Powerware® 9135 Two−in−One UPS
5000/6000 VA
User’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Class A EMC Statements
FCC Part 15
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.
EN 62040−2
Some configurations are classified under EN 62040−2 as ˆCategory C2 UPS.˜ For these configurations, the
following applies:
WARNING This is a category C2 UPS product. In a residential environment, this product may cause radio
interference, in which case the user may be required to take additional measures.
Download from Www.Somanuals.com. All Manuals Search And Download.
Special Symbols
The following are examples of symbols used on the UPS or accessories to alert you to important
information:
RISK OF ELECTRIC SHOCK − Observe the warning associated with the risk of electric shock
symbol.
CAUTION: REFER TO OPERATOR’S MANUAL − Refer to your operator’s manual for additional
information, such as important operating and maintenance instructions.
This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. This
product contains sealed, lead-acid batteries and must be disposed of properly. For more information,
contact your local recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in
the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
1
2
3
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Inspecting the Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the UPS Internal Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rackmount Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing the Rail Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tower Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Required Cable Cross−Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the Power Cables (EU Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the Power Cables (U Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS Rear Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Control Panel Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Turning the UPS On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting the UPS on Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Turning the UPS Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Eco Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Access to Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Access to UPS Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Access to Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
i
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
Life Cycle Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Anticipate Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reset or Disable LCM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
6
Additional UPS Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Communication Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
USB Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Relay Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Network Management Card (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EU Model Load Segments (PowerShare) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Hot−Swapping the Power Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hot−Swapping the Battery Tray . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
8
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Troubleshooting LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting Not Requiring Eaton Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting Requiring Eaton Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Two−Year Limited Warranty (US and Canada) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
ii
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 1
Introduction
®
The Powerware 9135 uninterruptible power system (UPS) protects
your sensitive electronic equipment from the most common power
problems including power failures, power sags, power surges,
brownouts, line noise, high voltage spikes, frequency variations,
switching transients, and harmonic distortion.
Power outages can occur when you least expect it and power
quality can be erratic. These power problems have the potential to
corrupt critical data, destroy unsaved work sessions, and damage
hardware ꢀ causing hours of lost productivity and expensive repairs.
With the Powerware 9135, you can safely eliminate the effects of power
the Powerware 9135 UPS.
Figure 1. The Powerware 9135 UPS
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
1
Download from Www.Somanuals.com. All Manuals Search And Download.
INTRODUCTION
Providing outstanding performance and reliability, the Powerware 9135’s
unique benefits include:
S Online UPS design with pure sine wave output. The UPS filters and
regulates incoming AC power and provides consistent power to your
equipment without draining the battery.
S Two−in−one form factor for using the UPS in a rack−mount
configuration or as a standalone cabinet.
S Hours of extended runtime with up to four EBMs per UPS.
S Start-on-battery capability for powering up the UPS even if utility
power is not available.
S Hot-swappable power module and battery tray that simplify
maintenance by allowing you to replace them safely without
powering down the critical load.
S Shutdown control through the remote power−off (RPO) port.
S Two standard communication options with a USB port and an RS−232
serial port.
S Advanced power management for graceful shutdowns and power
monitoring.
S For EU modelsꢀsequential shutdown and load management through
separate receptacle groups, called load segments (PowerShare).
S Optional communication cards with enhanced communication
capabilities for increased power protection and control.
S Backed by worldwide agency approvals.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
2
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 2
Safety Warnings
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and
maintenance of the UPS and batteries. Please read all instructions before operating the
equipment and save this manual for future reference.
DANGER
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS
inside the UPS.
WARNING
S
S
This UPS contains its own energy source (batteries). The UPS output may carry live
voltage even when the UPS is not connected to an AC supply.
For 208–240V models, the output receptacles may remain electrically live. If the input
power source in your application is wired line−to−neutral (as in most European
applications), the voltage to the output receptacles is 0V. With line−to−line input wiring,
the voltage to the output receptacles is 110–120V (measured from line−to−ground or
line−to−neutral, depending on the UPS wiring).
S
S
Do not remove or unplug the input cord when the UPS is turned on. This removes the
safety ground from the UPS and the equipment connected to the UPS.
To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity
controlled, indoor environment, free of conductive contaminants. Ambient temperature
must not exceed 40°C (104°F). Do not operate near water or excessive humidity
(95% maximum).
S
To comply with international standards and wiring regulations, the sum of the leakage
current of the UPS and the total equipment connected to the output of this UPS must not
have an earth leakage current greater than 3.5 milliamperes.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
3
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY WARNINGS
CAUTION
S
S
Batteries can present a risk of electrical shock or burn from high short−circuit current.
Observe proper precautions. Servicing should be performed by qualified service
personnel knowledgeable of batteries and required precautions. Keep unauthorized
personnel away from batteries.
Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
S
Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
S
Replace batteries with the same number and type of batteries as originally installed in
the UPS.
Sikkerhedsanvisninger
VIGTIGE SIKKERHEDSANVISNINGER
GEM DISSE ANVISNINGER
Denne manual indeholder vigtige instruktioner, som skal følges under installation og
vedligeholdelse af UPS’en og batterierne. Læs venligst alle instruktioner inden betjening af
udstyret og gem denne manual mhp. fremtidige opslag.
FARE
Denne UPS indeholder LIVSFARLIG HØJSPÆNDING. Alle reparationer og vedligeholdelse bør
kun udføres af en AUTORISERET SERVICETEKNIKER. Ingen af UPS’ens indvendige dele kan
repareres af brugeren.
ADVARSEL!
S
S
Denne UPS indeholder sin egen energikilde (batterier). Udgangsstikket på UPS’en kan
endog være strømførende, når UPS’en ikke er koblet til en vekselstrømsforsyning.
På 230V−modeller kan udgangsstikkene være strømførende. Hvis ledningsføringen til
indgangsstrømkilden på din enhed er fase−til−neutral (som på de fleste europæiske
enheder), er spændingen til udgangsstikkene 0V. Med en fase−til−fase
indgangsledningsføring er spændingen til udgangsstikkene 115V (målt fra fase−til−jord
eller fase−til−neutral, afhængig af UPS−ledningsføringen).
S
S
Netledningen må ikke fjernes og stikket må ikke trækkes ud, mens UPS’en er tændt.
Dette fjerner sikkerhedsjorden fra UPS’en og fra det udstyr, der er sat til.
Installér denne UPS i et temperatur− og fugtighedskontrolleret indendørsmiljø, frit for
ledende forureningsstoffer for at formindske risikoen for brand og elektrisk stød.
Rumtemperaturen må ikke overstige 40°C. UPS’en bør ikke betjenes nær vand eller høj
fugtighed (maksimalt 95%).
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
4
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY WARNINGS
S
S
I overensstemmelse med internationale normer og bestemmelser for el−installation må
det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke overskride en
jordafdelingsspænding på mere end 3,5 milliampere.
ADVARSEL
Batterierne kan give risiko for elektrisk stød eller brandsår forårsaget af høj
kortslutningsstrøm. Overhold gældende forsigtighedsregler. Servicering skal udføres af
kvalificeret servicepersonale med kendskab til batterier og gældende forsigtighedsregler.
Hold uautoriseret personale væk fra batterierne.
S
S
S
Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for
bortskaffelsesprocedurer.
Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan eksplodere ved
åben ild.
Udskift batterierne med samme batterinummer og −type som de oprindeligt installerede i
UPS’en.
Belangrijke Veiligheidsinstructies
BELANGRIJKE VEILIGHEIDSINSTRUCTIES
BEWAAR DEZE INSTRUCTIES
Deze handleiding bevat belangrijke instructies die u dient te volgen tijdens de installatie en
het onderhoud van de UPS en de accu’s. Lees alle instructies voordat u de apparatuur in
bedrijf neemt en bewaar deze handleiding als naslagwerk.
GEVAAR
Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING. Alle reparaties en
onderhoud dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL te worden uitgevoerd.
Er bevinden zich GEEN ONDERDELEN in de UPS die DOOR DE GEBRUIKER kunnen worden
GEREPAREERD.
WAARSCHUWING
S
S
Deze UPS bevat een eigen energiebron (accu’s). De UPS−uitgang kan onder spanning
staan, zelfs wanneer de UPS niet is aangesloten op de netspanning.
Bij de modellen van 230V kan de uitgangscontactdoos onder spanning blijven staan. Als
de bedrading van de ingangsspanningsbron in uw systeem loopt van fase naar aarde
(zoals bij de meeste Europese systemen) dan bedraagt de spanning op de
uitgangscontactdozen 0 V. Als de ingangsbedrading loopt van fase naar fase dan
bedraagt de spanning op de uitgangscontactdozen 115V (gemeten tussen fase en aarde
of tussen fase en neutraal, afhankelijk van de UPS−bedrading).
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
5
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY WARNINGS
S
S
Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit terwijl de
UPS aan staat. Hierdoor zou de UPS en uw aangesloten apparatuur geen
aardebeveiliging meer hebben.
Teneinde de kans op brand of elektrische schok te verminderen dient deze UPS in een
gebouw met temperatuur- en vochtigheidregeling te worden geïnstalleerd, waar geen
geleidende verontreinigingen aanwezig zijn. De omgevingstemperatuur mag 40°C niet
overschrijden. Niet gebruiken in de buurt van water of bij zeer hoge vochtigheid
(max. 95%).
S
Om aan de internationale normen en bedradingsvoorschriften te voldoen mag de gehele
apparatuur die op de uitgang van deze UPS is aangesloten, geen aardlekstroom van
meer dan 3,5 milliampère hebben.
OPGELET
S
S
Batterijen leveren gevaar op voor elektrische schokken en kunnen brandwonden
veroorzaken door een grote kortsluitstroom. Neem de juiste voorzorgsmaatregelen in
acht. Het onderhoud moet worden uitgevoerd door bevoegde onderhoudsmonteurs die
verstand hebben van accu’s en op de hoogte zijn van de vereiste voorzorgsmaatregelen.
Houd onbevoegden uit de buurt van de accu’s.
De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw
plaatselijke voorschriften.
S
Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen.
S
Vervang de accu’s door accu’s met hetzelfde nummer en van hetzelfde type als de
oorspronkelijke accu’s in de UPS.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
6
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY WARNINGS
Tarkeita Turvaohjeita
TÄRKEITÄ TURVAOHJEITA − SUOMI
SÄILYTÄ NÄMÄ OHJEET
Tämä käyttöohje sisältää tärkeitä ohjeita, joita on noudatettava UPS−virtalähteen ja akkujen
asennuksen ja huollon yhteydessä. Lue kaikki ohjeet ennen laitteiston käyttöä ja säilytä ohje
myöhempää tarvetta varten.
VAARA
Tämä UPS sisältää HENGENVAARALLISIA JÄNNITTEITÄ. Kaikki korjaukset ja huollot on
jätettävä VAIN VALTUUTETUN HUOLTOHENKILÖN TOIMEKSI. UPS ei sisällä MITÄÄN
KÄYTTÄJÄN HUOLLETTAVIA OSIA.
VAROITUS
S
S
Tässä UPS−virtalähteessä on oma energianlähde (akut). UPS−virtalähteen lähdössä voi
olla jännite, vaikka UPS−virtalähdettä ei ole kytketty verkkovirtaan.
230V −malleissa lähtövastakkeissa voi säilyä jännite. Jos sovelluksen tulovirtalähde on
johdotettu linjasta neutraaliin (kuten useimmissa eurooppalaisissa sovelluksissa)
lähtövastakkeiden jännite on 0 V. Linjasta linjaan –tulojohdotuksessa lähtövastakkeiden
jännite on 115V (mitataan linjasta maahan tai linjasta neutraaliin, UPS−virtalähteen
johdotuksesta riippuen).
S
S
Älä poista tai irrota sisääntulojohtoa, kun UPS on kytkettynä. Tämä poistaa
turvamaadoituksen UPS−laitteesta ja siihen liitetystä laitteistosta.
Vähentääksesi tulipalon ja sähköiskun vaaraa asenna tämä UPS sisätiloihin,
joissa lämpötila ja kosteus on säädettävissä ja joissa ei ole virtaa johtavia
epäpuhtauksia. Ympäristön lämpötila ei saa ylittää 40 °C. Älä käytä lähellä vettä ja vältä
kosteita tiloja (95 % maksimi).
S
S
Kansainväliset normit ja johdotusmääräykset vaativat, että kaikkien tämän UPS−laitteen
ulostulokytkentöjen yhteinen maavuotovirta ei ylitä 3,5 milliampeeria (mA).
VARO
Akut voivat aiheuttaa sähköiskun tai palovammojen vaaran johtuen suuresta
oikosulkuvirrasta. Noudata kaikkia asianmukaisia varotoimia. Laitteen saa huoltaa vain
ammattitaitoinen huoltohenkilökunta, joka tuntee akut ja niihin liittyvät varotoimet. Älä
päästä valtuuttamatonta henkilöstöä lähelle akkuja.
S
S
S
Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia määräyksiä.
Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää.
Vaihda UPS−virtalähteeseen vain samanlaiset akut ja sama määrä akkuja kuin siinä oli
alun perin.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
7
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY WARNINGS
Consignes de sécurité
CONSIGNES DE SÉCURITÉ IMPORTANTES
CONSERVER CES INSTRUCTIONS
Ce manuel comporte des instructions importantes que vous êtes invité à suivre lors de toute
procédure d’installation et de maintenance des batteries et de l’onduleur. Veuillez consulter
entièrement ces instructions avant de faire fonctionner l’équipement et conserver ce manuel
afin de pouvoir vous y reporter ultérieurement.
DANGER!
Cet onduleur contient des TENSIONS MORTELLES. Toute opération d’entretien et de
réparation doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ.
AUCUNE PIÈCE RÉPARABLE PAR L’UTILISATEUR ne se trouve dans l’onduleur.
AVERTISSEMENT!
S
S
Cette onduleur possède sa propre source d’alimentation (batteries). Il est possible que la
sortie de l’onduleur soit sous tension même lorsque l’onduleur n’est pas connectée à une
alimentation CA.
En ce qui concerne les modèles 230 V, il est possible que les prises de sortie restent
sous tension. Si la source d’alimentation de votre application est câblée phase et neutre
(comme dans la majorité des applications européennes), la tension vers les prises de
sortie est de 0 V. Avec un câblage d’entrée phase à phase, la tension vers les prises de
sortie est de 115 V (mesurée entre phase et terre ou phase et neutre suivant le câblage
de l’onduleur).
S
S
Ne pas retirer le cordon d’alimentation lorsque l’onduleur est sous tension sous peine de
supprimer la mise à la terre de l’onduleur et du matériel connecté.
Pour réduire les risques d’incendie et de décharge électrique, installer l’onduleur
uniquement à l’intérieur, dans un lieu dépourvu de matériaux conducteurs, où la
température et l’humidité ambiantes sont contrôlées. La température ambiante ne doit
pas dépasser 40 °C. Ne pas utiliser à proximité d’eau ou dans une atmosphère
excessivement humide (95 % maximum).
S
Afin d’être conforme aux normes et règlements internationaux de câblage, le courant de
fuite à la terre de la totalité du matériel branché sur la sortie de l’onduleur ne doit pas
dépasser 3,5 mA.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
8
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY WARNINGS
ATTENTION!
S
Les batteries peuvent présenter un risque de choc électrique ou de brûlure provenant
d’un courant de court−circuit haute intensité. Observez les précautions appropriées.
L’entretien doit être réalisé par du personnel qualifié connaissant bien les batteries et
les précautions nécessaires. N’autorisez aucun personnel non qualifié à manipuler les
batteries.
S
S
S
Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements
en vigueur dans votre localité.
Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les faire
exploser.
Remplacez les batteries par des batteries du même type et numéro que celles installées
à l’origine sur l’onduleur.
Sicherheitswarnungen
WICHTIGE SICHERHEITSANWEISUNGEN
AUFBEWAREN
Dieses Handbuch enthält wichtige Anweisungen, die Sie während der Installation und
Wartung des USV (Unterbrechungsfreies Stromversorgungssystem) und der Batterien
befolgen müssen. Bitte lesen Sie alle Anweisungen des Handbuches bevor sie mit dem
Gerät arbeiten. Bewaren Sie das Handbuch zum Nachlesen auf.
WARNUNG
Die USV führt lebensgefährliche Spannungen. Alle Reparatur− und Wartungsarbeiten sollten
nur von Kundendienstfachleuten durchgeführt werden. Die USV enthält keine vom Benutzer
zu wartenden Komponenten.
ACHTUNG
S
S
Dieses USV (Unterbrechungsfreies Stromversorgungssystem) enthält eine eigene
Energiequelle (Batterien). Der USV−Ausgang kann Spannung führen, auch wenn das USV
nicht an eine Wechselstromquelle angeschlossen ist.
Bei Modellen mit 208–240 Volt können die Ausgangssteckverbinder stromführend
bleiben. Wenn die Eingangsstromquelle in Ihrer Anlage mit Masseleitung verkabelt ist
(wie in den meisten europäischen Anlagen), beträgt die Spannung an den
Ausgangssteckverbindern 0 Volt. Bei einer Verkabelung mit Außenleitern beträgt die
Spannung an den Ausgangssteckverbindern 110–120 Volt (gemessen von Leitung zu
Masse oder Leitung zu Masseleiter, abhängig von der UPS (USV)−Verkabelung.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
9
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY WARNINGS
S
S
Das Eingangskabel nicht entfernen oder abziehen, während die USV eingeschaltet ist,
weil hierdurch die Sicherheitserdung von der USV und den daran angeschlossenen
Geräten entfernt wird.
Um die Brand- oder Elektroschockgefahr zu verringern, diese USV nur in Gebäuden mit
kontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine leitenden
Schmutzstoffen vorhanden sind. Die Umgebungstemperatur darf 40°C nicht übersteigen.
Die USV nicht in der Nähe von Wasser oder in extrem hoher Luftfeuchtigkeit (max. 95 %)
betreiben.
S
Um internationale Normen und Verdrahtungsvorschriften zu erfüllen, dürfen die an den
Ausgang dieser USV angeschlossenen Geräte zusammen einen Erdableitstrom von
insgesamt 3,5 Milliampere nicht überschreiten.
VORSICHT!
S
S
Batterien können das Risiko eines elektrischen Schlags bergen oder durch hohen
Kurzschlussstrom in Brand geraten. Die richtigen Vorsichtsmaßnahmen beachten. Die
Wartung muss von qualifiziertem Wartungspersonal durchgeführt werden, das im
Umgang mit Batterien geübt ist und über gute Kenntnisse der erforderlichen
Vorsichtsmaßnahmen verfügt. Nicht autorisiertes Personal von Batterien fern halten.
Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die örtlichen
Bestimmungen zu beachten.
S
Batterien niemals verbrennen, da sie explodieren können.
S
Falls Sie die Batterien austauschen, verwenden Sie bitte ausschließlich die gleiche
Anzahl und die Batterietypen.
Avvisi di sicurezza
IMPORTANTI ISTRUZIONI DI SICUREZZA
CONSERVARE QUESTE ISTRUZIONI
Il presente manuale contiene importanti istruzioni da seguire durante l’installazione e la
manutenzione dell’UPS e delle batterie. Leggere integralmente le istruzioni prima di
utilizzare l’apparecchiatura e conservare il presente manuale per futuro riferimento.
PERICOLO
La TENSIONE contenuta in questo gruppo statico di continuità è LETALE. Tutte le operazioni
di riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DA
PERSONALE TECNICO AUTORIZZATO. All’interno del gruppo statico di continuità NON vi
sono PARTI RIPARABILI DALL’UTENTE.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
10
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY WARNINGS
AVVERTENZA
S
S
L’UPS contiene la propria fonte di energia (batterie). Le prese d’uscita dell’UPS possono
essere sotto tensione anche quando l’UPS non è collegato all’alimentazione elettrica CA.
Nei modelli da 230 V è possibile che le prese d’uscita rimangano sotto tensione. Se la
fonte di alimentazione in entrata dell’installazione è costituita da un collegamento
linea−neutro (come accade nella maggior parte delle installazioni europee), la tensione
delle prese d’uscita è pari a 0 V. Con un cablaggio in entrata del tipo linea−linea, la
tensione sulle prese d’uscita è 115 V (con misurazione effettuata da linea a terra o da
linea a neutro in base al cablaggio dell’UPS).
S
S
Non rimuovere nè scollegare il cavo di ingresso quando il gruppo statico di continuità è
acceso poichè in tal modo si disattiverebbe il collegamento a terra di sicurezza del
gruppo statico di continuità e dell’apparecchiatura ad esso collegata.
Per ridurre il rischio di incendio o di scossa elettrica, installare il gruppo statico di
continuità in un ambiente interno a temperatura ed umidità controllata, privo di agenti
contaminanti conduttivi. La temperatura ambiente non deve superare i 40°C. Non
utilizzare l’unità in prossimità di acqua o in presenza di umidità eccessiva (95% max).
S
S
Per conformità con gli standard internazionali e con le norme in merito al cablaggio, tutta
l’apparecchiatura collegata con l’uscita del gruppo statico di continuità non deve avere
una corrente di dispersione di terra superiore a 3,5 milliampere.
ATTENZIONE
Le batterie possono comportare un rischio di scossa elettrica o di ustione in seguito a
un’elevata corrente di corto circuito. Osservare le dovute precauzioni. L’assistenza deve
essere eseguita da personale qualificato esperto di batterie e delle necessarie
precauzioni. Tenere il personale non autorizzato lontano dalle batterie.
S
S
S
Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento fare
riferimento alle disposizioni locali.
Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle
fiamme.
Sostituire le batterie con altre dello stesso numero e tipo di quelle originariamente
installate nell’UPS.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
11
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY WARNINGS
Viktig Sikkerhetsinformasion
VIKTIGE SIKKERHETSINSTRUKSJONER
GJEM DISSE INSTRUKSJONENE
Denne håndboken inneholder viktige instruksjoner som du bør overholde ved montering og
vedlikehold av UPS−enheten og batteriene. Les alle instruksjoner før utstyret tas i bruk, og
gjem håndboken til fremtidig referanse.
FARLIG
Denne UPS’en inneholder LIVSFARLIGE SPENNINGER. All reparasjon og service må kun
utføres av AUTORISERT SERVICEPERSONALE. BRUKERE KAN IKKE UTFØRE SERVICE PÅ
NOEN AV DELENE i UPS’en.
FARLIG
S
S
UPS−enheten inneholder sin egen energikilde (batterier). UPS−utgangen kan være
strømførende selv når UPS−enheten ikke er koblet til et strømuttak.
Utgangsstikkene kan være strømførende for 230V modellene. Spenningen til
utgangsstikkene vil være 0 V dersom din enhets strømkilde er fase−til−nøytral (som på de
fleste europeiske enheter). Med ledningsført fase−til−fase inngang vil spenningen til
utgangsstikkene være 115V (målt fra fase−til−jord eller fase−til−nøytral, avhenging av
UPS−ledningsføringen).
S
S
S
For å redusere fare for brann eller elektriske støt, bør denne UPS’en installeres i et
innendørs miljø med kontrollert temperatur og luftfuktighet som er fritt for ledende,
forurensende stoffer. Romtemperaturen må ikke overskride 40°C. Den må ikke brukes i
nærheten av vann eller ved meget høy luftfuktighet (95% maks.).
For å redusere fare for brann eller elektriske støt, bør denne UPS’en installeres i et
innendørs miljø med kontrollert temperatur og luftfuktighet som er fritt for ledende,
forurensende stoffer. Romtemperaturen må ikke overskride 40°C. Den må ikke brukes i
nærheten av vann eller ved meget høy luftfuktighet (95% maks.).
Alt utstyr som er forbundet med utgangen av denne UPS’en må ikke ha en sterkere total
lekkasjestrøm enn 3,5 milliampere for å være i overensstemmelse med internasjonale
standarder og forkablingsbestemmelser.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
12
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY WARNINGS
FORSIKTIG
S
S
Batterier kan utgjøre en fare for elektrisk støt eller brannsår pga. høy kortsluttingsstrøm.
Treff passende forholdsregler. Service bør utføres av kvalifisert servicepersonale med
kjennskap til batterier og nødvendige forholdsregler. Hold uautorisert personale borte fra
batteriene.
Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om fjerning av
batterier.
S
Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes for åpen ild.
Skift ut originalbatteriene i UPS−enheten med samme antall og type.
S
Regulamentos de Segurança
INSTRUÇÕES DE SEGURANÇA IMPORTANTES
GUARDE ESTAS INSTRUÇÕES
Este manual contém instruções importantes que devem ser seguidas durante a instalação e
manutenção do no−break e das baterias. Leia todas as instruções antes de operar o
equipamento e guarde este manual para consultá−lo futuramente.
CUIDADO
A UPS contém VOLTAGEM MORTAL. Todos os reparos e assistência técnica devem ser
executados SOMENTE POR PESSOAL DA ASSISTÊNCIA TÉCNICA AUTORIZADO. Não há
nenhuma PEÇA QUE POSSA SER REPARADA PELO USUÁRIO dentro da UPS.
ADVERTÊNCIA
S
S
Este no−break possui sua própria fonte de energia (baterias). A saída do no−break pode
estar energizada mesmo que este não esteja conectado a uma fonte de energia elétrica.
Nos modelos 230V, pode ser que as tomadas de saída permaneçam energizadas. Se a
alimentação da sua aplicação for do tipo fase−neutro (como ocorre na maioria das
aplicações na Europa), a tensão das tomadas de saída é de 0 V. Com a alimentação
fase−fase, a tensão das tomadas de saída é de 115V (medida como fase−terra ou
fase−neutro, dependendo da instalação elétrica do no−break).
S
Não remova ou desconecte o cabo de entrada quando a UPS estiver ligada. Isto
removerá o aterramento de segurança da UPS e do equipamento conectado.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
13
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY WARNINGS
S
S
Para reduzir o risco de incêndios ou choques elétricos, instale a UPS em ambiente
interno com temperatura e umidade controladas e livres de contaminadores condutíveis.
A temperatura ambiente não deve exceder 40°C. Não opere próximo a água ou em
umidade excessiva (máx: 95%).
Para estar de acordo com os padrões internacionais e os regulamentos de fiação, o
equipamento total conectado à saída desta UPS não deve ter uma corrente de fuga à
terra maior que 3,5 miliampères.
PERIGO
S
S
As baterias podem oferecer risco de choque elétrico ou queimadura, ocasionados por
alta tensão com possibilidade de curto−circuito. Tome as precauções adequadas. A
manutenção deve ser realizada por pessoal qualificado, com conhecimento sobre
baterias e ciente das precauções exigidas. Mantenha o pessoal não autorizado afastado
das baterias.
Siga as instruções apropriadas ao desfazer-se das baterias. Consulte os códigos do local
para maiores informações sobre os regulamentos de descarte de produtos.
S
Nunca jogue as baterias no fogo, porque há risco de explosão.
S
Ao realizar a troca das baterias, utilize a mesma quantidade e o mesmo tipo de bateria
instalada originalmente no no−break.
Ïðåäóïðåæäåíèÿ ïî ìåðàì áåçîïàñíîñòè
ÂÀÆÍÛÅ ÓÊÀÇÀÍÈß ÏÎ ÌÅÐÀÌ ÁÅÇÎÏÀÑÍÎÑÒÈ
ÑÎÕÐÀÍÈÒÅ ÝÒÈ ÓÊÀÇÀÍÈß
 äàííîì ðóêîâîäñòâå ñîäåðæàòñÿ âàæíûå èíñòðóêöèè ïî óñòàíîâêå è
îáñëóæèâàíèþ èñòî÷íèêà áåñïåðåáîéíîãî ïèòàíèÿ (ÈÁÏ) è áàòàðåé. Ïåðåä
ðàáîòîé ñ îáîðóäîâàíèåì ïðî÷òèòå âñå èíñòðóêöèè. Ñîõðàíèòå äàííîå
ðóêîâîäñòâî äëÿ äàëüíåéøåãî èñïîëüçîâàíèÿ.
ÎÏÀÑÍÎ
 äàííîì ÈÁÏ èìåþòñÿ ÑÌÅÐÒÅËÜÍÎ ÎÏÀÑÍÛÅ ÍÀÏÐßÆÅÍÈß. Âñå
ðàáîòû ïî ðåìîíòó è îáñëóæèâàíèþ äîëæíû âûïîëíÿòüñÿ ÒÎËÜÊÎ
ÓÏÎËÍÎÌÎ×ÅÍÍÛÌ ÎÁÑËÓÆÈÂÀÞÙÈÌ ÏÅÐÑÎÍÀËÎÌ. Âíóòðè
ÈÁÏ íåò óçëîâ, ÎÁÑËÓÆÈÂÀÅÌÛÕ ÏÎËÜÇÎÂÀÒÅËÅÌ.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
14
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY WARNINGS
ÏÐÅÄÓÏÐÅÆÄÅÍÈÅ
S
S
 äàííîì ÈÁÏ óñòàíîâëåíû ñîáñòâåííûå èñòî÷íèêè ýíåðãèè (áàòàðåè). Â
ÈÁÏ ìîæåò èìåòüñÿ íàïðÿæåíèå äàæå â òîì ñëó÷àå, åñëè îí íå ïîäêëþ÷åí
ê ñåòè ïåðåìåííîãî òîêà.
Íà âûõîäíûõ ðîçåòêàõ ìîäåëåé ñ íàïðÿæåíèåì 230 Â ìîæåò áûòü
íàïðÿæåíèå. Åñëè óñòðîéñòâî ðàññ÷èòàíî íà òèï ïîäêëþ÷åíèÿ
ꢀôàçà−íåéòðàëü" (êàê áîëüøèíñòâî óñòðîéñòâ, èçãîòàâëèâàåìûõ â Åâðîïå),
íàïðÿæåíèå íà âûõîäíûõ ðîçåòêàõ ðàâíî 0 Â. Ïðè òèïå ïîäêëþ÷åíèÿ
ꢀôàçà−ôàçà" íàïðÿæåíèå íà âûõîäíûõ ðîçåòêàõ ñîñòàâëÿåò 115 Â (ïðè
èçìåðåíèè ꢀôàçà−çåìëÿ" èëè ꢀôàçà−íåéòðàëü", â çàâèñèìîñòè îò
ýëåêòðè÷åñêîé ñõåìû ÈÁÏ).
S
S
Íå îòñîåäèíÿéòå ñåòåâîé øíóð è íå èçâëåêàéòå åãî âèëêó èç ðîçåòêè ïðè
âêëþ÷åííîì ÈÁÏ. Ïðè ýòîì çàùèòíîå çàçåìëåíèå îòêëþ÷àåòñÿ îò ÈÁÏ è
îò îáîðóäîâàíèÿ, ïîäêëþ÷åííîãî ê ÈÏÁ.
Äëÿ ñíèæåíèÿ îïàñíîñòè ïîæàðà èëè ïîðàæåíèÿ ýëåêòðè÷åñêèì òîêîì
óñòàíàâëèâàéòå ÈÁÏ â çàêðûòîì ïîìåùåíèè ñ êîíòðîëèðóåìûìè
òåìïåðàòóðîé è âëàæíîñòüþ, â êîòîðîì îòñóòñòâóþò ïðîâîäÿùèå
çàãðÿçíÿþùèå âåùåñòâà. Òåìïåðàòóðà îêðóæàþùåãî âîçäóõà íå äîëæíà
ïðåâûøàòü 40°Ñ. Íå ýêñïëóàòèðóéòå óñòðîéñòâî îêîëî âîäû èëè â ìåñòàõ ñ
ïîâûøåííîé âëàæíîñòüþ (ìàêñ. 95%).
S
Äëÿ îáåñïå÷åíèÿ ñîáëþäåíèÿ òðåáîâàíèé ìåæäóíàðîäíûõ ñòàíäàðòîâ è
òðåáîâàíèé ê ðàçâîäêå ýëåêòðè÷åñêèõ öåïåé, ñóììàðíàÿ âåëè÷èíà òîêà
óòå÷êè íà çåìëþ âñåãî îáîðóäîâàíèÿ, ïîäêëþ÷åííîãî ê âûõîäó ÈÁÏ, íå
äîëæíà ïðåâûøàòü 3,5 ìèëëèàìïåðà.
ÎÑÒÎÐÎÆÍÎ
S
S
Âûñîêîå íàïðÿæåíèå, âûçâàííîå êîðîòêèì çàìûêàíèåì â áàòàðåå, ìîæåò
ïðèâåñòè ê ïîðàæåíèþ ýëåêòðè÷åñêèì òîêîì èëè îæîãó. Ñîáëþäàéòå
ìåðû ïðåäîñòîðîæíîñòè. Òåõíè÷åñêîå îáñëóæèâàíèå äîëæíî
îñóùåñòâëÿòüñÿ êâàëèôèöèðîâàííûì ïåðñîíàëîì ïî ðàáîòå ñ
èñòî÷íèêàìè ïèòàíèÿ, çíàêîìûì ñ ìåðàìè ïðåäîñòîðîæíîñòè. Íå
äîïóñêàéòå ê ðàáîòå ñ áàòàðåÿìè ïîñòîðîííèõ.
Íåîáõîäèìî ñîáëþäàòü ïðàâèëà óòèëèçàöèè àêêóìóëÿòîðîâ. Îáðàòèòåñü ê
ìåñòíûì íîðìàòèâíûì àêòàì çà èíôîðìàöèåé î òðåáîâàíèÿõ ê
óòèëèçàöèè.
S
S
Íèêîãäà íå áðîñàéòå àêêóìóëÿòîðû â îãîíü. Àêêóìóëÿòîðû ìîãóò
âçîðâàòüñÿ ïîä âîçäåéñòâèåì îãíÿ.
Çàìåíÿéòå áàòàðåè ÈÁÏ òîëüêî òàêèì æå êîëè÷åñòâîì áàòàðåé
àíàëîãè÷íîãî òèïà.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
15
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY WARNINGS
Advertencias de Seguridad
INSTRUCCIONES DE SEGURIDAD IMPORTANTES
GUARDE ESTAS INSTRUCCIONES
Este manual contiene instrucciones importantes que debe seguir durante la instalación y el
mantenimiento del SIE y de las baterías. Por favor, lea todas las instrucciones antes de
poner en funcionamiento el equipo y guarde este manual para referencia en el futuro.
PELIGRO
Este SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio técnico deben
ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO TÉCNICO AUTORIZADO. No hay
NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro del SIE.
ADVERTENCIA
S
S
Este SIE contiene su propia fuente de energía (baterías). La salida del SIE puede
transportar voltaje activo aun cuando el SIE no esté conectado con una fuente de CA.
Para los modelos 230V, es posible que los receptáculos de salida permanezcan
eléctricamente activos. Si la fuente de energía de entrada de su aplicación está
cableada de línea a neutro (como la mayoría de las aplicaciones europeas), el voltaje a
los receptáculos de salida es 0V. Con cableado de entrada de línea a línea, el voltaje
hacia los receptáculos de salida es 115V (medido de línea a tierra o de línea a neutro, lo
que dependerá del cableado del SIE).
S
S
No retire o desenchufe el cable de entrada mientras el SIE se encuentre encendido. Esto
suprime la descarga a tierra de seguridad del SIE y de los equipos conectados al SIE.
Para reducir el riesgo de incendio o de choque eléctrico, instale este SIE en un lugar
cubierto, con temperatura y humedad controladas, libre de contaminantes conductores.
La temperatura ambiente no debe exceder los 40°C. No trabaje cerca del agua o con
humedad excesiva (95% máximo).
S
Para cumplir con los estándares internacionales y las normas de instalación, la totalidad
de los equipos conectados a la salida de este SIE no debe tener una intensidad de
pérdida a tierra superior a los 3,5 miliamperios.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
16
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY WARNINGS
PRECAUCIÓN
S
Las baterías pueden constituir un riesgo de descarga eléctrica o quemaduras por
corriente alta de corto circuito. Adopte las precauciones debidas. Personal calificado de
servicio que conozca de baterías y esté al tanto de las precauciones requeridas debe
darle servicio al equipo. Mantenga al personal no autorizado alejado de las baterías.
S
S
S
Es necesario desechar las baterías de un modo adecuado. Consulte las normas locales
para conocer los requisitos pertinentes.
Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se las expone a
la llama.
Reemplace las baterías con el mismo número y tipo de baterías como se instalaron
originalmente en el SAI.
Säkerhetsföreskrifter
VIKTIGA SÄKERHETSFÖRESKRIFTER
SPARA DESSA FÖRESKRIFTER
Den här anvisningen innehåller viktiga instruktioner som du ska följa under installation och
underhåll av UPS−enheten och batterierna. Läs alla instruktioner innan du använder
utrustningen och spara den här anvisningen för framtida referens.
FARA
Denna UPS−enhet innehåller LIVSFARLIG SPÄNNING. ENDAST AUKTORISERAD
SERVICEPERSONAL får utföra reparationer eller service. Det finns inga delar som
ANVÄNDAREN KAN UTFÖRA SERVICE PÅ inuti UPS−enheten.
VARNING
S
S
Den här UPS−enheten innehåller sin egen energikälla (batterier). UPS−enhetens uttag kan
vara spänningsförande även då UPS−enheten inte är ansluten till spänningsnätet.
På modellerna 230 V kan de utgående uttagen fortfarande vara strömförande. Om den
ingående strömkällan i din applikation är kopplad ledare−till−nolla (det vanligaste i
Europa) är spänningen till de utgående uttagen 0 V. Är den ingående strömkällan kopplad
ledare−till−ledare är spänningen i de utgående uttagen 115 V (uppmätt från
ledare−till−jord eller ledare−till−nolla beroende på UPS:ens anslutning).
S
Ta aldrig bort nätsladden när UPS−enheten är påslagen. Detta tar bort skyddsjordningen
från både UPS−enheten och den anslutna utrustningen.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
17
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY WARNINGS
S
S
Minska risken för brand eller elektriska stötar genom att installera denna UPS−enhet
inomhus, där temperatur och luftfuktighet är kontrollerade och där inga ledande
föroreningar förekommer. Omgivande temperatur får ej överstiga 40°C. Använd inte
utrustningen nära vatten eller vid hög luftfuktighet (max 95 %).
För att överensstämma med internationell standard och installationsföreskrifter får inte
den totala utrustning som anslutits till uttagen på denna UPS−enhet ha läcksström som
överstiger 3,5 milliampere.
VIKTIGT
S
Batterierna kan innebära en risk för elektrisk stöt eller brännskada från kortsluten
starkström. Iakttag lämpliga försiktighetsåtgärder. Service ska utföras av utbildad
servicepersonal med kunskap om batterierna och nödvändiga försiktighetsåtgärder. Håll
ej behörig personal borta från batterierna.
S
S
S
Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning.
Använda batterier får aldrig brännas upp. De kan explodera.
Byt ut batterierna mot samma antal och typer av batterier som ursprungligen installerats
i UPS−enheten.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 3
Installation
This section explains:
S Equipment inspection
S UPS internal battery connection
S UPS setup and installation, including Extended Battery Modules
(EBMs)
S Remote power−off (RPO) installation
S UPS rear panels
Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping
cartons and packing materials for the carrier or place of purchase and file
a claim for shipping damage. If you discover damage after acceptance,
file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with
the carrier within 15 days of receipt of the equipment; 2) Send a copy of
the damage claim within 15 days to your service representative.
NOTE Check the battery recharge date on the shipping carton label. If the date has expired
and the batteries were never recharged, do not use the UPS. Contact your service
representative.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
19
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Checking the Accessory Kit
NOTE Packaging must be destroyed according to waste management standards. Recycling
icons are displayed for easy selection.
Verify that the following additional items are included with the UPS:
Table 1. UPS Accessory Kit
Item
Description
UPS user’s guide or CD
Screwdriver
RS−232 serial cable
Rackmounting kit for 19−inch (48 cm) bays
Two sets of pedestals with screws for tower position
Optional.
Network Management Card
EU models only.
Four cord−retention brackets
EU models only.
Four, 10A equipment power cords
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
20
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
If you ordered an optional EBM, verify that the following items are
included with the EBM:
Table 2. EBM Accessory Items
Item
Description
EBM user’s guide
EBM cable
EBM communication cable
Rackmounting kit for 19−inch (48 cm) bays
Pedestal extenders for tower position
Joining bracket and screws for tower position
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
21
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Connecting the UPS Internal Battery
To ensure proper battery operation:
1. Verify that the UPS is off and unplugged.
Two
Screws
Battery Switch
Figure 2. Removing the Battery Switch Screws
3. Slide the battery connector so that you can read Connected (see
5. Continue to the following section, ꢁUPS Setup."
Figure 3. Connecting the Internal Battery Connector
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
22
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
UPS Setup
The Powerware 9135 UPS is designed for flexible configurations and can
be installed in a rack or as a standalone cabinet.
If you are installing the UPS in a rack, continue to the following section,
Rackmount Setup
The rail kit can be mounted in 19-inch panel (48 cm) racks from 24 to
30 inches (61 to 76 cm) deep and includes:
S Left and right sliding rail assemblies
®
S (20) M4 6 mm Phillips flat−head screws
S (4) M4 10 mm Phillips round−head screws
S (4) M6 12 mm Phillips round−head screws
S (8) M6 12 mm Phillips flat−head screws
S (2) mounting brackets
S (2) rear hold−down brackets
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
23
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Installing the Rail Kit
CAUTION
S
S
DO NOT install the UPS or EBM in a hermetically−closed environment without any
exchange of air.
battery tray from the UPS before lifting. 2) A minimum of two people are required to lift
the cabinets into the rack.
NOTE The rails and the necessary mounting hardware are supplied by Eaton.
To install the rail kit:
1. Adjust the UPS control panel orientation by slightly pulling out the
Figure 4. Adjusting the UPS Control Panel Orientation
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
24
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
S Remove the UPS front cover (six screws).
NOTE A ribbon cable connects the control panel to the UPS. Do not pull on the cable or
disconnect it.
S Place the front panel above the UPS.
S Remove the two battery retaining brackets (four screws).
S Slightly pull the battery tray, then lift it to extract it.
Figure 5. Removing the Battery Tray
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
25
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
3. Place the Powerware cabinet on a flat, stable surface with the front
of the cabinet facing you.
NOTE You can adjust the position of the mounting brackets.
4. Align the mounting brackets with the screw holes on the side of the
cabinet and secure with the supplied M4 6 mm flat−head screws.
cabinet.
Figure 6. Installing the Mounting Brackets
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
26
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
6. Loosen the assembly wing nuts on both rail assemblies and adjust
7. Select the proper holes in the rail for positioning the UPS in the
desired location in the rack.
8. Using two M6 12 mm flat−head screws, attach the rail to the rear
of the rack.
9. Secure the rail to the front of the rack with two M6 12 mm
screws.
Figure 7. Installing the Rails
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
27
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
11. Optional. Install the rear hold−down brackets (included with the rail
kit) if you need to move the rack enclosure with the UPS already
Figure 8. Installing the Rear Hold−Down Brackets
12. Slide the UPS and any optional EBMs into the rack.
13. Secure the front of the cabinet to the rack using two M6 12 mm
Figure 9. Installing the Cabinets
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
28
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
14. Optional. If you installed the rear hold−down brackets, secure the
brackets to the rear rails using two screws for each bracket (see
Figure 10. Securing the Rear Hold−Down Brackets
tray and secure with the battery retaining brackets.
Replace the UPS front cover.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
29
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Tower Setup
CAUTION
S
S
DO NOT install the UPS or EBM in a hermetically−closed environment without any
exchange of air.
the cabinets into the pedestals.
The setup varies depending on the number of cabinets you are installing:
Figure 11. Assembling the UPS Pedestals
For two or more cabinets, the pedestal extenders and the joining
NOTE Always keep 150 mm free space behind the UPS rear panel. The distance between
the tower stands should be 450 mm.
3. Carefully position the cabinet upright with the UPS indicators at the
4. Adjust the pedestals to the size of the UPS and secure the
pedestals with the captive screws.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
30
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
UPS Indicators
150 mm
(6")
450 mm
(17.7")
Figure 12. Tower Position with One Cabinet
5. Continue to the following section, ꢁInstalling the UPS."
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
31
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
6. Install pedestal extenders for each additional cabinet:
For two cabinets, insert the extender into position 3 on the pedestal
For three cabinets or more, insert the extender into position 4 on
4
3
2
1
4
3
2
1
Figure 13. Extending the Pedestals for Two Cabinets
4
3
2
1
4
3
2
1
4
3
2
1
Figure 14. Extending the Pedestals for Three or More Cabinets
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
32
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
7. Carefully position the cabinet upright with the UPS indicators at the
8. Adjust the pedestals to the size of the UPS and secure the
pedestals with the captive screws.
Figure 15. Tower Position with Two Cabinets
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
33
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
9. Align each joining bracket with the adjacent cabinet screw holes
NOTE Joining brackets are required for installations with two or more cabinets.
Joining Bracket
Figure 16. Installing the Joining Brackets
11. Continue to the following section, ꢁInstalling the UPS."
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
34
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Installing the UPS
NOTE Do not make unauthorized changes to the UPS or accessories; otherwise, damage
may occur to your equipment and void your warranty.
To install the UPS and optional EBMs:
2. Verify that the EBM battery circuit breaker is OFF.
3. Plug the EBM cable into the battery connector. Plug the EBM
Up to four EBMs may be connected to the UPS.
EBM Cable
EBM
Communication
Cable
Battery Circuit
Breaker
EBM Battery
Connectors
Figure 17. UPS Installation with Three EBMs
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
35
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
4. If you plan to install power management software, connect your
computer to the USB port or RS−232 communication port. For
RS−232, use only the serial cable supplied in the accessory kit. For
SWITCHED
GROUP
1
RS−232 Communication Cable
RS−232 Communication Port
RS−232
CONTACTS
BATT. NORP.
O
Figure 18. Installing the RS−232 Serial Cable
5. If you are installing a remote power−off (RPO) switch, see the
following section, ꢁRPO Installation," to install the switch before
powering on the UPS.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
36
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
RPO Installation
Installation of the RPO function must be carried out in compliance with
applicable regulations. The cable is not included.
In order to fully de−energize devices and the Powerware 9135 with the
RPO port, it is necessary to:
S Use a two−position switch (normally−open or normally−closed contact
and held more than one second).
S Connect this RPO switch to a device that trips all breaker(s) located
be achieved by means of a shunt trip:
(1)
(2)
upstream and downstream the Powerware 9135 UPS. This can
(1)
−
−
If not, the output devices could be powered again through static
switch when the two−position switch is released.
(2)
If not, the output devices will remain powered several seconds
after the RPO activation.
NOTE The internal batteries will remain connected to the power module after RPO
activation.
RPO Contact Normally−Open
RPO Contact Normally−Closed
RJ−12 (6p6c)
RJ−12 (6p6c)
5 Vdc to 27 Vdc
5 Vdc to 27 Vdc
Figure 19. RPO Communication Port
S Signal:
−
−
Activation voltage: 5 Vdc to 27 Vdc
Current: 10 mA maximum
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
37
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
UPS Electrical Connections
WARNING
Only qualified service personnel (such as a licensed electrician) shall perform the electrical
installation. Risk of electrical shock.
CAUTION
S
S
For UPS models with hardwired outputs, overcurrent protection for the output AC
circuit(s) is to be provided by others.
For UPS models with hardwired outputs, suitably rated disconnect switches for the
output AC circuit(s) are to be provided by others.
Recommended Upstream Protection
The indicated protection ensures discrimination for each output circuit
downstream of the UPS.
If these recommendations are not followed, protection discrimination is
not achieved and may result in a potential power interruption to the
connected devices.
UPS Power Rating
Upstream Circuit Breaker
EU Models
U Models
5000 VA
6000 VA
D curve − 32A
D curve − 35A
2 Poles Circuit Breaker
L (L1)
N (L2)
To Utility Source
G
N
L
(L2) (L1)
Figure 20. Recommended Upstream Protection
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
38
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Recommended Downstream Protection (EU Models Only)
The indicated protection ensures discrimination for each output circuit
downstream of the UPS.
If these recommendations are not followed, protection discrimination is
not achieved and may result in a potential power interruption to the
connected devices.
UPS Power Rating
Downstream Circuit Breaker
EU Models Only
Z curve − 10A
C curve − 4A
Z curve − 10A
C curve − 6A
5000 VA
6000 VA
Required Cable Cross−Sections
Wiring
Function
EU Models
U Models
Terminal block cable
capacity
2
6 mm , solid or stranded wire
2
2
6 mm , solid or stranded wire
2
(maximum 8 mm or
10 AWG).
(maximum 8 mm or 8 AWG).
Capacity for ground/
earthing conductor
Continue to the following section, ꢁConnecting the Power Cables (EU
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
39
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Connecting the Power Cables (EU Models)
WARNING
S
S
S
Only qualified service personnel (such as a licensed electrician) shall perform the
electrical connection. Risk of electrical shock.
Before carrying out any connection, check that the battery circuit breaker and upstream
protection device (utility input) are OFF (O).
Use included insulated ferrules with stranded wires.
1. Remove the terminal block cover (two screws) with the supplied
Input Cable Opening
Output Cable Opening
Figure 21. Removing the Terminal Block (EU Models)
2. Insert the input cable through the input cable opening (see
3. Connect the three wires to the input terminal block.
CAUTION
Always connect the ground/earthing wire first.
4. Insert the output cable through the output cable opening.
5. Connect the three wires to the output terminal block.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
40
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Input Cable
Output Cable
Figure 22. Installing the Input and Output Cables (EU Models)
6. Replace the terminal block cover and tighten the cables.
7. Secure the terminal block cover with the two screws removed in
8. Plug the equipment to be protected into the appropriate UPS output
Connect any high−power devices to the 16A outlet.
9. Install the cord−retention brackets to secure the cords and provide
strain relief.
(2) 16A Receptacles
(4) Priority Receptacles
(4) Non−Priority Receptacles
Cord−Retention
Brackets
Figure 23. Connecting the Power Cords (EU Models)
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
41
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
Connecting the Power Cables (U Models)
WARNING
S
S
S
Only qualified service personnel (such as a licensed electrician) shall perform the
electrical connection. Risk of electrical shock.
Before carrying out any connection, check that the battery circuit breaker and upstream
protection device (utility input) are OFF (O).
Use included insulated ferrules with stranded wires.
1. Remove the terminal block cover (two screws) with the supplied
N
L
CT:
E
IONN
TO
C
UISLE
DAB
OC
NY
D
ER
E
A
O
TO
AT
N
TCdc
VD
T
C
D
A
B
R
D
E
R
E
18
ORY
TU
A
0
O
B
N
N
A
4
C
2
0V~,
−25
00
2
Input Cable
Output Cable
Opening
Figure 24. Removing the Terminal Block (U Models)
2. Connect the three wires to the input terminal block.
CAUTION
Always connect the ground/earthing wire first.
3. Insert the output cable through the output cable opening.
4. Connect the three wires to the output terminal block.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
42
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
N
O
ATRTL
CT:
E
IONN
E
T
CO
UIS
E
L
A
T
DAB
OC
NY
C
O
R
A
D
D
E
B
Y
RD
ON
TU
R
E
c
BN
1
80
C
ATECDd
V
N
A
O
4
2
0V~,
−25
00
2
Input Terminal
Output Terminal
GND L2 L1
(N)
GND L2 L1
(N)
Figure 25. Installing the Input and Output Cables (U Models)
5. Replace the terminal block cover and tighten the cables.
6. Secure the terminal block cover with the two screws removed in
7. Plug the equipment to be protected into the appropriate UPS output
receptacles.
NOTE If more than one load is connected to the UPS, the total capacity of the loads should
not exceed 30A.
N
CT:
E
IONN
TO
C
T
UIS
LE
DB
A
A
COC
A
4
2
Vdc
0V~,
25
−
00
2
Figure 26. Connecting the Power Cords (U Models)
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
43
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
UPS Rear Panels
This section shows the rear panels of the Powerware 9135 models.
SWITCHED
GROUP
1
(2) Sets of 2 Programmable, 10A
Receptacles
(4) 10A Receptacles
Output Terminal Block
Input Terminal Block
(2) 16A Receptacles
12A Thermal Switch
20A Thermal Switch
12A Thermal Switch
Communication Bay
Relay Port
EBM Battery Connector
USB Port
RS−232 Port
EBM RJ−11 Connector
RS−232
CONTACTS
BATT. NO.
RPO
RPO Port
Figure 27. 5000/6000 VA, EU Models
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
44
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
(4) L6−30 Receptacles
Output Terminal Block
Input Cord with L6−30P
EBM Battery Connector
Communication Bay
Relay Port
USB Port
RPO Port
RS−232
BATT. NO. RPO
RS−232 Port
EBM RJ−11 Connector
Figure 28. 5000/6000 VA, U Models
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
45
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
46
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 4
Operation
This section describes:
S The control panel
S Turning the UPS on and off
S Starting the UPS on battery
S Operating modes
S Display functions
Control Panel Functions
The UPS has a four−button graphical LCD with backlight. It provides
useful information about the UPS itself, load status, events,
Battery Indicator
Power Indicator
Bypass Indicator
Alarm Indicator
esc
Escape Up
Down Enter
On/Off Button
Figure 29. UPS Control Panel
NOTE The On/Off button controls only the UPS output. The On/Off button has no effect on
equipment connected to the UPS.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
47
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION
Turning the UPS On
To turn the UPS on:
1. Verify that the UPS internal battery connector is connected (see
2. Set the upstream circuit breaker (not included) to the ON position.
The equipment is powered by utility power, but not protected by
the UPS.
Batteries are recharging. An eight−hour recharge period is necessary
to get full backup time.
The
and
indicators illuminate.
To change the factory-set defaults, see ꢁUser Settings " on
3. Press and hold the button until you hear the UPS beep
(approximately three seconds).
After the UPS is turned on, it conducts a self−test and enters
Normal mode. The
turns off indicating that power is available to your equipment.
indicator remains on and the
indicator
If the alarm beeps or a UPS alarm indicator stays on, see
Starting the UPS on Battery
NOTE Before using this feature, the UPS ON/OFF settings must have been enabled (see
To turn on the UPS without using utility power, press and hold the
button for three seconds. The UPS starts up in Battery mode and
supplies battery power to your equipment.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
48
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION
Turning the UPS Off
To shut down the UPS:
1. Press the button for approximately three seconds
The UPS beeps once, and the load is no longer protected by the
UPS. It is powered by utility power. If the UPS is set in frequency
converter mode, the equipment will not be powered.
If the utility power is out of tolerance, the UPS will generate a
10 ms output calibrated break.
2. For a full shutdown of UPS and connected load, the upstream
circuit breaker (not included) should be set to the OFF position.
Operating Modes
The Powerware 9135 front panel indicates the UPS status through the
controls.
On Battery Indicator
Power On Indicator
Bypass Indicator
Alarm Indicator
Indicator Legend
Unlit
Lit
Flashing
esc
On/Off Button
Figure 30. UPS Front Panel
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
49
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION
Normal Mode
During Normal mode, the
indicator illuminates. The UPS monitors
and charges the batteries as needed and provides power protection to
your equipment.
Eco Mode
During Eco mode, the indicator illuminates. Eco mode reduces the
consumption of electrical power.
Under normal conditions (utility power available), the equipment is
supplied in ECO mode.
NOTE ECO mode: operating mode by which the equipment is supplied directly by the
utility power if it is within the tolerances defined by the user.
If utility power is out of tolerance, the indicator flashes and the
indicator illuminates. The equipment is protected by the UPS.
Battery Mode
When the UPS is operating during a power outage, the alarm beeps
once every five seconds and the
and
indicators illuminate. The
equipment is protected by the UPS and supplied by the battery. The
display shows the remaining battery backup time.
If battery capacity becomes low while in Battery mode, the alarm beeps
every five seconds. Immediately complete and save your work to
prevent data loss and similar difficulties.
When the utility power returns, the UPS transfers to Normal mode
operation while the battery recharges.
End of backup time: all indicators turn off. The alarm beeps continuously
and the UPS displays End of backup time Battery low.
When utility power is restored after the UPS shuts down, the UPS
automatically restarts.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
50
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION
Bypass Mode
The UPS transfers to Bypass mode when:
S The utility power is out of tolerence
S There is an overload condition
S The
button is pressed
S There is a malfunction
The and
utility power.
indicators illuminate and the equipment is powered by
Display Functions
Status and Alarms
Measurements
UPS Input Measurements
UPS Output Measurements
Battery Measurements
UPS Setup
Maintenance
Local Settings
Model
Output Settings
ON/OFF Settings
Battery Settings
Alarm History
Manual Batt Test
LED & Buzzer Test
LCM
Statistics
Figure 31. Menu Map for Display Functions
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
51
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION
Access to Measurements
Press the button on the UPS front panel to access measurements for
voltage, current, frequency, power output, and battery capacity.
Access to UPS Setup
To access the UPS Setup menu:
1. Scroll to the UPS Setup menu by pressing the
button.
2. Press the
button to get access.
esc
Figure 32. Access to UPS Setup
The following tables display the options that can be changed by the
user.
Table 3. Local Settings
Function
Factory Setting
Options
Language
English
French, German, Italian, Portuguese, Spanish
US (MM−DD−YYYY/HH:MM AM/PM)
Date / Time Format
International
(DD−MM−YYYY/HH :MM)
Date / Time Change
Audible Alarm
GMT + 1
(Continental Europe)
MM−DD−YYYY/HH :MM adjustable
No
Yes
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
52
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION
Table 4. Output Settings
Function
Factory Setting
Options
Comments
Output Voltage
EU Models: 230V
U Models: 208V
200V / 208V / 220V /
240V / 250V
Freq Converter
Disable
Enable
60 Hz
Output Frequency
EU Models: 50 Hz
U Models: 60 Hz
User selectable under
frequency−converter mode
Eco Mode
Slew Rate
Disable
1 Hz / sec
Yes
Enable
0.5 Hz / sec
No
Bypass Transfer
If bypass Ac nok?
Transfer to bypass if utility power is
out of tolerance
Interrupt Time
10 ms
105%
20 ms, ...... , 200 ms
40%, 50%, 70%
Break time calibration during load
transfer on utility power out of
tolerance
Overload Prealarm
Alarm if threshold is overrun
Table 5. ON/OFF Settings
Function
Factory Setting
Disable
Options
Comments
Cold Start
Enable
Start on battery
Forced Reboot
Enable
Enables automatic restart of the
system even if utility power is
restored before the end of the
shutdown sequence
Auto Restart
Enable
Disable
Enable
UPS restarts automatically when
utility power is restored
Energy Saving
Disable
Automatic shutdown on battery if
output load level <10%
Sleep Mode
Enable
Enable
Disable
Disable
Remote Command
Enables consideration of shutdown or
restart orders from software to be
authorized
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
53
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION
Table 6. Battery Settings
Function
Factory Setting
Options
Comments
Auto Battery Test
Everyweek
No test / everyday /
everyweek /everymonth
Low Batt Warning
User Batt Settings
20%
0 to 100%
1% increment
UPS reads number of
battery modules
connected
From 0 to 95 Ah
5 Ah increment
Deep Disch Protect
Yes
No
Protection against deep discharge.
If disabled, the Eaton warranty will be
void.
Access to Maintenance
To access the Maintenance menu:
1. Scroll to the Maintenance menu by pressing the
button.
2. Press the
button to get access.
esc
Figure 33. Access to Maintenance
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
54
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION
The following table displays the maintenance options.
Table 7. Maintenance Settings
Function
Sub−Function
Power Module
Frame
Option/Display
Comments
Model
SN: xxxxxxxxx
SOFT: xxx
Serial number
Soft version
Alarm History
Read
Description
Date Hour
Alarm xxx
10 alarms can be stored automatically
Erase
No / Yes
Manual Batt Test
Led & Buzzer Test
Life Cycle Monitoring
Statistics
Manual Battery Test
Led & Buzzer Test
LCM
No / Yes
No / Yes
Enable / Disable
Statistics
Life cycling monitoring alarms
Auto Statistics
Custom Statistics
Reset Date ?
Are you sure ?
Life Cycle Monitoring
LCM displays messages on the UPS front panel and through the
communication channels, at every important stage of the UPS´s life.
Press the
button to display LCM warning details.
esc
Figure 34. LCM Warning Screen
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
55
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION
Anticipate Maintenance
Automatic warnings appear when maintenance actions need to be
planned:
Table 8. LCM Warning Details
LCM Warning Details
Signification
BATTERY CHECK RECOMMENDED Battery is approaching its reliability end of life.
Risk to reduce dramatically backup time.
Reset or Disable LCM
In case of any LCM messages displayed:
S For temporary reset: press the esc button for at least three seconds
while in the Status and Alarm menu to temporarily cancel the alarm
status.
The alert will be repeated twice every 30 days.
S For permanent reset: press the
button for at least three seconds
while in the LCM warning menu to permanently cancel the LCM
event.
At any time:
S To disable all LCM messages, select disable allwhile in the LCM
menu.
Be careful: if you disable all LCM messages, you will not be aware of
any LCM events that can happen on the UPS.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
56
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 5
Additional UPS Features
This section describes:
S Communication ports
S Network Management Card
S Load segments (PowerShare)
Communication Ports
The Powerware 9135 provides three communication methods that can
be used simultaneously:
S RS−232 or USB communication. Compatible with most power
management software applications. Note that both ports cannot be
used at the same time.
S The relay port uses output contacts for basic signaling or for
®
®
®
protection of IT systems like IBM iSeries (formerly AS/400 ) and
more.
S The communication bay is compatible with the optional Network
Management Card.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
57
Download from Www.Somanuals.com. All Manuals Search And Download.
ADDITIONAL UPS FEATURES
USB Port
The UPS can communicate with a USB−compliant computer using
®
Powerware LanSafe Power Management Software or other
HID−compliant power management software compatible with Microsoft
®
®
Windows 2000 and XP operating systems that support HID devices.
NOTE The latest versions of the Powerware LanSafe Power Management Software and
To establish communication between the UPS and a computer:
1. The USB port is hot−pluggable. Connect the USB cable to the USB
Connect the other end of the USB cable to the USB port on your
computer.
SWITCHED
GROUP
1
SWITCHED
GROUP
2
USB Port
RS−232
CONTACTS
BATT. NORP.
O
Figure 35. The USB Port
2. Install the Powerware LanSafe Power Management Software and
USB drivers according to the instructions provided at
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
58
Download from Www.Somanuals.com. All Manuals Search And Download.
ADDITIONAL UPS FEATURES
Relay Port
When the status is active, the contact between the common (Pin 5) and
the relevant information pin is closed.
Output relays specifications:
S
S
S
Voltage: 48 Vdc maximum
Current: 2A maximum
Power: 62.5 VA, 30W
Example: for 48 Vdc, Imax=625 mA
functions.
5
4
3
2
1
9
8
7
6
NC NO
Common
NO
NO
NO
NOTE Normally−open (NO)
Normally−closed (NC)
Figure 36. Communication Port
Table 9. Communication Port Pin Assignment
Pin Number
Function
1, 2
3
Not used
Remote Power−off signal (5–27 Vdc, 10 mA max)
Operation on mains (not on battery)
User common
4
5
6
Operation on automatic bypass
Low Battery
7
8
Load protected
9
Operation on battery
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
59
Download from Www.Somanuals.com. All Manuals Search And Download.
ADDITIONAL UPS FEATURES
Network Management Card (Optional)
It is not necessary to shut down the UPS before installing a
communication card.
1. Remove the slot cover secured by two screws.
2. Insert the communication card into the slot.
3. Secure the card with both screws.
SWITCHED
GROUP
1
Communication Card
(restricted access)
RS−232
CONTACTS
BATT. NO.RPO
Figure 37. Network Management Card (EU Model Shown)
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
60
Download from Www.Somanuals.com. All Manuals Search And Download.
ADDITIONAL UPS FEATURES
EU Model Load Segments (PowerShare)
During a power outage, you can keep key pieces of equipment running
while you turn off other equipment. It is preferable to connect the
1
2
non−priority loads to the programmable receptacles,
and
. This
feature allows you to save battery power. See your power management
information).
NOTE If power management software is not used, the individual load segments cannot be
controlled.
1
Programmable Receptacles
2
Programmable Receptacles
Figure 38. Load Segments (EU Models Only)
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
61
Download from Www.Somanuals.com. All Manuals Search And Download.
ADDITIONAL UPS FEATURES
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
62
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 6
Maintenance
This section describes replacing the power module and battery tray.
Hot−Swapping the Power Module
WARNING
Only qualified service personnel (such as a licensed electrician) shall perform the electrical
installation. Risk of electrical shock.
This operation can be performed without interrupting the equipment.
NOTE A ribbon cable connects the control panel to the UPS. Do not pull on the cable or
disconnect it.
2. Place the front panel above the UPS.
3. Remove the two power module brackets (four screws).
4. Slightly pull the power module, then lift it to extract it.
Figure 39. Removing the Power Module
5. Replace the faulty power module with one of the same power
rating (5000 VA or 6000 VA) and secure with the power module
brackets.
6. Replace the UPS front cover.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
63
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE
Hot−Swapping the Battery Tray
CAUTION
S
Batteries can present a risk of electrical shock or burn from high short−circuit current.
Observe proper precautions. Servicing should be performed by qualified service
personnel knowledgeable of batteries and required precautions. Keep unauthorized
personnel away from batteries.
S
S
S
Remove watches, rings, bracelets and all other metal objects from the hands and arms.
Use tools with an insulated handle.
When replacing batteries, replace with the same number of the BB/HR5.5−12 batteries.
This operation can be performed without interrupting the equipment.
NOTE A ribbon cable connects the control panel to the UPS. Do not pull on the cable or
disconnect it.
2. Place the front panel above the UPS.
3. Remove the two battery retaining brackets (four screws).
4. Slightly pull the battery tray, then lift it to extract it.
Figure 40. Removing the Battery Tray
5. Replace the battery tray and secure with the battery retaining
brackets.
NOTE To ensure safety and high performance, use only batteries supplied by Eaton.
6. Replace the UPS front cover.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
64
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 7
Specifications
Table 10. Input and Output Specifications
Power Levels
Output on
Battery Power
AC Input
Voltage
Model Number
(Rated at
Nominal
Voltage
Frequency
Range
Nominal Inputs)
3
Voltage
Frequency
60 Hz
1
2
Range
PW9135G5000−XL3UHW
PW9135G5000−XL3U
5000 VA, 3500W
6000 VA, 4200W
208V
156–280V
208V
230V
PW9135G6000−XL3UHW
PW9135G6000−XL3U
40–70 Hz
0.2 Hz)
(
PW9135G5000−XL3UEU
PW9135G6000−XL3UEU
5000 VA, 3500W
6000 VA, 4200W
230V
156–280V
50 Hz
1
Adjustable to 200V (10% derating of output power) 208/220/230/240/250V.
2
3
Table 11. Dimensions and Weights
Model
Dimensions (WxHxD)
Weight
5000 VA UPS
6000 VA UPS
444.5 130.6 741 mm
57 kg (125.7 lb)
(17.5" 5.1" 29.2")
198 127 603 mm
UPS Power Module
UPS Internal Battery
EBM
12 kg (26.5 lb)
30.5 kg (67.2 lb)
70.5 kg (155.4 lb)
(7.8" 5" 23.7")
214.5 116 498 mm
(8.4" 4.6" 19.6")
444.5 130.6 650 mm
(17.5" 5.1" 25.6")
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
65
Download from Www.Somanuals.com. All Manuals Search And Download.
SPECIFICATIONS
Table 12. Power Connections
Model
Input Connection
Output Receptacles
U Models
10 ft, L6−30P power cord
(4) NEMA L6−30R
Hardwired with
(8) 10A, IEC 320−C13; (2) 16A, IEC 320−C19
EU Models
Hardwired
Table 13. Environmental and Safety
U Models
EU Models
Operating Temperature
Storage Temperature
Relative Humidity
Operating Altitude
Audible Noise
0°C to 40°C (32°F to 104°F)
−25°C to 40°C (−13°F to 104°F)
5–95% noncondensing
Up to 1,000 meters above sea level
Less than 46 dBA Normal mode, typical load and Battery mode
ANSI C62.41 Category B, IEC 61000−4−5
Surge Suppression
Safety Conformance
UL 1778;
CSA C22.2, No. 107.1;
NOM−019−SCFI
UL 1778;
CSA C22.2, No. 107.1;
EN 62040−1−1, IEC 60950−1, IEC 50091−1−1
Agency Markings
EMC (Class A)
cUL, NOM
TUV(GS), CE, cUL, C−tick
FCC Part 15
EN 62040−2 C1, AS 62040−2 C1, FCC Part 15
Table 14. Battery
UPS Configuration
(15) 12V, 5.5 Ah internal batteries
EBM Configuration
Type
(2 strings of 15) 12V, 5.5 Ah internal batteries
Sealed, maintenance-free, lead-acid
Table 15. Battery Runtimes
UPS
UPS Internal Batteries
+1 EBM
22 min
17 min
+2 EBMs
41 min
+3 EBMs
1 hr 2 min
50 min
+4 EBMs
1 hr 23 min
1 hr 7 min
5000 VA
6000 VA
5 min
4 min
33 min
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
66
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 8
Troubleshooting
This section explains:
S UPS alarms and conditions
S Service and support
Troubleshooting LED
Press the esc button to stop the audible alarm.
NOTE In case of "MULTIPLE FAULT", press the
to further details.
button and the
button to get access
esc
Escape Up
Down Enter
Figure 41. Troubleshooting LED
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
67
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING
Troubleshooting Not Requiring Eaton Service
esc
Figure 42. Environment Fault
Press the
button to display the following details:
Displayed Details
NO BATTERY
Signification
Correction
The battery is incorrectly connected.
Check battery connections.
Check AC wiring.
I/O BAD CONNECTION
Utility input is not connected to the correct
terminals.
NO POWER MODULE
The power module is not inserted.
Check power module connections (see
page 63).
NO BATTERY MODULE
INV THERM OVERLOAD
The battery tray is incorrectly connected.
The UPS shuts down automatically because Check the power drawn by the connected
of a major overload.
devices and disconnect any non−priority
devices.
INVERT LIMITATION
Short circuit conditions on output devices.
Check the installation at the UPS output
(wiring, fault equipment).
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
68
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING
Troubleshooting Requiring Eaton Service
NOTE In case of multiple fault, press the
further details.
button and the
button to get access to
esc
Escape Up
Down Enter
Figure 43. Troubleshooting LED
Correction
Display
Signification
POWER MODULE FAULT Internal power module fault detected. Use
"Enter" button to display details.
Call the Help Desk. Replace the power
In Parallel: see the note below to start the
other UPS alone.
BATT MODULE FAULT
FRAME FAULT
Battery fault detected during the battery
test. Use "Enter" button to display details.
Call the Help Desk. Replace the battery tray
Internal chassis fault detected. Use "Enter" Call the Help Desk.
button to display details.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
69
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING
Service and Support
If you have any questions or problems with the UPS, call your Local
Distributor or the Help Desk at one of the following telephone numbers
and ask for a UPS technical representative.
United States:
Canada:
1−800−356−5737 or 1−919−870−3149
1−800−461−9166 ext 260
Call your local service representative
All other countries:
Please have the following information ready when you call the Help
Desk:
S Model number
S Serial number
S Version number (if available)
S Date of failure or problem
S Symptoms of failure or problem
S Customer return address and contact information
If repair is required, you will be given a Returned Material Authorization
(RMA) Number. This number must appear on the outside of the package
and on the Bill Of Lading (if applicable). Use the original packaging or
request packaging from the Help Desk or distributor. Units damaged in
shipment as a result of improper packaging are not covered under
warranty. A replacement or repair unit will be shipped, freight prepaid for
all warrantied units.
NOTE For critical applications, immediate replacement may be available. Call the Help
Desk for the dealer or distributor nearest you.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
70
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter 9
Warranty
Two−Year Limited Warranty (US and Canada)
®
Powerware UPS Models: 3105, 9120, 9125, 9135, 9140, and FERRUPS up to 3.1 kVA
WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Electrical Inc., a Delaware
Corporation company (ꢁCompany").
LIMITED WARRANTY: This limited warranty (this ꢁWarranty") applies only to the original End−User (the ꢁEnd−User")
of any Powerware 3105, 9120, 9125, 9135, 9140, and FERRUPS up to 3.1 kVA Products (individually and
collectively, the ꢁProduct") purchased on or after June 1, 2004 and cannot be transferred. This Warranty applies
even in the event that the Product is initially sold by Company for resale to an End−User.
LIMITED WARRANTY PERIOD: The period covered by this Warranty for Product installed [and currently located] in
the fifty (50) United States, the District of Columbia, and Canada is twenty−four (24) months from the date of
purchase.
WHAT THIS LIMITED WARRANTY COVERS: The warrantor warrants that the Product and battery (individually and
collectively, the "Warranted Items") are free from defects in material and workmanship. If, in the opinion of
Company, a Warranted Item is defective and the defect is within the terms of this Warranty, Company’s sole
obligation will be to repair or replace such defective Warranted Item (including by providing service, parts and labor,
as applicable), at the option of Company.
PROCEDURES FOR REPAIR OR REPLACEMENT OF WARRANTED ITEMS: The Warranted Item will be repaired or
replaced at a Company site or such other location as determined by Company.
If the Warranted Item is to be replaced by Company, and the End−User supplies a credit card number or purchase
order for the value of the replacement Product, Company will use commercially reasonable business efforts to ship
(via standard ground shipment and at no cost to the End−User) the replacement Warranted Item to the End−User
within one (1) business day after Company receives notice of the warranty claim. In such case, the End−User must
return (at Company’s expense) the defective Warranted Item to Company in the same packaging as the
replacement Warranted Item received by the End−User or as otherwise instructed by Company. If Company does
not receive the defective Warranted Item, Company will either charge the End−User’s credit card, or send the
End−User an invoice (which the End−User agrees to pay), for the value of the replacement Product.
If the Warranted Item is to be replaced by Company, but the End−User is unwilling or unable to supply a credit card
number or purchase order for the value of the replacement Product, Company will use commercially reasonable
business efforts to ship (via standard ground shipment and at no cost to the End−User) the replacement Warranted
Item to the End−User within one (1) business day after Company receives the defective Product from the End−User.
In any case, Company will provide shipping instructions and will pay its designated carrier for all shipping charges for
return of defective equipment and replacement of Warranted Items. Any returned Warranted Item or parts that are
replaced may be new or reconditioned. All Warranted Items returned to Company and all parts replaced by
Company shall become the property of Company.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
71
Download from Www.Somanuals.com. All Manuals Search And Download.
WARRANTY
WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages
caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than
the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect,
accident, abuse, misuse, misapplication, or incorrect installation; (d) repair or alteration not authorized in writing by
Company personnel or performed by an authorized Company Customer Service Engineer or Agent; (e) improper
testing, operation, maintenance, adjustment, or modification of any kind not authorized in writing by Company
personnel or performed by an authorized Company Customer Service Engineer or Agent; or (f) use of the Product
under other than normal operating conditions or in a manner inconsistent with the Product’s labels or instructions.
This Warranty is not valid if the Product’s serial numbers have been removed or are illegible. Any Warranted Items
repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the original Warranty
subject to all the terms thereof.
Company shall not be responsible for any charges for testing, checking, removal or installation of Warranted Items.
COMPANY DOES NOT WARRANT EQUIPMENT NOT MANUFACTURED BY COMPANY. IF PERMITTED BY THE
APPLICABLE MANUFACTURER, COMPANY SHALL PASS THROUGH SUCH MANUFACTURER’S WARRANTIES TO
END−USER.
COMPANY DOES NOT WARRANT SOFTWARE, INCLUDING SOFTWARE EMBEDDED IN PRODUCTS, THAT IS NOT
CREATED BY COMPANY. WITHOUT LIMITING THE FOREGOING, COMPANY SPECIFICALLY DOES NOT WARRANT
SOFTWARE (SUCH AS LINUX) THAT WAS CREATED USING AN ꢀOPEN SOURCE" MODEL OR IS DISTRIBUTED
PURSUANT TO AN OPEN SOURCE LICENSE.
THIS WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY OFFERED BY COMPANY WITH RESPECT TO THE
PRODUCTS AND SERVICES AND, EXCEPT FOR SUCH FOREGOING WARRANTY COMPANY DISCLAIMS ALL OTHER
WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY, TITLE,
NON−INFRINGEMENT, AND FITNESS FOR A PARTICULAR PURPOSE. CORRECTION OF NON−CONFORMITIES IN
THE MANNER AND FOR THE PERIOD OF TIME PROVIDED ABOVE SHALL CONSTITUTE COMPANY’S SOLE
LIABILITY AND END−USER’S EXCLUSIVE REMEDY FOR FAILURE OF COMPANY TO MEET ITS WARRANTY
OBLIGATIONS, WHETHER CLAIMS OF THE END−USER ARE BASED IN CONTRACT, IN TORT (INCLUDING
NEGLIGENCE OR STRICT LIABILITY), OR OTHERWISE.
LIMITATION OF LIABILITY: The remedies of the End−User set forth herein are exclusive and are the sole remedies
for any failure of Company to comply with its obligations hereunder. In no event shall Company be liable in contract,
in tort (including negligence or strict liability) or otherwise for damage to property or equipment other than the
Products, including loss of profits or revenue, loss of use of Products, loss of data, cost of capital, claims of
customers of the End−User or any special, indirect, incidental or consequential damages whatsoever. The total
cumulative liability of Company hereunder whether the claims are based in contract (including indemnity), in tort
(including negligence or strict liability) or otherwise, shall not exceed the price of the Product on which such liability
is based.
Company shall not be responsible for failure to provide service or parts due to causes beyond Company’s
reasonable control.
END−USER’S OBLIGATIONS: In order to receive the benefits of this Warranty, the End−User must use the Product
in a normal way; follow the Product’s user’s guide; and protect against further damage to the Product if there is a
covered defect.
OTHER LIMITATIONS: Company’s obligations under this Warranty are expressly conditioned upon receipt by
Company of all payments due to it (including interest charges, if any). During such time as Company has not
received payment of any amount due to it for the Product, in accordance with the contract terms under which the
Product is sold, Company shall have no obligation under this Warranty. Also during such time, the period of this
Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any
overdue or unpaid amounts.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
72
Download from Www.Somanuals.com. All Manuals Search And Download.
WARRANTY
COSTS NOT RELATED TO WARRANTY: The End−User shall be invoiced for, and shall pay for, all services not
expressly provided for by the terms of this Warranty, including without limitation, site calls involving an inspection
that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials,
freight charges, travel expenses or labor of Company representatives outside the terms of this Warranty will be
borne by the End−User.
OBTAINING WARRANTY SERVICE: In the USA, call the Customer Reliability Center 7x24 at 800−356−5737. Outside
of the USA, call your local Powerware product sales or service representative, or call the Customer Reliability Center
in the USA at 919−870−3149. For comments or questions about this Warranty, write to the Customer Quality
Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.
Ten−Year Pro−Rated Limited Warranty (US and Canada)
Powerware UPS Models: 5115, 5125, 5140, 9120, 9125, 9135, 9140, 9155, 9170+, and FERRUPS
WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Electrical Inc., a Delaware
Corporation company (ꢁCompany").
LIMITED WARRANTY: This pro−rated limited warranty (this ꢁWarranty") applies only to the original End−User (the
ꢁEnd−User") of any Powerware 5115, 5125, 5140, 9120, 9125, 9135, 9140, 9155, 9170+, and FERRUPS Products
(individually and collectively, the ꢁProduct") and cannot be transferred. This Warranty applies even in the event that
the Product is initially sold by Company for resale to an End−User.
WHAT THIS WARRANTY COVERS: In addition to the standard Two−Year Limited Warranty covering the applicable
Product, the warrantor warrants that the Product will have a service life (defined below) of ten years from the date
of purchase (the ꢁTen−Year Service Life") when used in accordance with the storage, handling, installation,
operation and maintenance procedures prescribed in the Product’s user’s guide. ꢁService life" means the Product’s
ability to deliver at least 80% of its original rated backup time.
If Company finds, in its sole discretion, that any Product has not provided the Ten−Year Service Life, Company will,
as its sole obligation and the End−User’s sole remedy for Company’s breach of this warranty, repair or replace the
Product, at its option, F.O.B. Company’s factory, for a charge, payable by the End−User to Company pro−rated on the
following basis:
The End−User will be allowed a credit against Company’s list price of equivalent equipment at the time of return of
the Product to Company, in proportion to the percentage of Ten−Year Service Life remaining at the time of return of
the Product to Company. In calculating the available credit, the remaining portion of the Ten−Year Service Life will be
rounded up or down to the nearest whole year. The End−User will assume responsibility to pay the balance of the
list price; and Company reserves the right to require payment prior to delivery of the repaired or replacement
equipment.
For the avoidance of doubt, Company’s responsibilities under this Warranty are as follows:
Years 1−2
−
Product repaired or replaced pursuant to terms of Limited Warranty
Years 3−10 − Unit Credit ($) = Current List Price ×
Years of Unexpired Life
10 Years of Warranted Life
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
73
Download from Www.Somanuals.com. All Manuals Search And Download.
WARRANTY
WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages
caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than
the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect,
accident, abuse, misuse, misapplication, or incorrect installation; (d) repair or alteration not authorized in writing by
Company personnel or performed by an authorized Company Customer Service Engineer or Agent; (e) improper
testing, operation, maintenance, adjustment, or modification of any kind not authorized in writing by Company
personnel or performed by an authorized Company Customer Service Engineer or Agent; or (f) use of the Product
under other than normal operating conditions or in a manner inconsistent with the Product’s labels or instructions.
This Warranty is not valid: (a) unless the End−User returns to Company the Warranty Registration Card within
thirty (30) days of purchase; or (b) if the Product’s serial numbers have been removed or are illegible. Any
Warranted Items repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the
original Warranty subject to all the terms thereof.
Company shall not be responsible for any charges for testing, checking, removal or installation of Warranted Items.
COMPANY DOES NOT WARRANT EQUIPMENT NOT MANUFACTURED BY COMPANY. IF PERMITTED BY THE
APPLICABLE MANUFACTURER, COMPANY SHALL PASS THROUGH SUCH MANUFACTURER’S WARRANTIES TO
END−USER.
COMPANY DOES NOT WARRANT SOFTWARE, INCLUDING SOFTWARE EMBEDDED IN PRODUCTS, THAT IS NOT
CREATED BY COMPANY. WITHOUT LIMITING THE FOREGOING, COMPANY SPECIFICALLY DOES NOT WARRANT
SOFTWARE (SUCH AS LINUX) THAT WAS CREATED USING AN ꢀOPEN SOURCE" MODEL OR IS DISTRIBUTED
PURSUANT TO AN OPEN SOURCE LICENSE.
THIS WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY OFFERED BY COMPANY WITH RESPECT TO THE
PRODUCTS AND SERVICES AND, EXCEPT FOR SUCH FOREGOING WARRANTY COMPANY DISCLAIMS ALL OTHER
WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY, TITLE,
NON−INFRINGEMENT, AND FITNESS FOR A PARTICULAR PURPOSE. CORRECTION OF NON−CONFORMITIES IN
THE MANNER AND FOR THE PERIOD OF TIME PROVIDED ABOVE SHALL CONSTITUTE COMPANY’S SOLE
LIABILITY AND END−USER’S EXCLUSIVE REMEDY FOR FAILURE OF COMPANY TO MEET ITS WARRANTY
OBLIGATIONS, WHETHER CLAIMS OF THE END−USER ARE BASED IN CONTRACT, IN TORT (INCLUDING
NEGLIGENCE OR STRICT LIABILITY), OR OTHERWISE.
LIMITATION OF LIABILITY: The remedies of the End−User set forth herein are exclusive and are the sole remedies
for any failure of Company to comply with its obligations hereunder. In no event shall Company be liable in contract,
in tort (including negligence or strict liability) or otherwise for damage to property or equipment other than the
Products, including loss of profits or revenue, loss of use of Products, loss of data, cost of capital, claims of
customers of the End−User or any special, indirect, incidental or consequential damages whatsoever. The total
cumulative liability of Company hereunder whether the claims are based in contract (including indemnity), in tort
(including negligence or strict liability) or otherwise, shall not exceed the price of the Product on which such liability
is based.
Company shall not be responsible for failure to provide service or parts due to causes beyond Company’s
reasonable control.
END−USER’S OBLIGATIONS: In order to receive the benefits of this Warranty, the End−User must use the Product
in a normal way; follow the Product’s operation and maintenance manual; and protect against further damage to the
Product if there is a covered defect.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
74
Download from Www.Somanuals.com. All Manuals Search And Download.
WARRANTY
OTHER LIMITATIONS: Company’s obligations under this Warranty are expressly conditioned upon receipt by
Company of all payments due to it (including interest charges, if any). During such time as Company has not
received payment of any amount due to it for the Product, in accordance with the contract terms under which the
Product is sold, Company shall have no obligation under this Warranty. Also during such time, the period of this
Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any
overdue or unpaid amounts.
COSTS NOT RELATED TO WARRANTY: The End−User shall be invoiced for, and shall pay for, all services not
expressly provided for by the terms of this Warranty, including without limitation, site calls involving an inspection
that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials,
freight charges, travel expenses or labor of Company representatives outside the terms of this Warranty will be
borne by the End−User.
OBTAINING WARRANTY SERVICE: In the USA, call the Customer Reliability Center 7x24 at 800−356−5737. Outside
of the USA, contact your local Powerware product sales or service representative, or call the Customer Reliability
Center in the USA at 919−870−3149. Company will not accept any Product for return, credit or exchange unless
expressly authorized by Company in writing and delivered FOB Company factory. For comments or questions about
this Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina
27616 USA.
Load Protection Guarantee (US and Canada)
Powerware UPS Models 3105, 5110, 5115, 5125, 9120, 9125, 9135, 9140, 9150, 9155, 9170+, and FERRUPS
GUARANTOR: The Guarantor for the load protection guaranty set forth herein is Eaton Electrical Inc., a Delaware
Corporation company (ꢁCompany").
LIMITED GUARANTY: This load protection guaranty (this ꢁGuaranty") applies only to the original End−User (the
ꢁEnd−User") of any Powerware 3105, 5110, 5115, 5125, 9120, 9125, 9135, 9140, 9150, 9155, 9170+, and FERRUPS
Products (individually and collectively, the ꢁProduct") and cannot be transferred. This Guaranty applies even in the
event that the Product is initially sold by Company for resale to an End−User.
WHAT THIS GUARANTY COVERS: For the lifetime of the Product, Guarantor promises to repair or replace, at
Guarantor’s option, the equipment (valued up to the limits shown below*) that is damaged by an AC power line
surge, spike, or other transient when properly connected to Guarantor’s uninterruptible power system (ꢁUPS").
Reimbursement for or restoration of data loss excluded. This Guaranty applies only if all of the following
circumstances arise:
1. The UPS is plugged into properly grounded and wired outlets, using no extension cords, adapters, other ground
wires or other electrical connectors;
2. The installation of the UPS complies with all applicable electrical and safety codes described by the National
Electrical Code (NEC);
3. The UPS was used under normal operating conditions and in accordance with all labels and instructions; and
4. The UPS was not damaged by accident (other than AC power line transient), misuse, or abuse.
*Cumulative Limits to be paid by Guarantor under this Load Protection Guaranty:
S
S
S
$25,000 for Powerware UPS Model 3105
$150,000 for Powerware UPS Models 5110, 5115, and 5125
$250,000 for Powerware UPS Models 9120, 9125, 9135, 9140, 9150, 9155, 9170+, and FERRUPS products
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
75
Download from Www.Somanuals.com. All Manuals Search And Download.
WARRANTY
WHAT THIS GUARANTY DOES NOT COVER: Any reimbursement or repair to End−User’s equipment does not
include reimbursement for or restoration of any data loss. This Guaranty does not cover any defects or damages
caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than
the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect,
accident, abuse, misuse, misapplication, or incorrect installation of Product; (d) repair or alteration of Product not
authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or
Agent; (e) improper testing, operation, maintenance, adjustment, or modification of any kind to the Product not
authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or
Agent; or (f) use of the Product under other than normal operating conditions or in a manner inconsistent with the
Product’s labels or instructions.
This Guaranty is not valid: (a) unless the End−User returns to Company the Warranty Registration Card within
thirty (30) days of purchase; or (b) if the Product’s serial numbers have been removed or are illegible.
Company shall not be responsible for any charges for testing, checking, removal or installation of any items.
LIMITATION OF LIABILITY: THE REMEDIES OF THE END−USER SET FORTH HEREIN ARE EXCLUSIVE AND ARE THE SOLE
REMEDIES FOR ANY FAILURE OF COMPANY TO COMPLY WITH ITS OBLIGATIONS HEREUNDER. EXCEPT AS OTHERWISE
PROVIDED FOR IN THIS GUARANTY, IN NO EVENT SHALL COMPANY BE LIABLE IN CONTRACT, IN TORT (INCLUDING
NEGLIGENCE OR STRICT LIABILITY) OR OTHERWISE FOR DAMAGE TO PROPERTY OR EQUIPMENT OTHER THAN THE
PRODUCTS, INCLUDING LOSS OF PROFITS OR REVENUE, LOSS OF USE OF PRODUCTS, LOSS OF DATA, COST OF
CAPITAL, CLAIMS OF CUSTOMERS OF THE END−USER OR ANY SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL
DAMAGES WHATSOEVER. THE TOTAL CUMULATIVE LIABILITY OF COMPANY HEREUNDER WHETHER THE CLAIMS ARE
BASED IN CONTRACT (INCLUDING INDEMNITY), IN TORT (INCLUDING NEGLIGENCE OR STRICT LIABILITY) OR
OTHERWISE, SHALL NOT EXCEED THOSE SET FORTH ABOVE.
Company shall not be responsible for failure to provide repair or replacement under this Guaranty due to causes
beyond Company’s reasonable control.
END−USER’S OBLIGATIONS: In order to receive the benefits of this Guaranty, the End−User must use the Product in
a normal way; follow the Product’s operation and maintenance manual; and protect against further damage to the
Product if there is a covered defect.
OTHER LIMITATIONS: Company’s obligations under this Guaranty are expressly conditioned upon receipt by
Company of all payments due to it (including interest charges, if any). During such time as Company has not
received payment of any amount due to it for the Product, in accordance with the contract terms under which the
Product is sold, Company shall have no obligation under this Guaranty.
COSTS NOT RELATED TO GUARANTY: The End−User shall be invoiced for, and shall pay for, all services not
expressly provided for by the terms of this Guaranty, including without limitation, site calls involving an inspection
that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials,
freight charges, travel expenses or labor of Company representatives outside the terms of this Guaranty will be
borne by the End−User.
TO MAKE A CLAIM: In the USA, call the Customer Reliability Center 7x24 at 800−356−5737. Outside of the USA,
contact your local Powerware product sales or service representative, or call the Customer Reliability Center in the
USA at 919−870−3149. For comments or questions about this Load Protection Guaranty, write to the Customer
Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1
76