MADE IN
USA
Use r ’s Gu id e
Shop on line at
®
®
omega.com
e-mail: info@omega.com
iSeries info:
omega.com/specs/iseries
For latest product manuals
omegamanual.info
Pro ce ss/ Stra in Ga u g e Co n tro lle r Ma n u a l
CN iS8 , CN iS8 C,
CN iS8 DH, CN iS8 DV,
CN iS1 6 , CN iS1 6 D, CN iS3 2
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
Part 1: Introduction............................................................................................2
1.1
1.2
1.3
Description .................................................................................2
Safety Considerations ...............................................................3
Before You Begin .......................................................................4
Part 2: Setup.......................................................................................................5
2.1
2.2
2.3
Front Panel .................................................................................5
Rear Panel Connections............................................................5
Electrical Installation .................................................................7
2.3.1 Power Connections........................................................7
2.3.2 Process Current .............................................................8
2.3.3 Process Voltage..............................................................8
2.3.4 Strain Gauge...................................................................9
2.3.5 Wiring Outputs - Wiring Hookup.................................10
Part 3: Operation: Configuration Mode .........................................................13
3.1
Introduction ..............................................................................13
Turning your Instrument On for the First Time
Buttons Functions in Configuration Mode
3.2
Menu Configuration ................................................................14
3.2.1 ID Number .....................................................................15
3.2.2 Set Points Menu ...........................................................16
3.2.3 Configuration Menu ....................................................17
3.2.4 Input Type Menu...........................................................17
3.2.5 Reading Configuration Menu .....................................19
3.2.6 Input/Reading (Scale and Offset) Menu ....................22
3.2.7 Alarm 1 Menu................................................................26
3.2.8 Analog Output (Retransmission) Menu......................30
3.2.9 Alarm 2 Menu................................................................33
3.2.10 Loop Break Time Menu................................................34
3.2.11 Output 1 Menu ..............................................................36
3.2.12 Output 2 Menu ..............................................................43
3.2.13 Ramp and Soak Menu..................................................46
3.2.14 ID Code Menu ...............................................................48
3.2.15 Communication Option Menu .....................................50
3.2.16 Display Color Selection Menu.....................................56
Part 4: Specifications ......................................................................................59
Part 5: Factory Preset Values .........................................................................62
CE APPROVAL INFORMATION.......................................................................64
i
Download from Www.Somanuals.com. All Manuals Search And Download.
LIST OF FIGURES:
Figure 2.1 Front Panel Display.....................................................................5
Figure 2.2 Rear Panel Power and Output Connections .............................5
Figure 2.3 Rear Panel Input Connections ...................................................6
Figure 2.4 Main Power Connections............................................................7
Figure 2.5 Process Current Wiring Hookup................................................8
Process Voltage
Figure 2.6 a) Process Voltage with Sensor Excitation...........................8
b) Process Voltage without Sensor Excitation .....................8
Strain Gauge
Figure 2.7 a) 4-Wire Voltage Input with Internal Excitation....................9
b) 4-Wire Bridge Input with External Excitation....................9
Figure 2.8 a) 6-Wire Voltage Input with Internal Excitation....................9
b) 6-Wire Bridge Input with External Excitation....................9
Figure 2.9 4-Wire Voltage Input with Internal Excitation..........................10
Wiring Outputs
Figure 2.10 a) Mechanical Relay and SSR Outputs Wiring Hookup .....10
b) Pulse and Analog Outputs Wiring Hookup.....................10
Figure 2.11 Snubber Circuits Wiring Hookup.............................................10
Figure 2.12 a) RS-232 Output Wiring Hookup.........................................11
b) RS-485 Outputs Wiring Hookup.......................................11
Figure 2.13 Typical Applications..................................................................12
Figure 2.14 a) Excitation Outputs ............................................................12
b) Top View Location of S2 ...................................................12
c) Top View Location of S2 on 1/8 DIN Compact Unit...........12
Figure 3.1 Flow Chart for ID and Setpoints Menu ....................................14
Figure 3.2 Flow Chart for Configuration Menu .........................................17
Figure 3.3 Flow Chart for Input Type Menu...............................................17
Figure 3.4 Flow Chart for Reading Configuration Menu..........................19
Figure 3.5 Flow Chart for Alarm 1 Menu....................................................26
Figure 3.6 Flow Chart for Analog Output (Retransmission) Menu..........30
Figure 3.7 Flow Chart for Alarm 2 Menu....................................................33
Figure 3.8 Flow Chart for Loop Break Time Menu....................................34
Figure 3.9 Flow Chart for Output 1 Menu..................................................36
Figure 3.10 Flow Chart for Output 2 Menu..................................................43
Figure 3.11 Flow Chart for Ramp and Soak Menu......................................46
Figure 3.12 Flow Chart for ID Code Menu ...................................................48
Figure 3.13 Flow Chart for Communication Option Menu.........................50
Figure 3.14 Flow Chart for Display Color Selection Menu.........................56
LIST OF TABLES:
Table 2.1
Table 2.2
Table 2.3
Table 2.4
Table 3.1
Table 3.2
Table 3.3
Table 5.1
Front Panel Display.....................................................................5
Rear Panel Connector.................................................................6
Fuse Requirements .....................................................................7
Jumper Connections.................................................................12
Button Function in Configuration Mode..................................13
Conversion Table.......................................................................23
Input Resolution Multiplier .......................................................23
Factory Preset Values ...............................................................62
ii
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES, WARNINGS and CAUTIONS
Information that is especially important to note is identified by following labels:
• NOTE
• WARNING or CAUTION
• IMPORTANT
• TIP
NOTE: Provides you with information that is important to successfully
setup and use the Programmable Digital Meter.
CAUTION or WARNING: Tells you about the risk of electrical shock.
CAUTION, WARNING or IMPORTANT: Tells you of circumstances or
practices that can effect the instrument’s functionality and must refer to
accompanying documents.
TIP: Provides you helpful hints.
1
Download from Www.Somanuals.com. All Manuals Search And Download.
PART 1
INTRODUCTION
1.1 Description
This device can be purchased as monitor (read process value only) or as
a controller.
•
The i Series Strain and Process controllers can measure a wide variety of
DC voltage and current inputs for all common load cells, pressure
transducers and strain gauge type of transducer. It offers unparalleled
flexibility in process control. The voltage /current inputs are fully scaleable to
virtually all engineering units, with selectable decimal point, perfect for use
with pressure, flow or other process input.
•
•
The process control can be achieved by using on/off or PID control strategy.
Control can be optimized with an Auto Tune feature. The controller offers a
ramp to set point with timed soak period before switching off the output.
The i Series controller features a large, three color programmable display
with capability to change a color every time when Alarm is triggered. The
standard features include dual outputs with relay, SSR, DC pulse, analog
voltage or current, built-in excitation for transducers, selectable as
10V @ 60 mA or 5 V @ 40 mA. Analog output is fully scaleable and may be
configured as a proportional controller or retransmission to follow your
display. Universal power supply accepts 90 to 240. Low voltage power option
accepts 24 Vac or 12 to 36 Vdc.
•
Options include programmable RS-232 or RS-485 serial communication and
ethernet with an embedded web server.
2
Download from Www.Somanuals.com. All Manuals Search And Download.
1.2 Safety Considerations
This device is marked with the international caution symbol. It is
important to read this manual before installing or commissioning this
device as it contains important information relating to Safety and EMC
(Electromagnetic Compatibility).
This instrument is a panel mount device protected in accordance with
EN 61010-1:2001, electrical safety requirements for electrical equipment
for measurement, control and laboratory. Installation of this instrument
should be done by qualified personnel. In order to ensure safe operation,
the following instructions should be followed.
This instrument has no power-on switch. An external switch or circuit-
breaker shall be included in the building installation as a disconnecting
device. It shall be marked to indicate this function, and it shall be in close
proximity to the equipment within easy reach of the operator. The switch
or circuit-breaker shall not interrupt the Protective Conductor (Earth wire),
and it shall meet the relevant requirements of IEC 947–1 and IEC 947-3
(International Electrotechnical Commission). The switch shall not be
incorporated in the main supply cord.
Furthermore, to provide protection against excessive energy being
drawn from the main supply in case of a fault in the equipment, an
overcurrent protection device shall be installed.
•
•
•
•
Do not exceed voltage rating on the label located on the top of the
instrument housing.
Always disconnect power before changing signal and power
connections.
Do not use this instrument on a work bench without its case for safety
reasons.
Do not operate this instrument in flammable or explosive
atmospheres.
Do not expose this instrument to rain or moisture.
Unit mounting should allow for adequate ventilation to ensure
instrument does not exceed operating temperature rating.
Use electrical wires with adequate size to handle mechanical strain
and power requirements. Install without exposing bare wire outside
the connector to minimize electrical shock hazards.
•
•
•
EMC Considerations
•
•
•
•
Whenever EMC is an issue, always use shielded cables.
Never run signal and power wires in the same conduit.
Use signal wire connections with twisted-pair cables.
Install Ferrite Bead(s) on signal wires close to the instrument if EMC
problems persist.
Failure to follow all instructions and warnings may result in injury!
3
Download from Www.Somanuals.com. All Manuals Search And Download.
1.3 Before You Begin
Inspecting Your Shipment:
Remove the packing slip and verify that you have received everything
listed. Inspect the container and equipment for signs of damage as soon
as you receive the shipment. Note any evidence of rough handling in
transit. Immediately report any damage to the shipping agent. The carrier
will not honor damage claims unless all shipping material is saved for
inspection. After examining and removing the contents, save the packing
material and carton in the event reshipment is necessary.
Customer Service:
If you need assistance, please call the nearest Customer Service
Department, listed in this manual.
Manuals, Software:
The latest Operation and Communication Manual as well as free
configuration software and ActiveX controls are available at the website
listed on the cover page of this manual or on the CD-ROM enclosed
with your shipment.
For first-time users: Refer to the QuickStart Manual for basic operation
and set-up instructions.
If you have the Serial Communications/Ethernet Option you can easily
configure the controller on your computer or on-line.
To Disable Outputs:
To ensure that menu changes are properly stored, Standby Mode should
be used during setup of the instrument. During Standby Mode, the
instrument remains in a ready condition, but all outputs are disabled.
Standby Mode is useful when maintenence of the system is necessary.
When the instrument is in "RUN" Mode, push d twice to disable all
outputs and alarms. It is now in "STANDBY" Mode. Push d once more
to resume "RUN" Mode.
PUSH d TWICE to disable the system during an EMERGENCY.
To Reset the Meter:
When the controller is in the "MENU" Mode, push c once to direct
controller one step backward of the top menu item.
Push c twice to reset controller, prior to resuming "Run" Mode except
after "Alarms", that will go to the "Run" Mode without resetting the
controller.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Refer to the Quick Start
Guide for assembly and
disassembly instructions.
PART 2
SETUP
2.1 Front Panel
1
1
1
/
/
/
8
DIN
16
DIN
32
DIN
Figure 2.1 Front Panel Display
Table 2.1 Front Panel Annunciators
1
2
Output 1/Setpoint 1/ Alarm 1 indicator
Output 2/Setpoint 2/ Alarm 2 indicator
a/MENU
Changes display to Configuration Mode and advances
through menu items*
b/PK/GRS
c/TARE
d/ENTER
Used in Program Mode and Peak or Gross Recall*
Used in Program Mode and to tare your reading*
Accesses submenus in Configuration Mode and stores
selected values*
* See Part 3 Operation: Configuration Mode
2.2 Rear Panel Connections
The rear panel connections are shown in Figures 2.2 and 2.3.
6
5
4
6
5
4
6
5
4
3
2
1
3
2
1
8
7
6
5
4
3
2
1
Figure 2.2 Rear Panel Power and Output Connections
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 2.3 Rear Panel Input Connections
Table 2.2 Rear Panel Connector
POWER
AC/DC Power Connector: All models
Input Connector:
INPUT
All models PR (Process) / ST (Strain)
OUTPUT 1 Based on one of the following models:
Relay SPDT
Solid State Relay
Pulse
Analog Output (Voltage and Current)
OUTPUT 2 Based on one of the following models:
Relay SPDT
Solid State Relay
Pulse
Based on one of the following models:
RS-232C or RS-485 programmable
Excitation
OPTION
6
Download from Www.Somanuals.com. All Manuals Search And Download.
2.3 Electrical Installation
2.3.1 Power Connections
Caution: Do not connect power to your device until you have completed all
input and output connections. Failure to do so may result in injury!
Connect the main power connections as shown in Figure 2.4.
Figure 2.4 Main Power Connections
Table 2.3 Fuse Requirements
FUSEConnector
Output
Power *
Power *
Type
N/A
N/A
For
115
Vac
100 mA(T)
N/A
For
100 mA(T)
400 mA(T)
230
FUSE 1
FUSE 2
100 mA(T)
N/A
For the low voltage power option, in order to maintain the same degree of
protection as the standard high voltage input power units (90 - 240 Vac),
always use a Safety Agency Approved DC or AC source with the same
Overvoltage Category and pollution degree as the standard AC unit (90 -
240 Vac).
The Safety European Standard EN61010-1 for measurement, control,
and laboratory equipment requires that fuses must be specified based on
IEC127. This standard specifies for a Time-lag fuse, the letter code “T”.
The above recommended fuses are of the type IEC127-2-sheet III. Be
aware that there are significant differences between the requirements
listed in the UL 248-14/CSA 248.14 and the IEC 127 fuse standards. As a
result, no single fuse can carry all approval listings. A 1.0 Amp IEC fuse
is approximately equivalent to a 1.4 Amp UL/CSA fuse. It is advised to
consult the manufacturer’s data sheets for a cross-reference.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
2.3.2 Process Current
The figure below shows the wiring hookup for Process Current 0 – 20 mA.
Figure 2.5 Process Current Wiring Hookup
(Internal and External Excitation)
2.3.3 Process Voltage
The figure below shows the wiring hookup for Process Voltage 0 – 100 mV,
0 – 1 V, 0 – 10 V.
Figure 2.6
a) Process Voltage Wiring Hookup b) Process Voltage Wiring Hookup
with Sensor Excitation
without Sensor Excitation
RL - Voltage limited resistor, which allows to convert 24 Vdc internal excitation
voltage to the appropriate process input value. For instance: if the potentiometer
value is equal to 10 kΩ, the minimum RL is 14 kΩ for 10 V process input.
When configuring your instrument, select Process Type in the Input Type Menu
(see Part 3).
8
Download from Www.Somanuals.com. All Manuals Search And Download.
2.3.4 Strain Gauge
The figure below shows the wiring hookup for 4-wire bridge input.
Figure 2.7
a) 4-Wire Voltage/Bridge Input
with Internal Excitation
Wiring Hookup
b) 4-Wire Bridge Input with
External Excitation Wiring
Hookup
In 4-Wire connections the voltage drop across long excitation lead wires of strain
gauge bridge may cause measurement errors. The output of a strain gauge
bridge also depends on the stability of excitation voltage. To correct for voltage
drop and changes in excitation voltage, 6-wire input configuration and ratio
measurement are used.
In order for the Ratiometric to work properly, the External Excitation should
not drop below 4.6 Vdc.
The figure below shows 6-wire hookup for 6-wire bridge input.
Figure 2.8
a) 6-Wire Bridge Input with
Internal Excitation and
Ratio Measurement Wiring
Hookup
b) 6-Wire Bridge Input with
External Excitation and
Ratio Measurement Wiring
Hookup
9
Download from Www.Somanuals.com. All Manuals Search And Download.
2.3.4 Strain Gauge (continued)
The figure below shows Voltage (bridge with
amplified output) input with internal excitation.
Where:
+S: signal plus
-S: signal return
+Ext: excitation plus
-Ext: excitation return
+E: plus excitation sense
-E: minus excitation sense.
Figure 2.9
4-Wire Voltage Input (Bridge
withAmplified Output)
with Internal Excitation.
2.3.5 Wiring Outputs
This meter has two, factory installed, outputs. The SPDT Mechanical Relay, SPST
Solid State Relay, Pulse and Analog Output Connection are shown below.
Figure 2.10 a) Mechanical Relay and SSR b) Pulse and Analog
Outputs Wiring Hookup
Outputs Wiring Hookup
This device has snubber circuits
designed to protect the contacts of the
mechanical relays when it switches
inductive loads (i.e. solenoids, relays). These
snubbers are internally connected between the
Common (C) and Normally Open (NO) relay
contacts of Output 1 and Output 2.
If you have an inductive load connected
between Common (C) and Normally Closed
(NC) contacts of the mechanical relays and you
want to protect them from the rush current
during the switching period, you have to connect
an external snubber circuit between Common
(C) and Normally Closed (NC) contacts as
indicated in the figure below.
Figure 2.11 Snubber
Circuits Wiring Hookup
10
Download from Www.Somanuals.com. All Manuals Search And Download.
2.3.5 Wiring Outputs (continued)
This device may also have a programmable communication output. The RS-232
and RS-485 Output Connection are shown below.
If your meter has the communication option, the internal excitation is not
available. Use external excitation for strain gauge meter.
External RS-232 connections are not available with -EI or C4EI options.
Figure 2.12
a) RS-232 Output Wiring Hookup b) RS-485 Output Wiring Hookup
dc CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH dc VOLTAGE SSR DRIVER OUTPUT
TEMPERATURE
CONTROLLER
dc INPUT
SSR
CONTROL
SIDE
LOAD
SIDE
HEATER
4
1
Vac
Vac
3
2
0 or 5 Vdc,
TYPICALLY
FAST BLOW
FUSE
ac CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH MECHANICAL RELAY OUTPUT
TEMPERATURE
ac INPUT
CONTROL
SIDE
LOAD
SIDE
CONTROLLER
SSR
HEATER
4
3
1
2
Vac
Vac
FAST BLOW
FUSE
Vac
DRIVING
SSR
ac CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH TRIAC OUTPUT
CONTROL SIDE
TEMPERATURE
ac INPUT
LOAD
LOAD
SIDE
CONTROLLER
SSR
RESISTOR
HEATER
4
3
1
2
Vac
Vac
FAST BLOW
FUSE
Vac
DRIVING
SSR
Figure 2.13 Typical Applications
11
Download from Www.Somanuals.com. All Manuals Search And Download.
2.3.5 Wiring Outputs (continued)
This meter is capable of supplying 5 or 10 Vdc sensor excitation. The excitation
output connection and location of S2 pin selection jumper are shown below.
Excitation is not available if Serial Communication (-C24) or Ethernet
(-C4EI) or Low Voltage Power Supply (-DC) options are installed.
Figure 2.14
a) Excitation Output
b) Top View Location of S2
c) Top View Location of S2 on 1/8 DIN Compact Unit
Install jumpers according to the table below.
Table 2.4 Jumper Connections
Excitation Output
S2
A
B
10 V
5 V
Close
Open
Open
Close
Factory default is 10 V.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
PART 3
OPERATION: CONFIGURATION MODE
3.1 Introduction
The instrument has two different modes of operation. The first, Run Mode, is
used to display values for the Process Variable, and to display or clear Peak
and Valley values. The other mode, Menu Configuration Mode, is used to
navigate through the menu options and configure the controller. Part 3 of this
manual will explain the Menu Configuration Mode. For your instrument to
operate properly, the user must first "program" or configure the menu options.
Turning your Controller On for the First Time
The device becomes active as soon as it is connected to a power source. It
has no On or Off switch. The device at first momentarily shows the software
version number, followed by reset
, and then proceeds to the Run Mode.
RST
For first-time users: Refer to the QuickStart Manual for basic operation
and set-up instructions.
If you have the Serial Communications/Ethernet Option you can easily
configure the controller on your computer or on-line.
Table 3.1 Button Function in Configuration Mode
• To enter the Menu, the user must first press button.
a
• Use this button to advance/navigate to the next menu item. The user can navigate
a
MENU
through all the top level menus by pressing
.
a
• While a parameter is being modified, press to escape without saving the parameter.
a
• Press the up button to scroll through “flashing” selections. When a numerical
b
value is displayed press this key to increase value of a parameter that is currently
being modified.
b
PK/GRS
• Holding the button down for approximately 3 seconds will speed up the rate at
b
(UP)
which the set point value increments.
•
In the Run Mode press causes the display to flash the PEAK or GROSS value –
press again to return to the Run Mode.
b
• Press the down button to go back to a previous Top Level Menu item.
c
• Press this button twice to reset the controller to the Run Mode.
• When a numerical value is flashing (except set point value) press to scroll digits
c
c
from left to right allowing the user to select the desired digit to modify.
TARE
• When a setpoint value is displayed press to decrease value of a setpoint that is
c
(DOWN)
currently being modified. Holding the button down for approximately 3 seconds
c
will speed up the rate at which the setpoint value is decremented.
• In the Run Mode press c causes the display to flash the TARE value to tare your
reading (zeroing). Press again to return to the Run Mode.
• Press the enter dbutton to access the submenus from a Top Level Menu item.
• Press d to store a submenu selection or after entering a value — the display will
d
ENTER
flash a
message to confirm your selection.
STRD
• To reset flashing Peak or Valley press d.
• In the Run Mode, press dtwice to enable Standby Mode with flashing
.
STBY
Reset: Except for Alarms, modifying any settings of the menu configuration
will reset the instrument prior to resuming Run Mode.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2 Menu Configuration
It is required that you put the controller in the Standby Mode for any
configuration change other than Set Points & Alarms.
Figure 3.1 Flow Chart for ID and Set Points Menu
14
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.1 ID Number Menu
SEE ID MENU SELECTION IN CONFIGURATION SECTION FOR
ENABLE/DISABLE OR CHANGE ID CODE.
If ID Code is Disabled or set as Default (0000) the menu will skip ID step
to Set Point Menu.
If ID Code is set to Full Security Level and user attempts to enter the
Main Menu, they will be prompted for an ID Code.
If ID Code is set to Setpoint/ID Security Level and user attempts to enter
the Configuration Menu, they will be prompted for an ID Code.
ENTERING YOUR NON-DEFAULT FULL SECURITY ID NUMBER.
Press a
1) Display shows
.
ID
2) Display advances to
Press d
.
____
Press b & c 3) Press to increase digit 0-9. Press to activate next digit
b
c
(flashing). Continue to use and c to enter your 4-digit ID code.
b
Press d
4) If the correct ID code is entered, the menu will advance to the
Setpoint 1 Menu, otherwise an error message
will be
ERRo
displayed and the instrument will return to the Run Mode.
To change ID Code, see ID Menu in the Configuration section.
ENTERING YOUR NON-DEFAULT SETPOINT/ID SECURITY ID NUMBER.
Press a
Press a
Press a
Press d
5) Display shows
6) Display shows
7) Display shows
Setpoint 1 Menu.
Setpoint 2 Menu.
SP1
SP2
ID Code Menu.
ID
8) Display advances to
.
____
Press b & c 9) Use b and c to change your ID Code.
Press d 10) If correct ID Code is entered, the display will advance to the
Input Menu, otherwise the error message will be
INPT
ERRo
displayed and the controller will return to the Run Mode.
To prevent unauthorized tampering with the setup parameters, the
instrument provides protection by requiring the user to enter the ID Code
before allowing access to subsequent menus. If the ID Code entered
does not match the ID Code stored, the controller responds with an error
message and access to subsequent menus will be denied.
Use numbers that are easy for you to remember. If the ID Code is
forgotten or lost, call customer service with your serial number to access
and reset the default to
.
0000
15
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.2 Set Points Menu
SETPOINT 1:
Press a
1) Press a, if necessary until
prompt appears.
SP1
Press d
2) Display shows previous value of “Setpoint 1” with 1st digit
flashing.
Press b & c 3) Press b and c to increase or decrease Setpoint 1
respectively.
Holding b & c buttons down for approximately 3 seconds will speed up the
rate at which the set point value increments or decrements.
Press b & c 4) Continue to use b and c to enter your 4-digit Setpoint 1 value.
Press d
5) Display shows
stored message momentarily and then
STRD
only, if a change was made, otherwise press a
advance to
SP2
to advance to
Setpoint 2 Menu.
SP2
SETPOINT 2:
Press d
6) Display shows previous value of “Setpoint 2” with 1st digit
flashing.
Press b & c 7) Press b and c to increase or decrease Setpoint 2
respectively.
Holding b & c buttons down for approximately 3 seconds will speed up
the rate at which the setpoint value increments or decrements.
Press d
8) Display shows
stored message momentarily and then
STRD
advances to
only, if a change was made, otherwise press a
CNFG
to advance to
Configuration Menu.
CNFG
16
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.3 Configuration Menu
Figure 3.2 Flow Chart for Configuration Menu
Enter Configuration Menu:
Press a
Press d
Press a
1) Press a, if necessary, until
prompt appear.
CNFG
Input Menu.
2) Display advance to
INPT
3) Press and release a to scroll through all available menus of
Configuration section.
3.2.4 Input Type Menu
Figure 3.3 Flow Chart for Input Type Menu
17
Download from Www.Somanuals.com. All Manuals Search And Download.
ENTER INPUT TYPE MENU:
Press a
Press d
Press d
1) Press a, if necessary, until
prompt appears.
CNFG
Input Menu.
2) Display advances to
INPT
,
3) Display flashes
,
or (0 to 100 mV,
0-0.1 0-1.0 0-10 0-20
0 to 1 V, 0 to 10 V or 0 to 20 mA).
INPUT TYPE MENU:
Press b
4) Scroll through the available selection of input ranges
,
0-0.1
,
or
to the selection of your choice.
stored message momentarily and then
0-1.0 0-10 0-20
Press d
5) Display shows
STRD
Ratiometric Operation Submenu.
advances to the
RT1B
Input Types:
Display:
100 mV 1 V 10 V
0-0.1 0-1.0 0-10
0 – 20 mA
0-20
RATIOMETRIC OPERATION SUBMENU:
Press d
Press b
Press d
6) Display flashes previous selection of
Disable.
Enable or
ENBL DSBL
7) Scroll through the available selection
(flashing).
or
ENBL DSBL
8) Display shows
stored message momentarily and then
STRD
Input/Reading Resolution Submenu.
advances to
RESO
The Ratiometric operations are typically used for Strain gauge controller.
If your controller is configured as Process (Voltage and Current), set
to
RTIB DSBL
disable Ratiometric operations.
If
Ratiometric operations Enabled was selected, the changes to
ENBL
the excitation voltage will be compensated through Ratio measurement.
If
Ratiometric operation Disabled was selected, any changes to
DSBL
the excitation voltage will effect the output of strain gauge bridge and, as
a result, a reading of the controller.
INPUT/READING RESOLUTION SUBMENU:
Press a
9) Display flashes previous selection of
Low or
High
HI
LO
resolution.
Press d
Press d
10) Scroll through the available selection
or
(flashing).
LO HI
11) Display shows
stored message momentarily and then
STRD
Button Selection Submenu.
advances to
BUTN
If
If
Low Resolution was selected the resolution of the display is 10 µV.
High Resolution was selected the resolution of the display is 1 µV.
LO
HI
In case of High Resolution, the maximum input signal is 10 mV.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
BUTTON SELECTION SUBMENU:
Press d
Press b
Press d
12) Display flashes previous selection of
Gross or
GROS PEAK
Peak.
13) Scroll through the available selection
selection of your choice.
or
GROS PEAK
to the
14) Display shows
stored message momentarily and then
STRD
Reading Configuration Menu.
advances to
RDG
If
was selected, in the Run Mode pressing
b
button causes the
GROS
display to flash Gross value (value measured without zeroing of the
display).
If
was selected, in the Run Mode pressing
b
button causes the
PEAK
display to flash Peak value.
0 - 20 mA current input used for process control only.
For 4 - 20 mA Input select 0 - 20 mA and adjust the Input/Reading
accordingly. To adjust 4 - 20 mA input, see example under
INPUT/READING Submenu.
3.2.5 Reading Configuration Menu
It is required that you put the controller in the Standby Mode
for any configuration change other than Set Points & Alarms.
Figure 3.4 Flow Chart for Reading Configuration Menu
19
Download from Www.Somanuals.com. All Manuals Search And Download.
ENTER READING CONFIGURATION MENU:
Press
Press
Press
Press
1) Press , if necessary, until
prompt appears.
a
d
a
d
a
CNFG
Input Menu.
2) Display advances to
3) Display advances to
4) Display advances to
INPT
RDG
DEC
Reading Configuration Menu.
Decimal Point.
DECIMAL POINT SUBMENU:
Press
Press
5) Display flashes previous selection for Decimal location.
d
b
6) Scroll though the available selections and choose Decimal
location:
,
,
or
FFFF FFF.F FF.FF F.FFF
Press
7) Display shows
stored message momentarily only, if
d
STRD
changes were made, otherwise press to advance to
a
LOAD
Known/Unknown Loads Submenu.
Decimal Point is passive.
KNOWN/UNKNOWN LOADS SUBMENU:
Press
Press
Press
8) Display flashes previous selection of
Enable or
ENBL DSBL
d
b
d
Disable.
9) Scroll though the available selection of
or
ENBL DSBL
(flashing).
10) Display shows
stored message momentarily and then
STRD
advances to L.PNT Linearization Points Submenu.
If Known Loads scaling method was selected, calculate
ENBL
the input values to the instrument based on the actual signal
being received. If
Without Known Loads scaling method
DSBL
was selected, calculate input values to the instrument based on
the transducer specification.
LINEARIZATION POINTS SUBMENU:
Press
Press
11) Display flashes previous selection of Linearization Points
Submenu.
12) Scroll though the available selections: 0002, 0003, 0004,
0006, 0006, 0007, 0008, 0009, 0010 - up to 10
Linearization Points can be selected. Default is 0002.
d
b
If display flashes NONE, your instrument has only 2 linearization
points.
Press
13) Display shows
stored message momentarily only, if a
d
STRD
change was made, otherwise press to advance to the
a
FLTR
Filter Constant Submenu.
Linearization Points allow users to customize the Transducer curve.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
FILTER CONSTANT SUBMENU:
Press
Press
14) Display flashes previous selection for Filter Constant.
15) Scroll though the available selections:
d
b
,
,
,
0001 0002 0004
. - Default is
,
,
,
,
0008 0016 0032 0064 0128
0004
Press
16) Display shows
stored message momentarily only, if a
d
STRD
change was made, otherwise press to advance to
a
IN.RD
Input/Reading Submenu.
The Filter Constant Submenu allows the user to specify the
number of readings stored in the Digital Averaging Filter.
For PID control select filter value 0001-0004. A filter value of 2 is
approximately equal to 1 second RC low pass time constant.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.6 Input/Reading (Scale and Offset) Menu
Input voltage or current can be converted or scaled into values appropriate for
the process or signal being measured. So, a reading may be displayed, for
example, in units of weight or velocity instead of in amperes and volts.
The controller determines scale and offset values based on two user-provided
input values entered with the corresponding readings.
There are two methods to scale this meter to display readings in engineering units.
The first method is to scale with known loads. Do this by applying known loads
to a transducer connected to a meter, or by simulating the output of the
transducer with voltage or current simulator.
The second method is to scale without known inputs. Do this by calculating
input values based on transducer specifications and manually entering them
through the front panel push-buttons.
Example 1: Scaling with Known Loads (On-Line Calibration).
When entering the input or reading values, disregard the position of the
decimal point.
If
Enabled Load Submenu was selected, instrument is ready for
ENBL
scaling with Known Loads method.
Apply a known load equal to approximately 0% of the
transducer range.
Press
17) Press at the
prompt. Display shows IN!2 Input 1
IN.RD
d
d
Submenu.
Press
Press
Press
Press
18) Display shows the actual signal being received.
d
d
d
b
19) Display advances to RD!1 Reading 1 Submenu.
st
20) Display shows last stored Reading 1 value with 1 digit flashing.
&
21) Use and buttons to enter RD!1 value.
c
b
c
This value corresponds to Input 1 in terms of some meaningful
engineering units. To show Input 1 as zero percent enter RD!1
value = 0000.
Press
22) Display shows IN!2 Input 2 Submenu.
d
Apply a known load equal to approximately 100% of the
transducer range.
Press
Press
Press
Press
23) Display shows the actual signal being received.
24) Display advances to RD!2 Reading 2 Submenu.
d
d
d
b
st
25) Display shows last stored Reading 1 value with 1 digit flashing.
&
26) Use and buttons to enter RD!2 value.
c
b
c
This value corresponds to Input 2 in terms of some meaningful
engineering units. To show Input 2 as 100% enter RD!2 value = 0100.
This scaling method based on 2 input values entered with 2 corresponding
reading. Up to 10 linearization points can be selected to customize the
transducer curve. To select linearization points see “L.PNt” Submenu.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Max scale should not be more than 50% FS because of noise related
issues.
Press
27) Display flashes
stored message momentarily and then
STRD
only, if a change was made, otherwise
Alarm 1 Menu.
d
advances to
advances to
ALR1
ALR1
Example 2: Scaling without Known Loads.
If
Disabled Load Submenu was selected, instrument is ready for
DSBL
scaling Without Known Loads method.
To scale without known inputs, calculate inputs based on transducer specifications
and manually enter them on the via front panel push-buttons. The following example
assumes load cells with this specification:
Maximum Load:
Output:
100.0 lb
3.0 mV/V
10 V
Sensor Excitation
Maximum Sensor Output = 3.0 (mV/V) x 10 (V) = 30 mV
(
)
1. Determine the correct values for Inputs IN!1 and IN!2 .
Calculate IN!1 and IN!2 using the following equation:
= (Sensor Output) x (Converison Number) x (Multiplier)
IN
Conversion number is a coefficient of conversion between input values
and real full display range (10000 counts). See Table 3.1 below for proper
conversion number.
Table 3.2 Conversion Table
INPUT RANGE CONVERSION NUMBER
0 ~ 100 mV
0 ~ 1 V
0 ~ 10 V
10000 / (100 x 1) = 100 cts/mV
10000 / (1000 x 1) = 10 cts/mV
10000 / (1000 x 10) = 1 cts/mV
10000 / (20 x 1) = 500 cts/mV
0 ~ 20 mA
(
Multiplier determined by the Input Resolution setting
Menu). See Table 3.2 below for proper multiplier.
in the
INPT
RESO
Table 3.3 Input Resolution Multiplier
INPUT
SROALNUGTEIORNE
LOW
1.0
1.0
1.0
1.0
HIGH
10.0
10.0
10.0
10.0
0 ~ 100 mV
0 ~ 1 V
0 ~ 10 V
0 ~ 20 mA
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Determine IN!1 and IN!2 Input Range and Resolution. For our transducer select
0 ~ 100 mV range and LOW resolution (10 µV)
IN!1 = 0 (mV) X 100 (cts/mV) x 1.0 = 0
IN!2 = 30 (mV) X 100 (cts/mV) x 1.0 = 3000
(
)
2. Determine correct values for Display Reading RD!1 and RD!2 . In most cases,
RD!1 and RD!2 are equal to the minimum and the maximum of the transducer
output range.
RD!1 = 0000
RD!2 = 100.0
3. Scaling the controller.
Press
28) Press at the
prompt. Display shows IN!1 Input 1
d
d
IN.RD
Submenu.
st
Press
Press
Press
29) Display shows last stored Input 1 value with 1 digit flashing.
d
b
d
&
30) Use and buttons to enter IN!1 value (0000).
c
b
c
31) Display advances to RD!1 only, if a change was made,
otherwise press to advance to RD!1 Reading 1 Submenu.
a
st
Press
32) Display shows last stored Reading 1 value with 1 digit
d
flashing.
Press
Press
Press
Press
Press
&
&
33) Use and buttons to enter RD!1 value (0000).
b
d
d
b
d
c
c
b
c
34) Display IN!2 Input 2 Submenu.
35) Display shows last stored Input 2 value with 1 digit flashing.
36) Use and buttons to enter IN!2 value (3000).
st
b
c
37) Display advances to RD!2 only, if a change was made,
otherwise press to advance to RD!2 Reading 2 Submenu.
a
st
Press
38) Display shows last stored Reading 2 value with 1 digit
d
flashing.
Press
Press
&
39) Use and buttons to enter RD!2 value (1000).
b
d
c
b
c
40) Display flashes
stored message momentarily and
STRD
only, if a change was made, otherwise
then advances to
ALR1
Alarm 1 Menu.
advances to
ALR1
This scaling method based on 2 input values entered with 2
corresponding reading. Up to 10 linearization points can be
selected to customize the transducer curve. To select
linearization points see “L.PNt” Submenu.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Example 3: Scaling with Current/Voltage Transducer (Process) Input.
The following example include details for a specific scenario in
which a 4 - 20 mA input is to be represented as a measurement
of 0 - 100 percent.
Press
41) Press at the
prompt. Display shows IN!1 Input 1
d
d
IN.RD
Submenu.
st
Press
Press
42) Display shows Input 1 value with 1 digit flashing.
d
b
&
&
43) Use and buttons to enter IN!1 value.
c
c
b
c
The IN!1 value = min. input value x conversion number
from Table 3.1
Enter 4 mA as 4 (mA) x 500 = 2000
Press
Press
44) Display advances to RD!1 Reading 1 Submenu.
d
b
45) Use and buttons to enter RD!1 value.
b
c
This value corresponds to Input 1 in terms of some meaningful
engineering units. To show 4 mA as zero percent enter RD!1
value = 0000.
Press
Press
46) Display IN!2 Input 2 Submenu.
d
d
st
47) Display shows IN!2 Input 2 value with 1 digit flashing
.
The IN!2 value = max. input value x conversion number
from Table 3.1
Enter 20 mA as 20 (mA) x 500 = 10000 (entered as 9999)
Press
Press
Press
&
&
48) Use and buttons to enter IN!2 value.
b
d
b
c
c
b
c
49) Display advances to RD!2 Reading 2 Submenu.
50) Use and buttons to enter RD!2 value.
b
c
To show 20 mA as 100 percent enter RD!2 value = 0100
51) Display flashes stored message momentarily and
Press
d
STRD
only, if a change was made, otherwise
then advances to
ALR1
Alarm 1 Menu.
advances to
ALR1
25
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.7 Alarm 1 Menu
This unit is equipped with two physical outputs that can only be configured as
follows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, Output 1 & Alarm 2, Output1
& Output 2, Analog Out 1 & Alarm 2, Analog Out 1 & Output 2. Analog Out
available only if Analog Output Option board is factory installed.
If Analog Output Option is installed, the controller will skip Alarm 1 Menu
item to Analog Output.
Alarm must be DISABLED if Ramp is ENABLED.
Figure 3.5 Flow Chart for Alarm 1 Menu
ENTER ALARM 1 MENU:
Press a
Press d
Press a
1) Press a, if necessary, until
prompt appears.
CNFG
Input Menu.
2) Display advances to
INPT
3) Press a, if necessary, until Display advances to
Alarm 1
ALR1
Enable or Disable
ENBL DSBL
Menu.
Press d
4) Display advances to Alarm 1
Submenu and flashes the previous selection.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
ALARM 1 ENABLE/DISABLE SUBMENU:
Press b
Press
5) Scroll though the available selection until
displays to
ENBL
use Alarm 1.
6) Display shows
stored message momentarily and then
STRD
d
advances to
only, if it was changed, otherwise press a
ABSo
to advance to
Alarm 1 Absolute/Deviation Submenu.
ABSo
If
Alarm 1 Disabled was selected, all submenus of Alarm
DSBL
1 Menu will be skipped and meter advances to
Alarm 2
ALR2
Alarm 1 Enabled was selected, Output 1 would
Menu. If
ENBL
be automatically disabled, and reassigned as Alarm 1.
ALARM 1 ABSOLUTE/DEVIATION SUBMENU:
Press
Press
7) Display flashes previous selection. Press to
ABSo
d
d
b
Absolute or
Deviation.
_DEV
8) Display shows
stored message momentarily and then
STRD
advances to
only, if it was changed, otherwise press a
LTçH
to advance to
Alarm 1 Latch/Unlatch Submenu.
LTçH
Absolute Mode allows Alarm 1 to function independently from Setpoint 1. If the
process being monitored does not change often, then "Absolute" Mode is
recommended.
Deviation Mode allows changes to Setpoint 1 to be made automatically to
Alarm 1. Deviation Mode is typically the ideal mode if the process value changes
often. In Deviation Mode, set Alarm 1 a certain number of degrees or counts
away from Setpoint 1 — this relation remains fixed even if Setpoint 1 is changed.
ALARM 1 LATCH/UNLATCH SUBMENU:
Press
Press
9) Display flashes previous selection. Press to
LTçH
d
d
b
Latched or
Unlatched.
UNLT
10) Display shows
stored message momentarily and then
STRD
advances to
only, if it was changed, otherwise press a to
CT.CL
advance to
Contact Closure Submenu.
CT.CL
Latched Mode: Relay remains "latched" until reset. To reset already latched
alarm, select Alarm Latch and press twice (i.e. Unlatch and then back to
b
Latch) or from a Run Mode, push twice to put the controller in Standby Mode
d
and then push one more time to return to the Run Mode.
d
Unlatched Mode: Relay remains latched only as long as the alarm condition is
true.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
CONTACT CLOSURE SUBMENU:
Press
11) Display flashes previous selection. Press b to
. Normally
N.ç.
d
Closed or
. Normally Open.
N.o.
Press
12) Display shows
stored message momentarily and then
only, if it was changed, otherwise press to
d
STRD
advances to
AçTV
AçTV
a
advance to
Active Submenu.
Normally Open: If this feature is selected, then the relay is "energized" only
when an alarm condition occurs.
Normally Closed: "Fail Safe" Mode. Relay is energized under "normal"
conditions and becomes de-energized during alarm or power failure.
ACTIVE SUBMENU:
Press
13) Display flashes previous selection. Press to scroll through
d
d
b
Below,
the available selections:
Above,
ABoV
BELo
_DEV
HI.Lo
Deviation was
HI/Low and
selected).
Band. (Band is active if
BAND
Press
14) Display shows
stored message momentarily and then
STRD
advances to
only, if it was changed, otherwise press a
A.P.oN
A.P.oN
to advance to
Alarm Enable/Disable at Power On
Submenu.
Above: Alarm 1 condition triggered when the process variable is greater than the
Alarm Hi Value (Low value ignored).
Below: Alarm 1 condition triggered when the process variable is less than the
Alarm Low Value (Hi value ignored).
Hi/Low: Alarm 1 condition triggered when the process variable is less than the
Alarm Low Value or above the Hi Value.
Band: Alarm 1 condition triggered when the process variable is above or below
the "band" set around Setpoint 1. Band equals Hi Value (Low Value ignored). A
"band" is set around the Setpoint by the instrument only in the "Deviation" Mode.
The Band for the AL 1 would be following the Setpoint 1 value
The Band for the AL 2 would be following the Setpoint 2 value.
The Band or the Deviation Value should be entered under:
AL1 High (if they want Alarm 1)
AL2 High (if they want Alarm 2)
AL Low value is ignored in the Band mode.
Example: if customer requires a Deviation Value of 10 degrees around a
setpoint (using Output 2 as alarm)
Output 2: disabled (this enables the Alarm 2)
Alarm 2: - Deviation
Contact Closure type: Deviation---Band
AL2 High: 10 (Band they want around Setpoint 2)
Then the Band Value is to be entered under AL2 HI: 10 not 80+10 = 90
28
Download from Www.Somanuals.com. All Manuals Search And Download.
ALARM ENABLE/DISABLE AT POWER ON:
Press
Press
15) Display flashes previous selection. Press to
enable
ENBL
d
d
b
or
disable.
DSBL
16) Display shows
stored message momentarily and then
STRD
only, if it was changed, otherwise press
advances to
ALR.L
to advance to the
a
Alarm 1 Low Value Submenu.
ALR.L
If the alarm is enabled at Power On, the alarm will be active right after
reset. If the alarm is disabled at Power On, the alarm will become
enabled when the process value enters the non alarm area. The alarm is
not active while the process value is approaching Setpoint 1.
ALARM 1 LOW VALUE SUBMENU:
st
Press
17) Display flashes 1 digit of previous value. Use and to
d
b
c
enter new value.
18) Use and to enter Alarm 1 Low Value.
Press
Press
&
b
d
c
b
c
19) Display shows
storage message momentarily and
only, if it was changed, otherwise press a
STRD
ALR.H
then advances to
to advance to
Alarm 1 HI Value Submenu.
ALR.H
ALARM 1 HI VALUE SUBMENU:
st
Press
20) Display flashes 1 digit of previous value. Use and to
d
b
c
enter new value.
21) Use and to enter Alarm1 HI Value.
STRD
advances to the next menu only, if it was changed, otherwise
press to advance to the next menu.
Press
Press
&
b
d
c
b
c
22) Display shows
stored message momentarily and then
a
If the input wires of the meter get disconnected or broken, it will display
+ OL Input (+) Overload message. For safety purposes you can set up
your alarm to be triggered when input is open.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.8 Analog Output (Retransmission) Menu
Analog Output can be configured as Retransmission or Control outputs.
In this section we will discuss Retransmission Output.
This unit is equipped with two physical outputs that can only be configured as
follows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, Output 1 & Alarm 2, Output
1 & Output 2, Analog Out 1 & Alarm 2, Analog Out 1 & Output 2. Analog
Output is available only if Analog Output Option board is factory installed.
If Analog Output Option is not installed, the instrument will skip to Alarm 2 Menu.
Figure 3.6 Flow Chart for Analog Output (Retransmission) Menu
ENTER ANALOG OUTPUT MENU:
Press
Press
Press
1) Press , if necessary, until
prompt appears.
a
d
a
a
CNFG
Input Menu.
2) Display advances to
INPT
3) Press , if necessary, until display advances to
Analog
ANLG
a
Output Menu.
Press
4) Display advances to Analog Output
Enable or
ENBL DSBL
d
Disable Submenu and flashes the previous selection.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
ANALOG OUTPUT ENABLE/DISABLE SUBMENU:
Press
5) Scroll though the available selection until
displays to
ENBL
b
use Analog Output Retransmission (output proportional to the
input signal).
Press
6) Display shows
stored message momentarily and then
d
STRD
or
advances to
Submenu only if it was changed,
CURR VoLT
otherwise press a to advance to
or Current/Voltage
CURR VoLT
Submenu.
If
Analog Output Disabled was selected, all submenus of Analog
DSBL
Output Menu will be skipped and the meter will advance to
Alarm 2
ALR2
Analog Output Enabled was selected, Output 1 would be
Menu. If
ENBL
automatically Disabled, and reassigned as Analog Output.
CURRENT/VOLTAGE SUBMENU:
Press
Press
7) Display flashes
Current or Voltage.
VoLT
d
b
CURR
8) Scroll through the available selection: Current or Voltage
(
)
.
Example
VoLT
9) Display shows
Press
stored message momentarily and then
d
STRD
Submenu only if it was changed, otherwise
advances to
press to advance to
RD1
Reading 1 Submenu.
RD1
a
READING 1:
st
Press
Press
Press
10) Display flashes 1 digit of previous “Reading 1” value.
d
b
d
&
11) Enter “Reading 1” value. (Example 0000)
12) Display advances to
c
Out 1 Submenu.
OUT.1
OUT 1:
st
Press d
13) Display flashes 1 digit of previous “Out 1” value.
Press b & c 14) Enter “Out 1” value. (Example 00.00)
Press d
15) Display advances to RD!2 Reading 2 Submenu.
READING 2:
st
Press
Press
Press
16) Display flashes 1 digit of previous “Reading 2” value.
d
b
d
&
17) Enter “Reading 2” value. (Example 9999)
18) Display advances to
c
c
Out 2 Submenu.
OUT.2
OUT 2:
t
st
Press
Press
Press
19) Display flashes 1 digit of previous “Out 2” value.
d
b
d
&
20) Enter “Out 2” value. (Example 10.00)
21) Display advances to the
Alarm 2 Menu.
ALR2
The above example is for 0 - 10 V of the entire range of the Process
Input and Analog Output. For 0 - 20 mA output you need to set “Analog
Type” to Current and OUT 2 to 20.00.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Accuracy of Analog Output board is +/-1% of FS (Full Scale) when following
conditions are satisfied:
1. The input is not scaled below 1% of Input FS (10 mV @ 1 V or 0.2 mA @
20 mA input ranges).
2. Analog Output is not scaled below 3% of Output FS (300 mV @ 10 V or
0.6 mA @ 20 mA output ranges).
Otherwise certain corrections need to be applied.
For example:
For entire range of process input, the Analog Output on 10 V FS scaled for
300 mV output range:
Rd1 = 0000, Out1 = 00.00
RD2 = 9999, Out2 = 00.30
The measured output will be as follows:
Rd1 = 0000, Out1 = -0.07 V
Rd2 = 9999, Out2 = 0.23 V
This means that for 300 mV output range we have -70 mV offset at zero and at
full scale. In order to compensate this 70 mV offset the correct scaling will be
as follows:
Rd1 = 0000, Out1 = 00.07
Rd2 = 9999, Out2 = 00.37
The above corrections need to be applied only for Input scaled below 1% of FS
and Output scaled below 3% of FS or if you need the Analog Output accuracy
to be better than 1% of FS.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.9 Alarm 2 Menu
This unit is equipped with two physical outputs that can only be configured as
follows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, Output 1 & Alarm 2, Output 1
& Output 2, Analog Out 1 & Alarm 2, Analog Out 1 & Output 2. Analog Out
available only if Analog Output Option board is factory installed.
Alarm must be DISABLED if Ramp is ENABLED.
Figure 3.7 Flow Chart for Alarm 2 Menu
ENTER ALARM 2 MENU:
Press
Press
Press
1) Press , if necessary, until
prompt appears.
a
d
a
a
CNFG
Input Menu.
2) Display advances to
INPT
3) Press , if necessary, until display advances to
Alarm 2
Disable
a
ALR2
Enable or
ENBL DSBL
Menu.
Press
4) Display advances to Alarm 2
d
Submenu.
33
Download from Www.Somanuals.com. All Manuals Search And Download.
ALARM 2 ENABLE/DISABLE SUBMENU:
Press
Press
5) Display flashes previous selection. Press until
d
d
b
ENBL
displays to use Alarm 2.
6) Display shows
stored message momentarily and then
STRD
advances to
only if it was changed, otherwise press to
ABSo
a
advance to
Absolute/Deviation Submenu.
ABSo
If
Alarm 2 Disabled was selected, all submenus of Alarm
DSBL
2 will be skipped and meter advances to
Loop Break Time
LOOP
Alarm 2 Enabled was selected, Output 2 will
Menu. If
ENBL
automatically be Disabled, and reassigned as Alarm 2.
The remaining Alarm 2 menu items are identical to Alarm 1 Menu.
Modifying Alarm Settings will not reset the instrument.
3.2.10 Loop Break Time Menu
It is required that you put the controller in the Standby Mode
for any configuration change other than Set Points & Alarms.
Figure 3.8 Flow Chart for Loop Break Time Menu
ENTER LOOP BREAK TIME MENU:
Press
Press
Press
1) Press , if necessary, until
prompt appears.
a
d
a
a
CNFG
Input Menu.
2) Display advances to
INPT
3) Press , if necessary, until Display advances to
Loop
LOOP
a
Break Time Menu.
34
Download from Www.Somanuals.com. All Manuals Search And Download.
LOOP BREAK ENABLE/DISABLE SUBMENU:
Press 4) Display advances to Loop Break Time
Enable or
DSBL
d
ENBL
Disable Submenu and flashes the previous selection.
5) Scroll through the available selections: or
Press b
Press
.
ENBL DSBL
stored message momentarily and then
6) Display shows
d
STRD
Loop Break Time Value Submenu.
advances to
B.TIM
Loop Break is an additional safety feature intended to monitor the rate of change
of the Process value, while approaching the SP1. It is strictly intended as an
additional warning system, therefore its use is entirely optional. An active Loop
Break will cause the Process Value digits to blink in a rotating pattern. If the
Process value reaches the set point the blinking will stop and
is
B.TIM
Break Alarm warning will flash, and
completed successfully, otherwise
Output 1 will be turned off.
BR.AL
LOOP BREAK TIME VALUE SUBMENU:
st
Press
Press
7) Display flashes 1 digit of previous Loop Value.
d
b
&
8) Press and buttons to enter a new Loop Value
c
b
c
(0 to 99.59).
Press
9) Display shows
stored message momentarily and then
d
STRD
Setpoint Deviation Submenu.
advances to
SP.DV
Loop Break Time Value allows the user to determine the time interval in MM:SS
(from zero to 99 minutes and 59 seconds) that the Process Value changes at
least 10 counts. At the specified time interval, if the process value change is less
than the stated rate, flashing
will be displayed, the output 1 will be de-
B.TIM
energized, and Alarm 1 energized. Loop break time will be disabled when the
Process Value (PV) enters the control band.
SETPOINT DEVIATION ENABLE/DISABLE SUBMENU:
Press
13) Display advances to Setpoint Deviation
DSBL
14) Scroll through the available selections:
Enable or
d
ENBL
Disable Submenu and flashes the previous selection.
Press
Press
or .
ENBL DSBL
b
d
15) Display shows
stored message momentarily and then
STRD
Output 1 Menu.
advances to
OUT1
Set Point Deviation Submenu, if “enabled”, allows changes to Setpoint 1 to be
made automatically to Setpoint 2. This mode is very helpful if the Process Value
changes often. In Set Point Deviation Mode, set SP2 a certain number of counts
away from SP1 - this relation remains fixed when SP1 is changed. For instance:
Setting SP1=200 and SP2=20 and enabling
means that the absolute
SP.DV
value of SP2=220. Moving SP1 to 300, the absolute value of SP2 becomes 320.
35
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.11 Output 1 Menu
Alarm 1 and Output 1 or Analog Output (Retransmission) share the same contacts
on the rear panel connector. If Alarm 1 or Analog Output (Retransmission) is
Enabled, Output 1 is automatically Disabled.
It is required that you put
the controller in the
Standby Mode for any
configuration change other
than Set Points & Alarms.
Figure 3.9 Flow Chart for Output 1 Menu
36
Download from Www.Somanuals.com. All Manuals Search And Download.
ENTER OUTPUT 1 MENU:
Press
Press
Press
1) Press , if necessary, until
prompt appears.
a
d
a
a
CNFG
Input Menu.
2) Display advances to
INPT
3) Press , if necessary, until display advances to
Output
OUT1
a
1 Menu.
4) Display advances to
Press
Self Submenu.
SELF
d
SELF SUBMENU:
The Self Option allows the output of the instrument to be controlled manually
from the front panel.
Press
5) Display flashes the current setting of Self,
Enabled or
ENBL
d
Disabled.
DSBL
6) Press the button to select between Enable and Disable.
Press
Press
b
d
b
ENBL
7) If Self
Enabled was selected, display shows
STRD
stored message momentarily and then advances to the next
menu (Output 1 setting is completed).
On the Run Mode display shows MXX.X The output is now
under the direct control of the operator and can be adjusted in
the Run Mode (M00.0 to M99.9), by pressing the and
b
c
buttons, where M calls for manual (Self) control. For example,
setting of M50.0 of an analog output of 0 to 10 Vdc would
produce roughly 5 Vdc at the output.
8) If Self
Disabled was selected, display shows
STRD
DSBL
o
o LO
stored message momentarily and then advances to
Minimum/Percent Low Submenu of Output 1 Menu.
There is a shorter way to Enable or Disable SELF Mode. From
a Run Mode press and then press . SELF Mode is Enabled
d
a
now. Press or to display MXX.X To Disable SELF press
b
c
a
d
and then press . Display goes to the Run Mode. SELF Mode
is Disabled now.
MINIMUM/PERCENT LOW SUBMENU:
Specify in percent, the minimum value (0000) for control output. If the output is
analog proportional (Current or Voltage), then the minimum voltage or current, in
percent, is specified. If the output is time proportional (Relay, SSR or Pulse),
then the minimum duty-cycle, in percent, is specified.
Press
Press
Press
9) Display flashes 1st digit of previous “Percent Low” setting.
d
b
d
&
10) Use and buttons to enter a new value for “Percent Low”.
c
b
c
11) Display shows
stored message momentarily and then
STRD
o
o HI
advances to
Maximum/Percent High Submenu.
37
Download from Www.Somanuals.com. All Manuals Search And Download.
MAXIMUM/PERCENT HIGH SUBMENU:
Specify in percent, the maximum value (99) for control output. If the output is
analog proportional (Current or Voltage), then the maximum voltage or current, in
percent, is specified. If the output is time proportional (Relay, SSR, or Pulse),
then the maximum duty-cycle, in percent, is specified.
st
Press
Press
Press
12) Display flashes 1 digit of previous “Percent High” setting.
d
b
d
&
13) Use and buttons to enter a new value for “Percent High”.
c
b
c
14) Display shows
stored message momentarily and then
STRD
Control Type Submenu.
advances to
CTRL
Example: On an Analog Output of 0-10 Vdc, a setting of %LO = 10 and %HI = 90,
cause the minimum on the control output to be 1 V and the maximum on the
control output to be 9 V. The same setting on a time proportional output, will cause
10% duty cycle for the minimum control output and 90% duty cycle for maximum
control output. To disable %LO/HI, set LO to 00 and HI to 99. If %LO/HI is at other
values than the default (%LO = 00, %HI =99),
is disabled.
SOAK
*CONTROL TYPE OUTPUT:
(Relay, SSR, Pulse or Analog)
Press
Press
Press
15) Display flashes
On/Off or PID.
PID
d
b
d
ON.OF
16) Scroll through the available selections: “ON.OF” or “PID”.
17) Display flashes stored message momentarily and then
STRD
only, if it was changed, otherwise press a to
advances to
AçTN
Action Type Submenu.
advance to
AçTN
The ON.OF control is a coarse way of controlling the process. The “Dead Band”
improves the cycling associated with the ON.OF control. The PID control is best
for processes where the set point is continuously changing and/or a tight control
of the process variable is required. PID control requires tuning and adjustment of
the “Proportional”, “Integral or Reset” and “Derivative or Rate” terms by a trial-
and-error method. The instrument provides an "Auto Tuning" feature making the
tuning process automatic, possibly optimum.
* If Analog Output (Current/Voltage) is your control Output 1, this menu i.e.
CTRL
for a
type will not appear, instead
Current will be displayed.
4-20
Select
for a 4-20 mA current (2-10 V Voltage) outputs or
DSBL
ENBL
0-20 mA current (0-10 V Voltage) outputs.
If 4-20 mA is enabled, %HI/LO setting will have no effect.
Both Current and Voltage control outputs are active simultaneously.
38
Download from Www.Somanuals.com. All Manuals Search And Download.
ACTION TYPE SUBMENU:
The error that results from the measurement of the Process Variable may be
positive or negative since it may be greater or smaller than the Setpoint. If a
positive error should cause the instrument output to increase, it would be called
Direct Acting. If a negative error should cause the output to decrease, it would be
called Reverse Acting.
Press
Press
Press
18) Display flashes
Direct or Reverse.
RVRS
d
b
d
DRçT
19) Scroll through the available selections: “Direct” or “Reverse”.
20) Display shows
stored message momentarily and then
only, if it was changed, otherwise press to
STRD
advances to
AUTo
a
advance to
selected).
Auto PID Submenu (if PID Control Type was
AUTo
If “ON/OFF” was selected in the Control Type, the display skips
to the Dead Band Submenu.
AUTO PID SUBMENU:
Press
Press
21) Display flashes
or .
ENBL DSBL
d
b
22) Scroll through the available selections: “Enable” or
“Disable”.
Press
23) Display shows
stored message momentarily and then
d
STRD
only, if it was changed, otherwise press to
advances to
ANTL
Anti Integral Submenu.
a
advance to
ANTL
If “Enabled”, the controller can determine, by enabling Start PID, the
optimum values for the three adjustments — Proportional, Reset and
Rate corresponding to P, I, and D. These values may be changed once
the auto tuning is complete.
If “Disabled” is selected, the user will manually enter these three
adjustment values. If you want the instrument to do the auto PID and the
P , PI or PID, first select auto disable and enter 0000 for each unwanted
parameter. e.g. for PI enter 0000 for the rate.
ANTI INTEGRAL SUBMENU:
Press
Press
Press
24) Display flashes
or .
ENBL DSBL
d
b
d
25) Scroll through the available selections: “Enable” or “Disable”.
26) Display shows stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
STRT
was Enabled).
STRT
a
advance to
to Start Auto Tune PID Submenu (If auto PID
If Auto PID was disabled display advances to
Proportional Band Submenu.
PRoP
39
Download from Www.Somanuals.com. All Manuals Search And Download.
If Anti Integral (Anti Windup) Submenu “Enabled”, this feature allows
the error term outside the proportional band to be calculated and
accumulated for integration. This may be an important feature in
applications where fast response time is desirable.
START AUTO TUNE PID:
Press
Press
Press
27) Display flashes
or .
ENBL DSBL
d
b
d
28) Scroll through the available selections: “Enable” or “Disable”.
29) Display shows stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
CYCL
Cycle Time Submenu.
a
advance to
CYCL
If “Enabled”, the controller is ready to calculate P, PI or PID parameters.
The instrument performs this by activating the output and observing the
delay and rate at which the Process Value changes. The set points must
be at least 20 counts above the (PV) Process Value in order to perform
Auto Tune, otherwise an error message will be displayed.
To start Auto Tune PlD select PID, enable Auto PID and enable Start PID.
Sometimes Auto PID parameter needs fine tuning i.e. for each 10 counts
over shoot increase the Proportional Band (PB) by 15% and for each 1
count fluctuation at the Set Point (SP) increase reset by 20%.
Once started, display shows A.TUN with letters blinking in the rotating
pattern. When auto tune stops, display will show process value. Do not
perform any operations or settings before first stopping Auto Tune. Any
alarms or other output is disabled during Auto Tune.
If “AUTO PID” was “DISABLED”, the display will show the following
three submenus. This allows the user to manually enter values for
Proportional, Reset and Rate terms corresponding to P, I, and D. It also
can be used for Auto PID by disabling unwanted parameter e.g. PI enter
0000 for Rate.
PROPORTIONAL BAND SUBMENU:
st
Press
Press
Press
30) Display flashes 1 digit of the previous P
Proportional
PRoP
d
b
d
band value.
&
31) Press and buttons to enter a new “Proportional Band”
c
b
c
value.
32) Display shows
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
advance to
REST
Reset Setup Submenu.
a
REST
Proportional Band is in counts. Proportional Band is defined, as the change in
the instrument input to cause a 100% change in the controller output.
40
Download from Www.Somanuals.com. All Manuals Search And Download.
RESET SETUP SUBMENU:
st
Press
Press
Press
33) Display flashes 1 digit of the previous I
Reset value.
d
b
d
REST
34) Press and buttons to enter a new “Reset” value.
&
c
b
c
35) Display shows
advances to
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
RATE
Rate Setup Submenu.
a
advance to
RATE
Reset unit is in seconds 0-3999.
RATE SETUP SUBMENU:
st
Press
Press
Press
36) Display flashes 1 digit of previous D
Rate value.
RATE
37) Press and buttons to enter a new value.
RATE
d
b
d
&
c
b
c
38) Display shows
advances to the
stored message momentarily and then
STRD
only, if it was changed, otherwise press
CYCL
Cycle Time submenu.
a
to advance to
CYCL
Rate unit is in seconds 000.0-399.9.
If the Output 1 is Analog Option the display skips to Damping
Factor.
CYCLE TIME SUBMENU:
st
Press
Press
Press
39) Display flashes 1 digit of the previous
Cycle Time
CYCL
d
b
d
value.
&
40) Press and buttons to enter a new “Cycle Time” value.
c
b
c
(1 to 199 seconds)
41) Display shows
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
DPNG
Damping Factor Submenu.
a
advance to
DPNG
A Cycle Time selected between 1 and 199 seconds determines the total On/Off
time of each proportional cycle.
For example, a 15 second cycle time means that every 15 seconds the output
will turn on for part or all of the cycle.
For Relay control outputs, do not select a cycle time of less than 7 seconds or
the relays’ lifetime will be shortened. For a cycle time of less than 7 seconds
select SSR or DC pulse.
Use an external SSR with the DC pulse option for higher currents (higher than 1
Amp).
41
Download from Www.Somanuals.com. All Manuals Search And Download.
DAMPING FACTOR SUBMENU:
Press
Press
42) Display flashes the previous “Damping Factor” selection.
d
b
43) Scroll through the available selections:
,
0000 0001
,
,
,
,
,
,
.
0002 0003 0004 0005 0006 0007
Press
44) Display flashes
stored message and then advances
d
STRD
to
to
only, if it was changed, otherwise press to advance
OUT2
OUT2
a
Output 2 Menu.
Damping Factor is a measure of speed, overshoot, and undershoot in which the
process variable responds to the output changes of the instrument, which were
used during the Auto Tune. This value is typically set to the ratio of Rate to
Reset.
This Default value is (0003). For fast response time, this value should be
decreased while for slow response time it should be increased.
The “DEADBAND” Submenu will only appear if “ON.OF” was
selected from the “Control Type” Menu.
DEADBAND SUBMENU:
st
Press
45) Display flashes 1 digit of the previous
Deadband
DEAD
d
value.
Press
Press
&
46) Press and buttons to enter a new “Deadband” value.
b
d
c
b
c
47) Display shows
stored message and then advances to
STRD
only, if it was changed, otherwise press to advance to
Output 2 Menu.
OUT2
OUT2
a
Dead Band units are the same as Proportional Band units.
The Dead Band or neutral zone is the number of counts around the set
point which the Process Variable must pass above or below the set point,
before the output changes state.
42
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.12 Output 2 Menu
Output 2 and Alarm 2 share the same contacts on the rear panel connector. If
Alarm 2 is Enabled, Output 2 is automatically Disabled.
It is required that you put
the controller in the
Standby Mode for any
configuration change other
than Set Points & Alarms.
Figure 3.10 Flow Chart for Output 2 Menu
ENTER OUTPUT 2 MENU:
Press
Press
Press
1) Press , if necessary, until
prompt appears.
a
d
a
a
CNFG
Input Menu.
2) Display advances to
INPT
3) Press , if necessary, until Display advances to
a
OUT2
Output 2 Menu.
4) Display advances to
Press
Control Type Submenu.
CTRL
d
CONTROL TYPE SUBMENU:
Press 3) Display flashes
On/Off, or PID.
PID
d
ON.OF
4) Scroll through the available selections: “ON.OF” or “PID”.
Press b
Press
5) Display shows
stored message momentarily and then
STRD
d
advances to
only, if it was changed, otherwise press to
Action Type Submenu.
AçTN
AçTN
advance to
The ON.OF control is a coarse way of controlling the Process. The “Dead Band”
improves the cycling associated with the ON.OF control. The PID control is best
for processes where the set point is continuously changing and/or tight control of
the Process Variable is required.
43
Download from Www.Somanuals.com. All Manuals Search And Download.
ACTION TYPE SUBMENU:
The error that results from the measurement of the process variable may be
positive or negative since it may be greater or smaller than the set point. If a
positive error should cause the instrument output to increase, it would be called
Direct Acting. If a negative error should cause the output to decrease, it would
be called Reverse Acting.
Press
Press
Press
6) Display flashes
Direct or Reverse.
RVRS
d
b
d
DRçT
7) Scroll through the available selections: “Direct” or “Reverse”.
8) Display shows
stored message momentarily and then
STRD
AUTo
advances to
only, if it was changed, otherwise press to
a
advance to
selected).
Auto PID Submenu (If PID Control type was
AUTo
If “ON.OF” was selected in the Control Type, the display skips
to the Dead Band Submenu.
AUTO PID SUBMENU:
Press
Press
9) Display flashes
Enable or
Disable.
DSBL
d
b
ENBL
10) Scroll through the available selections: “Enable” or “Disable”.
If “Enabled”, the PID parameter of Output 1 will be copied to
Output 2.
Press
11) Display shows
stored message momentarily and then
STRD
d
advances to the next submenu only, if it was changed, otherwise
press to advance to the next submenu.
a
If AUTO PID was “ENABLED”, the display skips to the
CYCL
CYCLE TIME submenu. If “AUTO PID” was “DISABLED”, the
display will show
PROPORTIONAL BAND Submenu
PRoP
allowing the user to manually enter the Proportional Band value.
The Reset and Rate value are the same as Output 1.
PROPORTIONAL BAND SUBMENU:
st
Press
Press
Press
12) Display flashes 1 digit of the previous Proportional Band
d
b
d
value.
&
13) Press and buttons to enter a new Proportional Band
c
b
c
value.
14) Display shows
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
CYCL
advance to the
a
Cycle Time Submenu.
CYCL
Refer to “Proportional Band” Submenu of “Output 1” Menu.
44
Download from Www.Somanuals.com. All Manuals Search And Download.
CYCLE TIME SUBMENU:
st
Press
Press
15) Display flashes 1 digit of the previous “Cycle Time” value.
16) Press and buttons to enter a new “Cycle Time” value
d
b
&
c
b
c
(1 to 199 seconds).
Press
17) Display shows
advances to
stored message momentarily and then
d
STRD
only, if it was changed, otherwise press to
RAMP
Ramp Value Submenu.
a
advance to
RAMP
A cycle time selected between 1 to 199 seconds indicates the total On/Off time
of each proportional cycle.
For example, a 15 second cycle time means that every 15 seconds the output
will turn on for part or all of the cycle.
For Relay Control Outputs, do not select a cycle time of less than 7 seconds or
the relays’ lifetime will be shortened. For a cycle time of less than 7 seconds
select SSR or DC pulse. Use an external SSR with the DC pulse option for
higher current (higher than 1 Amp).
The DEADBAND Submenu will only appear if the ON/OFF was selected
from the "Control Type" Submenu.
DEADBAND SUBMENU:
Press
Press
Press
18) Display flashes 1st digit of the previous “Dead Band” value.
19) Press and buttons to enter a new “Dead Band” value.
d
b
d
&
c
b
c
20) Display shows
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
RAMP
Ramp Value Menu.
a
advance to
RAMP
Dead Band units are the same as Proportional Band units.
The Dead Band or neutral zone is the number of counts around the set
point which the Process Variable must pass above or below the set point,
before the output changes state.
45
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.13 Ramp & Soak Menu
Alarm must be DISABLED if Ramp is ENABLED.
It is required that you put the controller in the Standby Mode for any
configuration change other than Set Points & Alarms.
Figure 3.11 Flow Chart for Ramp and Soak Menu
ENTER RAMP AND SOAK MENU:
Press
Press
Press
1) Press , if necessary, until
prompt appears.
a
d
a
a
CNFG
Input Menu.
2) Display advances to
INPT
3) Press , if necessary, until Display advances to
Ramp
RAMP
a
and
Soak Menu.
SOAK
RAMP ENABLE/DISABLE SUBMENU:
Press
4) Display advances to “Ramp Enable/Disable” Submenu and
flashes or
d
.
ENBL DSBL
5) Scroll through the available selections: “Enable” or “Disable”.
6) Display shows stored message momentarily and then
Press
Press
b
d
STRD
Soak Enable/Disable Menu.
advances to
SOAK
If
Disable was selected, display skips to the next menu
RAMP
item (ID Code).
46
Download from Www.Somanuals.com. All Manuals Search And Download.
SOAK ENABLE/DISABLE SUBMENU:
Press
Press
Press
7) Display flashes
or .
ENBL DSBL
d
b
d
8) Scroll through the available selections: “Enable” or “Disable”.
9) Display shows stored message momentarily and then
STRD
advances to “Ramp Value” Submenu.
Ramp & Soak provides users with the flexibility to slowly bring the Process
Variable (PV) to the desired set point. Ramp & Soak values are specified in
HH.MM format. The Ramp value indicates the time specified to bring the process
variable to Setpoint 1 (SP1). Once set point is reached, the PID takes over and
the Process Variable will be controlled at the desired set point indefinitely. If
Soak is enabled, PID will control the Process Variable at the specified set point
for the duration of Soak time and then will turn off Output 1. To start a new
Ramp/Soak cycle, reset the instrument by pressing and then button.
a
c
An active Ramp/Soak will change SP1 one count above the PV and will cause
the most significant digit to blink. The SP1 will be incremented by one count until
it reaches the original SP1. The minimum Ramp time must be at least twice the
time that it will take the PV to reach the Setpoint Value (SV) with OUT 1 fully ON.
RAMP VALUE SUBMENU:
st
Press
Press
Press
10) Display flashes 1 digit of previous stored “Ramp Value”.
d
b
d
&
11) Press and buttons to enter a new “Ramp Value”.
STRD
advances to “Soak Value” Submenu.
c
b
c
12) Display shows
stored message momentarily and then
SOAK VALUE SUBMENU:
Press
Press
Press
13) Display flashes 1st digit of previous stored “Soak Value”.
14) Press and buttons to enter a new “Soak Value”.
d
b
d
&
c
b
c
15) Display shows
stored message and advances to the
STRD
ID Code Menu.
ID
The Ramp and Soak time is 00:00 to 99:59 i.e. HH.MM. (from zero to 99 hours
and 59 minutes) During Ramp & Soak do not perform any operations or settings
before first stopping it. Any alarms or other output are disabled during this time.
To stop Ramp & Soak first put instrument into Standby Mode, then go to Ramp &
Soak Menu and disable it.
47
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.14 ID Code Menu
Figure 3.12 Flow Chart for ID Code Menu
ENTER ID CODE MENU:
Press 1) Press , if necessary, until
prompt appears.
a
a
CNFG
Input Menu.
Press d
2) Display advances to
INPT
Press
3) Press , if necessary, until display advances to
ID Code
a
a
ID
Menu.
ENTERING OR CHANGING YOUR (NON-DEFAULT) ID CODE:
st
Press d
Press
4) Display advances to
with 1 under score flashing.
____
&
5) Press and to enter your 4-digit “ID Code” number.
b
c
b
c
Press d
6) Display advances to
Change ID Code Submenu.
CH.ID
If entered “ID Code” is incorrect display shows
Error
ERRo
message momentarily and then skips to the Run Mode.
Press
7) Display flashes the first digit of previous entered “ID Code”
d
number.
Press
Press
&
8) Press and buttons to enter your new “ID Code” number.
b
d
c
b
c
9) Display shows
stored message momentarily and then
STRD
Full Security Submenu.
advances to the
FULL
48
Download from Www.Somanuals.com. All Manuals Search And Download.
ENTERING OR CHANGING YOUR (DEFAULT) ID CODE:
Enter menu (Repeat steps from 1 to 3).
ID
Press
Press
10) Display advances to
Change ID Code Submenu.
d
d
CH.ID
message with flashing 1 digit.
st
11) Display shows
0000
If you want to change your default “ID Code” you can do it now,
otherwise press and menu will skip to
Full Security
FULL
a
Submenu.
Press
Press
&
12) Press and buttons to enter your new “ID Code” number.
b
d
c
b
c
13) Display shows
stored message momentarily and then
STRD
Full Security Submenu.
advances to the
FULL
FULL SECURITY LEVEL SUBMENU:
Press
Press
Press
14) Display flashes
Enable or Disable.
DSBL
d
b
d
ENBL
15) Scroll through the available selections: “Enable” or “Disable”.
16) Display shows stored message momentarily and then
STRD
Setpoint/ID Submenu.
advances to
SP.ID
If "Full" Security Level is "Enabled" and the user attempts to
enter the Main Menu, they will be prompted for an ID Code. The
ID Code should be correct to enter the instrument Menu item.
SETPOINT/ID SECURITY LEVEL SUBMENU:
This Security Level can be functional only if
Level is Disabled.
Security
FULL
Press
Press
Press
17) Display flashes
Enable or
Disable.
DSBL
d
b
d
ENBL
18) Scroll through the available selections: “Enable” or “Disable”.
19) Display shows
stored message momentarily and then
STRD
Communication Submenu.
advances to
COMM
If "Setpoint/ID" Security Level is "Enabled" and the user
attempts to advance into the Configuration Menu, he will
CNFG
be prompted for ID Code number. The ID Code should be
correct to proceed into the Configuration Menu, otherwise
display will show an Error and skip to the Run Mode.
If “Full” and “Setpoint/ID” Security Levels are "Disabled", the
ID code will be “Disabled” and user will not be asked for ID
Code to enter the Menu items (“ID” Submenu will not show upin
“ID/Setpoint” Menu).
49
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.15 Communication Option Menu
Purchasing the controller with Serial Communications permits an instrument to
be configured or monitored from an IBM PC compatible computer using software
available from the website listed on the cover page of this manual or on the CD-
ROM enclosed with your shipment. For complete instructions on the use of the
Communications Option, refer to the Serial Communications Reference Manual
.
*
Valid only for -C24
and -EI options.
** Valid only for -C24
and -C4EI options.
External RS-232 connections are not available with -EI or -C4EI options.
Figure 3.13 Flow Chart for Communication Option Menu
50
Download from Www.Somanuals.com. All Manuals Search And Download.
ENTER COMMUNICATION OPTION MENU:
Press
Press
Press
1) Press , if necessary, until
prompt appears.
a
d
a
a
CNFG
Input Menu.
2) Display advances to
INPT
3) Press , if necessary, until display advances to
a
COMM
Communication Options Menu.
Press
4) Display advances to
Submenu.
Communication Parameters
C.PAR
d
If Communication Option is not installed, the display shows
and skips to the Color Display Menu.
NONE
COMMUNICATION PARAMETERS SUBMENU:
Allows the user to adjust Serial Communications Settings of the instrument.
When connecting an instrument to a computer or other device, the
Communications Parameters must match. Generally the default settings
(as shown in Section 5) should be utilized.
Press
5) Display advances to
Baud Submenu.
BAUD
d
BAUD SUBMENU:
Press
Press
6) Display flashes previous selection for
value.
BAUD
d
b
7) Scroll through the available selections:
,
300_ 600_ 1200_
,
,
,
,
,
.
2400_ 4800_ 9600_ 19.2K
8) Display shows
Press
stored message momentarily and then
d
STRD
only, if it was changed, otherwise press to
advances to
PRTY
Parity Submenu.
a
advance to
PRTY
PARITY SUBMENU:
Press
Press
Press
9) Display flashes previous selection for “Parity”.
d
b
d
10) Scroll through the available selections: NO, ODD, EVEN.
11) Display shows
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
DATA
Data Bit Submenu.
a
advance to
DATA
DATA BIT SUBMENU:
Press
Press
Press
12) Display flashes previous selection for “Data Bit”.
d
b
d
13) Scroll through the available selections: 7-BIT, 8-BIT.
14) Display shows
STOP
STOP
stored message and then advances to
STRD
only, if it was changed, otherwise press to advance to
a
Stop Bit Submenu.
51
Download from Www.Somanuals.com. All Manuals Search And Download.
STOP BIT SUBMENU:
Press
Press
Press
15) Display flashes previous selection for “Stop Bit”.
16) Scroll through the available selections:
d
b
d
,
.
1-BIT 2-BIT
17) Display shows
stored message momentarily and then
STRD
only, if it was changed, otherwise press
advances to
BUS.F
to advance to
a
Bus Format Submenu.
BUS.F
BUS FORMAT SUBMENU:
Determines Communications Standards and Command/Data Formats for
transferring information into and out of the controller via the Serial
Communications Bus. Bus Format submenus essentially determine how and
when data can be accessed via the Serial Communications of the device.
Press
18) Display advances to
Modbus Submenu.
M.BUS
d
MODBUS PROTOCOL SUBMENU:
Press
Press
Press
19) Display flashes previous selection for
.
d
b
d
M.BUS
20) Scroll through the available selections: NO, YES.
21) Display shows stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
_LF_
Line Feed submenu.
a
advance to
_LF_
To select iSeries Protocol, set Modbus submenu to “No”.
To select Modbus Protocol, set Modbus submenu to “Yes”.
If Modbus Protocol was selected, the following Communications
Parameters must be set as: No Parity, 8-bit Data Bit, 1-Stop Bit. Do not
attempt to change these parameters.
LINE FEED SUBMENU:
Determines if data sent from the instrument will have a Line Feed appended to
the end - useful for viewing or logging results on separate lines when displayed
on communications software at a computer.
Press
Press
Press
22) Display flashes previous selection for “Line Feed”.
d
b
d
23) Scroll through the available selections: NO, YES.
24) Display shows
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
ECHO
Echo Submenu.
a
advance to
ECHO
ECHO SUBMENU:
When valid commands are sent to the instrument, this determines whether the
command will be echoed to the Serial Bus. Use of echo is recommended in most
situations, especially to help verify that data was received and recognized by the
controller.
52
Download from Www.Somanuals.com. All Manuals Search And Download.
Press
Press
Press
25) Display flashes previous selection for “Echo”.
d
b
d
26) Scroll through the available selections: NO, YES.
27) Display flashes
stored message momentarily and then
STRD
only if it was changed, otherwise press to
advances to
STND
Communication Standard Submenu.
a
advance to
STND
COMMUNICATION INTERFACE STANDARD SUBMENU:
Determines whether device should be connected to an RS-232C serial port
(as is commonly used on IBM PC-compatible computers) or via an RS-485 bus
connected through appropriate RS-232/485 converter. When used in RS-485
Mode, the device must be accessed with an appropriate Address Value as
selected in the Address Submenu described later.
Press
Press
Press
28) Display flashes previous selection for “Standard”.
d
b
d
29) Scroll through the available selections: 232C, 485.
30) Display shows
stored message momentarily and then
STRD
advances to
only, if it was changed, otherwise press to
MoDE
MoDE
a
advance to
Data Flow Mode Submenu.
DATA FLOW MODE SUBMENU:
Determines whether the instrument will wait for commands and data requests
from the Serial Bus or whether the instrument will send data automatically and
continuously to the Serial Bus. Devices configured for the RS-485
Communications Standard operate properly only under Command Mode.
Press
Press
31) Display flashes previous selection for “Mode”.
32) Scroll through the available selections:
d
b
“Command”,
_
CMD
“Continuous”.
CoNT
33) Display shows
Press
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
d
advances to
SEPR
Data Separation Submenu.
a
advance to
SEPR
DATA SEPARATION CHARACTER SUBMENU:
Determines whether data sent from the device in Continuous Data Flow Mode
will be separated by spaces or by Carriage Returns.
Press
Press
34) Display flashes previous selection for “Separation” Submenu.
35) Scroll through the available selections: “Space” or
d
b
SPCE
“Carriage Return”.
_çR_
36) Display shows
Press
stored message momentarily and then
STRD
d
advances to
only, if it was changed, otherwise press
DAT.F
to advance to
a
Data Format Submenu.
DAT.F
53
Download from Www.Somanuals.com. All Manuals Search And Download.
DATA FORMAT SUBMENU:
Preformatted data can be sent automatically or upon request from the controller.
Use the Data Format Submenus to determine what data will be sent in this
preformatted data string. Refer to the iSeries Communications Manual for more
information about the data format. At least one of the following suboptions must
be enabled and hence output data to the Serial Bus.
This menu is applicable for Continuous Mode of RS-232 communication.
Press
37) Display advances to
Alarm Status Submenu.
STAT
d
ALARM STATUS SUBMENU:
Includes Alarm Status bytes in the data string.
Press
Press
Press
38) Display flashes previous selection for “Status” (alarm status).
d
b
d
39) Scroll through the available selections: NO, YES.
40) Display shows
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
advance to
RDNG
Reading Submenu.
a
RDNG
MAIN READING SUBMENU:
Includes Main Reading in the data string.
Press
Press
Press
41) Display flashes previous selection for “Reading”.
d
b
d
42) Scroll through the available selections: NO, YES.
43) Display shows
stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
PEAK
Peak Submenu.
a
advance to
PEAK
PEAK VALUE SUBMENU:
Includes Peak Value in the data string.
Press
Press
Press
44) Display flashes previous selection for
Submenu.
d
b
d
PEAK
45) Scroll through the available selections: NO, YES.
46) Display shows stored message momentarily and then
STRD
only, it was changed, otherwise press to
advances to
advance to
GROS
Gross Submenu.
a
GROS
GROSS VALUE SUBMENU:
Includes Gross Value in the data string.
Press
Press
Press
47) Display flashes previous selection for “Gross”.
d
b
d
48) Scroll through the available selections: NO, YES.
49) Display shows
stored message momentarily and then
STRD
advances to
only, if it was changed, otherwise press to
UNIT
a
advance to
Unit Submenu.
UNIT
54
Download from Www.Somanuals.com. All Manuals Search And Download.
UNIT SUBMENU (not applicable):
Press
Press
Press
50) Display flashes previous selection for
.
d
b
d
UNIT
51) Scroll through the available selections: NO, YES.
52) Display shows stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
ADDR
Address Setup Submenu.
a
advance to
ADDR
ADDRESS SETUP SUBMENU:
This menu is applicable to the RS-485 Option only.
Press
53) Display advances to “Address Value” (0000 to 0199)
d
Submenu.
ADDRESS VALUE SUBMENU:
st
Press
Press
Press
54) Display flashes 1 digit of previously stored Address Value.
55) Press and to enter new “Address Value”.
d
b
d
&
c
b
c
56) Display shows
stored message momentarily and then
STRD
only, if it was changed, otherwise press
advances to
TR.TM
to advance to
a
Transmit Time Interval Submenu.
TR.TM
TRANSMIT TIME INTERVAL SUBMENU:
This menu is applicable if “Continuous” Mode was selected in the “Data
Flow Mode” Submenu and the device is configured as an RS-232C
Standard device. Also, one or more options under the Data Format
Submenu must be enabled.
Press
57) Display advances to “Transmit Time Value” Submenu.
d
TRANSMIT TIME INTERVAL VALUE SUBMENU:
Determines the interval at which data will be emitted to the RS-232 Serial Bus
when the instrument is in Continuous Data Flow Mode.
st
Press
Press
Press
58) Display flashes 1 digit of previous “Transmit Time Value” in
d
b
d
seconds.
&
59) Press and to enter new “Transmit Time Value”, e.g.
c
b
c
0030 will send the data every 30 seconds in Continuous Mode.
60) Display shows stored message momentarily and then
STRD
only, if it was changed, otherwise press to
advances to
COLR
Color Display Selection Menu.
a
advance to
COLR
For more details, refer to the Communication Manual available at
the website listed on the cover page of this manual or on the
CD-ROM enclosed with your shipment.
55
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.16 Display Color Selection Menu
The menu below allows the user to select the color of the display.
Figure 3.14 Flow Chart for Display Color Selection Menu
ENTER DISPLAY COLOR SELECTION MENU:
Press
Press
Press
1) Press , if necessary, until
prompt appears.
a
d
a
a
CNFG
Input Menu.
2) Display advances to
INPT
3) Press , if necessary, until Display advances to
a
COLR
Display Color Selection Menu.
Press
4) Display advances to
Normal Color Submenu.
N.CLR
d
NORMAL COLOR DISPLAY SUBMENU:
Press
Press
Press
5) Display flashes the previous selection for “Normal Color”.
6) Scroll through the available selections: or
d
b
d
,
.
GRN RED AMBR
stored message momentarily and then
7) Display shows
STRD
only, if it was changed, otherwise press
advances to
1.CLR
to advance to
a
Alarm 1 Display Color Submenu.
1.CLR
The menu below allows the user to change the color of display when alarm is
triggered.
ALARM 1 DISPLAY COLOR SUBMENU:
Press
8) Display flashes previous selection for “Alarm 1 Color
d
Display”.
Press
Press
9) Scroll through the available selections:
,
or .
b
d
GRN RED AMBR
stored message momentarily and then
10) Display shows
STRD
advances to
only, if it was changed, otherwise press
2.CLR
to advance to
a
Alarm 2 Display Color Submenu.
2.CLR
56
Download from Www.Somanuals.com. All Manuals Search And Download.
ALARM 2 DISPLAY COLOR SUBMENU:
Press
Press
Press
11) Display flashes previous selection for “Alarm 2 Color Display”.
12) Scroll through the available selections: or
d
b
d
,
.
GRN RED AMBR
stored message momentarily and then
13) Display shows
STRD
momentarily shows the software version number, followed by
Reset, and then proceeds to the Run Mode.
RST
IN ORDER TO DISPLAY ONE COLOR, SET THE SAME DISPLAY
COLOR ON ALL THREE SUBMENUS ABOVE.
If user wants the Display to change color every time that both Alarm 1
and Alarm 2 are triggered, the Alarm values should be set in such a way
that Alarm 1 value is always on the top of Alarm 2 value, otherwise value
of Alarm 1 will overwrite value of Alarm 2 and Display Color would not
change when Alarm 2 is triggered.
Example 1:
Output 1 & Output 2: SSR
Alarm Setup: Absolute, Above, Alarm 2 HI Value “ALR.H” = 200,
Alarm 1 HI Value “ALR.H” = 400
Color Display Setup: Normal Color “N.CLR” = Green, Alarm 1 Color
“1.CLR” = Amber, Alarm 2 Color “2.CLR” = Red
Display Colors change sequences:
GREEN RED
AMBER
-- ------------------------------ ----------------------------- ------------------------------
• ➤
•
•
➤
0
AL2.H = 200
AL1.H = 400
Example 2:
Output 1 & Output 2: Pulse
Alarms Setup: Absolute, Below, Alarm 2 Low Value “ALR.L” = 300,
Alarm 1 Low Value “ALR.L” = 100
Color Display Setup: "N.CLR" = Green, "1.CLR" = Amber, "2.CLR" = Red
Display Colors change sequences:
AMBER RED
GREEN
➤
➤
-------------- ---------------------------------- ------------------------------------------- --
•
0
•
•
•
AL1.L = 100
AL2.L = 300
57
Download from Www.Somanuals.com. All Manuals Search And Download.
Example 3:
Output 1 = Analog Output (Alarm 1 disabled), Setpoint 1 = 300,
Output 2 = Relay, Setpoint 2 = 200
Alarm 1 & 2 Setup: Deviation, Band, “ALR.H” = 10
Color Display Setup: “N.CLR” = Green, “1.CLR” = Amber, “2.CLR” = Red
Display Colors change sequences:
AMBER
--------------- ------ ------ -------------------------------- ------ ------- ----------------
➤
AMBER
AMBER
GREEN
AMBER
•➤
•
•
•
•
•
•
0
190 200 210
290 300 310
Alarm 1 is designed to monitor the Process Value around the Setpoint 1.
Alarm 2 is designed to monitor the Process Value around the Setpoint 2.
If Analog Output Option board is installed (Alarm 1 is disabled), only
Alarm 2 is active and only two colors are available.
Example 4:
Output 1 = Relay, Setpoint 1 = 200
Output 2 = Relay, Setpoint 2 = 200
Alarm 1 Setup: Deviation, Band, “ALR.H” = 20
Alarm 2 Setup: Deviation, Hi/Low, “ALR.H” = 10, “ALR.L” = 5
Color Display Setup: “N.CLR” = Green, “1.CLR” = Amber, “2.CLR” = Red
Display colors change sequences:
AMBER RED GREEN GREEN
RED
AMBER
-- --------------- ---------------- ------------- -------------- ------------- ---------------------
• ➤
•
•
•
•
•
➤
0
180
195
200
210
220
Reset: The instrument automatically resets after the last menu of
the Configuration Mode has been entered. After the instrument
resets, it advances to the Run Mode.
58
Download from Www.Somanuals.com. All Manuals Search And Download.
PART 4
SPECIFICATIONS
Accuracy 0.03% reading
Resolution 10 / 1 µV
Temperature Stability 50 ppm/°C
NMRR 60 dB
Linearization Points
Up to 10 Linearization Points
Configuration
Single-ended
Polarity
Unipolar
CMRR 120 dB
Step Response
0.7 sec for 99.9%
A/D Conversion Dual slope
Reading Rate
3 samples per second
Decimal Selection
None, 0.1, 0.01 or 0.001
Digital Filter
Programmable
Setpoint Adjustment
-1999 to 9999 counts
Display
Span Adjustment
4-digit, 9-segment LED
0.001 to 9999 counts
•
10.2 mm (0.40"): iS32, iS16, iS16D
(DualDisplay), iS8DV (Dual Vertical)
• 21 mm (0.83"): iS8
Offset Adjustment
-1999 to +9999
• 10.2 mm (0.40”) and 21 mm (0.83”):
iS8DH (Dual Horizontal)
CONTROL
Action
Reverse or direct
red, green and amber programmable
colors for process variable, set point
Warm up to Rated Accuracy
30 min.
Modes
Time and Amplitude Proportional
Control Modes; selectable Manual or
Auto PID, Proportional, Proportional
with Integral, Proportional with
Derivative with Anti-reset Windup and
ON/OFF
INPUT
Input Types
Analog Voltage, Analog Current
Voltage Input
0 to 100 mV
0 to 1 V (+100 mV),
0 to 10 Vdc
Rate
0 to 399.9 seconds
Reset
0 to 3999 seconds
Input Impedance:
10 MΩ for 100 mV
1 MΩ for 1 V or 10 Vdc
Current Input
0 to 20 mA (5 ohm load)
59
Download from Www.Somanuals.com. All Manuals Search And Download.
Cycle Time
1 to 199 seconds; set to 0 for on/off
operation
RS-232/RS-422/RS-485/MODBUS:
Selectable from menu; both ASCII and
modbus protocol selectable from
menu. Programmable 300 to 19.2 K
baud; complete programmable setup
capability; program to transmit current
display, alarm status, min/max, actual
measured input value and status.
RS-485
Addressable from 0 to 199
Gain
0.5 to 100% of span; Setpoints 1 or 2
Damping
0000 to 0008
Soak
Connection
Screw terminals
00.00 to 99.59 (HH:MM), or off
Ramp to Setpoint
00.00 to 99.59 (HH:MM), or off
ALARM 1 & 2 (programmable):
Same as Output 1 & 2
Auto Tune
Operator initiated from front panel
Operation
High/low, above/below, band,
latch/unlatch, normally open/normally
closed and process/deviation;
front panel configurations
CONTROL OUTPUT 1 & 2
Relay
250 Vac or 30 Vdc @ 3 A
(Resistive Load); configurable for
on/off, PID and Ramp and Soak
ANALOG OUTPUT (programmable)
Non-Isolated, Retransmission 0 to
10 Vdc or 0 to 20 mA, 500 Ω max
(Output 1 only). Accuracy is +1% of
FS, for Scaling Gain from 0.03 to
100 mV per count
Output 1: SPDT type, can be
configured as Alarm 1 output
Output 2: SPDT type, can be
configured as Alarm 2 output
EXCITATION
(optional in place of Communication)
5 Vdc @ 40 mA
SSR
20-265 Vac @ 0.05-0.5 A
(Resistive Load); continuous
10 Vdc @ 60 mA
Not available for Low Power Option
DC Pulse
INSULATION
Non-Isolated; 10 Vdc @ 20 mA
Power to Input/Output, (Reinforce)
2300 Vac per 1 min. test
Analog Output (Output 1 only)
Non-Isolated, Proportional 0 to 10 Vdc
or 0 to 20 mA; 500 Ω max
1500 Vac per 1 min. test,
(Low Voltage/Power Option)
Power to Relays/SSR Outputs
NETWORK AND COMMUNICATIONS
(Optional -C24, -C4EI, -EI not
available with excitation)
Ethernet: Standards Compliance
IEEE 802.3 10Base-T
Supported Protocols: TCP/IP, ARP,
HTTPGET
2300 Vac per 1 min. test
Relays/SSR to Relay/SSR Outputs
2300 Vac per 1 min. test
RS-232/485 to Inputs/Outputs
500 Vac per 1 min. test
(no isolation is provided for Strain units)
60
Download from Www.Somanuals.com. All Manuals Search And Download.
Approvals
UL, C-UL and see CE Approval Section
Protection
NEMA-4x/Type 4x/IP65 front bezel:
iS32, i1S6D, iS8C
NEMA-1/Type 1 front bezel: iS8, iS8DH,
iS8DV
GENERAL
Line Voltage/Power
90-240 Vac +/-10%, 50-400 Hz*
110-375 Vdc, equivalent voltage
4 W power for iS8, iS8C, iS16, iS32
5 W, power for iS8DV, iS8DH, iS16D
* No CE compliance above 60 Hz
Dimensions
i/8 Series:
48 H x 96 W x 127 mm D
(1.89 x 3.78 x 5")
Low Voltage/Power Option
12-36 Vdc, 3 W**power for iS8, iS8C,
iS16, and iS32
20-36 Vdc, 4 W, power for iS8DV, iS8DH,
and iS16D
i/8 Compact Series:
48 H x 96 W x 74 mm D
(1.89 x 3.78 x 2.91")
External power source must meet
Safety Agency Approvals.
** Units can be powered safely with 24 Vac
power but, no Certification for CE/UL are
claimed.
i/16 Series: 48 H x 48 W x 127 mm D
(1.89 x 1.89 x 5")
i/32 Series:
25.4 H x 48 W x 127 mm D
(1.0 x 1.89 x 5")
External Fuse Required
Time-Delay, UL 248-14 listed:
100 mA/250 V
Panel Cutout
i/8 Series:
45 H x 92 W mm (1.772" x 3.622 "),
1/8 DIN
400 mA/250 V (Low Voltage/Power Option)
Time-Lag, IEC 127-3 recognized:
100 mA/250 V
400 mA/250 V (Low Voltage/Power Option)
i/16 Series: 1/16 DIN
45 mm (1.772") square
Environmental Conditions
•All models: 0 to 55 °C (32 to 131 °F),
90% RH non-condensing
•iS8DV, iS8DH, iS8C, iS16D:
0 to 50 °C (32 to 122 °F) for UL only,
90% RH non-condensing
i/32 Series:
22.5 H x 45 W mm (0.886" x 1.772"),
1/32 DIN
Weight
i/8 Series: 295 g (0.65 lb)
i/16 Series: 159 g (0.35 lb)
i/32 Series: 127 g (0.28 lb)
61
Download from Www.Somanuals.com. All Manuals Search And Download.
PART 5
FACTORY PRESET VALUES
Table 5.1 Factory preset value
MENU ITEMS
FACTORY PRESET VALUES
NOTES
Set Point 1 (SP1)
Set Point 2 (SP2)
000.0
000.0
Input:
Input Type (INPT)
Ratiometric Operation (RTIO)
0 TO 100 MV (0-0.1)
Enable (ENBL)
Input/Reading
Resolution (RESO) Low (LO)
b Button
Peak (PEAK)
Reading Configuration (RDG):
Decimal Point (DEC.P)
Known/Unknown Load (LOAD)
Linearization Points (L.PNt)
Filter Value (FLTR)
FFF.F
Disable (DSBL)
0002 or NONE
0004
Input/Reading (IN.RD)
Scale and Offset
0-100 mV = 0-9999
:
Alarm 1 & 2
Alarm 1 (ALR1), Alarm 2 (ALR2)
Absolute/Deviation (ABSO/DEV)
Latch/Unlatch (LTCH/UNLT)
Contact Closure (CT.CL)
Active (ACTV)
Disable (DSBL)
Absolute (ABSO)
Unlatch (UNLT)
Normally Open (N.O.)
Above (ABOV)
Disable (DSBL)
-100.0
Alarm At Power On (A.P.ON)
Alarm Low (ALR.L)
Alarm 1 only
Alarm High (ALR.H)
400.0
Loop:
Loop Break Time (LOOP)
Loop Value (B.TIM)
Disable (DSBL)
00:59
Setpoint Deviation (SP.dV)
Disable (DSBL)
ANALOG OUTPUT (Retransmission):
Analog Output (ANLG)
Current/Voltage (CURR/VOLT)
Scale and Offset
Enabled (ENBL)
Voltage (VOLT)
Reading: 0 - 999.9 cts, Output: 0 - 10 V
:
Output 1 & 2
Self (SELF)
Disabled (DSBL)
0000
0099
On/Off
Reverse (RVRS)
020.0
Output 1 only
Output 1 only
Output 1 only
% Low Value (%LO)
% High Value (%HI)
Control Type (CTRL)
Action Type (ACTN)
Dead Band (DEAD)
62
Download from Www.Somanuals.com. All Manuals Search And Download.
MENU ITEMS
FACTORY PRESET VALUES
NOTES
PID:
PID Auto (AUTO)
Anti Integral (ANTI)
Proportion Value (PROP)
Reset Value (REST)
Rate Value (RATE)
Cycle Value (CYCL)
Damping Factor (DPNG)
Disable (DSBL)
Disable (DSBL)
020.0
0180
0000
Output 1 only
Output 1 only
Output 1 only
0007
0003
:
Ramp & Soak (RAMP)
Ramp (RAMP)
Disable (DSBL)
Disable (DSBL)
00:00
Soak (SOAK)
Ramp Value (RAMP)
Soak Value (SOAK)
00:00
:
ID
ID Value
0000
Full ID (FULL)
Set Point ID (ID.SP)
Disable (DSBL)
Disable (DSBL)
Communication Parameters:
Baud Rate (BAUD)
Parity (PRTY)
9600
Odd
Data bit (DATA)
7 bit
Stop Bit
1 bit
Modbus Protocol (M.BUS)
Line Feed (LF)
No
No
Echo (ECHO)
Yes
Standard Interface (STND)
Command Mode (MODE)
Separation (SEPR)
Alarm Status (STAT)
Reading (RDNG)
RS-232 (232C)
Command (CMD)
Space (SPCE)
No
Yes
No
Peak
Gross (GROS)
No
Units (UNIT)
No
Multipoint Address (ADDR)
Transmit Time (TR.TM)
Display Color (COLR):
Normal Color (N.CLR)
Alarm 1 Color (1.CLR)
Alarm 2 Color (2.CLR)
0001
0016
Green (GRN)
Red (RED)
Amber (AMBR)
63
Download from Www.Somanuals.com. All Manuals Search And Download.
PART 6
CE APPROVALS INFORMATION
This product conforms to the EMC directive 89/336/EEC amended by
93/68/EEC, and with the European Low Voltage Directive 72/23/EEC.
Electrical Safety EN61010-1:2001
Safety requirements for electrical equipment for measurement, control and laboratory.
Double Insulation
Pollution Degree 2
Dielectric withstand Test per 1 min
• Power to Input/Output:
• Power to Input/Output:
(Low Voltage dc Power Option*)
2300Vac (3250Vdc)
1500Vac (2120Vdc)
• Power to Relays/SSR Output:
• Ethernet to Inputs:
• Isolated RS232 to Inputs:
• Isolated Analog to Inputs:
• Analog/Pulse to Inputs:
Measurement Category I
2300Vac (3250Vdc)
1500Vac (2120Vdc)
500Vac (720Vdc)
500Vac (720Vdc)
No Isolation
Category I are measurements performed on circuits not directly connected to the
Mains Supply (power). Maximum Line-to-Neutral working voltage is 50Vac/dc.
This unit should not be used in Measurement Categories II, III, IV.
Transients Overvoltage Surge (1.2 / 50uS pulse)
• Input Power:
• Input Power:
(Low Voltage dc Power Option*)
2500V
1500V
• Ethernet:
• Input/Output Signals:
1500V
500V
Note: *Units configured for external low power dc voltage, 12-36Vdc
EMC EN61326:1997 + and A1:1998 + A2:2001
Immunity and Emissions requirements for electrical equipment for measurement,
control and laboratory.
• EMC Emissions Table 4, Class B of EN61326
• EMC Immunity** Table 1 of EN61326
Note: **I/O signal and control lines require shielded cables and these cables
must be located on conductive cable trays or in conduits. Furthermore,
the length of these cables should not exceed 30 meters
Refer to the EMC and Safety installation considerations (Guidelines) of this manual
for additional information.
64
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
65
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
66
Download from Www.Somanuals.com. All Manuals Search And Download.
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of one (1) year
from the date of purchase. In addition to OMEGA’s standard warranty period, OMEGA Engineering will extend the warranty
period for four (4) additional years if the warranty card enclosed with each instrument is returned to OMEGA.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an
Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found
to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any
action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits,
improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered
with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration;
improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components which
wear are not warranted, including but not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes
responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its
products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the
parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESS OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL
IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are
exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence,
indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability
is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component”
under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on
humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on
humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/DISCLAIMER
language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage
whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING
ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM
OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR
number should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in
transit.
FOR WARRANTY RETURNS, please have the following
information available BEFORE contacting OMEGA:
FOR NON-WARRANTY REPAIRS, consult OMEGA for current
repair charges. Have the following information available
BEFORE contacting OMEGA:
1. Purchase Order number under which the product was
PURCHASED,
1. Purchase Order number to cover the COST of the repair,
2. Model and serial number of product, and
2. Model and serial number of the product under warranty,
and
3. Repair instructions and/or specific problems relative to the
product.
3. Repair instructions and/or specific problems relative to
the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our
customers the latest in technology and engineering.
© Copyright 2006 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied,
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior
written consent of OMEGA ENGINEERING, INC.
® , and ® are Trademarks of OMEGA ENGINEERING, INC.
®
®
TRADEMARK NOTICE:
, omega.com ,
PATENT NOTICE: This product is covered by one or more of the following patents: U.S. Pat. No. Des. 336,895; 5,274,577;
6,243,021 / CANADA 2052599; 2052600 / ITALY 1249456; 1250938 / FRANCE BREVET No. 91 12756 / SPAIN 2039150;
2048066 / UK PATENT No. GB2 249 837; GB2 248 954 / GERMANY DE 41 34398 C2. The “Meter Bezel Design” is a Trademark
of NEWPORT Electronics, Inc. USED UNDER LICENSE. Other US and International Patents pending or applied for.
Download from Www.Somanuals.com. All Manuals Search And Download.
Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA…Of Course!
Shop on line at omega.com
TEMPERATURE
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies
Wire: Thermocouple, RTD & Thermistor
Calibrators & Ice Point References
Recorders, Controllers & Process Monitors
Infrared Pyrometers
PRESSURE, STRAIN AND FORCE
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Transducers & Strain Gauges
Load Cells & Pressure Gauges
Displacement Transducers
Instrumentation & Accessories
FLOW/LEVEL
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Rotameters, Gas Mass Flowmeters & Flow Computers
Air Velocity Indicators
Turbine/Paddlewheel Systems
Totalizers & Batch Controllers
pH/CONDUCTIVITY
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ pH Electrodes, Testers & Accessories
Benchtop/Laboratory Meters
Controllers, Calibrators, Simulators & Pumps
Industrial pH & Conductivity Equipment
DATA ACQUISITION
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Data Acquisition & Engineering Software
Communications-Based Acquisition Systems
Plug-in Cards for Apple, IBM & Compatibles
Datalogging Systems
Recorders, Printers & Plotters
HEATERS
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Heating Cable
Cartridge & Strip Heaters
Immersion & Band Heaters
Flexible Heaters
Laboratory Heaters
ENVIRONMENTAL
MONITORING AND CONTROL
Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Ⅺ
ߜ Metering & Control Instrumentation
Refractometers
Pumps & Tubing
Air, Soil & Water Monitors
Industrial Water & Wastewater Treatment
pH, Conductivity & Dissolved Oxygen Instruments
M3540/1106
Download from Www.Somanuals.com. All Manuals Search And Download.
|