Powerware® 9135 Two−in−One UPS  
5000/6000 VA  
User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Class A EMC Statements  
FCC Part 15  
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to  
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference  
when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate  
radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful  
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful  
interference in which case the user will be required to correct the interference at his own expense.  
EN 62040−2  
Some configurations are classified under EN 62040−2 as ˆCategory C2 UPS.˜ For these configurations, the  
following applies:  
WARNING This is a category C2 UPS product. In a residential environment, this product may cause radio  
interference, in which case the user may be required to take additional measures.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Special Symbols  
The following are examples of symbols used on the UPS or accessories to alert you to important  
information:  
RISK OF ELECTRIC SHOCK − Observe the warning associated with the risk of electric shock  
symbol.  
CAUTION: REFER TO OPERATOR’S MANUAL − Refer to your operator’s manual for additional  
information, such as important operating and maintenance instructions.  
This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. This  
product contains sealed, lead-acid batteries and must be disposed of properly. For more information,  
contact your local recycling/reuse or hazardous waste center.  
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in  
the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
1
2
3
4
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
5
6
7
8
9
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 1  
Introduction  
®
The Powerware 9135 uninterruptible power system (UPS) protects  
your sensitive electronic equipment from the most common power  
problems including power failures, power sags, power surges,  
brownouts, line noise, high voltage spikes, frequency variations,  
switching transients, and harmonic distortion.  
Power outages can occur when you least expect it and power  
quality can be erratic. These power problems have the potential to  
corrupt critical data, destroy unsaved work sessions, and damage  
hardware ꢀ causing hours of lost productivity and expensive repairs.  
With the Powerware 9135, you can safely eliminate the effects of power  
the Powerware 9135 UPS.  
Figure 1. The Powerware 9135 UPS  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INTRODUCTION  
Providing outstanding performance and reliability, the Powerware 9135’s  
unique benefits include:  
S Online UPS design with pure sine wave output. The UPS filters and  
regulates incoming AC power and provides consistent power to your  
equipment without draining the battery.  
S Two−in−one form factor for using the UPS in a rack−mount  
configuration or as a standalone cabinet.  
S Hours of extended runtime with up to four EBMs per UPS.  
S Start-on-battery capability for powering up the UPS even if utility  
power is not available.  
S Hot-swappable power module and battery tray that simplify  
maintenance by allowing you to replace them safely without  
powering down the critical load.  
S Shutdown control through the remote power−off (RPO) port.  
S Two standard communication options with a USB port and an RS−232  
serial port.  
S Advanced power management for graceful shutdowns and power  
monitoring.  
S For EU modelsꢀsequential shutdown and load management through  
separate receptacle groups, called load segments (PowerShare).  
S Optional communication cards with enhanced communication  
capabilities for increased power protection and control.  
S Backed by worldwide agency approvals.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2  
Safety Warnings  
IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE INSTRUCTIONS  
This manual contains important instructions that you should follow during installation and  
maintenance of the UPS and batteries. Please read all instructions before operating the  
equipment and save this manual for future reference.  
DANGER  
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by  
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS  
inside the UPS.  
WARNING  
S
S
This UPS contains its own energy source (batteries). The UPS output may carry live  
voltage even when the UPS is not connected to an AC supply.  
For 208–240V models, the output receptacles may remain electrically live. If the input  
power source in your application is wired line−to−neutral (as in most European  
applications), the voltage to the output receptacles is 0V. With line−to−line input wiring,  
the voltage to the output receptacles is 110–120V (measured from line−to−ground or  
line−to−neutral, depending on the UPS wiring).  
S
S
Do not remove or unplug the input cord when the UPS is turned on. This removes the  
safety ground from the UPS and the equipment connected to the UPS.  
To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity  
controlled, indoor environment, free of conductive contaminants. Ambient temperature  
must not exceed 40°C (104°F). Do not operate near water or excessive humidity  
(95% maximum).  
S
To comply with international standards and wiring regulations, the sum of the leakage  
current of the UPS and the total equipment connected to the output of this UPS must not  
have an earth leakage current greater than 3.5 milliamperes.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SAFETY WARNINGS  
CAUTION  
S
S
Batteries can present a risk of electrical shock or burn from high short−circuit current.  
Observe proper precautions. Servicing should be performed by qualified service  
personnel knowledgeable of batteries and required precautions. Keep unauthorized  
personnel away from batteries.  
Proper disposal of batteries is required. Refer to your local codes for disposal  
requirements.  
S
Never dispose of batteries in a fire. Batteries may explode when exposed to flame.  
S
Replace batteries with the same number and type of batteries as originally installed in  
the UPS.  
Sikkerhedsanvisninger  
VIGTIGE SIKKERHEDSANVISNINGER  
GEM DISSE ANVISNINGER  
Denne manual indeholder vigtige instruktioner, som skal følges under installation og  
vedligeholdelse af UPS’en og batterierne. Læs venligst alle instruktioner inden betjening af  
udstyret og gem denne manual mhp. fremtidige opslag.  
FARE  
Denne UPS indeholder LIVSFARLIG HØJSPÆNDING. Alle reparationer og vedligeholdelse bør  
kun udføres af en AUTORISERET SERVICETEKNIKER. Ingen af UPS’ens indvendige dele kan  
repareres af brugeren.  
ADVARSEL!  
S
S
Denne UPS indeholder sin egen energikilde (batterier). Udgangsstikket på UPS’en kan  
endog være strømførende, når UPS’en ikke er koblet til en vekselstrømsforsyning.  
På 230V−modeller kan udgangsstikkene være strømførende. Hvis ledningsføringen til  
indgangsstrømkilden på din enhed er fase−til−neutral (som på de fleste europæiske  
enheder), er spændingen til udgangsstikkene 0V. Med en fase−til−fase  
indgangsledningsføring er spændingen til udgangsstikkene 115V (målt fra fase−til−jord  
eller fase−til−neutral, afhængig af UPS−ledningsføringen).  
S
S
Netledningen må ikke fjernes og stikket må ikke trækkes ud, mens UPS’en er tændt.  
Dette fjerner sikkerhedsjorden fra UPS’en og fra det udstyr, der er sat til.  
Installér denne UPS i et temperatur− og fugtighedskontrolleret indendørsmiljø, frit for  
ledende forureningsstoffer for at formindske risikoen for brand og elektrisk stød.  
Rumtemperaturen må ikke overstige 40°C. UPS’en bør ikke betjenes nær vand eller høj  
fugtighed (maksimalt 95%).  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY WARNINGS  
S
S
I overensstemmelse med internationale normer og bestemmelser for el−installation må  
det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke overskride en  
jordafdelingsspænding på mere end 3,5 milliampere.  
ADVARSEL  
Batterierne kan give risiko for elektrisk stød eller brandsår forårsaget af høj  
kortslutningsstrøm. Overhold gældende forsigtighedsregler. Servicering skal udføres af  
kvalificeret servicepersonale med kendskab til batterier og gældende forsigtighedsregler.  
Hold uautoriseret personale væk fra batterierne.  
S
S
S
Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for  
bortskaffelsesprocedurer.  
Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan eksplodere ved  
åben ild.  
Udskift batterierne med samme batterinummer og −type som de oprindeligt installerede i  
UPS’en.  
Belangrijke Veiligheidsinstructies  
BELANGRIJKE VEILIGHEIDSINSTRUCTIES  
BEWAAR DEZE INSTRUCTIES  
Deze handleiding bevat belangrijke instructies die u dient te volgen tijdens de installatie en  
het onderhoud van de UPS en de accu’s. Lees alle instructies voordat u de apparatuur in  
bedrijf neemt en bewaar deze handleiding als naslagwerk.  
GEVAAR  
Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING. Alle reparaties en  
onderhoud dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL te worden uitgevoerd.  
Er bevinden zich GEEN ONDERDELEN in de UPS die DOOR DE GEBRUIKER kunnen worden  
GEREPAREERD.  
WAARSCHUWING  
S
S
Deze UPS bevat een eigen energiebron (accu’s). De UPS−uitgang kan onder spanning  
staan, zelfs wanneer de UPS niet is aangesloten op de netspanning.  
Bij de modellen van 230V kan de uitgangscontactdoos onder spanning blijven staan. Als  
de bedrading van de ingangsspanningsbron in uw systeem loopt van fase naar aarde  
(zoals bij de meeste Europese systemen) dan bedraagt de spanning op de  
uitgangscontactdozen 0 V. Als de ingangsbedrading loopt van fase naar fase dan  
bedraagt de spanning op de uitgangscontactdozen 115V (gemeten tussen fase en aarde  
of tussen fase en neutraal, afhankelijk van de UPS−bedrading).  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY WARNINGS  
S
S
Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit terwijl de  
UPS aan staat. Hierdoor zou de UPS en uw aangesloten apparatuur geen  
aardebeveiliging meer hebben.  
Teneinde de kans op brand of elektrische schok te verminderen dient deze UPS in een  
gebouw met temperatuur- en vochtigheidregeling te worden geïnstalleerd, waar geen  
geleidende verontreinigingen aanwezig zijn. De omgevingstemperatuur mag 40°C niet  
overschrijden. Niet gebruiken in de buurt van water of bij zeer hoge vochtigheid  
(max. 95%).  
S
Om aan de internationale normen en bedradingsvoorschriften te voldoen mag de gehele  
apparatuur die op de uitgang van deze UPS is aangesloten, geen aardlekstroom van  
meer dan 3,5 milliampère hebben.  
OPGELET  
S
S
Batterijen leveren gevaar op voor elektrische schokken en kunnen brandwonden  
veroorzaken door een grote kortsluitstroom. Neem de juiste voorzorgsmaatregelen in  
acht. Het onderhoud moet worden uitgevoerd door bevoegde onderhoudsmonteurs die  
verstand hebben van accu’s en op de hoogte zijn van de vereiste voorzorgsmaatregelen.  
Houd onbevoegden uit de buurt van de accu’s.  
De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw  
plaatselijke voorschriften.  
S
Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen.  
S
Vervang de accu’s door accu’s met hetzelfde nummer en van hetzelfde type als de  
oorspronkelijke accu’s in de UPS.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY WARNINGS  
Tarkeita Turvaohjeita  
TÄRKEITÄ TURVAOHJEITA − SUOMI  
SÄILYTÄ NÄMÄ OHJEET  
Tämä käyttöohje sisältää tärkeitä ohjeita, joita on noudatettava UPS−virtalähteen ja akkujen  
asennuksen ja huollon yhteydessä. Lue kaikki ohjeet ennen laitteiston käyttöä ja säilytä ohje  
myöhempää tarvetta varten.  
VAARA  
Tämä UPS sisältää HENGENVAARALLISIA JÄNNITTEITÄ. Kaikki korjaukset ja huollot on  
jätettävä VAIN VALTUUTETUN HUOLTOHENKILÖN TOIMEKSI. UPS ei sisällä MITÄÄN  
KÄYTTÄJÄN HUOLLETTAVIA OSIA.  
VAROITUS  
S
S
Tässä UPS−virtalähteessä on oma energianlähde (akut). UPS−virtalähteen lähdössä voi  
olla jännite, vaikka UPS−virtalähdettä ei ole kytketty verkkovirtaan.  
230V −malleissa lähtövastakkeissa voi säilyä jännite. Jos sovelluksen tulovirtalähde on  
johdotettu linjasta neutraaliin (kuten useimmissa eurooppalaisissa sovelluksissa)  
lähtövastakkeiden jännite on 0 V. Linjasta linjaan –tulojohdotuksessa lähtövastakkeiden  
jännite on 115V (mitataan linjasta maahan tai linjasta neutraaliin, UPS−virtalähteen  
johdotuksesta riippuen).  
S
S
Älä poista tai irrota sisääntulojohtoa, kun UPS on kytkettynä. Tämä poistaa  
turvamaadoituksen UPS−laitteesta ja siihen liitetystä laitteistosta.  
Vähentääksesi tulipalon ja sähköiskun vaaraa asenna tämä UPS sisätiloihin,  
joissa lämpötila ja kosteus on säädettävissä ja joissa ei ole virtaa johtavia  
epäpuhtauksia. Ympäristön lämpötila ei saa ylittää 40 °C. Älä käytä lähellä vettä ja vältä  
kosteita tiloja (95 % maksimi).  
S
S
Kansainväliset normit ja johdotusmääräykset vaativat, että kaikkien tämän UPS−laitteen  
ulostulokytkentöjen yhteinen maavuotovirta ei ylitä 3,5 milliampeeria (mA).  
VARO  
Akut voivat aiheuttaa sähköiskun tai palovammojen vaaran johtuen suuresta  
oikosulkuvirrasta. Noudata kaikkia asianmukaisia varotoimia. Laitteen saa huoltaa vain  
ammattitaitoinen huoltohenkilökunta, joka tuntee akut ja niihin liittyvät varotoimet. Älä  
päästä valtuuttamatonta henkilöstöä lähelle akkuja.  
S
S
S
Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia määräyksiä.  
Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää.  
Vaihda UPS−virtalähteeseen vain samanlaiset akut ja sama määrä akkuja kuin siinä oli  
alun perin.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY WARNINGS  
Consignes de sécurité  
CONSIGNES DE SÉCURITÉ IMPORTANTES  
CONSERVER CES INSTRUCTIONS  
Ce manuel comporte des instructions importantes que vous êtes invité à suivre lors de toute  
procédure d’installation et de maintenance des batteries et de l’onduleur. Veuillez consulter  
entièrement ces instructions avant de faire fonctionner l’équipement et conserver ce manuel  
afin de pouvoir vous y reporter ultérieurement.  
DANGER!  
Cet onduleur contient des TENSIONS MORTELLES. Toute opération d’entretien et de  
réparation doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ.  
AUCUNE PIÈCE RÉPARABLE PAR L’UTILISATEUR ne se trouve dans l’onduleur.  
AVERTISSEMENT!  
S
S
Cette onduleur possède sa propre source d’alimentation (batteries). Il est possible que la  
sortie de l’onduleur soit sous tension même lorsque l’onduleur n’est pas connectée à une  
alimentation CA.  
En ce qui concerne les modèles 230 V, il est possible que les prises de sortie restent  
sous tension. Si la source d’alimentation de votre application est câblée phase et neutre  
(comme dans la majorité des applications européennes), la tension vers les prises de  
sortie est de 0 V. Avec un câblage d’entrée phase à phase, la tension vers les prises de  
sortie est de 115 V (mesurée entre phase et terre ou phase et neutre suivant le câblage  
de l’onduleur).  
S
S
Ne pas retirer le cordon d’alimentation lorsque l’onduleur est sous tension sous peine de  
supprimer la mise à la terre de l’onduleur et du matériel connecté.  
Pour réduire les risques d’incendie et de décharge électrique, installer l’onduleur  
uniquement à l’intérieur, dans un lieu dépourvu de matériaux conducteurs, où la  
température et l’humidité ambiantes sont contrôlées. La température ambiante ne doit  
pas dépasser 40 °C. Ne pas utiliser à proximité d’eau ou dans une atmosphère  
excessivement humide (95 % maximum).  
S
Afin d’être conforme aux normes et règlements internationaux de câblage, le courant de  
fuite à la terre de la totalité du matériel branché sur la sortie de l’onduleur ne doit pas  
dépasser 3,5 mA.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY WARNINGS  
ATTENTION!  
S
Les batteries peuvent présenter un risque de choc électrique ou de brûlure provenant  
d’un courant de court−circuit haute intensité. Observez les précautions appropriées.  
L’entretien doit être réalisé par du personnel qualifié connaissant bien les batteries et  
les précautions nécessaires. N’autorisez aucun personnel non qualifié à manipuler les  
batteries.  
S
S
S
Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements  
en vigueur dans votre localité.  
Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les faire  
exploser.  
Remplacez les batteries par des batteries du même type et numéro que celles installées  
à l’origine sur l’onduleur.  
Sicherheitswarnungen  
WICHTIGE SICHERHEITSANWEISUNGEN  
AUFBEWAREN  
Dieses Handbuch enthält wichtige Anweisungen, die Sie während der Installation und  
Wartung des USV (Unterbrechungsfreies Stromversorgungssystem) und der Batterien  
befolgen müssen. Bitte lesen Sie alle Anweisungen des Handbuches bevor sie mit dem  
Gerät arbeiten. Bewaren Sie das Handbuch zum Nachlesen auf.  
WARNUNG  
Die USV führt lebensgefährliche Spannungen. Alle Reparatur− und Wartungsarbeiten sollten  
nur von Kundendienstfachleuten durchgeführt werden. Die USV enthält keine vom Benutzer  
zu wartenden Komponenten.  
ACHTUNG  
S
S
Dieses USV (Unterbrechungsfreies Stromversorgungssystem) enthält eine eigene  
Energiequelle (Batterien). Der USV−Ausgang kann Spannung führen, auch wenn das USV  
nicht an eine Wechselstromquelle angeschlossen ist.  
Bei Modellen mit 208–240 Volt können die Ausgangssteckverbinder stromführend  
bleiben. Wenn die Eingangsstromquelle in Ihrer Anlage mit Masseleitung verkabelt ist  
(wie in den meisten europäischen Anlagen), beträgt die Spannung an den  
Ausgangssteckverbindern 0 Volt. Bei einer Verkabelung mit Außenleitern beträgt die  
Spannung an den Ausgangssteckverbindern 110–120 Volt (gemessen von Leitung zu  
Masse oder Leitung zu Masseleiter, abhängig von der UPS (USV)−Verkabelung.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY WARNINGS  
S
S
Das Eingangskabel nicht entfernen oder abziehen, während die USV eingeschaltet ist,  
weil hierdurch die Sicherheitserdung von der USV und den daran angeschlossenen  
Geräten entfernt wird.  
Um die Brand- oder Elektroschockgefahr zu verringern, diese USV nur in Gebäuden mit  
kontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine leitenden  
Schmutzstoffen vorhanden sind. Die Umgebungstemperatur darf 40°C nicht übersteigen.  
Die USV nicht in der Nähe von Wasser oder in extrem hoher Luftfeuchtigkeit (max. 95 %)  
betreiben.  
S
Um internationale Normen und Verdrahtungsvorschriften zu erfüllen, dürfen die an den  
Ausgang dieser USV angeschlossenen Geräte zusammen einen Erdableitstrom von  
insgesamt 3,5 Milliampere nicht überschreiten.  
VORSICHT!  
S
S
Batterien können das Risiko eines elektrischen Schlags bergen oder durch hohen  
Kurzschlussstrom in Brand geraten. Die richtigen Vorsichtsmaßnahmen beachten. Die  
Wartung muss von qualifiziertem Wartungspersonal durchgeführt werden, das im  
Umgang mit Batterien geübt ist und über gute Kenntnisse der erforderlichen  
Vorsichtsmaßnahmen verfügt. Nicht autorisiertes Personal von Batterien fern halten.  
Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die örtlichen  
Bestimmungen zu beachten.  
S
Batterien niemals verbrennen, da sie explodieren können.  
S
Falls Sie die Batterien austauschen, verwenden Sie bitte ausschließlich die gleiche  
Anzahl und die Batterietypen.  
Avvisi di sicurezza  
IMPORTANTI ISTRUZIONI DI SICUREZZA  
CONSERVARE QUESTE ISTRUZIONI  
Il presente manuale contiene importanti istruzioni da seguire durante l’installazione e la  
manutenzione dell’UPS e delle batterie. Leggere integralmente le istruzioni prima di  
utilizzare l’apparecchiatura e conservare il presente manuale per futuro riferimento.  
PERICOLO  
La TENSIONE contenuta in questo gruppo statico di continuità è LETALE. Tutte le operazioni  
di riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DA  
PERSONALE TECNICO AUTORIZZATO. All’interno del gruppo statico di continuità NON vi  
sono PARTI RIPARABILI DALL’UTENTE.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY WARNINGS  
AVVERTENZA  
S
S
L’UPS contiene la propria fonte di energia (batterie). Le prese d’uscita dell’UPS possono  
essere sotto tensione anche quando l’UPS non è collegato all’alimentazione elettrica CA.  
Nei modelli da 230 V è possibile che le prese d’uscita rimangano sotto tensione. Se la  
fonte di alimentazione in entrata dell’installazione è costituita da un collegamento  
linea−neutro (come accade nella maggior parte delle installazioni europee), la tensione  
delle prese d’uscita è pari a 0 V. Con un cablaggio in entrata del tipo linea−linea, la  
tensione sulle prese d’uscita è 115 V (con misurazione effettuata da linea a terra o da  
linea a neutro in base al cablaggio dell’UPS).  
S
S
Non rimuovere nè scollegare il cavo di ingresso quando il gruppo statico di continuità è  
acceso poichè in tal modo si disattiverebbe il collegamento a terra di sicurezza del  
gruppo statico di continuità e dell’apparecchiatura ad esso collegata.  
Per ridurre il rischio di incendio o di scossa elettrica, installare il gruppo statico di  
continuità in un ambiente interno a temperatura ed umidità controllata, privo di agenti  
contaminanti conduttivi. La temperatura ambiente non deve superare i 40°C. Non  
utilizzare l’unità in prossimità di acqua o in presenza di umidità eccessiva (95% max).  
S
S
Per conformità con gli standard internazionali e con le norme in merito al cablaggio, tutta  
l’apparecchiatura collegata con l’uscita del gruppo statico di continuità non deve avere  
una corrente di dispersione di terra superiore a 3,5 milliampere.  
ATTENZIONE  
Le batterie possono comportare un rischio di scossa elettrica o di ustione in seguito a  
un’elevata corrente di corto circuito. Osservare le dovute precauzioni. L’assistenza deve  
essere eseguita da personale qualificato esperto di batterie e delle necessarie  
precauzioni. Tenere il personale non autorizzato lontano dalle batterie.  
S
S
S
Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento fare  
riferimento alle disposizioni locali.  
Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle  
fiamme.  
Sostituire le batterie con altre dello stesso numero e tipo di quelle originariamente  
installate nell’UPS.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY WARNINGS  
Viktig Sikkerhetsinformasion  
VIKTIGE SIKKERHETSINSTRUKSJONER  
GJEM DISSE INSTRUKSJONENE  
Denne håndboken inneholder viktige instruksjoner som du bør overholde ved montering og  
vedlikehold av UPS−enheten og batteriene. Les alle instruksjoner før utstyret tas i bruk, og  
gjem håndboken til fremtidig referanse.  
FARLIG  
Denne UPS’en inneholder LIVSFARLIGE SPENNINGER. All reparasjon og service må kun  
utføres av AUTORISERT SERVICEPERSONALE. BRUKERE KAN IKKE UTFØRE SERVICE PÅ  
NOEN AV DELENE i UPS’en.  
FARLIG  
S
S
UPS−enheten inneholder sin egen energikilde (batterier). UPS−utgangen kan være  
strømførende selv når UPS−enheten ikke er koblet til et strømuttak.  
Utgangsstikkene kan være strømførende for 230V modellene. Spenningen til  
utgangsstikkene vil være 0 V dersom din enhets strømkilde er fase−til−nøytral (som på de  
fleste europeiske enheter). Med ledningsført fase−til−fase inngang vil spenningen til  
utgangsstikkene være 115V (målt fra fase−til−jord eller fase−til−nøytral, avhenging av  
UPS−ledningsføringen).  
S
S
S
For å redusere fare for brann eller elektriske støt, bør denne UPS’en installeres i et  
innendørs miljø med kontrollert temperatur og luftfuktighet som er fritt for ledende,  
forurensende stoffer. Romtemperaturen må ikke overskride 40°C. Den må ikke brukes i  
nærheten av vann eller ved meget høy luftfuktighet (95% maks.).  
For å redusere fare for brann eller elektriske støt, bør denne UPS’en installeres i et  
innendørs miljø med kontrollert temperatur og luftfuktighet som er fritt for ledende,  
forurensende stoffer. Romtemperaturen må ikke overskride 40°C. Den må ikke brukes i  
nærheten av vann eller ved meget høy luftfuktighet (95% maks.).  
Alt utstyr som er forbundet med utgangen av denne UPS’en må ikke ha en sterkere total  
lekkasjestrøm enn 3,5 milliampere for å være i overensstemmelse med internasjonale  
standarder og forkablingsbestemmelser.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY WARNINGS  
FORSIKTIG  
S
S
Batterier kan utgjøre en fare for elektrisk støt eller brannsår pga. høy kortsluttingsstrøm.  
Treff passende forholdsregler. Service bør utføres av kvalifisert servicepersonale med  
kjennskap til batterier og nødvendige forholdsregler. Hold uautorisert personale borte fra  
batteriene.  
Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om fjerning av  
batterier.  
S
Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes for åpen ild.  
Skift ut originalbatteriene i UPS−enheten med samme antall og type.  
S
Regulamentos de Segurança  
INSTRUÇÕES DE SEGURANÇA IMPORTANTES  
GUARDE ESTAS INSTRUÇÕES  
Este manual contém instruções importantes que devem ser seguidas durante a instalação e  
manutenção do no−break e das baterias. Leia todas as instruções antes de operar o  
equipamento e guarde este manual para consultá−lo futuramente.  
CUIDADO  
A UPS contém VOLTAGEM MORTAL. Todos os reparos e assistência técnica devem ser  
executados SOMENTE POR PESSOAL DA ASSISTÊNCIA TÉCNICA AUTORIZADO. Não há  
nenhuma PEÇA QUE POSSA SER REPARADA PELO USUÁRIO dentro da UPS.  
ADVERTÊNCIA  
S
S
Este no−break possui sua própria fonte de energia (baterias). A saída do no−break pode  
estar energizada mesmo que este não esteja conectado a uma fonte de energia elétrica.  
Nos modelos 230V, pode ser que as tomadas de saída permaneçam energizadas. Se a  
alimentação da sua aplicação for do tipo fase−neutro (como ocorre na maioria das  
aplicações na Europa), a tensão das tomadas de saída é de 0 V. Com a alimentação  
fase−fase, a tensão das tomadas de saída é de 115V (medida como fase−terra ou  
fase−neutro, dependendo da instalação elétrica do no−break).  
S
Não remova ou desconecte o cabo de entrada quando a UPS estiver ligada. Isto  
removerá o aterramento de segurança da UPS e do equipamento conectado.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY WARNINGS  
S
S
Para reduzir o risco de incêndios ou choques elétricos, instale a UPS em ambiente  
interno com temperatura e umidade controladas e livres de contaminadores condutíveis.  
A temperatura ambiente não deve exceder 40°C. Não opere próximo a água ou em  
umidade excessiva (máx: 95%).  
Para estar de acordo com os padrões internacionais e os regulamentos de fiação, o  
equipamento total conectado à saída desta UPS não deve ter uma corrente de fuga à  
terra maior que 3,5 miliampères.  
PERIGO  
S
S
As baterias podem oferecer risco de choque elétrico ou queimadura, ocasionados por  
alta tensão com possibilidade de curto−circuito. Tome as precauções adequadas. A  
manutenção deve ser realizada por pessoal qualificado, com conhecimento sobre  
baterias e ciente das precauções exigidas. Mantenha o pessoal não autorizado afastado  
das baterias.  
Siga as instruções apropriadas ao desfazer-se das baterias. Consulte os códigos do local  
para maiores informações sobre os regulamentos de descarte de produtos.  
S
Nunca jogue as baterias no fogo, porque há risco de explosão.  
S
Ao realizar a troca das baterias, utilize a mesma quantidade e o mesmo tipo de bateria  
instalada originalmente no no−break.  
Ïðåäóïðåæäåíèÿ ïî ìåðàì áåçîïàñíîñòè  
ÂÀÆÍÛÅ ÓÊÀÇÀÍÈß ÏÎ ÌÅÐÀÌ ÁÅÇÎÏÀÑÍÎÑÒÈ  
ÑÎÕÐÀÍÈÒÅ ÝÒÈ ÓÊÀÇÀÍÈß  
 äàííîì ðóêîâîäñòâå ñîäåðæàòñÿ âàæíûå èíñòðóêöèè ïî óñòàíîâêå è  
îáñëóæèâàíèþ èñòî÷íèêà áåñïåðåáîéíîãî ïèòàíèÿ (ÈÁÏ) è áàòàðåé. Ïåðåä  
ðàáîòîé ñ îáîðóäîâàíèåì ïðî÷òèòå âñå èíñòðóêöèè. Ñîõðàíèòå äàííîå  
ðóêîâîäñòâî äëÿ äàëüíåéøåãî èñïîëüçîâàíèÿ.  
ÎÏÀÑÍÎ  
 äàííîì ÈÁÏ èìåþòñÿ ÑÌÅÐÒÅËÜÍÎ ÎÏÀÑÍÛÅ ÍÀÏÐßÆÅÍÈß. Âñå  
ðàáîòû ïî ðåìîíòó è îáñëóæèâàíèþ äîëæíû âûïîëíÿòüñÿ ÒÎËÜÊÎ  
ÓÏÎËÍÎÌÎ×ÅÍÍÛÌ ÎÁÑËÓÆÈÂÀÞÙÈÌ ÏÅÐÑÎÍÀËÎÌ. Âíóòðè  
ÈÁÏ íåò óçëîâ, ÎÁÑËÓÆÈÂÀÅÌÛÕ ÏÎËÜÇÎÂÀÒÅËÅÌ.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY WARNINGS  
ÏÐÅÄÓÏÐÅÆÄÅÍÈÅ  
S
S
 äàííîì ÈÁÏ óñòàíîâëåíû ñîáñòâåííûå èñòî÷íèêè ýíåðãèè (áàòàðåè).   
ÈÁÏ ìîæåò èìåòüñÿ íàïðÿæåíèå äàæå â òîì ñëó÷àå, åñëè îí íå ïîäêëþ÷åí  
ê ñåòè ïåðåìåííîãî òîêà.  
Íà âûõîäíûõ ðîçåòêàõ ìîäåëåé ñ íàïðÿæåíèåì 230 Â ìîæåò áûòü  
íàïðÿæåíèå. Åñëè óñòðîéñòâî ðàññ÷èòàíî íà òèï ïîäêëþ÷åíèÿ  
ꢀôàçà−íåéòðàëü" (êàê áîëüøèíñòâî óñòðîéñòâ, èçãîòàâëèâàåìûõ â Åâðîïå),  
íàïðÿæåíèå íà âûõîäíûõ ðîçåòêàõ ðàâíî 0 Â. Ïðè òèïå ïîäêëþ÷åíèÿ  
ꢀôàçà−ôàçà" íàïðÿæåíèå íà âûõîäíûõ ðîçåòêàõ ñîñòàâëÿåò 115 Â (ïðè  
èçìåðåíèè ꢀôàçà−çåìëÿ" èëè ꢀôàçà−íåéòðàëü", â çàâèñèìîñòè îò  
ýëåêòðè÷åñêîé ñõåìû ÈÁÏ).  
S
S
Íå îòñîåäèíÿéòå ñåòåâîé øíóð è íå èçâëåêàéòå åãî âèëêó èç ðîçåòêè ïðè  
âêëþ÷åííîì ÈÁÏ. Ïðè ýòîì çàùèòíîå çàçåìëåíèå îòêëþ÷àåòñÿ îò ÈÁÏ è  
îò îáîðóäîâàíèÿ, ïîäêëþ÷åííîãî ê ÈÏÁ.  
Äëÿ ñíèæåíèÿ îïàñíîñòè ïîæàðà èëè ïîðàæåíèÿ ýëåêòðè÷åñêèì òîêîì  
óñòàíàâëèâàéòå ÈÁÏ â çàêðûòîì ïîìåùåíèè ñ êîíòðîëèðóåìûìè  
òåìïåðàòóðîé è âëàæíîñòüþ, â êîòîðîì îòñóòñòâóþò ïðîâîäÿùèå  
çàãðÿçíÿþùèå âåùåñòâà. Òåìïåðàòóðà îêðóæàþùåãî âîçäóõà íå äîëæíà  
ïðåâûøàòü 40°Ñ. Íå ýêñïëóàòèðóéòå óñòðîéñòâî îêîëî âîäû èëè â ìåñòàõ ñ  
ïîâûøåííîé âëàæíîñòüþ (ìàêñ. 95%).  
S
Äëÿ îáåñïå÷åíèÿ ñîáëþäåíèÿ òðåáîâàíèé ìåæäóíàðîäíûõ ñòàíäàðòîâ è  
òðåáîâàíèé ê ðàçâîäêå ýëåêòðè÷åñêèõ öåïåé, ñóììàðíàÿ âåëè÷èíà òîêà  
óòå÷êè íà çåìëþ âñåãî îáîðóäîâàíèÿ, ïîäêëþ÷åííîãî ê âûõîäó ÈÁÏ, íå  
äîëæíà ïðåâûøàòü 3,5 ìèëëèàìïåðà.  
ÎÑÒÎÐÎÆÍÎ  
S
S
Âûñîêîå íàïðÿæåíèå, âûçâàííîå êîðîòêèì çàìûêàíèåì â áàòàðåå, ìîæåò  
ïðèâåñòè ê ïîðàæåíèþ ýëåêòðè÷åñêèì òîêîì èëè îæîãó. Ñîáëþäàéòå  
ìåðû ïðåäîñòîðîæíîñòè. Òåõíè÷åñêîå îáñëóæèâàíèå äîëæíî  
îñóùåñòâëÿòüñÿ êâàëèôèöèðîâàííûì ïåðñîíàëîì ïî ðàáîòå ñ  
èñòî÷íèêàìè ïèòàíèÿ, çíàêîìûì ñ ìåðàìè ïðåäîñòîðîæíîñòè. Íå  
äîïóñêàéòå ê ðàáîòå ñ áàòàðåÿìè ïîñòîðîííèõ.  
Íåîáõîäèìî ñîáëþäàòü ïðàâèëà óòèëèçàöèè àêêóìóëÿòîðîâ. Îáðàòèòåñü ê  
ìåñòíûì íîðìàòèâíûì àêòàì çà èíôîðìàöèåé î òðåáîâàíèÿõ ê  
óòèëèçàöèè.  
S
S
Íèêîãäà íå áðîñàéòå àêêóìóëÿòîðû â îãîíü. Àêêóìóëÿòîðû ìîãóò  
âçîðâàòüñÿ ïîä âîçäåéñòâèåì îãíÿ.  
Çàìåíÿéòå áàòàðåè ÈÁÏ òîëüêî òàêèì æå êîëè÷åñòâîì áàòàðåé  
àíàëîãè÷íîãî òèïà.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY WARNINGS  
Advertencias de Seguridad  
INSTRUCCIONES DE SEGURIDAD IMPORTANTES  
GUARDE ESTAS INSTRUCCIONES  
Este manual contiene instrucciones importantes que debe seguir durante la instalación y el  
mantenimiento del SIE y de las baterías. Por favor, lea todas las instrucciones antes de  
poner en funcionamiento el equipo y guarde este manual para referencia en el futuro.  
PELIGRO  
Este SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio técnico deben  
ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO TÉCNICO AUTORIZADO. No hay  
NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro del SIE.  
ADVERTENCIA  
S
S
Este SIE contiene su propia fuente de energía (baterías). La salida del SIE puede  
transportar voltaje activo aun cuando el SIE no esté conectado con una fuente de CA.  
Para los modelos 230V, es posible que los receptáculos de salida permanezcan  
eléctricamente activos. Si la fuente de energía de entrada de su aplicación está  
cableada de línea a neutro (como la mayoría de las aplicaciones europeas), el voltaje a  
los receptáculos de salida es 0V. Con cableado de entrada de línea a línea, el voltaje  
hacia los receptáculos de salida es 115V (medido de línea a tierra o de línea a neutro, lo  
que dependerá del cableado del SIE).  
S
S
No retire o desenchufe el cable de entrada mientras el SIE se encuentre encendido. Esto  
suprime la descarga a tierra de seguridad del SIE y de los equipos conectados al SIE.  
Para reducir el riesgo de incendio o de choque eléctrico, instale este SIE en un lugar  
cubierto, con temperatura y humedad controladas, libre de contaminantes conductores.  
La temperatura ambiente no debe exceder los 40°C. No trabaje cerca del agua o con  
humedad excesiva (95% máximo).  
S
Para cumplir con los estándares internacionales y las normas de instalación, la totalidad  
de los equipos conectados a la salida de este SIE no debe tener una intensidad de  
pérdida a tierra superior a los 3,5 miliamperios.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY WARNINGS  
PRECAUCIÓN  
S
Las baterías pueden constituir un riesgo de descarga eléctrica o quemaduras por  
corriente alta de corto circuito. Adopte las precauciones debidas. Personal calificado de  
servicio que conozca de baterías y esté al tanto de las precauciones requeridas debe  
darle servicio al equipo. Mantenga al personal no autorizado alejado de las baterías.  
S
S
S
Es necesario desechar las baterías de un modo adecuado. Consulte las normas locales  
para conocer los requisitos pertinentes.  
Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se las expone a  
la llama.  
Reemplace las baterías con el mismo número y tipo de baterías como se instalaron  
originalmente en el SAI.  
Säkerhetsföreskrifter  
VIKTIGA SÄKERHETSFÖRESKRIFTER  
SPARA DESSA FÖRESKRIFTER  
Den här anvisningen innehåller viktiga instruktioner som du ska följa under installation och  
underhåll av UPS−enheten och batterierna. Läs alla instruktioner innan du använder  
utrustningen och spara den här anvisningen för framtida referens.  
FARA  
Denna UPS−enhet innehåller LIVSFARLIG SPÄNNING. ENDAST AUKTORISERAD  
SERVICEPERSONAL får utföra reparationer eller service. Det finns inga delar som  
ANVÄNDAREN KAN UTFÖRA SERVICE PÅ inuti UPS−enheten.  
VARNING  
S
S
Den här UPS−enheten innehåller sin egen energikälla (batterier). UPS−enhetens uttag kan  
vara spänningsförande även då UPS−enheten inte är ansluten till spänningsnätet.  
På modellerna 230 V kan de utgående uttagen fortfarande vara strömförande. Om den  
ingående strömkällan i din applikation är kopplad ledare−till−nolla (det vanligaste i  
Europa) är spänningen till de utgående uttagen 0 V. Är den ingående strömkällan kopplad  
ledare−till−ledare är spänningen i de utgående uttagen 115 V (uppmätt från  
ledare−till−jord eller ledare−till−nolla beroende på UPS:ens anslutning).  
S
Ta aldrig bort nätsladden när UPS−enheten är påslagen. Detta tar bort skyddsjordningen  
från både UPS−enheten och den anslutna utrustningen.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY WARNINGS  
S
S
Minska risken för brand eller elektriska stötar genom att installera denna UPS−enhet  
inomhus, där temperatur och luftfuktighet är kontrollerade och där inga ledande  
föroreningar förekommer. Omgivande temperatur får ej överstiga 40°C. Använd inte  
utrustningen nära vatten eller vid hög luftfuktighet (max 95 %).  
För att överensstämma med internationell standard och installationsföreskrifter får inte  
den totala utrustning som anslutits till uttagen på denna UPS−enhet ha läcksström som  
överstiger 3,5 milliampere.  
VIKTIGT  
S
Batterierna kan innebära en risk för elektrisk stöt eller brännskada från kortsluten  
starkström. Iakttag lämpliga försiktighetsåtgärder. Service ska utföras av utbildad  
servicepersonal med kunskap om batterierna och nödvändiga försiktighetsåtgärder. Håll  
ej behörig personal borta från batterierna.  
S
S
S
Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning.  
Använda batterier får aldrig brännas upp. De kan explodera.  
Byt ut batterierna mot samma antal och typer av batterier som ursprungligen installerats  
i UPS−enheten.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3  
Installation  
This section explains:  
S Equipment inspection  
S UPS internal battery connection  
S UPS setup and installation, including Extended Battery Modules  
(EBMs)  
S Remote power−off (RPO) installation  
S UPS rear panels  
Inspecting the Equipment  
If any equipment has been damaged during shipment, keep the shipping  
cartons and packing materials for the carrier or place of purchase and file  
a claim for shipping damage. If you discover damage after acceptance,  
file a claim for concealed damage.  
To file a claim for shipping damage or concealed damage: 1) File with  
the carrier within 15 days of receipt of the equipment; 2) Send a copy of  
the damage claim within 15 days to your service representative.  
NOTE Check the battery recharge date on the shipping carton label. If the date has expired  
and the batteries were never recharged, do not use the UPS. Contact your service  
representative.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
Checking the Accessory Kit  
NOTE Packaging must be destroyed according to waste management standards. Recycling  
icons are displayed for easy selection.  
Verify that the following additional items are included with the UPS:  
Table 1. UPS Accessory Kit  
Item  
Description  
UPS user’s guide or CD  
Screwdriver  
RS−232 serial cable  
Rackmounting kit for 19−inch (48 cm) bays  
Two sets of pedestals with screws for tower position  
Optional.  
Network Management Card  
EU models only.  
Four cord−retention brackets  
EU models only.  
Four, 10A equipment power cords  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
If you ordered an optional EBM, verify that the following items are  
included with the EBM:  
Table 2. EBM Accessory Items  
Item  
Description  
EBM user’s guide  
EBM cable  
EBM communication cable  
Rackmounting kit for 19−inch (48 cm) bays  
Pedestal extenders for tower position  
Joining bracket and screws for tower position  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
Connecting the UPS Internal Battery  
To ensure proper battery operation:  
1. Verify that the UPS is off and unplugged.  
Two  
Screws  
Battery Switch  
Figure 2. Removing the Battery Switch Screws  
3. Slide the battery connector so that you can read Connected (see  
5. Continue to the following section, ꢁUPS Setup."  
Figure 3. Connecting the Internal Battery Connector  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
UPS Setup  
The Powerware 9135 UPS is designed for flexible configurations and can  
be installed in a rack or as a standalone cabinet.  
If you are installing the UPS in a rack, continue to the following section,  
Rackmount Setup  
The rail kit can be mounted in 19-inch panel (48 cm) racks from 24 to  
30 inches (61 to 76 cm) deep and includes:  
S Left and right sliding rail assemblies  
®
S (20) M4 6 mm Phillips flat−head screws  
S (4) M4 10 mm Phillips round−head screws  
S (4) M6 12 mm Phillips round−head screws  
S (8) M6 12 mm Phillips flat−head screws  
S (2) mounting brackets  
S (2) rear hold−down brackets  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
Installing the Rail Kit  
CAUTION  
S
S
DO NOT install the UPS or EBM in a hermetically−closed environment without any  
exchange of air.  
battery tray from the UPS before lifting. 2) A minimum of two people are required to lift  
the cabinets into the rack.  
NOTE The rails and the necessary mounting hardware are supplied by Eaton.  
To install the rail kit:  
1. Adjust the UPS control panel orientation by slightly pulling out the  
control panel and rotating it 90° counterclockwise (see Figure 4).  
Figure 4. Adjusting the UPS Control Panel Orientation  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
S Remove the UPS front cover (six screws).  
NOTE A ribbon cable connects the control panel to the UPS. Do not pull on the cable or  
disconnect it.  
S Place the front panel above the UPS.  
S Remove the two battery retaining brackets (four screws).  
S Slightly pull the battery tray, then lift it to extract it.  
Figure 5. Removing the Battery Tray  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
3. Place the Powerware cabinet on a flat, stable surface with the front  
of the cabinet facing you.  
NOTE You can adjust the position of the mounting brackets.  
4. Align the mounting brackets with the screw holes on the side of the  
cabinet and secure with the supplied M4 6 mm flat−head screws.  
cabinet.  
Figure 6. Installing the Mounting Brackets  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
6. Loosen the assembly wing nuts on both rail assemblies and adjust  
7. Select the proper holes in the rail for positioning the UPS in the  
desired location in the rack.  
8. Using two M6 12 mm flat−head screws, attach the rail to the rear  
of the rack.  
9. Secure the rail to the front of the rack with two M6 12 mm  
screws.  
Figure 7. Installing the Rails  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
11. Optional. Install the rear hold−down brackets (included with the rail  
kit) if you need to move the rack enclosure with the UPS already  
Figure 8. Installing the Rear Hold−Down Brackets  
12. Slide the UPS and any optional EBMs into the rack.  
13. Secure the front of the cabinet to the rack using two M6 12 mm  
Figure 9. Installing the Cabinets  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
14. Optional. If you installed the rear hold−down brackets, secure the  
brackets to the rear rails using two screws for each bracket (see  
Figure 10. Securing the Rear Hold−Down Brackets  
tray and secure with the battery retaining brackets.  
Replace the UPS front cover.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
Tower Setup  
CAUTION  
S
S
DO NOT install the UPS or EBM in a hermetically−closed environment without any  
exchange of air.  
the cabinets into the pedestals.  
The setup varies depending on the number of cabinets you are installing:  
Figure 11. Assembling the UPS Pedestals  
For two or more cabinets, the pedestal extenders and the joining  
NOTE Always keep 150 mm free space behind the UPS rear panel. The distance between  
the tower stands should be 450 mm.  
3. Carefully position the cabinet upright with the UPS indicators at the  
4. Adjust the pedestals to the size of the UPS and secure the  
pedestals with the captive screws.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
UPS Indicators  
150 mm  
(6")  
450 mm  
(17.7")  
Figure 12. Tower Position with One Cabinet  
5. Continue to the following section, ꢁInstalling the UPS."  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
6. Install pedestal extenders for each additional cabinet:  
For two cabinets, insert the extender into position 3 on the pedestal  
For three cabinets or more, insert the extender into position 4 on  
4
3
2
1
4
3
2
1
Figure 13. Extending the Pedestals for Two Cabinets  
4
3
2
1
4
3
2
1
4
3
2
1
Figure 14. Extending the Pedestals for Three or More Cabinets  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
7. Carefully position the cabinet upright with the UPS indicators at the  
8. Adjust the pedestals to the size of the UPS and secure the  
pedestals with the captive screws.  
Figure 15. Tower Position with Two Cabinets  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
9. Align each joining bracket with the adjacent cabinet screw holes  
NOTE Joining brackets are required for installations with two or more cabinets.  
Joining Bracket  
Figure 16. Installing the Joining Brackets  
11. Continue to the following section, ꢁInstalling the UPS."  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
Installing the UPS  
NOTE Do not make unauthorized changes to the UPS or accessories; otherwise, damage  
may occur to your equipment and void your warranty.  
To install the UPS and optional EBMs:  
2. Verify that the EBM battery circuit breaker is OFF.  
3. Plug the EBM cable into the battery connector. Plug the EBM  
Up to four EBMs may be connected to the UPS.  
EBM Cable  
EBM  
Communication  
Cable  
Battery Circuit  
Breaker  
EBM Battery  
Connectors  
Figure 17. UPS Installation with Three EBMs  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
4. If you plan to install power management software, connect your  
computer to the USB port or RS−232 communication port. For  
RS−232, use only the serial cable supplied in the accessory kit. For  
SWITCHED  
GROUP  
1
RS−232 Communication Cable  
RS−232 Communication Port  
RS232  
CONTACTS  
BATT. NORP.  
O
Figure 18. Installing the RS−232 Serial Cable  
5. If you are installing a remote power−off (RPO) switch, see the  
following section, ꢁRPO Installation," to install the switch before  
powering on the UPS.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
RPO Installation  
Installation of the RPO function must be carried out in compliance with  
applicable regulations. The cable is not included.  
In order to fully de−energize devices and the Powerware 9135 with the  
RPO port, it is necessary to:  
S Use a two−position switch (normally−open or normally−closed contact  
and held more than one second).  
S Connect this RPO switch to a device that trips all breaker(s) located  
be achieved by means of a shunt trip:  
(1)  
(2)  
upstream and downstream the Powerware 9135 UPS. This can  
(1)  
If not, the output devices could be powered again through static  
switch when the two−position switch is released.  
(2)  
If not, the output devices will remain powered several seconds  
after the RPO activation.  
NOTE The internal batteries will remain connected to the power module after RPO  
activation.  
RPO Contact Normally−Open  
RPO Contact Normally−Closed  
RJ−12 (6p6c)  
RJ−12 (6p6c)  
5 Vdc to 27 Vdc  
5 Vdc to 27 Vdc  
Figure 19. RPO Communication Port  
S Signal:  
Activation voltage: 5 Vdc to 27 Vdc  
Current: 10 mA maximum  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
UPS Electrical Connections  
WARNING  
Only qualified service personnel (such as a licensed electrician) shall perform the electrical  
installation. Risk of electrical shock.  
CAUTION  
S
S
For UPS models with hardwired outputs, overcurrent protection for the output AC  
circuit(s) is to be provided by others.  
For UPS models with hardwired outputs, suitably rated disconnect switches for the  
output AC circuit(s) are to be provided by others.  
Recommended Upstream Protection  
The indicated protection ensures discrimination for each output circuit  
downstream of the UPS.  
If these recommendations are not followed, protection discrimination is  
not achieved and may result in a potential power interruption to the  
connected devices.  
UPS Power Rating  
Upstream Circuit Breaker  
EU Models  
U Models  
5000 VA  
6000 VA  
D curve − 32A  
D curve − 35A  
2 Poles Circuit Breaker  
L (L1)  
N (L2)  
To Utility Source  
G
N
L
(L2) (L1)  
Figure 20. Recommended Upstream Protection  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
Recommended Downstream Protection (EU Models Only)  
The indicated protection ensures discrimination for each output circuit  
downstream of the UPS.  
If these recommendations are not followed, protection discrimination is  
not achieved and may result in a potential power interruption to the  
connected devices.  
UPS Power Rating  
Downstream Circuit Breaker  
EU Models Only  
Z curve − 10A  
C curve − 4A  
Z curve − 10A  
C curve − 6A  
5000 VA  
6000 VA  
Required Cable Cross−Sections  
Wiring  
Function  
EU Models  
U Models  
Terminal block cable  
capacity  
2
6 mm , solid or stranded wire  
2
2
6 mm , solid or stranded wire  
2
(maximum 8 mm or  
10 AWG).  
(maximum 8 mm or 8 AWG).  
Capacity for ground/  
earthing conductor  
Continue to the following section, ꢁConnecting the Power Cables (EU  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
Connecting the Power Cables (EU Models)  
WARNING  
S
S
S
Only qualified service personnel (such as a licensed electrician) shall perform the  
electrical connection. Risk of electrical shock.  
Before carrying out any connection, check that the battery circuit breaker and upstream  
protection device (utility input) are OFF (O).  
Use included insulated ferrules with stranded wires.  
1. Remove the terminal block cover (two screws) with the supplied  
Input Cable Opening  
Output Cable Opening  
Figure 21. Removing the Terminal Block (EU Models)  
2. Insert the input cable through the input cable opening (see  
3. Connect the three wires to the input terminal block.  
CAUTION  
Always connect the ground/earthing wire first.  
4. Insert the output cable through the output cable opening.  
5. Connect the three wires to the output terminal block.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
Input Cable  
Output Cable  
Figure 22. Installing the Input and Output Cables (EU Models)  
6. Replace the terminal block cover and tighten the cables.  
7. Secure the terminal block cover with the two screws removed in  
8. Plug the equipment to be protected into the appropriate UPS output  
Connect any high−power devices to the 16A outlet.  
9. Install the cord−retention brackets to secure the cords and provide  
strain relief.  
(2) 16A Receptacles  
(4) Priority Receptacles  
(4) Non−Priority Receptacles  
Cord−Retention  
Brackets  
Figure 23. Connecting the Power Cords (EU Models)  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
Connecting the Power Cables (U Models)  
WARNING  
S
S
S
Only qualified service personnel (such as a licensed electrician) shall perform the  
electrical connection. Risk of electrical shock.  
Before carrying out any connection, check that the battery circuit breaker and upstream  
protection device (utility input) are OFF (O).  
Use included insulated ferrules with stranded wires.  
1. Remove the terminal block cover (two screws) with the supplied  
N
L
CT:  
E
IONN  
TO  
C
UISLE  
DAB  
OC  
NY  
D
ER  
E
A
O
TO  
AT  
N
TCdc  
VD  
T
C
D
A
B
R
D
E
R
E
18  
ORY  
TU  
A
0
O
B
N
N
A
4
C
2
0V~,  
25  
00  
2
Input Cable  
Output Cable  
Opening  
Figure 24. Removing the Terminal Block (U Models)  
2. Connect the three wires to the input terminal block.  
CAUTION  
Always connect the ground/earthing wire first.  
3. Insert the output cable through the output cable opening.  
4. Connect the three wires to the output terminal block.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
N
O
ATRTL  
CT:  
E
IONN  
E
T
CO  
UIS  
E
L
A
T
DAB  
OC  
NY  
C
O
R
A
D
D
E
B
Y
RD  
ON  
TU  
R
E
c
BN  
1
80  
C
ATECDd  
V
N
A
O
4
2
0V~,  
25  
00  
2
Input Terminal  
Output Terminal  
GND L2 L1  
(N)  
GND L2 L1  
(N)  
Figure 25. Installing the Input and Output Cables (U Models)  
5. Replace the terminal block cover and tighten the cables.  
6. Secure the terminal block cover with the two screws removed in  
7. Plug the equipment to be protected into the appropriate UPS output  
receptacles.  
NOTE If more than one load is connected to the UPS, the total capacity of the loads should  
not exceed 30A.  
N
CT:  
E
IONN  
TO  
C
T
UIS  
LE  
DB  
A
A
COC  
A
4
2
Vdc  
0V~,  
25  
00  
2
Figure 26. Connecting the Power Cords (U Models)  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
UPS Rear Panels  
This section shows the rear panels of the Powerware 9135 models.  
SWITCHED  
GROUP  
1
(2) Sets of 2 Programmable, 10A  
Receptacles  
(4) 10A Receptacles  
Output Terminal Block  
Input Terminal Block  
(2) 16A Receptacles  
12A Thermal Switch  
20A Thermal Switch  
12A Thermal Switch  
Communication Bay  
Relay Port  
EBM Battery Connector  
USB Port  
RS−232 Port  
EBM RJ−11 Connector  
RS232  
CONTACTS  
BATT. NO.  
RPO  
RPO Port  
Figure 27. 5000/6000 VA, EU Models  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
(4) L6−30 Receptacles  
Output Terminal Block  
Input Cord with L6−30P  
EBM Battery Connector  
Communication Bay  
Relay Port  
USB Port  
RPO Port  
RS232  
BATT. NO. RPO  
RS−232 Port  
EBM RJ−11 Connector  
Figure 28. 5000/6000 VA, U Models  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4  
Operation  
This section describes:  
S The control panel  
S Turning the UPS on and off  
S Starting the UPS on battery  
S Operating modes  
S Display functions  
Control Panel Functions  
The UPS has a four−button graphical LCD with backlight. It provides  
useful information about the UPS itself, load status, events,  
Battery Indicator  
Power Indicator  
Bypass Indicator  
Alarm Indicator  
esc  
Escape Up  
Down Enter  
On/Off Button  
Figure 29. UPS Control Panel  
NOTE The On/Off button controls only the UPS output. The On/Off button has no effect on  
equipment connected to the UPS.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPERATION  
Turning the UPS On  
To turn the UPS on:  
1. Verify that the UPS internal battery connector is connected (see  
2. Set the upstream circuit breaker (not included) to the ON position.  
The equipment is powered by utility power, but not protected by  
the UPS.  
Batteries are recharging. An eight−hour recharge period is necessary  
to get full backup time.  
The  
and  
indicators illuminate.  
To change the factory-set defaults, see ꢁUser Settings " on  
3. Press and hold the button until you hear the UPS beep  
(approximately three seconds).  
After the UPS is turned on, it conducts a self−test and enters  
Normal mode. The  
turns off indicating that power is available to your equipment.  
indicator remains on and the  
indicator  
If the alarm beeps or a UPS alarm indicator stays on, see  
Starting the UPS on Battery  
NOTE Before using this feature, the UPS ON/OFF settings must have been enabled (see  
To turn on the UPS without using utility power, press and hold the  
button for three seconds. The UPS starts up in Battery mode and  
supplies battery power to your equipment.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPERATION  
Turning the UPS Off  
To shut down the UPS:  
1. Press the button for approximately three seconds  
The UPS beeps once, and the load is no longer protected by the  
UPS. It is powered by utility power. If the UPS is set in frequency  
converter mode, the equipment will not be powered.  
If the utility power is out of tolerance, the UPS will generate a  
10 ms output calibrated break.  
2. For a full shutdown of UPS and connected load, the upstream  
circuit breaker (not included) should be set to the OFF position.  
Operating Modes  
The Powerware 9135 front panel indicates the UPS status through the  
controls.  
On Battery Indicator  
Power On Indicator  
Bypass Indicator  
Alarm Indicator  
Indicator Legend  
Unlit  
Lit  
Flashing  
esc  
On/Off Button  
Figure 30. UPS Front Panel  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPERATION  
Normal Mode  
During Normal mode, the  
indicator illuminates. The UPS monitors  
and charges the batteries as needed and provides power protection to  
your equipment.  
Eco Mode  
During Eco mode, the indicator illuminates. Eco mode reduces the  
consumption of electrical power.  
Under normal conditions (utility power available), the equipment is  
supplied in ECO mode.  
NOTE ECO mode: operating mode by which the equipment is supplied directly by the  
utility power if it is within the tolerances defined by the user.  
If utility power is out of tolerance, the indicator flashes and the  
indicator illuminates. The equipment is protected by the UPS.  
Battery Mode  
When the UPS is operating during a power outage, the alarm beeps  
once every five seconds and the  
and  
indicators illuminate. The  
equipment is protected by the UPS and supplied by the battery. The  
display shows the remaining battery backup time.  
If battery capacity becomes low while in Battery mode, the alarm beeps  
every five seconds. Immediately complete and save your work to  
prevent data loss and similar difficulties.  
When the utility power returns, the UPS transfers to Normal mode  
operation while the battery recharges.  
End of backup time: all indicators turn off. The alarm beeps continuously  
and the UPS displays End of backup time Battery low.  
When utility power is restored after the UPS shuts down, the UPS  
automatically restarts.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPERATION  
Bypass Mode  
The UPS transfers to Bypass mode when:  
S The utility power is out of tolerence  
S There is an overload condition  
S The  
button is pressed  
S There is a malfunction  
The and  
utility power.  
indicators illuminate and the equipment is powered by  
Display Functions  
Status and Alarms  
Measurements  
UPS Input Measurements  
UPS Output Measurements  
Battery Measurements  
UPS Setup  
Maintenance  
Local Settings  
Model  
Output Settings  
ON/OFF Settings  
Battery Settings  
Alarm History  
Manual Batt Test  
LED & Buzzer Test  
LCM  
Statistics  
Figure 31. Menu Map for Display Functions  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPERATION  
Access to Measurements  
Press the button on the UPS front panel to access measurements for  
voltage, current, frequency, power output, and battery capacity.  
Access to UPS Setup  
To access the UPS Setup menu:  
1. Scroll to the UPS Setup menu by pressing the  
button.  
2. Press the  
button to get access.  
esc  
Figure 32. Access to UPS Setup  
The following tables display the options that can be changed by the  
user.  
Table 3. Local Settings  
Function  
Factory Setting  
Options  
Language  
English  
French, German, Italian, Portuguese, Spanish  
US (MM−DD−YYYY/HH:MM AM/PM)  
Date / Time Format  
International  
(DD−MM−YYYY/HH :MM)  
Date / Time Change  
Audible Alarm  
GMT + 1  
(Continental Europe)  
MM−DD−YYYY/HH :MM adjustable  
No  
Yes  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPERATION  
Table 4. Output Settings  
Function  
Factory Setting  
Options  
Comments  
Output Voltage  
EU Models: 230V  
U Models: 208V  
200V / 208V / 220V /  
240V / 250V  
Freq Converter  
Disable  
Enable  
60 Hz  
Output Frequency  
EU Models: 50 Hz  
U Models: 60 Hz  
User selectable under  
frequency−converter mode  
Eco Mode  
Slew Rate  
Disable  
1 Hz / sec  
Yes  
Enable  
0.5 Hz / sec  
No  
Bypass Transfer  
If bypass Ac nok?  
Transfer to bypass if utility power is  
out of tolerance  
Interrupt Time  
10 ms  
105%  
20 ms, ...... , 200 ms  
40%, 50%, 70%  
Break time calibration during load  
transfer on utility power out of  
tolerance  
Overload Prealarm  
Alarm if threshold is overrun  
Table 5. ON/OFF Settings  
Function  
Factory Setting  
Disable  
Options  
Comments  
Cold Start  
Enable  
Start on battery  
Forced Reboot  
Enable  
Enables automatic restart of the  
system even if utility power is  
restored before the end of the  
shutdown sequence  
Auto Restart  
Enable  
Disable  
Enable  
UPS restarts automatically when  
utility power is restored  
Energy Saving  
Disable  
Automatic shutdown on battery if  
output load level <10%  
Sleep Mode  
Enable  
Enable  
Disable  
Disable  
Remote Command  
Enables consideration of shutdown or  
restart orders from software to be  
authorized  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPERATION  
Table 6. Battery Settings  
Function  
Factory Setting  
Options  
Comments  
Auto Battery Test  
Everyweek  
No test / everyday /  
everyweek /everymonth  
Low Batt Warning  
User Batt Settings  
20%  
0 to 100%  
1% increment  
UPS reads number of  
battery modules  
connected  
From 0 to 95 Ah  
5 Ah increment  
Deep Disch Protect  
Yes  
No  
Protection against deep discharge.  
If disabled, the Eaton warranty will be  
void.  
Access to Maintenance  
To access the Maintenance menu:  
1. Scroll to the Maintenance menu by pressing the  
button.  
2. Press the  
button to get access.  
esc  
Figure 33. Access to Maintenance  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPERATION  
The following table displays the maintenance options.  
Table 7. Maintenance Settings  
Function  
Sub−Function  
Power Module  
Frame  
Option/Display  
Comments  
Model  
SN: xxxxxxxxx  
SOFT: xxx  
Serial number  
Soft version  
Alarm History  
Read  
Description  
Date Hour  
Alarm xxx  
10 alarms can be stored automatically  
Erase  
No / Yes  
Manual Batt Test  
Led & Buzzer Test  
Life Cycle Monitoring  
Statistics  
Manual Battery Test  
Led & Buzzer Test  
LCM  
No / Yes  
No / Yes  
Enable / Disable  
Statistics  
Life cycling monitoring alarms  
Auto Statistics  
Custom Statistics  
Reset Date ?  
Are you sure ?  
Life Cycle Monitoring  
LCM displays messages on the UPS front panel and through the  
communication channels, at every important stage of the UPS´s life.  
Press the  
button to display LCM warning details.  
esc  
Figure 34. LCM Warning Screen  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPERATION  
Anticipate Maintenance  
Automatic warnings appear when maintenance actions need to be  
planned:  
Table 8. LCM Warning Details  
LCM Warning Details  
Signification  
BATTERY CHECK RECOMMENDED Battery is approaching its reliability end of life.  
Risk to reduce dramatically backup time.  
Reset or Disable LCM  
In case of any LCM messages displayed:  
S For temporary reset: press the esc button for at least three seconds  
while in the Status and Alarm menu to temporarily cancel the alarm  
status.  
The alert will be repeated twice every 30 days.  
S For permanent reset: press the  
button for at least three seconds  
while in the LCM warning menu to permanently cancel the LCM  
event.  
At any time:  
S To disable all LCM messages, select disable allwhile in the LCM  
menu.  
Be careful: if you disable all LCM messages, you will not be aware of  
any LCM events that can happen on the UPS.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 5  
Additional UPS Features  
This section describes:  
S Communication ports  
S Network Management Card  
S Load segments (PowerShare)  
Communication Ports  
The Powerware 9135 provides three communication methods that can  
be used simultaneously:  
S RS−232 or USB communication. Compatible with most power  
management software applications. Note that both ports cannot be  
used at the same time.  
S The relay port uses output contacts for basic signaling or for  
®
®
®
protection of IT systems like IBM iSeries (formerly AS/400 ) and  
more.  
S The communication bay is compatible with the optional Network  
Management Card.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ADDITIONAL UPS FEATURES  
USB Port  
The UPS can communicate with a USB−compliant computer using  
®
Powerware LanSafe Power Management Software or other  
HID−compliant power management software compatible with Microsoft  
®
®
Windows 2000 and XP operating systems that support HID devices.  
NOTE The latest versions of the Powerware LanSafe Power Management Software and  
To establish communication between the UPS and a computer:  
1. The USB port is hot−pluggable. Connect the USB cable to the USB  
Connect the other end of the USB cable to the USB port on your  
computer.  
SWITCHED  
GROUP  
1
SWITCHED  
GROUP  
2
USB Port  
RS232  
CONTACTS  
BATT. NORP.  
O
Figure 35. The USB Port  
2. Install the Powerware LanSafe Power Management Software and  
USB drivers according to the instructions provided at  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ADDITIONAL UPS FEATURES  
Relay Port  
When the status is active, the contact between the common (Pin 5) and  
the relevant information pin is closed.  
Output relays specifications:  
S
S
S
Voltage: 48 Vdc maximum  
Current: 2A maximum  
Power: 62.5 VA, 30W  
Example: for 48 Vdc, Imax=625 mA  
functions.  
5
4
3
2
1
9
8
7
6
NC NO  
Common  
NO  
NO  
NO  
NOTE Normally−open (NO)  
Normally−closed (NC)  
Figure 36. Communication Port  
Table 9. Communication Port Pin Assignment  
Pin Number  
Function  
1, 2  
3
Not used  
Remote Power−off signal (5–27 Vdc, 10 mA max)  
Operation on mains (not on battery)  
User common  
4
5
6
Operation on automatic bypass  
Low Battery  
7
8
Load protected  
9
Operation on battery  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ADDITIONAL UPS FEATURES  
Network Management Card (Optional)  
It is not necessary to shut down the UPS before installing a  
communication card.  
1. Remove the slot cover secured by two screws.  
2. Insert the communication card into the slot.  
3. Secure the card with both screws.  
SWITCHED  
GROUP  
1
Communication Card  
(restricted access)  
RS232  
CONTACTS  
BATT. NO.RPO  
Figure 37. Network Management Card (EU Model Shown)  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ADDITIONAL UPS FEATURES  
EU Model Load Segments (PowerShare)  
During a power outage, you can keep key pieces of equipment running  
while you turn off other equipment. It is preferable to connect the  
1
2
non−priority loads to the programmable receptacles,  
and  
. This  
feature allows you to save battery power. See your power management  
information).  
NOTE If power management software is not used, the individual load segments cannot be  
controlled.  
1
Programmable Receptacles  
2
Programmable Receptacles  
Figure 38. Load Segments (EU Models Only)  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ADDITIONAL UPS FEATURES  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 6  
Maintenance  
This section describes replacing the power module and battery tray.  
Hot−Swapping the Power Module  
WARNING  
Only qualified service personnel (such as a licensed electrician) shall perform the electrical  
installation. Risk of electrical shock.  
This operation can be performed without interrupting the equipment.  
NOTE A ribbon cable connects the control panel to the UPS. Do not pull on the cable or  
disconnect it.  
2. Place the front panel above the UPS.  
3. Remove the two power module brackets (four screws).  
4. Slightly pull the power module, then lift it to extract it.  
Figure 39. Removing the Power Module  
5. Replace the faulty power module with one of the same power  
rating (5000 VA or 6000 VA) and secure with the power module  
brackets.  
6. Replace the UPS front cover.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
MAINTENANCE  
Hot−Swapping the Battery Tray  
CAUTION  
S
Batteries can present a risk of electrical shock or burn from high short−circuit current.  
Observe proper precautions. Servicing should be performed by qualified service  
personnel knowledgeable of batteries and required precautions. Keep unauthorized  
personnel away from batteries.  
S
S
S
Remove watches, rings, bracelets and all other metal objects from the hands and arms.  
Use tools with an insulated handle.  
When replacing batteries, replace with the same number of the BB/HR5.5−12 batteries.  
This operation can be performed without interrupting the equipment.  
NOTE A ribbon cable connects the control panel to the UPS. Do not pull on the cable or  
disconnect it.  
2. Place the front panel above the UPS.  
3. Remove the two battery retaining brackets (four screws).  
4. Slightly pull the battery tray, then lift it to extract it.  
Figure 40. Removing the Battery Tray  
5. Replace the battery tray and secure with the battery retaining  
brackets.  
NOTE To ensure safety and high performance, use only batteries supplied by Eaton.  
6. Replace the UPS front cover.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 7  
Specifications  
Table 10. Input and Output Specifications  
Power Levels  
Output on  
Battery Power  
AC Input  
Voltage  
Model Number  
(Rated at  
Nominal  
Voltage  
Frequency  
Range  
Nominal Inputs)  
3
Voltage  
Frequency  
60 Hz  
1
2
Range  
PW9135G5000−XL3UHW  
PW9135G5000−XL3U  
5000 VA, 3500W  
6000 VA, 4200W  
208V  
156–280V  
208V  
230V  
PW9135G6000−XL3UHW  
PW9135G6000−XL3U  
40–70 Hz  
0.2 Hz)  
(
PW9135G5000−XL3UEU  
PW9135G6000−XL3UEU  
5000 VA, 3500W  
6000 VA, 4200W  
230V  
156–280V  
50 Hz  
1
Adjustable to 200V (10% derating of output power) 208/220/230/240/250V.  
2
3
Table 11. Dimensions and Weights  
Model  
Dimensions (WxHxD)  
Weight  
5000 VA UPS  
6000 VA UPS  
444.5 130.6 741 mm  
57 kg (125.7 lb)  
(17.5" 5.1" 29.2")  
198 127 603 mm  
UPS Power Module  
UPS Internal Battery  
EBM  
12 kg (26.5 lb)  
30.5 kg (67.2 lb)  
70.5 kg (155.4 lb)  
(7.8" 5" 23.7")  
214.5 116 498 mm  
(8.4" 4.6" 19.6")  
444.5 130.6 650 mm  
(17.5" 5.1" 25.6")  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SPECIFICATIONS  
Table 12. Power Connections  
Model  
Input Connection  
Output Receptacles  
U Models  
10 ft, L6−30P power cord  
(4) NEMA L6−30R  
Hardwired with  
(8) 10A, IEC 320−C13; (2) 16A, IEC 320−C19  
EU Models  
Hardwired  
Table 13. Environmental and Safety  
U Models  
EU Models  
Operating Temperature  
Storage Temperature  
Relative Humidity  
Operating Altitude  
Audible Noise  
0°C to 40°C (32°F to 104°F)  
−25°C to 40°C (−13°F to 104°F)  
5–95% noncondensing  
Up to 1,000 meters above sea level  
Less than 46 dBA Normal mode, typical load and Battery mode  
ANSI C62.41 Category B, IEC 61000−4−5  
Surge Suppression  
Safety Conformance  
UL 1778;  
CSA C22.2, No. 107.1;  
NOM−019−SCFI  
UL 1778;  
CSA C22.2, No. 107.1;  
EN 62040−1−1, IEC 60950−1, IEC 50091−1−1  
Agency Markings  
EMC (Class A)  
cUL, NOM  
TUV(GS), CE, cUL, C−tick  
FCC Part 15  
EN 62040−2 C1, AS 62040−2 C1, FCC Part 15  
Table 14. Battery  
UPS Configuration  
(15) 12V, 5.5 Ah internal batteries  
EBM Configuration  
Type  
(2 strings of 15) 12V, 5.5 Ah internal batteries  
Sealed, maintenance-free, lead-acid  
Table 15. Battery Runtimes  
UPS  
UPS Internal Batteries  
+1 EBM  
22 min  
17 min  
+2 EBMs  
41 min  
+3 EBMs  
1 hr 2 min  
50 min  
+4 EBMs  
1 hr 23 min  
1 hr 7 min  
5000 VA  
6000 VA  
5 min  
4 min  
33 min  
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 8  
Troubleshooting  
This section explains:  
S UPS alarms and conditions  
S Service and support  
Troubleshooting LED  
Press the esc button to stop the audible alarm.  
NOTE In case of "MULTIPLE FAULT", press the  
to further details.  
button and the  
button to get access  
esc  
Escape Up  
Down Enter  
Figure 41. Troubleshooting LED  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TROUBLESHOOTING  
Troubleshooting Not Requiring Eaton Service  
esc  
Figure 42. Environment Fault  
Press the  
button to display the following details:  
Displayed Details  
NO BATTERY  
Signification  
Correction  
The battery is incorrectly connected.  
Check battery connections.  
Check AC wiring.  
I/O BAD CONNECTION  
Utility input is not connected to the correct  
terminals.  
NO POWER MODULE  
The power module is not inserted.  
Check power module connections (see  
page 63).  
NO BATTERY MODULE  
INV THERM OVERLOAD  
The battery tray is incorrectly connected.  
The UPS shuts down automatically because Check the power drawn by the connected  
of a major overload.  
devices and disconnect any non−priority  
devices.  
INVERT LIMITATION  
Short circuit conditions on output devices.  
Check the installation at the UPS output  
(wiring, fault equipment).  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TROUBLESHOOTING  
Troubleshooting Requiring Eaton Service  
NOTE In case of multiple fault, press the  
further details.  
button and the  
button to get access to  
esc  
Escape Up  
Down Enter  
Figure 43. Troubleshooting LED  
Correction  
Display  
Signification  
POWER MODULE FAULT Internal power module fault detected. Use  
"Enter" button to display details.  
Call the Help Desk. Replace the power  
In Parallel: see the note below to start the  
other UPS alone.  
BATT MODULE FAULT  
FRAME FAULT  
Battery fault detected during the battery  
test. Use "Enter" button to display details.  
Call the Help Desk. Replace the battery tray  
Internal chassis fault detected. Use "Enter" Call the Help Desk.  
button to display details.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TROUBLESHOOTING  
Service and Support  
If you have any questions or problems with the UPS, call your Local  
Distributor or the Help Desk at one of the following telephone numbers  
and ask for a UPS technical representative.  
United States:  
Canada:  
1−800−356−5737 or 1−919−870−3149  
1−800−461−9166 ext 260  
Call your local service representative  
All other countries:  
Please have the following information ready when you call the Help  
Desk:  
S Model number  
S Serial number  
S Version number (if available)  
S Date of failure or problem  
S Symptoms of failure or problem  
S Customer return address and contact information  
If repair is required, you will be given a Returned Material Authorization  
(RMA) Number. This number must appear on the outside of the package  
and on the Bill Of Lading (if applicable). Use the original packaging or  
request packaging from the Help Desk or distributor. Units damaged in  
shipment as a result of improper packaging are not covered under  
warranty. A replacement or repair unit will be shipped, freight prepaid for  
all warrantied units.  
NOTE For critical applications, immediate replacement may be available. Call the Help  
Desk for the dealer or distributor nearest you.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Chapter 9  
Warranty  
Two−Year Limited Warranty (US and Canada)  
®
Powerware UPS Models: 3105, 9120, 9125, 9135, 9140, and FERRUPS up to 3.1 kVA  
WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Electrical Inc., a Delaware  
Corporation company (ꢁCompany").  
LIMITED WARRANTY: This limited warranty (this ꢁWarranty") applies only to the original End−User (the ꢁEnd−User")  
of any Powerware 3105, 9120, 9125, 9135, 9140, and FERRUPS up to 3.1 kVA Products (individually and  
collectively, the ꢁProduct") purchased on or after June 1, 2004 and cannot be transferred. This Warranty applies  
even in the event that the Product is initially sold by Company for resale to an End−User.  
LIMITED WARRANTY PERIOD: The period covered by this Warranty for Product installed [and currently located] in  
the fifty (50) United States, the District of Columbia, and Canada is twenty−four (24) months from the date of  
purchase.  
WHAT THIS LIMITED WARRANTY COVERS: The warrantor warrants that the Product and battery (individually and  
collectively, the "Warranted Items") are free from defects in material and workmanship. If, in the opinion of  
Company, a Warranted Item is defective and the defect is within the terms of this Warranty, Company’s sole  
obligation will be to repair or replace such defective Warranted Item (including by providing service, parts and labor,  
as applicable), at the option of Company.  
PROCEDURES FOR REPAIR OR REPLACEMENT OF WARRANTED ITEMS: The Warranted Item will be repaired or  
replaced at a Company site or such other location as determined by Company.  
If the Warranted Item is to be replaced by Company, and the End−User supplies a credit card number or purchase  
order for the value of the replacement Product, Company will use commercially reasonable business efforts to ship  
(via standard ground shipment and at no cost to the End−User) the replacement Warranted Item to the End−User  
within one (1) business day after Company receives notice of the warranty claim. In such case, the End−User must  
return (at Company’s expense) the defective Warranted Item to Company in the same packaging as the  
replacement Warranted Item received by the End−User or as otherwise instructed by Company. If Company does  
not receive the defective Warranted Item, Company will either charge the End−User’s credit card, or send the  
End−User an invoice (which the End−User agrees to pay), for the value of the replacement Product.  
If the Warranted Item is to be replaced by Company, but the End−User is unwilling or unable to supply a credit card  
number or purchase order for the value of the replacement Product, Company will use commercially reasonable  
business efforts to ship (via standard ground shipment and at no cost to the End−User) the replacement Warranted  
Item to the End−User within one (1) business day after Company receives the defective Product from the End−User.  
In any case, Company will provide shipping instructions and will pay its designated carrier for all shipping charges for  
return of defective equipment and replacement of Warranted Items. Any returned Warranted Item or parts that are  
replaced may be new or reconditioned. All Warranted Items returned to Company and all parts replaced by  
Company shall become the property of Company.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
WARRANTY  
WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages  
caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than  
the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect,  
accident, abuse, misuse, misapplication, or incorrect installation; (d) repair or alteration not authorized in writing by  
Company personnel or performed by an authorized Company Customer Service Engineer or Agent; (e) improper  
testing, operation, maintenance, adjustment, or modification of any kind not authorized in writing by Company  
personnel or performed by an authorized Company Customer Service Engineer or Agent; or (f) use of the Product  
under other than normal operating conditions or in a manner inconsistent with the Product’s labels or instructions.  
This Warranty is not valid if the Product’s serial numbers have been removed or are illegible. Any Warranted Items  
repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the original Warranty  
subject to all the terms thereof.  
Company shall not be responsible for any charges for testing, checking, removal or installation of Warranted Items.  
COMPANY DOES NOT WARRANT EQUIPMENT NOT MANUFACTURED BY COMPANY. IF PERMITTED BY THE  
APPLICABLE MANUFACTURER, COMPANY SHALL PASS THROUGH SUCH MANUFACTURER’S WARRANTIES TO  
END−USER.  
COMPANY DOES NOT WARRANT SOFTWARE, INCLUDING SOFTWARE EMBEDDED IN PRODUCTS, THAT IS NOT  
CREATED BY COMPANY. WITHOUT LIMITING THE FOREGOING, COMPANY SPECIFICALLY DOES NOT WARRANT  
SOFTWARE (SUCH AS LINUX) THAT WAS CREATED USING AN ꢀOPEN SOURCE" MODEL OR IS DISTRIBUTED  
PURSUANT TO AN OPEN SOURCE LICENSE.  
THIS WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY OFFERED BY COMPANY WITH RESPECT TO THE  
PRODUCTS AND SERVICES AND, EXCEPT FOR SUCH FOREGOING WARRANTY COMPANY DISCLAIMS ALL OTHER  
WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY, TITLE,  
NON−INFRINGEMENT, AND FITNESS FOR A PARTICULAR PURPOSE. CORRECTION OF NON−CONFORMITIES IN  
THE MANNER AND FOR THE PERIOD OF TIME PROVIDED ABOVE SHALL CONSTITUTE COMPANY’S SOLE  
LIABILITY AND END−USER’S EXCLUSIVE REMEDY FOR FAILURE OF COMPANY TO MEET ITS WARRANTY  
OBLIGATIONS, WHETHER CLAIMS OF THE END−USER ARE BASED IN CONTRACT, IN TORT (INCLUDING  
NEGLIGENCE OR STRICT LIABILITY), OR OTHERWISE.  
LIMITATION OF LIABILITY: The remedies of the End−User set forth herein are exclusive and are the sole remedies  
for any failure of Company to comply with its obligations hereunder. In no event shall Company be liable in contract,  
in tort (including negligence or strict liability) or otherwise for damage to property or equipment other than the  
Products, including loss of profits or revenue, loss of use of Products, loss of data, cost of capital, claims of  
customers of the End−User or any special, indirect, incidental or consequential damages whatsoever. The total  
cumulative liability of Company hereunder whether the claims are based in contract (including indemnity), in tort  
(including negligence or strict liability) or otherwise, shall not exceed the price of the Product on which such liability  
is based.  
Company shall not be responsible for failure to provide service or parts due to causes beyond Company’s  
reasonable control.  
END−USER’S OBLIGATIONS: In order to receive the benefits of this Warranty, the End−User must use the Product  
in a normal way; follow the Product’s user’s guide; and protect against further damage to the Product if there is a  
covered defect.  
OTHER LIMITATIONS: Company’s obligations under this Warranty are expressly conditioned upon receipt by  
Company of all payments due to it (including interest charges, if any). During such time as Company has not  
received payment of any amount due to it for the Product, in accordance with the contract terms under which the  
Product is sold, Company shall have no obligation under this Warranty. Also during such time, the period of this  
Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any  
overdue or unpaid amounts.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARRANTY  
COSTS NOT RELATED TO WARRANTY: The End−User shall be invoiced for, and shall pay for, all services not  
expressly provided for by the terms of this Warranty, including without limitation, site calls involving an inspection  
that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials,  
freight charges, travel expenses or labor of Company representatives outside the terms of this Warranty will be  
borne by the End−User.  
OBTAINING WARRANTY SERVICE: In the USA, call the Customer Reliability Center 7x24 at 800−356−5737. Outside  
of the USA, call your local Powerware product sales or service representative, or call the Customer Reliability Center  
in the USA at 919−870−3149. For comments or questions about this Warranty, write to the Customer Quality  
Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.  
Ten−Year Pro−Rated Limited Warranty (US and Canada)  
Powerware UPS Models: 5115, 5125, 5140, 9120, 9125, 9135, 9140, 9155, 9170+, and FERRUPS  
WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Electrical Inc., a Delaware  
Corporation company (ꢁCompany").  
LIMITED WARRANTY: This pro−rated limited warranty (this ꢁWarranty") applies only to the original End−User (the  
ꢁEnd−User") of any Powerware 5115, 5125, 5140, 9120, 9125, 9135, 9140, 9155, 9170+, and FERRUPS Products  
(individually and collectively, the ꢁProduct") and cannot be transferred. This Warranty applies even in the event that  
the Product is initially sold by Company for resale to an End−User.  
WHAT THIS WARRANTY COVERS: In addition to the standard Two−Year Limited Warranty covering the applicable  
Product, the warrantor warrants that the Product will have a service life (defined below) of ten years from the date  
of purchase (the ꢁTen−Year Service Life") when used in accordance with the storage, handling, installation,  
operation and maintenance procedures prescribed in the Product’s user’s guide. ꢁService life" means the Product’s  
ability to deliver at least 80% of its original rated backup time.  
If Company finds, in its sole discretion, that any Product has not provided the Ten−Year Service Life, Company will,  
as its sole obligation and the End−User’s sole remedy for Company’s breach of this warranty, repair or replace the  
Product, at its option, F.O.B. Company’s factory, for a charge, payable by the End−User to Company pro−rated on the  
following basis:  
The End−User will be allowed a credit against Company’s list price of equivalent equipment at the time of return of  
the Product to Company, in proportion to the percentage of Ten−Year Service Life remaining at the time of return of  
the Product to Company. In calculating the available credit, the remaining portion of the Ten−Year Service Life will be  
rounded up or down to the nearest whole year. The End−User will assume responsibility to pay the balance of the  
list price; and Company reserves the right to require payment prior to delivery of the repaired or replacement  
equipment.  
For the avoidance of doubt, Company’s responsibilities under this Warranty are as follows:  
Years 1−2  
Product repaired or replaced pursuant to terms of Limited Warranty  
Years 3−10 − Unit Credit ($) = Current List Price ×  
Years of Unexpired Life  
10 Years of Warranted Life  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
WARRANTY  
WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages  
caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than  
the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect,  
accident, abuse, misuse, misapplication, or incorrect installation; (d) repair or alteration not authorized in writing by  
Company personnel or performed by an authorized Company Customer Service Engineer or Agent; (e) improper  
testing, operation, maintenance, adjustment, or modification of any kind not authorized in writing by Company  
personnel or performed by an authorized Company Customer Service Engineer or Agent; or (f) use of the Product  
under other than normal operating conditions or in a manner inconsistent with the Product’s labels or instructions.  
This Warranty is not valid: (a) unless the End−User returns to Company the Warranty Registration Card within  
thirty (30) days of purchase; or (b) if the Product’s serial numbers have been removed or are illegible. Any  
Warranted Items repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the  
original Warranty subject to all the terms thereof.  
Company shall not be responsible for any charges for testing, checking, removal or installation of Warranted Items.  
COMPANY DOES NOT WARRANT EQUIPMENT NOT MANUFACTURED BY COMPANY. IF PERMITTED BY THE  
APPLICABLE MANUFACTURER, COMPANY SHALL PASS THROUGH SUCH MANUFACTURER’S WARRANTIES TO  
END−USER.  
COMPANY DOES NOT WARRANT SOFTWARE, INCLUDING SOFTWARE EMBEDDED IN PRODUCTS, THAT IS NOT  
CREATED BY COMPANY. WITHOUT LIMITING THE FOREGOING, COMPANY SPECIFICALLY DOES NOT WARRANT  
SOFTWARE (SUCH AS LINUX) THAT WAS CREATED USING AN ꢀOPEN SOURCE" MODEL OR IS DISTRIBUTED  
PURSUANT TO AN OPEN SOURCE LICENSE.  
THIS WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY OFFERED BY COMPANY WITH RESPECT TO THE  
PRODUCTS AND SERVICES AND, EXCEPT FOR SUCH FOREGOING WARRANTY COMPANY DISCLAIMS ALL OTHER  
WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY, TITLE,  
NON−INFRINGEMENT, AND FITNESS FOR A PARTICULAR PURPOSE. CORRECTION OF NON−CONFORMITIES IN  
THE MANNER AND FOR THE PERIOD OF TIME PROVIDED ABOVE SHALL CONSTITUTE COMPANY’S SOLE  
LIABILITY AND END−USER’S EXCLUSIVE REMEDY FOR FAILURE OF COMPANY TO MEET ITS WARRANTY  
OBLIGATIONS, WHETHER CLAIMS OF THE END−USER ARE BASED IN CONTRACT, IN TORT (INCLUDING  
NEGLIGENCE OR STRICT LIABILITY), OR OTHERWISE.  
LIMITATION OF LIABILITY: The remedies of the End−User set forth herein are exclusive and are the sole remedies  
for any failure of Company to comply with its obligations hereunder. In no event shall Company be liable in contract,  
in tort (including negligence or strict liability) or otherwise for damage to property or equipment other than the  
Products, including loss of profits or revenue, loss of use of Products, loss of data, cost of capital, claims of  
customers of the End−User or any special, indirect, incidental or consequential damages whatsoever. The total  
cumulative liability of Company hereunder whether the claims are based in contract (including indemnity), in tort  
(including negligence or strict liability) or otherwise, shall not exceed the price of the Product on which such liability  
is based.  
Company shall not be responsible for failure to provide service or parts due to causes beyond Company’s  
reasonable control.  
END−USER’S OBLIGATIONS: In order to receive the benefits of this Warranty, the End−User must use the Product  
in a normal way; follow the Product’s operation and maintenance manual; and protect against further damage to the  
Product if there is a covered defect.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARRANTY  
OTHER LIMITATIONS: Company’s obligations under this Warranty are expressly conditioned upon receipt by  
Company of all payments due to it (including interest charges, if any). During such time as Company has not  
received payment of any amount due to it for the Product, in accordance with the contract terms under which the  
Product is sold, Company shall have no obligation under this Warranty. Also during such time, the period of this  
Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any  
overdue or unpaid amounts.  
COSTS NOT RELATED TO WARRANTY: The End−User shall be invoiced for, and shall pay for, all services not  
expressly provided for by the terms of this Warranty, including without limitation, site calls involving an inspection  
that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials,  
freight charges, travel expenses or labor of Company representatives outside the terms of this Warranty will be  
borne by the End−User.  
OBTAINING WARRANTY SERVICE: In the USA, call the Customer Reliability Center 7x24 at 800−356−5737. Outside  
of the USA, contact your local Powerware product sales or service representative, or call the Customer Reliability  
Center in the USA at 919−870−3149. Company will not accept any Product for return, credit or exchange unless  
expressly authorized by Company in writing and delivered FOB Company factory. For comments or questions about  
this Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina  
27616 USA.  
Load Protection Guarantee (US and Canada)  
Powerware UPS Models 3105, 5110, 5115, 5125, 9120, 9125, 9135, 9140, 9150, 9155, 9170+, and FERRUPS  
GUARANTOR: The Guarantor for the load protection guaranty set forth herein is Eaton Electrical Inc., a Delaware  
Corporation company (ꢁCompany").  
LIMITED GUARANTY: This load protection guaranty (this ꢁGuaranty") applies only to the original End−User (the  
ꢁEnd−User") of any Powerware 3105, 5110, 5115, 5125, 9120, 9125, 9135, 9140, 9150, 9155, 9170+, and FERRUPS  
Products (individually and collectively, the ꢁProduct") and cannot be transferred. This Guaranty applies even in the  
event that the Product is initially sold by Company for resale to an End−User.  
WHAT THIS GUARANTY COVERS: For the lifetime of the Product, Guarantor promises to repair or replace, at  
Guarantor’s option, the equipment (valued up to the limits shown below*) that is damaged by an AC power line  
surge, spike, or other transient when properly connected to Guarantor’s uninterruptible power system (ꢁUPS").  
Reimbursement for or restoration of data loss excluded. This Guaranty applies only if all of the following  
circumstances arise:  
1. The UPS is plugged into properly grounded and wired outlets, using no extension cords, adapters, other ground  
wires or other electrical connectors;  
2. The installation of the UPS complies with all applicable electrical and safety codes described by the National  
Electrical Code (NEC);  
3. The UPS was used under normal operating conditions and in accordance with all labels and instructions; and  
4. The UPS was not damaged by accident (other than AC power line transient), misuse, or abuse.  
*Cumulative Limits to be paid by Guarantor under this Load Protection Guaranty:  
S
S
S
$25,000 for Powerware UPS Model 3105  
$150,000 for Powerware UPS Models 5110, 5115, and 5125  
$250,000 for Powerware UPS Models 9120, 9125, 9135, 9140, 9150, 9155, 9170+, and FERRUPS products  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
WARRANTY  
WHAT THIS GUARANTY DOES NOT COVER: Any reimbursement or repair to End−User’s equipment does not  
include reimbursement for or restoration of any data loss. This Guaranty does not cover any defects or damages  
caused by: (a) failure to properly store the Product before installation, including the charge of batteries no later than  
the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect,  
accident, abuse, misuse, misapplication, or incorrect installation of Product; (d) repair or alteration of Product not  
authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or  
Agent; (e) improper testing, operation, maintenance, adjustment, or modification of any kind to the Product not  
authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or  
Agent; or (f) use of the Product under other than normal operating conditions or in a manner inconsistent with the  
Product’s labels or instructions.  
This Guaranty is not valid: (a) unless the End−User returns to Company the Warranty Registration Card within  
thirty (30) days of purchase; or (b) if the Product’s serial numbers have been removed or are illegible.  
Company shall not be responsible for any charges for testing, checking, removal or installation of any items.  
LIMITATION OF LIABILITY: THE REMEDIES OF THE END−USER SET FORTH HEREIN ARE EXCLUSIVE AND ARE THE SOLE  
REMEDIES FOR ANY FAILURE OF COMPANY TO COMPLY WITH ITS OBLIGATIONS HEREUNDER. EXCEPT AS OTHERWISE  
PROVIDED FOR IN THIS GUARANTY, IN NO EVENT SHALL COMPANY BE LIABLE IN CONTRACT, IN TORT (INCLUDING  
NEGLIGENCE OR STRICT LIABILITY) OR OTHERWISE FOR DAMAGE TO PROPERTY OR EQUIPMENT OTHER THAN THE  
PRODUCTS, INCLUDING LOSS OF PROFITS OR REVENUE, LOSS OF USE OF PRODUCTS, LOSS OF DATA, COST OF  
CAPITAL, CLAIMS OF CUSTOMERS OF THE END−USER OR ANY SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL  
DAMAGES WHATSOEVER. THE TOTAL CUMULATIVE LIABILITY OF COMPANY HEREUNDER WHETHER THE CLAIMS ARE  
BASED IN CONTRACT (INCLUDING INDEMNITY), IN TORT (INCLUDING NEGLIGENCE OR STRICT LIABILITY) OR  
OTHERWISE, SHALL NOT EXCEED THOSE SET FORTH ABOVE.  
Company shall not be responsible for failure to provide repair or replacement under this Guaranty due to causes  
beyond Company’s reasonable control.  
END−USER’S OBLIGATIONS: In order to receive the benefits of this Guaranty, the End−User must use the Product in  
a normal way; follow the Product’s operation and maintenance manual; and protect against further damage to the  
Product if there is a covered defect.  
OTHER LIMITATIONS: Company’s obligations under this Guaranty are expressly conditioned upon receipt by  
Company of all payments due to it (including interest charges, if any). During such time as Company has not  
received payment of any amount due to it for the Product, in accordance with the contract terms under which the  
Product is sold, Company shall have no obligation under this Guaranty.  
COSTS NOT RELATED TO GUARANTY: The End−User shall be invoiced for, and shall pay for, all services not  
expressly provided for by the terms of this Guaranty, including without limitation, site calls involving an inspection  
that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials,  
freight charges, travel expenses or labor of Company representatives outside the terms of this Guaranty will be  
borne by the End−User.  
TO MAKE A CLAIM: In the USA, call the Customer Reliability Center 7x24 at 800−356−5737. Outside of the USA,  
contact your local Powerware product sales or service representative, or call the Customer Reliability Center in the  
USA at 919−870−3149. For comments or questions about this Load Protection Guaranty, write to the Customer  
Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.  
EATON Powerware® 9135 Two−in−One UPS (5000/6000 VA) User’s Guide S 164201726 Rev 1  
76  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Peavey Stereo Amplifier PV1600 User Manual
Philips Baby Monitor SCD450 79 User Manual
Philips CD Player 170B5 User Manual
Philips Indoor Furnishings 37340 48 16 User Manual
Pioneer Car Video System AVH P6000DVD User Manual
Planar Home Theater Screen EL640480 AM User Manual
Polaris Offroad Vehicle 340 Edge User Manual
Polaroid Typewriter FLM 2632 User Manual
ProForm Treadmill PFTL989081 User Manual
Profoto Indoor Furnishings 250 W User Manual