BLUE FLAME VENT-FREE
NATURAL GAS
SPACE HEATER
’
OWNER S OPERATION AND INSTALLATION MANUAL
Do not store, or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
WHAT TO DO IF YOU SMELL GAS
l
l
Do not try to light any appliance.
Do not touch any electrical switch; do not
use any phone in your building.
l
l
Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
If you cannot reach your gas supplier, call
the fire department.
MN060HBA MN100HBA MN100TBA
Installation and service must be performed by a
qualified installer, service agency or gas
supplier.
Table of Contents
Important Safety Information.................................2
Product Features.....................................................3
Proper Ventilation & Fresh Air...............................4
Installation................................................................6
Operating Your Heater...........................................10
Cleaning & Maintenance.......................................13
Trouble Shooting...................................................14
Specifications..........................................................17
Parts List.................................................................19
WARNING: Improper
installation,
adjustment, alteration, service or mainte-
nance can cause injury or property damage.
Refer to this manual for correct installation and
operational procedures. For assistance or
additional information consult a qualified
installer, service agency, or gas supplier.
This appliance may be installed in an aftermar-
ket* permanently located, manufactured
(mobile) home, where not prohibited by local
codes.
This appliance is only for use with the type of
gas indicated on the rating plate. This
appliance is not convertible for use with other
gases.
WARNING: If the information in this
manual is not followed exactly, a fire or
explosion may result causing property
damage, personal injury, or loss of life.
WARNING: This is an unvented gas-fired
heater. It uses air (oxygen) from the room
in which it is installed. Provisions for
adequate combustion and ventilation air must
be provided. Refer to Air For Combus-
tion and Ventilation section on page 4 of this
manual.
*Aftermarket: Completion of sale, not for purpose of
resale, from the manufacturer.
WATER VAPOR: A BY-PRODUCT OF UNVENTED
ROOM HEATERS
Water vapor is a by-product of gas combustion. An
unvented room heater produces approximately one
(1) ounce (30ml) of water for every 1,000 BTU’s
(.3KW’s) of gas input per hour. Refer to page 3.
CONTINENTAL APPLIANCE INC/U.S. OFFICE
5 Musick
Irvine
4600 Highlands Parkway S.E.
Suite # D/E
CA 92618
Smyrna, GA 30080
Nanjing PRO-COM Electric Appliance Co.,Ltd.
#6 Chuangye Road,High New Tech.Zone,
Great Bridge Road North,Nanjing,210061,
China.
Installer: Please leave these instructions with the
consumer.
Consumer: Please retain these instructions for
future use.
TOLL FREE NUMBER: 1-877-886-5989
PR-ML062-15-0803
Download from Www.Somanuals.com. All Manuals Search And Download.
PRODUCT FEATURES
Figure1-Vent-Free Natural Gas Heater
SAFETY DEVICE
LOCAL CODES
A standard requirement for all vent-free room
heaters. This heater has a pilot with an Oxygen
Depletion Sensor(ODS) safety shutoff system.
The ODS/pilot shuts off the heater if there is
not enough fresh air.
Install and use heater with care. Follow all local
codes. In the absence of local codes, use the
latest edition of National Fuel Gas Code ANSZ223.1,
also known as NFPA 54*.
*Available from :
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
PIEZO IGNITION SYSTEM
This heater is equipped with a piezo ignitor.
This system requires no matches, batteries, or
other sources to light heater.
Quincy, MA 02269
UNPACKING
1. Remove heater from carton.
THERMOSTATIC CONTROL ON
THERMOSTAT MODEL
2. Remove all protective packaging applied to
heater for shipment.
3. Check heater for any shipping damage. If heater
is damaged. promptly inform dealer where you
bought heater.
These heaters have a control valve with a
thermostat sensing bulb. This results in the
greatest heater comfort and may result in
lower gas bills.
WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS
The following steps will help insure that water vapor
does not become a problem.
1. Be sure the heater is sized properly for the
application, including ample combustion air and
circulation air.
2. If high humidity is experienced, a dehumidifier
may be used to help lower the water vapor con-
tent of the air.
3. Do not use an unvented room heater as the pri-
mary heat source.
Water vapor is a by-product of gas combustion. An
unvented room heater produces approximately one
(1) ounce (30ml) of water for every 1,000 BTU’s
(.3KW’s) of gas input per hour.
Unventedroomheatersarerecommendedassupple-
mental heat (a room) rather than a primary heat
source (an entire house). In most supplemental heat
applications, the water vapor does not create a
problem. In most applications, the water vapor en-
hances the low humidity atmosphere experienced
during cold weather.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Unusually Tight Construction
The air that leaks around doors and
windows may provide enough fresh
air for combustion and ventilation.
However, in buildings of unusually
tight construction. you must provide
additional fresh air.
Unusually tight construction is
defined as construction where:
a. walls and ceilings exposed to the
Confined and
Unconfined Space
The National Fuel Gas Code ANS
Z223.1 defines a confined space as
a space whose volume is less than
50 cubic feet per 1,000 Btu per hour
( 4 . 8 m 3 p e r k w )
aggregate input rating of all
appliances installed in that space
FRESH AIR FOR
COMBUSTION AND
VENTILATION
WARNING: This heater
shall not be installed in a
confined space or unusually
o f
t h e
tight
provisions are provided for
adequate combustion and
construction
unless
and an unconfined space as
a
outside
atmosphere
have
a
space whose volume is not less
than 50 cubic feet per 1,000 Btu per
hour (4.8 m3 per kw) of the
aggregate input rating of all
appliances installed in that space.
Rooms communicating directly with
the space in which the
appliances are installed*, through
openings not furnished with doors,
are considered
unconfined space.
This heater shall not be installed
in a confined space or unusually
ventilation air. Read the
following instructions to
insure proper fresh air for this
continuous water vapor retarder
witha rating of one perm (6 10-11 kg
×
per pa-sec-m2)
or less with
and
other
fuel-burning
openings gasketed or sealed and
b. weather stripping has been
added on openable windows and
doors and
appliances in your home.
PROVIDING ADEQUATE
VENTILATION
c. caulking or sealants are applied to
areas such as joints around
window and door frames, between
sole plates and floors, between
wall-ceiling joints, between wall
panels, at penetrations for plumbing,
electrical, and gas lines, and at
other openings. If your home meets
all of the three criteria above, you
must provide additional fresh air.
See Ventilation Air From Outdoors,
page 6.
a
part of the
The following are excerpts from
National Fuel Gas Code. NFPA
54/ANS Z223.1, Section 5.3. Air for
Combustion and Ventilation. All
spaces in homes fall into one of
the three following ventilation
classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space
ti ght
co nstructio n
u nle ss
provisions are provided for
adequate
combustion
and
a r e
ventilation air.
A d j o i n i n g
communicating only if there are
r o o m s
*
doorless
passageways
or
The information on pages 4
through 6 will help you classify
your space and provide adequate
ventilation.
If your home does not meet all of
the three criteria above see
Determining Fresh-Air Flow for
Heater Location, page 5.
ventilation grills between them.
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if you have a Confined or Unconfined Space*
Use this worksheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways
or ventilation grills between the rooms.
1. Determine the volume of the space (length width height).
×
×
Length Width Height=
cu.ft. (volume of space)
×
×
Example: Space size 18ft. (length) 16ft.( width) 8ft. (ceiling height)=2304cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these
rooms to the total volume of the space.
×
×
2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.
(volume of space)÷50 cu. ft.=(Maximum Btu/Hr the space can support)
Example: 2304 cu. ft. (volume of space)÷50 cu.ft.=46.1 or 46.100(maximum Btu/Hr the space can support)
WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined
space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one
of the methods described in the National Fuel Gas Code, ANS Z223.1, Section 5.3
or applicable local codes.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free heater
Gas water heater*
Gas furnace
Vented gas heater
Gas Fireplace logs
Other gas appliances* +
Total
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Example:
Gas water heater
Vent free heater
Total
44,000
10,000
54,000
Btu/Hr
Btu/Hr
Btu/Hr
+
=
=
*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and
vents to the outdoors.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
Btu/Hr (maximum the space can support)
Btu/Hr (actual amount of Btu/Hr used)
Example : 51,200 Btu/Hr(maximum the space can support)
54,000 Btu/Hr(actual amount of Btu/Hr used)
The space in the above example is a confined space because the actual Btu/Hr used is more than the
maximum Btu/Hr the space can support.
You must provide additional fresh are. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined
space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From
inside Building, page 5.
B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6 .
C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an
unconfined space. You will need no additional fresh air ventilation.
AIR FOR COMBUSTION AND
VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconfined space. When ventilating to an
adjoining unconfined space, you must
provide two permanent openings: one within
12" of the ceiling and one within 12" of the
floor on the wall connecting the two spaces
(see options 1 and 2, Figure 2). You can also
remove door into adjoining room (see option
3, Figure 2). Follow the National Fuel Gas
Code NFPA 54/ANS Z223.1. Section 5.3, Air
for Combustion and Ventilation for required
size of ventilation grills or ducts
WARNING: Rework worksheet, add-
ing the space of the adjoining
unconfined space. The combined spaces
must have enough fresh air to supply all
appliances in both spaces.
Figure 2 -Ventilation Air from Inside Building
5
Download from Www.Somanuals.com. All Manuals Search And Download.
VENTILATION AIR
Ventilation Air From Outdoors
Provide extra fresh air by using
ventilation grills or duels: You must
provide two permanent openings: one within
12" of the ceiling and one within
12" of the floor.
Connect these items directly to the
outdoors or spaces open to the outdoors.
These spaces include attics and crawl
spaces. Follow the National Fuel Gas
Code NFPA 54/ANS Z223.1, Section 5.3.
Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a
thermostat-controlled power vent.
Heated air entering the attic will activate
the power vent.
Figure 3 -Ventilation Air from Outdoors
INSTALLATION
INSTALLATION NEEDS
WARNING: Never install
Before installing heater, make sure
you have the items listed below:
NOTICE: This heater is
the heater
in
l
a
bathroom (Models
intended for use as supplemental
heat. Use this heater along with
your primary heating system. Do
not install this heater as your
primary heat source. If you have
a central heating system, you
may run system’s circulating
blower while using heater. This
will help circulate the heat
throughout the house. In the
event of a power outage, you can
use this heater as your primary
heat source.
l
l
l
l
l
l
l
l
piping (check local codes)
sealant (resistant to natural gas)
equipment shutoff valve*
ground joint union
MN100HBA and MN100TBA, only
MN060HBA is allowed in bathroom.
Check local codes.)
l
l
in a recreational vehicle.
where curtains, furniture,
test gauge connection*
sediment trap
clothing, or other flammable ob-
jects are less than 36 inches
from the front, top, or sides of the
heater.
tee joint
pipe wrench
l
l
l
as a fireplace insert.
in high traffic areas.
in windy or drafty areas.
*A CSA/AGA design-certified equip-
ment shutoff valve with 1/8" NPT
tap is an acceptable alternative to
test gauge connection. Purchase
the optional CSA/AGA design cer-
tified equipment shutoff valve from
your dealer. See Accessories, page
17.
When the heater is installed in
Bathrooms,do not use flammable
products such as aerosol hair spray,
foot spary or any product that contains
flammable vapors and keep towels
away from heater.(only MN060HBA is
allowed in a bathroom.)
WARNING: A qualified
service person must install
heater. Follow all local codes.
LOCATING HEATER
CHECK GAS TYPE
Use only natural gas. If your This heater is designed to be
gas supply is not natural, do not m o u n t e d
o n
a
w a l l .
install heater. Call dealer where you For convenience and efficiency,
bought heater for proper type heater. install heater
CAUTION: This heater cre-
ates warm air currents.These cur-
rents move heat to wall surfaces
next to heater. Installing heater
next to vinyl or cloth wall cover-
ings or operating heater where
impurities (such as tobacco
smoke, aromatic candles, clean-
ing fluids, oil or kerosene lamps,
etc.) in the air exist may discolor
walls.
l
where there is easy access for
operation, inspection, and service
in coldest part of room
l
CAUTION: If you install the
heater in a home garage
l
heater pilot and burner must
be at least 18 inches above
floor.
l
locate heater where moving
vehicle will not hit it.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
FASTENING HEATER TO WALL
Mounting Bracket
Attaching to Wall Anchor: This
method allows you to attach
mounting bracket to hollow walls (wall
areas between studs) or to
solid walls (concrete or masonry).
WARNING: Maintain the
minimum clearances shown
in Figure 4. If you can,
provide greater clearances from
floor, ceiling, and joining wall.
The mounting bracket is located
on back panel of heater (see
Figure 6). It has been taped there
for shipping. Remove mounting
bracket from back panel.
Decide which method better
your needs. Either method
suits
will
provide a secure hold for the
mounting bracket.
Marking Screw Locations
1. Tape mounting bracket to wall
where heater will be located.
Make sure mounting bracket is
level.
Figure 6 -Mounting Bracket
Location
WARNING:
Maintain
Removing Lower Front Panel Of
Heater
1. Remove two Screws near
bottom corners of lower front
panel.
minimum clearances shown in
Figure 8. If you can, provide
greater clearances from floor
and joining wall.
Figure 4 -Mounting clearances As
View From Front of Heater
2. Pull bottom of lower front panel
forward, then down (see Figure
7).
2. Mark screw locations on
wall. (see Figure 8)
Note: Only mark last hole on
each end of mounting bracket.
Insert mounting screws through
these holes only.
INSTALLING THERMOSTAT
SENSING BULB
For T-Stat Model Only
1. Pull out the sensing bulb from the
two clips located in the shippng
position according to the direction
as shown by the arrow. There is no
need to take out the two bulb clips.
2. Take out the bulb clip from the
hardware package and insert it into
the square hole and then insert the
sensing bulb into the bulb clip (see
Figure 5).
3. Remove tape and mounting
bracket from wall.
Figure 7 - Removing Lower Front
Panel Of Heater
Methods For Attaching Mounting
Bracket To Wall
Only use last hole on each end of
mounting bracket to attach bracket
to wall. Attach mounting bracket to
wall only in one of two ways:
Figure 8 - Mounting Bracket
Clearances
1. Attaching to wall stud
2. Attaching to wall anchor
Attaching to Wall Stud: This method
provides the strongest hold. Insert
mounting screws through mounting
bracket and into wall studs.
Figure 5 -Moving Thermostat
Sensing Bulb
7
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Attaching Mounting Bracket To
Wall
Installing Bottom Mounting
Screw
1. Locate bottom mounting
hole. This hole is near bottom
IMPORTANT: Do not
hammer
key! For thick walls
(over 1/2" thick) or solid walls,
do not pop open wings.
Note: Wall anchors, mounting
screws, and spacers are in
hardware package. The hardware
package is provided with heater.
Attaching to Wall Stud Method
For attaching mounting bracket to
wall studs
on back
panel of heater
(see Figure 12).
1. Drill holes at marked locations
using 9/64" drill bit.
2. Place mounting bracket onto
wall. Line up last hole on each
end of bracket with holes drilled
in wall.
3. Insert mounting screws through
bracket and into wall studs.
4. Tighten screws until mounting
bracket is firmly fastened to
wall studs.
Attaching to Wall Anchor Method
For attaching mounting bracket to
hollow walls (wall areas between
studs) or solid walls (concrete or
masonry)
Figure 10 - Popping Open Anchor
Wing For Thin Walls
5. Place mounting bracket onto
wall. Line up last hole on
each end of bracket with wall
anchors.
6. Insert mounting screws through
bracket and into wall anchors.
7. Tighten screws until mounting
bracket is firmly fastened to
wall.
Figure 12 - Installing Bottom
Mounting Screw
2. Mark screw locations on wall.
3. Remove
heater
from
mounting bracket.
4. If installing bottom mounting
screw into hollow or solid wall,
install wall anchors. Follow steps
1 through 4 under Attaching To
Wall Anchor Method. If installing
bottom mounting screw into wall
Placing Heater On Mounting
Bracket
1. Locate two horizontal slots on
back panel of heater (see
Figure 11).
2. Place heater onto mounting
bracket. Slide horizontal slots
stud, drill
hole at marked
1. Drill holes at marked locations
using 5/16" drill bit. For solid
walls (concrete or masonry),
drill at least 1" deep.
2. Fold wall anchor as shown in
Figure 9 below.
locations using 9/64" drill bit.
5. Replace heater onto mounting
bracket.
6. Place spacer between bottom
mounting holes and wallanchor
or drilled hole.
7. Hold spacer in place with one
hand. With other hand, insert
mounting screw through bottom
mounting hole and spacer. Place
tip of screw in opening of wall
anchor or drilled hole.
onto stand-out
mounting bracket.
tabs
on
Figure 9 - Folding Anchor
8. Tighten screw until heater is firmly
secured to wall. Do not over tighten.
l Note: Do not replace lower front
panel at this time. Replace lower
front panel after making gas
connections and checking for
leaks (see page 9).
3. Insert wall anchor (wings
first) into hole. Tap anchor
flush to wall.
4. For thin walls (1/2" or less),
insert red key into wall
anchor. Push red key to
"pop" open anchor wings.
(see Figure 10)
Figure 11 - Mounting Heater Onto
Mounting Mracket
8
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
CONNECTING TO GAS SUPPLY
WARNING: qualified
A
service person must connect
heater gas supply. Follow all
local codes.
WARNING: This appliance
requires a 3/8" NPT (National Pipe
Thread) inlet connection
to the pressure regulator.
WARNING: Never connect
heater to private (non-utility) gas
well. This gas is commonly
known as well-head gas.
IMPORTANT: Check your gas line
pressure before connecting heater to
gas line. Gas line pressure must be
no greater than 10.5 inches of water.
If gas line pressure is higher, heater
regulator damage could occur.
Figure 13 -Gas Connection
CAUTION: Use only new,
black iron or steel pipe.
Internally-tinned copper tubing
may be used in certain areas.
Check your local codes. Use pipe
of large enough diameter to
allow proper gas volume to heater.
*A CSA/AGA design-certified equipment shutoff valve with 1/8" NPT tap is
an acceptable alternative to test gauge connection. Purchase the optional
CSA/AGA design-certified equipment shutoff valve from
your dealer. See Accessories, page 17.
IMPORTANT: Install an equipment
shutoff valve in an accessible
location. The equipment shutoff
valve is for turning on or shutting
off the gas to the appliance.
Install sediment trap in supply line
as shown in Figure 13. Locate
sediment trap where it is within
If
pipe
is
too
small,
undue loss of pressure will
occur.
reach
sediment
for cleaning. Locate
trap where trapped
Typical Inlet Pipe Diameters
All models up to 20,000 BTU’s use
3/8’’ or greater pipe;
All models 25,000 BTU’s and higher,
use 1/2” or greater pipe.
matter is not likely to freeze. A
sediment trap traps moisture and
contaminants. This keeps them
from going into heater controls. If
sediment trap is not installed or is
installed wrong, heater may
not run properly.
Apply pipe joint sealant lightly to
male threads. This will prevent
excess sealant from going into
pipe. Excess sealant in pipe could
result in clogged heater valves.
Installation must include an
equip-
ment shutoff valve, union, and
plugged 1/8" NPT tap. Locate NPT
tap within reach for test gauge hook
up. NPT tap must be up stream from
heater (see Figure 13).
CAUTION: Use pipe joint
sealant that is resistant to
natural gas.
IMPORTANT:
Hold pressure
regulator with wrench when
connecting it to gas piping and/or
fittings.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING YOUR HEATER
NON-THERMOSTAT MODEL
INSTALLATION
Pressure Testing Heater Gas
Connections
CHECKING GAS
CONNECTIONS
nFOR YOUR SAFETYn
READ BEFORE LIGHTING
1. Open equipment shutoff valve
WARNING: Test all gas
(see Figure 14).
2. Open main gas valve located on
or near gas meter.
piping and connections for leaks after
installing or servicing. Correct all
leaks at once.
WARNING: If you do not
follow
exactly, a fire or explosion may
result causing property
these
instructions
3. Make sure control knob of
heater is in the OFF position.
4. Check all joints from equipment
shutoff valve to control valve
(see Figure 15 ). Apply mixture of
liquid soap and water to gas
joints. Bubbles forming show
a leak.
5. Correct all leaks at once.
6. Light heater (see Operating
Heater, pages 10 and 11 for
non-thermostat models or page
12 for thermostat model).Check
the rest of the internal joints for
leaks.
WARNING: Never use an open
flame to check for a leak. Apply
a
damage, personal injury or
loss of life.
mixture of liquid soap and water
to all joints. Bubbles forming
show a leak. Correct all leaks at
once.
A. When lighting the pilot, follow ,
these instructions exactly.
Pressure Testing Gas Supply
Piping System
Test Pressures In Excess Of
1/2 PSIG (3.5 K Pa)
B. BEFORE LIGHTING smell all
around the appliance area for
gas. Be sure to smell next to
the floor because some gas is
heavier than air and will settle
on the floor .
1. Disconnect appliance with its
appliance
main
gas valve
(control valve) and equipment
shutoff valve from gas supply
piping system. Pressures in
excess of 1/2 psig will damage
heater regulator.
WHAT TO DO IF YOU SMELL GAS
7. Turn off heater (see To Turn Off
Gas to Appliance, page 11 for
non-thermostat models or page
12 for thermostat model).
l
l
Do not try to light any appliance.
Do not touch any electric switch;
do not use any phone in your
building.
2. Cap off open end of gas pipe
where equipment shutoff valve
was connected.
8. Replace lower front panel.
l
l
Immediately
supplier from
phone. Follow
supplier’s instructions.
If you cannot reach your
gas supplier, call the fire
department.
call
a
your gas
neighbor’s
3. Pressurize
supply
piping
the
gas
system by either using
compressed air or opening
main gas valve located on or
near gas meter.
4. Check all joints of gas supply
piping system. Apply mixture of
liquid soap and water to gas
joints. Bubbles forming show
a leak.
C. Use only your hand to push in
or turn the gas control knob.
Never use tools. If the knob
will not push in or turn by
hand, don’t try to repair it, call
a qualified service technician or
gas supplier. Force or attempted
repair may result in a fire or
explosion.
Figure 14 -Equipment Shutoff Valve
5. Correct all leaks at once.
6. Reconnect heater and equipment
shutoff valve to gas supply. Check
reconnected fittings for leaks.
Test Pressures Equal To or
Less Than 1/2 PSIG (3.5 K Pa)
1. Close equipment shutoff valve
(see Figure 14).
D. Do not use this appliance if any
part has been under water.
Immediately call
a
qualified
2. Pressurize supply piping system
by either using compressed air
or opening main gas valve
located on or near gas meter.
3. Check all joints from gas meter to
equipment shutoff valve (see
Figure 15).Apply mixture of liquid
soap and water to gas joints.
Bubbles forming show a leak.
4. Correct all leaks at once.
service technician to inspect
the appliance and to replace
any part of the control system
and any gas control which has
been under water.
Figure 15 -Checking Gas Joints
WARING:Do not over tighten gas
connections.
1 0
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING YOUR HEATER
l
Set control knob to desired
heating position.
Manual Control Models
nLIGHTINGn
nTO TURN OFFn
GAS TO APPLIANCE
NOTE: Both HIGH and LOW
are locked positions. You
must press in control knob
before turning it from these
positions.
INSTRUCTIONS
Shutting Off Heater
1. Turn control knob clockwise
to the OFF position.
1. STOP! Read
the safety
information on the side of
heater.
2. Check that gas supply to
heater is on.
2. Turn off all electric power to
the appliance if service is to
be performed.
3. Push in gas control knob
Shutting Off Burner Only
(Pilot Stays Lit)
Turn control knob clockwise
to the PILOT/IGN position.
slightly and turn clockwise
the OFF position.
4. Wait five (5) minutes to clear
out any air. Then smell for
gas, including near the floor.
to
Figure 16 -1- Control Knob In
The OFF Position (MN060HBA)
If
you
smell gas, STOP!
in the safety
nMANUAL LIGHTINGn
PROCEDURE
1. Remove lower front panel(see
Follow “B”
information on the side of the
heater. If you do not smell
gas, go to the next step.
Figure 7 page 7).
2. Follow steps
1
through 5
5. Push
slightly
counterclockwise
in gas control knob
under Lighting Instructions.
3. With control knob pressed in,
strike match. Hold match to
pilot until pilot lights.
and
turn
to
“PILOT/IGN” and depress for
five(5) seconds
4. Keep control knob pressed in
for 30 seconds after lighting
pilot. After 30 seconds, release
control knob. Follow step 8
under Lighting Instructions.
NOTE: The first time that the
Figure 16-2 - Control Knob in The
OFF Position
(MN100HBA&MN100TBA)
heater
is operated after
connecting the gas supply , the
control knob should be depressed
for about thirty (30) seconds. This
will allow air to bleed from the gas
system.
5. Replace lower front panel.
6. With control knob pressed in,
push down and release the
ignitor button. This will light
pilot. If needed, keep pressing
ignitor button until pilot lights.
7. Keep control knob depressed
for ten (10) seconds after
lighting pilot. If pilot goes out,
repeat steps 5,6 and 7.
Figure 17 - Pilot
8. To select the desired heating
level, partially press down the
control knob slightly and rotate
CAUTION: Do not try to
adjust heating levels by using
the equipment shutoff valve.
counterclockwise
. Release the
downward pressure on the knob
while continuing to turn until the
knob locks at the desired setting
position. Do not operate
between locked positions.
1 1
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING YOUR HEATER
4.
Wait five(5) minutes to clear
out any gas. Then smell for gas,
including near the floor. If you
smell gas, STOP! Follow “B”in the
safety information on the side of
heater. If you don’t smell
gas, go to the next step.
THERMOSTAT MODEL
CAUTION: Do not try to ad-
just heating levels by using the
equipment shutoff valve.
nFOR YOUR SAFETYn
READ BEFORE LIGHTING
WARNING: If you do not follow
these instructions exactly, a fire or
explosion may result causing
property damage, personal injury
or loss of life.
5. Turn control knob counterclock-
wise to the PILOT position.
Press in control knob for five(5)
seconds. (see Figure18).
Figure 18 - Control Knob in The
OFF Position
A.
When lighting the pilot, follow
these instructions exactly.
Note: You may be running
this heater for the first time
after hooking up to gas supply.
If so, the control knob may
need to be pressed in for 30
seconds. This will allow air to
bleed from the gas system.
B.
BEFORE LIGHTING smell all
around the appliance area for gas.
Be sure to smell next to the floor
because some gas is heavier than
air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
l If control knob does not pop
up when released, contact a
qualified service person or
gas supplier for repairs.
l
l
Do not try to light any appliance.
Do not touch any electric
switch, do not use any phone
in your building.
Immediately call your gas
supplier from a neighbor’s
phone. Follow the gas
supplier’s instructions.
Figure 19 - Pilot
nTHERMOSTAT CONTROL OPERATIONn
The thermostatic control used on this
m o d e l d i f f e r s f r o m s t a n d a r d
thermostats.Standard thermostats
simply turn on and off the burner. The
thermostat used on this heater senses
the room temperature. At times the
room may exceed the set temperature.
If so,the burner will shut off. The burner
will cycle back on when room tempera-
ture drops below the set temperature.
The control knob can be set to any com-
fort level between HI and LO.
Note: The thermostat sensing bulb mea-
sures the temperature of air near the
heater cabinet.This may not always agree
with room temperature(depending on
housing construction, installation location,
room size, open air temperatures,etc.)
Frequent use of your heater will let you
determine your own comfort levels.
6. With control knob pressed in,
push down and release ignitor
button. This will light pilot. The
pilot is attached to the front of
burner. The pilot can be seen
through the glass panel. If
needed, keep pressing ignitor
button until pilot lights.
Note: If pilot does not stay lit, refer
to Troubleshooting, pages 14 through
16. Also contact a qualified service
person or gas supplier for repairs.
Until repairs are made, light pilot with
match.To light pilot with match, see
Manual Lighting Procedure.
l
l
If you cannot reach your gas
supplier, call the fire department.
Use only your hand to push
C.
in or turn the gas control knob.
Never use tools. If the knob will
not push in or turn by hand, don’t
try to repair it , call a qualified
service technician or gas supplier.
Force or attempted repair may
result in a fire or explosion.
D. Do not use this appliance if
any part has been under water.
Immediately call a qualified service
technician to inspect the appliance
and to replace any part of the control
system and any gas control which
has been under water.
7.
Keep control
knob pressed
in for 30 seconds after lighting
pilot. After 30 seconds, release
control knob.
l If control knob does not pop
up when released, contact a quali-
fied service person or gas
supplier for repairs.
nTO TURN OFF GASn
TO APPLIANCE
Shutting Off Heater
Note: If pilot goes out,repeat steps 3
through 7.This heater has a safety
interlock system. Wait one(1)
minute before lighting pilot again.
8. Turn control knob counter-
nLIGHTINGn
INSTRUCTIONS
1. Turn control knob clockwise
to the OFF position.
2. Turn off all electric power to the
appliance if service is to
be performed.
1. STOP!
Read
the
safety
information on the side of heater.
Make sure equipment shutoff
valve is fully open.
clockwise
to desired heating
2.
Shutting Off Burner Only (pilot
stays lit )
Turn control knob clockwise
the PILOT position.
level. The main burner should
light. Set control knob to any
heat level between HI and LO.
3. Turn control knob clockwise
to the OFF position.
to
1 2
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING HEATER
ODS/PILOT AND BURNER
BURNER FLAME PATTERN
Continued
l
Use a vacuum cleaner, pres-
surized air or a small, soft
bristled brush to clean.
Figure 22 shows a correct burner
flame pattern. Figure 23 shows an
incorrect burner flame pattern. If
pilot flame pattern is incorrect, as
shown in Figure 23.
nMANUAL LIGHTINGn
PROCEDURE
1. Remove lower front panel (see
Figure 7 page 7).
CLEANING BURNER
PILOT AIR INLET HOLE
WARNING: If yellow tipping
occurs, your heater could produce
increased levels of carbon
monoxide. If burner flame pattern
shows yellow tipping, follow instruc-
tions at bottom of this page.
2. Follow steps through 5 under
Lighting Instructions on page12.
3. With control knob pressed in,
strike match. Hold match to pilot
until pilot lights.
4. Keep control knob pressed in for
30 seconds after lighting pilot. After
30 seconds, release control knob.
Follow step 8 under Lighting
Instuctions on page 12.
We recommend that you clean the
unit every 2,500 hours of operation or
every three months. We also
recommend that you keep the burner
tube and pilot assembly clean and free
of dust and dirt. To clean these parts
we recommend using compressed
air no greater than 30 PSl. Your local
computer store, hardware store, or
home center may carry compressed
air in a can. You can use a vacuum
cleaner in the blow position. If using
compressed air in a can, please follow
the directions on the can. If you don’t
follow directions on the can, you could
damage the pilot assembly.
Notice: Do not mistake orange
flames with yellow tipping. Dirt or
other fine particles enter the heater
a n d b u r n c a u s i n g b r i e f
patches of orange flame.
5. Replace lower front panel.
l
l
turn heater off (see To Turn Off
Gas to Appliance pages10 & 11
for non-thermostat models and
page 12 for thermostat models)
see Troubleshooting. pages 14
through 16
nINSPECTING BURNERn
Check pilot flame pattern and
burner flame pattern often.
1.
Shut off the unit, including the
pilot. Allow the unit to cool for
at least thirty minutes.
PILOT FLAME PATTERN
Figure 20 shows a correct pilot
flame pattern. Figure 21 shows an
incorrect pilot flame pattern. The
incorrect pilot flame is not touching
thermocouple. This will cause the
thermocouple to cool. When the
thermocouple cools, the heater will
shut down. If pilot flame pattern is
incorrect, as shown in Figure 21.
2. Inspect burner and pilot for dust
and dirt.
3.
Blow air through the ports/slots
and holes in the burner.
Also clean the pilot assembly. A
yellow tip on the pilot flame indi-
cates dust and dirt in the pilot
assembly. There is a small pilot air
inlet hole about two inches from
where the pilot flame comes out of
the pilot assembly (see Figure 24).
With the unit off , lightly blow air through
the air inlet hole. You may blow through
Figure 22 - Correct Burner Flame
Pattern
l turn heater off (see To Turn
Off
Gas to Appliance on page 11
for non-thermostat models or
page 12 for thermostat models.)
see Troubleshooting. pages 14
through 16.
a drinking straw if
not available.
compressed air is
Figure 23 - Incorrect Burner
Flame Pattern
l
CLEANING AND
MAINTENANCE
WARNING: Turn off heater
and let cool before servicing.
Figure 20 - Correct Pilot Flame
Pattern
Figure 24 - Pilot Inlet Air Hole
CAUTION: You must keep con-
trol areas, burner, and circulating
air passageways of heater clean.
Inspect these areas of heater
before each use. Have heater
inspected yearly by a qualified
service person. Heater may need
CABINET
Air Passageways
l
Use
pressurized air to clean.
Exterior
a
vacuum cleaner or
more frequent cleaning due to l Use a soft cloth dampened with
excessive lint from carpeting,
bedding material, pet hair, etc.
a mild soap and water mixture.
Wipe the cabinet to remove dust.
Figure 21 - Incorrect Pilot Flame
Pattern
1 3
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING
Note :
All
troubleshooting
CAUTION: Never use a wire,
needle, or similar object to clean
ODS/pilot. This can damage
ODS/pilot unit.
WARNING: Only a qualified
service person should service and
repair heater.
items are listed in order of
operation.
OBSERVED PROBLEM
POSSIBLE CAUSE
REMEDY
When ignitor button is pressed in,
there is no spark at ODS/pilot.
1. Ignitor electrode is positioned
wrong.
1. Replace ignitor.
2. Ignitor electrode is broken.
3. Ignitor electrode is not connected
to ignitor cable.
2. Replace ignitor.
3. Reconnect ignitor cable.
4. Ignitor cable is pinched or wet.
4. Free ignitor cable if pinched by
any
metal or tubing. Keep
ignitor cable dry.
5. Broken ignitor cable.
6. Bad piezo ignitor.
5. Replace ignitor cable.
6. Replace piezo ignitor.
When ignitor button is pressed in,
there is a spark at ODS/pilot but no
ignition.
1 . G a s s u p p l y t u r n e d o f f o r 1. Turn on gas supply or open
equipment shutoff valve is closed.
equipment shutoff valve.
2. Control knob not fully pressed in 2. Fully press in control knob
while pressing ignitor button.
while pressing ignitor button.
3. Air in gas lines when installed. 3. Continue holding down control
knob. Repeat igniting operation
until air is removed.
4. ODS/pilot is clogged.
4. Clean ODS/pilot (see Cleaning
and Maintenance Page 13) or
replace ODS/pilot assembly.
5. Replace gas regulator.
5. Gas regulator setting is not cor-
rect
6. Control knob not in PILOT position. 6. Turn control knob to PILOT
position.
ODS/pilot lights but flame goes out
when control knob is released.
1. Control knob is not fully pressed
in.
1. Press in control knob fully.
2. Control knob is not pressed in
long enough.
2. After ODS/pilot lights, keep control
knob pressed in 30 seconds.
3. Equipment shutoff valve is not
fully open.
3. Fully open equipment shutoff valve.
4. Thermocouple connection is
loose at control valve.
4. Hand tighten until snug, then
tighten 1/4 turn more.
5. Thermocouple damaged.
6. Control valve damaged.
5. Replace thermocouple.
6. Contact Dealer or PRO-COM.
1 4
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
REMEDY
OBSERVED PROBLEM
1. Burner orifice is clogged.
1. Clean burner orifice (see Cleaning
and Maintenance Page 13) or
replace burner orifice.
Burner(s)does not light after
ODS/pilot is lit.
2. Burner orifice diameter is too small. 2. Replace burner orifice.
3. Inlet gas pressure is too low.
3. Contact local natural gas company.
1. Manifold pressure is too low.
2. Burner orifice is clogged.
1. Contact local natural gas company.
2. Clean burner (see Cleaning and
Maintenance Page 13) or replace
burner orifice.
Delayed ignition of burner(s).
1. Burner orifice is clogged or 1. Clean burner orifice (see Cleaning
Burner backfiring during combustion.
damaged.
and Maintenance Page 13) or
replace.
2. Burner is damaged.
3. Gas regulator is defective.
2. Contact Dealer or PRO-COM.
3. Replace gas regulator.
1. Not enough air.
1. Check burner for dirt and debris.
If found, clean burner(see Cleaning
And Maintenance Page 13).
Yellow flame during burner
combustion.
2. Gas regulator is defective.
2. Replace gas regulator.
3. Inlet gas pressure is too low .
3. Contact local natural gas company.
1. Residues from manufacturing
processes
.
1. Problem will stop after a few hours
of operation.
Slight smoke or odor during
initial operation.
1. Turning control knob to HI position 1. Turn control knob to LO position
Heater produces a whistling noise
when burner is lit.
when burner is cold.
2. Air in gas line.
and let warm up for a minute.
2. Operate burner until air is removed
from line. Have gas line checked
by local natural gas company.
3. Air passageways on heater 3. Observe
blocked.
clearances (see Figure 4, Page 7).
4. Dirty or partially clogged burner 4. Clean burner (see Cleaning and
minimum installation
orifice.
Maintenance Page 13) or replace
burner orifice.
1. Metal is expanding while heating 1. This is common with most
Heater produces a clicking/ticking
noise just after burner is lit or
shut off.
or contracting while cooling.
heaters. if noise is excessive,
contact qualified service person.
1. When heated the vapors from 1. Turn heater off when using
White powder residue forming within
burner box or on adjacent
walls or furniture.
furniture polish, wax, carpet
cleaners, etc. turn into white
powder residue.
furniture polish, wax, carpet
cleaner or similar products.
1 5
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING
Continued
WARNING: If you smell gas
l
l
l
l
Shut off gas supply.
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s instructions.
l
If you cannot reach your gas supplier, call the fire department.
IMPORTANT: Operating beater where impurities in air exist may create odors. Clean-
ing supplies, paint, paint remover, cigarette smoke, cements and glues, new carpet or
textiles, etc., create fumes. These fumes may mix with combustion air and create odors.
REMEDY
POSSIBLE CAUSE
OBSERVED PROBLEM
1. Ventilate room. Stop using odor
causing products while heater
is running.
1. Heater is burning vapors from
paint, hair spray, glues, etc.
(See IMPORTANT statement
above).
Heater produces unwanted odors.
2. Locate and correct all leaks(see
Checking Gas Connections,
page 10).
2. Gas leak. See Warning
Statement at top of page.
1. Open window and/or door for
ventilation.
2. Contact local natural gas
company.
1. Not enough fresh air is available.
2. Low line pressure.
Heater shuts off in use (ODS operates).
3. Clean ODS/pilot (see Cleaning
page 12).
3. ODS/pilot is partially clogged.
1. Locate and correct all leaks(see
Checking Gas Connections,
page 10).
1. Gas leak. See Warning
Statement at top of page.
Gas odor exists even when control
knob is in OFF position.
2. Replace control valve.
2. Control valve is defective.
1. Take apart gas tubing and
remove foreign matter.
1. Foreign matter between control
valve and burner.
Gas odor during combustion.
2. Locate and correct all leaks
(see Checking Gas Connections,
page 10).
2. Gas
leak.
See Warning
Statement at top of page.
1. Refer to Air for Combustion and
1. Not enough combustion/ventilation
air.
Moisture/condensation noticed on
windows.
Ventilation requirements, page
4.
1 6
Download from Www.Somanuals.com. All Manuals Search And Download.
SPECIFICATIONS
MN060HBA
6,000
MN100HBA
6,000/10,000
Natural Only
Piezo
MN100TBA
10,000
Btu(available)
Gas Type
Natural Only
Piezo
Natural Only
Piezo
Ignition
Pressure Regulator setting
3"W.C
3"W.C
3"W.C
Inlet Gas Pressure* (inches of water)
Maximum
10.5"
4"
10.5"
4"
10.5"
4"
Minimum
Dimensions, Inches (HxWxD)
Heater
19-1/8 14-1/8 6-3/8 19-1/8 14-1/8 6-3/8
×
×
×
×
19-1/8 14-1/8 6-3/8
×
×
Carton
22 16-3/4 8-1/8
22 16-3/4 8-1/8
×
×
×
×
22 16-3/4 8-1/8
×
×
Weight (pounds)
Heater
12
15
13
16
14
17
Shipping
Note: Dimensions listed are outer most points on the heater (includes control knobs and grill).
* For purposes of input adjustment.
REPLACEMENT PARTS
Note: Use only original replacement
parts. This will protect your warranty
coverage for parts replaced under
warranty.
TECHNICAL SERVICE
You may have further questions
about installation, operation, or
troubleshooting. If so, contact
PRO-COM through the phone num-
ber 1-877-886-5989.The information
is listed on the front of manual.
PARTS UNDER WARRANTY
Contact authorized dealer from
whom you purchased this product.
If they are unable to supply original
replacement part(s), call the num-
ber on the front of this manual. When
contacting your dealer or PRO-COM,
have ready:
SERVICE HINTS
EQUIPMENT SHUTOFF VALVE
For all models. Equipment shutoff
valve with 1/8" NPT tap.
When Gas Pressure Is Too
Low
lPilot will not stay lit
lBurner will have delayed ignition
lHeater will not produce specified
heat
l
l
your name
your address
l model and serial numbers of
your heater
l
l
how heater was malfunctioning
type of gas used (propane/LP or
natural gas)
purchase date
warranty card
When Gas Quality Is Bad
l
l
Pilot will not stay lit
Burner will produce flames and
soot
l
l
l
Heater will backfire when lit
Usually, we will ask you to return the
defective part to the factory.
You may feel your gas pressure is
too low or the gas quality is poor. If
so, contact your local natural gas
supplier.
PARTS NOT UNDER
WARRANTY
Contact authorized dealers of this
product. If they can’t supply original
replacement part(s), contact PRP-
COM through the phone number 1-
877-886-5989.
FLOOR MOUNTING STAND
Models MN060HBA,MN100HBA,
MN100TBA
ACCESSORIES
Purchase these heater accesso-
ries from your local dealer. If they
can not supply these accessories,
contact PRO-COM for information.
You can also write to the address
listed on the front of this manual.
For locating heater on the floor away
from a wall. Complete installation
instructions provided with floor
mounting stand.
1 7
Download from Www.Somanuals.com. All Manuals Search And Download.
ILLUSTRATED PARTS
BREAKDOWN
MN060HBA
1 8
Download from Www.Somanuals.com. All Manuals Search And Download.
This list contains replaceable parts for your heater. When ordering replacement
parts, follow the instructions listed under Replacement Parts on page17 of this
manual.
PARTS LIST
MN060HBA
KEY
NO.
QTY.
PART NO.
DESCRIPTION
1
1
1
1
1
1
12
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
MB10008
MB09003
MB11005
ML086-03
ML087-03
ML088-03
ML069-02
NV2020-12
ML073-01
ML029-01
MB16002
NRV81FI-3
ML079-01
ML119-01
MB40033
MB40045
MB40043
NBB10-000M1
ML101-02
ML091-06
ML103-02
ML129-02
Cabinet Assembly
Lower Front Panel Assembly
Reflector Unit
Glass
Upper Glass Retainer
Lower Glass Retainer
Self Tapping Screw
Control Valve
Ignitor Line
Control Valve Fixed Nut
Control Knob Assembly
Pressure Regulator
Self Locking Screw
Pressure Tap
Main Inlet Tube Assembly
ODS Line Assembly
Gas Outlet Tube Assembly
Burner
Burner Connector
Injector
Left Burner Support Bracket
Regulator Mounting Bracket
22
23
ND1103x600x9 ODS/Pilot Assembly
Thermocouple
Ignitor Electrode
ODS Deflector
Nut
23-1 ND0803-6
23-2 ND0807
24
25
26
27
28
29
ML105-01
6170-5Z
MB29003
ML084-03
ML060-02
ML083-03
Grill Guard
Middle Panel
Mounting Bracket
Ignitor Assembly
Assembly Hardware
CSA/AGA Label
Gas Instruction Decal
MB28001
ML070-11
ML071-01
1
1
1
1 9
Download from Www.Somanuals.com. All Manuals Search And Download.
ILLUSTRATED
2 0
Download from Www.Somanuals.com. All Manuals Search And Download.
This list contains replaceable parts for your heater. When ordering replacement
parts, follow the instructions listed under Replacement Parts on page17 of this
manual.
PARTS LIST
MN100HBA
KEY
NO.
QTY.
PART NO.
DESCRIPTION
1
1
1
1
1
1
12
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
MB10008
MB09003
MB11005
ML086-03
ML087-03
ML088-03
ML069-02
NV2020-1213
ML073-01
ML029-01
MB16002
NRV81FI-3
ML079-01
MB40034
MB40056
MB40054
NBB10-000M1
ML101-01
ML091-05
ML103-02
ML129-02
Cabinet Assembly
Lower Front Panel Assembly
Reflector Unit
Glass
Upper Glass Retainer
Lower Glass Retainer
Self Tapping Screw
Control Valve
Ignitor Line
Control Valve Fixed Nut
Control Knob Assembly
Pressure Regulator
Self Locking Screw
Main Inlet Tube Assembly
ODS Line Assembly
Gas Outlet Tube Assembly
Burner
Burner Connector
Injector
Left Burner Support Bracket
Regulator Mounting Bracket
22
ND1103x600x9 ODS/Pilot Assembly
Thermocouple
Ignitor Electrode
ODS Deflector
Nut
22-1 ND0803-6
22-2 ND0807-B2
23
24
25
26
27
28
ML105-01
6170-5Z
MB29003
ML084-03
ML060-02
ML083-03
Grill Guard
Middle Panel
Mounting Bracket
Ignitor Assembly
Assembly Hardware
CSA/AGA Label
Gas Instruction Decal
MB28001
ML070-13
ML071-01
1
1
1
2 1
Download from Www.Somanuals.com. All Manuals Search And Download.
ILLUSTRATED PARTS
BREAKDOWN
MN100TBA
2 2
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS LIST
MN100TBA
This list contains replaceable parts for your heater. When ordering repalcement
parts, follow the instructions listed under Replacement Parts on page17 of this
manual.
KEY
NO.
QTY
DESCRIPTION
PART NO.
1
1
1
1
1
1
1
12
1
1
2
2
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Cabinet Assembly
Lower Front Panel Assembly
Reflector Unit
MB10007
MB09003
MB11005
ML086-03
ML087-03
ML088-03
ML069-02
SIT544-130
ML111-02
2
3
4
5
6
7
8
9
Glass
Upper Glass Retainer
Lower Glass Retainer
Self Tapping Screw
SIT Thermostat Valve Assembly
Thermostat Valve Base/Bracket
NUT
Screws
Grill
Self Locking Screw
Middle Panel
Pressure Regulator
Ignitor Line
Mounting Bracket
Main Inlet Tube Assembly
ODS Line Assembly
Burner Inlet Tube Assembly
Burner
Burner Connector
Injector
Left Burner Support Bracket
Regulator Mounting Bracket
ODS/Pilot Assembly
Thermocouple
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
26-1
26-2
27
28
6170-5Z
845-4.8x60Z
MB29003
ML079-01
ML084-03
NRV81FI-3
ML073-01
ML060-02
MB40048
MB40049
MB40050
NBB10-000M1
ML101-01
ML091-05
ML103-02
ML129-02
ND1103x800x9
ND0803-8
ND0807-B2
ML105-01
ML083-03
Ignitor Electrode
ODS Upper Deflector
Ignitor Assembly
MB28001
ML160-19
ML071-01
ML065-01
Assembly Hardware
CSA/AGA Label
Gas Instruction Decal
Thermostat Sensing Bulb Clip
1
1
1
1
2 3
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
|