve?
YES
main gasValve is inoperative
and must be replaced.
ignition Control module is inoperative and
must be replaced.
Check Continuity of Blue and White
wires between ignition Control module and
gas Control Valve. Repair or replace as
required to restore power to gas valve.
NO
CAUTION
!
label all wires prior to disconnection when servicing controls.Wiring errors can cause improper and dangerous operation. VERiFY PROP-
ER OPERATiON AFTER SERViCiNg!
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Replacement Parts
Instructions For Placing a Parts Order
All parts orders should include:
CAUTiON: For your safety DO NOT attempt repair of
!
gas piping, gas control (thermostat), burners, vent con-
The model and serial number of the water heater from the rating
plate.
nectors or other safety devices. Refer repairs to qualified
service personnel.
Specify type of gas (natural or LP) as marked on the rating plate.
Part description (as noted below) and number of parts desired.
Blower Assembly
T&P Valve
Handhole Sealplate
Gasket SP5886
(Beneath Cover)
Thermostat
Ignition Control
Assembly
w/ Relay*
Drain Valve
Gas Valve
Burner Assembly
Pilot/Ignitor
Assembly
*Some assembly components are available individually
(Control Module, Transformer, and ON/OFF Switch).
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring and Schematic Diagrams
N O R M A L O P E R A T I O N S E Q U E N C E
I N D I C A T E D B Y B O X E D N U M E R A L S
L 1
L 2
1 2 0 V
2
3
B L O W E R
LED
INDICATORS
BL
BR
BR
-
-
-
4
3
4
POWER
2 4 V
THERMOSTAT
IGNITION
THERMOSTAT
AND
120V
POWER
LED
L1
L2
PILOT VALVE
ECO
HIGH LIMIT
IGNITION
LED
MAIN VALVE
BLACK
SWITCH
WHITE
1
4
ON
TRANSFORMER
THERM.
N.C.S.W.
Y-2
OFF
GRAY
W4
BK-2
BLOWER
THERMOSTAT LED
Y-2
W
IGNITION
CONTROL
GR/YL
BK
G2
MAIN VALVELED
GY-5
6
BK3
NC
1
4
3
6
IGNITION CONTROL
MGV
GND
MV
TEMP
SWITCH
Y7
Y6
5
2
24 MV/PV
NC
5
LIMIT
Y-5
C
C
BL6
PGV
N
PV
PS2
PS1
R8
BR-1
R-3
BL-5
GY-1
ECO LED
GND
BR-3
PILOT VALVE
LED
BL-2
W-1
PV
PV
5
IGN.
MV
PILOT
ELECTRODE ASSY.
MV
GAS VALVE
CONNECTION DIAGRAM
SCHEMATIC
Figure 14. — Diagrams for units supplied with honeywellVR8304P orVR8304m gasValve and honeywell S8600m ignition Control, honeywellThermo-
stat andTemperature limiting Switch for vent pipe..
NOTiCE: if any of the original wire as supplied with this appliance must be replaced, it mUST be replaced with 18 gA., 600V, 105°C
wire or its equivalent, unless otherwise noted.
CAUTiON! label all wires prior to disconnection when servicing controls.Wiring errors can cause improper and dangerous operation.
VERiFY PROPER OPERATiON AFTER SERViCiNg!
!
N O R M A L O P E R A T I O N S E Q U E N C E
I N D I C A T E D B Y B O X E D N U M E R A L S
L 1
L 2
1 2 0 V
2
3
B L O W E R
LED
INDICATORS
BL - 4
BR - 3
BR - 4
POWER
2 4 V
THERMOSTAT
IGNITION
120V
POWER
LED
THERMOSTAT
AND
L1
L2
PILOT VALVE
ECO
IGNITION
LED
HIGH LIMIT
MAIN VALVE
BLACK
SWITCH
WHITE
1
4
ON
TRANSFORMER
THERM.
N.C.S.W.
OFF
GRAY
W4
BK-2
BLOWER
W
THERMOSTAT LED
MAIN VALVELED
Y-2
IGNITION
CONTROL
GR/YL
BK
G2
GY-5
IGNITION CONTROL
6
BK3
NC
1
4
3
6
MGV
GND
MV
TEMP
SWITCH
Y7
Y6
5
2
24 MV/PV
NC
5
LIMIT
Y-5
C
C
BL6
PGV
N
PV
PS2
PS1
R8
BR-1
R-3
BL-5
GY-1
ECO LED
GND
BR-3
PILOT VALVE
LED
BL-2
W-1
PV
PV
5
IGN.
MV
PILOT
ELECTRODE ASSY.
MV
GAS VALVE
CONNECTION DIAGRAM
SCHEMATIC
Figure 14. — Diagrams for units supplied with honeywellVR8304P orVR8304m gasValve and honeywell S8600m ignition Control,White-Rodgers
Thermostat andTemperature limiting Switch for vent pipe..
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring and Schematic Diagrams
NORMAL OPERATION SEQUENCE
INDICATED BY BOXED NUMERALS
NOTICE: If any of the original wire as supplied
L1
L2
with this appliance must be replaced, it MUST be
replaced with 18 GA., 600V, 105°C wire or its equiv-
alent, unless otherwise noted.
120V
2
3
BLOWER
M
R
LED
INDICATORS
BL-4
BR-3
BR-4
POWER
24V
THERMOSTAT
AND
THERMOSTAT
IGNITION
PILOT VALVE
ECO
120V
L1
POWER
LED
L2
LIMIT
IGNITION
LED
MAIN VALVE
BLACK
SWITCH
WHITE
1
THERM.
4
ON
TRANSFORMER
Y2
N.C.S.W.
OFF
R
GRAY
W4
BK-2
THERMOSTAT LED
BLOWER
W
Y-2
G2
IGNITION
CONTROL
GR/YL
BK
MAIN VALVE LED
GY-5
6
BK3
1
4
3
6
IGNITION CONTROL
MGV
GND
MV
Y7
Y6
NC
5
2
24 MV/PV
5
LIMIT
Y-5
NC
C
C
BL6
PGV
NO
PV
PS2
PS1
R8
BR-1
R-3
BL-5
ECO LED
GND
BR-3
GY-1
PILOT VALVE
LED
BL-2
W-1
PV
5
IGN.
PV
MV
ANY REPLACEMENT WIRE
MUST BE RATED FOR 250°C.
PILOT
ELECTRODE ASSY.
MV
GAS VALVE
SCHEMATIC
CONNECTION DIAGRAM
CAUTiON! label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. VERi-
FY PROPER OPERATiON AFTER SERViCiNg!
!
Figure 14. — Diagrams for units supplied with honeywellVR8304P orVR8304m gasValve and honeywell S8600m ignition Control.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
how to Obtain Service Assistance
1. Should you have any questions about your new water heater, or if it
be made available:
requires adjustment, repair, or routine maintenance, it is suggested
that you first contact your installer, plumbing contractor or previously
agreed upon service agency. In the event that the firm has moved, or
is unavailable, refer to the telephone directory commercial listings or
local utility for qualified service assistance.
a. Model and serial numbers of the water heater as shown on the rating
plate attached to the jacket of the heater.
b. Address where water heater is located and can be seen.
2. Should your problem not be solved to your complete satisfaction, you
should then contact the Manufacturer’s National Service Department
at one of the following address:
c. Name and address of installer and any service agency who performed
service on the water heater.
d. Date of original installation and dates any service work was per-
formed.
In The U.S.A.:
Rheem Manufacturing Co., Water Heater Division
2600 Gunter Park Drive
e. Details of the problem as you can best describe them.
Montgomery, Alabama 36109-1413
Phone: 1-800-432-8373.
f. List of people, with dates, who have been contacted regarding your
problem.
In CANADA:
Rheem Canada, Ltd. / Ltée
P.O. Box 2846
Hamilton, ON L8N 3P3
Phone: 1-800-268-6966.
When contacting the manufacturer, the following information should
The following Gaskets are required for Normal Maintenance for all Models:
SP5886 Tank Handhole Sealplate Gasket
All other Parts can be ordered by providing the following information:
1. Description of Part(s), such as:
Main Gas Valve
Pilot Burner
Main Burner
Thermostat
Blower Assembly
Anode Rod
Or other parts as required.
2. Quantity of each part required.
3. Complete models number and name of the water heater.
4. Serial Number of water heater.
5. Specify Type of Gas.
6. Address Parts Orders to your distributor or dealer.