Owners &
Installation Manual
P48-1 Gas Fireplace
MODELS: P48-NG1 Natural Gas P48-LP1 Propane
WARNING:
FOR YOUR SAFETY
Iftheinformationintheseinstructionsarenotfollowedexactly, What to do if you smell gas:
a fire or explosion may result causing property damage,
personal injury or loss of life.
Do not try to light any appliance
Do not touch any electrical switch:
do not use any phone in your
building.
Immediately call your gas supplier
from a neighbour's phone. Follow
the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fire department.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
Tested by:
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
09/28/05
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
918-458
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
Page
Page
FlushTrim .................................................................28
BayDoor...................................................................29
Bay Trim ...................................................................29
BayLouvers ..............................................................29
FinishingTrim ...........................................................30
DoubleScreenDoor ..................................................30
RemoteControl(optional) ..........................................31
Remote Wall Switch (optional) ..................................31
WallThermostat(optional) ........................................31
WiringDiagram .........................................................32
OptionalFan .............................................................33
ConversiontoPropane ..............................................34
Safety Label
SafetyLabel ............................................................... 4
Installation
ImportantMessage .................................................... 5
Before You Start ........................................................ 5
GeneralSafetyInformation ......................................... 5
Installation Checklist .................................................. 5
ManufacturedMobileHome
AdditionalRequirements ...................................... 6
UnitSpecifications ..................................................... 6
LocatingYourStove ................................................... 6
Optional Duct System Kit .......................................... 6
Optional Heat Release Kit .......................................... 6
Hearth ..................................................................... 6
Clearances ................................................................. 7
Mantels ..................................................................... 8
MantelLegClearances............................................... 8
FramingandFinishing ................................................ 9
Top Assembly & Nailing Strips..................................10
VentingIntroduction ..................................................10
ExteriorVentTerminationLocations..........................11
VentingArrangements
Operating Instructions
OperatingInstructions ...............................................35
LightingProcedure ....................................................35
ShutdownProcedure .................................................35
First Fire ...................................................................35
AerationAdjustment..................................................35
NormalOperatingSoundsof
Gas Appliances ..................................................36
Lighting Plate Instructions .........................................36
Maintenance
HorizontalTerminations ......................................12
SimpsonDura-VentComponentsList .................13
HorizontalTerminations ......................................14
HorizontalVenting ..............................................15
Vertical Venting ..................................................16
VerticalTerminations ..........................................18
Venting-Dura-VentHorizontalInstallations ..............20
Venting-Dura-VentVerticalTermination...................21
Direct Vent System (Flex).........................................22
System Data .............................................................23
HighElevation ...........................................................23
Gas Line Installation..................................................23
Pilot Adjustment .......................................................23
Gas Pipe Pressure Test ............................................23
SITValveDescription ................................................23
Brick Panel Installation..............................................24
Log Set Installation ...................................................25
StandardFlushDoor .................................................28
FlushLouvers ............................................................28
MaintenanceInstructions ..........................................37
GeneralVentMaintenance ........................................37
LogReplacement ......................................................37
Thermopile/Thermocouple .........................................37
Glass Gasket............................................................37
Gold-PlatedLouvers ..................................................37
DoorGlass................................................................38
Bay Glass Replacement ...........................................38
InstallingValve ..........................................................38
RemovingValve .........................................................39
PartsList
Replacement/SparePartsList...................................40
Warranty
Warranty ...................................................................47
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
3
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY LABEL
Thisisacopyofthelabelthataccompanieseach
P48-NG1 and P48-LP1 Zero Clearance Direct
Vent Gas Fireplace. We have printed a copy of
the contents here for your review. The safety
label is located on the front inside base of the
unit, visible when the bottom louver is open.
NOTE: Regency units are constantly being im-
proved. Check the label on the unit and if there
is a difference, the label on the unit is the correct
one.
For the State of Massachusetts, installation
and repair must be done by a plumber or
gasfitter licensed in the Commonwealth of
Massachusetts.
For the State of Massachusetts, flexible
connectors shall not exceed 36 inches in
length.
For the State of Massachusetts, the appli-
ances individual manual shut-off must be a
t-handle type valve.
4
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
annually. Make it a practice to have all of
your gas appliances checked annually.
IMPORTANT:
SAVE THESE
INSTRUCTIONS
YOUNG CHILDREN SHOULD BE
CAREFULLY SUPERVISEDWHEN
THEYAREINTHESAMEROOMAS
THEAPPLIANCE.
13) Do not slam shut or strike the glass door.
14) Under no circumstances should any solid
fuels (wood, paper, cardboard, coal, etc.)
be used in this appliance.
The P48-NG1/P48-LP1 Direct Vent Fireplace
must be installed in accordance with these in-
structions. Carefully read all the instructions in
this manual first. Consult the "authority having
jurisdiction" to determine the need for a permit
prior to starting the installation. It is the responsi-
bility of the installer to ensure this fireplace is
installed in compliance with manufacturers in-
structions and all applicable codes.
CLOTHING OR OTHER FLAMMA-
BLEMATERIALSHOULDNOTBE
PLACEDONORNEARTHEAPPLI-
ANCE.
15) The appliance area must be kept clear and
free of combustible materials, (gases and
other flammable vapours and liquids).
Emissions from burning wood or gas could
contain chemicals known to the State of
California to cause cancer, birth defects or
other reproductive harm.
GENERAL SAFETY
INFORMATION
BEFORE YOU START
1) The appliance installation must conform
with local codes or, in the absence of local
codes, with the current Canadian or Nation-
al Gas Codes, CAN1-B149 or ANSI Z223.1
Installation Codes.
Safeinstallationandoperationofthisappliance
requires common sense, however, we are
required by the Canadian Safety Standards
and ANSI Standards to make you aware of the
following:
INSTALLATION
CHECKLIST
2) Theappliancewheninstalled, mustbeelec-
trically grounded in accordance with local
codes, or in the absence of local codes with
the current National Electrical Code, ANSI/
NFPA70orCSAC22.1CanadianElectrical
Code.
1) Locate appliance
INSTALLATION AND REPAIR
SHOULDBEDONEBYANAUTHOR-
IZEDSERVICEPERSON. THEAP-
PLIANCESHOULDBEINSPECTED
BEFOREUSEANDATLEASTAN-
NUALLY BY A PROFESSIONAL
SERVICE PERSON. MORE FRE-
QUENT CLEANING MAY BE RE-
QUIREDDUETOEXCESSIVELINT
FROMCARPETING,BEDDINGMA-
TERIAL, ETC. IT IS IMPERATIVE
THAT CONTROL COMPART-
MENTS,BURNERSANDCIRCULAT-
ING AIR PASSAGEWAYS OF THE
APPLIANCEBEKEPTCLEAN.
a) Room location, page 6
b) Clearances to Combustibles, page 7
c) Mantel Clearances, page 8
d) Framing & Finishing Requirements,
page 9
3) See general construction and assembly
instructions. The appliance and vent should
be enclosed.
e) Venting Requirements, pages 10-18.
2) Assemble Top Facing Support and Side
Nailing Strips, page 10.
4) This appliance must be connected to the
specified vent and termination cap to the
outsideofthebuildingenvelope.Nevervent
to another room or inside a building. Make
sure that the vent is fitted as per Venting
instructions.
NOTE: must be done before installing
unit into fireplace.
3) Install venting, pages 20-21.
4) Make gas and electrical connections. Test
the pilot. Must be as per diagram. Page 23.
5) Inspect the venting system annually for
blockage and any signs of deterioration.
5) Test Gas Pressure. Page 23.
6) Venting terminals shall not be recessed into
a wall or siding.
6) Install brick panels (optional), page 24.
DUE TO HIGH TEMPERATURES,
THEAPPLIANCESHOULDBELO-
CATED OUT OF TRAFFIC AND
AWAY FROM FURNITURE AND
DRAPERIES.
7) Any safety glass removed for servicing
must be replaced prior to operating the
appliance.
7) Install Flush Door Front (Standard) and
optional Flush Gold Trim, page 28.
8) Install Optional Bay Front and optional Bay
8) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
fireplace.
Gold Trim, page 29.
9) Install Louvers (Flush or Bay), pages
WARNING:FAILURETOINSTALL
THIS APPLIANCE CORRECTLY
WILLVOIDYOURWARRANTYAND
MAY CAUSE A SERIOUS HOUSE
FIRE.
28-29.
9) Wear gloves and safety glasses for pro-
tection while doing required maintenance.
10) Installationof WallSwitch,RemoteControl,
or Wall Thermostat, page 31.
10) Be aware of electrical wiring locations in
walls and ceilings when cutting holes for
termination.
11) Final check.
CHILDRENANDADULTSSHOULD
BE ALERTED TO THE HAZARDS
OF HIGH SURFACE TEMPERA-
TURES, ESPECIALLY THE FIRE-
PLACE GLASS, AND SHOULD
STAYAWAYTOAVOIDBURNSOR
CLOTHINGIGNITION.
11) Under no circumstances should this appli-
ance be modified. Parts that have to be
removed for servicing should be replaced
prior to operating this appliance.
Before leaving this unit with the customer, the
installer must ensure that the appliance is firing
correctly and operation fully explained to
customer.
12) Installationandanyrepairstothisappliance
should be done by an authorized service
person. A professional service person
should be called to inspect this appliance
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
5
INSTALLATION
This includes:
LOCATING YOUR
GAS STOVE
1) Clocking the appliance to ensure the correct
firing rate (rate noted on label 51,000 (NG)
Btu/h, 48,000 (LP) Btu/h) after burning ap-
pliance for 15 minutes.
1) When selecting a location for your stove,
ensure that the clearances outlined on this
page are met.
OPTIONAL
DUCT SYSTEM
KIT #946-556
2) If required, adjusting the primary air to en-
sure that the flame does not carbon. First
allow the unit to burn for 15-20 min. to
stabilize.
2) Provide adequate clearances for servic-
ing.
CAUTION: Any alteration to the product
that causes sooting or carboning that
results in damage is not the responsibil-
The HeatWave Air Duct Kit increases the
effectiveness of your fireplace by dispersing
warm air from the fireplace to remote locations
in the same room or other rooms in your home.
3) The appliance must be installed on a flat,
solid, continuous surface (e.g. wood, met-
al, concrete). This may be the floor, or
raised up on a platform to enhance its
visualimpact. Iftheapplianceisgoingtobe
installed on carpeting, combustible linole-
um tile or other combustible material other
than wood flooring, the appliance must be
installed on a metal or wood panel extend-
ing the full width and depth of the appli-
ance.
ity of the manufacturer.
Up to two kits may be installed on the fireplace.
Please Note: Only 1 HeatWave kit may be
operated at one time. This includes the internal
blower option as well.
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
OPTIONAL
HEAT RELEASE
KIT #946-570
4) The P48-1 Direct Vent Gas Fireplace can
beinstalledinarecessedpositionorframed
out into the room as in A, B, C, D. See
Diagram 1.
1) Ensure that structural members are not cut
or weakened during installation.
2) Ensure proper grounding using the #8
The Heat Release Kit expels warm air from the
fireplace to the outside of the building, allowing
the fireplace to be operated with less heat
enteringtheroom.Thekitmaybeusedoneither
the left or right side.
ground lug provided. See page 32.
Diagram 1
A) Flat on Wall
B) Flat on Wall Corner
C) Recessed into
Wall/Alcove
UNIT SPECIFICATIONS
HEARTH
D) Corner
A hearth is not mandatory, but is recommended
for aesthetics and for added safety.
5) ThisapplianceisListedforbedroom instal-
lations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
6) The P48-1 Direct Vent Gas Fireplace is
approved for alcove installations, which
meet the clearances listed on this page.
7) We recommend that you plan your installa-
tion on paper using exact measurements
for clearances and floor protection before
actually installing this appliance. Have an
authorized inspector, dealer, or installer
review your plans before installation.
Note: For vent terminations see page 11.
6
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of
the greatest importance that this fireplace and vent system be installed only in accordance with these instructions.
Clearance to Combustibles from:
Caution Requirements
Back
Side
Floor
0"
0"
0"
(0mm)
(0mm)
(0mm)
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
Minimum Clearance from Top of Front Facing:
Mantel
min. 8"
(203mm)
Ceiling
39"
(990mm) from top of front facing above louvers.
Side Wall:
6"
(152mm)
Horizontal Vent Clearances:
Top
Side
Bottom
2-1/2"
1-1/2"
1-1/2"
(64mm)
(38mm)
(38mm)
Vertical Vent Clearances:
1-1/4"
(32mm)
Alcove Clearances:
Max. Depth 36"
Min. Width 60"
Min. Height 80"
(914mm)
(1524mm)
(2032mm)
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials
are not adhered to. It is of greatest importance that this
fireplace and vent system be installed only in
accordance with these instructions.
The HeatWave Duct Kit
and the Heat Release
Kit have different clear-
ance and framin require-
ments, check the Heat-
Heat Release Kit
Wave and Heat Release
manual for details.
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
7
INSTALLATION
MANTELS
Because of the extreme heat this fireplace emits, the mantel clearances are critical. Combustible mantel clearances from louver are
shown in the diagram below.
Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-
combustible board.
This drawing is to scale at 1:6 (one inch = 6
inches)
Mantel can be installed anywhere in shaded
area using the above scale for units with the
Flush Front and with the optional Bay Front.
Note: Ensure the paint that is used on
the mantel and the facing is "heat
resistant" or the paint may discol-
our.
MANTEL LEG CLEARANCES
Combustible mantel leg clearances as per diagram:
Maximum
1-1/2" projection at 3"
minimumclearance.
8
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
FRAMING & FINISHING
1) Determine the total thickness of facing material (eg. drywall plus
ceramic tiles) to allow the finished surface to be flush with the front
of the unit. Total facing thickness can vary from 1/2" (13mm) to
1-1/4" (32mm) thick.
2) Frame in the enclosure for the unit with framing material. The framed
opening for the assembled kit is 47-1/2" high x 48-1/2" wide x
26-1/4" deep (1207mm H x 1232mm W x 667mm D). See Diagram 1.
Diagram 1
Note: 43" (1092mm) is the minimum height for flex termination
and Simpson Dura-Vent terminations.
3) For exterior walls, insulate the enclosure to the same degree as the
rest of the house, apply vapour barrier and drywall, as per local
installation codes. (Do not insulate the fireplace itself.)
4) The unit does not have to be completely enclosed in a chase. The
clearance on top of the unit from the top standoffs is 0" so
combustible building materials can be laid directly on top of the
standoffs. You must maintain clearances from the vent to combus-
tiblematerials:Seepage7.Combustiblematerialscanbelaidagainst
the side and back standoffs and the stove base.
The HeatWave Duct Kit has different
clearance and framing requirements,
check the HeatWave manual for details.
IMPORTANT
When installing the unit with any vertical venting off the top of the
unit as shown, the minimum framing depth changes accordingly.
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
9
INSTALLATION
Top Facing Support and
Side Nailing Strips
"C" Screw Position:
UNIT ASSEMBLY
PRIOR TO
INSTALLATION
For a facing material depth of 1-1/4"
(32mm), the top facing support must be
reversed.
Determine the total thickness of facing material
(e.g. drywall plus ceramic tiles) to allow the
finished surface to be flush with the front of the
unit. Total facing thickness can vary from 1/2"
(13mm) to 1-1/4" (32mm) thick.
TheTopFacingSupport, theSideNailingStrips
and the 2 Top Standoffs must be correctly
positioned and attached to the top before unit
is slipped into position.
The Top Facing Support & Side Nailing Strips
can be mounted in 3 different positions depend-
ing on the thickness of the facing material.
TopStandoffAssembly
The top standoffs are shipped in a flat position
and must be folded into shape and attached.
Screw
Position
Facing Material
Depth
1) Remove the standoffs from the fireplace
top.
A
B
C*
1/2" / 13mm
7/8" / 22mm
1-1/4" / 32mm
2) Take each standoff and bend into the cor-
rect shape. Bend up at the bend lines until
the screw holes in the standoff and the pre-
punched screw holes on the fireplace top
line up.
2) Use the same screw hole position for the
Side Nailing Strips as was used for the Top
Facing Support. Attach each side nailing
strip using 3 screws.
* For "C" screw position the top facing support
is reversed.
3) Attach the standoff securely to the top with
2 screws per standoff (on opposite cor-
ners).
1) Mount Top Facing Support using the 3
supplied screws into the three pre-punched
screw holes on the top front of the unit. Use
hole positions A, B, or C depending on your
facing depth.
VENTING
INTRODUCTION
The P48-1 uses the "balanced flue" tech-
nology Co Axial system. The inner liner vents
products of combustion to the outside while the
outer liner draws outside combustion air into
the combustion chamber thereby eliminating
the need to use heated room air for combustion
and losing warm room air up the chimney.
Note: These flue pipes must not be con-
nected to any other appliance.
The gas appliance and vent system must be
vented directly to the outside of the building,
and never be attached to a chimney serving a
separate solid fuel or gas burning appliance.
Each direct vent gas appliance must use it's
own separate vent system. Common vent
systems are prohibited.
10
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
EXTERIOR VENT TERMINATION REQUIREMENTS
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
11
INSTALLATION
VENTING
Regency Direct Vent System (Flex) Horizontal
Terminations Only
These venting systems, in combination with the P48-1 Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by
Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram on page 11.
Regency Direct Vent (Flex) System Termina-
tion Kit (Part# 946-615) includes all the parts
needed to install the P48-1 with a maximum
run of 4 feet.
1) 8" dia. flexible liner (4 ft. length)
2) 5" dia. flexible liner (4 ft. length)
3) spring spacers (4)
4) thimble (2)
5) AstroCap XL termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1-1/2" Drill Point, Stainless Steel (4)
10) vinyl siding standoff
If longer runs are needed, the Regency Direct
Vent system (Flex) Part# 946-616 includes all
the parts needed to install the P48-1 with a
maximum 10' run.
1) 8" dia. flexible liner (10 ft. length)
2) 5" dia. flexible liner (10 ft. length)
3) spring spacers (7)
4) thimble (2)
5) AstroCap XL termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1-1/2" Drill Point, Stainless Steel (4)
10) vinyl siding standoff
Notes:
1) Liner sections should be continuous without any joints or seams.
2) Only Flex pipe purchased from Regency may be used for Flex installations.
3) If you are installing the P48-1 into a Regency Mantel Kit, use the minimum horizontal vent height (centre-line of 43"). Remember
to include the mantel base in your calculations and to maintain the 2-1/2" clearance to the underside of the mantel top.
12
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
SIMPSON DURA-VENT VENTING
Horizontal or Vertical Terminations
The Simpson Dura-Vent Direct Vent System offers a complete line of component parts for installation of both horizontal and vertical installations.
Many items are offered in decorative black, as well as galvanized finish. We recommend using the galvanized finish for installation with the P48-
1.
Flat Wall Installation
The minimum components required for a basic
horizontal termination are:
Wall Thickness
(inches)
Vent Length
Required (inches)
4" - 5-1/2"
7" - 8-1/2"
10" - 11-1/2"
9" - 14-1/2"
15" - 23-1/2"
none
1
1
1
1
1
Horizontal Termination Cap
45o Elbow
Flue Adaptor
WallThimble
Length of pipe to suit wall thickness
(see chart)
6"
9"
12"
11" - 14-5/8" Adj. Pipe
Wall thickness is measured from the back
standoffs to the inside mounting surface of
termination cap. For siding other than vinyl
furring strips may be used, instead of the vinyl
siding standoff, to create a level surface to
mounttheventterminal. TheTerminalmustnot
be recessed into siding. Measure the wall
thickness including furring strips.
If a Vinyl Siding Standoff is required (it must be
used with vinyl siding), measure to outside
surface of wall without siding and add 2
inches.
Alternate
Horizontal Termination
Caps
SIMPSON DURA-VENT VENTING
COMPONENTS LIST
Part # Description
Part # Description
Part # Description
1281 Snorkel-36" Rise Term.Cap
1240 Wall Thimble-Suprt/Box
1241 Cathdrl/Clng-Sprt/Box
3951 BrassTrimforWallThimble/CeilingSupport
1263 Firestop Spacer
1243 Flashing 0/12-6/12
1243S Flashing 7/12-12/12
1253 StormCollar
1208B 6" Pipe Length-Black
1207B 9" Pipe Length-Black
1206 12" Pipe Length Galv.
1206B 12" Pipe Length-Black
1204 24" Pipe Length Galv.
1204B 24" Pipe Length-Black
1203 36" Pipe Length Galv.
1203B 36" Pipe Length-Black
1202 48" Pipe Length Galv.
1202B 48" Pipe Length-Black
1211B 11"-14 5/8" Adj./P/L-Black
1217B 17"- 24" Adj. Length Black
1245
45O Elbow Galv.
1245B 45O Elbow-Black
1245G 45O Elbow-Swivel Galv.
1245BG 45O Elbow-Swivel-Black
1290
90O Elbow Galv.
1290B 90O Elbow-Black
1290G 90O Elbow-Swivel Galv.
1290BG 90O Elbow-Swivel-Black
1250 Vinyl Siding Standoff
1288 Wall Strap
1247 WallThimble
1291 High Wind Term. Cap (Vertical Only)
1285 Horiz.Sq.HighWind Trm.Cap (Only)
1282 Snorkel-14" Rise Term.Cap
Parts not supplied by Dura-Vent
770-994 Dura-Vent Flue Adaptor
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
13
INSTALLATION
VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS
SIMPSON DURA-VENT DIRECT VENT GS SYSTEM and
REGENCY DIRECT VENT SYSTEM (FLEX)
(Propane & Natural Gas)
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 45o and one 90o elbow (two 45o elbows equal
one 90o elbow).
Note: Must use optional flue adapter (Part # 770-994) when using Simpson Dura-Vent pipe. (Refer to page 13.)
Simpson Dura-Vent
5" inner diameter
8" outer diameter
Regency Flex Vent
5" inner diameter
8" outer diameter
A vent guard should be used when-
ever the termination is lower than the
specified minimum or as per local
codes.
Note: Regency Direct Vent System
(Flex) is only approved for hor-
izontal terminations.
•
•
•
Maintain clearances to combustibles as listed on pages 6 to 9.
Horizontal vent must be supported every 3 feet.
Firestops are required at each floor level and whenever passing through a wall.
14
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Horizontal Venting with Two (2) 90o Elbows
Horizontal Venting with Three (3) 90o Elbows
One 90o elbow = Two 45o elbows.
One 90o elbow = Two 45o elbows.
Option
A)
V
H + H1
3' Max.
Option
A)
H
V
H + H1 + H2
3' Max.
5' Max.
6' Max.
7' Max.
With these options, maxi-
mum total pipe length is 30
feet with minimum of 6 feet
total vertical and maximum
8 feet total horizontal.
Please note minimum 1
foot between 90o elbows
is required.
Withtheseoptions, max.
total pipe length is 30
feet with min. of 11 feet
total vertical and max. 9
feet total horizontal.
Please note min.
1' Min.
2' Min.
3' Min.
4' Min.
5' Min.
6' Min.
1 Max. 1' Min.
2'Max. 3' Min.
3'Max. 5' Min.
4'Max. 7' Min.
5'Max. 9' Min.
B)
C)
D)
E)
4' Max.
5' Max.
6' Max.
7' Max.
8' Max.
B)
C)
D)
E)
1 foot between 90o
elbows is required.
8' Max.
F)
F)
6'Max. 11' Min. 9' Max.
Horizontal Venting with Two (2) 90o Elbows
One 90o elbow = Two 45o elbows.
Option
A)
H
V
H + H1
With these options, max.
total pipe length is 30 feet
with min. of 8 feet total
vertical and max. 8 feet
total horizontal.
Please note min. 1 foot
between 90o elbows is
required.
1'Max. 1' Min. 3' Max.
2'Max. 2' Min. 5' Max.
3'Max. 4' Min. 6' Max.
4'Max. 6' Min. 7' Max.
5'Max. 8' Min. 8' Max.
B)
C)
D)
E)
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
15
INSTALLATION
Horizontal Venting with Three (3) 90o Elbows
One 90o elbow = Two 45o elbows.
Option
A)
V
H
V + V1
H + H1
With these options,
max. total pipe length
is 30 feet with min. of
12 feet total vertical
and max. 9 feet total
horizontal.
Please note min. 1
foot between 90o
elbows is required.
2' Min. 1'Max. 3' Min. 4' Max.
3' Min. 2'Max. 4' Min. 5' Max.
4' Min. 3'Max. 6' Min. 6' Max.
5' Min. 4'Max. 8' Min. 7' Max.
6' Min. 5Max. 10' Min. 8' Max.
7' Min. 6'Max. 12' Min. 9' Max.
B)
C)
D)
E)
F)
Vertical Venting with Two (2) 90o Elbows
Vertical Venting with Two (2) 90o Elbows
One 90o elbow = Two 45o elbows.
One 90o elbow = Two 45o elbows.
Option H + H1
V
Option
A)
V
H
V + V1
With these options, max. total
pipe length is 30 feet with min.
of6feettotalverticalandmax.
8 feet total horizontal.
Please note min. 1 foot
between 90o elbows is re-
quired.
Withtheseoptions,max.total
pipelengthis30feetwithmin.
of 6 feet total vertical and
max. 6 feet total horizontal.
Please note min. 1 foot
between 90o elbows is re-
quired.
A)
B)
C)
D)
E)
2' Max. 2' Min.
3' Max. 3' Min.
4' Max. 4' Min.
5' Max. 5' Min.
6' Max. 6' Min.
1' Min. 4'Max. 2' Min.
2' Min. 5'Max. 3' Min.
3' Min. 6'Max. 4' Min.
4' Min. 7'Max. 5' Min.
5' Min. 8'Max. 6' Min.
B)
C)
D)
E)
Foradditionalverticalvent-
ing with 2 x 90o elbows,
refer to page 18.
16
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Vertical Venting with Three (3) 90o Elbows
One 90o elbow = Two 45o elbows.
Option
A)
H
V
H + H1 V + V1
With these options, max. total
pipelengthis30feetwithmin.
of 11 feet total vertical and
max. 7 feet total horizontal.
Please note min. 1 foot
between 90o elbows is re-
quired.
1'Max. 1' Min. 3'Max. 3' Min.
2'Max. 2' Min. 4'Max. 5' Min.
3'Max. 3' Min.' 5'Max. 7' Min.
4'Max. 4' Min. 6'Max. 9' Min.
5'Max. 5' Min. 7'Max. 11' Min.
B)
C)
D)
E)
Vertical Venting with Three (3) 90o Elbows
One 90o elbow = Two 45o elbows.
Option
A)
V
H + H1 V + V1
With these options, max. to-
tal pipe length is 30 feet with
min. of 10 feet total vertical
and max. 8 feet total horizon-
tal.
Please note min. 1 foot
between 90o elbows is re-
quired.
2' Min. 3'Max. 4' Min.
3' Min. 4'Max. 6' Min.
4' Min. 5'Max. 7' Min.
5' Min. 6'Max. 8' Min.
6' Min. 7'Max. 9' Min.
7' Min. 8'Max. 10' Min.
B)
C)
D)
E)
F)
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
17
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
VENTING ARRANGEMENTS - VERTICAL TERMINATIONS
SIMPSON DURA-VENT DIRECT VENT GS SYSTEM
(Propane & Natural Gas)
The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations , using two 90o elbows,
with Simpson Dura-Vent Direct Vent GS vent systems for Propane and Natural Gas.
•
•
•
Vent must be supported at offsets.
Firestops are required at each floor level and whenever passing through a wall.
Maintain clearances to combustibles.
Note: Must use optional flue adapter when using Simpson Dura-Vent pipe (Part # 510-994).
18
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
The P48-1 is approved for a maximum 40 ft. straight vertical, with Simpson
Dura-Vent Direct Vent GS vent systems for Propane and Natural Gas, as
per diagram.
The shaded area in the diagram shows all allowable combinations of straight
vertical and offset to vertical terminations with Simpson Dura-Vent Direct
Vent GS vent systems for Propane and Natural Gas. Maximum two 45o
elbows allowed.
•
•
Vent must be supported at offsets
Firestops are required at each floor level and whenever passing
through a wall.
•
Maintain clearances to combustibles as listed on pages 6 to 9.
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
19
INSTALLATION
They may be located by examining the
inside of the female ends.
HORIZONTAL
INSTALLATIONS
Note: Apply sealant "Mill-Pac" to inner
pipe and high temp silicone seal-
ant to outer pipe on every twist-
lock joint.
Install the vent system according to the manu-
facturer's instructions included with the com-
ponents.
b) Horizontal runs of vent must be sup-
ported every 3 feet (0.9meter). Wall
straps are available for this purpose.
1) Set the unit in its desired location. Check to
determine if wall studs or roof rafters are
in the way when the venting system is
attached. If this is the case, you may want
to adjust the location of the unit. Rough in
the gas preferably on the right side of the
unit and the electrical (junction block is on
the left side) on the left.
5) Mark the wall for a 11" x 11" (279mm x
279mm) square hole. The center of the
square hole should line up with the center-
lineofthehorizontalpipe.Cutandframethe
11inch (279mm)squareholeintheexterior
wall where the vent will be terminated.
Diagram 5
The four wood screws provided should be
replaced with appropriate fasteners for
stucco, brick, concrete, or other types of
sidings.
2) Direct Vent pipe and fittings are designed
with special twist-lock connections to con-
nect the venting system to the appliance
flue outlet. A twist-lock appliance adaptor
is an available option that must be used in
conjunction with the Simpson Dura-Vent
Direct Vent GS system. Install the adaptor
after the unit is set in its desired location
otherwise the unit will not fit through the
36-5/8" (930mm) high frame opening.
If the wall being penetrated is constructed
of non-combustible material, i.e. masonry
block or concrete, a 8" (203mm) diameter
hole is acceptable.
7) Before connecting the horizontal run of
vent pipe to the vent termination, slide the
Wall Thimble (Part # 1247) over the vent
pipe.
8) Slide the appliance and vent assembly to-
wards the wall carefully inserting the vent
pipe into the vent cap assembly. It is impor-
tant that the vent pipe extends into the vent
cap sufficient distance so as to result in a
minimum pipe overlap of 1-1/4 inches
(32mm). Secure the connection between
the vent pipe and the vent cap by attaching
the two sheet metal strips extending from
the vent cap assembly into the outer wall of
the vent pipe. Use the two sheet metal
screws provided to connect the strips to
the pipe section. See Diagram 6.
3) Put a bead of silicone inside the outer
section of the adapter and a bead of Stove
Mate on the inner collar. Slip the adapter
over the existing inner and outer flue collar
and fasten to the outer collar only with the
3 supplied screws (drilling pilot holes will
make this easier). Level the fireplace and
fasten it to the framing using nails or screws
through the nailing strips.
4) Assemble the desired combination of pipe
and elbows to the appliance adaptor and
twist-lock for a solid connection.
Diagram 2
Note:
Note:
a) The horizontal run of vent must be level,
or have a 1/4 inch rise for every 1 foot
of run towards the termination. Never
allow the vent to run downward. This
could cause high temperatures and
may present the possibility of a fire.
a) Twist-lock procedure: Four indenta-
tions, located on the female ends of
pipes and fittings, are designed to slide
straight onto the male ends of adjacent
pipes and fittings, by orienting the four
pipe indentations so they match and
slide in to the four entry slots on the
male ends. (Diagram 1) Push the pipe
sections completely together, then
twist-lock one section clockwise ap-
proximately one-quarter turn, until the
two sections are fully locked. The fe-
malelockinglugswillnotbevisiblefrom
theoutside,ontheBlackPipeorfittings.
b) The location of the horizontal vent ter-
mination on an exterior wall must meet
alllocalandnationalbuildingcodes,and
must not be blocked or obstructed. For
External Vent Terminal Locations, see
diagram on page 11.
Diagram 6
9) Install wall thimble in the center of the 11"
(279mm) square and attach with wood
screws (Diagram 7).
6) The arrow on the vent cap should be
pointing up. Insure that the 1-1/4"(32mm)
clearances to combustible materials are
maintained(Diagram5).Installthetermina-
tion cap.
Diagram 1
Note: If installing termination on a siding
covered wall, a vinyl siding stand-
off or furring strips must be used
to ensure that the termination is
not recessed into the siding.
Diagram 7
20
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
4) Assemble the desired lengths of pipe and
elbows. Ensure that all pipes and elbow
connections are in the fully twist-locked
position and sealed.
VERTICAL
TERMINATION
1) Maintain the 1-1/4"(32mm)
clearances (air spaces) to
combustibles when pass-
ing through ceilings, walls,
roofs, enclosures, attic raft-
er, or other nearby combusti-
ble surfaces. Do not pack air
spaces with insulation.
Check pages 16-17 for the
maximum vertical rise of the
venting system and the maxi-
mum horizontal offset limita-
Note:
Diagram 5
Apply sealant "Mill-Pac" to inner pipe and
high temp silicone sealant to outer pipe
on every twist-lock joint.
Roof Pitch
Minimum Vent Height
Feet
2
Meters
0.61
0.61
0.61
0.76
0.99
1.22
1.52
1.83
2.13
2.29
2.44
flat to 7/12
over 7/12 to 8/12
over 8/12 to 9/12
over 9/12 to 10/12
over 10/12 to 11/12
over 11/12 to 12/12
over 12/12 to 14/12
over 14/12 to 16/12
over 16/12 to 18/12
over 18/12 to 20/12
over 20/12 to 21/12
2
2
tions.
2.5
3.25
4
Diagram 1
2) Set the gas appliance in its
desiredlocation.Drop
5
a plumb bob down
from the ceiling to the
position of the appli-
ance flue exit, and
mark the location
where the vent will
penetrate the ceiling. Drill a small hole at his
point. Next, drop a plumb bob from the roof
to the hole previously drilled in the ceiling,
and mark the spot where the vent will
penetratetheroof.Determineifceilingjoists,
roof rafters or other framing will
obstruct the venting system. You
may wish to relo-
6
5) Cut a hole in the roof centered on the small
drilled hole placed in the roof in Step 2. The
hole should be of sufficient size to meet the
minimum requirements for clearance to
combustibles of 1-1/4"(32mm). Slip the
flashingundertheshingles(shinglesshould
overlap half the flashing) as per Diagram 4.
7
7.5
8
A poor draft, or down drafting can result from
high wind conditions near big trees or adjoin-
ing roof lines, in these cases, increasing the
vent height may solve the problem.
7) Ensure vent is vertical and secure the base
of the flashing to the roof with roofing rails,
slide storm collar over the pipe section and
seal with a mastic.
cate the appliance
or to offset, as
shown in Diagram
2 to avoid cutting
8) Install the vertical termination cap by twist-
loadbearingmem-
locking it.
bers.
Note: Any closets or storage spaces,
which the vent passes through
must be enclosed.
Diagram 4: The upper half of the flashing is
installed under the roofing material and not
nailed down until the chimney is installed.
This allows for small adjustments.
Diagram 2
OffsetChart
3) A Firestop spacer must be installed in the
floor or ceiling of every level. To install the
Firestop spacer in a flat ceiling or wall, cut
a 11 inch (279mm) square hole. Frame the
hole as shown in Diagram 3 and install the
firestop.
6) Continue to assemble pipe lengths.
Note: If an offset is necessary in the attic
to avoid obstructions, it is impor-
tant to support the vent pipe every
3 feet (0.9 meter), to avoid exces-
sive stress on the elbows, and
possible separation. Wall straps
are available for this purpose
(Diagram 2).
Galvanized pipe is desirable above the roof-
line due to its higher corrosion resistance.
Continue to add pipe sections through the
flashing until the height of the vent cap meets
theminimumheightrequirementsspecifiedin
Diagram 5 or local codes. Note that for steep
roof pitches, the vertical height must be in-
creased.
Diagram 3
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
21
INSTALLATION
4) Separate the 2 halves of the wall thimble
and securely fasten the one with the tabs
to the outside wall making sure that the tabs
are on top and bottom. Fasten the other
thimble half to the inside wall. The thimble
halves slip inside each other and can be
adjusted for 2 x 4 or 2 x 6 walls. The liners
must slip over the collars a minimum
of 1-3/8".
IMPORTANT: Do not locate termination
hood where excessive snow or ice build-
up may occur. Be sure to check vent
terminationareaaftersnowfalls, andclear
to prevent accidental blockage of venting
system. When using snow blowers, make
sure snow is not directed towards vent
termination area.
INSTALLATION
PROCEDURES
for Regency Direct Vent
System (Flex)
1) Locate the unit in the framing, rough in the
gas (preferably on the right side of the unit)
and the electrical (Junction block is on the
left side) on the left. Locate the centerline 5) Slip the assembled liner and termination
of the termination and mark wall according-
ly. Cuta11"(279mm)holeinthewall(inside
dimension).
assembly through the thimble making sure
the termination cap faces up (there are
markings on the cap that show which way
is up). This will position the termination cap
with proper down slope for draining water.
Fasten the cap to the outer wall with the 4
supplied screws.
ASTROCAPXL
DIMENSIONS
Note: A top clearance of 2-1/2"(64mm)
and side & bottom clearance of
1-1/2"(38mm) must be maintained
except that only a 1" (25mm) clear-
ance is needed at the termination 6) Pull the centre 5"(127mm) liner and outer
end. We recommend framing a
11"(279mm) x 11"(279mm) (inside
dimensions) hole to give struc-
tural rigidity for mounting the ter-
mination.
8"(203mm) liner out enough to slip over the
flue collars of the fireplace. (You may wish
to cut the liner shorter to make it more
workable.) Do not bend liner more than 90o.
7) Apply Mill Pac over the fireplace inner collar
and slip the 5"(127mm) liner down over it
and attach with 3 supplied screws.
8) Do the same with the 8"(203mm) liner.
Note: To make the
installation more
aesthetically pleas-
ing, we recom-
mend framing out a
square to mount
the terminal to.
9) Apply a bead of silicone between the thim-
ble and termination and around the outer
edge of the terminal at the wall in order to
keep the water out.
Note: If installing termination on a siding
covered wall, furring strips must
be used to ensure that the termi-
nation is not recessed into the
siding.
2) Level the fireplace and fasten it to the
framing using nails or screws through the
nailing strips.
3) Assemble the vent assembly by applying
Mill Pac to the 5"(127mm) inner collar of the
terminationand slippingthe5"(127mm)liner
over it at least 1-3/8" (35mm). Fasten with
the 3 screws (drilling pilot holes will make
this easier). Apply Mill Pac or high temper-
aturesiliconetothe8"(203mm)flexpipeand
slip it over the 8" outer collar of the vent
terminal at least 1-3/8"(35mm) and fasten
with the 3 screws.
NOTE: Horizontal sections must be sup-
ported at intervals not exceeding 3
feet (0.9 meter). (Flame picture and
performance will be affected by
sags in the liner).
22
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
The manifold pressure is controlled by a regu-
lator built into the gas control, and should be
checked at the pressure test point.
For USA installations follow local codes and/or
the current National Fuel Gas Code, ANSI
Z223.1.
P48-NG1SystemData
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes: #27
Note: To properly check gas pressure,
both inlet and manifold pressures
should be checked using the valve
pressure ports on the valve.
When using copper or flex connectors use only
approved fittings. Always provide a union so
that gas lines can be easily disconnected for
servicing. Flare nuts for copper lines and flex
connectors are usually considered to meet this
requirement.
Max. Input Rating 51,000 Btu/h
Min. Input Rating 29,000 Btu/h
Supply Pressure min.5.0" w.c.
1) Makesurethevalveisinthe"OFF"position.
Manifold Pressure
2) Loosen the "IN" and/or "OUT" pressure
tap(s), turning counterclockwise with a
1/8" wide flat screwdriver.
Important: Always check for gas leaks
with a soap and water solution or gas
leak detector. Do not use open flame for
leak testing.
(High)
3.8"+/- 0.2"w.c.
Log Set: Ceramic fibre, 8 per set.
Vent System: Simpson Dura-Vent Direct
Vent System, Regency Flex Kit
3) Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" ID hose.
PILOT ADJUSTMENT
4) Light the pilot and turn the valve to "ON"
P48-LP1 System Data
position.
Conversion Kit# 370-969
5) The pressure check should be carried out
with the unit burning and the setting should
be within the limits specified on the safety
label.
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes: #47
Max. Input Rating 48,000 Btu/h
Min. Input Rating 26,000 Btu/h
6) When finished reading manometer, turn off
the gas valve, disconnect the hose and
tighten the screw (clockwise) with a 1/8"
flat screwdriver. Note: Screw should be
snug, but do not over tighten.
Supply Pressure min.12.0" w.c.
Manifold Pressure
Periodically check the pilot flames. Cor-
rect flame pattern has three strong blue
flames: 1 flowing around the thermopile,
1 around the thermocouple and 1 flowing
across the burner (it does not have to be
touching the burner).
(High)
11"+/- 0.2" w.c.
S.I.T. VALVE DESCRIPTION
Log Set: Ceramic fibre, 8 per set.
Vent System: Simpson Dura-Vent Direct
Vent System, Regency Flex Kit
1) Gas cock knob
2) Manual high/low adjustment
3) Pilot Adjustment
4) Thermocouple Connection - option
5) Outlet Pressure Tap
6) Inlet Pressure Tap
7) PilotOutlet
Note: If you have an incorrect flame pat-
tern, contact your Regency dealer
for further instructions.
HIGH ELEVATION
Incorrect flame pattern will have small,
probably yellow flames, not coming into
proper contact with the rear burner or
thermopile or thermocouple.
8) Main Gas Outlet
9) Alternative TC Connection
Point
This unit is approved in Canada for altitude 0 to
4500 ft. (CAN1 2.17-M91).
GAS LINE
INSTALLATION
The gas line can be brought through either the
right,theleftside orthebottomoftheappliance.
The gas valve is situated on the bottom of the
unit.
The gas line connection may be made of rigid
pipe, copper pipe or an approved flex connec-
tor. (If you are using rigid pipe, ensure that the
valve can be removed for servicing.) Since
somemunicipalitieshaveadditionallocalcodes
it is always best to consult with your local
authorities and the CAN/CGA B149 installation
code.
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig. (3.45
kPa). Disconnect piping from valve at pres-
sures over 1/2 psig.
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
23
INSTALLATION
BRICK PANELS INSTALLATION
1) Unhook the 2 spring loaded hooks from the bottom of the flush door
5) Place the top bracket onto the front edge of the top panel (refer to
and lift the Flush Front off the unit.
Diagram 5).
2) Unwrap the brick pattern panels from the protective wrapping.
Top Bracket
Note: The logs must not be in the unit.
a)
Loosen the two screws from the bottom of the
baffle plate. Install the bottom clips onto the
plate (refer to Diagram 1).
b a f f l e
Diagram 5
6) Slide the top panel and bracket assembly carefully onto the baffle
plate ensuring the panel is centered. Make sure the tabs of the top
bracket fit into the baffle openings (refer to Diagrams 6 & 7). The
back of the top brick panel sits on top of the bottom clips.
Bottom
Clips
Tabs
Diagram 1
Diagram 6
3) Insert the back brick panel first by carefully slipping it between the
back wall of the firebox and the rear log bracket (refer to Diagram
2).
Diagram 2
Diagram 7
4) Put the side panels in next. Tilt them in towards the middle of the
firebox and put the bottom front corner in first. Be very careful not
to scratch them on the firebox hardware. Place them flat up against
the wall, they should fit snugly against the top of the firebox (refer
to Diagrams 3 & 4).
NOTE:
If the bottom brick panel must be removed: Remove
the grate, then remove the Burner Tray. See instructions in
manual.
IMPORTANT
Dangerous operating conditions
may occur if the panels are broken.
Diagrams 3 & 4
24
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
LOG SET INSTALLATION
Read the instructions below carefully and refer to the diagrams.
If logs are broken do not use the unit until they are replaced.
Broken logs can interfere with the pilot operation.
The gas log kit (Part # 370-930) contains the following pieces:
a) 02-83
b) 02-84
c) 02-85
d) 02-86
e) 02-87
f) 02-88
g) 02-89
h) 02-90
i)
Center Cross Log
Right Side Cross Log
Front Left Side Log
Front Right Side Log
Left Side End Log
Rear Log
Middle Right Side Log
Right Side End Log
Embers (Lava)
902-338
902-339
902-340
902-341
902-342
902-343
902-344
902-345
902-154
902-179
02-88
h)
Vermiculite
02-90
4) Place Log 02-85 on the front left side of the burner. Position the right
end of the log into the pin on the burner and rest the left end of the
log between the 1st grate post and the front tab.
02-88
02-88
02-85
02-87
02-89
02-86
02-84
02-85
02-83
Pin
Tab
1st Grate Post
The "02" reference numbers (i.e. 02-83) are molded
into the rear of each log.
5) Line up the two holes on the underside of Log 02-86 with the 2 pins
on the right side of the burner and position into place.
1) Carefully remove the logs from the box and unwrap them. The logs
are fragile, handle with care - do not force into position.
02-88
2) Sprinkle the vermiculite all over the top of the base brick panel.
3) Line up the two holes on the underside of Log 02-88 with the 2 pins
at the rear of the grate and position into place.
02-86
02-85
Pins
Pins
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
25
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
6) Embers should be placed in front of Log 02-85 and Log 02-86.
8) Line up the hole on the underside of Log 02-84 with the pin on Log
02-86andpositionthenotchonthebottomofthelogintothelastgrate
post.
02-88
02-84
02-86
02-85
02-86
02-83
Embers
Last Grate Post
Pin in Log
CAUTION: DO NOT cover burner ports with embers.
9) Place Log 02-89 against the notch in Log 02-84. Rest the notch at
the end of the log against the grate.
7) Place Log 02-83 onto the pin in Log 02-88 and position the notch on
the bottom of the log into the 4th grate post.
02-88
02-88
02-83
02-86
02-89
02-85
02-84
Rest log onto the pin
in Log 02-88.
Rest notch at the end of
the log against the grate.
Notch
02-83
02-86
02-85
4th Grate Post
Position the notch on the bottom of
the log into the 4th grate post.
26
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
10) Place Log 02-90 onto the right side of the grate. Position the cut-out on
the underside of the log onto the grate bar.
11) Place Log 02-87 on the middle left side of the burner. Position the
bottom rear of the log against the rear tab on the left side of the
grate. Rest the front edge of the log in the notches on Log 02-85.
02-87
02-90
Tab
Cut-out
on the underside of
the log.
02-85
02-90
02-83
02-88
02-89
02-87
02-84
02-85
Position the cut-out onto the
grate bar.
Notches
02-87
02-90
02-89
02-88
02-85
02-83
02-84
02-86
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
27
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
STANDARD
FLUSH LOUVERS
FLUSH DOOR
1) Install the top louver by sliding the two
bracket clips into the brackets located un-
derneath the top of the firebox.
The standard flush door comes with a black
frame. To install the frame, simply hook the top
door flange onto the top of the unit and swing
the door towards the unit, diagram 1.
2) Install the bottom louver by folding the lou-
ver down and then sliding the Bottom Lou-
ver bracket down onto the 2 pins on the
base of the unit (diagram 1). Secure with 1
screw as per diagram 2.
Burner ON/OFF control box attached to
bottom flush louver.
Optional Flush Trim
Attach the round magnets to the back of the top
trim piece and to the bottom trim piece, then
attach trim to the top and bottom of Flush door.
Diagram 1
Diagram 2
Diagram 1
Be careful that the glass gasket does not roll up;
there must be a gap between the gasket and the
door lip to ensure that the door sits securely on
the unit. Diagram 2.
Note: Top and
bottom louvers
are different.
3) Openthebottomlouver.PulltheBurnerON/
OFF control box from inside the bottom of
the fireplace. Using the 2 screws on the
louver, secure the control box in place.
Diagram 2
Use the hook to pull the spring out until you can
put the hook into the slot on the bottom door
bracket. Repeat for 2nd and 3rd spring. See
diagram 3.
Diagram 3
NOTE: Springs must always be OVER
not under the gas line.
To remove the flush door, reverse the above
steps.
Burner ON/OFF
control box
Screws on
louver bracket
28
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
4) Reconnect the 2 spring hooks securing the
flush door.
OPTIONAL BAY DOOR
BAY LOUVERS
The Bay louvers MUST be used
with the Bay glass option.
1) Install top louver by sliding the two bracket
clips into the brackets located on top of the
bay door. See below. The fitted louver
leaves a small gap between faceplate
bottom and louver top.
5) Slide the valve extension knobs onto the
valve knobs.
The optional Bay door is an overlay on the
flush front. The standard flush door and glass
must remain on the unit.
1) Unhook the 2 spring loaded hooks from the
bottom of the flush door.
Note: If any maintenance etc. must be
done in the firebox, first remove
the Bay louvers and door.
2) Hook the top of the bay door over the flush
door flange and swing the bottom against
the bottom flange of the flush door.
Note: Top and bottom louvers and
brackets are different.
Optional Bay Trim
Attach the supplied magnets each to the back
ofthetopandbottomtrimpieces,andattachtrim
to the topand bottomof Bay door. See diagrams
3 and 4.
2) Install bottom louver by sliding the two
bracket clips into the brackets located un-
derneath the bay door. Install bottom louver
by sliding the two bracket clips into the
brackets located underneath the bay door
and secure with 1 screw on each end.
Diagram 3
3) Openthebottomlouver.PulltheBurnerON/
OFF control box from inside the bottom of
the fireplace. Using the 2 screws on the
louver, secure the control box in place.
3) Secure to the flush door bottom bracket with
2 screws provided.
Burner
ON/OFF
control
box
Screws
on louver
bracket
Diagram 4
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
29
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
DOUBLE SCREEN
DOOR
OPTIONAL FINISHING TRIM
NOTE: Remove both the Flush Louvers or Bay Louvers and the Flush Front or Bay Front prior
to installing the Finishing Trim.
1) Pull out the top louver.
1) Install the Finishing Trim sides as shown in the diagram, line up the holes in the side trim with
the holes in the firebox side.
2) Secure with 2 screws per side.
2) Center the screen door and hook over the
flush door.
3) Loosen the 3 screws in the top inside edge of the firebox.
4) Slide the Finishing Trim Top over the Side Trim pieces and fit the bottom bracket slots over the
screws. Tighten the 3 screws to secure.
3) Open the screen door(s) and secure the
screen door to the flush door front with 2
clips on the bottom left and right side.
Clip locations
Clip installed on right side.
30
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
OPTION 1:
OPTION 2:
OPTION 3:
REMOTE CONTROL
WALL SWITCH
WALL THERMOSTAT
Can be used with Option 1 or 2
but not both.
Can be used with Option 2 or 3
but not both.
Can be used with Option 1 or 3
but not both.
A wall thermostat may be installed if desired,
connect the wires as per the wiring diagram on
page 29. Use the table below to determine the
maximum wire length.
Use the Regency Remote Control Kit approved
for this unit. Use of other systems may void your
warranty.
1) Run the supplied 15' of wire through the
back gas inlet opening. Be careful not to
damage wire.
The remote control kit comes with a hand held
transmitter, a receiver and a wall mounting
plate.
Note: We recommend a maximum of 15'
of wire but if you wish to go with a
longer run, use the Thermostat
Wire Table.
Note: Preferable if the thermostat is in-
stalled on an interior wall.
Regencyoffersanoptionalprogrammablether-
mostat but any 250-750 millivolt rated non-
anticipator type thermostat that is CSA, ULC or
UL approved may be used.
1) Choose a convenient location on the wall to
install the receiver and the receptacle box
(protection from extreme heat is very im-
portant). Run wires from the fireplace to
that location. Use the Thermostat Wire Ta-
ble.
2) Connect the wire to the supplied wall switch
and install into the receptacle box.
CAUTION
Do not connect millivolt
wall switch wire to a 120V wire.
CAUTION
Do not connect millivolt
wall thermostat wires
to a 120V wire.
2) Connect the two wires to the gas valve.
See diagram.
Thermostat Wire Table
Recommended Maximum Lead Length
(Two-Wire) When Using Wall
Thermostat (CP-2 System)
Wire Size
Max. Length
14 GA.
16 GA.
18 GA.
20 GA.
22 GA.
50 Ft.
32 Ft.
20 Ft.
12 Ft.
9 Ft.
CAUTION
Do not connect millivolt remote
control wires to a 120V wire.
3) Install 3 AAA alkaline batteries in transmitter
and 4 AA alkaline batteries in the receiver.
Install the receiver and its cover in the wall.
Switch the remote receiver to "remote"
mode. The remote control is now ready for
operation.
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
31
INSTALLATION
WIRING DIAGRAM
No electrical power supply is required for the
gas control to operate. 120 Volt AC power is
needed for the fan switch and blower. The fan
can be hard wired if desired. A terminal block
is provided on the left hand side of the unit. A
three wire power cord can also be used and
plugged into a suitable receptacle.
NOTE: Even if the fan is not purchased with the
unit, itisstillagoodideatohardwiretheterminal
block in case the fan is installed at a later date.
(Do not cut the ground terminal off under
any circumstances.)
** However DO NOT leave this connection
live until the fan is installed.**
Fan
Ground
Nut
Star washer
#8 Ground Lug
(for mobile home)
Neutral
Live
Green
OFF
Ground
ON
120V AC
60 Hz
Black
Red
Red
Pilot
Assembly
Lockwasher
Fan Thermodisc
(normally open)
Rotary Speed
Control
Fan
ground wire
Piezo
Ignitor
White
(To THTP)
(To TH)
ON
Burner
OFF
Thermostat
Brown
White
F
Gas
In
Red
Black
To Thermocouple IN
"S.I.T" Valve
T-Stat
ON OFF
Remote Receiver
or Thermostat
(Millivolt) (Optional)
Remote Transmitter
(Optional)
Caution: Ensure that the wires do
not touch any hot surfaces and are
away from sharp edges.
CAUTION: Label all wires
prior to disconnection
when servicing controls.
Wiring errors can cause
improper and dangerous
operation.
32
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
INSTALLING THE OPTIONAL FAN
120 Volt AC power is needed for the fan switch
and blower. The fan can be hard wired if
desired. The receptacle box should be installed
on the left hand side of the unit by a qualified
electrician. The neutral (wider) slot of the po-
larized receptacle should be at the top.
9) Attach the two control boxes to the bottom
louver and tighten the 2 screws on the left
side and 2 screws on the right side.
Unit must be grounded at all times. Do not
cut the ground terminal off under any
circumstances.
1) Shut the power off.
2) Remove the standard flush door and the
optional bay door, if installed. Open the
bottom louver door.
Diagram 1
3) Remove the 2 screws holding the Burner
ON/OFF switch and bracket to the bottom
louver and lift the assembly out.
Secure left side with 2 screws.
Secure right side with 2 screws.
Diagram 2
4) Turn the fan base on its side (with the base
facing towards you) and then slide the fan
in towards the rear of the unit. Turn the fan
upright and slip it over the two mounting
studs. Take care not to damage the insula-
tion on the fan base. Ensure that the fan
blades do not rub against the valve
tubing. Diagram 1.
10) Secure the fan wires and power cord by
attaching one of the adhesive backed wire
holder clips (Part #910-199) onto the stove
base. Use the second clip to bundle up the
wires approximately 4" from the control
box. Ensure that there is no interference
with the wires when the louver is closed
and that no wire will touch the hot metal
surfaces or sharp edges.
5) Connect fan ground cable to ground lug.
Refer to wiring diagram.
11) Plug the fan power cord into the rear end of
the receptacle box to provide the maximum
clearance from the louvers.
6) Slide the thermodisc/cover assembly into
the bracket clip on the underside of the
firebox. Check that no wire will touch the hot
surfaces. Diagram 2.
Diagram 3: Use the clip & hook on the side
of the control boxes to join them together.
To Remove the Fan
1) Shut the power off.
8) Secure the two boxes together with one
7) AttachtheFancontrolboxtothe BurnerON/
screw.
OFF control box. Diagram 3.
2) Reverse the above instructions.
NOTE: The bearings are lubricated for life.
Do not lubricate them. Make sure you
vacuum the fan area on a regular basis.
IMPORTANT:
These fans collect a lot of dust from
within your home. Ensure you maintain
these fan motors on a regular basis by
vacuuming out the fan blades and hous-
ing using a soft brush nozzle.
Secure the 2 boxes together
with one screw.
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
33
INSTALLATION
CONVERSION KIT FROM NATURAL GAS TO PROPANE MODEL #370-969
FOR P48-1 USING SIT 820 NOVA GAS VALVE
THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER
IF IN DOUBT DO NOT DO THIS CONVERSION !!
Conversion Kit Contains:
5) Pull off the pilot
cap to expose the
pilot orifice.
Qty. Part # Description
1
910-018 SIT Conversion Kit-50%
Turndown LP
1
1
1
1
1
910-037 LP Injector (Pilot Orifice)
904-434 Burner Orifice #47
908-255 Decal "Converted to Propane"
908-529 5/32" Allen Key
6) Unscrew the pilot orifice with the allen key
and replace with the LP pilot orifice in the kit
and replace pilot cap.
918-032 Instruction Sheet
1) Removethelouversandtrimkit.Removethe
front door.
2) Remove the logs, embers.
3) Remove the grate by lifting straight up.
7) Remove burner orifice with a 1/2" wrench
and discard. Use another wrench to hold
on to the elbow behind the orifice.
4) Remove the burner assembly by removing
the 1 Phillips head screw and then slide the
burner assembly away from the orifice and
lift out.
Burner Orifice
8) ReinstallnewburnerorificeLPstamped#47
and tighten.
9) Remove and discard the 3 pressure regu-
lator mounting screws (A), pressure regu-
lator tower (B) and diaphragm (C).
10) Insure that the rubber gasket (D) is properly
positioned and install the new HI/LO pres-
sure regulator assembly to the valve using
the new screws (E) supplied with the kit.
Tighten screws securely.
Diagram 1: Remove the left screw and then
slide the burner assembly away from the
orifice and lift out.
11) Reverse steps 4) to 1).
14) Check for gas leaks.
12) Attach clear label "This unit has been con-
verted to Propane" near or on the serial #
decal. Attach white label "This valve has
been converted from NG to LPG using SIT
conversion Kit Code 0.907.202" onto the
valve.
15) Check inlet and outlet pressures.
16) Check operation of flame control.
17) Check for proper flame appearance and
glow on logs.
13) Replace yellow "Natural Gas" label with red
"Propane" label
34
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING INSTRUCTIONS
3) Turn gas control knob counterclockwise
During the first few fires, a white film
may develop on the glass front as part of
the curing process. The glass should be
cleaned after the unit has cooled down
or the film will bake on and become very
difficult to remove. Use a non-abrasive
cleaner and DO NOT ATTEMPT TO CLEAN
THE GLASS WHILE IT IS HOT.
OPERATING
so indicator points to the "PILOT" position.
Depress the gas control knob fully. De-
press the igniter button several times until
the pilot lights. After approximately one
minute, release the gas control knob. The
pilot flame should continue to burn. If the
pilot does not remain lit, repeat operation
allowing a longer period before releasing
gas control knob.
INSTRUCTIONS
1) Read and understand these instructions
before operating this appliance.
2) Check to see that all wiring is correct and
enclosed to prevent possible shock.
3) Check to ensure there are no gas leaks.
4) When the pilot stays lit, turn the gas knob
further counterclockwise to the "ON" po-
sition.
AERATION
ADJUSTMENT
4) Make sure the glass in the door frame is
properly positioned. Never operate the ap-
pliance with the glass removed.
5) Use the wall switch, thermostat or remote
control to turn on the unit.
The air shutter can be adjusted by moving the
adjusting wire up or down. The wire is ac-
cessed through the bottom louver opening.
Open the air shutter for a blue flame or close for
a more yellow flame. The burner aeration is
factory set but may need adjusting due to either
the local gas supply or altitude.
5) Verify that the venting and cap are unob-
structed.
6) Rotate the flame height regulator to adjust
the flame height higher or lower.
6) Ensure that the brick panels are installed.
7) Verify log placement. If the pilot cannot be
seen when lighting the unit, the logs have
been incorrectly positioned.
SHUTDOWN
PROCEDURE
Minimum Air Shutter Opening:
3/16"
Fully Open
Natural Gas
Propane
8) The unit should never be turned off, and on
again without a minimum of a 60 second
wait.
1) Use the wall switch, thermostat or remote
control to turn off the main burner.
2) Turn the main gas control clockwise to the
CAUTION: Carbon will be produced if air
shutter is closed too much.
"OFF" position to turn off the pilot.
3) Turn off all electric power to appliance if
Note: Any damage due to carboning re-
sulting from improperly setting the
aeration controls is NOT covered
under warranty.
service is to be performed.
FIRST FIRE
DO NOT BURN THE APPLIANCE
WITHOUT THE GLASS FRONT IN
PLACE.
LIGHTING
PROCEDURE
The first fire in your stove is part of the paint
curing process. To ensure that the paint is
properly cured, it is recommended that you
burn your fireplace for at least four (4) hours
the first time before you use it with the fan on.
IMPORTANT
To ignite or reignite the pilot,
you must first release the
tension springs below the door.
When first operated, the unit will release an
odour caused by the curing of the paint, the
burning off of any oils remaining from manu-
facturing. Smoke detectors in the house may
go off at this time. Open a few windows to
ventilate the room for a couple of hours.
Adjustment Wire - Pull down to open or
push up to close aeration cap.
Only when the pilot holds, without pressure
being applied to the control knob, reapply the
tension springs to the door. The unit must
not be operated with the tension springs
unattached.
Closed - Tall yellow
Open - Short Blue
Note: When the glass is cold and the
appliance is lit, it may cause con-
densation and fog the glass. This
condensation is normal and will
disappear in a few minutes as the
glass heats up.
Note: Aeration Adjustment should only
be performed by an authorized
Regency Installer at the time of
installation or service.
IMPORTANT Gas cock knob cannot be
turned from "PILOT" to "OFF" unless it is
partially depressed.
1) Turn burner OFF using "ON/OFF" switch.
2) Turn gas control knob so indicator points to
"OFF" position and allow 5 minutes for any
gas in the combustion chamber to escape.
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
35
OPERATING INSTRUCTIONS
Copy of the Lighting Plate Instructions
NORMAL OPERATING
SOUNDS OF
GAS APPLIANCES
It is possible that you will hear some sounds
from your gas appliance. This is perfectly
normal due to the fact that there are various
gauges and types of steel used within your
appliance. Listedbelowaresomeexamples. All
are normal operating sounds and should
not be considered as defects in your appliance.
Blower:
Regency gas appliances use high tech blow-
ers to push heated air farther into the room. It
is not unusual for the fan to make a "whirring"
sound when ON. This sound will increase or
decrease in volume depending on the speed
setting of your fan speed control.
Burner Tray:
The burner tray is positioned directly under the
burner tube and logs and is made of a different
gauge material from the rest of the firebox and
body. Therefore, the varying thicknesses of
steel will expand and contract at slightly differ-
ent rates which can cause "ticking" and "crack-
ing" sounds. You should also be aware that as
there are temperature changes within the unit
these sounds will likely re-occur. Again, this is
normal for steel fireboxes.
Blower Thermodisc:
When this thermally activated switch turns ON
it will create a small "clicking" sound. This is the
switch contacts closing and is normal.
Pilot Flame:
While the pilot flame is on it can make a very
slight "whisper" sound.
Gas Control Valve:
As the gas control valve turns ON and OFF, a
dullclickingsoundmaybeaudible,thisisnormal
operation of a gas regulator or valve.
Unit Body/Firebox:
Different types and thicknesses of steel will
expand and contract at different rates resulting
in some "cracking" and "ticking" sounds will be
heard throughout the cycling process.
36
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE
7) Drop the thermocouple or thermopile down
through the extrusion and pull it out of the
unit.
2) Remove the Cap, and shine a flashlight
down the Vent. Remove any bird nests, or
other foreign material.
MAINTENANCE
INSTRUCTIONS
8) Reinstall the new ones in reverse order.
3) Check for evidences of excessive con-
densation, such as water droplets forming
intheinnerliner,andsubsequentlydripping
out the joints, Continuous condensation
can cause corrosion of caps, pipe, and
fittings. It may be caused by having exces-
sive lateral runs, too many elbows, and
exterior portions of the system being ex-
posed to cold weather.
1) Always turn off the gas valve before
cleaning. For relighting, refer to lighting
instructions. Keep the burner and control
compartment clean by brushing and vacu-
uming at least once a year. When cleaning
the logs, use a soft clean paint brush as the
logs are fragile and easily damaged.
GLASS GASKET
If the glass gasket requires replacement use
a tadpole glass gasket (Part # 936-155).
2) Cleanapplianceanddoorwithadampcloth
(never when unit is hot). Never use an
abrasive cleaner. The glass should be
cleaned with a gas fireplace glass cleaner.
The glass should be cleaned when it
starts looking cloudy.
4) Inspect joints, to verify that no pipe sections
or fittings have been disturbed, and conse-
quently loosened. Also check mechanical
supports such as Wall Straps, or plumbers'
tape for rigidity.
GOLD-PLATED
LOUVERS
3) The heater is finished in a heat resistant
paint and should only be refinished with
heat resistant paint. Regency uses Stove-
Bright Paint - Metallic Black #6309.
The 24 carat gold-plated finish on the louvers
and trim requires little maintenance, and need
only be cleaned with a damp cloth.
LOG REPLACEMENT
DO NOT use abrasive materials or chemical
cleaners, as they may harm the finish and void
the warranty.
4) Make a periodic check of burner for proper
position and condition. Visually check the
flame of the burner periodically, making
sure the flames are steady; not lifting or
floating. Ifthereisaproblem, callaqualified
service person.
Theunitshouldneverbeusedwithbrokenlogs.
Turn off the gas valve and allow the unit to cool
before opening door and carefully remove the
logs. (The pilot light generates enough heat to
burn someone.) If for any reason a log should
need replacement, you must use the proper
replacement log. The position of these logs
must be as shown in the diagrams under Log
Installation.
Clean any fingerprints off before turning
the unit on.
5) The appliance and venting system must be
inspected before use, and at least annual-
ly, by a qualified field service person, to
ensure that the flow of combustion and
ventilation air is not obstructed.
Note: Improper positioning of logs may
create carbon build-up and will
severely alter the unit's perform-
ance which is not covered under
warranty.
Note: Never operate the appliance with-
out the glass properly secured in
place.
6) Do not use this appliance if any part has
been under water. Immediately call a qual-
ified service technician to inspect the ap-
pliance and to replace nay part of the
control system and any gas control which
has been under water.
THERMOPILE/
THERMOCOUPLE
1) OpentheBottomLouversorGrills.Remove
7) In the event this appliance has been serv-
iced check that the vent-air system has
been properly resealed & reinstalled in
accordance with the manufacturer's in-
structions.
the Top Louver or Grill.
2) Open and remove door.
3) Remove log set and embers.
4) Remove grate and burner.
8) Verify operation after servicing.
General Vent Maintenance
5) Disconnect thermocouple by loosening nut
from the valve with a 9mm wrench. Discon-
nect thermopile by loosening 2 screws
marked TP on the valve.
Conduct an inspection of the venting system
semiannually. Recommended areas to inspect
as follows:
6) Remove 2 screws from the pilot assembly
and pull up far enough to be able to loosen
thethermocoupleorthermopilewitha7/16"
wrench. NOTE: the pilot line is very fragile,
use caution when pulling it up.
1) Check the Venting System for corrosion in
areas that are exposed to the elements.
These will appear as rust spots or streaks,
and in extreme cases, holes. These com-
ponents should be replaced immediately.
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
37
MAINTENANCE
Bay Glass Replacement
INSTALLING VALVE
DOOR GLASS
1) Remove the door from the unit and place on
Your Regency fireplace is supplied with high
temperature 5mm-Ceramic glass. If your glass
requires cleaning, we recommend using an
approved glass cleaner available at all author-
ized dealers. Do not use abrasive materials.
1) Attach the valve to the valve bracket with
a soft surface to prevent scratching.
the 4 (m5x8 metric) screws provided.
2) Remove the nuts holding the glass clips in
2) Reconnect the "gas out" flare fitting with an
place and remove.
11/16" wrench.
3) Replace the glass. The glass must have
CAUTION&WARNINGS:
3) Reconnect the "gas out" flare nut with a 13/
gasketing around it.
16" wrench.
* Do not clean when the glass is hot.
* Theuseofsubstituteglasswillvoidallproduct
warranties.
* Care must be taken to avoid breakage of the
glass.
4) Install piezo ignitor push button assembly
and reconnect wire.
5) Reconnectthequickdropoutthermocouple
* Do not strike or abuse the glass.
* Do not operate this fireplace without the glass
front or with a cracked or broken glass front.
* Wear gloves when removing damaged or
broken glass.
nut with a 9mm wrench.
6) Reconnect the pilot tube nut with a 7/16"
wrench.
* Replacement of the glass panel(s) should be
done by a licensed or qualified service per
son.
7) Scrape off the old gasket from the floor of
the firebox and from the valve tray assem-
bly.
8) Install a new gasket and reinstall the valve
GLASSREPLACEMENT
tray assembly.
Note: Failure to install a new gasket
may severely affect the appliance
performance.
In the event that you break your glass by impact,
purchase your replacement from an authorized
Regency dealer only.
9) Reinstall the 10 hold down screws.
Replacement glass is shipped already installed
into the door frame. Reinstall as per Glass Door
Installation on page 28.
10) Hook up the 2 TP and 2 TH wires to the
appropriate connections on the valve.
11) Reinstall the two bottom deflectors and
CAUTION: Wear gloves when re-
moving damaged or broken glass.
brick panels.
4) Reverse the previous steps, replace the
glass clips and fasten with the nuts but do
not over tighten, as this can break the glass.
12) Install burner and grate assembly.
13) Hookupthegaslineandcheckforgasleaks
with a soap and water solution or a gas leak
detector. (Do not use open flame for leak
testing.)
WARNING: Do not operate the
appliance with the glass panels
removed, cracked or broken. Re-
placement of the glass panels
should be done by a licensed or
qualified service person.
5) Replace door on the stove and check the
seal.
14) Fire up the unit temporarily.
15) Check the manifold pressure.
16) Reinstall the logs and brick panels as need-
ed.
17) Close the door and replace the louvers.
18) Fire up the unit again and check for proper
flame appearance and glow on logs.
38
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE
7) Remove the right and left side deflectors by
REMOVING VALVE
removing the 2 screws on each deflector.
1) Shut off the gas supply.
2) Remove the louvers (and bay door if it has
been installed).
3) Open the flush door and remove the door.
4) Remove the logs and side brick panels, if
installed.
Lift entire valve tray
assembly out.
5) Remove the grate by lifting up and out.
11) Disconnect the 2 TP wires and the 2 TH
wires from the valve.
Right Side
Deflector
12) Undo the pilot tube from the valve with a 7/
16" wrench.
13) Undo the quick drop out thermocouple nut
on the valve with a 9mm (metric) wrench.
14) Remove the Piezo igniter wire and push
Grate
button assembly.
6) Remove the burner by removing the screw
on the left side and then slide the burner to
the left and lift out.
Left Side
Deflector
8) Remove the base brick panels.
9) Disconnect the inlet gas line.
Thermopile Thermocouple
Wire Wire
Pilot Nut
10) Remove the 10 Phillips head screws secur-
ing the valve tray assembly in place and
then lift the entire assembly out.
15) Undo the "gas out" flare nut with a 13/16"
wrench.
Remove the screw on the left
side of the burner.
16) Undo the "gas out" flare fitting with an 11/
16" wrench.
17) Removethe4Phillipsheadscrewsfromthe
sides of the valve bracket and remove
valve.
Hint: If you are using black pipe, ensure
that there is a union by the valve,
otherwise removal will be almost
impossible.
Slide the burner to the left and lift out.
Valve Tray
Assembly
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
39
PARTS LIST
P48-1 MAIN ASSEMBLY
Part #
Description
Part #
Description
1) 948-259 Door Handle
3) 948-046 Chain
4) 948-115 Spring
51) 902-331 Brick Panel - Base Center
52) 902-332 Brick Panel - Base Left
53) 902-333 Brick Panel - Base Right
6) 430-129 Receptacle Box Mount
7) 910-429 Box - Receptacle
8) 910-428 Duplex Receptacle
9) 910-430 Cover - Receptacle
10) 904-687 Clamp Connector
370-928 Brick Panel Set - Standard
54) 902-334 Brick Panel - Back
55) 902-335 Brick Panel - Left
56) 902-336 Brick Panel - Right
57) 902-582 Brick Panel - Top
20) 370-037 Top Nailing Strip
21) 370-038 Side Nailing Strip
370-945 Herringbone Brick Panel Set
902-364 Herringbone Brick Panel - Back
902-365 Herringbone Brick Panel - Left
902-366 Herringbone Brick Panel - Right
902-583 Heringbone Brick Panel - Top
22) 370-015 Baffle Plate
23) 780-011 Standoff - Top
24) 780-013 Standoff - Side/Back
370-901 Brick Panel Set - Standard Brown
370-902 Brick Panel Set - Standard Red
370-903 Brick Panel Set - Herringbone Brown
370-904 Brick Panel Set - Herringbone Red
27) *
28) *
29) *
30) *
Outer Flue Collar
Inner Flue Collar Assy
FlueMountingPlate
Gasket for Flue Collar
946-556 Optional Heat Wave Duct Kit
89) 946-004 Junction Box
35) *
Thermodisc Bracket
90) 946-000 Round Duct Adaptor
91) 946-002 Round to Oval Adaptor
92) 946-001 Oval Duct Adaptor
93) 946-007 Angle Bracket
38) 910-241 Switch - Burner ON/OFF(3-way)
910-899 Wire Harness-Valve to Burner
432-917 Fan & Speed Control Assy (120 Volts) Optional
94) 946-517/P Fan Assembly - HeatWave Option
95) 946-006 Grill Plate - White
42) 910-331/P Fan Motor
96) 946-005/01 Wall Adaptor Plate - White
97) 910-417 Knob - White
432-966 Fan Switch Assy (120 Volts) Optional
98) 910-366 Switch Cover Plate - White
99) 910-412 Fan Speed Controller
43) 910-813 Power Cord (120 Volts)
46) 910-330 Fan Speed Control Switch
47) 904-586 Knob - Speed Control
48) 910-199 Wire Holder Clip
49) 910-142 Thermodisc - Fan (Auto ON/OFF)
910-845 Wire Harness - Plug In Fan
100) 910-367 Box - Plastic Switch Receptacle
101) 690-022 Cover Plate - Outer Box Side
102) 946-010 Flexible Air Duct
946-011 Insulation 6" dia. x 24"
50) 770-994 Optional Dura-Vent Adaptor
946-570 Heat Release Duct Kit (Optional)
105) 910-165 Fan (120 Volts)
106) 946-000 Flexible Air Release Duct
370-969 Conversion Kit - NG to LP
918-458 Manual
*Not available as a replacement part.
40
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS LIST
30
28
89
50
93
94
30
20
29
93
27
21
23
92
91
22
96
95
23
102
100
99
24
21
97
98
90
HEAT WAVE DUCT KIT
DOORS & LOUVERS PLEASE
REFER SEPARATE SECTION
10
101
6
7
8
4
35
3
9
55
57
1
24
42
54
106
56
49
48
38
43
47
105
46
52
51
HEAT RELEASE DUCT KIT
53
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
41
PARTS LIST
P48-1 BURNER & LOG ASSEMBLY
Part #
Description
370-574/P
370-576/P
*
Valve Assembly - Natural Gas
Valve Assembly - Propane
Gasket - Valve Access Plate
52)
56) 910-190
57) 910-378
910-380
Piezo Ignitor & Nut
Valve S.I.T. - Natural Gas
Valve S.I.T. - Propane
66) 910-038
910-039
Pilot Assy - S.I.T. - 3 Flame NG
Pilot Assy - S.I.T. - 3 Flame LP
PilotHolder
67)
*
68) W840470
69) 904-662
904-434
Pilot Assembly Gasket
#27 Orifice - N.G.
#47 Orifice - Propane
Orifice Gasket
936-170
75)
*
Valve Access Plate
Burner Assembly
Burner/Grate Assembly
79) 370-535
82) 370-019
90) 910-421
91) 910-422
Pilot ON/OFF Extension Knob (with Bay Front)
HI/LOW Extension Knob (with Bay Front)
370-930
93) 902-338
94) 902-339
95) 902-340
96) 902-341
97) 902-342
98) 902-343
100) 902-344
101) 902-345
P48-1 Log Set
Center Cross Log
Right Side Cross Log
Front Left Side Log
Front Right Side Log
Left Side End Log
Rear Log
Middle Right Side Log
Right Side End Log
*Not available as a replacement part.
42
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS LIST
P48-1 FLUSH DOOR & LOUVERS
Part #
Description
Part #
Description
370-925
370-924
370-926
Flush Louvers (Set) - Steel/Black
Flush Louvers (Set) - Black
Flush Louvers (Set) - Gold/Black
Flush Louver Assembly - Top
Flush Louver Assembly - Bottom
150) *
Flush Glass Trim
370-920
370-922
904-196
Flush Glass Trim (Set) - Steel
Flush Glass Trim (Set) - Gold
Magnet
133) *
134) *
370-933
171) *
172) *
174) 511-085
178) 948-257
180) 512-546
Double Screen Door (Complete)
Door Frame Assembly - Left
Door Frame Assembly - Right
Handle
Lift Hinge on Door
Door Latch Assembly
370-518/P
135) 940-335/P
138) *
Flush Door Assembly Complete
Glass (Flush)
Flush Door Frame
139) 936-155
Glass Gasket (Tadpole)
140) 948-042
Spring Hinge
188) 948-216
Regency Logo Plate
370-944
370-946
141) *
Finishing Trim - Black
Finishing Trim - Steel
Trim Side Left
*Not available as a replacement part.
142) *
143) *
TrimSideRight
TrimTop
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
43
PARTS LIST
P48-1 BAY FRONT & LOUVERS
Part #
Description
Bay Front Complete with Glass & Black Trim
Bay Front Screen & Black Trim
370-931
370-932
106) 940-337/P
107) 936-243
108) 940-336/P
111) 902-362
112) 902-363
370-905
Side Glass
Glass Gasket
Center Glass
Brick Panel - Left Side Bay
Brick Panel - Right Side Bay
Bay Brick Panel Set - Standard Brown
Bay Brick Panel Set - Standard Red
370-906
113) 370-086
370-936
Bay Door Trim (Each) -Black
Bay Door Trim (Set) - Gold
Bay Door Trim (Set) - Steel
370-934
370-938
370-942
370-940
Bay Louvers (Set) - Black
Bay Louvers (Set) - Gold/Black
Bay Louvers (Set) - Steel/Black
Bay Louver Assembly - Top
Bay Louver Assembly - Bottom
Magnet (1" round)
115) *
116) *
117) 904-196
119) 370-093
120) 400-189
Bay Door Baffle
Flush Glass Retainer Bracket
122) 948-216
Regency Logo Plate
*Not available as a replacement part.
44
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
_____________________________________________________________________________________
____________________________________________________________
__________________________________________________________
____________________________________________________________
_______________________________________________________
_____________________________________________________
__________________________________________________________
_________________________________________________________
_________________________________________________________
______________________________________________________
______________________________________________________
_______________________________________________________________
___________________________________________________________
__________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
_____________________________________________________________
__________________________________________________________
__________________________________________________________
_____________________________________________________
________________________________________________________
_________________________________________________________
_________________________________________________________
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
45
NOTES
_____________________________________________________________________________________
____________________________________________________________
__________________________________________________________
____________________________________________________________
_______________________________________________________
_____________________________________________________
__________________________________________________________
_________________________________________________________
_________________________________________________________
______________________________________________________
______________________________________________________
_______________________________________________________________
___________________________________________________________
__________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
_____________________________________________________________
__________________________________________________________
__________________________________________________________
_____________________________________________________
________________________________________________________
_________________________________________________________
_________________________________________________________
46
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
WARRANTY
Regency Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each
unit thoroughly before it leaves our facility. FPI Fireplace Products International Ltd. is pleased to extend this limited lifetime warranty to the original
purchaser of a Regency Product. This warranty is not transferable.
The Warranty: Limited Lifetime
The combustion chamber, heat exchanger, burner tubes/pans, logs, brick panels and gold plating (against defective manufacture only) are covered under the Limited
Lifetime Warranty for five (5) years for parts and subsidized labour* and parts only thereafter.
Glass is covered for lifetime against thermal breakage only, parts and subsidized labour* for five (5) years and parts only thereafter from date of purchase.
External casting, surrounds and grills are covered against cracks and warps resulting from manufacturer defects, parts and subsidized labour* for three (3) years from
the date of purchase and parts only thereafter.
Special Finishes - One year on brushed nickel and antique copper full screens and doors. You can expect some changes in color as the product "ages" with constant
heating and cooling. FPI warranties the product for any manufacturing defects on the original product. However, the manufacturers warranty does not cover changing
colors and marks, ie. finger prints, etc applied after the purchase of the product. Damage from the use of abrasive cleaners is not covered by warranty.
Electrical and mechanical components such as blowers, switches, wiring, thermodiscs, FPI remote controls, spill switches, thermopiles, thermocouples, pilot assembly
components, and gas valves are covered for one year parts and subsidized labour* from the date of purchase. Blowers and valves replaced under warranty are considered
repairs and continue as if new with appliance. ie. twelve (12) months from original purchase date of appliance with a minimum of three (3) months coverage from date
of replacement.
FPI venting components are covered parts and subsidized labour* for three (3) years from date of purchase.
Simpson Dura-Vent venting components (Direct Vent units) are covered by Simpson Dura-Vent Inc. warranty.
Conditions:
Any part or parts of this unit which in our judgement show evidence of such defects will be repaired or replaced at FPI's option, through an accredited distributor or agent
provided that the defective part be returned to the distributor or agent Transportation Prepaid, if requested.
Porcelain/Enamel - Absolute perfection is either guaranteed nor commercially possible. Any chips must be reported and inspected by an authorized dealer within three
days of installation. Reported damage after this time will be subject to rejection.
It is the general practice of FPI to charge for larger, higher priced replacement parts and issue credit once the replaced component has been returned to FPI and evaluated
for manufacturer defect.
The authorized selling dealer is responsible for all in-field service work carried out on your Regency product. FPI will not be liable for results or costs of workmanship
from unauthorized service persons or dealers.
At all times FPI reserves the right to inspect product in the field which is claimed to be defective.
All claims must be submitted to FPI by authorized selling dealers. It is essential that all submitted claims provide all of the necessary information including customer
name, purchase date, serial #, type of unit, problem, and part or parts requested, without this information the warranty will be invalid.
Exclusions:
This limited Lifetime Warranty does not extend to or include paint, door or glass gasketing or trim.
At no time will FPI be liable for any consequential damages which exceed the purchase price of the unit. FPI has no obligation to enhance or modify any unit once manufactured.
ie. as products evolve, field modifications or upgrades will not be performed.
FPI will not be liable for travel costs for service work.
Installation and environmental problems are not the responsibility of the manufacturer and therefore are not covered under the terms of this warranty policy.
Embers, rockwool, gaskets, door handles and paint are not covered under the terms of this warranty policy.
Any unit which shows signs of neglect or misuse is not covered under the terms of this warranty policy.
The warranty will not extend to any part which has been tampered with or altered in any way, or in our judgment has been subject to misuse, improper installation, negligence
or accident, spillage or downdrafts caused by environmental or geographical conditions, inadequate ventilation, excessive offsets, negative air pressure caused by
mechanical systems such as furnaces, fans, clothes dryer, etc.
Freight damage to stoves and replacement parts is not covered by warranty and is subject to a claim against the freight carrier by the dealer.
FPI will not be liable for acts of God, or acts of terrorism, which cause malfunction of the appliance.
Performance problems due to operator error will not be covered by this warranty policy.
Products made or provided by other manufacturers and used in conjunction with the operation of this appliance without prior authorization from FPI, may nullify your
warranty on this product.
Any alteration to the unit which causes sooting or carboning that results in damage to the interior / exterior facia is not the responsibility of FPI.
* Subsidy according to job scale as predetermined by FPI.
Regency P48-1 Zero Clearance Direct Vent Gas Fireplace
Download from Www.Somanuals.com. All Manuals Search And Download.
47
Regency fireplace products are designed
withreliabilityandsimplicityinmind. In
addition, our internal QualityAssurance
Team carefully inspects each unit
thoroughly before it leaves our
door.
Fireplace Products International
Ltd. is pleased to extend this Lim-
ited Lifetime Warranty to the original
purchaser of a Regency Product.
See the inside back cover for details.
Register your Regency online at
Installer:Pleasecompletethefollowinginformation
Dealer Name & Address:______________________________________________
__________________________________________________________________
Installer: ___________________________________________________________
Phone #: ___________________________________________________________
Date Installed: ______________________________________________________
Serial No.: _________________________________________________________
Regency and Panorama are trademarks of FPI Fireplace Products International Ltd.
© Copyright 2005, FPI Fireplace Products International Ltd. All rights reserved.
Printed in Canada