Pentair Swimming Pool Heater MiniMax Plus HP Series User Manual |
1
®
™
MiniMax Plus and PowerMax
POOL & SPA HEATERS
OPERATION & INSTALLATION MANUAL
WARNING
FOR YOUR SAFETY - READ BEFORE OPERATING
Warning: If you do not follow these instructions exactly, a fire or explosion may
result, causing property damage, personal injury or loss of life.
For additional free copies of this manual; call (800) 831-7133.
To
Consumer
Retain For
Future
Reference
U.S. Patent Numbers
6,295,980
5,318,007 - 5,228,618
5,201,307 - 4,595,825
WARNING
Warning: Improper installation, adjustment, alteration, service or maintenance can
cause property damage, personal injury or death. Installation and service must be
performed by a qualified installer, service agency or the gas supplier.
WHAT TO DO IF YOU SMELL GAS
•
•
•
Do not try to light any appliance.
For Your
Safety
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone.
Follow the gas supplier's instructions.
•
If you cannot reach your gas supplier, call the fire department.
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or other appliances.
Pentair Pool Products, Inc.
1620 Hawkins Ave., Sanford, NC 27330 • (919) 774-4151
10951 W. Los Angeles Ave., Moorpark, CA 93021 • (805) 523-2400
Rev. G 1-22-04
P/N 471048
Download from Www.Somanuals.com. All Manuals Search And Download.
3
Introduction
MiniMax® Plus and PowerMax™*
Pool and Spa Heaters
Congratulations on your purchase of a MiniMax Plus high performance heating system. Proper installation and
service of your new heating system and correct chemical maintenance of the water will ensure years of enjoyment.
The MiniMax Plus is a compact, lightweight and efficient gas fired high performance pool and spa heater that can be
directly connected to schedule 40 PVC pipe and has a built-in top. The MiniMax Plus, also comes equipped with
PurexTriton’s nine function indicator lights (electronic ignition only) which show, at a glance, the proper functioning
of the heater. All electronic ignition MiniMax Plus heaters are designed with an intermittent ignition device (IID)
which eliminates the need for a standing pilot. The electronic ignition MiniMax Plus requires is an external power
source (120 VAC or 240 VAC) 50/60 Hz to operate. The millivolt MiniMax Plus has a self sustaining pilot and
requires NO external power source.
All MiniMax and PowerMax pool and spa heaters are year 2000 compliant.
*Unless noted otherwise, any references to the MiniMax Plus include the PowerMax (Induced Draft)
models. The wiring and venting of the PowerMax is covered in an appendix to this manual.
IMPORTANT NOTICES
...For the installer and operator of the MiniMax Plus pool and spa heater. The manufacturer’s warranty may be void
if, for any reason, the heater is improperly installed and/or operated. Be sure to follow the instructions set forth in this
manual. If you need any more information, or if you have any questions regarding to this pool heater, please contact
Pentair Pool Products, Inc. at (800) 831-7133.
These heaters are designed for the heating of swimming pools and spas, and should never be employed for use as
space heating boilers, general purpose water heaters, in non-stationary installations, or for the heating of salt water.
CAUTION
OPERATING THIS HEATER CONTINUOUSLY AT WATER TEMPERATURE BELOW 68° F. WILL CAUSE
HARMFUL CONDENSATION AND WILL DAMAGE THE HEATER AND WILL VOID THE WARRANTY.
Do not use the heater to protect pools or spas from freezing if the final maintenance temperature desired is
below 68° F. as this will cause condensation related problems.
CODE REQUIREMENTS
The installation must conform with local codes or in the absence of local codes with the latest National Fuel Gas
Code, ANSI Z223.1, and the latest edition of the National Electrical Code, NFPA 70.
Installation in Canada to be made in accordance with the latest CAN/CGA-B149.1 or .2 and CSA C22.1 Canadian
Electric Code, part 1.
Rev. G 1-22-04
P/N 471048
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation (contd.)
4
This instruction manual provides operating
instructions, installation and service information for
the MiniMax Plus high performance heater. The
information in this manual applies to the MiniMax
Plus 150, 195, 200, 250, 300, 350, and 400 natural
gas and propane (LP) models.
WARRANTY INFORMATION
The MiniMax Plus pool heater is sold with a limited
factory warranty. Specific details are described on
the back cover of this manual and a copy of the
warranty and warranty registration card are
included with the product. Return the warranty
registration card after filling in the serial number
from the rating plate inside the heater.
It is very important that the owner/installer read and
understand the section covering installation
instructions, and recognize the local and state codes
before installing the MiniMax Plus. History and
experience has shown that most heater damage is
caused by improper installation practices.
Pentair Pool Products’ high standards of excellence
include a policy of continuous product improvement
resulting in your state-of-the-art heater. We reserve
the right to make improvements which change the
specifications of the heater without incurring an
obligation to update the current heater equipment.
Operation
SAFETY RULES
4. Before entering the spa or hot tub, the user
should check the water temperature with an
accurate thermometer. Spa or hot tub
1. Spa or hot tub water temperatures should never
exceed 104° F (40° C). A temperature of 100° F
(38° C) is considered safe for a healthy adult.
Special caution is suggested for young children.
thermostats may err in regulating water
temperatures by as much as 4° F (2.2° C).
2. Drinking of alcoholic beverages before or during
spa or hot tub use can cause drowsiness which
could lead to unconsciousness and subsequently
result in drowning.
5. Persons with a medical history of heart disease,
circulatory problems, diabetes or blood pressure
problems should obtain their physician's advice
before using spas or hot tubs.
3. Pregnant women beware! Soaking in water
above 102° F (39° C) can cause fetal damage
during the first three months of pregnancy
(resulting in the birth of a brain-damaged or
deformed child). Pregnant women should stick
to the 100° F (38° C) maximum rule.
6. Persons taking medication which induce
drowsiness, such as tranquilizers, antihistamines
or anticoagulants should not use spas or hot
tubs.
WARNING
Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the
appliance. Do not use this heater if any part has been under water. Immediately call a qualified service
technician to inspect the heater and to replace any part of control system and gas control which has been
under water.
P/N 471048
Rev. G 1-22-04
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation (contd.)
5
MINIMAX PLUS ELECTRONIC IGNITION LIGHTING/OPERATION - NATURAL GAS
FOR YOUR SAFETY: READ BEFORE LIGHTING
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing personal injury, loss of life
and property damage.
Do not attempt to light the heater if you suspect a natural gas leak. Lighting the heater can result in a fire or
explosion which can cause personal injury, death, and property damage.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will
not push in or turn by hand, don't try to repair it.
Call a qualified service technician. Forced or
attempted repair may result in a fire or explosion.
D. Do not use this heater if any part has been under
water. Immediately call a qualified service
technician to inspect the heater and to replace
any part of the control system and any gas
control which has been under water.
A. This heater is equipped with an ignition device
which automatically lights the pilot. Do not try
to light the pilot by hand.
B. BEFORE OPERATING smell all around the
heater area for gas. Be sure to smell next to
the floor because some gas is heavier than air
and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
-
-
Do not try to light any heater.
Do not touch any electrical switch; do not use
any phone in your building.
E. The MiniMax Plus incorporates (9) nine
indicator lights to aid you in the operation of the
heater, and to assist in diagnosing a failure in the
heater’s function.
-
-
Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions.
If you cannot reach your gas supplier, call the
Fire Department.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Set the thermostat to the lowest setting.
3. Turn off electric power to the heater.
4. This heater is equipped with an ignition device
which automatically lights the pilot. Do not try
to light the pilot by hand.
9. Replace the control access door.
10. Turn on the electrical power to the heater.
11. Set the thermostat to the desired setting.
12. If the heater will not operate, follow the instruc-
tions "To Turn Off Gas To Heater" and call your
service technician or gas supplier.
5. Remove the control access door.
6. Push in gas control knob slightly and turn clock-
wise
to “OFF”.
Gas
Inlet
7. Wait five (5) minutes to clear out any gas. If you
then smell gas, STOP! Follow "B" in the safety
information above. If you don't smell gas, go to the
next step.
ON
OFF
8. Turn knob on gas control counterclockwise
to “ON”; see Figure 1.
Figure 1.
Gas control knob shown in “ON” position.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the heater if
service is to be performed.
4. Push in gas control knob slightly and turn
clockwise to "OFF". Do not force.
5. Replace control access door.
3. Remove control access door.
Rev. G 1-22-04
P/N 471048
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation (contd.)
6
MINIMAX PLUS ELECTRONIC IGNITION LIGHTING/OPERATION - PROPANE
FOR YOUR SAFETY: READ BEFORE LIGHTING
NOTE
The MiniMax Plus propane models have special features for additional safety and protection.
Read the safety instructions for natural gas (page 5) before proceeding.
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing personal injury, loss of life
and property damage.
Since propane gas is heavier than air, escaping propane will accumulate and remain at ground level. Do not
attempt to light the heater. If you suspect a propane leak, lighting the heater can result in a fire or explosion
which can cause personal injury, death, and property damage.
WHAT TO DO IF YOU SMELL GAS
-
Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions.
If you cannot reach your gas supplier, call the
Fire Department.
-
-
-
Do not try to light matches or lighter.
Do not try to light any heater.
Do not touch any electrical switch; do not
use any phone in your building.
-
-
-
Shut off gas line at propane tank.
Do not tamper with the heater because it is
dangerous and voids all warranties.
Safety Lockout:
This MiniMax Plus Propane Heater is equipped with a 100% safety lockout feature. If the pilot does not
light within a maximum of 90 seconds, lockout will occur.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Set the thermostat to the lowest setting.
3. Turn off electric power to the heater.
4. This heater is equipped with an ignition device
which automatically lights the pilot. Do not try to
light the pilot by hand.
9. Replace the control access door.
10. Turn on the electrical power to the heater.
11. Set the thermostat to the desired setting.
12. If the heater will not operate, follow the instruc-
tions "To Turn Off Gas To Heater" and call your
service technician or gas supplier.
5. Remove the control access door.
6. Push in gas control knob slightly and turn clock-
wise
to “OFF”.
7. Wait five (5) minutes to clear out any gas. If you
then smell gas, STOP! Follow "B" in the safety
information on page 5. If you don't smell gas, go to
the next step.
Gas
Inlet
ON
8. Turn knob on gas control counterclockwise
to “ON”; see Figure 2.
OFF
Figure 2.
Gas control knob shown in “ON” position.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the heater if
service is to be performed.
4. Push in gas control knob slightly and turn
clockwise to "OFF". Do not force.
5. Replace control access door.
3. Remove control access door.
P/N 471048
Rev. G 1-22-04
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation (contd.)
7
MINIMAX PLUS MILLIVOLT LIGHTING/OPERATION-NATURAL GAS & PROPANE
FOR YOUR SAFETY: READ BEFORE LIGHTING
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing personal injury, loss of life
and property damage.
Since propane gas is heavier than air, escaping propane will accumulate and remain at ground level. Do not
attempt to light the heater. If you suspect a propane leak, lighting the heater can result in a fire or explosion
which can cause personal injury, death, and property damage.
-
If you cannot reach your gas supplier, call the Fire
Department.
A. This heater is equipped with a pilot which must be
lighted manually. When lighting the pilot, follow
these instructions exactly.
B. BEFORE LIGHTING smell all around the heater
area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will settle
on the floor.
C. Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not push in or
turn by hand, don't try to repair it. Call a qualified
service technician. Forced or attempted repair may
result in a fire or explosion.
D. Do not use this heater if any part has been under
water. Immediately call a qualified service
technician to inspect the heater and to replace any
part of the control system and any gas control which
has been under water.
WHAT TO DO IF YOU SMELL GAS
-
-
Do not try to light any heater.
Do not touch any electrical switch; do not use any
phone in your building.
-
Immediately call your gas supplier from a neighbor's
phone. Follow the gas supplier's instructions.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Set the thermostat to the lowest setting.
3. Turn off electric power to the heater.
7. Push the control knob all the way and hold in.
Immediately light the pilot with Presslite matchless
ignition system by pressing the red igniter button
(located at the panel next to the gas valve). Continue
to hold the control knob in for about one (1) minute
after the pilot is lit. Release knob and it will pop
back up. Pilot should remain lit. If it goes out, repeat
steps 4 through 7.
4. Push in gas control knob slightly and turn clock-
wise
to “OFF”.
•
If knob does not pop up when released, stop and
immediately call your service technician or gas
supplier.
Figure 5.
•
If the pilot will not stay lit
after several tries, turn the
gas control knob to “OFF”
and call your service
technician or gas supplier.
Figure 6.
Robertshaw Millivolt Gas Valve
Honeywell Millivolt Gas Valve
Figure 3.
Figure 4.
Gas control knobs shown in “OFF” position.
NOTE
Knob cannot be turned from “Pilot to “OFF”” unless
knob is pushed in slightly. DO NOT FORCE.
8. Turn knob on gas control
counterclockwise
“ON”.
to
5. Wait five (5) minutes to clear out any gas. If you then
smell gas, STOP! Follow "B" in the safety informa-
tion above. If you don't smell gas, go to the next step.
6. Push in gas control knob slightly and turn counter-
9. Replace the control access
door.
10. Set the thermostat to the
desired setting.
Pilot
clockwise
to “Pilot”.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the heater if service is
to be performed.
4. Push in gas control knob slightly and turn clockwise
to "OFF". Do not force.
5. Replace control access door.
3. Remove control access door.
Rev. G 1-22-04
P/N 471048
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation (contd.)
8
OPERATING (CONTROLS)
Dual Temperature Control System - (Electronic and Millivolt Models)
For convenience and economy all MiniMax Plus heaters
are equipped with two thermostats on the front of the heater
control panel; see Figure 7.
THERMOSTAT ADJUSTMENT
The knob with locking feature eliminates the need for
constant thermostat adjustments. Set the knob pointer to
the desired pool or spa temperature.
If further adjustment is needed, rotate the knob until the
desired temperature is obtained. This knob position
corresponding to your desired maximum pool or spa
temperature may now be preset (locked) by the knob
stopper which prevents the knob from being turned beyond
the maximum temperature you set.
Figure 7.
THERMOSTAT KNOB STOPPER
Each thermostat is equipped with a mechanical stop that
can be locked or unlocked with use of a screwdriver to
prevent temperatures in excess of that desired by the user;
see Figure 8.
Knob Stopper
Screw A
Figure 8.
The maximum setting can be adjusted by loosening the screw
"A" and turning the stopper dial to desired maximum setting.
Lock the setting by tightening the screw. The Mechanical
stop is under the knob. Ensure that the knob is stopping at the
correct position when the knob is rotated clockwise from a
lower temperature position. (See Thermostat Adjustment.)
POWER (THERMOSTAT SELECT) SWITCH
The Pool/Off/Spa switch allows the heater to be turned off
when heating is not desired.
1. “Pool” position - Maintains selected pool
temperature.
2. “Off” position - Heater will not come on regardless
of drop in pool or spa temperature.
NOTE
To eliminate error due to piping heat losses,
measure pool temperature with an accurate
thermometer directly at the pool or spa.
3. “Spa” position - This allows separate control of spa
water temperature.
INDICATOR LIGHT DESCRIPTION
The MiniMax Pool Heater provides nine status indicator lights, six can be seen from the front of the control panel which
help you understand the operation of the heater. If something should go wrong, the lights will aid in troubleshooting the
problem. Three additional lights can be seen after opening the control panel. These three lights give the service technician
advanced troubleshooting capability. All the LED lights are green with the exception of the red service LED.
POWER LIGHT (POWER)
AUXILIARY (AUX)
This light is on when it indicates the remote switch contacts
are closed. This allows you to observe if your remote switch
is properly closing the heater control circuit. When shipped
from the factory a jumper is installed to maintain closed
circuit in the absence of a remote switch.
The light is on at all times, in any switch position, indicating
24 VAC power is being supplied to the control circuit. If it
fails to light, no other light will be on. Possible causes are:
a) external power to the heater is disconnected, check
service panel circuit breaker or fuses; b) local circuit
breaker inside the transformer has tripped -- investigate
cause before resetting; c) transformer has failed.
PRESSURE (PRESS)
This light is on when Spa/Pool Selector switch is on,
indicates the circulation pump is running properly. If
pressure light fails to light, the pump may have lost its
prime or water flow may be restricted by an inadvertently
closed valve or clogged filter or pump basket. If you have
determined that there is no water flow restriction to the
heater, you should call a qualified serviceman.
THERMOSTAT (TSTAT)
This light is on when the thermostat contacts close, signaled
by the water temperature falling below the setpoint, calling
for the heater to fire to maintain the desired water
temperature.
P/N 471048
Rev. G 1-22-04
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation (contd.)
9
HEAT (HEAT)
SERVICE (SERVICE)
The heat light is on any time the thermostat has
signaled a call for heat which initializes the ignition
safety firing circuit -- the light comes on to indicate
successful firing of the main burners.
The service light is off during normal operation of
heater. The light only comes on if a problem with a
control has occurred or when the heater is first
firing. The problem must be investigated by the
serviceman prior to attempts to fire the heater again.
The diagrams that follow give examples of
troubleshooting a malfunctioning heater using the
assistance of the indicator lights.
TROUBLESHOOTING (CONTROLS)
Example of troubleshooting with the assistance of the indicator lights.
SYMBOL TABLE
SWITCH OR DEVICE
OPEN CIRCUIT
(BLOCK CURRENT)
SWITCH OR DEVICE
CLOSED CIRCUIT
(PASS CURRENT)
LED OFF
LED LIT
IGNITION MODULE
IND
GND
VAL
GAS VALVE
MV
TRANSFORMER
INCOMING
LINE VOLTAGE
CIRCUIT
BREAKER
HI TEMP
LIMIT SWITCHES
REMOTE
PRESS
TFUSE
MV
THERMOSTAT
RELAY
PWR
TSTAT
RMT
PRESS
HI TEMP
TFUSE
MV
HEAT
SRVE
POWER
THERM
CLOSE IF
NO MV
SERVICE
AUX
THERMOSTAT CIRCUIT BOARD
WATER AT SELECTED TEMPERATURE.... NORMAL OPERATION
PRESS
HEAT
FRONT PANEL LEDS
OR POOL/OFF/SPA THERMOSTAT SELECT SWITCH OFF.... NORMAL OPERATION
IGNITION MODULE
IND
GND
VAL
GAS VALVE
TRANSFORMER
INCOMING
LINE VOLTAGE
CIRCUIT
BREAKER
HI TEMP
LIMIT SWITCHES
REMOTE
PRESS
TFUSE
MV
MV
THERMOSTAT
RELAY
PWR
TSTAT
RMT
PRESS
HI TEMP
TFUSE
MV
HEAT
SRVE
THERM
AUX
POWER
CLOSE IF
NO MV
SERVICE
THERMOSTAT CIRCUIT BOARD
PRESS
HEAT
THERMOSTAT CALLING FOR HEAT - PUMP OFF(NO PRESSURE) BLOCKS FIRING
NORMAL OPERATION
FRONT PANEL LEDS
Rev. G 1-22-04
P/N 471048
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation (contd.)
10
TROUBLESHOOTING (CONTROLS) - Continued
SYMBOL TABLE
SWITCH OR DEVICE
OPEN CIRCUIT
(BLOCK CURRENT)
SWITCH OR DEVICE
CLOSED CIRCUIT
(PASS CURRENT)
LED OFF
LED LIT
IGNITION MODULE
IND
GND
VAL
GAS VALVE
MV
TRANSFORMER
INCOMING
LINE VOLTAGE
CIRCUIT
BREAKER
HI TEMP
LIMIT SWITCHES
REMOTE
PRESS
TFUSE
MV
THERMOSTAT
RELAY
RMT
PRESS
HEAT
PWR
TSTAT
HI TEMP
TFUSE
MV
SRVE
POWER
THERM
CLOSE IF
NO MV
SERVICE
AUX
THERMOSTAT CIRCUIT BOARD
HEATER FIRING - NORMAL OPERATION
PRESS
HEAT
FRONT PANEL LEDS
IGNITION MODULE
IND
GND
VAL
GAS VALVE
TRANSFORMER
INCOMING
LINE VOLTAGE
CIRCUIT
BREAKER
HI TEMP
LIMIT SWITCHES
REMOTE
PRESS
TFUSE
MV
MV
THERMOSTAT
RELAY
RMT
PWR
TSTAT
PRESS
HI TEMP
TFUSE
MV
HEAT
SRVE
THERM
AUX
POWER
CLOSE IF
NO MV
SERVICE
PRESS
HEAT
THERMOSTAT CIRCUIT BOARD
THERMOSTAT CALLING FOR HEAT - BLOWN THERMAL FUSE BLOCKS FIRING
NOTE: SERVICE LED LIT FLAGS PROBLEM, TFUSE LED OFF SHOWS PROBLEM
IS IN THERMAL FUSE CIRCUIT
FRONT PANEL LEDS
P/N 471048
Rev. G 1-22-04
Download from Www.Somanuals.com. All Manuals Search And Download.
11
Maintenance
MAINTENANCE INSTRUCTIONS
It is recommended that you check the following items at
least every six months and at the beginning of every
swimming season.
3. Keep the heater area clear and free from
combustibles and flammable liquids.
1. Examine the venting system. Make sure there are no
obstructions in the flow of combustion and ventila-
tion air.
2. Visually inspect the main burner and the pilot burner
flame. The normal color of the flame is blue. When
flame appears yellow, burners should be inspected
and cleaned; see Figure 10.
Relief Valve
In some installations, a
relief valve is required
on the MiniMax Plus.
Standard
Test the relief valve at
least once a year by
lifting the valve lever.
(A.S.M.E. version varies
slightly and has the relief
valve pre-installed at
factory.)
Blue Flame
3/8 to 1/2 in.
Insulated
Electrode
Figure 11.
A.S.M.E. Version
Figure 10.
Figure 9.
ENERGY SAVING TIPS
5. Set time clock to start circulation system no earlier
than daybreak. The swimming pool loses less heat at
this time.
1. If possible, keep pool or spa covered when not in
use. This will not only cut heating costs, but also
keep dirt and debris from settling in the pool and
conserve chemicals.
6. For pools that are only used on the weekends, it is
not necessary to leave the thermostat set at 78° F.
Lower the temperature to a range that can be
2. Reduce the pool thermostat setting to 78° F. or
lower. This is accepted as being the most healthy
temperature for swimming by the American Red
Cross.
achieved easily in one day. Generally, this would be
10° F. to 15° F., if pool heater is sized properly.
7. During the winter or while on vacation, turn the
heater off.
3. Use an accurate thermometer.
8. Set up a regular program of preventative
maintenance for the heater each new swimming
season. Check heat exchanger, controls, burners,
operation, etc.
4. When the proper maximum thermostat settings have
been determined, tighten the thermostat knob
stopper.
SPRING AND FALL OPERATION
will keep the pool and the surrounding ground warm
enough to bring the pool up to a comfortable swimming
temperature in a shorter period of time.
If the pool is being used occasionally, do not turn the heater
completely off. Set the thermostat down to 65° F. This
WINTER OPERATION
If the pool won't be used for a month or more, turn the
heater off at the main gas valve. For areas where there is
no danger of water freezing, water should circulate
through the heater all year long, even though you are not
heating your swimming pool. The MiniMax Plus should
not be operated out doors at temperatures below 0° F. for
propane and -20° F. for natural gas. Where freezing is
possible, it is necessary to drain the water from the
heater. This may be done by opening the drain valve
located at the inlet/outlet header (see Figure 11.) allow-
ing all water to drain out of the heater. It would be a
good practice to use compressed air to blow the water
out of the heat exchanger. (See additional notes under
Important Notices in Introduction on page 3.)
Rev. G 1-22-04
P/N 471048
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance (contd.)
12
RULE: 7.4 to 7.6 is a desirable pH range. It is essential
to maintain correct pH, see Table 2.
CHEMICAL BALANCE
POOL AND SPA WATER
If pH becomes too high (over alkaline), it
has these effects:
Your Pentair Pool Products pool heater was designed
specifically for your spa or pool and will give you many
years of trouble free service provided you keep your
water chemistry in proper condition.
1. Greatly lowers the ability of chlorine to destroy
bacteria and algae.
2. Water becomes cloudy.
Three major items that can cause problems with your
pool heater are improper pH, disinfectant residual, and
total alkalinity. These items, if not kept properly bal-
anced, can shorten the life of the heater and cause
permanent damage.
3. There is more danger of scale formation on the
plaster or in the heat exchanger.
4. Filter elements may become blocked.
If pH is too low (over acid) the following
conditions may occur:
CAUTION
Heat exchanger damage resulting from chemical
imbalance is not covered by the warranty.
1. Excessive eye burn or skin irritation.
2. Etching of the plaster.
3. Corrosion of metal fixtures in the filtration and
recirculation system, which may create brown, blue,
green, or sometimes almost black stains on the
plaster.
WHAT A DISINFECTANT DOES
Two pool guests you do not want are algae and bacteria.
To get rid of them and make pool water sanitary for
swimming - as well as to improve the water's taste, odor
and clarity - some sort of disinfectant must be used.
4. Corrosion of copper in the heater, which may cause
leaks.
Chlorine and bromine are universally approved by health
authorities and are accepted disinfecting agents for
bacteria control.
5. If you have a sand and gravel filter, the alum used as
a filter aid may dissolve and pass through the filter.
CAUTION: Do not test for pH when the chlorine
residual is 3.0 ppm or higher, or bromine residual
is 6.0 ppm or higher. See your local pool supply
store for help in properly balancing your water
chemistry.
WHAT IS A DISINFECTANT
RESIDUAL?
When you add chlorine or bromine to the pool water, a
portion of the disinfectant will be consumed in the
process of destroying bacteria, algae and other oxidiz-
able materials. The disinfectant remaining is called
chlorine residual or bromine residual. You can deter-
mine the disinfectant residual of your pool water with a
reliable test kit, available from your local pool supply
store.
RULE: Chemicals that are acid lower pH. Chemicals
that are alkaline raise pH.
pH Control Chart
Table 2.
7.2
7.4 7.6
7.8
8.0 8.2 8.4
Add Acid
6.8
7.0
Add Soda, Ash or
Marginal Ideal Marginal
You must maintain a disinfectant residual level adequate
enough to assure a continuous kill of bacteria or virus
introduced into pool water by swimmers, through the air,
from dust, rain or other sources.
Sodium Bicarbonate
ALKALINITY High - Low:
"Total alkalinity" is a measurement of the total amount
of alkaline chemicals in the water, and control pH to a
great degree. (It is not the same as pH which refers
merely to the relative alkalinity/acidity balance.) Your
pool water's total alkalinity should be 100 - 140 ppm to
permit easier pH control.
It is wise to test pool water regularly. Never allow
chlorine residual to drop below 0.6 ppm (parts per
million). The minimum level for effective chlorine or
bromine residual is 1.4 ppm.
pH - The term pH refers to the acid/alkaline balance of
water expressed on a numerical scale from 0 to 14. A test
kit for measuring pH balance of your pool water is avail-
able from your local pool supply store; see Table 1.
A total alkalinity test is simple to perform with a
reliable test kit. You will need to test about once a
week and make proper adjustments until alkalinity is
in the proper range. Then, test only once every month
or so to be sure it is being maintained. See your local
pool dealer for help in properly balancing the water
chemistry.
Table 1.
Strongly Acid
pH Chart
Neutral
Strongly Alkaline
0
1
2
3
4
5
6
7
8
9
10 11 12 13 14
Muriatic Acid has a pH of about 0. Pure water is 7
(neutral). Weak Lye solution have a pH of 13-14.
P/N 471048
Rev. G 1-22-04
Download from Www.Somanuals.com. All Manuals Search And Download.
13
Installation Instructions
SPECIFICATIONS
IMPORTANT NOTICE: These installation instructions are designed for use by qualified personnel
only, trained especially for installation of this type of heating equipment and related components. Some
states require installation and repair by licensed personnel. If this applies in your state, be sure your
contractor bears the appropriate license.
Outdoor installation - stackless
Model
150
"A" Dim
17 7/8 in.
20 7/8 in.
23 7/8 in.
26 7/8 in.
29 7/8 in.
"B" Dim
6½ in.
TM
HIGH PERFORMANCE HEATER
32
195/200
250
9½ in.
12½ in.
15½ in.
18½ in.
300
5-1/2
"B" DIM.
"A" DIM.
350
3
21 12
400
33 3/8 in. 22 3/8 in.
Table 3.
FRONT VIEW
SIDE VIEW
Outdoor installation - with vent kit
Model
150
195/200 20 7/8 in.
"A" Dim "B" Dim "C" Dim "D" Dim
"E" DIM.
"C"
DIM.
17 7/8 in.
6½ in.
9½ in.
7¾ in.
10 in.
10 in.
10¼ in.
13 in.
17 in.
39¾ in.
42¾ in.
42¾ in.
43¾ in.
47¾ in.
"D"
DIM
POWER
PRESSURE
HEAT
HI-LIMIT
POOL
TM
OFF
HIGH PERFORMANCE HEATER
HOT
COLD
HOT
COLD
SPA
POOL TEMPERATURE
POWER
SPA/AUXILIARY TEMPERATURE
250
300
350
400
23 7/8 in.
26 7/8 in.
29 7/8 in.
12½ in.
15½ in.
18½ in.
28"
"B" DIM.
"A" DIM.
5-1/2
33 3/8 in. 22 3/8 in.
51¾ in.
Table 4.
1
21
2
3
"E" DIM.
Indoor installation - stack (USA only)
Outdoor shelter installation (Canada)
Model "A" Dim "B" Dim "C" Dim "D" Dim "E" Dim
"C"
150
17 7/8 in.
6½ in.
9½ in.
13 in.
13 in.
13 in.
13 in.
13 in.
17 in.
52¾ in.
53 7/8 in.
53 7/8 in.
55 in.
6 in.
7 in.
7 in.
8 in.
9 in.
DIM.
"D"
DIM
195/200 20 7/8 in.
POWER
PRESSURE
HEAT
HI-LIMIT
250
300
350
400
23 7/8 in. 12½ in.
26 7/8 in. 15½ in.
29 7/8 in. 18½ in.
33 3/8 in. 22 3/8 in.
POOL
TM
OFF
HIGH PERFORMANCE HEATER
HOT
COLD
HOT
COLD
SPA
POOL TEMPERATURE
POWER
SPA/AUXILIARY TEMPERATURE
28
1
2
14
56 in.
7
8
10
5-1/2
"B" DIM.
"A" DIM.
60¾ in.
10 in.
GAS LINE
OPENING
1
21
2
3
Table 5.
Rev. G 1-22-04
P/N 471048
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation (contd.)
14
WATER CONNECTIONS
Reversible Inlet/Outlet Connection
The MiniMax Plus heater is factory assembled with
right side inlet/outlet water connections. The inlet/
outlet header can be reversed for left side water
connections without removing the heat exchanger.
TO
POOL
PUMP
FILTER
POOL
HEATER
MANUAL
BY-PASS
ISOLATION
VALVE
3
CHECK
1
VALVE
Reversing Water Connections
Disassembly
Tools needed:
ISOLATION
VALVE
CHECK
VALVE
2
1
2
3
Optional.
FROM
POOL
Required when installation is below water level.
Required when flow rates exceed 120 gpm.
Figure 12.
1/4 in Nut Driver
9/16 in. Socket and Wrench
1/2 in. & 9/16 in. Open Wrench
PLUMBING CONNECTIONS
The MiniMax Plus heater has the unique capability of
direct schedule 40 PVC plumbing connections. A
Quick-Flange has been included with the MiniMax
Plus to insure conformity with PurexTriton’s recom-
mended PVC plumbing procedure. Other plumbing
connections can be used. The instructions on page 13
show methods for successfully connecting plumbing to
the inlet/outlet header, with the Quick-Flange.
1. Remove the inspection plates.
2. Disconnect all wires from the high-limit
switches except the short jumper wire. The
exact order of the disconnection is not impor-
tant.
3. Disconnect the pressure switch wiring.
4. Remove the temperature sensing bulb from the
in/out header. Note: You may cut the wire
bundle ties.
5. Exchange the in/out header with the return
header. Replace the heat exchanger tube seals
with new seals provided in the Quick-Flange
Accessory Bag.
6. Install the temperature sensing bulb by passing
the wires through the hole provided on the left
side of the brace panel. Route wires through the
support bracket.
CAUTION
Before operating the heater on a new installation,
turn on the circulation pump and bleed all the air
from the filter using the air relief valve on top of the
filter. Water should flow freely through the heater.
Do not operate the heater unless water in the pool/
spa is at the proper level.
7. Reconnect all the high limit wires. Reconnect
the pressure switch wiring. Route the wires
through the same hole as the thermostat sensor
wires.
MANUAL BY-PASS
Where the flow rate exceeds the maximum 120
GPM, a manual bypass should be installed and
adjusted. After adjustments are made, the valve
8. Reinstall the inspection plates.
handle should be removed to avoid tampering.
PLUMBING
Model
150
Min.
20
Max. *
120
VALVES
195/200
250
20
120
When any equipment is located below the surface of
the pool or spa, valves should be placed in the
circulation piping system to isolate the equipment
from the pool or spa.
30
120
300
30
120
350
40
120
400
40
120
* Do not exceed the maximum recommended
flow rate for the connecting piping.
Check valves are recommended to prevent back
siphon.
Table 6.
CAUTION
Exercise care when installing chemical feeders so
as to not allow back siphoning of chemical into the
heater, filters or pump.
BELOW POOL INSTALLATION
If the heater is below water level, the pressure
switch must be adjusted. This adjustment must be
done by a qualified service technician.
P/N 471048
Rev. G 1-22-04
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation (contd.)
15
WATER CONNECTIONS
QUICK-FLANGE INSTALLATION INSTRUCTIONS
Each MiniMax Plus Quick-Flange Accessory Kit contains the following items:
One (1) Quick-Flange unit
Four (4) 3/8 Bolts
Two (2) Plastic sleeves
Two (2) 2 in. Rubber gaskets
Four (4) 3/8 in. Washers
FOR 1½ & 2 in. SCHEDULE 40 PVC PIPE
FOR 1½ & 2 in. COPPER PIPE
Pipe
Plastic Bushing
Figure 13.
Gasket/Sleeve
Figure 15.
Gasket
1. Insert plastic sleeves into the “Quick-Flange”
inlet/outlet openings.
2. Slip the 2 in. rubber gaskets over the plastic
sleeves.
NOTE
You “DO NOT” need the plastic bushings.
*
1. Insert pipe into the inlet/outlet openings of the
“Quick-Flange”
3. Bolt the “Quick-Flange” to the header.
NOTE
Tighten the bolts evenly! Do not over tighten!
2. Slip the rubber gaskets over the pipe, using the
supplied 2 in. rubber gasket for 2 in. copper pipe
or the 1½ in. rubber gasket (not supplied,
available from the factory) for the 1½ in. copper
pipe.
4. Use plumbers roll or medium grit sand paper and
clean the inlet/outlet openings of the “Quick-
Flange”. Use the same method to clean the 2 in.
PVC pipe. The sand paper will break up any
grease or contaminant that may not be cleaned
away with a primer.
3. Bolt the “Quick-Flange” to the header.
5. Use 711 PVC glue (or equivalent) and follow the
manufacturer’s recommendations. Apply to the
inlet opening of the “Quick-Flange”. Do the
same to the PVC pipe and quickly insert the
pipe into the “Quick-Flange” and twist the pipe
a 1/4 turn. Do the same to the other opening of
the “Quick-Flange”.
6. For 1½ in. PVC pipe installations, first glue a 1½
in. X 2 in. sch 40 PVC bushing (not supplied or
shown) to the end of the pipe prior to gluing to
the “Quick-Flange”.
Figure 14.
*
Rev. G 1-22-04
P/N 471048
Download from Www.Somanuals.com. All Manuals Search And Download.
16
Installation (contd.)
Table 7.
GAS CONNECTIONS
Pipe Sized For Length Of Run In Equivalent Feet
1/2 in.
3/4 in.
1 in.
1¼ in.
1½in.
2 in.
GAS LINE INSTALLATIONS
Nat LP Nat LP Nat LP Nat LP Nat LP Nat LP
Model
150
Before installing the gas line, be sure to
check which gas the heater has been
designed to burn. This is important
because different types of gas require
different gas pipe sizes. The rating plate
on the heater will indicate which gas the
heater is designed to burn. Table 7,
shows which size pipe is required for the
10' 40' 50' 150' 150' 600'
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
20' 30' 80' 125' 250' 450' 600'
195/200
250
10' 20' 50' 70' 150' 250' 500' 600'
-
-
-
10' 30' 50' 100' 200' 350' 400' 600'
300
10' 20' 30' 70' 125' 250' 250' 500' 500'
10' 20' 60' 100' 150' 200' 450' 400'
350
-
400
REGULATED MANIFOLD PRESSURE TEST
1. Attach the manometer to the heater jacket.
2. Shut off the main gas valve.
distance from the gas meter to the heater. The table
is for natural gas at a specific gravity of .65 and
propane at specific gravity of 1.5.
3. Remove 1/8 in. NPT plug on the outlet side of the
valve and screw in the fitting from the manometer kit.
4. Connect the manometer hose to the fitting.
5. Fire the heater.
6. The manometer must read 4 in. WC for natural gas,
11 in. WC for propane gas, while the heater is
operating.
7. For adjustment, remove the Regulator Adjustment
Cap and using a screwdriver turn the screw clock-
wise to increase - counterclockwise to decrease gas
When sizing gas lines, calculate three (3) additional
feet of straight pipe for every elbow used.
When installing the gas line, avoid getting dirt,
grease or other foreign material in the pipe as this
may cause damage to the gas valve, which may
result in heater failure.
The gas meter should be checked to make sure that
it will supply enough gas to the heater and any other
appliances that may be used on the same meter.
pressure.
Regulator Adjustment Cap
1/8" NPT Plug
(Inlet Press)
The gas line from the meter will usually be of a
larger size than the gas valve supplied with the
heater. Therefore a reduction of the connecting gas
pipe will be necessary. Make this reduction as close
to the heater as possible.
Figure 16.
ON
OFF
1/8" NPT Plug
(Manifold Press)
REGULATOR
ADJUSTMENT CAP
The heater and any other gas appliances must be
disconnected from the gas supply piping system
during any pressure testing on that system, (greater
that ½ PSIG).
Figure 17.
PILOT
HONEYWELL
1/2 P.S.I.
PRESS
TAP
PILOT
ADJ.
The heater and its gas connection must be leak
tested before placing the heater in operation. Do not
use flame to test the gas line. Use soapy water or
another nonflammable method.
CAUTION
The use of Flexible Connectors (FLEX) is NOT
recommended as they cause high gas pressure drops.
A manual main shut-off valve must be installed
externally to the heater.
MINIMAX PLUS GAS PRESSURE REQUIREMENTS*
Propane
Natural
Maximum inlet gas pressure 10 in. WC 14 in. WC
Minimum inlet gas pressure **5 in. WC 12 in. WC
Normal manifold pressure
** 6 WC for 400 model
*All Readings are taken with the heater fired. Any adjustments
made with heater off will give incorrect readings.
4 in. WC 11 in. WC
WARNING
Do not install the gas line union inside the heater
cabinet. This will void your warranty.
Table 8.
P/N 471048
Rev. G 1-22-04
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation (contd.)
17
VENTILATION
STACK TYPE OUTDOOR VENT KIT
Model
150
Vent Cap Product No. Vent Dia.
OUTDOOR INSTALLATION ONLY
OV15
OV20
OV25
OV30
OV35
OV40
460237
460222
460223
460224
460225
460226
6 in.
7 in.
7 in.
8 in.
9 in.
10 in.
(See additional instructions for outdoor Power-
Max units in PowerMax Appendix)
195/200
250
For outdoor installation with built in vent top, the heater
must be placed in a suitable area on a level, noncombus-
tible surface. Do not install the heater under an overhang
with clearances less than 3 feet from the top of the
heater. The area under an overhang must be open on
three sides.
300
350
400
Table 9.
Outdoor Stack
Top Cover
IMPORTANT!
In an outdoor installation it is important to protect
your heater from water damage. Ensure water is
diverted from overhanging eves with a proper gutter/
drainage system. The heater must be set on a level
foundation for proper rain drainage.
Flue Adaptor
Inner Panel
Maintain minimum clearances as indicated below. Install
a minimum of 4 feet below, and 4 feet horizontally from
any opening to a building.
Flue Collector
The heater should not be installed closer than 6 inches to
any fences, walls or shrubs at any side or back, nor
closer than 18 inches at the plumbing side. A minimum
clearance of 24 inches must be maintained at the front of
the heater.
Figure 19.
Figure 20.
6"
6"
OUTDOOR VENT CAP INSTALLATION
24"
The MiniMax Plus heater is shipped standard as an
outdoor stackless unit. To install the outdoor vent kit:
1. Take out the louvered outer top after first
removing all 1/4 in. sheet metal screws attaching
it along its perimeter to the cabinet. Set it aside.
18"
2. Place the flue adaptor over the flue collector
opening. Temporarily, put the top cover, from the
kit, on with the label to the front of the heater.
Center the flue adaptor evenly inside the top cover
flue stack opening. Remove the top cover and
secure the centered flue adaptor to the inner panel
with the provided #8 x 1/2 in. drill qwik screws.
3. Place the top cover, with the hole for the stack, on
the heater cabinet.
4. Install the vent stack through the hole in the top
cover, over the flue adaptor top ring.
5. Using a 3/32 in. drill bit, position the “L” bracket
to hold the top cover and outdoor stack. Drill the
pilot holes through the “L” bracket holes to accept
the screws.
6. Secure the vent stack and the inner top with the #8
x 1/4 in. sheet metal screws through the “L”
brackets.
Figure 18.
IMPORTANT!
When locating the heater, consider that high
winds can roll over or deflect off adjacent
buildings and walls. Normally, placing the
heater at least three feet from any wall will
minimize downdraft.
Unusually high prevailing wind conditions and
downdrafts may require the use of a stack type
outdoor vent kit (available at additional cost).
NOTE
This unit shall not be operated outdoors at
temperatures below 0o F. for propane and -20o F. for
natural gas.
Rev. G 1-22-04
P/N 471048
Download from Www.Somanuals.com. All Manuals Search And Download.
18
Installation (contd.)
INDOOR INSTALLATION (USA ONLY)
OUTDOOR SHELTER INSTALLATION (CANADA)
(See additional instructions for outdoor
PowerMax units in PowerMax Appendix)
All products of combustion and vent gases must
be completely removed to the outside atmosphere
through a vent pipe which is connected to the
draft hood. A vent pipe extension of the same
size must be connected to the draft hood and
extended at least 2 feet higher than highest point
of the roof within a 10 foot horizontal radius, and
at least 3 ft. higher than the point at which it
passes through the roof, or as permitted by local
code; see Figures 21 and 22. The vent should
terminate with an approved vent cap (weather
cap) for protection against rain or blockage by
snow. Double-wall vent pipe and an approved
roof jack shall be employed through the roof
penetration. The use of double-walled type B vent
pipe is recommended.
Installations in basements, garages, or
underground structures where flammable liquids
may be stored must have the heater elevated 18
inches from the floor using a non-combustible
base. The following minimum clearances from
combustible materials must be provided.
Side
18 in.
6 in.
Front
Back
Top
Water Connection
Remaining
24 in.
6 in.
Ceiling Clearance
36 in.*
*To ceiling or roof.
Vent terminated at
least 24 in. above
any object within 10 ft.
The draft hood must be installed so as to be in the
same atmospheric pressure zone as the
combustion air inlet to the pool heater. The
certified (factory) draft hood must not be
modified in any way and must be employed in
every indoor installation (with the exception of
the PowerMax units).
10 ft.
Vent
Cap
Ridge
2 ft. min.
3 ft. min.
Roof
Jack
Chimney
The heater must be located as close as practical to
a chimney or gas vent. The heater should be
installed at least 5 feet away from the pool or spa.
Figure 21.
Vent Cap and
Riser Furnished
by Installer
The heater must be placed in a suitable room on a
non-combustible floor or on a non-combustible
base and in an area where leakage from heat
exchanger or water connections will not result in
damage to the area adjacent to the heater or the
structure. When such locations cannot be
avoided, it is recommended that a suitable drain
pan with adequate drainage, be installed under the
heater. The pan must not restrict air flow.
* Rise
Air Supply
Ventilation
Air Supply
Gas Combustion
* 1” Rise Per Foot
Recommended
Figure 22.
P/N 471048
Rev. G 1-22-04
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation (contd.)
19
NOTE
The heater requires two uninterrupted air supply
openings; one for ventilation and one to supply
oxygen for proper gas combustion. The air supply
openings should be sized according to Tables 10.
and 11.
b) Construct a non-combustible base from masonry
blocks as illustrated, see Figure 23.
Air supply requirements below apply to all
MiniMax heaters, including PowerMax versions.
BASE FOR USE ON
COMBUSTIBLE FLOORS
T
O
H
All Air From Inside
TM
ER
AT
HE
CE
AN
M
OR
RF
PE
GH
HI
Air for Combustion
Sq. In.
Air Ventilation
Sq. In.
Model
IT
IM
-L
HI
AT
HE
RE
SU
ES
PR
L
OLD
RE
ER
P
OO
C
W
PO
TU
FF
RA
PE
O
A
H
OT
LIA
T
EM
SP
RY
U
XI
E
R
A
/
A
W
P
PO
S
6" Min.
LD
RE
CO
TU
RA
PE
T
HO
T
EM
OL
PO
150
195/200
250
150
200
250
300
350
400
150
200
250
300
350
400
6" Min.
SHEET METAL
BLOCKS
300
HOLLOW MASONARY BLOCKS, NOT LESS THAN 4" THICK
(LAID WITH ENDS UNSEALED AND JOINTS MATCHED
FOR AIR CIRCULATION). COVER BLOCKS WITH
24 GA. (MIN.) GALVANIZED SHEET METAL.
350
400
Figure 23.
Table 10.
All Air From Outside
Air for Combustion
Sq. In.
Air Ventilation
Sq. In.
Model
150
195/200
250
37
37
50
50
CAUTION
63
63
Chemicals should not be stored near the heater
installation. Combustion air can be contaminated by
corrosive chemical fumes which can void the warranty.
300
77
77
350
90
90
400
100
100
Table 11.
INSTALLATION ON FLOORS CONSTRUCTED
OF COMBUSTIBLE MATERIALS
The heater may be placed on a “combustible floor”
using either of the two methods listed below:
STACK TYPE INDOOR DRAFT HOOD KIT
The proper draft hood and adapter must be installed on
the heater as shown below and on page 20:
a) Use Listed Factory Non-combustible Base Kit
for use on combustible floors.
Model Non-Combustible Base Kit
Model Draft Hood Product No. Vent Dia.
150
195/200
250
471389
471390
471391
471392
471393
471394
150
195/200
250
DH15
DH20
DH25
DH30
DH35
DH40
460227
460228
460230
460231
460233
460234
6 in.
7 in.
7 in.
8 in.
9 in.
10 in.
300
300
350
350
400
400
Table 13.
Table 12.
Rev. G 1-22-04
P/N 471048
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation (contd.)
20
Draft Hood
Top Cover
INDOOR DRAFT HOOD INSTALLATION
1. Take out the louvered outer top piece after first
removing the sheet metal screws, attaching it to
the cabinet.
Adaptor
Screw
(2 PLC's)
2. Install the adaptor (vent kit).
3. Install the top cover (vent kit).
4. Install the draft hood (vent kit).
Use the provided screws to secure the vent assembly.
HEATER
Figure 24.
Transformer Wiring Instruction
ELECTRICAL, IID ELECTRONIC UNITS
Electrical Rating
60 Hz
115 V.A.C. or 230 V.A.C.
50/60 Hz 208 V.A.C. or 240 V.A.C.
NOTE
If any of the original wiring supplied with this
heater must be replaced, installer must supply
(No. 18 AWG 105° C. U.L. approved AWM low
energy stranded) copper wire or it's equivalent.
In Canada: wires must be CSA approved.
WARNING
The heater must be electrically grounded and
bonded in accordance with local codes or, in the
absence of local codes, with the latest national
electrical codes ANSI/NFPA No. 70.
In Canada: CSA standard C22.1 Canada Electrical
Code Part 1 and/or local codes.
Always use crimp type connectors when connecting
two wires.
This heater is equipped with a reversible junction box
to allow line voltage to be wired from either side.
Figure 26.
Figure 25.
P/N 471048
Rev. G 1-22-04
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation (contd.)
21
MiniMax Plus Electronic Ignition Wiring Diagram
PLUG
PLUG
4
3
2
1
3
2
1
6
T F U S E
H L M T
5
4
3
2
1
2
P R E S S
1
Rev. G 1-22-04
P/N 471048
Download from Www.Somanuals.com. All Manuals Search And Download.
22
Installation (contd.)
PILOT
GENERATOR
MINIMAX WIRING DIAGRAM
(MILLIVOLT) DUAL THERM
(HONEYWELL ELECTRONIC)
TH/PP
WHT
RED
TH
PP
IF ORIGINAL FACTORY WIRING MUST BE REPLACED,
INSTALLER MUST SUPPLY UL OR CSA (IF CANADA)
APPROVED WIRE, 18 GAUGE, 600V, 105 C˚ TEMPERATURE RATING.
THERMAL FUSE WIRING MUST BE REPLACED WITH
UL OR CSA (IF CANADA) APPROVED WIRE,
SAFETY
PRESS
SWITCH
GAS VALVE
WHT
HI-LIMIT
SHUT-OFF
WHT
WHT
WHT
18 GAUGE, 600V, 125 C˚ TEMPERATURE RATING.
INTERCONNECTING WIRING TO APPLIANCE MUST
CONFORM TO THE NATIONAL ELECTRICAL
THERMAL
CUT-OFF
ORN
CODE OR SUPERCEDING LOCAL (WIRING) CODES.
WHT
WHT
POT 1
POT 2
THERMOSTAT BOARD
POOL
SPA
MiniMax Plus Millivolt Wiring Diagram
After 1-15-01
OFF
SENSOR
Figure 27.
REMOTE SWITCH DUAL THERM IID ONLY
JUMPER REQUIRED IF NO 2 WIRE REMOTE SWITCH
24 VAC
PRESS HILMT TFUSE
VALVE
IGNITION MOD
3 Wire Remote
OUT
RETURN
THERMOSTAT CIRCUIT BOARD
SPA COM POOL
TPROBE
REMOTE POOL/OFF/SPA
THERMOSTAT SELECT SWITCH
FRONT PANEL
POOL/
OFF/SPA
THERMOSTAT SELECT SWITCH
Figure 28.
JUMPER REQUIRED IF NO 2 WIRE REMOTE SWITCH
24 VAC PRESS HILMT TFUSE
RETURN
VALVE
IGNITION MOD
OUT
2 Wire Remote
THERMOSTAT CIRCUIT BOARD
SPA COM POOL
TPROBE
FRONT PANEL
POOL/OFF/SPA
THERMOSTAT SELECT SWITCH
Figure 29.
NOTE: When connecting a remote control to the MiniMax Plus, you must install the low voltage
thermostat wires in separate conduit from ANY line voltage wires. Failure to follow these
instructions will cause the thermostat relay to react erratically..
P/N 471048
Rev. G 1-22-04
Download from Www.Somanuals.com. All Manuals Search And Download.
23
Troubleshooting - General
Possible Cause
Remedy
Heater will not come on
Automatic ignition system fails
Check if electrical connections are
correct and securely fastened –
If YES, call serviceperson.
Pump not running
Place pump in operation
Check for leaks
Pump air locked
Filter dirty
Clean filter
Pump strainer clogged
Defective wiring or connection
Defective pressure switch
Defective gas controls
On-Off switch in "OFF" position
Clean strainer
Repair or replace wires
Replace switch
Call serviceperson
Turn switch to "ON"
Heater Short Cycling (Rapid On and Off Operation)
Insufficient water flow
Clean filter and pump strainer
Defective wiring
Repair or replace wiring
Call serviceperson
Call serviceperson
Defective flow valve or out of adjustment
Defective hi-limit and/or thermostat
Heater Makes Knocking Noises,
Make sure all valves on system are open
Heater operating after pump has shut off
Heater exchanger scaled
Shut off gas supply and call serviceperson
Shut off gas supply and call serviceperson
CAUTION
Please consult the latest edition of the “MiniMax Plus Service Manual” for complete service and repair
instructions. Repairs should only be attempted by properly trained service personnel.
Rev. G 1-22-04
P/N 471048
Download from Www.Somanuals.com. All Manuals Search And Download.
24
MINIMAX PLUS HEATER - ALL MODELS
39
INNER TOPS
Model No. Part No.
15
470024
470025
470026
470027
470028
470029
200
250
300
350
400
38
5
37
4
3
2
1a
25
36
21
35
6
1
33
7
32
31
34
27
28
22
23
29
26
9
30
41
13
12
42
10
14
15
24
44
40
20
16
17
18
19
11
8
P/N 471048
Rev. G 1-22-04
Download from Www.Somanuals.com. All Manuals Search And Download.
25
MiniMax Plus (Only) Parts List
ITEM DESCRIPTION
Vent kit assy. (indoor)
QTY
1
150
195/200
250
300
350
400
1
460227 460228 460230 460231 460233 460234
460237 460222 460223 460224 460225 460226
070994 070994 070994 070994 070994 070994
074216 074216 074216 074216 074216 074216
073739 073739 073739 073739 073739 073739
070416 070416 070416 070416 070416 070416
072180 072180 072180 072180 072180 072180
070951 070951 070951 070951 070951 070951
471360 471360 471360 471360 471360 471360
470179 470179 470179 470179 470179 470179
073584 073584 073584 073584 073584 073584
073585 073585 073585 073585 073585 073585
470122 470122 470122 470122 470122 470122
470184 470184 470184 470184 470184 470184
470186 470186 470186 470186 470186 470186
470295 470296 470297 470298 470299 470187
470987 470988 470989 470990 470991 470992
471020 471021 471022 471023 471024 471025
075468 075604 075488 075605 075606 075490
070256 075525 070257 075526 075527 070258
073998 073998 073998 073998 073998 073998
073999 073999 073999 073999 073999 073999
075457 075457 075457 075457 075457 075457
075458 075458 075458 075458 075458 075458
075191 075191 075192 075192 075193 075193
076084 076084 076085 076085 076086 076086
073752 075499 073751 075500 075501 073750
073906 075508 073905 075509 075510 073904
075493 075496 075494 075497 075498 075495
075502 075505 075503 075506 075507 075504
1a
2
Vent kit assy. (outdoor)
1
Return header
1
3
Bracket washer
2
4
Bolt HH 3/8" x 2"
4
5
Bolt 3/8" - 16 x 1 1/2"
4
6
Washer 3/8" ID 1" OD
4
7
Tube seal gasket
18
1
8
Transformer - w/circuit breaker - dual voltage
ElectronicThermostat circuit board - IID Models
Module natural gas
9
1
1
10
Module propane gas
1
11
12
13
Junction Box (IID Units)
1
Thermostat knob
2
Switch rocker (single pole & double throw)
Control panel assy. (complete) - IID Nat
Control panel assy. (complete) - IID Pro
Control panel assy. (complete) - Millivolt
Door - IID or Millivolt
1
1
14
1
1
15
16
1
Manifold burner
1
Gas valve natural - IID
1
Gas valve propane- IID
1
17
18
19
Gas valve natural - Millivolt
Gas valve propane - Millivolt
Pilot tube - IID
1
1
1
Pilot tube - Millivolt
Burner tray assy. natural (complete) - IID
Burner tray assy. propane (complete) - IID
Burner tray assy. natural (complete) - Millivolt
Burner tray assy. propane (complete) - Millivolt
1
1
1
1
2 EA.
3 EA.
4 EA.
5 EA.
6 EA.
7 EA.
20
20a
21
22
23
24
25
26
Burner
070230 070230 070230 070230 070230 070230
470550 470550 470550 470550 470550 470550
470190 470190 470190 470190 470190 470190
073858 075586 073857 075587 075588 073856
072134 072134 072134 072134 072134 072134
075459 075459 075459 075459 075459 075459
072138 072138 072138 072138 072138 072138
471678 471678 471678 471678 471678 471678
471424 471424 471424 471424 471424 471424
073989 073989 073989 073989 073989 073989
074015 074015 074015 074015 074015 074015
075492 075492 075492 075492 075492 075492
075284 075284 075284 075284 075284 075284
Burner with Pilot Bracket
Pressure switch
1
1
1
1
1
1
2
1
1
4
2
1
Combustion chamber assy. (complete)
Valve drain 3/4"
Presslite igniter assy. (Millivolt Units only)
Valve relief 3/4" 50# - ASME or Local Code
Potentiometer (Millivolt Units only)
Flow valve assy., Standard (complete)
Flow valve assy., ASME (complete)
Flow valve gasket
27
28
29
30
Bolt 3/8" - 16 x 2 1/2
Quick flange Kit
Rev. G 1-22-04
P/N 471048
Download from Www.Somanuals.com. All Manuals Search And Download.
26
MiniMax Plus (Only) Parts List, contd.
ITEM DESCRIPTION
QTY
150
195/200
250
300
350
400
31
Bushing in/out Lexan
2
2
2
2
1
1
1
070544 070544 070544 070544 070544 070544
071895 071895 071895 071895 071895 071895
070229 070229 070229 070229 070229 070229
071017 071017 071017 071017 071017 071017
070985 070985 070985 070985 070985 070985
074452 075628 074451 075629 075630 074074
470364 470365 470366 470367 470368 470369
Sleeve, rubber in/out 2"
Sleeve, rubber in/out 1½"
Safety Shutoff
32
33
34
Main header (in/out)
Heat exchanger (without heads)
Heat exchanger (with heads)
35
8 ea.
8 ea.
8 ea.
8 ea.
16 ea.
16 ea.
070277 075559 070276 075560 070277 070278
073810 073810 073810 073810 073810 073810
073864 075622 073863 075623 075624 073862
470471 470472 470473 470474 470475 470476
075783 075784 075785 075786 075787 075788
471677 471677 471677 471677 471677 471677
073789 073789 073789 073789 073789 073789
073790 073790 073790 073790 073790 073790
470180 470180 470180 470180 470180 470180
36
37
Baffle
Baffle hold down (2) baffles on 400
1
1
1
1
1
38
39
40
41
42
43
44
Flue collector
Outdoor Top assy.
Lightback Shield (Propane Gas units only)
Electronic Thermostat (Millivolt models)
Panel (return)
Panel (in/out)
Thermistor (probe) - (IID models)
1
* Not Shown
*
*
*
*
*
*
*
*
*
*
*
*
Plastic mounting bracket
Wire Kit - Harness IID (complete)
Clips for wire harness
Wire Kit - Millivolt
070715 070715 070715 070715 070715 070715
470965 470965 470965 470965 470965 470965
471277 471277 471277 471277 471277 471277
075511 075511 075511 075511 075511 075511
071703 071703 071703 071703 071703 071703
071698 071698 071698 071698 071698 071698
071716 071716 071716 071716 071716 071716
071659 071659 071659 071659 071659 071659
075692 075692 075692 075692 075692 075692
070551 070551 070551 070551 070551 070551
470414 470414 470414 470414 470414 470414
073725 073725 073725 073725 073725 073725
Screw 8 x 1/4" HH
Screw 8 x 1/2" HH
Screw 6 x 1/4"
Screw 10 -32 x 1/4"
Screw 10-32 x 3/16
Bushing 1/2"
Therm knob stopper
Bolt 5/16" - 18 x 3/4'
2
2
3 ea.
N or P
4 ea.
N or P
5 ea.
N or P
6 ea.
N or P
7 ea.
N or P
8 ea.
N or P
Orifice main burner natural
Orifice main burner propane
Pilot - natural - IID
073727 073727 073727 073727 073727 073727
073728 073728 073728 073728 073728 073728
471204 471204 471204 471204 471204 471204
471205 471205 471205 471205 471205 471205
471292 471292 471292 471292 471292 471292
471291 471291 471291 471291 471291 471291
071515 071515 071515 071515 071515 071515
075173 075173 075173 075173 075173 075173
471740 471740 471740 471740 471740 471740
470178 470178 470178 470178 470178 470178
471293 471293 471293 471293 471293 471293
471328 471328 471328 471328 471328 471328
470181 470181 470181 470181 470181 470181
070715 070715 070715 070715 070715 070715
074540 074540 074540 074540 074540 074540
471271 471271 471271 471271 471271 471271
072253 072253 072253 072253 072253 072253
071240 071240 071240 071240 071240 071240
*
*
*
*
*
*
*
*
*
*
*
*
*
1
1
1
1
1
1
1
1
1
1
2
Pilot - propane - IID
Pilot - natural - millivolt
Pilot - propane - millivolt
Pilot - generator
Thermal cutoff - fusible link
Thermistor (probe) complete (Millivolt models)
Power element (flow-valve)
Pilot rainshield
Pilot electrode (only)
Stem, thermostat control (IID models)
Clips for transformer
*
*
*
*
*
"L" brackets
3
Bracket adapter Q379 pilot, MV
Jumper
Door latch
P/N 471048
Rev. G 1-22-04
Download from Www.Somanuals.com. All Manuals Search And Download.
PowerMax™ Pool & Spa Heater
OPERATION & INSTALLATION MANUAL
(APPENDIX)
INSTALLER: AFFIX THESE INSTRUCTIONS
TO OR ADJACENT TO POOL & SPA HEATER
Pentair Pool Products, Inc.
1620 Hawkins Ave., Sanford, NC 27330 • (919) 774-4151
10951 W. Los Angeles Ave., Moorpark, CA 93021 • (805) 523-2400
A-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Rev. G 1-22-04
P/N 471048
PowerMax™
Pool and Spa Heater
INTRODUCTION
This manual provides information for the proper installation, operation and
maintenance of the PowerMax pool and spa heater. Please read these installation and
operation instructions thoroughly before attempting installation or operation of your
pool and spa heater.
GENERAL SPECIFICATION
...For the installer and operator of the PowerMax pool and spa heater. The
manufacturer’s warranty may be void if, for any reason, the heater is improperly
installed and/or operated. Be sure to follow the instructions set forth in this manual.
CODE REQUIREMENTS
The installation must conform with local codes or in the absence of local codes with the
latest national fuel Gas Code, ANSI Z223.1.
Installation in Canada to be made in accordance with the latest CAN/CGA-B149.1 OR .2
and CSA C22.1 Canadian Electric Code part 1.
The PowerMax Induced Draft Pool and Spa Heater is a fan assisted balanced flue gas
combination, the field installation kit is designed for application to the PurexTriton
Pool and Spa Heater Electronic Ignition Models 150 to 400. The PowerMax is
approved for both indoor and outdoor installation using either natural gas or propane.
The unit operates in both vertical and horizontal reduced vent pipe locations, in both
the new and existing installations, and for applications such as through the (side) wall
venting.
MODEL NO.
INPUT
MBH
MINIMUM
DISCHARGE DIA
(Inches)
150
200
250
300
350
400
150
200
250
300
350
400
3
3
4
4
4
4
Table 1.
A-2
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 471048
Rev. G 1-22-04
MOUNTING ASSEMBLY
Follow these instructions if the PowerMax
venting system was purchased as an assembly
kit.
1. Remove the vent kit assembly (indoor).
2. Mount the plenum assembly on the flue collector
top using the screw provided.
3. Connect the wire harness to the heater control box.
Follow the instructions on page 5.
4. Mount the new top on the top of the heater. Using
a #28 drill bit to drill the four holes on the right
side of the heater for the mounting screws. The
front and back side of the top will snap into the
heater with no screws.
Figure 1.
DESCRIPTION OF SYSTEM OPERATION
SYSTEM OPERATION:
1. Set the thermostat to the lowest setting.
2. Push the power switch off. The electric power supply requirement is:
• 115 volts 60 Hz, 1 Ph, 1.5 Amp
3. Remove the door.
4. Push in the gas control knob slightly and turn clockwise
to “OFF”.
5. Wait (5) minutes to clear out any gas. If you then smell gas STOP. Follow the safety information.
If you don’t smell gas, go to the next step.
6. Turn the knob on the gas control counterclockwise
7. Replace the door.
to “ON”.
8. Make sure the pump is running and is primed.
9. Push the power switch on.
10. Set the thermostat to the desired setting.
• a. Fan motor starts, draft proving switch closes.
• b. Ignition module energized.
• c. Check for spark at the gas pilot.
11. The pilot should spark and then ignite, then the main burners will ignite.
12. Heater will operate until the desired temperature is reached.
AIR PRESSURE SWITCH
PRESSURE SWITCH
OPERATION
The air pressure switch is a safety device to insure that
the blower is operating and has been designed to monitor
the vacuum (negative) pressure within the fan housing.
The air pressure switch is in the ignition module circuit
and the ignition module does not operate unless the
switch is closed.
Figure 2.
A-3
Download from Www.Somanuals.com. All Manuals Search And Download.
Rev. G 1-22-04
P/N 471048
VENTING
The vent pipe must be the same size or larger than what is indicated in Table 1. The PowerMax heaters are
capable of a 360-degree discharge rotation and operate with a positive vent static pressure and with a vent gas
temperature less than 400 F. The total length of the horizontal run must not exceed an equivalent of 45 feet. For
all cases, each 90-degree elbow reduces the maximum horizontal vent run by 8 feet and each 45-degree elbow in
the vent run reduces the maximum vent run by 4 feet. See Table 2 for the maximum vent lengths using a 90
degree and 45 degree elbows. The PowerMax induced-draft pool and spa heater uses positive pressure to push
flue gases through the vent pipe to the outside. This requires a completely sealed vent system--single wall vent
pipe with sealed-seams and joints may be used. Flue gases under positive pressure may escape into the dwell-
ing with any cracks or loose joints in the vent pipe, or improper vent installation. The vent pipe must be of a
sealed-seam construction such as those listed for use with category III appliances. Alternately, single wall or
double-wall type B duct which has had duct seams and joints permanently sealed using cements or other suitable
means which are rated for use at the flue gas temperatures of 325° F. and are permanent are acceptable. The use
of listed thimbles, roof jacks and/or side vent terminals are required; and the proper clearances to combustible
materials must be maintained in accordance with type of vent pipe employed- in the absence of a clearance
recommendation by the vent pipe manufacturer, the requirements of the Uniform Mechanical Code should be
met. The ventilation air and combustion air requirements for the PowerMax heaters are identical to the
requirements for the Standard MiniMax heaters of the same output capacities and can be found in the main
section of the Operation/Installation Manual, page 18. It is recommended that vent runs over 18 feet be insu-
lated to reduce condensation related problems and/or the use of a condensate trap in the vent run close to the
heater may be necessary in certain installations such as cold climates. The PowerMax is suitable for through-the-
wall venting. (Refer to page A-5, diagram 1.).
Recommended sources for Side-wall vent hood terminals include: The Field Controls Co. (2308 Airport Road,
Kingston, NC 28501, (800) 742-8368) and Tjernlund Products Inc. (1601 Ninth Street, White Bear Lake, MN
55110, (800) 255-4208)--consult manufacturer for model information and availability.
CAUTION
Do NOT combine exhaust vent pipes to a common exhaust vent in multiple unit installations. Run separate vent pipes.
Reduced Maximum Equivalent Vent Run (feet)
Additional 90° elbows
after first elbow
Additional 45° elbows
after first elbow
Quantity
Maximum Length
Quantity
Maximum Length
1 (2 total)
2 (3 total)
3 (4 total)
37
29
21
1 (2 total)
2 (3 total)
3 (4 total)
41
37
33
Table 2.
Figure 3.
A-4
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 471048
Rev. G 1-22-04
31
A-5
Download from Www.Somanuals.com. All Manuals Search And Download.
Rev. G 1-22-04
P/N 471048
A-6
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 471048
Rev. G 1-22-04
PowerMax Electronic Ignition Wiring Diagram
PLUG
PLUG
4
3
2
1
3
2
1
6
T F U S E
H L M T
5
4
3
2
1
2
P R E S S
1
A-7
Download from Www.Somanuals.com. All Manuals Search And Download.
Rev. G 1-22-04
P/N 471048
INSTRUCTION FOR WIRING A POWERMAX INDUCED DRAFT
ASSEMBLY TO A POOL HEATER WITH IID IGNITION.
WARNING
Make sure all power is off before wiring the heater. The Power vent assembly only operates on a 120 VAC.
The following instructions configure the power vent assembly to operate with the PowerMax on a single 120
VAC circuit. Take care as wiring errors may burn-out the transformer and blower motor.
If the Field installation is supported and the installed heater operates from 230 VAC, there must be a
separate 120 VAC service ran for the Power vent assembly.
1. Route the PowerMax wiring through a corner opening into the lower compartment area.
2. Disconnect the orange wire from the ignition module pin 6 (24V) and connect it to the orange wire from
the air pressure switch.
3. Connect the blue wire from the air pressure switch to the ignition module pin 6 (24V).
4. The green wire that comes from the relay connect to the same place ignition module is grounded in the
main control box.
5. Twist the red and white/red tracer wires from the transformer with the white wire from the fan motor.
Using a wire nut, connect the common wire from the 120 VAC line circuit with these wires.
6. Twist the black and white/black tracer wires from the transformer with the black wire from the fan motor.
Using a wire nut, connect the hot wire from the 120 VAC line circuit with these wires.
7. Connect the branch circuit’s safety ground wire (green) to the heater ground lug.
(Refer to Figure 4.)
CAUTION
The heater must be electrically grounded and bonded in accordance with the local codes or, in absence of
local codes, with the latest national codes ANSI/NFPA No. 70.
A-8
Download from Www.Somanuals.com. All Manuals Search And Download.
P/N 471048
Rev. G 1-22-04
WIRING DIAGRAM FOR POWERMAX KIT
AIR PRESSURE
SWITCH
BLACK
BLACK
GREEN
24 VAC RELAY
GRD
FAN
MOTOR
HEATER
GROUND
LUG
BLACK
HOT
120 VAC ONLY
WHITE
COMMON
ORANGE
BLUE
GREEN
SAFETY
GROUND
MALE
TAB
FEMALE
TAB
FEMALE
TAB
TO GROUND
MAIN CONTROL BOX.
ORANGE
TO IGNITION
TO THERMOSTAT
CIRCUIT BOAD
MODULE PIN 6
24V
Figure 4.
A-9
Download from Www.Somanuals.com. All Manuals Search And Download.
Rev. G 1-22-04
P/N 471048
POWERMAX HEATER - ALL MODELS
1
38
37
5
4
3
2
OPTIONAL OUTDOOR VENT
25
21
36
Models 150 - 200
Models 250 - 400
471395
471396
35
6
33
32
7
31
34
27
22
28
23
29
30
9
13
12
10
14
15
40
20
16
17
19
11
8
18
A-10
P/N 471048
Rev. G 1-22-04
Download from Www.Somanuals.com. All Manuals Search And Download.
PowerMax Heater (Only) Parts List
ITEM DESCRIPTION
QTY
150
195/200
250
300
350
400
1
PowerMax Vent Kit (complete)*
1
460048 460049 460050 460051 460052 460221
(Power Max Vent replacement parts
detailed in PowerMax Appendix, A-13)
2
3
4
5
6
7
8
9
Return header
1
2
4
4
4
18
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
070994 070994 070994 070994 070994 070994
074216 074216 074216 074216 074216 074216
073739 073739 073739 073739 073739 073739
070416 070416 070416 070416 070416 070416
072180 072180 072180 072180 072180 072180
070951 070951 070951 070951 070951 070951
471360 471360 471360 471360 471360 471360
470179 470179 470179 470179 470179 470179
073584 073584 073584 073584 073584 073584
073585 073585 073585 073585 073585 073585
470122 470122 470122 470122 470122 470122
470184 470184 470184 470184 470184 470184
470186 470186 470186 470186 470186 470186
470388 470389 470390 470391 470392 470393
471039 471040 471041 471042 471043 471044
075468 075604 075488 075605 075606 075490
070256 075525 070257 075526 075527 070258
073998 073998 073998 073998 073998 073998
073999 073999 073999 073999 073999 073999
075191 075191 075192 075192 075193 075193
073752 075499 073751 075500 075501 073750
073906 075508 073905 075509 075510 073904
Bracket washer
Bolt HH 3/8" x 2"
Bolt 3/8" - 16 x 1 1/2"
Washer 3/8" ID 1" OD
Tube seal gasket
Transformer - w/circuit breaker - dual voltage
Thermostat circuit board - IID
Module natural gas
10
Module propane gas
11
12
13
Junction Box
Thermostat knob
Switch rocker (S.P.D.T.)
Control panel assy. (complete) - IID Nat
Control panel assy. (complete) - IID Pro
Door - assy.
14
15
16
Manifold burner
Gas valve natural - IID
Gas valve propane- IID
Pilot tube - IID
17
18
19
Burner tray assy. natural (complete) - IID
Burner tray assy. propane (complete) - IID
2 EA.
3 EA.
4EA.
5 EA.
6 EA.
7 EA.
20
20a
21
22
23
25
Burner
070230 070230 070230 070230 070230 070230
470550 470550 470550 470550 470550 470550
470190 470190 470190 470190 470190 470190
073858 075586 073857 075587 075588 073856
072134 072134 072134 072134 072134 072134
072138 072138 072138 072138 072138 072138
471424 471424 471424 471424 471424 471424
073989 073989 073989 073989 073989 073989
074015 074015 074015 074015 074015 074015
075492 075492 075492 075492 075492 075492
075284 075284 075284 075284 075284 075284
Burner with Pilot bracket
Pressure switch
1
1
1
1
1
1
1
4
2
1
Combustion chamber assy. (complete)
Valve drain 3/4"
Valve relief 3/4" 50# - ASME or Local Code
Flow valve assy., Standard (complete)
Flow valve assy., ASME (complete)
Flow valve gasket
27
28
29
30
Bolt 3/8" - 16 x 2 1/2
Quick flange Kit
A-11
Rev. G 1-22-04
P/N 471048
Download from Www.Somanuals.com. All Manuals Search And Download.
PowerMax Heater (Only) Parts List, contd.
ITEM DESCRIPTION
QTY
150
195/200
250
300
350
400
31
Bushing in/out Lexan
2
2
2
2
1
1
1
070544 070544 070544 070544 070544 070544
071895 071895 071895 071895 071895 071895
070229 070229 070229 070229 070229 070229
071017 071017 071017 071017 071017 071017
070985 070985 070985 070985 070985 070985
074452 075628 074451 075629 075630 074074
470364 470365 470366 470367 470368 470369
Sleeve, rubber in/out 2"
Sleeve, rubber in/out 1½"
Safety Shutoff
32
33
34
Main header (in/out)
Heat exchanger (without heads)
Heat exchanger (with heads)
35
8 ea.
8 ea.
8 ea.
8 ea.
16 ea.
16 ea.
36
37
38
40
Baffle
070277 075559 070276 075560 070277 070278
073810 073810 073810 073810 073810 073810
073864 075622 073863 075623 075624 073862
075783 075784 075785 075786 075787 075788
Baffle hold down (2) baffles on 350, 400
Flue collector
1
1
1
Lightback Shield (Propane Gas units only)
* Not Shown
*
*
*
*
*
*
*
*
*
*
*
Plastic mounting bracket
Wire Kit - Harness (gas valve) IID
Screw 8 x 1/4" HH
070715 070715 070715 070715 070715 070715
470965 470965 470965 470965 470965 470965
071703 071703 071703 071703 071703 071703
071698 071698 071698 071698 071698 071698
071716 071716 071716 071716 071716 071716
071659 071659 071659 071659 071659 071659
075692 075692 075692 075692 075692 075692
070551 070551 070551 070551 070551 070551
470414 470414 470414 470414 470414 470414
470178 470178 470178 470178 470178 470178
073725 073725 073725 073725 073725 073725
Screw 8 x 1/2" HH
Screw 6 x 1/4"
Screw 10 - 32 x 1/4"
Screw 10 - 32 x 3/16"
Bushing 1/2"
Therm knob stopper
Power element (flow valve)
Bolt 5/16" - 18 x 3/4"
2
1
2
3 ea.
4 ea.
5 ea.
6 ea.
7 ea.
8 ea.
N or P
N or P
N or P
N or P
N or P
N or P
*
*
*
*
*
*
*
Orifice main burner natural
Orifice main burner propane
Pilot - natural - IID
073727 073727 073727 073727 073727 073727
073728 073728 073728 073728 073728 073728
471204 471204 471204 471204 471204 471204
471205 471205 471205 471205 471205 471205
075173 075173 075173 075173 075173 075173
470180 470180 470180 470180 470180 470180
470181 470181 470181 470181 470181 470181
1
1
1
1
2
Pilot - propane - IID
Thermal cutoff
Thermistor (probe) complete (IID models)
Stem, thermistat control (IID Models)
A-12
P/N 471048
Rev. G 1-22-04
Download from Www.Somanuals.com. All Manuals Search And Download.
PowerMax Assembly
PowerMax Assembly Parts List
ITEM DESCRIPTION
QTY
1
150
200
250
300
350
400
1
2
3
4
5
6
7
8
Plenum
470139 470140 470141 470142 470143 470144
470008 470008 470007 470007 470007 470007
470331 470331 470331 470331 470331 470331
470337 470337 470337 470337 470337 470337
470336 470336 470326 470326 470326 470326
470334 470334 470325 470325 470325 470325
470328 470328 470328 470328 470328 470328
470010 470010 470010 470010 470010 470010
Blower combustion
Control box side & base
Control box top
Adapter ring
1
1
1
1
Adapter base
Silicone rubber tube
Relay
1
1
1
Pressure Switch
9
9
1
1
470009 470009 470009 470009 470009 470009
471428 471428 471428 471428 471428 471428
Sea Level to 4000 ft.
Pressure Switch
High Altitude
Sea Level 4000 - 8000 ft.
A-13
Download from Www.Somanuals.com. All Manuals Search And Download.
Rev. G 1-22-04
P/N 471048
SAVE THESE INSTRUCTIONS.