Omega Vehicle Security Switch 430 User Manual

FSW-420/430  
Thermal Flow Switches  
M-4586/1007  
FSW-420/430 INSTALLATION & INSTRUCTION SHEET  
1.0 Install the FSW-420/430 by inserting the ½” MNPT threaded sensor tip into a tapped pipe or T-fitting. Use Pipe Tape or  
Plumbers Putter on NPT threads to aid in sealing. Tighten firmly, but do not over tighten as this could damage the NPT  
threads and prevent proper sealing.  
2.0 With provided connection cable disconnected, complete unit wiring by connecting the Brown wire to +24VDC supply and the  
Blue wire to common. The Black wire is now connected to the + side of your load. The – side or common of your load is  
now also connected to ground. NOTE: Be sure that the common (ground) of the FSW-420/430 and the LOAD are the same.  
The white wire (if present) is not used.  
3.0 Setting unit zero point: With the media flow turned off depress setup button located on the front of the unit with a small  
instrument (Screwdriver or Paper Clip) and hold while connecting the pre-wired cable to the unit. The setup button is located  
on the face of the FSW-420/430 just between the Flow OK and the Overflow LED’s. The cable would have been pre-wired  
in step 2 above. Once the unit comes on remove the instrument from the setup button and allow the unit to go through it’s  
zero point calibration. The unit will start with the far right LED and increment to the left. Once finished all LED’s should be  
off except for the blinking set-point indicator.  
4.0 Setting unit range: Turn on your flow and allow the flow to reach full normal flow rate. Then with the setup instrument used  
in step 3.0 above, depress the set/range button on the face of the FSW-420/430 (located just between the Flow OK and  
Overflow LED’s). Hold for 5-6 seconds and the FSW-420/430 will range itself to the full flow rate or 5 ft/second whichever is  
less (this process could take 45-60 seconds). All of the 7 LED’s will flash when auto scaling is complete and the Set Point  
LED will begin to flash (default is set for 50%). The Green Flow OK LED will come on when the flow rate goes above the set  
point and the output signal of the unit will change states.  
5.0 Should you wish to set the set-point at a different LED setting (or rage of flow) simply depress the set/range button repeatedly  
inshore intervals, and the set-point will change clockwise to any LED you wish to choose. When the correct LED is flashing  
your new set point is established.  
6.0 The Over Range light (Offset RED LED) will come on if your already established full flow rate were to increase. If you wish to  
rescale to the new flow rate, simply depress the set button again as you did in Step 3.0 and reset your set-point if desired,  
using the same procedure as in item 4.0 above. See additional notes.  
NOTE: Use caution while installing the FSW-420/430 so as not to damage the tip of the sensor. The electronics are  
embedded just behind the tip of the FSW-420/430 and denting or bottoming out of the tip could cause damage.  
Maintenance is not required, as the FSW-420/430 has no moving parts. However, should the sensor become coated after a period  
of time in operation due to water or media conditions, simply wipe the probe tip with a soft cloth and alcohol.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Miele Cooktop KM400 User Manual
Miele Food Warmer ESW4711 User Manual
Napoleon Grills Gas Grill PTSS215 User Manual
New Holland Lawn Mower 410GM User Manual
Nikon Camera Lens AF S VR User Manual
Nikon Digital Camera 2168 PC User Manual
Onkyo Speaker System SKC 230C User Manual
Opel Door Audi A3 Avant User Manual
Panasonic Camcorder AG HVX200E User Manual
Paradyne Modem 6310 A4 User Manual