Rheem Water Heater Commercial Power Direct Vent Water heater User Guide

Commercial Power Direct Vent Water heater  
USE & CARE mANUAl  
WiTh iNSTAllATiON iNSTRUCTiONS FORThE CONTRACTOR  
mUlTi-FlUE COmmERCiAl mODElS  
S
I
G
N
D
R
T
E
I
®
CERTIFIED  
R
Recognize this symbol as an indication of important  
Do Not Destroy this manual. Please read carefully and  
!
!
!
Safety information!  
keep in a safe place for Future Reference.  
NOTiCE:This water heater is designed for use in a commercial application and the installation and maintenance of it should be per-  
formed by a qualified, licensed service personnel. if the foregoing assumption is not appropriate, then we recommend that you obtain  
and retain our Residential Use & Care manual.  
CAliFORNiA PROPOSiTiON 65WARNiNg:This product contains chemicals known to the State of California to cause cancer, birth  
defects or other reproductive harm.  
!
WARNiNg: if the information in these instructions are not followed exactly, a fire or explosion may result  
causing property damage, personal injury or death.  
!
!
immediately call your gas supplier from a neighbor's  
FORYOUR SAFETY!  
phone. Follow the gas supplier's instructions.  
— Do not store or use gasoline or other flammable  
vapors or liquids or other combustible materials in  
the vicinity of this or any other appliance. To do so  
may result in an explosion or fire.  
if you cannot reach your gas supplier, call the fire  
department.  
Do not return to your building until authorized by  
the gas supplier or fire department.  
— WhATTO DO iFYOU SmEll gAS  
improper installation, adjustment, alteration, service  
or maintenance can cause injury, property dam-  
age or death. Refer to this manual. installation and  
service must be performed by a qualified installer,  
service agency or the gas supplier.  
Do not try to light any appliance.  
Do not touch any electrical switch; do not use any  
phone in your building.  
AP13463-3 (02/07)  
Printed in USA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
general Safety Precautions  
To meet commercial water use needs, the thermostat on this water  
heater is adjustable up to 180°F. however, water temperatures over  
125°F. can cause severe burns instantly or death from scalds.This  
is the preferred starting point for setting the control for supplying  
general purpose hot water.  
The following chart details the relationship of water temperature  
and time with regard to scald injury and may be used as a guide in  
determining the safest water temperature for your applications.  
Temperature  
120° F  
125° F  
130° F  
135° F  
140° F  
145° F  
150° F  
155° F  
Time to Produce Serious Burn  
More than 5 minutes  
11/2 to 2 minutes  
Safety and energy conservation are factors to be considered when  
setting the water temperature on the thermostat. The most energy  
efficient operation will result when the temperature setting is the  
lowest that satisfies the needs consistent with the application.  
About 30 seconds  
About 10 seconds  
Less than 5 seconds  
Less than 3 seconds  
About 11/2 seconds  
About 1 second  
Table courtesy of Shriners Burn Institute  
!
D A N G E R  
TimE / TEmPERATURE RElATiONShiPS iN SCAlDS  
The temperature of the water in the heater can be regulated by  
setting the temperature dial on front of the thermostat.To comply  
with safety regulations the thermostat was set at its lowest setting  
before water heater was shipped from the factory.The illustration  
below illustrates the thermostat and how to adjust the water tem-  
perature.  
HOT  
BURN  
F
To adjust the water temperature, insert a small straight  
screwdriver into slotted screw in hole in front of ther-  
mostat and turn wheel to desired setting. Thermostat  
is adjustable up to 180º F.  
Water temperature over 125°F can  
cause severe burns instantly or  
death from scalds.  
CAUTiON!! - hotter water increases the risk of SCAlDiNg!  
Children, disabled and elderly are  
at highest risk of being scalded.  
THERMOSTAT  
See instruction manual before  
setting temperature at water  
heater.  
White-Rodgers  
honeywell  
NOTiCE: Each water heater will contain one (1) of the above ther-  
mostats. Refer to actual unit to determine which one.  
Feel water before bathing or  
showering.  
DANGER  
!
Temperature limiting valves are  
available, see manual.  
hotter water increases the Potential for hotWater SCAlDS.  
NOTiCE: mixing valves are available for reducing point of use  
water temperature by mixing and cold water in branch water lines  
Contact a licensed plumber or the local plumbing authority for  
further information.  
maximum water temperatures occur just after burner has shut off.  
To find hot water temperature being delivered, turn on a hot water  
faucet and place a thermometer in the hot water stream and read  
the thermometer.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
general Safety Precautions  
!
Be sure to read and understand the entire Use & Care Manual before attempting to install or operate this water heater. Pay particular attention  
to the following General Safety Precautions. Failure to follow these warnings could result in a fire or explosion, causing property damage, bodily  
injury or death . Should you have any problems understanding the instructions in this manual, STOP, and get help from a qualified installer or  
service technician or the gas supplier.  
DANGER  
!
WARNING  
!
liQUEFiED PETROlEUm mODElS — Propane, or lP gas,  
gasoline, as well as other flammable materials and liquids  
(adhesives, solvents, etc.), and the vapors they produce,  
are extremely dangerous. DO NOT handle, use or store  
gasoline or other flammable or combustible materials any-  
where near or in the vicinity of a water heater. Be sure to  
read and follow the warning label pictured below and other  
labels on the water heater, as well as the warnings printed  
in this manual. Failure to do so can result in property dam-  
age, bodily injury, or death.  
must be used with great caution.  
it is heavier than air and will collect first in lower areas  
making it hard to detect at nose level.  
make sure to look and smell for lP leaks before  
attempting to light appliance. Use a soapy solution to  
check all gas fittings and connections. Bubbling at a  
connection indicates a leak that must be corrected.  
When smelling to detect an lP leak, be sure to sniff  
near the floor too.  
gas detectors are recommended in lP applications  
and their installation should be in accordance with the  
manufacturer's recommendations and/or local laws,  
rules, regulations or customs.  
DANGER  
!
it is recommended that more than one method be used  
to detect leaks in lP applications.  
Failure to properly vent the water heater to the outdoors  
as outlined in the Venting Section of this manual can result  
in unsafe operation of the water heater. To avoid the risk  
of fire, explosion, or asphyxiation from carbon monoxide,  
never operate this water heater unless it is properly vented  
and has an adequate air supply for proper operation. Be  
sure to inspect the vent system for proper installation at  
initial start-up; and at least annually thereafter. Refer to  
maintenance section of this manual for more information  
regarding vent system inspections.  
iF lP gAS iS PRESENT OR SUSPECTED:  
• DO NOT attempt to find the cause yourself;  
• DO NOT try to light any appliance;  
• DO NOT touch any electrical switch;  
• DO NOT use any phone in your building.  
leave the house immediately and make sure your fam-  
ily and pets leave also.  
leave the doors open for ventilation and contact the  
gas supplier, a qualified service agency or the fire  
department.  
• Keep the area clear until the service call has been  
made, the leak is corrected, and a qualified agency has  
determined the area to be safe.  
!
D A N G E R  
WARNING  
!
Both lP and natural gas have an odorant added to help  
detection. Some people may not physically be able to  
smell or recognize this odorant. if unsure or unfamiliar  
about the smell associated with lP or natural gas, ask the  
gas supplier. Other conditions, such as "Odorant Fade",  
which causes the odorant to "fade", or diminish in inten-  
sity can also hide or camouflage a gas leak.  
FLAMMABLES  
FlammableVapors  
!
Vapors from flammable  
liquids will explode and  
catch fire causing death or  
severe burns.  
Do not use or store flammable  
products such as gasoline,  
solvents or adhesives in the  
same room or area near the  
water heater.  
Water heater has a main  
burner and pilot flame.  
The pilot flame:  
1. which can come on at  
any time and  
DANGER  
!
2. will ignite flammable  
vapors.  
Water heaters utilizing liquefied Petroleum gas (lP) are  
different from natural gas models. A natural gas heater will  
not function safely on lP gas and vice versa. No attempt  
should ever be made to convert a heater from natural gas  
to lP gas. To avoid possible equipment damage, personal  
injury or fire: DO NOT connect this water heater to a fuel  
type not in accordance with unit data plate. Propane for  
propane units. Natural gas for natural gas units. These  
units are not certified for any other type fuel.  
Vapors:  
1. cannot be seen,  
2. are heavier than air,  
3. go a long way on the  
floor and  
Keep flammable products:  
1. far away from heater,  
2. in approved containers,  
3. tightly closed and  
4. can be carried from  
other rooms to the pilot  
flame by air currents.  
4. out of children's reach.  
Installation:  
are at least 18" above the  
floor.This will reduce, but not  
eliminate, the risk of vapors  
being ignited by the main  
burner or pilot flame.  
Do not install water heater  
where flammable products will  
be stored or used unless the  
main burner and pilot flames  
WARNING  
!
lP appliances should not be installed below-grade (for  
example, in a basement) if such installation is prohibited  
by federal, state and/or local laws, rules, regulations or cus-  
toms.  
Read and follow water heater warnings and instructions.If owners  
manual is missing,contact the retailer or manufacturer.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
introduction  
C. All models are certified for installation on combustible floors and in  
WARNING  
!
alcoves. The minimum side and top clearance to walls and ceiling for  
providing protection of combustible materials are shown on the water  
heater’s rating label. A front clearance of 18 inches (46 cm) should be  
provided for adequate inspection and servicing.  
Read and Review this entire manual with special emphasis  
on the Venting Sections (Pages 8-12) and Operation Section  
(Pages 14-17) prior to any installation work.  
LOCAL INSTALLATION REGULATIONS  
If the water heater must be installed on carpeting, place a metal or  
wood panel beneath water heater extending beyond its full width and  
depth at least 3 inches (7.6 cm) in all directions. If the water heater is  
installed in an alcove, the entire floor must be covered by the panel.  
The water heater should not be located in an area where leakage of  
the tank or connections will result in damage to the area adjacent  
This water heater must be installed in accordance with these instructions,  
local codes, utility company requirements and/or, in the absence of local  
codes, the latest edition of the National Fuel Gas Code, ANSI Z223.1 in  
the United States, or CGA/CAN B149 Installation Codes in Canada.  
LOCATION  
A. This water heater is of the direct vent design. All air for combustion  
and all products of combustion are routed through the venting system,  
directly from and to the outside of the building.  
CAUTION  
!
to it or to lower floors of the structure.When such areas cannot be  
avoided, it is recommended that a suitable catch pan, adequately  
drained, be installed under the water heater. The pan mUST NOT  
restrict the flow of combustion air flow to bottom of water heater.  
The water heater should be installed in a clean, dry location as close  
as practical to the gas vent terminals. Long hot water lines should be  
insulated to conserve water and energy. The water heater and water  
lines should be protected from exposure to freezing temperatures.  
NOTICE: Auxiliary catch pan installation MUST conform to the ap-  
plicable local codes.  
B. A gas fired water heater should not be installed in a space where liquids  
which give off flammable vapors are to be used or stored. Such liquids  
include gasoline, LP gas (butane and propane), paint or adhesives and  
their thinners, solvents or removers. Because of natural air movement  
in a room or other enclosed space, flammable vapors can be carried  
some distance from where their liquids are being used or stored. The  
open flame of the water heater’s intermittent pilot or main burner can  
ignite these vapors causing an explosion or fire which may result in  
severe burns or death to those in range, as well as property damage.  
For these reasons, installation of a gas fired water heater in a garage  
is not desirable.  
D. RESTAURANTS — If the water heater is to be installed in a restau-  
rant or other location where the floor is frequently cleaned, it must be  
elevated to provide at least six inches (15 cm) of clearance from the  
floor to comply with NSF International recommendations.  
E. CORROSIVE ATMOSPHERES — The heater should not be installed  
near an air supply containing halogenated hydrocarbons. For example,  
the air in beauty shops, dry cleaning establishments, photo processing  
labs, and storage areas for liquid and powdered bleaches or swim pool  
chemicals often contain such hydrocarbons.The air there may be safe  
to breathe, but when it passes through a gas flame, corrosive elements  
are released that will shorten the life of any gas burning appliance.  
Propellants from common spray cans or gas leaks from refrigeration  
equipment are highly corrosive after passing through a flame.The lim-  
ited warranty is voided when failure of water heater is due to a corrosive  
atmosphere. (Refer to the Certificate of Limited Warranty for complete  
terms and conditions.)  
WARNING  
!
if a location in a garage is the only alternative, the gas water heater  
should be installed so that the open flame of the pilot and main  
burner are no less than 18 inches above the garage floor.The water  
heater must be located or protected so it is not subject to physical  
damage by moving vehicles or area flooding. Raising the gas fired  
water heater will reduce BUT NOT eliminate the possibility of light-  
ing the vapor of any flammable liquids which may be improperly  
stored or accidentally spilled.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
installation  
heater. If special instructions are required for any specific water heater,  
they will be included in the bag.  
WARNING  
!
Cap or plug unused connections. Use only clean, new galvanized steel,  
copper or approved plastic pipe for water connections. Local codes  
or regulations shall govern the exact type of material to be used. The  
installation of unions on the inlet and outlet water lines and a shut-off  
valve in at least the cold water inlet line is recommended, so the water  
heater may be easily disconnected for servicing. Dielectric unions are  
not required for protection of water heater.  
The manufacturer’s warranty does not cover any damage or defect  
caused by installation, or attachment, or use of any special attach-  
ment such as energy saving devices (other than those authorized  
by the manufacturer) into, onto, or in conjunction with the water  
heater. The use of such unauthorized devices may shorten the  
life of the water heater and may endanger life and property. The  
manufacturer disclaims any responsibility for such loss or injury  
resulting from the use of such unauthorized devices.  
When this water heater is supplying general purpose hot water require-  
ments for use by individuals, a thermostatically controlled mixing valve  
is recommended to reduce the risk of scald injury. Contact a licensed  
plumber or the local plumbing authority for further information.  
1. INSPECT SHIPMENT — for possible damage. The manufacturer’s  
responsibility ceases upon delivery of goods to the carrier in good  
condition. Any claims for damage, shortage in shipments, or non de-  
livery must be filed immediately against carrier by consignee.  
Thermometer(s) should be installed so that they indicate the tempera-  
ture of the water at or near the outlet of the water heater and storage  
tank(s) if provided. See Fig. 4 on page 7.  
2. THERMAL EXPANSION — Determine if a check valve exists in the  
inlet water line. It may have been installed in the cold water line as a  
separate back flow preventer, or it may be part of a pressure reduc-  
ing valve, water meter or water softener. A check valve located in  
the cold water inlet line can cause what is referred to as a ”closed  
water system”. A cold water inlet line with no check valve or back  
flow prevention device is referred to as an ”open” water system.  
3. RELIEF VALVE — A new factory installed combination pressure and  
temperature relief valve, complying with the Standard for Relief Valves  
and Automatic Gas Shutoff Devices for Hot Water Supply Systems,  
ANSI Z21.22, or Standard CAN1-4.4, Temperature, Pressure, Tempera-  
ture and Pressure Relief Valves and Vacuum Relief Valves is provided  
with the water heater. No valve is to be placed between the relief valve  
and the water heater. For a circulating tank installation, the separate  
storage tank(s) must have similar protection.The pressure rating of the  
relief valve must not exceed 150 psi (160 psi for ASME models), the  
maximum working pressure as marked on front of the water heater.  
As water is heated, it expands in volume and creates an increase  
in the pressure within the water system. This action is referred to as  
”thermal expansion”. In an ”open” water system, expanding water  
which exceeds the capacity of the water heater flows back into the  
city main where the pressure is easily dissipated.  
The Btu/h rating of the relief valve must equal or exceed the Btu/h input  
of the water heater as marked on its rating plate.  
A ”closed water system”, however, prevents the expanding water  
from flowing back into the main supply line, and the result of ”thermal  
expansion” can create a rapid, and dangerous pressure increase in  
the water heater and system piping.This rapid pressure increase can  
quickly reach the safety setting of the relief valve, causing it to oper-  
ate during each heating cycle. Thermal expansion, and the resulting  
rapid, and repeated expansion and contraction of components in the  
water heater and piping system can cause premature failure of the  
relief valve, and possibly the heater itself. Replacing the relief valve  
will not correct the problem!  
Connect the outlet of the relief valve to a suitable open drain. The  
discharge line must pitch downward from the valve to allow complete  
draining (by gravity) of the relief valve and discharge line, and be no  
smaller than the outlet of the valve. The end of the discharge line  
should not be threaded or concealed and should be protected from  
freezing. No valve of any type, restriction or reducer coupling should be  
installed in the discharge line. Local codes shall govern the installation  
of relief valves.  
4. GAS SUPPLY — The inlet gas pressure to the water heater must not  
exceed 10.5” w.c. (2.6 kPa) for Natural gas. For purposes of input adjust-  
ment, the minimum inlet gas pressure (with main burner on) is shown on  
the rating plate. Check to see if high or low gas pressure is present and  
then contact the gas company for correction.  
The suggested method of controlling thermal expansion is to install an  
expansion tank in the cold water line between the water heater and the  
check valve.The expansion tank is designed with an air cushion built in  
that compresses as the system pressure increases, thereby relieving  
the over pressure condition and eliminating the repeated operation of  
the relief valve. Other methods of controlling thermal expansion are also  
available. Contact your installing contractor, water supplier, or plumbing  
inspector for additional information regarding this subject.  
The gas line should be of adequate size to prevent undue pressure  
drop. Sizing based upon Table 1 (on pg. 13) is recommended. No ad-  
ditional allowance is necessary for an ordinary number of fittings.  
A ground joint union and manual shutoff valve should be installed in  
the gas line near the water heater so that the burner assembly may  
be easily removed. The shut-off valve must be readily accessible for  
turning on or off. See Fig. 4 on page 7.  
If a recirculation line is installed, the return connection should be made  
to a tee close to the inlet connection on the water heater. A check valve  
should always be installed in the recirculation line to prevent cold water  
from entering.  
A sediment trap must be installed at the bottom of the gas line. See  
Fig. 4 on page 7.  
WATER CONNECTIONS — This water heater may be connected indi-  
vidually, in multiples with others, or with an external hot water storage  
tank.  
LEAK TESTING — The water heater and its gas connections MUST  
be leak tested at normal operating pressure before it is placed in op-  
eration. Turn ON the manual gas shut-off valve near the water heater.  
Use a soapy water solution to test for gas leaks at all connections and  
fittings. Bubbles indicate a gas leak that must be corrected.The water  
heater factory connections to the gas valve should also be leak tested  
after placing the water heater in operation.  
Inlet water connections are made to the lower coupling on the heater,  
and outlet water connections are made to the upper coupling.  
Each water heater is supplied with the necessary components (Diffuser  
tubes) to make the water connections that will ensure proper perfor-  
mance. The components are supplied in a bag attached to the water  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
installation  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
installation  
The unit may be vented horizontally through a wall or vertically through  
WARNING  
!
the roof. Pipe runs must be adequately supported along both vertical  
and horizontal runs. Maximum unsupported span is recommended to  
be no more than 4 feet. It is imperative that the first hanger be located  
on the horizontal run immediately adjacent to the first 90-degree elbow  
from the vertical rise or at the blower outlet in the case of a horizontal  
blower position. Support method used should isolate the vent pipe from  
floor joists or other structural members to help prevent the transmission  
of noise and vibration. Do not support, pin or otherwise secure the vent-  
ing system in a way that restricts the normal thermal expansion and  
contraction of the chosen venting material.  
NEVER use open flame to test for gas leaks, as bodily injury or  
property damage could result.  
PRESSURE TESTING THE GAS SUPPLY SYSTEM — The water  
heater and its manual gas shut-off valve MUST be disconnect-  
ed from the gas supply piping system during any high pressure  
testing of that system at pressures in excess of 1/2 psi  
(14” w.c. / 3.5 kPa).  
The water heater MUST be isolated from the gas piping system  
by closing the manual gas shut-off valve during any pressure test-  
ing of the gas supply piping at pressures equal to or less than  
1/2 psi (14” w.c. / 3.5 kPa).  
If the water heater is being installed as a replacement for an existing  
power vented water heater, a thorough inspection of the existing venting  
system must be performed prior to any installation work. Verify that the  
correct materials, as detailed above have been used, and that the mini-  
mum or maximum vent length and terminal locations as detailed in this  
manual have been met. Carefully inspect the entire venting system for  
any signs of cracks or fractures, particularly at the joints between elbows  
or other fittings and the straight runs of vent pipe. Check the system for  
signs of sagging or other stresses in the joints as a result of misalignment  
of any components in the system. If any of these conditions are found,  
they must be corrected in accordance with the venting instructions in this  
manual before completing the installation and putting the water heater  
into service.  
5. VENTING —  
WARNING  
!
The water heater must be vented to the outdoors as described  
in these instructions. DO NOT connect this water heater to an  
existing Vent or Chimney it must be vented separately from all  
other appliances.  
VENT PIPE CONNECTION —  
WARNING  
!
Outlet  
Vent Connection  
Failure to properly vent the water heater to the outdoors as outlined  
above and in the following section can result in unsafe operation of  
the water heater causing bodily injury, explosion, fire or death.  
Inlet  
Vent Connection  
WARNING  
!
To avoid the risk of fire, explosion or asphyxiation from carbon  
monoxide, NEVER operate this water heater unless it is properly  
vented and has an adequate air supply for proper operation. The  
vent pipe must overlap a minimum of ½" on each connection. it is  
important that the vent pipe engages fully into any pipe fitting and  
be kept in that position until the adhesive has fully cured. DO NOT  
drill or punch holes in the plastic pipe or fittings.  
Figure 5.  
Vent Pipe Connection locations  
The blower assembly is preinstalled at the factory, so all that is required  
for connecting the vent system is attaching the vent pipe to the blower  
and the PVC Tee. Before starting the vent installation, careful planning  
should be given to the routing and termination of the vent pipe.The length  
of the vent pipe (inlet and outlet) should be kept to a minimum. Also, see  
page 10 & 12 for vent terminal placement.The GP100-150 & GP100-200  
model can be vented using either 3 inch or 4 inch Schedule 40 PVC pipe  
and fittings.  
NOTICE: This unit can be vented using only the following  
recommended pipe material. Use only 3- or 4-inch diameter pipe.  
PVC (Schedule 40, ASTM D-1785)  
CPVC (Schedule 40, ASTM F-441)  
ABS (Schedule 40, ASTM D-2661)  
To use 3 inch PVC, you can connect directly to the blower outlet (rubber  
coupling provided for outlet connection) and PVC Tee. Make sure that  
clamps on rubber coupling are tight, after the pipe is installed. The inlet  
vent pipe should be cemented into the PVC Tee.  
The fittings, other than the VENT TERMINAL, should be equiva-  
lent to the following:  
PVC (Schedule 40 DWV, ASTM D-2665)  
CPVC (Schedule 40 DWV, ASTM F-438)  
ABS (Schedule 40 DWV, ASTM D-2661)  
If 4 inch PVC pipe is going to be used, then it will be necessary to have  
a short piece ( at least 3 inches long ) of 3 inch PVC pipe to join into the  
coupling and tee. Then a 4 X 3 reducer would need to be joined to the  
short piece of pipe, so that the 4 inch pipe could be used.The 4 inch pipe  
will then need to be stepped back down, using a 4 X 3 reducer, to 3 inch  
PVC. To install the vent terminals, a short length of 3 inch (maximum of  
16 inches long) pipe will need to be used. (Refer to Figure 9b on page  
10.)  
The GP100-250 model can only be vented using 4 inch Schedule 40 PVC  
pipe and fittings. The 4 inch pipe can be connected directly to the blower  
coupling and 4 inch tee.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
miNimUm AND mAximUm VENT lENgThS  
Charts are for installation from 0 - 2000 ft. elevation ONLY. (Please see supplement sheet for installations above 2000 feet.)  
NOTICE: Be sure to mount inlet vent terminal 6 inches higher than the outlet vent terminal. Vent terminals need to be a minimum of 7 inches  
(center to center) horizontally apart and a maximum of 24 inches apart.  
gP100-250  
Venting Information for 4” Vents  
gP100-150 & gP100-200  
Venting Information for 3” Vents  
Number of 90º Elbows with  
Vent Terminal  
Minimum Pipe Maximum  
Length Required Pipe Length  
Number of 90º Elbows with  
Vent Terminal  
Minimum Pipe Maximum  
Length equired Pipe Length  
Number of  
45º Elbows  
Number of  
45º Elbows  
(Ft)  
10.0  
7.5  
5.0  
2.5  
5.0  
2.5  
5.0  
2.5  
(Ft)  
Inlet Vent  
Outlet Vent  
One (1)  
(Ft)  
5.0  
2.5  
5.0  
2.5  
5.0  
2.5  
5.0  
2.5  
(Ft)  
Inlet Vent  
Outlet Vent  
One (1)  
One (1)  
One (1)  
Two (2)  
None  
One (1)  
None  
45.0  
42.5  
40.0  
37.5  
35.0  
32.5  
30.0  
27.5  
One (1)  
One (1)  
Two (2)  
None  
One (1)  
None  
40.0  
37.5  
35.0  
32.5  
30.0  
27.5  
25.0  
22.5  
One (1)  
Two (2)  
One (1)  
Two (2)  
Two (2)  
Two (2)  
One (1)  
None  
Two (2)  
Two (2)  
One (1)  
None  
Three (3)  
Three (3)  
Four (4)  
Four (4)  
Three (3)  
Three (3)  
Four (4)  
Four (4)  
Three (3)  
Three (3)  
Four (4)  
Four (4)  
Three (3)  
Three (3)  
Four (4)  
Four (4)  
One (1)  
None  
One (1)  
None  
One (1)  
Vent lengths for the inlet and the outlet pipes should not have a  
difference of more than five (5) equivalent feet.  
One (1)  
Vent lengths for the inlet and the outlet pipes should not have a dif-  
ference of more than five (5) equivalent feet.  
GP100-250 can only be vented with four (4) inch PVC pipe and fit-  
tings. Use only the vent terminals supplied withthe water heater  
Venting Information for 4” Vents  
HORIZONTAL VENT TERMINAL LOCATION - The location of the  
vent terminal depends on the minimum clearances and consider-  
ations shown in the charts on pages 11 and 12..  
Number of 90º Elbows with  
Vent Terminal  
Minimum Pipe Maximum  
Length Required Pipe Length  
Number of  
45º Elbows  
(Ft)  
10.0  
9.5  
5.0  
2.5  
5.0  
2.5  
5.0  
2.5  
(Ft)  
Inlet Vent  
One (1)  
Outlet Vent  
One (1)  
None  
One (1)  
None  
50.0  
47.5  
45.0  
42.5  
40.0  
37.5  
35.0  
32.5  
One (1)  
Two (2)  
One (1)  
Two (2)  
Two (2)  
Two (2)  
One (1)  
None  
Three (3)  
Three (3)  
Four (4)  
Four (4)  
Three (3)  
Three (3)  
Four (4)  
Four (4)  
One (1)  
None  
One (1)  
Vent lengths for the inlet and the outlet pipes should not have a differ-  
ence of more than five (5) equivalent feet.  
NOTICE: 3” and 4” vent pipe should not be mixed, other than  
to reduce the 4” vent for the 3” PVC Vent Terminal. This unit  
is supplied with two (2) 3-inch Schedule 40 PVC 45º vent  
terminals.  
The 4” vent pipe can use up to 16 inches of 3” PVC, preceding  
the vent terminal. This unit uses the same vent terminals (sup-  
plied with the unit) for both 3” and 4” pipe. A 4” to 3” reducer  
will be required to go from 4” to 3” pipe.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
installation  
gP100-150 & gP100-200  
Additional Considerations (See Figure 9)  
Sheet Metal Shield on Brick or  
Masonry Walls  
1. Do Not install vent terminal under any patio or deck.  
§
Mortar or  
Silicone Caulk  
§
§
2. To help prevent moisture from freezing on walls and  
under eaves, do not locate vent terminal on the side of a  
building with prevailing winter winds.  
3” Pipe  
Coupling  
3Vent  
Pipe  
Vent Terminal with 1/2  
Mesh Protective  
Screen Inside  
"
§
§
3. Do Not terminate vent pipe directly on brick or masonry  
surfaces. Use a rust-resistant sheet metal backing plate  
behind vent. (See Figure 9.)  
3Vent  
Pipe  
3” Pipe  
Coupling  
4. Do Not locate vent terminal too close to shrubbery,  
since flue gases may damage them.  
§
§
Outside of  
Building Wall  
From Water  
Heater  
5. Caulk all cracks, seams and joints within six (6) feet of  
vent terminal.  
Figure ꢀa – Typical horizontal 3Vent installation  
6. All painted surfaces should be primed to lessen the  
chance of physical damage. Painted surfaces will require  
maintenance.  
Sheet Metal Shield on Brick or  
Masonry Walls  
§
Mortar or  
Silicone Caulk  
§
§
4x3 Reducer  
7. Insulate vent pipe exposed to cold conditions (attics,  
crawl spaces, etc.) to help prevent moisture from accu-  
mulating in vent pipe.  
Coupling  
4Vent  
Pipe  
§
Vent Terminal with 1/2  
Mesh Protective  
Screen Inside  
"
§
4x3 Reducer  
Coupling  
3Vent  
Pipe  
WARNING  
!
From  
moisture in the flue gas will condense as it leaves the  
vent terminal. in cold weather this condensate can  
freeze on the exterior wall, under the eaves and on  
surrounding objects. Some discoloration to the  
exterior of the building is to be expected. however,  
improper location or installation can result in se-  
vere damage to the structure or exterior finish of the  
building.  
Water  
Heater  
§
§
Outside of  
Building Wall  
Figure ꢀb – Typical horizontal 4Vent installation  
gP100-250  
Sheet Metal Shield on Brick or  
Masonry Walls  
§
Mortar or  
Silicone Caulk  
§
§
Inlet  
4” Pipe  
Coupling  
Inlet Min. 6”  
above  
outlet  
Short Piece of Vent Pipe  
4Vent  
Pipe  
Vent Terminal with 1/2  
Mesh Protective  
Screen Inside  
"
§
§
Outlet  
4Vent  
Pipe  
4” Pipe  
Coupling  
§
§
Outside of  
Building Wall  
From Water  
Heater  
Min. 12" Above Roof  
Vent Pipe  
Through Roof  
Min. 12" Above Anticipated  
Snow Level.  
Figure ꢀc – Typical horizontal 4Vent installation  
Max. 24" Above Roof  
Elbows  
(Without Additional Support)  
Figure 8 – Vertical Vent Terminal location  
HORIZONTAL VENT INSTALLATION – Once the vent terminal  
location has been determined, make a hole through the exterior wall to  
accommodate the vent pipe.Vent pipe must exit exterior wall horizontally  
only. (See Figures 9a and 9b.)  
Min. 7”  
Max. 24”  
Insert a small length of vent pipe through the wall and connect the  
coupling as shown in Figure 9. Connect terminal as shown to the vent  
pipe on the exterior of the building. Seal any opening around the vent  
pipe or fittings with mortar or silicone caulk as shown in Figures 9a and  
9b.  
Complete the rest of the vent pipe installation to the water  
heater’s vent connector fitting on the blower outlet. If  
necessary support horizontal run as previously mentioned.  
Inlet  
Outlet  
6” above outlet  
Figure 6  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
installation  
VERTICAL VENT INSTALLATION – Once the vent termi-  
3. Maximum twenty-four (24) inches above roof level without  
additional support for vent pipe.  
nal location has been determined, make a hole through the  
roof and interior ceiling to accommodate the vent pipe. Com-  
plete the vent pipe installation to the water heater’s vent  
connector fitting on the blower outlet. Support vertical or  
horizontal runs as previously mentioned.  
4. Four (4) feet from any gable, dormer or other roof structure with  
building interior access (i.e., vent, window, etc.).  
5. Ten (10) feet from any forced air inlet to the building. Any  
fresh or make-up air inlet such as a dryer or furnace area is  
considered to be a forced air inlet.  
Install adequate flashing where the vent pipe passes through the  
roof. Determine the vent terminal height and cut vent pipe ac-  
cordingly. Refer to Fig. 8 for proper vent terminal height. Connect  
vent elbow onto vertical pipe through roof. Connect short piece  
6. The inlet is a minimum of six (6) inches vertically above the outlet.  
of vent pipe (approximately 3  
to the short piece of vent pipe.  
"
long) to elbow, then join terminal  
7. Terminals are a minimum of seven (7) inches horizontally apart with  
a maximum of twenty-four (24) inches.  
VERTICAL VENT TERMINAL LOCATION – The location of  
vertical vent terminal depends on the following considerations  
(see Figure 8):  
VENT INSTALLATION – Before proceeding, make certain you  
understand the procedure and cautions covered in the section  
“Joining Pipes and Fittings.”  
1. Minimum twelve (12) inches above roof.  
2. Minimum twelve (12) inches above anticipated snow level.  
AREA WHERE TERMINAL IS NOT PERMITTED  
AIR SUPPLY INLET  
VENT TERMINAL  
X
V
Horizontal Vent Terminal Location  
The following information should be used for determining the proper location of the vent terminal  
for direct vent water heaters.  
1
2
Canadian Installations  
US Installations  
A= Clearance above grade, veranda,  
porch, deck or balcony.  
12 inches (30 cm) above anticipated  
snow level.  
12 inches (30 cm) above anticipated  
snow level.  
B= Clearance to window or door that may 6 inches (15 cm) for appliances < 10,000  
6 inches (15 cm) for appliances < 10,000  
be opened.  
Btuh (3 kW), 12 inches (30 cm) for appli- Btuh (3 kW), 9 inches (23 cm) for appli-  
ances > 10,000 Btuh (3kW) and < 100,000 ances > 10,000 Btuh (3 kW) and  
Btuh (30kW), 36 inches (91 cm) for appli- < 50,000 Btuh (15 kW), 12 inches  
ances > 100,000 Btuh (30kW).  
(30 cm) for appliances > 50,000 Btuh  
(15 kW).  
C= Clearance to permanently closed  
window.  
*
*
D= Vertical Clearance to ventilated soffit  
located above the terminal within a  
horizontal distance of 2 feet (61 cm)  
from the center line of the terminal.  
3 feet (91 cm)  
3 feet (91 cm)  
E= Clearance to unventilated soffit.  
F= Clearance to outside corner.  
G= Clearance to inside corner.  
*
*
*
*
18 inches (46 cm)  
18 inches (46 cm)  
Figure 9 - Horizontal Vent Terminal Location  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
2
Canadian Installations  
US Installations  
H = Clearance to each side of center line  
extended meter/regulator assembly.  
above  
3 feet (91 cm) within a height 15 feet (4.57  
m) above the meter/regulator assembly.  
*
I = Clearance to service regulator vent  
outlet.  
3 feet (91 cm)  
*
J = Clearance to nonmechanical air supply 6 inches (15 cm) for appliances < 10,000  
4 feet (1.2 m) below or to side of opening;  
Btuh (3 kW), 12 inches (30 cm) for appli- 1 foot (300 mm) above opening.  
ances > 10,000 Btuh (3kW) and  
< 100,000 Btuh (30kW), 36 inches (91 cm)  
inlet to the combustion air inlet to any  
building or other appliance.  
for appliances > 100,000 Btuh (30kW).  
6 feet (1.83 m)  
7 feet (2.13 m)  
3 feet (91 cm) above if within 10 feet  
(3 m) horizontally.  
K = Clearance to mechanical air supply  
inlet.  
L = Clearance above paved side walk or  
paved driveway located on public  
property.  
7 feet (2.13 m)  
M = Clearance under veranda, porch, deck  
or balcony.  
Not Allowed  
Not Allowed  
1 In accordance with current CAN/CGA-B149 Installation Codes.  
2 In accordance with current ANSI Z223.1/ NFPA 54 National Fuel Gas Code.  
+ A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.  
* If clearances are not specified then follow local installation codes and the requirement of the gas supplier.  
DRAINING THE CONDENSATE – In certain conditions,  
installations in unconditioned space or having long horizontal or vertical  
runs may accumulate condensate. In order to prevent condensate from  
draining back into the blower, we recommend that it be drained. This  
unit is provided with a special fitting on the blower that allows for the  
draining of condensate formed in the vent. The drain hose should have  
two (2) loops formed, to act as traps. Before operation of the water  
heater, both loops should have water placed in them. Support the traps  
so that they remain horizontal. Condensate is known to be acidic; refer  
to local, state or federal codes for proper handling methods.  
PVC materials should use ASTM D-2564 grade cement.  
CPVC materials should use ASTM F-493 grade cement.  
ABS materials should use ASTM D-2235 grade cement.  
Cleaner-Primer and Medium Body Solvent Cement  
1. Cut pipe end square, remove jagged edges and burrs. Cham-  
fer end of pipe, then clean fitting socket and pipe joint area  
of all dirt, grease or moisture.  
2. After checking pipe and socket for proper fit, wipe  
socket and pipe with cleaner-primer. Apply a liberal coat of  
primer to inside surface of socket and outside of pipe. Do not  
allow primer to dry before applying cement.  
3. Apply a thin coat of cement evenly in the socket. Quickly  
apply a heavy coat of cement to the pipe end and in-  
sert pipe into fitting with a slight twisting motion until it  
bottoms out.  
NOTICE: Cement must be fluid; if not, recoat.  
Figure 10 - Draining the Condensate  
4. Hold the pipe fitting for 30 seconds to prevent the tapered  
socket from pushing the pipe out of the fitting.  
JOINING PIPES AND FITTINGS – All pipe, fittings, solvent  
cement, primers and procedures must conform to Ameri-  
can National Standards Institute and American Society for  
Testing and Materials (ANSI/ASTM) standards.  
5. Wipe all excess cement from the joint with a rag. Allow 15  
minutes before handling. Cure time will vary according to fit,  
temperature and humidity.  
NOTICE: Stir the solvent cement frequently while using. Use  
a natural bristle brush or the dauber supplied with the can.  
The proper brush size is one inch.  
CEMENTING JOINTS – All joints in the vent piping must  
be properly sealed and we recommend using the following mate-  
rial:  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR PROPER iNSTAllATiON:  
Avoid skin or eye contact. Observe all cautions  
and warnings on material containers.  
CAUTION  
!
6. WIRING — A polarized 120V 50/60 Hz power supply, with suitable  
disconnect means, must be connected to the black and white leads  
provided. The current draw by the Power Direct Vent unit is 1.5 Amps.  
The water heater, when installed, must be electrically grounded in ac-  
cordance with local codes, or, in the absence of local codes, with the  
National Electrical Code, ANSI/NFPA 70 in the United States; or CSA  
C22.1 Electrical Code, in Canada. Refer to Fig. 14 on page 26 & 27  
of this manual for water heater internal wiring diagrams.  
DO NOT use solvent cement that has become  
curdled, lumpy or thickened.  
DO NOT thin solvent cement. Observe shelf  
precautions printed on the containers.  
For applications below 32°F use only low  
temperature type solvent cement.  
Appropriate solvent and cleaner must be used for  
the type of vent pipe used (PVC, CPVC or ABS).  
NOTICE: DO NOT use in conjunction with a GFCI.  
WARNING  
!
DANgER OF FiRE OR BODilY iNJURY – Solvent  
cements and primers are highly flammable. Pro-  
vide adequate ventilation and do not assemble  
near heat source or open flame. Do not smoke.  
installation Check list  
C. Gas Supply  
A. Water Heater Location  
Close to area of vent.  
Gas line equipped with shut-off valve, union, and sediment  
trap/drip leg.  
Indoors and protected from freezing temperatures.  
Approved pipe joint compound used.  
Proper clearance from combustible surfaces observed and  
water heater not installed on carpeted floor.  
Soap and water solution used to check all connections and  
fittings for possible gas leak.  
Air supply free of corrosive elements and flammable vapors.  
Provisions made to protect area from water damage.  
Sufficient room to service heater.  
Gas Company inspected installation (if required).  
D. Relief Valve  
Discharge line run to open drain.  
B. Water Supply  
Discharge line protected from freezing.  
Water heater completely filled with water.  
E. Venting  
Water heater and piping air vented.  
All pipe connections are secure (at blower, vent terminals and for  
each pipe joint connection)  
Water connections tight and free of leaks.  
Vent terminals mounted properly and in correct location.  
Condensate tube has water in both loops.  
TABlE 1  
maximum Capacity of Pipe in Cubic Feet of gas per hour for gas Pressures of  
--------0.5 psig or less and a Pressure Drop of 0.3 inch Water Column  
Based on a 0.60 Specific gravity Natural gas; if 1.5 Specific gravity l.P. gas is used, multiply capacity by 0.63  
Nominal  
internal  
Diameter  
inches  
.622  
.824  
1.04ꢀ  
1.380  
1.610  
2.067  
2.46ꢀ  
Length of Pipe, Feet  
iron Pipe Size,  
inches  
1/2  
3/4  
1
1 1/4  
1 1/2  
2
10  
132  
278  
20  
ꢀ2  
1ꢀ0  
350  
730  
1,100  
2,100 1,650  
3,300 2,700  
5,ꢀ00 4,700  
30  
73  
152  
285  
5ꢀ0  
8ꢀ0  
40  
63  
130  
245  
500  
760  
1,450 1,270  
2,300 2,000  
4,100 3,600  
8,300 7,400  
50  
56  
115  
215  
440  
670  
60  
50  
70  
46  
80  
43  
ꢀ0  
40  
84  
160  
320  
4ꢀ0  
ꢀ30  
100  
38  
125  
34  
150  
31  
175  
28  
200  
26  
105  
1ꢀ5  
400  
610  
ꢀ6  
ꢀ0  
170  
350  
530  
ꢀꢀ0  
7ꢀ  
72  
64  
5ꢀ  
55  
520  
180  
370  
560  
150  
305  
460  
870  
1,400 1,250  
2,500 2,200  
5,100 4,500  
130  
275  
410  
780  
120  
250  
380  
710  
1,130  
2,000  
4,100  
110  
225  
350  
650  
1,050  
1,850  
3,800  
100  
210  
320  
610  
ꢀ80  
1,700  
3,500  
1,050  
1,600  
3,050  
4,800  
8,500  
1,150 1,050  
2 1/2  
3
1,850 1,700 1,600 1,500  
3,250 3,000 2,800 2,600  
6,800 6,200 5,800 5,400  
3.068  
4.026  
4
17,500 12,000 ꢀ,700  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Before operating this water heater, be sure to read and follow the instructions on the label pictured below and all other labels on the water  
heater, as well as the warnings printed in this manual. Failure to do so can result in unsafe operation of the water heater resulting in prop-  
erty damage, bodily injury, or death. Should you have any problems reading or following the instructions in this manual, STOP, and get  
help from a qualified person.  
1. LIGHTING PROCEDURE - Lighting procedures are outlined on the label pictured below. This label is also located on the water heater near the thermostat.  
NOTICE: The Gas Valve supplied with this water heater may vary from the one pictured on the label below, but the Lighting Instructions are the same for all  
types of valves supplied with this model water heater.  
FORYOURSAFETYREADBEFOREOPERATING  
WARNING: Ifyoudonotfollowtheseinstructionsexactly, afireorexplosionmay  
resultcausingpropertydamage,personalinjuryorlossoflife  
A. This appliance is equipped with an ignition  
device which automatically lights the pilot. DO  
NOT try to light the pilot by hand.  
B. BEFORE OPERATI NG smell all around the  
appliance area for gas. Be sure to smell next to  
the floor because some gas is heavier than air  
and will settle on the floor.  
• If you cannot reach your gas supplier, call  
the fire department.  
C .Use only your hand to turn the gas control knob.  
Never use tools. If the knob will not turn by hand,  
don't try to repair it, call a qualified service  
technician. Force or attempt to repair may result  
in a fire or explosion.  
D.Do not use this appliance if any part has been  
under water. Immediately call a qualified ser-  
vice technician to inspect the appliance and to  
replace any part of the control system and any  
gas control which has been under water.  
WHAT TO DO IF YOU SMELL GAS  
• Do not try to light any appliance  
• Do not touch any electrical switch; do not use  
any phone in your building.  
Immediately call your gas supplier from a  
neighbor's phone. Follow the gas supplier's  
instructions.  
OPERATINGINSTRUCTIONS  
1. STOP! READ THE SAFETY INFORMATI ON  
ABOVE ON THIS LABEL.  
5. TURN THE "GAS COCK KNOB" CLOCKWISE  
TO "OFF."  
2.  
USING A SLOTTED SCREW DRIVER — INSERT  
INTO TEMPERATURE ADJUSTMENT OPEN-  
ING. TURN SCREW CLOCKWISE  
LOWEST SETTING  
6. WAIT FIVE (5) MINUTES TO CLEAR OUT  
ANY GAS. IF YOU THEN SMELL GAS, STOP!  
FOLLOW "B" IN THE SAFETY INFORMATI ON  
ABOVE ON THIS LABEL. IF YOU DON'T  
SMELL GAS, GO TO NEXT STEP.  
TO THE  
7. TURN "GAS COCK KNOB" COUNTER-  
CLOCKWISE  
TO "ON".  
THERMOSTAT  
ON  
OFF  
8. TURN ON ALL ELECTRIC POWER TO THE  
APPLIANCE.  
INDEX  
GAS COCK  
KNOB  
TEMPERATURE  
ADJUSTMENT  
SCREW  
GAS VALVE  
9. SET THERMOSTAT TO DESIRED SETTING  
10. IF THE APPLIANCE WILL NOT OPERATE ,  
FOLLOW THE INSTRUCTIONS "TO TURN  
OFF GAS TO APPLIANCE" AND CALL YOUR  
SERVICE TECHNICIAN OR GAS SUPPLIER.  
3. TURN OFF ALL ELECTRIC POWER TO THE  
APPLIANCE.  
4. THIS APPLIANCE IS EQUIPPED WITH AN IGNITION  
DEVICE WHICH AUTOMATICALLY LIGHTS THE  
PILOT.DO NOT TRY TO LIGHT THE PILOT BY HAND.  
TOTURNOFFGASTOAPPLIANCE  
1. SET THE THERMOSTAT TO LOWEST SETTING. 3. TURN THE "GAS COCK KNOB" CLOCKWISE  
TO "OFF".  
2. TURN OFF ALL ELECTRIC POWER TO THE  
APPLIANCE IF SERVICE IS TO BE PERFORMED.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Before operating this water heater, be sure to read and follow the instructions on the label pictured below and all other labels on the water  
heater, as well as the warnings printed in this manual. Failure to do so can result in unsafe operation of the water heater resulting in prop-  
erty damage, bodily injury, or death. Should you have any problems reading or following the instructions in this manual, STOP, and get  
help from a qualified person.  
1. LIGHTING PROCEDURE - Lighting procedures are outlined on the label pictured below. This label is also located on the water heater near the thermostat.  
NOTICE: The Gas Valve supplied with this water heater may vary from the one pictured on the label below, but the Lighting Instructions are the same for all  
types of valves supplied with this model water heater.  
FOR YOUR SAFETY READ BEFORE OPERATING  
WARNING: If youdonot followthese instructionsexactly, a fire or explosion  
may result causing propertydamage, personal injury or loss of life.  
A. This appliance is equipped with an ignition  
device which automatically lights the pilot. DO  
NOT try to light the pilot by hand.  
• If you cannot reach your gas supplier, call  
the fire department.  
B. BEFORE OPERATING smell all around the  
appliance area for gas. Be sure to smell next to  
the floor because some gas is heavier than air  
and will settle on the floor.  
C. Use only your handtoturnthe gas controlknob.  
Never use tools. If theknobwill not turnbyhand,  
don'ttry to repair it, call a qualified service  
technician. Force or attemptedrepair may result  
in a fire or explosion.  
D. Do not use this appliance if any part has been  
under water. Immediately call a qualified ser -  
vice technician to inspect the appliance and to  
replace any part of the control system and any  
gas control which has been under water.  
WHAT TO DO IF YOU SMELL GAS  
• Do not try to light any appliance  
• Do not touch any electric switch; do not use  
any phone in your building.  
• Immediately call your gas supplier from a  
neighbor's phone. Follow the gas supplier's  
instructions.  
OPERATING INSTRUCTIONS  
STOP! READ THE SAFETY INFORMATION  
ABOVE ON THIS LABEL.  
1.  
TURN THE "GAS CONTROL KNOB" CLOCK-  
5.  
WISE  
TO " OFF".  
2. REMOVE OUTER COVER. USING A SLOTTED  
SCREWDRIVER - INSERT INTO SLOT IN CENTER  
OF DIAL. TURN DIAL COUNTERCLOCKWISE  
6. WAIT FIVE (5) MINUTES TO CLEAR OUT ANY  
GAS. IF YOU THEN SMELL GAS, STOP! FOL-  
LOW "B" IN THE SAFETY INFORMATION  
ABOVE ON THIS LABEL. IF YOU DON'T SMEL L  
TO THE LOWEST SETTING .  
THERMOST AT  
Honeywell  
GAS,  
GO TO NEXT STEP.  
7. TURN THE "GAS CONTROL KNOB" COUNTER-  
CLOCKWISE TO "ON".  
TEMPERATURE  
ADJUSTMENT  
DIAL  
Index  
NOTE: Thermostat  
shown with cover  
removed .  
8. TURN ONALL ELECTRIC POWER TO THE  
APPLIANCE.  
Ga s C ock  
Knob  
GAS VA LV E  
9. SET THERMOSTAT TO D ESIRED SETTING.  
INSTAL L OUTER COVER.  
3. TURN OFF ALL ELECTRIC POWER TO TH E  
APPLIANCE.  
4. THIS APPLIANCE IS EQUIPPED WITH AN  
IGNITION DEVICE WHICH AUTOMATICALLY  
LIGHTS THE PILOT. DO NOT TRY TO LIGHT THE  
10. IF THE APPLIANCE WILL NOTOPERATE, FOL-  
LOW THE INSTRUCTIONS "TO TURN OFF GAS  
TO APPLIANCE" AND CALL YOUR SERVICE  
PILOT  
BY HAND.  
TECHNICIAN  
OR GAS SUPPLIER.  
TO TURN OFF GAS TO APPLIANCE  
1. TURN OFF ALL ELECTRIC POWER TO THE 3. TURN THE "GAS CONTROL KNOB" CLOCK-  
APPLIANCE IF SERVICE IS TO BE PERFORMED.  
2. SET THE THERMOSTA T TO LOWEST SETTING.  
WISE TO "OFF" .  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
SAFETY PRECAUTIONS  
A. Do turn off manual gas shut-off valve if water heater has been sub-  
E. Do not allow combustible materials such as newspaper, rags or  
mops to accumulate near water heater.  
jected to over heating, fire, flood, physical damage or if gas supply  
fails to shut off.  
F. If there is any difficulty in understanding or following the OPERA-  
TION or MAINTENANCE instructions, it is recommended that a  
qualified person or serviceman perform the work.  
B. Do Not turn on water heater unless it is filled with water.  
C. Do Not turn on water heater if cold water supply shut-off valve is  
closed.  
CAUTION  
!
hydrogen gas can be produced in a hot water system served by  
this water heater that has not been used for a long period of time  
(generally two weeks or more). hYDROgEN gAS iS ExTREmElY  
FlAmmABlE!!To dissipate such gas and to reduce risk of injury,  
it is recommended that the hot water faucet be opened for several  
minutes at the kitchen sink before using any electrical appliance  
connected to the hot water system. if hydrogen is present, there  
will probably be an unusual sound such as air escaping through  
the pipe as the water begins to flow. Do not smoke or use an  
open flame near the faucet at the time it is open.  
D. Do Not store or use gasoline or other flammable vapors and liquids,  
such as adhesives or paint thinner, in vicinity of this or any other  
appliance. If such flammables must be used, open doors and win-  
dows for ventilation, and all gas burning appliances in vicinity should  
be shut off, including their pilot lights, to avoid vapors igniting.  
NOTICE: Flammable vapors may be drawn by air currents from sur-  
rounding areas to the water heater.  
2. TEMPERATURE SETTINGS — The thermostat is adjusted to its lowest  
temperature position when shipped from the factory. To meet com-  
mercial water use needs, it is adjustable up to 180°F (82°C). How-  
ever, water temperatures over 125°F (52°C) can cause severe burns  
instantly or death from scalds. This is the preferred starting point for  
setting the control for supplying general purpose hot water.  
WARNING  
!
When this water heater is supplying general purpose hot water  
requirements for individuals, a thermostatically controlled mixing  
valve for reducing point of use water temperature is recommend-  
ed. Contact a licensed plumber or the local plumbing authority for  
further information.  
Safety and energy conservation are factors to be considered when  
setting the water temperature on the thermostat. The most energy ef-  
ficient operation will result when the temperature setting is the lowest  
that satisfies the needs consistent with the application.  
Outlet water temperature will vary during normal operating cycles. Reli-  
able temperature readings should be taken shortly after main burner  
cycles off during a period of little or no use.  
hotter water increases the Potential for hotWater SCAlDS.  
3. GAS MANIFOLD PRESSURE — With the gas valve supplied with this  
water heater, main burner ignition occurs at a low or step manifold  
pressure, which will then automatically build up to its normal operat-  
ing level .The rated operating manifold pressure is listed on the water  
heater rating plate. For purposes of input adjustment, the minimum inlet  
gas pressure(with main burner on) is also shown on the rating plate.  
A 1/8” NPT tapping is provided on the outlet side of the gas valve for  
connecting a manometer to check this pressure. If necessary, adjust  
the pressure to the proper value by turning regulator adjustment screw  
clockwise to increase pressure or counterclockwise to decrease pres-  
sure.  
DANGER  
!
4. CHECK INPUT — Consult the local Gas Company to determine the  
heating value of the gas supplied. Check input by clocking gas meter with  
all other gas appliances turned off. Use the following formula:  
F
To adjust the water temperature, insert a small straight  
screwdriver into slotted screw in hole in front of ther-  
mostat and turn wheel to desired setting. Thermostat  
is adjustable up to 180º F.  
(3,600) x (Heating Value) x (Number of Cubic Feet Timed)  
INPUT (btu/h) =  
Seconds Clocked  
WARNING  
!
CAUTiON!! - hotter water increases the risk of SCAlDiNg!  
THERMOSTAT  
DO NOT exceed input shown on the water heater's rating plate!  
White-Rodgers  
honeywell  
Figure 11. Thermostat adjustment  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
To insure accuracy for rating, clock enough cubic feet of gas so that  
7. EMERGENCY SHUTDOWN —  
the clocked time is at least 60 seconds.  
Small adjustments can be made by varying the manifold pressure from  
the designated settings mentioned above.  
WARNING  
!
Should overheating occur or the gas supply fail to shut off, turn off  
the manual gas control valve to the appliance.  
5. INTERMITTENT PILOT FLAME ADJUSTMENT — No adjustment is  
required with normal inlet gas pressures. The pilot flame adjustment  
valve is pre-set, and does not normally require re-adjustment.  
WARNING  
!
6. HIGH ALTITUDE — Ratings of gas appliances are based on installation  
and operation at sea level of elevations of 2000 feet.  
DO NOT use this appliance if any part has been under water. imme-  
diately call a qualified service technician to inspect the appliance  
and to replace any part of the control system and any gas control  
which has been under water.  
Factory prepared high altitude models are available and are specifically  
rated for installation at elevation up to 8000 feet. Refer to rating plate  
on the front of the water heater for number and altitude specifications.  
Also refer to the supplement sheet for information on venting high  
altitude models.  
If the water heater has been subjected to fire or physical damage, turn  
off gas at the manual gas control (shut-off) valve. Do not operate the  
water heater again until it has been checked out by a qualified service  
technician.  
maintenance  
Properly maintained, this water heater will provide years of dependable,  
trouble free service. It is strongly suggested that a regular routine main-  
tenance program be established and followed by the owner. It is further  
recommended that a periodic inspection of the blower, thermostat, burner,  
relief valve, internal flueway, draft hood / damper assembly and venting  
system should be made by service technicians qualified in gas appliance  
repair.  
TO REMOVE BURNERTRAY:  
1. Turn off manual gas shut-off valve.  
2. Disconnect gas pipe union and wiring to gas valve and pilot.  
3. Remove retaining screws from plate on the same side as the gas  
valve.  
4. Slide burner tray assembly out. When reinstalling the burner tray  
assembly, make certain it is pushed in all the way so that the plate  
lines up with the holes in the plenum side.Then reinstall the retain-  
ing screws.  
1. ROUTINE PREVENTIVE MAINTENANCE  
A. BURNERS — Visually inspect the main burner flame and the pilot flame  
at least every three months. Refer to Figures 12 and 13 for normal  
flame pattern. Fallen scale can usually be dislodged from the tops of  
the burners with a thin rod, then vacuumed or brushed from the bottom  
of the burner box. If a more thorough cleaning is deemed necessary  
to restore a normal flame pattern, the burner tray assembly should be  
removed and the burners cleaned individually.  
5. Reconnect gas pipe union and wiring to gas valve and pilot, turn  
on manual gas shut-off valve and test for gas leak.  
B. VENTING SYSTEM — Inspect venting system at least yearly to make  
certain the passageways are free and unobstructed, and that the vent  
connector from the water heater’s blower assembly is properly posi-  
tioned and securely attached. Remove any obstructions in vent con-  
nector or vent terminal.  
CAUTION  
!
C. CONTROLS — The manifold pressure and controls should be checked  
at least yearly by a qualified service technician.  
For your safety, removal and cleaning of burner tray and individual  
burners should be performed ONlY by a qualified service techni-  
cian, as it involves disconnection of gas piping and leak testing.  
Figure 13. — Pilot & main Burner Flame Pattern  
Figure 12. — Pilot Flame Pattern  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
maintenance  
D. BLOWER — Clean the blower periodically to remove any buildup of  
lint or dirt. Remove the inlet plate and blow out any lint or dirt on the  
wheel and on the screen of the inlet plate. Before operation, re-install  
the inlet plate to the blower.  
A wet-dry shop vac with a nozzle fashioned from 1” and/or 3/4” poly-  
ethylene pipe makes a good tool for scraping and removing scale.  
TO CLEAN OR INSPECT TANK:  
1. Shut off gas valve and drain tank.  
E. PRESSURE SWITCH — Inspect the inlet to the pressure switch and  
the tubing for debris or blockage. Clean out the tubing periodically to  
prevent buildup of debris.  
2. Remove tank clean-out cover on jacket and with pocket knife cut  
and remove a circular plug of insulation the full size of jacket open-  
ing.  
F. EMERGENCY CUT-OFF — This water heater is equipped with a com-  
bination thermostat/temperature limiting device (ECO) that should be  
checked annually by qualified service personnel.  
3. Loosen nut on seal plate assembly enough to twist yoke sideways.  
Hold assembly securely and push inward, then remove from tank.  
G. THERMAL CUTOFF SWITCH — Some units are equipped with a  
thermal cutoff switch which will shut down the unit if the flue gas tem-  
perature is above permissible limits. The switch is a manual reset  
type.  
4. Remove as much built-up scale from flue tubes and tank bottom as  
practical. Do not attempt to clean so thoroughly that the tool used  
damages the glass lining.  
CAUTION  
!
5. Clean the seal plate and install a new gasket. Wipe clean the inte-  
rior surface of the tank that contacts the gasket. Reinstall the seal  
plate and tighten in position. Fill tank with water and check for leaks.  
If no leaks are found, install insulation plug and clean-out cover on  
jacket and re-light the water heater.  
label all wires prior to disconnection when servicing controls.Wir-  
ing errors can cause improper and dangerous operation.  
VERiFY PROPER OPERATiON AFTER SERViCiNg!  
If chemical lime dissolving cleaners are preferred, cautiously follow  
the instructions supplied with the cleaner. DO NOT use a muriatic or  
hydrochloric acid (HCl) base cleaner.  
G. RELIEF VALVE — The Temperature and Pressure Relief Valve must  
be free to operate properly. Check (at least once a year) by lifting the  
handle fully and allowing several gallons of water to flush through the  
discharge line. Make certain the discharged water is directed to a  
suitable drain.  
2. ANODE INSPECTION — The water supply in certain areas contains  
very aggressive elements. In these areas, periodic inspection of the  
anode is recommended to determine if replacement is necessary.The  
anode(s) supplied in this water heater is slowly consumed , thereby  
eliminating or minimizing corrosion and protecting the glass lined tank.  
The anode(s) should be replaced when more than 6 inches (15 cm) of  
core wire is exposed at either end.  
DANGER  
!
Before manually operating the relief valve, make certain no one  
will be exposed to the danger of coming in contact with the hot  
water released by this valve.The water may be hot enough to cre-  
ate a SCAlD hazard. The water released should be directed to a  
suitable drain to prevent injury or damage.  
3. SEASONAL OPERATION — If the water heater is to remain idle for an  
extended period (60 days or more) the heater should be turned off.The  
water heater and piping should be drained if they might be subjected  
to freezing temperatures. It is recommended that the water heater’s  
operation is thoroughly checked (by a qualified service technician)  
before it is placed back in service. NOTICE: Refer to Hydrogen Gas  
caution notation on page 16.  
NOTICE: If the temperature and pressure relief valve on the water  
heater discharges periodically, this may be due to thermal expansion  
in a “closed” water system. Contact the water supplier or local plumbing  
inspector on how to correct this. DO NOT plug the relief valve outlet.  
H. TANK— Good maintenance requires that the tank be cleaned of de-  
posits. Unless the water supply is soft (0 to 5 grains hardness), scale  
or lime deposits will accumulate in the tank. Hard water scale is de-  
posited at an increasingly high rate in proportion to increased water  
temperature. Accumulation of these deposits may reduce efficiency,  
and shorten the life of the water heater.  
Any new installation should have a tank inspection program set up  
initially for frequent inspection. The first inspection should be within a  
six month period. Once the scaling tendencies have been established,  
the inspection program can be modified to suit the water conditions.  
Cleaning should be performed if the scale has accumulated above the  
drain valve opening.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
“System Sentinel” Diagnostic System  
The “System Sentinel” Diagnostic system on this water heater provides the user or service technician with a visual representation of the  
operational status of the various sections of the water heater’s control system. A quick glance at the System Sentinel panel on the front of  
the heater will give an indication of where to begin trouble shooting of a non operational heater.  
The LED’s (light emitting diodes) on the panel are arranged from top to bottom based on their function in the normal sequence of operation,  
and their function is explained as follows:  
POWER  
When illuminated, this green LED indicates that 120VAC power is  
being supplied to the heater, the ON/OFF switch is functioning and  
the 24V transformer is functioning properly.  
(Refer to Section 1 of Troubleshooting Guide)  
THERMOSTAT  
When illuminated, this red LED indicates that the ther-  
mostat is functioning(calling for heat) and 24VAC power  
is being supplied to the relay (to turn on the blower) and  
the N/C terminal of the pressure switch with N/C and N/O  
terminals.  
SYSTEMSENTINEL  
(Refer to Section 2 of Troubleshooting Guide)  
POWER  
IGNITION  
THERMOSTAT  
IGNITION  
When illuminated, this red LED indicates that 24 VAC  
power is being supplied to the Ignition Control Module,  
and the ignition sequence has begun.The N/O side of the  
pressure switch with N/C and N/O terminals closes  
(Refer to Section 3 of Troubleshooting Guide)  
PILOT VALVE  
ECO  
PILOT VALVE  
When illuminated, this red LED indicates that the Ignition  
Control Module is supplying 24 VAC power to the ECO  
(Energy Cut Off device), or High Limit.  
MAIN VALVE  
(Refer to Section 4 of Troubleshooting Guide)  
®
ECO  
When illuminated, this red LED indicates that the ECO  
(Energy Cut Off device), or High Limit is closed, and 24  
VAC power is being supplied to the PV (Pilot Valve) ter-  
minal on the Gas Control Valve.  
(Refer to Section 5 of Troubleshooting Guide)  
MAIN VALVE  
When illuminated, this red LED indicates that the Ignition Control  
Module is supplying 24 VAC power to the MV (Main Valve) terminal  
on the Gas Control Valve.  
(Refer to Section 6 of Troubleshooting Guide)  
1ꢀ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
“System SentinelTroubleshooting guide  
Section 1... thePOWERlED  
is thePOWERlED illuminated?  
YES  
NO  
is theON/OFFSwitch in the  
Turn switch to ON position. is the  
Power is  
YES  
NO  
“ONposition?  
Power lED now illuminated?  
being supplied to the heater,  
the ON/OFF Switch is func-  
tioning, and the 24V AC  
Transformer is functioning.  
YES  
NO  
is 120 VAC power present at the  
Check circuit breaker or fuse and field connec-  
tion of branch circuit wiring to leads of switch.  
Repair or replace as required. is “POWER” lED  
now illuminated?  
NO  
branch circuit connections to Black  
wire of the switch and White wire of  
the transformer ?  
YES  
YES  
NO  
Replace Switch, then verify that  
power is present. is “POWER” lED  
now illuminated?  
is 120 VAC power present between  
the Black and White wires to the  
transformer ?  
YES  
NO  
NO  
YES  
Replace Transformer, then verify  
that power is present. is “POWER”  
lED now illuminated?  
is 24 VAC power present between  
the Yellow and gray wires from the  
transformer ?  
NO  
YES  
YES  
NO  
The System Senti-  
nel Panel is defective and must be  
replaced.  
CAUTION  
!
label all wires prior to disconnection when servicing controls.Wiring errors can cause improper and dangerous operation. VERiFY PROP-  
ER OPERATiON AFTER SERViCiNg!  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
“System SentinelTroubleshooting guide  
Section 2... theThERmOSTATlED  
NO  
YES  
is the “ThERmOSTAT” lED illuminated?  
Ensure that power is being supplied to  
the water heater. Refer to “Section 1...the  
POWER lEDin thisTroubleshooting guide,  
and correct if necessary. is the “ThERmO-  
STAT lEDnow illuminated.  
Thermostat is calling for  
heat, and 24VAC power.  
YES  
YES  
NO  
is Thermostat set at a tempera-  
Adjust  
ture higher than the water tem-  
Thermostat to a higher setting.  
is Thermostat lED now illumi-  
nated?  
NO  
perature in tank?  
YES  
NO  
Ensure that power is being supplied to  
the water heater. Refer to “Section 1...the  
POWER lEDin thisTroubleshooting guide,  
and correct if necessary. is the “ThERmO-  
STAT lEDnow illuminated.  
is 24 VAC  
power present at Yellow Wire  
Terminal insideThermostat?  
NO  
YES  
YES  
NO  
is 24 VAC power present at  
Blue Wire Terminal inside Ther-  
mostat?  
YES  
NO  
Thermostat is  
defective or out of calibration  
and must be replaced.  
CAUTION  
!
label all wires prior to disconnection when servicing controls.Wiring errors can cause improper and dangerous operation. VERiFY PROP-  
ER OPERATiON AFTER SERViCiNg!  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
“System SentinelTroubleshooting guide  
Section 3... theigNiTiONlED  
YES  
is the ignition lED illuminated?  
NO  
The Thermostat has called for  
heat, the Blower is running, and  
24VAC power is being supplied to  
the ignition Control module and  
the ignition sequence will begin.  
is Spark ignitor operating?  
is the Blower Operating?  
YES  
(Can sparking be heard?)  
NO  
YES  
NO  
is there 120 VAC  
across Black wire  
and White wire of  
blower?  
The System Sentinel Panel is  
defective and must be replaced.  
NO  
is 24 VAC present between the  
gray ground wire and the Red  
24 V wire connected to the igni-  
tion Control module?  
is there 24 VAC present  
NO  
YES  
between the common and  
Normally open terminal of  
pressure switch 1?  
is there 120  
VAC between  
the black wire at  
the relay and the  
whitewireonthe  
transformer?  
Blower is  
defective  
and must be  
replaced.  
YES  
YES  
NO  
1. Remove ignition Cable and check for  
good continuity, replace if necessary.  
2. Check ignitor Electrode(s) gap for proper  
spacing (1/8” to 5/32”). Correct if neces-  
sary.  
3. Examine Ceramic insulator on Pilot  
Assembly for cracks. Replace if cracks  
are evident.  
NO  
YES  
Check Con-  
tinuity of the  
Red wire from  
the ignition  
module to  
the Pressure  
Switch.  
Check con-  
Check continuity  
of black wire to  
relay.  
tinuity of  
yellow wires  
to pressure  
s w i t c h e s  
and between  
switches.  
Check continuity  
of black wire from  
relay to blower  
motor and white  
wire to motor.  
YES  
if all of the above components check okay,  
replace ignition Control module.  
is continuity  
is continuity  
good?  
good?  
is continuity  
good?  
Pressure Switch  
is defective and  
must be replaced.  
is continuity  
good?  
C h e c k  
wire con-  
nections.  
NO  
YES  
YES  
W i r e  
NO  
NO  
YES  
is defec-  
tive and  
must be  
replaced.  
is there 120 VAC between the  
black wire on the relay (power  
going to blower) and the white  
wire of the transformer?  
Wiring harness is defec-  
tive and must be replaced.  
YES  
NO  
Recheck all connections,  
P o w e r  
should be  
at 24 VAC  
of ignition  
module.  
Relay is  
d e fe c t i v e  
and must be  
replaced.  
is 24  
should have power at blower motor.  
VAC present  
across coil  
of relay?  
YES  
Review pressure switch circuit  
on this page.  
NO  
CAUTION  
!
label all wires prior to disconnection when servicing controls.Wiring errors can cause improper and dangerous operation. VERiFY PROP-  
ER OPERATiON AFTER SERViCiNg!  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
“System SentinelTroubleshooting guide  
Section 4... thePilOTVAlVElED  
is thePilOTVAlVElED illuminated?  
NO  
YES  
The ignition Control module is in  
the ignition sequence, and is pro-  
viding 24 VAC power to the ECO  
(Energy Cut-Off Device) inside of  
theThermostat  
is the Spark ignitor operating?  
(Can sparking be heard?)  
YES  
is the Pilot Flame burning?  
YES  
NO  
NO  
The System Sentinel Panel is  
defective and must be replaced.  
1. Remove ignition Cable and check for good conti-  
nuity, replace if necessary.  
2. Check ignitor Electrode gap for proper spacing  
(1/8to 5/32”). Correct if necessary.  
3. Examine Ceramic insulator on Pilot Assembly  
for cracks. Replace if cracks are evident.  
is 24 VAC present between the Brown wire on “PV”  
Terminal and White wire on “PV/mV” Terminal on  
the gas ControlValve?  
YES  
YES  
is 24 VAC present between the Brown wire on “PV”  
Terminal and gray ground wire on ignition Control  
module?  
YES  
NO  
i s  
the inlet gas pres-  
sure at or below the  
maximum as speci-  
fied on the rating  
plate?  
gas Control Valve  
is inoperable and must  
be replaced  
NO  
is theigNiTiONlED illuminated?  
is the “ECO” lED  
illuminated?  
YES  
NO  
NO  
YES  
Check continuity of Brown wire  
between ECO Device (inside of Ther-  
mostat), and “PV” Terminal on gas  
ControlValve. Repair or replace wire as  
needed to restore power toPV”Termi-  
nal on gas valve.  
ignition Control module  
is inoperable and must be  
replaced.  
Refer to Section 3...theigNi-  
TiONlED in theTroubleshooting guide  
Refer to Section 5...theECOlED in  
theTroubleshooting guide  
CAUTION  
!
label all wires prior to disconnection when servicing controls.Wiring errors can cause improper and dangerous operation. VERiFY PROP-  
ER OPERATiON AFTER SERViCiNg!  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
“System SentinelTroubleshooting guide  
Section 5... theECOlED  
NO  
YES  
is the "ECO" lED illuinated?  
ECO is “open”. Allow tank to cool,  
and reset. if ECO again trips, the  
Thermostat/high limit is defective.  
Replace as required.  
T h e  
ECO (Energy Cut-Off device) is  
not tripped (open) and power is  
being supplied to the “PV” termi-  
nal on the gas ControlValve.  
YES  
isECO lED now illuminated?  
NO  
The System Sentinel Panel is  
defective and must be replaced.  
YES  
is the Pilot Flame burning?  
NO  
Refer to  
Section 3...the “igNiTiONlED; and Section  
4...the “PilOT VAlVE”lED of Troubleshoot-  
ing guide. Repair or replace components as  
required.  
Section 6... themAiNVAlVElED  
is themAiNVAlVElED illuminated?  
NO  
YES  
The ignition Control module is  
providing 24 VAC between the  
mV” and “mV/PV” terminals on  
gas ControlValve, and main Burn-  
er should be operating  
is main Burner on?  
is the Pilot Flame burning?  
YES  
YES  
NO  
NO  
is 24 VAC present between Blue wire on  
mV Terminal and White wire on “mV/PV”  
terminal on the ignition Control module?  
The System Sentinel Panel is  
defective and must be replaced.  
is the Spark ignitor operating?  
(Can sparking be heard?)  
is the inlet gas pressure at or below the  
maximum as specified on the rating plate?  
YES  
NO  
NO  
is 24 VAC present between Blue  
wire on “mV Terminal and White  
wire on “mV/PV” terminal on gas  
valve?  
YES  
main gasValve is inoperative  
and must be replaced.  
ignition Control module is inoperative and  
must be replaced.  
Check Continuity of Blue and White  
wires between ignition Control module and  
gas Control Valve. Repair or replace as  
required to restore power to gas valve.  
NO  
CAUTION  
!
label all wires prior to disconnection when servicing controls.Wiring errors can cause improper and dangerous operation. VERiFY PROP-  
ER OPERATiON AFTER SERViCiNg!  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Replacement Parts  
Instructions For Placing a Parts Order  
All parts orders should include:  
CAUTiON: For your safety DO NOT attempt repair of  
!
gas piping, gas control (thermostat), burners, vent con-  
The model and serial number of the water heater from the rating  
plate.  
nectors or other safety devices. Refer repairs to qualified  
service personnel.  
Specify type of gas (natural or LP) as marked on the rating plate.  
Part description (as noted below) and number of parts desired.  
Blower Assembly  
T&P Valve  
Handhole Sealplate  
Gasket SP5886  
(Beneath Cover)  
Thermostat  
Ignition Control  
Assembly  
w/ Relay*  
Drain Valve  
Gas Valve  
Burner Assembly  
Pilot/Ignitor  
Assembly  
*Some assembly components are available individually  
(Control Module, Transformer, and ON/OFF Switch).  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring and Schematic Diagrams  
N O R M A L O P E R A T I O N S E Q U E N C E  
I N D I C A T E D B Y B O X E D N U M E R A L S  
L 1  
L 2  
1 2 0 V  
2
3
B L O W E R  
LED  
INDICATORS  
BL  
BR  
BR  
-
-
-
4
3
4
POWER  
2 4 V  
THERMOSTAT  
IGNITION  
THERMOSTAT  
AND  
120V  
POWER  
LED  
L1  
L2  
PILOT VALVE  
ECO  
HIGH LIMIT  
IGNITION  
LED  
MAIN VALVE  
BLACK  
SWITCH  
WHITE  
1
4
ON  
TRANSFORMER  
THERM.  
N.C.S.W.  
Y-2  
OFF  
GRAY  
W4  
BK-2  
BLOWER  
THERMOSTAT LED  
Y-2  
W
IGNITION  
CONTROL  
GR/YL  
BK  
G2  
MAIN VALVELED  
GY-5  
6
BK3  
NC  
1
4
3
6
IGNITION CONTROL  
MGV  
GND  
MV  
TEMP  
SWITCH  
Y7  
Y6  
5
2
24 MV/PV  
NC  
5
LIMIT  
Y-5  
C
C
BL6  
PGV  
N
PV  
PS2  
PS1  
R8  
BR-1  
R-3  
BL-5  
GY-1  
ECO LED  
GND  
BR-3  
PILOT VALVE  
LED  
BL-2  
W-1  
PV  
PV  
5
IGN.  
MV  
PILOT  
ELECTRODE ASSY.  
MV  
GAS VALVE  
CONNECTION DIAGRAM  
SCHEMATIC  
Figure 14. — Diagrams for units supplied with honeywellVR8304P orVR8304m gasValve and honeywell S8600m ignition Control, honeywellThermo-  
stat andTemperature limiting Switch for vent pipe..  
NOTiCE: if any of the original wire as supplied with this appliance must be replaced, it mUST be replaced with 18 gA., 600V, 105°C  
wire or its equivalent, unless otherwise noted.  
CAUTiON! label all wires prior to disconnection when servicing controls.Wiring errors can cause improper and dangerous operation.  
VERiFY PROPER OPERATiON AFTER SERViCiNg!  
!
N O R M A L O P E R A T I O N S E Q U E N C E  
I N D I C A T E D B Y B O X E D N U M E R A L S  
L 1  
L 2  
1 2 0 V  
2
3
B L O W E R  
LED  
INDICATORS  
BL - 4  
BR - 3  
BR - 4  
POWER  
2 4 V  
THERMOSTAT  
IGNITION  
120V  
POWER  
LED  
THERMOSTAT  
AND  
L1  
L2  
PILOT VALVE  
ECO  
IGNITION  
LED  
HIGH LIMIT  
MAIN VALVE  
BLACK  
SWITCH  
WHITE  
1
4
ON  
TRANSFORMER  
THERM.  
N.C.S.W.  
OFF  
GRAY  
W4  
BK-2  
BLOWER  
W
THERMOSTAT LED  
MAIN VALVELED  
Y-2  
IGNITION  
CONTROL  
GR/YL  
BK  
G2  
GY-5  
IGNITION CONTROL  
6
BK3  
NC  
1
4
3
6
MGV  
GND  
MV  
TEMP  
SWITCH  
Y7  
Y6  
5
2
24 MV/PV  
NC  
5
LIMIT  
Y-5  
C
C
BL6  
PGV  
N
PV  
PS2  
PS1  
R8  
BR-1  
R-3  
BL-5  
GY-1  
ECO LED  
GND  
BR-3  
PILOT VALVE  
LED  
BL-2  
W-1  
PV  
PV  
5
IGN.  
MV  
PILOT  
ELECTRODE ASSY.  
MV  
GAS VALVE  
CONNECTION DIAGRAM  
SCHEMATIC  
Figure 14. — Diagrams for units supplied with honeywellVR8304P orVR8304m gasValve and honeywell S8600m ignition Control,White-Rodgers  
Thermostat andTemperature limiting Switch for vent pipe..  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring and Schematic Diagrams  
NORMAL OPERATION SEQUENCE  
INDICATED BY BOXED NUMERALS  
NOTICE: If any of the original wire as supplied  
L1  
L2  
with this appliance must be replaced, it MUST be  
replaced with 18 GA., 600V, 105°C wire or its equiv-  
alent, unless otherwise noted.  
120V  
2
3
BLOWER  
M
R
LED  
INDICATORS  
BL-4  
BR-3  
BR-4  
POWER  
24V  
THERMOSTAT  
AND  
THERMOSTAT  
IGNITION  
PILOT VALVE  
ECO  
120V  
L1  
POWER  
LED  
L2  
LIMIT  
IGNITION  
LED  
MAIN VALVE  
BLACK  
SWITCH  
WHITE  
1
THERM.  
4
ON  
TRANSFORMER  
Y2  
N.C.S.W.  
OFF  
R
GRAY  
W4  
BK-2  
THERMOSTAT LED  
BLOWER  
W
Y-2  
G2  
IGNITION  
CONTROL  
GR/YL  
BK  
MAIN VALVE LED  
GY-5  
6
BK3  
1
4
3
6
IGNITION CONTROL  
MGV  
GND  
MV  
Y7  
Y6  
NC  
5
2
24 MV/PV  
5
LIMIT  
Y-5  
NC  
C
C
BL6  
PGV  
NO  
PV  
PS2  
PS1  
R8  
BR-1  
R-3  
BL-5  
ECO LED  
GND  
BR-3  
GY-1  
PILOT VALVE  
LED  
BL-2  
W-1  
PV  
5
IGN.  
PV  
MV  
ANY REPLACEMENT WIRE  
MUST BE RATED FOR 250°C.  
PILOT  
ELECTRODE ASSY.  
MV  
GAS VALVE  
SCHEMATIC  
CONNECTION DIAGRAM  
CAUTiON! label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. VERi-  
FY PROPER OPERATiON AFTER SERViCiNg!  
!
Figure 14. — Diagrams for units supplied with honeywellVR8304P orVR8304m gasValve and honeywell S8600m ignition Control.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
how to Obtain Service Assistance  
1. Should you have any questions about your new water heater, or if it  
be made available:  
requires adjustment, repair, or routine maintenance, it is suggested  
that you first contact your installer, plumbing contractor or previously  
agreed upon service agency. In the event that the firm has moved, or  
is unavailable, refer to the telephone directory commercial listings or  
local utility for qualified service assistance.  
a. Model and serial numbers of the water heater as shown on the rating  
plate attached to the jacket of the heater.  
b. Address where water heater is located and can be seen.  
2. Should your problem not be solved to your complete satisfaction, you  
should then contact the Manufacturer’s National Service Department  
at one of the following address:  
c. Name and address of installer and any service agency who performed  
service on the water heater.  
d. Date of original installation and dates any service work was per-  
formed.  
In The U.S.A.:  
Rheem Manufacturing Co., Water Heater Division  
2600 Gunter Park Drive  
e. Details of the problem as you can best describe them.  
Montgomery, Alabama 36109-1413  
Phone: 1-800-432-8373.  
f. List of people, with dates, who have been contacted regarding your  
problem.  
In CANADA:  
Rheem Canada, Ltd. / Ltée  
P.O. Box 2846  
Hamilton, ON L8N 3P3  
Phone: 1-800-268-6966.  
When contacting the manufacturer, the following information should  
The following Gaskets are required for Normal Maintenance for all Models:  
SP5886 Tank Handhole Sealplate Gasket  
All other Parts can be ordered by providing the following information:  
1. Description of Part(s), such as:  
Main Gas Valve  
Pilot Burner  
Main Burner  
Thermostat  
Blower Assembly  
Anode Rod  
Or other parts as required.  
2. Quantity of each part required.  
3. Complete models number and name of the water heater.  
4. Serial Number of water heater.  
5. Specify Type of Gas.  
6. Address Parts Orders to your distributor or dealer.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  

PYLE Audio Speaker System PHSP101T User Guide
Renesas Computer Hardware SH7243 User Guide
Rotel DJ Equipment RSP980 User Guide
Rotel Stereo Amplifier RC 1090 User Guide
Russell Hobbs Washer RH1042 User Guide
Ryobi Outdoor Cultivator RY46501A User Guide
Samsung Flat Panel Television UN75F8000 User Guide
Samsung Projection Television HL S6167W, HL S6767W User Guide
Samsung Refrigerator RF24FSEDBSR User Guide
Sanyo Battery Charger SEB 013SEB 013 User Guide