Panasonic Smoke Alarm 1548 User Manual

Fire alarm system  
EBL512  
1548, 1549 and 1550  
EBL512 -- an intelligent analog addressable fire alarm system  
Up to 512 addresses per control and indicating equipment (c.i.e.)  
TLON network for up to 30 c.i.e.:s  
Analog addressable system  
EBL512 is an intelligent analog addressable  
fire alarm system, conforming to the EN54-2  
and –4 standards.  
Up to 512 addresses  
EBL512 has the capacity of connecting 512  
addresses. Basic configurations 128, 256 or  
512 addresses. Can be upgraded on site.  
Each c.i.e. has four COM loops for  
connection of up to 512 loop units. Each  
addressable loop unit uses one address.  
Features / functions  
The fire alarm system EBL512 meets the  
most stringent requirements relating to fire  
detection and alarm.  
Some loop units that can be connected:  
Analog detectors (sensors)  
A user-friendly PC software Win512 is used  
for site specific data editing, download,  
backup and SW download.  
Addressable manual call points  
Addressable short circuit isolators  
Addressable input and output units  
Addressable sirens & sounder bases  
Addressable external power supply units  
Conventional detectors and manual call  
points  
Some features / functions:  
Adaptation of each analog detector's  
alarm level in relation to its contamina-  
tion. Service signal when required.  
Algorithms for filtering and alarm, to  
reduce nuisance alarms. Algorithm for  
faster detection of smouldering fires.  
Functions, customer related: Test mode,  
alert annunciation, disablements, etc.  
Functions: Fire door closing, inter-  
locking combinations of outputs &  
inputs, time channels, alarm delay, two-  
unit dependence, user definable text  
message for each alarm point, etc.  
TLON Network  
Up to 30 EBL512 c.i.e.:s can be connected  
to a TLON network. A TLON connection  
board 1590 is then required in each c.i.e.  
Miscellaneous  
EBL512 has space in the cabinet for two  
sealed Lead Acid 24 (27) Ah batteries.  
In each c.i.e. can be mounted up to six  
expansion boards 1580-1587. The ext. FBPs  
182x and the Alert Annunciation units 173x,  
shall be connected via a 1587 board.  
Programmable inputs and outputs and  
a large number of trigger conditions.  
Expansion boards (options) with zone  
line inputs or relay outputs.  
Interface (option) for ext. Fire brigade  
panels, alert annunciation units, data  
converters, etc.  
One Web-server II 1598 (option) connects  
the EBL512 system to Internet / an Intranet  
(LAN).  
Panasonic Electric Works Fire & Security Technology Europe AB  
Citadellsvägen 23, SE-211 18 Malmö, Sweden  
Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Miele Washer W 916 User Manual
Miller Electric Welding System Big 40 CAT User Manual
NEC Cell Phone NDA 24300 User Manual
Newcon Optik Hunting Equipment LRM 220SI User Manual
Omnimount TV Mount LEDP75 User Manual
Onkyo Stereo Receiver TX NR1009 User Manual
Optoma Technology Projector Digital Tuner Output Projector User Manual
Panasonic Security Camera GP MF130 User Manual
Panasonic Vacuum Cleaner MC GG283 User Manual
ParaBody Home Gym 835102 User Manual