Raypak Water Heater 2600401 User Guide

INSTALLATION & OPERATING  
INSTRUCTIONS  
Econopak  
Water  
Heaters  
Models 0260–0401  
Type WH  
WARNING: If the information in these instructions is not followed exactly, a fire or  
explosion may result causing property damage, personal injury or death.  
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and  
liquids in the vicinity of this or any other appliance.  
WHAT TO DO IF YOU SMELL GAS:  
Do not try to light any appliance.  
Do not touch any electrical switch; do not use any phone in your building.  
Immediately call your gas supplier from a neighbor's phone. Follow the gas  
supplier's instructions.  
If you cannot reach your gas supplier, call the fire department.  
Installation and service must be performed by a qualified installer, service agency or  
the gas supplier.  
This manual should be maintained in legible condition and kept adjacent to the heater or in a safe place for future  
reference.  
Catalog No. 3000.51F  
Effective: 04-08-09  
Replaces: 03-25-08  
P/N 240726 Rev. 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONTENTS  
WARNINGS  
Pay Attention to These Terms  
GENERAL SAFETY  
Time/Temperature Relationships in Scalds 5 Controls  
RECEIVING EQUIPMENT  
GENERAL  
SPECIFICATIONS  
INSTALLATION  
Code Requirements  
Mounting Base  
Clearances  
4 SERVICING PROCEDURES  
22  
22  
22  
26  
28  
30  
32  
33  
4
5
Sequence of Operation  
Start-up Procedures  
6
Repair Section  
TROUBLESHOOTING  
Electrical (Electronic Ignition IID)  
Electrical (Standing Pilot)  
6
8
8 ADJUSTMENTS & REPLACEMENT  
8 OF COMPONENTS  
8 WARRANTY  
34  
36  
Combustion & Ventilation Air  
Venting Connections  
Gas Supply Connections  
Water Connections & System Piping  
Electrical Wiring  
8
9
13  
14  
16  
17  
Wiring Diagrams  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNINGS—Pay Attention to These Terms  
Indicates the presence of immediate hazards which will cause severe  
personal injury, death or substantial property damage if ignored.  
DANGER:  
Indicates the presence of hazards or unsafe practices which could cause  
WARNING:  
severe personal injury, death or substantial property damage if ignored.  
Indicates the presence of hazards or unsafe practices which could cause  
CAUTION:  
minor personal injury or product or property damage if ignored.  
Indicates special instructions on installation, operation, or maintenance which  
are important but not related to personal injury hazards.  
NOTE:  
DANGER: Failure to install the draft hood and  
properly vent the water heater to the outdoors as  
outlined in the Venting section of this manual can  
result in unsafe operation of the water heater. To  
avoid the risk of fire, explosion, or asphyxiation from  
carbon monoxide, never operate this water heater  
unless it is properly vented and has an adequate air  
supply for proper operation. Be sure to inspect the  
vent system for proper installation at initial start-up;  
and at least annually thereafter. Refer to the  
Maintenance section of this manual for more  
information regarding vent system inspections.  
WARNING: Gasoline, as well as other flammable  
materials and liquids (adhesives, solvents, etc.), and  
the vapors they produce, are extremely dangerous.  
DO NOT handle, use or store gasoline or other  
flammable or combustible materials anywhere near  
or in the vicinity of a water heater. Be sure to read  
and follow the warning label pictured below and  
other labels on the water heater, as well as the  
warnings printed in this manual. Failure to do so can  
result in property damage, bodily injury, or death.  
WARNING: LP appliances should not be installed  
below-grade (for example, in a basement) if such  
installation is prohibited by federal, state and/or local  
laws, rules, regulations or customs.  
DANGER: Water heaters utilizing Liquefied  
Petroleum gas (LP) are different from natural gas  
models. A natural gas heater will not function safely  
on LP gas and vice versa. Conversion from Natural  
gas to LP gas (or vice versa) must be done by a  
qualified service technician. To avoid possible  
equipment damage, personal injury or fire: DO NOT  
connect this water heater to a fuel type not in  
accordance with unit data plate. Propane for  
propane units, Natural gas for natural gas units.  
These units are not certified for any other type fuel.  
DANGER: LIQUEFIED PETROLEUM MODELS:  
Propane, or LP gas, must be used with great  
caution.  
Vapors from  
Water heater has a main  
flammable liquids will  
burner and pilot flame.  
explode and catch fire  
The pilot flame:  
causing death or severe  
1. is on all the time and  
• It is heavier than air and will collect first in lower  
areas making it hard to detect at nose level.  
• Make sure to look and smell for LP leaks before  
attempting to light appliance. Use a soapy solution to  
check all gas fittings and connections. Bubbling at a  
connection indicates a leak that must be corrected.  
When smelling to detect an LP leak, be sure to sniff  
near the floor too.  
burns.  
2. will ignite flammable  
vapors.  
Do not use or store flammable  
products such as gasoline  
solvents or adhesives in the  
same room or area near the  
water heater.  
Vapors:  
1. cannot be seen,  
2. are heavier than air,  
3. go a long way on the  
floor,  
Keep flammable products:  
1. far away from heater,  
2. in approved containers,  
3. tightly closed and  
4. can be carried from other  
room to the pilot flame by  
their currents.  
4. out of childrenʼs reach.  
• Gas detectors are recommended in LP applications  
and their installation should be in accordance with  
the manufacturer's recommendations and/or local  
laws, rules, regulations or customs.  
• It is recommended that more than one method be  
used to detect leaks in LP applications.  
Installation:  
are at least 18" above the  
floor. This will reduce, but  
not eliminate, the risk of  
vapors being ignited by the  
main burner or pilot flame.  
Do not install water heater  
where flammable products  
will be stored or used unless  
the main burner and pilot flames  
Read and follow water heater warnings and instructions. If owners  
manual is missing, contact the retailer or manufacturer.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table A details the relationship of water temperature  
and time with regard to scald injury and may be used  
as a guide in determining the safest water temperature  
for your applications.  
GENERAL SAFETY  
To meet commercial hot water requirements, the tank-  
stat is adjustable up to 190°F. However, water  
temperatures over 125°F can cause severe burns  
instantly or death from scalds. This is the preferred  
starting point for setting the control for supplying gen-  
eral purpose hot water.  
Temperature  
120°F  
Time to Produce Serious Burn  
More than 5 minutes  
1-1/2 to 2 minutes  
125°F  
Safety and energy conservation are factors to be con-  
sidered when setting the water temperature on the  
tankstat. The most energy efficient operation will result  
when the temperature setting is the lowest that satis-  
fies the needs consistent with the application.  
130°F  
About 30 seconds  
135°F  
About 10 seconds  
140°F  
Less than 5 seconds  
Less than 3 seconds  
About 1-1/2 seconds  
About 1 second  
145°F  
150°F  
155°F  
Table courtesy of Shriners Burn Institute.  
Table A: Time to Produce Serious Burn  
Time/Temperature  
Relationships in Scalds  
The temperature of the water in the storage tank can  
be regulated by setting the temperature dial on front of  
the tankstat. To comply with safety regulations, the  
tankstat was set at its lowest setting before shipment  
from the factory.  
Water temperature over 125°F can  
causeinstantsevereburnsordeath  
from scalds.  
Fig. 1 illustrates the tankstat. To adjust the water tem-  
perature, insert a small straight screwdriver into slotted  
screw in hole in front of tankstat and turn wheel to  
desired setting. Thermostat is adjustable up to 190°F.  
Children, disabled, and elderly are  
at highest risk of being scalded.  
See instruction manual before set-  
ting temperature at water heater.  
Feel water before bathing or show-  
ering.  
Temperature limiting valves are  
available, see manual.  
Maximum water temperatures occur just after burner  
has shut off. To find hot water temperature being deliv-  
ered, turn on a hot water faucet and place a  
thermometer in the hot water stream and read the  
thermometer.  
Fig. 1: Tankstat Adjustment  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
warranty conditions, you must also specify date of  
installation.  
DANGER: There is a Hot Water SCALD Potential if  
the tankstat is set too high.  
Raypak recommends that this manual be reviewed  
thoroughly before installing your Raypak heater. If  
there are any questions which this manual does not  
answer, please contact your local Raypak representa-  
tive.  
CAUTION: Hotter water increases the risk of  
SCALDING!  
NOTE: When this heater is supplying general  
purpose hot water requirements for use by  
individuals, a thermostatically controlled mixing  
valve for reducing point of use water temperature is  
recommended to reduce the risk of scald injury.  
Contact a licensed plumber or the local plumbing  
authority for further information.  
GENERAL  
SPECIFICATIONS  
The Raypak water heaters are design certified by the  
and tested under the requirements of the American  
National Standard, ANSI Z21.10.3. Each heater has  
been constructed and pressure tested in accordance  
with the requirements of Section IV of the American  
Society of Mechanical Engineers Code, and factory  
fire tested.  
RECEIVING EQUIPMENT  
On receipt of your equipment it is suggested that you  
visually check for external damage to the carton. If the  
carton is damaged, it is suggested that a note be made  
on the Bill of Lading when signing for equipment.  
Remove the heater from the carton and if it is dam-  
aged report the damage to the carrier immediately. Be  
sure that you receive the number of packages indicat-  
ed on the Bill of Lading. Claims for shortages and  
damages must be filed with carrier by consignee.  
These heaters are designed for indoor and outdoor  
installations, and can be installed on combustible floor-  
ing when the appropriate listed floor shield base is  
used.  
Models are available with standing pilot or with inter-  
mittent ignition device (IID), and are equipped with the  
following components as standard: water circulation  
pump, pressure relief valve, manual reset high limit  
switch, flow switch, vent thermal and flame roll-out  
switches (except for models 330 and 400), a solid  
state Economaster pump control relay, 40VA trans-  
former, and redundant combination gas valve for use  
with either Natural or Propane gases. A tankstat is  
supplied loose for installation in the field.  
Purchased parts are subject to replacement only  
under the manufacturer's warranty. Debits for defec-  
tive replacement parts will not be accepted and  
defective parts will be replaced in kind only per our  
standard warranties.  
When ordering parts, you must specify Model and  
Serial Number of the heater. When ordering under  
Piping  
Dimensions (in.)***  
Connections  
Recovery  
Model  
No.  
Input  
(MBH)  
Tank  
(Gal)**  
(gph)  
H
G
Indoor*  
A
C
J
K
(NPT) (NPT)  
0260/0261  
0330/0331  
0400/0401  
264  
334  
399  
262  
332  
396  
80  
80  
80  
1-1/2  
1-1/2  
1-1/2  
3/4  
3/4  
1
22-3/8 62-7/8 11-1/8  
25-3/4 63-3/4 10-3/4  
29-1/4 65-3/8 12-1/2  
7
8
9
*Recovery based on manufacturer's rating.  
**May be used with other tank size capacity.  
***Refer to Fig. 2 for dimensions.  
Table B: Specifications and Dimensions  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
A
2
11  
8-1/2  
6-3/4  
K
J
H
40  
STACKLESS  
OUTDOOR TOP  
C
G
UP  
GAS  
OUT  
IN  
FRONT  
CONTROLS  
38  
21-1/4  
26-1/2  
ELEC  
CONN  
13-1/4  
2-1/2  
OUTDOOR  
BASE  
OPTIONAL  
COMBUSTIBLE  
FLOOR SHIELD  
8
26-1/2  
A
TANK  
UPPER  
LOWER  
HEATER  
Components should be placed as close as possible.  
Fig. 2: Dimensions and System Component Layout  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Clearances  
INSTALLATION  
Code Requirements  
Minimum Distance  
from Combustible  
Surfaces  
Heater Side  
Installation must be in accordance with local codes, or,  
in the absence of local codes, with the latest editions  
of the National Fuel Gas Code, ANSI Z223.1,/NFPA  
54, and the National Electrical Code, ANSI/NFPA 70.  
In Canada installations must conform with the current  
CAN/CSA B149 and the Canadian Electrical Code  
Part 1 CSA C22.2 No.1.  
Floor  
Front  
Combustible*  
Alcove**  
12 in.  
Back  
Right  
12 in.  
Where required by the authority having jurisdiction, the  
installation must conform to American Society of  
Mechanical Engineers Safety Code for Controls and  
Safety Devices for Automatically Fired Heaters, CSD-  
1.  
Left  
12 in.  
Top (Indoor)  
Top (Outdoor)  
Flue Vent  
39 in.  
Unobstructed  
6 in.  
Mounting Base  
*Except for carpeted flooring, heaters are certified for installation on  
combustible floors, when equipped with listed floor shield base.  
**A front clearance of at least 24 in. is recommended for adequate  
service of burner-tray and controls.  
This heater should be mounted on a level, non-com-  
bustible surface. Heater must not be installed on  
carpeting. This heater can be installed on a com-  
bustible surface only when the appropriate listed floor  
shield base is provided. An optional listed floor shield  
base is available for factory installation with the heater  
on all indoor models.  
Table C: Minimum Clearances from Combustible  
Surfaces  
Combustion & Ventilation Air  
(Indoor models only)  
NOTE: The heater should be located in an area  
where water leakage will not result in damage to the  
area adjacent to the appliance or to the structure.  
When such locations cannot be avoided, it is  
recommended that a suitable drain pan, adequately  
drained, be installed under the appliance. The pan  
must not restrict air flow.  
WARNING: Air supply to the heater room must not  
be affected by mechanical exhaust vents located in  
other parts of the house, such as kitchen or  
bathroom fans, or attic blowers. Mechanical exhaust  
vents may create a negative pressure condition in  
the heater room that can become a hazard of  
asphyxiation, explosion or fire.  
In addition, the heater shall be installed such that the  
gas ignition system components are protected from  
water (dripping, spraying, rain, etc.) during appliance  
operation and service (circulator replacement, control  
replacement, etc.).  
CAUTION: Combustion air must not be  
contaminated by corrosive chemical fumes which  
can damage the heater. Measures must be taken to  
prevent the entry of corrosive chemical fumes to the  
combustion and ventilation air supply. Such  
chemicals include, but are not limited to, chlorinated  
and/or fluorinated hydrocarbons such as found in  
refrigerants, aerosol propellants, dry-cleaning fluids,  
degreasers, and paint removers. Other harmful  
elements may come from bleaches, air fresheners,  
or mastics. Vapors from these types of products can  
form corrosive acid compounds when burned in a  
gas flame. The resulting acid condensate can  
damage or substantially reduce the life of the heater.  
It may be necessary to provide outside air directly to  
the heater in order to avoid this problem.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. The heater must be provided with adequate sup-  
ply of air for proper combustion and ventilation in  
accordance with the latest edition of the National  
Fuel Gas Code, ANSI Z223.1, or applicable provi-  
sions of the local building codes.  
sure. If horizontal ducts are used, the area must  
be doubled and the duct area shall not be less  
than the area of the openings they connect, and in  
no case shall the smallest dimension be less than  
3 inches.  
2. When the heater is installed in a confined space  
where all air is supplied from inside the building,  
the heater room must be provided with TWO  
openings, each one having a minimum net free  
area, in square inches as shown in Table D.  
Outdoor Models  
Heaters must not be installed under an overhang of  
less than three (3) feet from the top on the heater.  
Three (3) sides must be open in the area under the  
overhang. Roof water drainage must be diverted away  
from the heater installed under overhangs with the use  
of gutters.  
Model No.  
0260/0261  
0330/0331  
0400/0401  
Sq. in. of Each Free Area  
264  
334  
399  
The point from where the flue products exit the heater  
must be a minimum of four (4) feet below, four (4) feet  
horizontally from or one (1) foot above any door, win-  
dow or gravity inlet to a building. The top surface of the  
heater shall be at least three (3) feet above any forced  
air inlet, or intake ducts located within ten (10) feet hor-  
izontally.  
Table D: Minimum Net Free Area  
One opening shall be within 12 inches of the top,  
and the other opening within 12 inches of the floor.  
If additional gas appliances are installed in the  
same space, the total input of all gas appliances  
installed in the same space, must be considered in  
the calculation. Refer to Sec. 5.3.5 of the latest  
edition of the National Fuel Gas Code for addition-  
al requirements.  
In areas where high winds are frequent, it may be nec-  
essary to locate the heater a minimum of three (3) feet  
from high vertical walls, or install a wind break so the  
heater is not in direct wind current.  
Venting Connections  
NOTE: If louvers, grills or screens are used on the  
openings, obtain the net free area from their supplier  
or manufacturer. If the design free area of a louver is  
not known nor available, it shall be assumed that  
wood louvers will have 20-25 percent free area and  
metal louvers will have 60-75 percent free area as  
shown in the National Fuel Gas Code.  
Outdoor Models  
Outdoor vent top is shipped separately and must be  
installed on site.  
Models 0260–0401  
1. Insert screw retainer clip over mounting flange, (4  
places).  
3. If the heater room is located against an outside  
wall and air openings can communicate directly  
with the outdoors, the TWO openings on the out  
side wall must each have a net free area, in  
square inches as shown in Table E.  
Model No.  
0260/0261  
0330/0331  
0400/0401  
Sq. in. of Each Free Area  
66  
84  
Fig. 3: Location of Mounting Clips  
100  
Table E: Minimum Net Free Area  
Location of the openings is the same as in the pre-  
vious case - that is, within 12 inches of the top,  
and within 12 inches of the bottom of the enclo-  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Attach mounting angles to heater jacket with 1/2"  
sheet metal screws, (4 places).  
TEMPERATURE  
SENSOR  
MOUNTING  
SCREWS (2)  
CONNECT ONE  
VENT SENSOR  
WIRE TO THE  
HARNESS  
ASSEMBLY  
HIGH LIMIT WIRE  
CONNECT ONE  
VENT SENSOR  
WIRE TO THE  
ROLL-OUT  
SENSOR WIRE  
WIRE FROM  
TRANSFORMER  
ROLL-OUT  
SENSOR  
Fig. 4: Location of Mounting Angles  
Fig. 6: Mounting Flue Sensor  
3. Lower outdoor top to heater and secure with 1"  
sheet metal screws.  
4. Remove door and locate wire from roll out sensor  
to Hi Limit with the male/female connector.  
WIRE FROM TRANSFORMER  
MALE/FEMALE  
WIRE TERMINAL  
WIRE FROM HIGH LIMIT  
ROLL OUT SENSOR  
Fig. 5: Long Side of Mounting Angle Located as Shown  
Fig. 7: Before Installation of Drafthood  
Indoor Models  
WIRE FROM TRANSFORMER  
CONNECT ONE VENT SENSOR WIRE  
TO HIGH LIMIT WIRE  
The drafthood is shipped separately and must be  
installed on the heater.  
CONNECT ONE VENT SENSOR WIRE  
TO ROLL OUT SENSOR WIRE  
Models 0260 & 0261  
ROLL OUT SENSOR  
1. Mount drafthood on top of heater and attach with  
the 4 sheet metal screws provided. Drafthood  
should be positioned with the vent sensor located  
on the front left side as shown.  
2. Remove plastic plug from left side of heater jacket  
and install plastic grommet provided.  
Fig. 8: After Installation of Drafthood  
3. Route flue sensor wire harness through the grom-  
met installed in Step 2.  
5. Disconnect male/female connector and attach to  
the 2 wires from drafthood vent sensor harness.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Models 0330, 0331, 0400 & 0401  
WARNING: Indoor heaters require a drafthood that  
must be connected to a vent pipe and properly  
vented to the outside. Failure to follow this procedure  
can cause fire or fatal carbon monoxide poisoning.  
Vent Terminal/Indoor Stack Installation  
1. Remove the louvered jacket top by removing four  
(4) #10 flat head screws.  
Vent piping the same size or larger than the draft hood  
outlet is recommended, however, when the total vent  
height is at least ten (10) feet (draft hood relief open-  
ing to vent terminal), the vent pipe size may be  
reduced as specified in the National Fuel Gas Code,  
ANSI Z 223.1. As much as possible avoid long hori-  
zontal runs of vent pipe and too many elbows.  
2. If originally installed, remove "Pagoda" top from  
the louvered jacket top.  
3. Place the inner stack adapter panel over the flue  
collector inside the heater. Make sure the flanged  
side of the flue opening is up.  
If installation requires horizontal runs, the vent pipe  
must have a minimum of 1/4 inch per foot rise and  
should be supported at not more than five foot inter-  
vals. Plumbers tape, crisscrossed, will serve to space  
both horizontal and vertical piping. Maximum vent con-  
nector horizontal length shall be 1-1/2 feet (18 inches)  
for each inch of connector diameter as shown in Table  
F.  
4. Turn the stack (draft hood) up side down and set it  
down bottom side up.  
5. Turn the jacket top panel (removed in Step 1) up  
side down and place it through the stack.  
6. Attach the three (3) mounting brackets to the stack  
using the screws provided and the holes that are  
pre-drilled in the stack. Make sure the brackets are  
positioned with the flange near the top side of the  
stack (see Fig. 9). Caution must be taken not to  
over tighten and strip the screw threads.  
Vent  
Max.  
Horizontal  
Length (ft)  
Model No.  
Connector  
Diameter (in.)  
0260/0261  
0330/0331  
0400/0401  
7
8
9
12  
13.5  
15  
7. Turn the assembled stack and jacket top, right  
side up. The jacket top will be trapped between the  
brackets and the top of the stack. Place the stack  
over the inner adapter panel flanged hole and  
lower the louvered jacket top panel back into its  
original position. Reinstall the four (4) green #10  
flat head screws removed in Step 1 above.  
Table F: Vent Piping Specifications  
Gas vents supported only by the flashing and extend-  
ing above the roof more than five feet should be  
securely guyed or braced to withstand snow and wind  
loads. We recommend use of insulated vent pipe  
spacer through the roofs and walls.  
DRAFTHOOD  
JACKET TOP PANEL  
SCREW HOLE  
LOCATION  
(part of the heater)  
For protection against rain or blockage by snow, the  
vent pipe must terminate with a listed vent cap which  
complies with the local codes or, in the absence of  
such codes, to the latest edition of the National Fuel  
Gas Code, ANSI Z223.1.  
#10 SHEET METAL SCREW (3)  
MOUNTING BRACKET (3)  
4-3/4"  
INNER STACK ADAPTER PANEL  
FLUE COLLECTOR  
(part of heater)  
The discharge opening must be a minimum of two feet  
vertically from the roof surface and at least two(2) feet  
higher than any part of the building within ten (10) feet.  
Vent stack shall be at least five (5) feet in vertical  
height above the drafthood outlet. The vent cap loca-  
tion shall have a minimum clearance of four (4) feet  
horizontally from, and in no case above or below,  
unless a 4-foot horizontal distance is maintained, from  
electric meters, gas meters regulators and relief equip-  
ment.  
COMBUSTIBLE FLOOR SHIELD  
(optional for indoor)  
2-1/2"  
Fig. 9: Vent Terminal/Indoor Stack Installation  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The weight of the vent stack or chimney must not rest  
on heater draft hood. Support must be provided in  
compliance with applicable codes. The heater top and  
draft hood must be readily removable for maintenance  
and inspection. Vent pipe should be adequately sup-  
ported to maintain proper clearances from combustible  
construction.  
Common Vents  
Manifolds that connect more than one heater to a com-  
mon chimney must be sized to handle the combined  
load. Consult available guides for proper sizing of the  
manifold and the chimney. At no time should the area  
be less than the area of the largest outlet.  
Type "B" double wall or equivalent vent pipe is recom-  
mended. However single wall metal vent pipe may be  
used as specified in the latest edition of the National  
Flue Gas Code ANSI Z223.1.  
10' OR LESS  
VENT CAP  
2' MIN  
2' MIN  
Drafthood  
Heater  
5' MIN  
VENT PIPE  
Fig. 11: Common Venting  
DRAFT HOOD  
At the time of removal of an existing heater, the follow-  
ing steps shall be followed with each appliance  
remaining connected to the common venting system  
placed in operation, while the other appliances remain-  
ing connected to the common venting system are not  
in operation.  
HEATER  
(a) Seal any unused openings in the common venting  
system.  
Fig. 10: Venting Minimum Clearances  
(b) Visually inspect the venting system for proper size  
and horizontal pitch and determine there is no  
blockage or restriction, leakage, corrosion and  
other deficiencies which could cause an unsafe  
condition.  
WARNING: These heaters must not be connected  
into any portion of mechanical draft systems  
operating under positive pressure. To do so may  
cause the flue products to be discharged into the  
living space causing serious health injury.  
(c) Insofar as is practical, close all building doors and  
windows and all doors between the space in which  
the appliances remaining connected to the com-  
mon venting system are located and other spaces  
of the building. Turn on clothes dryers and any  
appliance not connected to the common venting  
system. Turn on any exhaust fans, such as range  
hoods and bathroom exhausts, so they will oper-  
For connections to gas vents or chimneys, vent instal-  
lations shall be in accordance with Part 7, Venting of  
Equipment, of the National Fuel Gas Code, ANSI  
Z223.1, or applicable provisions of the local building  
codes.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ate at maximum speed. Do not operate a summer  
exhaust fan. Close fireplace dampers.  
(d) Place in operation the appliance being inspected.  
Follow the lighting instructions. Adjust tankstat so  
appliance will operate continuously.  
(e) Test for spillage at the draft hood relief opening  
after 5 minutes of main burner operation. Use the  
flame of a match or candle, or smoke from a ciga-  
rette, cigar or pipe to visually check spillage.  
(f) After it has been determined that each appliance  
remaining connected to the common venting sys-  
tem properly vents when tested as outlined above,  
return doors, windows, exhaust fans, fireplace  
dampers and any other gas burning appliance to  
their previous conditions of use.  
SUPPLIED BY  
INSTALLER  
Fig. 12: Sediment Trap  
(g) Any improper operation of the common venting  
system should be corrected so the installation  
conforms with the latest edition of the National  
Fuel Gas Code, ANSI Z223.1. When re-sizing any  
portion of the common venting system, the com-  
mon venting system should be re-sized to  
approach the minimum size as determined using  
the appropriate tables in Chapter 10 and in  
Appendix G of the National Fuel Gas Code, ANSI  
Z223.1 and CAN/CSA-B149.  
CAUTION: The heater and its manual shut off  
valve must be disconnected from the gas supply  
during any pressure testing of that system at test  
pressures in excess of 1/2 psi (3.45 kPa). Dissipate  
test pressure in the gas supply line before  
reconnecting the heater and its manual shut off valve  
to gas supply line. FAILURE TO FOLLOW THIS  
PROCEDURE MAY DAMAGE THE GAS VALVE.  
OVER PRESSURED GAS VALVES ARE NOT  
COVERED BY WARRANTY. The heater and its gas  
connections shall be leak tested before placing the  
appliance in operation. Use soapy water for leak test  
DO NOT use open flame.  
Gas Supply Connections  
The inlet gas connection to the heater gas valve is  
3/4" for models 260/261 and 330/331; and 1" for mod-  
els 400/401. Provide an adequate gas supply line  
according to Table G below.  
NOTE: Do not use teflon tape on gas line pipe  
thread. A flexible sealant suitable for use with Natural  
and Propane gases is recommended.  
Gas piping must have a sediment trap ahead of the  
heater gas controls, and a manual shut-off valve locat-  
ed outside the heater jacket. All gas piping should be  
tested after installation in accordance with local codes.  
3/4 in.  
Pro  
1 in.  
1-1/4 in.  
1-1/2 in.  
Nat Pro  
Model No.  
Nat  
20  
Nat  
60  
Pro  
140  
85  
Nat  
Pro  
560  
380  
260  
0260/0261  
0330/0331  
0400/0401  
40  
25  
15  
250  
150  
100  
15  
35  
360  
250  
25  
60  
Natural gas, 1000 BTUH/ft .60 specific gravity @ 0.5 in. WC pressure drop.  
Propane gas, 2500 BTUH/ft 1.53 specific gravity @ 0.6 in. WC pressure drop.  
Table G: Maximum Equivalent Pipe Length (ft)  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Gas Pressure Specifications  
The gas pressure regulator is preset and sealed at 4  
in. WC for natural gas, and 11 in. WC for propane gas.  
Between the gas valve and the burners is a 1/8 in. pipe  
plug. The pressure at this point, taken with a manome-  
ter, should be about 3.7 in. WC natural gas and 10.5  
in. WC propane gas. Lo NOx models should be 3.9 in.  
WC natural gas only. If an adjustment is needed,  
remove seal and turn adjustment screw clockwise to  
increase pressure or counter-clockwise to decrease  
pressure.  
Inches WC  
Type of  
Gas  
Regulator  
Setting  
Min.  
Max.*  
10.5  
Natural  
7.0  
4.0  
Propane  
12.0  
13.0  
11.0  
*Do not exceed maximum inlet gas pressure. The minimum value  
shown is for input adjustment.  
Table H: Gas Pressure Specifications  
Water Connections & System  
Piping  
Gas Pressure Regulator  
The pipe size and fittings between the heater and the  
tank should be at least 1-1/2" for all models. The tank  
should be located as close to the heater as possible,  
as shown in Fig. 13 below.  
The gas valve is provided with pressure taps to meas-  
ure gas pressure upstream of the gas valve and  
downstream which is the same as the manifold pres-  
sure.  
Fig. 13: Heater with Storage Tank  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If this water heater is installed in a closed water supply Valves and Automatic Gas Shut Off Devices for Hot  
system, such as one having a back-flow preventer in Water Supply Systems, ANSI Z21.22, must be  
the cold water supply line, means shall be provided to installed in the opening provided on top of the storage  
control thermal expansion. Contact the water supplier tank, at the time of installation. No valve is to be placed  
or local plumbing inspector on how to control this situ- between the relief valve and the storage tank.  
ation.  
The pressure rating of the relief valve must not exceed  
When this water heater system is supplying general the 160 maximum working pressure indicated on the  
purpose hot water requirements for use by individuals, water heater rating plate. The BTUH rating of the relief  
a thermostatically controlled mixing valve is recom- valve must not be less than the BTUH input of the  
mended to reduce the risk of scald injury. Contact a heater.  
licensed plumber or the local plumbing authority for  
further information.  
Connect the outlet of the relief valve to a suitable open  
drain. The discharge line must pitch downward from  
Thermometer(s) should be installed so that they indi- the valve to allow complete draining (by gravity) of the  
cate the water temperature at or near the outlet of the relief valve and discharge line. The discharge line  
storage tank.  
should be no smaller than the outlet of the valve. The  
end of the discharge line should not be threaded or  
concealed, and should be protected from freezing. No  
valve of any type, restriction or reducer coupling,  
should be installed in the discharge line. Local codes  
shall govern installation of relief valve.  
Relief Valve  
A new combination temperature and pressure (T & P)  
relief valve, complying with the Standard for Relief  
RATING PLATE  
ON/OFF  
PRV  
FLOW SWITCH  
SWITCH  
ELECTRICAL  
CONTROLS  
LOCATION  
INLET/OUTLET  
WATER  
CONNECTIONS  
HIGH LIMITS  
OPTIONAL  
PUMP  
COMBINATION  
GAS VALVE  
PILOT LOCATION  
Fig. 14: 0261 Low NOx WH1 with Pressure Relief Valve  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical Wiring  
NOTE: Minimum 18 AWG, 105°C, stranded wire  
must be used for all low voltage (less than 30 volts)  
external connections to the unit. Solid conductors  
should not be used because they can cause  
excessive tension on contact points. Install conduit  
as appropriate. All high voltage wires must be the  
same size (105°C, stranded wire) as the ones on the  
unit or larger.  
The electrical power supply requirement for these  
heaters is 120 volts, 60 Hz. Field wiring connections  
and electrical grounding must comply with the local  
codes, or in the absence of local codes, with the latest  
edition of the National Electrical Code, ANSI/NFPA 70.  
Provide a separate fused circuit from the main electri-  
cal panel to the heater, and a disconnecting means  
within sight of the heater.  
NOTE: If it is necessary to replace any of the  
original wiring, it must be replaced with 105°C wire or  
its equivalent, except 150° black wire which must be  
replaced with 150° wire or its equivalent.  
Remove the control box cover and make the power  
supply connections in the field wiring compartment.  
The pump is supplied and factory wired to operate with  
the heater. The current draw is approximately 2.0  
amps. Refer to the heater internal wiring diagrams  
shown on pages 17 to 21.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagrams  
(FIELD INSTALLED)  
Fig. 15: Standing Pilot Model 0260  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 16: Intermittent Ignition Device (IID) Model 0260  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 17: Intermittent Ignition Device (IID) Models 0330 & 0400  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 18: Intermittent Ignition Device (IID) Model 0261 Low NOx  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 19: Intermittent Ignition Device (IID) Models 0331 & 0401 Low NOx  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Checking the Circulator  
SERVICING  
PROCEDURES  
Before lighting the heater and after system is filled,  
make sure that circulator is operating properly. Manual  
gas valve should be off.  
Sequence of Operation  
NOTE: Circulator motor supplied with the heater  
does not require lubrication.  
Intermittent Ignition Device (IID)  
Heaters equipped with the IID system will automatical-  
ly light the pilot burner first and then the main burner,  
each time there is a call for heat from the tankstat.  
Whenever the tankstat calling for heat, the circulator  
supplied with the heater, will be energized and should  
be running.  
Lighting the Heater  
For your safety read carefully before proceeding to  
light the heater.  
CAUTION: Propane gas is heavier than air and  
sinks to the ground. Exercise extreme care in light-  
ing heater in confined areas.  
The ignition control module will also be energized to  
initiate the pilot ignition by opening the first main valve  
(pilot). At the same time, the electronic spark genera-  
tor in the module produces a high voltage spark pulse  
output that lights the pilot burner. If the pilot burner  
does not light, the module will not energize the second  
main valve and the burners will not light. Ignition spark  
continues only until the timed trial for ignition period  
ends.  
For Standing Pilot Models  
WARNING: If you do not follow these instructions  
exactly, a fire or explosion may result causing prop-  
erty damage, personal injury or loss of life.  
A. This heater has a pilot which must be lighted by  
hand. When lighting the pilot, follow these instruc-  
tions exactly.  
Then, the module goes into safety shutdown or lock-  
out. Lockout de-energizes the first main valve operator  
and closes the first main (pilot) valve in the gas con-  
trol, stopping pilot gas flow. The ignition control system  
must be reset by setting the tankstat below water tem-  
perature for one minute or by turning off power to the  
module for one minute.  
B. BEFORE LIGHTING smell all around the heater  
area for gas. Be sure to smell next to the floor  
because some gas is heavier than air and will set-  
tle on the floor.  
When the pilot flame is established, flame rectification  
circuit is completed between the sensor and burner  
ground. The flame sensing circuit in the module  
detects the flame current, shuts off the spark genera-  
tor and energizes the second main valve operator  
which opens the second main valve. This allows gas to  
flow to the burners where it is ignited by the pilot burn-  
er flame.  
WHAT TO DO IF YOU SMELL GAS  
Do not try to light any appliance.  
Do not touch any electric switch.  
Do not use any phone in your building.  
Immediately call your gas supplier from a neigh-  
bor's telephone. Follow the gas supplier's  
instructions.  
If you cannot reach your gas supplier, call the fire  
department.  
When the tankstat is satisfied, the valve operators are  
de-energized shutting off the pilot and main burners,  
and also the circulator.  
C. Use only your hand to push in, move or turn the  
gas control knob or lever. Never use tools. If the  
knob or lever will not push in, move or turn by  
hand, don't try to repair it, call a qualified service  
technician. Force or attempted repair may result in  
a fire or explosion.  
Start-up Procedures  
Filling the System  
D. Do not use this heater if any part has been under  
water. Immediately call a qualified service techni-  
cian to inspect the heater and to replace any part  
of the control system and any gas control which  
has been under water.  
Fill system with water. Purge all air from the system  
using purge valve sequence. After system is purged of  
air, lower system pressure. Flush system before put-  
ting into operation to ensure that foreign material does  
not damage pump seals.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9. Push in control knob all the way and hold in,  
immediately light the pilot with a match. Continue  
to hold control knob in for about one minute after  
the pilot is lighted, release knob and it will pop  
back up. Pilot should remain lighted. If it goes out,  
repeat steps 4 through 8.  
For Standing Pilot Model with  
Robertshaw Gas Valve, On/Off  
Operation  
1. STOP! Read the safety information above.  
2. Set the tankstat on the lowest setting.  
3. Turn OFF all electric power to the heater.  
4. Remove heater door panel.  
*
If knob does not pop up when released, stop  
and immediately call your service technician  
or gas supplier.  
If the pilot does not stay lit after several tries,  
turn the gas control knob to "OFF" and call  
your service technician or gas supplier.  
5. Push in gas control knob slightly and turn clock-  
*
wise  
to "OFF".  
10. Stand to the side of the heater and turn the gas  
control knob counter-clockwise  
11. Replace heater door.  
to "ON".  
GASCONTROL  
KNOBSHOWN  
IN"OFF"POSITION  
12. Turn "ON" all electrical power to the heater.  
13. Set the tankstat to the desired setting.  
GASINLET  
For Standing Pilot Model with  
Honeywell Gas Valve, On/Off  
Operation  
Fig. 20: Robertshaw Gas Valve  
1. STOP! Read the safety information.  
2. Set the tankstat to the lowest setting.  
3. Turn Off all electrical power to the heater.  
4. Remove heater door panel.  
NOTE: Knob cannot be turned from "PILOT" to  
"OFF" unless knob is pushed in slightly. Do not force.  
5. Turn gas control knob clockwise  
to "OFF".  
6. Wait five (5) minutes to clear out any gas. Then  
smell for gas, including near the floor. If your smell  
gas, STOP! Follow "B" in the safety information  
above on this label. If you don't smell gas, go to  
the next step.  
GASCONTROL  
KNOBSHOWN  
IN"OFF"  
7. Locate pilot mounted on the right side of the burn- POSITION  
er drawer, right of first burner.  
GASINLET  
8. Turn knob on gas control counter-clockwise  
to "Pilot".  
Fig. 22: Honeywell Gas Valve  
6. Wait five (5) minutes to clear out any gas. Then  
smell for gas, including near the floor. If you smell  
gas, STOP! Follow "B" in the safety information  
above on this label. If you don't smell gas, go to  
the next step.  
7. Locate pilot mounted on the right side of the burn-  
er drawer, right of first burner.  
8. Turn knob on gas control counter-clockwise  
to "PILOT".  
9. Push down and hold the red reset button in, imme-  
diately light the pilot with a match. Continue to hold  
down red reset button for about one minute after  
the pilot is lighted. Release red reset button and it  
will pop back up. Pilot should remain lighted. If it  
goes out, repeat steps 4 through 8.  
HONEYWELLPILOT  
ROBERTSHAW PILOT  
Fig. 21: Honeywell and Robertshaw Pilots  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
hand, don't try to repair it, call a qualified service  
technician. Force or attempted repair may result in  
a fire or explosion.  
* If red reset button does not pop up when  
released, STOP and immediately call your  
service technician or gas supplier.  
* If the pilot does not stay lit after several tries,  
turn the gas control knob to "OFF" and call your  
Service technician or gas supplier.  
D. Do not use this heater if any part has been under  
water. Immediately call a qualified service techni-  
cian to inspect the heater and to replace any part  
of the control system and any gas control which  
has been under water.  
10. Stand to the side of the heater and turn the gas  
control knob counterclockwise  
11. Replaceheaterdoor.  
to "ON".  
12. Turn "ON" all electrical power to the heater.  
13. Set the tankstat to the desired setting.  
For Intermittent Ignition (IID) with  
Honeywell or Robertshaw Gas  
Valve  
System Shut Down Procedure  
1. Set the tankstat to "OFF" or the lowest setting.  
2. Turn off all electric switches to the heater.  
3. Turn off all gas valves supplying gas to the heater.  
Refer to operating instruction label on the heater.  
4. Shut off the water supply to the heater piping sys-  
tem loop.  
1. STOP! Read the safety information above on this  
label.  
2. Set the tankstat on the lowest setting.  
3. Turn off all electric power to the appliance.  
4. This appliance is equipped with an ignition device  
which automatically lights the pilot. Do not try to  
light the pilot by hand.  
5. Open drain valve on the tank to remove water from  
the heater and the piping circuits.  
5. Remove heater door panel.  
6. For Robertshaw Gas Valve: Turn gas control knob  
For Automatic Ignition Models  
clockwise  
to "OFF". For Honeywell Gas  
to  
Valve: Turn gas control knob clockwise  
Please read carefully and understand the following  
safety information before operating the heater.  
"OFF". Make sure knob rest against stop. For  
Honeywell Gas Valve: Push in gas control knob  
slightly and turn clockwise to "OFF". Knob cannot  
be turned to "OFF" unless knob is pushed in slight-  
ly. Do not force.  
WARNING: If you do not follow these instructions  
exactly, a fire or explosion may result causing prop-  
erty damage, personal injury or loss of life.  
7. Wait five (5) minutes to clear out any gas. Then  
smell for gas, including near the floor. If you smell  
gas, STOP! Follow "b" in the safety information  
previously stated. If you do not smell gas, go to the  
next step.  
A. This heater is equipped with an ignition device  
which automatically lights the pilot. Do not try to  
light the pilot by hand.  
8. For Robertshaw Gas Valve: Turn gas control  
B. BEFORE OPERATING smell all around the heater  
area for gas. Be sure to smell next to the floor  
because some gases are heavier than air and will  
settle on the floor.  
knob counter-clockwise  
to "ON".  
WHAT TO DO IF YOU SMELL GAS:  
GAS CONTROL  
KNOB SHOWN  
IN "ON" POSITION  
Do not try to light any appliance.  
Do not touch any electric switch.  
Do not use any phone in your building.  
Immediately call your gas supplier from a neigh-  
bor's phone. Follow the gas supplier's instructions.  
If you cannot reach your gas supplier, call the fire  
department.  
GASINLET  
C. Use only your hand to push in, move or turn the  
gas control knob or lever. Never use tools. If the  
knob or lever will not push in, move or turn by  
Fig. 23: Robertshaw Gas Valve  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
For Honeywell Gas Valve: Turn gas control knob  
counter-clockwise from “OFF” until it stops.  
Push in gas control knob and continue rotating  
counter-clockwise to “ON” position. Make  
Testing the Ignition Safety Shut-off  
The ignition system safety shutoff must be tested by  
conducting the following tests:  
sure knob rest against stop.  
For Standing Pilot Systems  
GAS CONTROL  
KNOB SHOWN  
IN “ON” POSITION  
1. With the main burners on, remove the pilot adjust-  
ment cover screw.  
2. Insert a small slot screw driver and turn the adjust-  
GAS INLET  
ment screw clockwise  
until pilot flame goes  
out. Count and note number of turns made.  
3. Gas valve will shut off main burners after about  
three (3) minutes. End of test. If the gas valve will  
not shut off, follow the instructions "To Turn Off  
Gas To Heater" and call service technician or your  
gas supplier.  
Fig. 24: Honeywell Gas Valve  
4. Return pilot adjustment screw counterclockwise  
For Honeywell Gas Valve: Turn gas control knob  
same number of turns as in step (b).  
5. Replace pilot adjustment cover screw, then follow  
the lighting instructions to get heater ready for  
operation.  
counter-clockwise  
to “ON”.  
GAS CONTROL  
KNOB SHOWN  
IN “ON” POSITION  
For Automatic Ignition Systems  
GAS INLET  
1. Turn on power to the ignition systems and turn gas  
supply off at the gas valve.  
2. Check ignition module as follows:  
a. Set the tankstat to high setting.  
b. Watch for continuous spark at the pilot burner.  
c. Time the spark operation. Time must be with-  
in the lockout timing period (15 or 90  
seconds).  
Fig. 25: Honeywell Gas Valve  
9. Replace door panel.  
10. Turn on all electric power to the appliance.  
11. Set tankstat to desired setting.  
12. If the appliance will not operate, follow the instruc-  
tions “To Turn Off Gas To Appliance” and call your  
service technician or gas supplier.  
d. Turn tankstat down to end call for heat and  
wait 60 seconds on lockout models before  
beginning step 3.  
3. Turn on gas supply.  
4. Set tankstat to high setting.  
5. Systems should start as follows:  
a. Spark will turn on and pilot gas valve will open  
at once. Pilot burner should ignite after gas  
reaches the pilot burner.  
To Turn Off Gas To Appliance  
1. Set the thermostat to the lowest setting.  
2. Turn off all the electric power to the appliance if  
service is to be performed.  
3. Remove door panel.  
4. For Robertshaw IID Gas Valve: Turn gas control  
b. Spark ignition should cut off when pilot flame  
is established.  
c. Main gas valve should open and main burner  
should ignite after gas reaches the burner  
port.  
knob clockwise  
to “OFF”.  
For Honeywell Gas Valve: Turn gas control knob  
clockwise  
to “OFF”. Make sure knob rest  
against stop.  
For Honeywell 24V Standing Pilot Gas Valve:  
Push in gas control knob slightly and turn clock-  
wise  
to “OFF”.  
5. Replace heater door panel.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inspection Procedures  
Controls  
Burners  
Check all controls to see that they are operational. To  
check electronic safety (IID Models) , turn off main  
burner. Observe pilot burner when shutting off pilot  
gas. Ignition spark should go on. Main gas valve will  
also drop out.  
Clean main burners and air louvers of dust, lint and  
debris. Keep heater area clear and free from com-  
bustibles and flammable liquids. Do not obstruct the  
flow of combustion and ventilating air. Make visual  
check of burner and pilot flame. Yellow flame indicates  
clogging of air openings. Lifting or blowing flame indi-  
cates excess high gas pressure. Low flame indicates  
low gas pressure.  
High Limit Switch - to check high limit switch, turn dial  
setting down to a point slightly below the temperature  
of the water leaving the heater. The reset button  
should snap out and the burner should shut off. Reset  
dial to 30°F to 40°F above desired operating tempera-  
ture, and push reset button. Burner should light.  
Low NOx Heaters—Models 261–401  
The Low NOx Heater is offered as a model W1-ON-  
OFF firing.  
The heaters are certified and tested under the ANSI  
Z21.10.3 Standards for hot water heaters.  
The heater should be installed to meet all local codes,  
the National Fuel Gas Code Z223.1 and with the  
National Electrical Code, ANSI/NFPA 70.  
Fig. 26: Typical Main Burner Flame  
Fig. 27: Pilot Burner Flame (IID units)  
Fig. 28: Pilot Burner Flame (STG Pilot Units)  
DETAIL A  
SEE DETAIL VIEW A  
Fig. 29: Burner Detail  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
High/Low Gas Pressure Switch  
On call for heat, the ignition system, consisting of an Pressure switch senses high/low pressure and auto-  
electronic spark module, gas pilot system is energized. matically shuts down burner if abnormal pressure  
Providing pilot is proven blower will start running, the exists.  
main gas valve will open and the heater will operate.  
When the operating control is satisfied the heater will  
shut down.  
Start-up Procedures (S8610B)  
1. Turn on power to the heater with gas supply off.  
2. Check ignition module as follows:  
a. Set the thermostat or controller to call for heat.  
b. Watch for continuous spark at the pilot burner.  
c. Check the ignition spark operation. Time must  
be within the lockout timing period (15 or 90  
seconds).  
d. Turn control down to end call for heat and wait  
60 seconds on lockout models before begin-  
ning step 3.  
Fig. 30: Gas Pressure Switch  
3. Turn on gas supply.  
4. Set controller to call for heat.  
5. System should start as follows:  
a. Spark will turn on and pilot gas valve will open  
and the blower will begin running.  
b. Heater will operate until call for heat is satis-  
fied.  
Burner Adjustment  
This burner assembly does not require any adjust-  
ments.  
Visual Inspection  
Flame can be observed through the slot opening  
above the plenum. Flame color is blue and evenly  
spread on the top surface of the burner. At least every  
three months a visual inspection should be made of  
the burners. In case flame lifting is observed on the  
burner, check gas pressure on manifold and static  
pressure in plenum. Gas pressure in manifold should  
be 3.9 in. WC and static pressure in plenum should be  
greater than 0.5 in. WC.  
Fig. 31: Low NOx Burner Tray Assembly  
Burner Drawer Removal  
1. Shut off main electrical power switch to heater.  
2. Shut off gas upstream of heater.  
3. Remove front door.  
Electrical  
4. Disconnect gas line from gas valve.  
5. Remove (2) screws that mount burner tray to unit,  
and (4) screws that secure gas valve to jacket.  
6. Disconnect wires that terminate at gas valve.  
7. Unscrew (4) screws that secure the control box.  
8. Disconnect pilot wire from the ignition module.  
9. Disconnect wire harness from the combustion  
blower.  
Be sure that electrical service to the heater has over-  
load fuse or circuit breaker protection, wire size and  
connections that comply with all applicable codes.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10. Carefully slide out the burner tray assembly.  
11. Reverse above procedure to reinstall.  
5. Pull the pilot bracket downward and outward.  
6. Reverse above procedure to re-install.  
Gas Valve Removal  
Combustion Fan Removal  
1. Shut off main electrical power switch to heater.  
2. Shut off gas supply to the heater.  
3. Remove front door.  
1. Remove burner drawer. See burner drawer  
removal procedure.  
2. Remove (4) screws the mount the combustion  
blower to the manifold assembly.  
4. Disconnect gas line from gas valve.  
5. Disconnect wires, pilot tubing and bleed line, if 3. Reverse above procedure to re-install.  
required.  
6. Remove (2) screws that secure gas valve to jack-  
et.  
Normal Inspection Procedures  
7. Turn vertical gas pipe from manifold slightly and  
unscrew gas valve.  
First and third month after initial start up and then on  
an annual basis. If problems are found, refer to  
Trouble Shooting Guide for additional directions.  
8. Reverse above procedure to re-install.  
Main Burner And Orifice Removal  
1. Remove top of heater and inspect heat exchanger  
for soot and examine venting system.  
1. Remove burner drawer. See burner drawer 2. Remove rear header and inspect for scale  
removal procedure.  
2. Remove (8) screws from the hold down brackets.  
deposits.  
*3. Inspect pilot and main burner flame and firing rate.  
3. Remove (8) screws from the left and right sides of *4. Inspect and operate all controls and gas valve.  
the Manifold assembly. Detach the manifold *5. Visually inspect system for water leaks.  
assembly from the burner tray assembly.  
4. Use a long 3/8” socket wrench to remove orifices  
from the atmospheric gas manifold, 9/16” for Low  
NOx.  
5. Remove burners by raising the bracket on the  
back end of the burners up and out of their slots.  
6. Reverse above procedure to re-install.  
*6. a. Oil pump motor and bearing assembly, if oil  
cups are provided.  
b. Disconnect pump from header and check con-  
dition of pump impeller. Check condition of  
bearing by attempting to move impeller from  
side to side. Replace any parts showing wear.  
c. Check pump coupler for wear and vibration.  
7. Check flow switch paddle (if provided).  
8. Clean room air intake openings to assure ade-  
quate flow of combustion and ventilation air.  
CAUTION: Combustion air must not be contami-  
nated by corrosive chemical fumes which can  
damage the heater and void the warranty.  
9. Keep heater area clear and free from combustible  
materials, gasoline, and other flammable vapors  
and liquids.  
*Should be checked monthly. (Takes approximately  
15 minutes).  
Fig. 32: IID Pilot  
Repair Section  
Pilot Removal  
Tube Cleaning Procedure (Typical)  
1. Disconnect pilot tubing from gas valve.  
2. Remove (4) screws from control box. Open the  
control box.  
3. Remove the pilot wire from the ignition wire.  
4. Remove (2) screws that mount the pilot bracket to  
the air manifold assembly.  
Establish a regular inspection schedule, the frequency  
depending on the local water condition and severity of  
service. Do not let the tubes clog up solidly. Clean out  
deposits over 1/16" in thickness.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The heater may be cleaned from the side opposite the  
water connections, without breaking pipe connections.  
should be at the 1/4 mark and the balance of the  
tank filled with air.  
It is preferable, however, to remove both headers for 9. Install flue collector, jacket top and inspection pan-  
better visibility through the tubes and to be sure the  
residue does not get into the system. Generally, you  
do not remove the top pan or the heat exchanger .  
els. Install top holding screws. Install draft diverter  
and vent piping if so equipped.  
10. If gas piping was disconnected, reconnect gas pip-  
ing system and check for leakage using a soap  
solution.  
After reaming with the auger, mount the wire brush  
and clean out the debris remaining in the tubes. 11. Check for correct water pressure and water level  
Another method is to remove the heat exchanger,  
ream tubes and immerse heat exchanger in non-inhib-  
ited de-scale solvent.  
in the system. Make sure that system pump oper-  
ates immediately on the call for heat. The system  
is ready for operation.  
12. Within two (2) days of start-up, recheck all air  
vents and expansion tank levels.  
Heat Exchanger Removal  
Combustion Chamber Removal  
1. Shut water, gas and electricity off, close valves  
and relieve pressure, remove relief valve. Remove  
side inspection panels.  
To remove combustion chamber you must first have  
removed the heat exchanger. Unbolt metal combus-  
2. Remove top holding screws.  
3. Remove draft diverter, lift and remove top and flue tion chamber retainer from top and remove  
collector on stack type models. Remove inspec- combustion chamber panels individually.  
tion panels.  
4. Loosen bolts and disconnect flange nuts on inlet-  
outlet header, loosen union(s) at gas pipe, and  
slide heater away from piping until studs clear the  
heater.  
5. Remove heat exchanger corner brackets.  
6. Remove combustion chamber clips at the four cor-  
ners of the heat exchanger.  
7. Lift heat exchanger straight up using caution not to  
damage refractory.  
Heat Exchanger Re-assembly  
Fig. 33: Refractory Panels—Top View  
1. Heat exchanger water header O-rings should be  
replaced with new ones.  
2. Install inlet-outlet and return water headers and  
install header retainer nuts and torque nuts even-  
ly.  
3. Install the four (4) corner clips between tube  
sheets and refractory. Replace "V" baffles.  
4. Install thermostat sensing bulbs in header wells  
and replace bulb retaining clips.  
5. Install inlet and return pipes in water headers  
using pipe thread sealant.  
6. Install water pressure relief valve, flow switch, and  
low water cutoff devices if so equipped.  
7. Open water supply and return shut-off valves. Fill  
heater and water piping system with water. Check  
heater and piping system for leaks at full line pres-  
sure. Run system circulating pump for a minimum  
of 1/2 hour with heater shut-off.  
8. Shut down entire system and vent all radiation  
units and high points in system piping. Check all  
strainers for debris. Expansion tank water level  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING  
Theseinstructionsareprimarilyintendedfortheuseofqualifiedpersonnelspecificallytrainedandexperiencedinthe  
installationofthistypeofheatingequipmentandrelatedsystemcomponents. Installationandservicepersonnelmay  
be required by some states to be licensed. Persons not qualified shall not attempt to install this equipment nor  
attempt repairs according to these instructions.  
SOLUTION(S)  
PROBLEM(S)  
CAUSE(S)  
1)Check circuit breakers, disconnect  
switch. Make sure power is on.  
1)When tankstat is turned on, heater  
does not operate.  
1)No power to the heater.  
2)Check continuity on thermostat and  
wiring circuit. Replace thermostat, or  
repair wiring connections.  
2)Defective tankstat or disconnected  
wire in thermostat circuit.  
3) Check secondary voltage. If no 24V,  
replacetransformer.  
3)Defective transformer.  
1)Light pilot burner. (Follow lighting  
instructions on rating plate).  
2)When tankstat is calling for heat,  
pump is on, but burners will not turn  
on.  
1)For Standing pilot models pilot burner  
not lighted.  
2)Check thermocouple MV generation.  
If less than 25MV (open circuit), re-  
place thermocouple. If between 25-  
35 MV, replace gas valve.  
2)If pilot burner will not stay lighted,  
thermocouple or gas valve may be  
defective.  
3)Turn knob to "ON" position.  
4) Check for blockage of venting sys  
temordisconnectedventpiping. After  
problem is corrected push button to  
resetventswitch.  
3)Gas knob in "Pilot" position.  
4)Vent switch is open.  
5)Check for blockage of flue or sooted  
heat exchanger. After problem is  
corrected push button to reset  
roll-out switch.  
5)Roll-out switch is open.  
6)Check water flow and adjust to  
obtain 8° to 10°F temperature rise.  
7)On Honeywell module, check voltage  
across terminals MV and MV/PV. If  
no 24V is present, replace module. If  
24V is present, replace gas valve.  
6)Manual Reset High limit is open.  
7) Defective ignition module or  
defective gas valve.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3)Pilot Outage.  
1) Adjust inlet gas pressure as  
shown on rating plate.  
1) Too low or too high gas  
pressures.  
(Standing pilot models)  
2) Restricted pilot.  
3) Weak thermocouple.  
2) Clean pilot orifice.  
3) Replace thermocouple.  
4)Yellow lazy flame.  
5)Sooting  
1) Too low gas pressure.  
2) Restricted burner intake ports.  
3) Restricted gas line.  
1) Adjust manifold pressure as  
shown on rating plate.  
2) Clean burners free of debris or  
insects.  
3) Clean gas line or increase gas line  
piping.  
1) Insufficient combustion air.  
1) Refer to installation instructions  
regarding combustion air  
requirements.  
2) Improper venting.  
2) Refer to installations instructions.  
3) See yellow flame section above.  
3) Severe yellow burner flames.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING: HIGH VOLTAGE: For qualified  
technicians ONLY  
TROUBLESHOOTING  
Electrical  
(Electronic Ignition IID)  
NOTE: Some heaters may be equipped with an  
ignition module that shuts off pilot gas if the pilot fails  
to light. To reset, interrupt power to heater.  
Intermittent Pilot System—  
Honeywell S8600  
START  
TURN GAS SUPPLY OFF.  
TURNTHERMOSTAT  
(CONTROLLER) TO CALL  
FORHEAT  
NOTE: Before troubleshooting, familiarize yourself with the start-up and checkout  
procedure.  
Check line voltage power, low voltage transformer, limit controller, thermostat  
(controller) and wiring.  
NO  
NO  
POWER TO MODULE  
(24 V NOMINAL)  
YES  
Pull ignition lead and check spark at module.  
SPARKACROSS  
IGNITER/SENSORGAP  
YES  
Spark Okay?  
YES  
• Check ignition cable, ground wiring, ceramic insulator and gap, and correct.  
• Check boot of the ignition cable for signs of melting or buckling. Take protective  
action to shield cable and boot from excessive temperatures.  
TURN GAS SUPPLY ON  
PILOT BURNER LIGHTS?  
YES  
• Check that all manual gas valves are open, supply tubing and pressures are  
NO  
NO  
good,  
and pilot burner orifice is not blocked.  
• Check electrical connections between module and pilot operator on gas control.  
• Check for 24 Vac across PV-MV/PV terminals on module. If voltage is okay,  
replace gas control; if not, replace module.  
NOTE: If S8600H goes into lockout, reset system. Lockout is used on L.P.G.  
models.  
SPARK STOPS WHEN  
PILOT IS LIT?  
YES  
• Check continuity of ignition cable and ground wire.  
• Clean flame rod.  
• Check electrical connections between flame rod and module.  
• Check for cracked ceramic flame rod insulator.  
• Check that pilot flame covers flame rod and is steady and blue.  
• Adjust pilot flame.  
If problem persists, replace module.  
• Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace module.  
• Check electrical connections between module and gas control. If okay, replace  
gas valve or gas control operator, i.e. pilot gas valve, flow switch etc.  
NO  
NO  
MAIN BURNER LIGHTS?  
YES  
NOTE: IF S8600H goes into lockout, reset system.  
SYSTEM RUNS UNTIL  
CALL FOR HEAT ENDS?  
YES  
• Check continuity of ignition cable and ground wire.  
NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though  
operation is normal at the time of checkout.  
• Check that pilot flame covers flame rod and is steady and blue.  
If checks are okay, replace module.  
CALL FOR HEAT ENDS  
SYSTEMSHUTSOFF?  
YES  
• Check for proper thermostat (controller) operation.  
• Remove MV lead at module; if valve closes, recheck temperature controller and  
wiring; if not, replace gas valve.  
NO  
TROUBLESHOOTING  
Repeat procedure until troublefree operation is obtained.  
ENDS  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical (Standing Pilot)  
WARNING: HIGH VOLTAGE: For qualified  
technicians ONLY  
STARTHEATER  
IFPILOTBURNERLIGHTS  
BUTMAINBURNERSDONOT  
IFPILOTBURNER  
DOESNOTLIGHT  
CHECK FOR 24 V  
AT GAS VALVE  
CHECKTHERMOCOUPLE  
IF NOT 24 V:  
IF 24 V:  
IF O.K.  
IFDEFECTIVE  
CHECKTRANSFORMEROUPUT  
FOR 24 V  
REPLACE  
GAS VALVE  
REPLACE  
REPLACE  
GAS VALVE  
THERMOCOUPLE  
IFNO  
24V:  
IF 24 V:  
REPLACE  
PROBLEMIN  
TRANSFORMER  
LIMIT  
CIRCUITS  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Lift burners from slotted spacer and slide from ori-  
fices. Clean with a wire brush.  
3. Orifices usually do not need to be replaced. To  
clean, run either copper wire or wood through ori-  
fice. Do not enlarge hole. To remove orifice, use a  
socket wrench and remove the manifold. DO NOT  
over tighten when reinstalling.  
ADJUSTMENTS &  
REPLACEMENT OF  
COMPONENTS  
CAUTION: Label all wires prior to disconnection  
when servicing controls. Wiring errors can cause  
improper and dangerous operation. Verify proper  
operation after servicing.  
High Limit or Tankstat Removal  
1. Turn off electrical power.  
2. Remove front inspection panel.  
3. Remove wires to high limit and loosen screws  
holding high limit to cabinet.  
DANGER: SHOCK HAZARD: Make sure electri-  
cal power to the heater is disconnected to avoid  
potential serious injury or damage to components.  
4. Remove wedge clip holding sensing bulb in con-  
trol well.  
5. Remove high limit and install a new one.  
6. Check control operation before leaving job.  
Gas Valve Removal  
1. Shut off gas supply to the heater. Remove gas pip-  
ing to gas valve inlet.  
Flame Roll-Out Switch Replacement  
2. Disconnect wires, pilot tubing and bleed line, if  
required.  
1. Shut off electrical power to the heater.  
2. Remove wiring connections to switch.  
3. Remove screws (2) holding the switch.  
4. Reverse above procedure to re-install.  
3. Turn vertical gas pipe from manifold slightly and  
unscrew gas valve.  
4. Reverse above procedure to re-install.  
Vent Thermal Switch Replacement  
Pilot Removal and Cleaning  
1. Shut off electrical power to the heater.  
2. Remove wiring connections to switch.  
3. Remove the screws (2).  
1. Disconnect pilot tubing at pilot and sensor/igniter  
wire. Remove screws holding pilot bracket to burn-  
er drawer.  
2. Remove pilot and bracket, clean pilot of debris,  
small bugs, etc., with wire or small brush.  
3. Replace pilot, pilot tubing, sensor ignition wires  
and check for leaks.  
4. Reverse above procedure to re-install.  
Ignition Module Replacement  
1. Shut off electrical power to the heater.  
2. Remove control cover screws and open control  
compartment.  
Burner Drawer Removal  
3. Disconnect wiring connections to module.  
4. Remove screws (2) holding module.  
5. Reverse above procedure to re-install.  
1. Shut off power and gas supply to the heater.  
Disconnect union(s) and pilot tubing, then loosen  
and remove burner hold down screws.  
2. Disconnect wires at gas valve and slide burner  
drawer out.  
Transformer Replacement  
1. Shut off electrical power to the heater.  
2. Remove control cover screws and open control  
compartment.  
Main Burner and Orifice Removal  
1. Remove screws and burner hold down bracket.  
3. Disconnect wiring connections from transformer  
leads.  
NOTE: If the heat exchanger is sooted badly, the  
burner hold down bracket and spacer can become  
distorted from direct flame impingement and this  
usually necessitates replacement of these parts.  
4. Remove screws (2) holding transformer.  
5. Reverse above procedure to re-install.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. Reverse drill motor and withdraw tube roller, if  
necessary wrench out by hand.  
Circulator Replacement  
9. DO NOT apply excessive torque during rolling  
operation and avoid thinning any wall of the tube  
beyond 0.015".  
10. Use same procedure on opposite end.  
11. Apply line pressure test. Re-roll if necessary.  
12. Reinstall as outlined under HEAT EXCHANGER  
REASSEMBLY.  
1. Shut off electrical power to the heater.  
2. Shut off water supply and open drain valve to  
remove water in the piping at the pump level.  
CAUTION: To avoid damage to electrical compo-  
nents keep water from getting into the control  
compartments and gas valve.  
Procedure for Cleaning Flue Gas  
Passage Ways  
3. Disconnect wiring and conduit connections to the  
pump.  
4. Remove the nuts and bolts at the inlet and outlet  
flanges. Remove old gaskets.  
Soot will clog areas behind fins and eventually cause  
tube failure. Any sign of soot at base of burners or  
around outer jacket indicates a need for cleaning.  
5. Remove the pump.  
6. Reverse the above procedure to re-install. Use  
new gaskets and make sure they are seated prop-  
erly when tightening the nuts and bolts.  
1. Lift off draft hood and flue collector by removing  
bolts and screws.  
2. Remove "V" baffles from heat exchanger.  
3. Remove burner tray, see Burner Drawer Removal.  
4. Take garden hose and wash heat exchanger, mak-  
ing sure soot is removed from between fins. (Avoid  
excessive water against refractory).  
Control Well Replacement  
Remove top, sensing bulb and clip. Collapse well tube  
at the open end with a chisel, push through into head-  
er and remove the well through header. Insert a new 5. Reassemble; when heater is fired, some steam  
well and roll into place. If a roller is not available, sol-  
der the well in place with silver solder.  
will form from wet refractory, which is normal.  
NOTE: In extreme cases it may be necessary to  
remove the heat exchanger completely for cleaning.  
The simplest method is steam cleaning at a local car  
wash.  
Tube Replacement Procedure  
1. Remove heat exchanger from heater following  
instructions outlined under HEAT EXCHANGER  
REMOVAL.  
2. Remove inlet/outlet and return headers. Remove  
"V" Baffle from damaged tube.  
CAUTION: Soot is combustible. Exercise extreme  
care. Do not wire brush.  
3. Remove damaged tube by cutting with a hack saw  
or shearing with a chisel adjacent to each tube  
sheet.  
Replacement Parts  
4. Collapse stub ends in tube sheets using a chisel or  
screwdriver. DO NOT cut into tube sheet or mar Any part returned for replacement under standard  
surface in tube hole in any way.  
manufacturer warranties must be properly tagged with  
5. Insert replacement tube by inserting the end with a return parts tag, completely filled in with the heater  
the most fins removed in the opening of one tube serial number, model number etc., and shipped to the  
sheet. Slide tube until the opposite end clears the manufacturer freight prepaid.  
other tube sheet and fits the tube into the hole.  
6. Insert the tube roller into tube opening up to stop, If the manufacturer determines the part is defective  
making certain that 1/8" of tube projects beyond and within warranty, the part will be returned in kind or  
the tube sheet.  
equal substitution, freight collect. Credit will not be  
7. Attach drill to tube roller, holding it straight and issued.  
level.  
RAYPAK, INC.  
2151 Eastman Avenue  
Oxnard, CA 93030  
NOTE: Use a 3/8 in. heavy duty, reversible, electric  
drill or larger. Proceed to expand tube until tool starts  
to grab. Approximately 1/2 to 1 in. of the tool shank  
will be visible.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIMITEDPARTSWARRANTYECONOPAKWATERHEATERS  
MODELS WH - 0260 TO 0401  
SCOPE:  
Raypak, Inc. ("Raypak") warrants to the original owner that all parts of this water heater which are actually manufactured by Raypak  
will be free from failure under normal use and service for the specified warranty periods and subject to the conditions set forth in this  
Warranty. Labor charges and other costs for parts removal or reinstallation, shipping and transportation are not covered by this Warranty  
but are the owner's responsibility.  
HEATEXCHANGERWARRANTY:  
Five (5) Years from date of water heater installation. This includes only the copper, bronze and cast iron waterways.  
Twenty (20) Years from date of water heater installation against "Thermal Shock" (excluded, however, if caused by operation  
at large changes exceeding 150°F between the water temperature at intake and water heating temperature, or operating at water  
heater temperatures exceeding 190°F).  
ANYOTHERPARTMANUFACTUREDBYRAYPAK:  
One (2) year warranty from date of installation, or eighteen (18) months from date of factory shipment based on Raypak's records,  
whichever comes first.  
SATISFACTORYPROOFOFINSTALLATIONDATE,SUCHASINSTALLERINVOICE,ISREQUIRED. THISWARRANTYWILLBEVOID  
IFTHEWATERHEATERRATINGPLATEISALTEREDORREMOVED.  
ADDITIONALWARRANTYEXCLUSIONS:  
This warranty does not cover failures or malfunctions resulting from:  
1. Failure to properly install, operate or maintain the water heater in accordance with our printed instructions provided;  
2. Abuse, alteration, accident, fire, flood and the like;  
3. Sediment or lime buildup, freezing, or other conditions causing inadequate water circulation;  
4. High velocity flow exceeding water heater design rates;  
5. Failure of connected systems devices, such as pump or controller;  
6. Use of non-factory authorized accessories or other components in conjunction with the water heater system;  
7. Failing to eliminate air from, or replenish water in, the connected water system;  
8. Chemical contamination of combustion air or use of chemical additives to water.  
PARTSREPLACEMENT:  
Under this Warranty, Raypak will furnish a replacement for any failed part. The failed part must first be returned to Raypak if  
requested, with transportation charges prepaid, and all applicable warranty conditions found satisfied. The replacement part will be  
warranted for only the unexpired portion of the original warranty. Raypak makes no warranty whatsoever on parts not manufactured  
by it, but Raypak will apply any such warranty as may be provided to it by the parts manufacturer.  
TO MAKE WARRANTY CLAIM:  
Promptly notify the original installer, supplying the model and serial numbers of the unit, date of installation and description of the  
problem. The installer must then notify his Raypak distributor for instructions regarding the claim. If either is not available, contact Service  
Manager, Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 or call (805) 278-5300. In all cases proper authorization must first be  
received form Raypak before replacement of any part.  
EXCLUSIVE WARRANTY - LIMITATION OF LIABILITY:  
This is the only warranty given by Raypak, No one is authorized to make any other warranties on Raypak's behalf. THIS WARRANTY  
IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF  
MERCHANTABILITYANDFITNESSFORAPARTICULARPURPOSE. RAYPAK'SSOLELIABILITYANDTHESOLEREMEDYAGAINST  
RAYPAKWITHRESPECTTODEFECTIVEPARTSSHALLBEASPROVIDEDINTHISWARRANTY. ITISAGREEDTHATRAYPAKSHALL  
HAVENOLIABILITY,WHETHERUNDERTHISWARRANTY,ORINCONTRACT,TORT,NEGLIGENCEOROTHERWISE,FORANYSPECIAL,  
CONSEQUENTIAL,ORINCIDENTALDAMAGE,INCLUDINGDAMAGEFORMWATERLEAKAGE. Somestatesdonotallowlimitationsonhow  
long an implied warranty lasts, or for the exclusion of incidental or consequential damages. So the above limitation or exclusion may not  
apply to you.  
This Limited Warranty gives you specific legal rights. You may also have other rights which may vary from state to state. Wesuggest  
that you complete the information below and retain this certificate in the event warranty service is needed. Reasonable proof of the  
effective date of the warranty (date of installation) must be presented, otherwise, the effective date will be based on the rate of  
manufacture plus thirty (30) days.  
_____________________________________________________  
Name of Owner  
____________________________________________________  
Name of Dealer  
_____________________________________________________  
Address  
____________________________________________________  
Address  
_____________________________________________________  
____________________________________________________  
_____________________________________________________  
____________________________________________________  
ModelNo.  
Serial No.  
Date of Installation: _____________________________________  
Date of Initial Operation: ________________________________  
CORPORATEHEADQUARTERS:  
RAYPAK, INC., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 FAX (805) 278-5489  
Litho in U.S.A.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468  
Litho in U.S.A.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

RCA Microwave Oven RMW982 User Guide
RCA Network Card SpeedTouchTM706 User Guide
RCA Portable Stereo System TC1801 User Guide
Ricoh All in One Printer D052 User Guide
Roberts Radio Stereo System R9924 User Guide
Roland Musical Instrument SRX 12 User Guide
Salton Waffle Iron FWM85B User Guide
Samsung Refrigerator RF266 User Guide
Sanyo Flat Panel Television CE32LD90 B User Guide
Schneider Electric Network Card AP9635 User Guide