| 	
		 Use r’s Gu id e   
					http://www.omega.com   
					e-mail: info@omega.com   
					DRA-DCC-8   
					DIGITAL TO 8 CURRENT LOOP CONVERTER   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Contents   
					1. MOUNTING INSTRUCTIONS   
					2. REPLACING FUSES   
					3. ASSEMBLY   
					4. SUPPLY VOLTAGE   
					5. MODES OF OPERATION   
					5.1 0-20 or 4-20mA output current selection   
					5.2 Switch Settings   
					6. PARALLEL CONTROL MODE   
					6.1 PLC Interface   
					6.2 The "E" (ENABLE) Terminal   
					7. SERIAL CONTROL MODE   
					7.1 RS232c / RS422 Select   
					7.2 RS422 Termination   
					7.3 Serial Control Switch Settings   
					7.4 Serial Communication Parameters   
					7.4.1 Baud Rate Select   
					7.4.2 ID Code   
					7.4.3 Command Formats   
					8. SELF TEST MODES   
					8.1 Self Test # 1   
					8.2 Self Test # 2   
					8.3 Self Test # 3   
					9. MULTIDROP CONFIGURATION   
					10. PUTTING THE UNIT INTO OPERATION   
					11. CALIBRATION   
					12. SPECIFICATIONS   
					1 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				1. MOUNTING INSTRUCTIONS   
					The DRA-DCC-8 is designed for standard DIN rail mounting.   
					Place the unit on the upper part of the mounting rail with the fastening tab facing   
					down. Using a suitable flat screwdriver loosen the tab slightly and attach the unit   
					to the rail. Once the tab is loosened, ensure that the unit is fastened securely in   
					place.   
					2. REPLACING FUSES   
					In order to replace a blown fuse, the unit has to be disassembled, as follows:   
					a. Take off both terminal strips by removing the four screws at the edges.   
					Note: This does not require disconnecting the cables connected to the strips.   
					b.   
					Remove the front panel using a suitable flat screwdriver. Press down gently on   
					the plastic springloaded tabs located in the slots either side of the unit.   
					c. Disconnect the flat connector which couples the LED circuit on the front panel.   
					d. Replace the blown fuse.   
					WARNING: Never install a fuse rated more than 800mA   
					3. ASSEMBLY   
					The DRA-DCC-8 unit includes   
					two printed circuit cards   
					designated as P.N 7041 and   
					P.N 7040. The two printed   
					circuit cards should occupy   
					the slots in the enclosure   
					according to fig 1.   
					Figure 1   
					Insert the two printed cards into their slots. Connect the flat cable between them.   
					Connect the front panel flat cable. The panel must be inserted into the grooves on   
					both sides of the case while pressing down until a distinct "click" is heard. Assembly   
					is completed by laying the terminal strips in place.   
					Note: The terminal strips are polarized and must not be placed backwards.   
					2 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				4. SUPPLY VOLTAGE   
					The DRA-DCC-8 is powered by a DC power supply at a range of 15-32Vdc. In order   
					to determine the minimum supply voltage, use the following equation:   
					Vmin = 8 + Rload(Ω) * 0.02   
					where:   
					Vmin is the minimum required supply voltage.   
					Rload(Ω) is the maximum output load including the leads resistance.   
					Note: If Vmin turns to be less than 15V, the minimum required voltage   
					should be 15 Vdc.   
					5. MODES OF OPERATION   
					The DRA-DCC-8 unit can be operated in several modes, determined by an internal   
					array of 8 DIP switches as follows:   
					4-20 or 0-20mA output current mode   
					Parallel control mode   
					Serial control mode   
					Self test mode   
					5.1 0-20 OR 4-20mA OUTPUT CURRENT MODE   
					Two current output spans are available: 4-20mA or 0-20mA selected by SW6.   
					The DRA-DCC-8 receives 12 bits of data which determine the output current value.   
					A channel data value of 4095 (FFF) is always interpreted as a 20mA output current.   
					A channel data value of 0 (000) will produce a 0mA output current when SW6   
					is OFF, or 4mA when ON.   
					5.2 SWITCH SETTINGS   
					Parallel Control Mode   
					MODE   
					S1   
					S2   
					S3   
					X 
					S4   
					X 
					S5   
					X 
					S6   
					S7   
					0-20mA   
					4-20mA   
					OFF OFF   
					OFF OFF   
					OFF OFF   
					ON OFF   
					X 
					X 
					X 
					3 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Serial Control Mode   
					BAUD RATE (BPS)   
					300   
					S1 S2 S3   
					S4 S5   
					S6   
					S7   
					ON   
					ON   
					OFF OFF   
					ON OFF   
					OFF ON   
					ON ON   
					ON=4-20mA   
					4800   
					9600   
					UNIT ID CODE   
					OFF=0-20mA ON   
					ON   
					19200   
					SW5 MSB   
					Self Test Mode   
					S1 S2 S3   
					MODE   
					SELF TEST#1   
					S4   
					X 
					S5   
					S6   
					S7   
					ON OFF   
					OFF ON   
					ON ON   
					X 
					* 
					OFF   
					OFF   
					OFF   
					X 
					SELF TEST#2   
					SELF TEST#3   
					X 
					* 
					* according to para #5.2   
					6. PARALLEL CONTROL MODE   
					MODE   
					S1   
					S2   
					S3   
					S4   
					X 
					S5   
					S6   
					* 
					S7   
					PARALLEL MODE   
					OFF OFF   
					OFF   
					* according to para #5.2   
					In the parallel control mode, the DRA-DCC-8 unit is controlled via a 15 bit bus.   
					Three Address bits (A0-A3) select the proper current output channel and 12 Data   
					bits (D0-D11) determine its value (A0 and D0 are MSB). The DRA-DCC-8   
					microprocessor continuously scans the input vector (Address + Data) terminals   
					and updates its memory tables upon recognizing a new vector. The unit is   
					asynchronous in nature. The data should be valid for at least 160 microseconds.   
					SOURCE   
					SINK   
					6.1 PLC INTERFACE   
					The PLC's output modules can be divided into   
					three popular types; TTL output module, 24Vdc   
					sink type and 24Vdc source type.   
					There is a jumper selector on printed circuit card   
					PN 7040 which selects between Sink/ Source   
					input. (TTL output module should usualy be   
					considered as sink type). See figure 2.   
					Figure 2.   
					4 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				6.2 THE "E" (ENABLE) TERMINAL   
					For E="1" the unit is enabled, which means that all input vectors are received and   
					the output is updated. When E="0" the unit ignores any new input vector. The E   
					terminal is recommended to be used as a strobe for parallel data which has a long   
					setup time. In this case the following sequence is recommended: prior to applying   
					a new vector, the E terminal should be set to logical 0 (inhibit state), then the new   
					input vector should be imposed. Once the new data is set, the E terminal should   
					be pulsed.   
					The E terminal is also used for multidrop configuration. The 15 bit vectors are   
					applied to the units in parallel and the selection is carried out by controlling the   
					"E" inputs.   
					7. SERIAL CONTROL MODE   
					7.1 RS232c / RS422 SELECT   
					he DRA-DCC-8 is equipped with two serial   
					communication ports: The RS232c and the   
					RS422. A jumper switch at the right side of the   
					DIP switch array is used to select the required   
					communication type. See figure 3.   
					RS-422   
					RS-232c   
					Figure 3.   
					7.2 RS422 TERMINATION   
					The SW8's ON state terminates the RS422 receiver terminals with a 100W load.   
					In a multidrop configuration, the last (most distant) DRA-DCC-8 unit should be   
					terminated in order to match the transmission lines.   
					Note: Only one termination load per RS422 communication link is permissible.   
					7.3 SERIAL CONTROL SWITCH SETTINGS   
					S1   
					BAUD RATE   
					* according to para #5.2   
					S2   
					S3   
					S4   
					S5   
					S6   
					* 
					S7   
					ID CODE   
					ON   
					7.4 SERIAL COMMUNICATION PARAMETERS   
					The communication protocol is 8 bit ASCII, even parity, and one stop bit.   
					5 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				7.4.1 BAUD RATE SELECT   
					SW1 and SW2 select one out of four available baud rates.   
					SW1   
					OFF   
					ON   
					SW2   
					OFF   
					OFF   
					ON   
					300 BPS   
					4800 BPS   
					9600 BPS   
					19200 BPS   
					OFF   
					ON   
					ON   
					7.4.2 ID CODE   
					Up to eight DRA-DCC-8s can be connected in a multidrop configuration. Switches   
					SW3, SW4, and SW5 (MSB) set the ID code.   
					7.4.3 COMMAND FORMATS   
					Three types of command formats are available:   
					Without echo back   
					The host computer sends a massage and does not receives an   
					acknowledgment.   
					With echo back   
					The host computer sends a message and receives an acknowledgment stating   
					the DRA-DCC-8 ID number and the addressed channel number.   
					Status report   
					7.4.3.1. WITHOUT ECHO BACK FORMAT   
					[A] [ID CODE] [CHANNEL VALUE] [CR]   
					The character A begins the command block.   
					The second byte is the ID code (07). The third byte is the addressable channel   
					number (07). Up to four bytes of a channel's value can be in BCD mode (0-4095).   
					Leading zeroes can be omitted. The last byte is [CR] which must terminate the   
					command block.   
					7.4.3.2. WITH ECHO BACK FORMATS   
					[C] [ID CODE] [CHANNEL VALUE] [CR]   
					This format differs only in the opening character. After every command block   
					transfer, the DRA-DCC-8 echoes back the following:   
					6 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				[C] [ID CODE CHANNEL] [LF] [CR]   
					Note: If the value is omitted it will be treated as zero. Separators such as   
					blanks or commas are not allowed.   
					Example:   
					Channel 4 in DRA-DCC-8 no. 7 has to receive the value of 981. Echo back is required   
					The command format is:   
					[C] [7] [4] [981] [CR]   
					The echo back will be: C 7 4   
					Note: The channel numbers on the DRA-DCC-8 front panel are designated   
					from 1 to 8, in binary they are designated from 0 to 7.   
					Note: When applying the echo back mode, it is advisable to wait for the   
					echo back before transmitting a new command.   
					7.4.3.3 STATUS REPORT FORMAT   
					[S] [ID CODE] [CR]   
					The addressed DRA-DCC-8 unit will respond with the values stored in its eight   
					channels. The response will start with S, ID code, following with eight channel   
					values separated with commas and [LF] [CR] as terminators.   
					Example:   
					DRA-DCC-8 unit number 3 has the following stored data: ch1: 300, ch2: 1270,   
					ch3: 0, ch4: 4087, ch5: 2099, ch6: 764, ch7: 3078, ch8: 550. The response from   
					the device will be:   
					S3,300,1270,0,4087,2099,764,3078,550 [LF] [CR].   
					Note: Wait until the status report has terminated before transmitting new   
					commands.   
					8. SELF TEST MODES   
					The DRA-DCC-8 is provided with three test modes.   
					MODE   
					SELF TEST#1   
					S1   
					S2   
					S3   
					S4   
					X 
					S5   
					S6   
					S7   
					ON   
					OFF   
					X 
					* 
					OFF   
					OFF   
					OFF   
					X 
					SELF TEST#2   
					SELF TEST#3   
					OFF ON   
					ON ON   
					X 
					* 
					* according to para #5.2   
					7 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				8.1 SELF TEST #1 (Communication Ports Test)   
					In order to test the serial communication ports, this test mode converts the unit to   
					a transponder for ASCII characters. Any transmitted character will be echoed to   
					the host terminal. The host parameters should be set to:   
					Baud rate : 4800, Word length: 8 bits, Parity: even, Stop bit: 1   
					8.2 SELF TEST #2 (Same Leve)l   
					In this test mode, the DRA-DCC-8 unit ignores the address field. All the outputs   
					are set according to the data field only.   
					8.3 SELF TEST #3 (Saw Tooth)   
					In this test mode, only one output channel (according to the address setting) will   
					produce a saw tooth wave form in which the whole value range is used.   
					9. MULTIDROP CONFIGURATION   
					Up to eight DRA-DCC-8 units can be installed in a multidrop configuration using   
					the RS422 communication port.   
					The controller's RS-422 transmitter is connected to the units' receivers while the   
					controller's RS-422 receiver is connected to the units' transmitters.   
					As the communication cable might be several thousand feet long, it is necessary   
					to terminate the end of the line with its characteristic impedance in order to avoid   
					reflections in the transmission line causing data distortion. SW8 in its ON state   
					terminates the Rx inputs with a 100Ω load.   
					10. PUTTING THE UNIT INTO OPERATION   
					The DRA-DCC-8 is supplied with a set configuration for parallel control mode.   
					The DIP switch setting is:   
					S1   
					S2   
					S3   
					S4   
					S5   
					S6   
					S7   
					MODE   
					PARALLEL 4-20mA   
					OFF OFF OFF OFF OFF   
					ON OFF   
					The communication port selector (see para #7.1) is set to RS232C.   
					The unit should be set up according to the required configuration.   
					Before applying voltage to the unit see para #4 for power supply consideration.   
					8 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				The channel LEDs are connected in series with the output current so that they will   
					light only as an indication of a closed current loop.   
					Note: After every power on, the unit is reset and the initialized   
					default output currents are according to the SW6 setting   
					(see para #5.2).   
					In the parallel control mode, internal pull-up resistors on each of the input terminals   
					keep them in logical 1 state. The unit will recognize input voltage up to 0.5V as   
					logical 0 and voltages from 4V to 60V as logical 1.   
					11. DRA-DCC-8 CALIBRATION   
					Generally there is no need to calibrate the DRA-DCC-8 unit. However if calibration   
					is required, the following steps should be carried out: Two potentiometer trimmers,   
					one for "Zero" and the other for "Span" are located on printed card 7040. The   
					trimmer close to the card edge is the "Zero". Use the following switch setup for   
					switching all the outputs between 4 and 20mA   
					MODE   
					S1   
					S2   
					S3   
					X 
					S4   
					X 
					S5   
					X 
					S6   
					S7   
					ALL CH. = 4mA   
					OFF OFF   
					ON OFF   
					ON OFF   
					ALL CH. = 20mA OFF ON   
					X 
					X 
					X 
					Note: Set the unit to sink mode (fig.2).   
					Step 1:   
					Select one channel (for example ch.#1) for the initial tuning. Set the DIPswitch array   
					to "all 4mA".   
					Apply supply voltage to the unit. The initial state of all the output currents is 4 mA.   
					Use SW2 to switch all the outputs between 4 and 20mA. Iteratively set the "Zero"   
					and the "Span" trimmers for 4.00mA and 20.00mA.   
					Step 2:   
					Monitor all the 8 channels in 4mA state, and calibrate the Zero trimmer so that   
					their average readings is 4.000mA.   
					Then repeat for 20mA state, and calibrate the Span trimmer so that their average   
					readings is 20.000mA. This procedure should be repeated until calibration is   
					satisfactory.   
					9 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				12. SPECIFICATIONS   
					INPUTS:   
					PARALLEL INPUTS   
					Parallel & Serial control inputs   
					3 - Output current loop address   
					12 - Output current value (Data)   
					1- Enable (E)   
					LOGIC LEVELS:   
					0<"0"<0.5V, 4 <"1"< 60V   
					160 microsecond   
					DATA HOLD TIME:   
					MAXIMUM PARALLEL INPUT RATE:   
					SERIAL COMMUNICATION   
					6000 updates per second   
					RS232c full duplex   
					RS422 full duplex   
					BAUD RATES:   
					PARITY:   
					300, 4800, 9600, 19200 BPS   
					Even   
					STOP BIT:   
					One   
					STATUS REPORT:   
					MULTIDROP CAPABILITY:   
					Reports as interrogated   
					Up to eight units   
					OUTPUTS:   
					OUTPUT CURRENT SPAN:   
					OUTPUT CURRENT SETTLING TIME:   
					8 continues current loops   
					0-20mA or 4-20mA (user selected)   
					4.2 ms max. for 99% of step   
					POWER SUPPLY:   
					15-32 Vdc (regulated)   
					85mA max.   
					CURRENT CONSUMPTION:   
					MAXIMUM LOOP RESISTANCE:   
					ACCURACY:   
					According to Rmax(K   
					Ω 
					)= (Vsupply -6)/ 20   
					0.2% of span max.   
					±0.1% of span typical,   
					± 
					RESOLUTION:   
					0.025% of span typical,0.05% of span max.   
					INDICATORS:   
					Yellow Power On LED   
					8 Red output channel LEDs   
					AMBIENT TEMPERATURE   
					Operation:   
					Storage:   
					-10 to 60 oC (14 to 140 oF)   
					-25 to +85 oC (-13 to 185 oF)   
					RELATIVE HUMIDITY:   
					5 to 95%, non condensing   
					HOUSING   
					Box:   
					Terminals:   
					Plastic Polycarbonate   
					According to IP 50 DIN 40050   
					According to IP 20 DIN 40050   
					MOUNTING:   
					FUSE:   
					Standard DIN rail   
					630mA fast blow (5x20mm)   
					0.7Kg (1.5 lb.)   
					WEIGHT:   
					DIMENSIONS:   
					73.2H x 200W x 121mmD (2.88"x7.88"x4.76")   
					10   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				WARRANTY/DIS CLAIMER   
					OMEGA ENGINEERING, INC. w a rra n ts th is u n it to b e fre e o f d e fe cts in m a te ria ls a n d workm anship   
					fo r a p e rio d o f 1 3 m o n t h s fro m d a te o f p u rch a s e . OMEGA Wa rra n ty a d d s a n a d d itio n a l o n e (1) m o n th   
					g ra ce p e rio d to th e n o rm a l o n e (1 ) y e a r p r o d u c t w a r r a n t y to cover handling and shipping tim e. This   
					ensures that OMEGA’s custom ers receive m axim um coverage on each product. If the unit should m alfunction,   
					it m ust be returned to the factory for evaluation. OMEGA’s Custom er Service Departm ent will issue an Authorized   
					Return (AR) num ber im m ediately upon phone or written request. Upon exam ination by OMEGA, if the unit is   
					found to be defective it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects   
					resulting from any action of the purchaser, including but not lim ited to m ishandling, im proper interfacing,   
					operation outside of design lim its, im proper repair, or unauthorized m odification. This WARRANTY is VOID if   
					the unit shows evidence of having been tam pered with or shows evidence of being dam aged as a result   
					of excessive corrosion; or current, heat, m oisture or vibration; im proper specification; m isapplication; m isuse   
					or other operating conditions outside of OMEGA’s control. Components which wear are not warranted, including   
					but not lim ited to contact points, fuses, and triacs.   
					OMEGA is p le a s e d t o o ffe r s u g g e s t io n s o n t h e u s e o f it s va rio u s p ro d u c t s . Ho w e ve r,   
					OMEGA n e it h e r a s s u m e s re s p o n s ib ilit y fo r a n y o m is s io n s o r e rro rs n o r a s s u m e s   
					lia b ilit y fo r a n y d a m a g e s t h a t re s u lt fro m t h e u s e o f it s p ro d u c t s in a c c o rd a n c e   
					w it h in fo rm a t io n p ro vid e d b y OMEGA, e it h e r ve rb a l o r w rit t e n . OMEGA w a rra n t s   
					o n ly t h a t t h e p a rt s m a n u fa c t u re d b y it w ill b e a s s p e c ifie d a n d fre e o f d e fe c t s .   
					OMEGA MAKES NO OTHER WARRANTIES OR REP RES ENTATIONS OF ANY KIND   
					WHATS O EVER, EX P RES S ED O R IM P LIED , EX C EP T THAT O F TITLE, A N D A LL   
					IM P LIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND   
					FITNES S FOR A PARTICULAR P URP OS E ARE HEREBY DIS CLAIMED. LIMITATION   
					OF LIABILITY: Th e re m e d ie s o f p u rc h a s e r s e t fo rt h h e re in a re e xc lu s ive a n d t h e   
					t o t a l lia b ilit y o f OMEGA w it h re s p e c t t o t h is o rd e r, w h e t h e r b a s e d o n c o n t ra c t ,   
					w a rra n t y, n e g lig e n c e , in d e m n ific a t io n , s t ric t lia b ilit y o r o t h e rw is e , s h a ll n o t e xc e e d   
					t h e p u rc h a s e p ric e o f t h e c o m p o n e n t u p o n w h ic h lia b ilit y is b a s e d . In n o e v e n t   
					s h a ll O M EG A b e lia b le f o r c o n s e q u e n t ia l, in c id e n t a l o r s p e c ia l d a m a g e s .   
					CONDITIONS: Equipm ent sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic   
					Com ponent” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in m edical   
					applications or used on hum ans. Should any Product(s) be used in or with any nuclear installation or activity,   
					m edical application, used on hum ans, or m isused in any way, OMEGA assum es no responsibility as set forth   
					in our basic WARRANTY / DISCLAIMER language, and additionally, purchaser will indem nify OMEGA and   
					hold OMEGA harm less from any liability or d a m a g e w h a t s o e v e r a r is in g o u t o f t h e u s e o f t h e   
					P r o d u c t (s ) in s u c h   
					a 
					m a n n e r.   
					RETURN REQUES TS / INQUIRIES   
					Direct all warranty and repair requests/inquiries to the OMEGA Custom er Service Departm ent.   
					BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED   
					RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID   
					PROCESSING DELAYS). The assigned AR num ber should then be m arked on the outside of the return   
					package and on any correspondence.   
					The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent   
					breakage in transit.   
					FOR WARRANTY RETURNS, please have the   
					following inform ation available BEFORE contacting   
					OMEGA:   
					FOR NON-WARRANTY REPAIRS, consult   
					OMEGA for current repair charges. Have the   
					following inform ation available BEFORE   
					contacting OMEGA:   
					1. P.O. num ber under which the product was   
					PURCHASED,   
					1. P.O. num ber to cover the COST   
					of the repair,   
					2. Model and serial num ber of the product under   
					warranty, and   
					2. Model and serial num ber of product, and   
					3. Repair instructions and/or specific   
					problem s relative to the product.   
					3. Repair instructions and/or specific problem s   
					relative to the product.   
					OMEGA’s policy is to m ake running changes, not m odel changes, whenever an im provem ent is possible.   
					This affords our custom ers the latest in technology and engineering.   
					OMEGA is a registered tradem ark of OMEGA ENGINEERING, INC.   
					© 
					Copyright 1996 OMEGA ENGINEERING, INC. All rights reserved. This docum ent m ay not be copied,   
					photocopied, reproduced, translated, or reduced to any electronic m edium or m achine-readable form , in   
					w h o le o r in p a r t , w it h o u t p r io r w r it t e n c o n s e n t o f O M EG A EN G IN EERIN G , IN C.   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				W h e re Do I Fin d Eve r y th in g I N e e d fo r   
					Pro ce ss Me a su re m e n t a n d Co n tro l?   
					O MEGA…O f Co u rse !   
					TEMPERATURE   
					ߜ  Thermocouple, RTD & Thermistor Probes,  Connectors, Panels & Assemblies   
					ߜ  Wire: Thermocouple, RTD & Thermistor  ߜ  Calibrators & Ice Point References  ߜ  Recorders, Controllers & Process Monitors  ߜ  Infrared Pyrometers  PRESSURE, STRAIN AN D FO RCE   
					ߜ  Transducers & Strain Gauges  ߜ  Load Cells & Pressure Gauges  ߜ  Displacement Transducers  ߜ  Instrumentation & Accessories  FLO W / LEVEL   
					ߜ  Rotameters, Gas Mass Flowmeters & Flow Computers  ߜ  Air Velocity Indicators  ߜ  Turbine/ Paddlewheel Systems  ߜ  Totalizers & Batch Controllers  p H/ CO N DUCTIVITY   
					ߜ  pH Electrodes, Testers & Accessories  ߜ  Benchtop/ Laboratory Meters  ߜ  Controllers, Calibrators, Simulators & Pumps  ߜ  Industrial pH & Conductivity Equipment  DATA ACQ UISITIO N   
					ߜ  Data Acquisition & Engineering Software  ߜ  Communications-Based Acquisition Systems  ߜ  Plug-in Cards for Apple, IBM & Compatibles  ߜ  Datalogging Systems  ߜ  Recorders, Printers & Plotters  HEATERS   
					ߜ  Heating Cable  ߜ  Cartridge & Strip Heaters  ߜ  Immersion & Band Heaters  ߜ  Flexible Heaters  ߜ  Laboratory Heaters  EN VIRO N MEN TAL   
					MO N ITO RIN G AN D CO N TRO L   
					ߜ  Metering & Control Instrumentation  ߜ  Refractometers  ߜ  Pumps & Tubing  ߜ  Air, Soil & Water Monitors  ߜ  Industrial Water & Wastewater Treatment  ߜ  pH, Conductivity & Dissolved Oxygen Instruments  M2612/ 0197   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				 |