National Instruments Network Router cFP DO 403 User Manual

FIELDPOINTOPERATING INSTRUCTIONS  
AND SPECIFICATIONS  
FP-DO-403 and cFP-DO-403  
16-Channel, 5 to 30 V Sinking Digital Output Module  
These operating instructions describe how to install and use the  
National Instruments FP-DO-403 and cFP-DO-403 digital output  
modules, referred to inclusively as the [c]FP-DO-403. For  
information about configuring and accessing the [c]FP-DO-403  
over a network, refer to the user manual for the FieldPoint network  
module you are using.  
Features  
The [c]FP-DO-403 is a FieldPoint digital output module with the  
following features:  
16 sinking digital output channels  
Outputs that sink 2 A per channel, 16 A2 per module  
Compatible with voltages from 5 to 30 VDC  
250 Vrms CAT II continuous channel-to-ground isolation,  
verified by 2,300 Vrms, 5 s dielectric withstand test  
–40 to 70 °C operation  
ON/OFF LED indicators  
Hot swappable  
Installing the FP-DO-403  
The FP-DO-403 mounts on a FieldPoint terminal base (FP-TB-x),  
which provides operating power to the module. Installing the  
FP-DO-403 onto a powered terminal base does not disrupt the  
operation of the bank.  
To install the FP-DO-403, refer to Figure 1 and complete the  
following steps:  
1. Slide the terminal base key to either position X, used for any  
module, or position 6, used for the FP-DO-403 module.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4
3
5
2
4
2
1
1
2
3
cFP I/O Module  
Captive Screws  
cFP Controller Module  
4
5
Screw Holes  
cFP Backplane  
Figure 2. Installing the cFP-DO-403  
Wiring the [c]FP-DO-403  
The FP-TB-x terminal base has connections for each FP-DO-403  
output channel and for an external supply to power field devices.  
The cFP-CB-x connector block provides the same connections for  
the cFP-DO-403.  
Each channel has one output terminal, VOUT. The output channels  
share eight VSUP terminals and eight COM terminals. All of the  
channels are referenced to the COM terminals. The V and VSUP  
terminals are all internally connected, as are the C and COM  
terminals.  
Use a 5–30 VDC external power supply for the output channels.  
The power supply must provide enough current to power all of the  
© National Instruments Corp.  
3
[c]FP-DO-403  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
loads on the output channels, up to 2 A per channel.1 Connect  
the external power supply to multiple V and VSUP terminals and  
to multiple C and COM terminals as needed to ensure that the  
maximum current through any terminal is 2 A or less.  
Install a 2 A maximum, fast-acting fuse (F2A 250V) between the  
external power supply and the VSUP terminal on each channel.  
Install a 2 A maximum, fast-acting fuse suitable for the load at the  
VOUT terminal. Figure 3 shows fuses where appropriate.  
Table 1 lists the terminal assignments for the signals associated  
with each channel. Terminal assignments and wiring diagrams are  
also listed on the side panel of the cFP-DO-403 and under the  
slide-in card on the front of the FP-DO-403 module.  
Table 1. Terminal Assignments  
Terminal Numbers  
Terminal Numbers  
V
V
COM  
V
V
COM  
Channel  
Channel  
OUT  
SUP  
17  
17  
19  
19  
21  
21  
23  
23  
OUT  
9
SUP  
25  
25  
27  
27  
29  
29  
31  
0
1
2
3
4
5
6
7
1
2
3
4
5
6
7
8
18  
18  
20  
20  
22  
22  
24  
24  
8
26  
26  
28  
28  
30  
30  
32  
9
10  
11  
12  
13  
14  
15  
16  
10  
11  
12  
13  
14  
15  
National Instruments recommends that you wire the external  
power supply to multiple VSUP and COM terminals. Figure 3  
shows how to connect two output channels to loads.  
Wiring for Low-Current Applications  
If your application requires 2 A or less combined current through  
all channels of the [c]FP-DO-403, you can wire your application  
as shown in Figure 3. Install a 2 A maximum, fast-acting fuse  
(F2A 250V) between the external power supply and the V terminal  
as shown.  
1
Refer to the Digital Output Circuit and Specifications sections for the maximum  
output current level on all channels.  
[c]FP-DO-403  
4
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2 A Max  
User-Supplied  
Fuse  
V
VSUP  
VOUT  
VOUT  
5–30 VDC  
External Power  
Supply  
+
Load  
Load  
COM  
C
[c]FP-DO-403  
Figure 3. Wiring for Low-Current Applications  
Wiring for High-Current Applications  
If your application requires more than 2 A combined current  
through all channels of the [c]FP-DO-403, wire your application  
as shown in Figure 4. Install a 2 A maximum, fast-acting fuse  
(F2A 250V) in series with each load as shown.  
2 A Max  
User-Supplied  
Fuse  
V
2 A Max  
VSUP  
User-Supplied  
Fuse  
VOUT  
Load  
2 A Max  
User-Supplied  
5–30 VDC  
External Power  
Fuse  
VOUT  
Load  
Supply  
+
COM  
C
[c]FP-DO-403  
Figure 4. Wiring for High-Current Applications  
© National Instruments Corp.  
5
[c]FP-DO-403  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Digital Output Circuit  
The [c]FP-DO-403 digital output channels are optically isolated  
from the rest of the FieldPoint bank. In the ON state, a transistor is  
turned on between the VOUT terminal and the external supply (the  
C and COM terminals). In the OFF state, this transistor is turned  
off, allowing only a small leakage current to flow. The VOUT  
terminal sinks current from external devices. Sinking current  
means the VOUT terminal provides a path to the supply common.  
Ensure that no channel sinks more than 2 A, and that the total  
current supplied by all channels at any time is no more than 16 A2.  
To determine whether the total current is within the limit, square  
the current on each channel and add the squares together. If the sum  
of all the squares is less than or equal to 16 A2, the total current is  
within the limit. In the following example, three channels sink 2 A  
and four channels sink 1 A each:  
(2 A)2 + (2 A)2 + (2 A)2 + (1 A)2  
+ (1 A)2 + (1 A)2 + (1 A)2 16 A2  
Caution The outputs must not be short-circuited to the  
potential of the V or VSUP terminals (the positive voltage  
of the external supply). Short circuits damage the  
[c]FP-DO-403 output channels. Check all wiring  
carefully before applying power.  
In the ON state, there is an effective resistance of 0.12 Ω between  
the output (VOUT) and the supply voltage (the C and COM  
terminals). This resistance causes a voltage drop between the  
external supply voltage and the output voltage. For example,  
if the external supply voltage is 5 V and the output current is 1 A,  
the output voltage is 4.88 V:  
5 V – 1 A × 0.12 Ω = 4.88 V  
Protection for Inductive Loads  
When an inductive load, such as a motor or relay, is connected to  
an output, a large counter-electromotive force may occur at  
switching time because of the energy stored in the inductive load.  
This flyback voltage can damage the outputs and the power supply.  
It is best to limit such flyback voltages at the inductive load by  
installing a flyback diode across the load. Typically, you should  
[c]FP-DO-403  
6
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
mount the flyback diode within 18 in. of the load. Figure 5 shows  
a flyback diode connected to an inductive load.  
V or VSUP  
VOUT  
Load  
Flyback Diode  
Figure 5. Connection to Inductive Load with Flyback Diode  
Although the [c]FP-DO-403 contains flyback diodes to prevent  
excessively high voltage from damaging the module, National  
Instruments recommends the use of an external protection circuit  
across any inductive load.  
Status Indicators  
The [c]FP-DO-403 has two green status LEDs, POWER and  
READY. After you insert the FP-DO-403 into a terminal base  
or the cFP-DO-403 into a backplane and apply power to the  
connected network module, the green POWER indicator lights  
and the [c]FP-DO-403 informs the network module of its presence.  
When the network module recognizes the [c]FP-DO-403, it sends  
initial configuration information to the [c]FP-DO-403. After the  
module receives this initial information, the green READY  
indicator lights and the [c]FP-DO-403 is in normal operating  
mode.  
In addition to the green POWER and READY indicators, each  
channel has a numbered, green output state indicator, which lights  
when the channel is in the ON state.  
Isolation and Safety Guidelines  
Caution Read the following information before  
attempting to connect the [c]FP-DO-403 to any circuits  
that may contain hazardous voltages.  
This section describes the isolation of the [c]FP-DO-403 and its  
compliance with international safety standards. The field wiring  
connections are isolated from the backplane and the inter-module  
communication bus. The isolation barriers in the module provide  
© National Instruments Corp.  
7
[c]FP-DO-403  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
250 Vrms Measurement Category II continuous isolation, verified  
by 2,300 Vrms, 5 s dielectric withstand test. The [c]FP-DO-403  
provides double insulation (compliant with IEC 61010-1) for  
working voltages of 250 Vrms1. Safety standards (such as those  
published by UL and IEC) require the use of double insulation  
between hazardous voltages and any human-accessible parts or  
circuits.  
Never try to use any isolation product between human-accessible  
parts (such as DIN rails or monitoring stations) and circuits that  
can be at hazardous potentials under normal conditions, unless the  
product is specifically designed for such an application, as is the  
[c]FP-DO-403.  
Even though the [c]FP-DO-403 is designed to handle applications  
with hazardous potentials, follow these guidelines to ensure a safe  
total system:  
There is no isolation between channels on the [c]FP-DO-403.  
If a hazardous voltage is present on any channel, all channels  
are considered hazardous. Make sure that all other devices and  
circuits connected to the module are properly insulated from  
human contact.  
Do not share the external supply voltages (the V and C  
terminals) with other devices (including other FieldPoint  
devices), unless those devices are isolated from human contact.  
For Compact FieldPoint, you must connect the protective earth  
(PE) ground terminal on the cFP-BP-x backplane to the system  
safety ground. The backplane PE ground terminal has the  
following symbol stamped beside it: . Connect the  
backplane PE ground terminal to the system safety ground  
using 14 AWG (1.6 mm) wire with a ring lug. Use the 5/16 in.  
panhead screw shipped with the backplane to secure the ring  
lug to the backplane PE ground terminal.  
As with any hazardous voltage wiring, make sure that all  
wiring and connections meet applicable electrical codes and  
commonsense practices. Mount terminal bases and backplanes  
in an area, position, or cabinet that prevents accidental or  
unauthorized access to wiring that carries hazardous voltages.  
1
Working voltage is defined as the signal voltage plus the common-mode voltage.  
Common-mode voltage is the voltage of the module with respect to ground.  
[c]FP-DO-403  
8
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Do not use the [c]FP-DO-403 as the only isolating barrier  
between human contact and working voltages higher than  
250 Vrms  
.
Operate the [c]FP-DO-403 only at or below Pollution  
Degree 2. Pollution Degree 2 means that only nonconductive  
pollution occurs in most cases. Occasionally, however, a  
temporary conductivity caused by condensation must be  
expected.  
Operate the [c]FP-DO-403 at or below Measurement  
Category II. Measurement Category II is for measurements  
performed on circuits directly connected to the low-voltage  
installation. This category refers to local-level distribution,  
such as that provided by a standard wall outlet.  
Safety Guidelines for Hazardous Locations  
The [c]FP-DO-403 is suitable for use in Class I, Division 2, Groups  
A, B, C, D, T4 hazardous locations; Class I, Zone 2, AEx nA IIC  
T4 and Ex nA IIC T4 hazardous locations; and nonhazardous  
locations only. Follow these guidelines if you are installing the  
[c]FP-DO-403 in a potentially explosive environment. Failing to  
follow these guidelines may result in serious injury or death.  
Caution Make sure that all products you use in hazardous  
locations are certified for such use. Refer to the product  
label or visit ni.com/certification, search by model  
number or product line, and click the appropriate link in  
the Certification column.  
Caution Do not disconnect I/O-side wires or connectors  
unless power has been switched off or the area is known  
to be nonhazardous.  
Caution Do not remove modules unless power has been  
switched off or the area is known to be nonhazardous.  
Caution Substitution of components may impair  
suitability for Class I, Division 2.  
Caution For Zone 2 applications, install the FieldPoint  
system in an enclosure rated to at least IP 54 as defined  
by IEC 60529 and EN 60529.  
© National Instruments Corp.  
9
[c]FP-DO-403  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Caution For Zone 2 applications, install a protection  
device across the external power supply and the COM  
terminal. The device must prevent the external power  
supply voltage from exceeding 42 V if there is a transient  
overvoltage condition.  
Special Conditions for Hazardous Locations Use in Europe  
The [c]FP-DO-403 has been evaluated as EEx nC IIC T4  
equipment under DEMKO Certificate No. 03 ATEX 0251502X.  
Each module is marked  
hazardous locations.  
II 3G and is suitable for use in Zone 2  
Specifications  
These specifications are typical for –40 to 70 °C unless otherwise  
noted. Specifications are subject to change without notice.  
Output Characteristics  
Number of channels..........................16  
Output type .......................................Sinking  
Voltage range ....................................5 to 30 VDC  
Output impedance.............................0.12 Ω  
(0.12 V drop at 1 A)  
Maximum current  
Per channel .................................2 A  
All channels  
FP-DO-403...........................16 A2  
cFP-DO-403.........................16 A2 at –40 to 60 °C  
12 A2 at 60 to 70 °C  
Maximum OFF state leakage............50 μA  
Output delay time .............................50 μs  
Physical Characteristics  
Indicators ..........................................Green POWER and  
READY indicators, 16 green  
output state indicators  
Weight  
FP-DO-403.................................140 g (4.8 oz)  
cFP-DO-403 ...............................110 g (3.7 oz)  
[c]FP-DO-403  
10  
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Power Requirements  
Power from network module ............600 mW  
Safety Isolation Voltage  
Isolation voltage is verified by a dielectric withstand test.  
Channel to ground  
Continuous .................................250 Vrms, Measurement  
Category II  
Dielectric withstand....................2,300 Vrms, 5 s  
Channel to channel ...........................None  
Environmental  
FieldPoint modules are intended for indoor use only. For outdoor  
use, they must be mounted inside a sealed enclosure.  
Operating temperature  
Input voltage 25 V....................40 to 70 °C  
Input voltage 30 V....................40 to 50 °C  
Storage temperature..........................45 to 85 °C  
Humidity...........................................10 to 90% RH,  
noncondensing  
Maximum altitude.............................2,000 m; at higher altitudes,  
the isolation voltage ratings  
must be lowered  
Pollution Degree ...............................2  
Shock and Vibration  
These specifications apply only to the cFP-DO-403. NI  
recommends Compact FieldPoint if your application is  
subject to shock and vibration.  
Operating vibration, random  
(IEC 60068-2-64)..............................10–500 Hz, 5 grms  
Operating vibration, sinusoidal  
(IEC 60068-2-6)................................10–500 Hz, 5 g  
Operating shock  
(IEC 60068-2-27)..............................50 g, 3 ms half sine,  
18 shocks at 6 orientations;  
30 g, 11 ms half sine,  
18 shocks at 6 orientations  
© National Instruments Corp.  
11  
[c]FP-DO-403  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety  
This product is designed to meet the requirements of the following  
standards of safety for electrical equipment for measurement,  
control, and laboratory use:  
IEC 61010-1, EN-61010-1  
UL 61010-1, CSA 61010-1  
Note For UL and other safety certifications, refer to the  
product label or visit ni.com/certification, search  
by model number or product line, and click the  
appropriate link in the Certification column.  
Electromagnetic Compatibility  
This product is designed to meet the requirements of the following  
standards of EMC for electrical equipment for measurement,  
control, and laboratory use:  
EN 61326 EMC requirements; Industrial Immunity  
EN 55011 Emissions; Group 1, Class A  
CE, C-Tick, ICES, and FCC Part 15 Emissions; Class A  
CE Compliance  
This product meets the essential requirements of applicable  
European Directives, as amended for CE marking, as follows:  
2006/95/EC; Low-Voltage Directive (safety)  
2004/108/EC; Electromagnetic Compatibility Directive (EMC)  
Note Refer to the Declaration of Conformity (DoC) for  
this product for any additional regulatory compliance  
information. To obtain the DoC for this product, visit  
ni.com/certification, search by model number or  
product line, and click the appropriate link in the  
Certification column.  
Environmental Management  
National Instruments is committed to designing and manufacturing  
products in an environmentally responsible manner. NI recognizes  
that eliminating certain hazardous substances from our products is  
beneficial not only to the environment but also to NI customers.  
For additional environmental information, refer to the NI and the  
Environment Web page at ni.com/environment. This page  
[c]FP-DO-403  
12  
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
contains the environmental regulations and directives with which  
NI complies, as well as other environmental information not  
included in this document.  
Waste Electrical and Electronic Equipment (WEEE)  
EU Customers At the end of their life cycle, all products  
must be sent to a WEEE recycling center. For more  
information about WEEE recycling centers and  
National Instruments WEEE initiatives, visit ni.com/  
environment/weee.htm.  
⬉ᄤֵᙃѻક∵ᶧ᥻
ㅵ⧚
⊩ ˄Ё೑  
˅
RoHS  
ヺড়Ё೑⬉ᄤֵᙃ  
Ё೑ᅶ᠋  
National Instruments  
ѻકЁ䰤
Փ⫼ᶤѯ᳝ᆇ⠽䋼ᣛҸ  
DŽ݇Ѣ  
(RoHS)  
Ё೑  
ড়㾘ᗻֵᙃˈ䇋ⱏᔩ  
RoHS  
National Instruments  
ni.com/environment/rohs_chinaDŽ  
about China RoHS compliance, go to  
environment/rohs_china  
(For information  
ni.com/  
.)  
Mechanical Dimensions  
Figure 6 shows the mechanical dimensions of the FP-DO-403  
installed on a terminal base. Dimensions are given in millimeters  
[inches]. If you are using the cFP-DO-403, refer to the Compact  
FieldPoint controller user manual for the dimensions and cabling  
clearance requirements of the Compact FieldPoint system.  
107.19  
[4.22]  
109.5  
[4.31]  
91.44  
[3.60]  
Figure 6. FP-DO-403 Mechanical Dimensions  
© National Instruments Corp.  
13  
[c]FP-DO-403  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Where to Go for Support  
For more information about setting up the FieldPoint system, refer  
to these National Instruments documents:  
FieldPoint network module user manual  
Other FieldPoint I/O module operating instructions  
FieldPoint terminal base and connector block operating  
instructions  
Go to ni.com/support for the most current manuals, examples,  
and troubleshooting information.  
National Instruments corporate headquarters is located at 11500  
North Mopac Expressway, Austin, Texas, 78759-3504. National  
Instruments also has offices located around the world to help  
address your support needs. For telephone support in the United  
States, create your service request at ni.com/support and follow  
the calling instructions or dial 512 795 8248. For telephone support  
outside the United States, contact your local branch office:  
Australia 1800 300 800, Austria 43 662 457990-0,  
Belgium 32 (0) 2 757 0020, Brazil 55 11 3262 3599,  
Canada 800 433 3488, China 86 21 5050 9800,  
Czech Republic 420 224 235 774, Denmark 45 45 76 26 00,  
Finland 358 (0) 9 725 72511, France 01 57 66 24 24,  
Germany 49 89 7413130, India 91 80 41190000,  
Israel 972 3 6393737, Italy 39 02 413091, Japan 81 3 5472 2970,  
Korea 82 02 3451 3400, Lebanon 961 (0) 1 33 28 28,  
Malaysia 1800 887710, Mexico 01 800 010 0793,  
Netherlands 31 (0) 348 433 466, New Zealand 0800 553 322,  
Norway 47 (0) 66 90 76 60, Poland 48 22 3390150,  
Portugal 351 210 311 210, Russia 7 495 783 6851,  
Singapore 1800 226 5886, Slovenia 386 3 425 42 00,  
South Africa 27 0 11 805 8197, Spain 34 91 640 0085,  
Sweden 46 (0) 8 587 895 00, Switzerland 41 56 2005151,  
Taiwan 886 02 2377 2222, Thailand 662 278 6777,  
Turkey 90 212 279 3031, United Kingdom 44 (0) 1635 523545  
[c]FP-DO-403  
14  
ni.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  
National Instruments, NI, ni.com, and LabVIEW are trademarks of National Instruments Corporation. Refer to the  
Terms of Use section on ni.com/legal for more information about National Instruments trademarks. Other  
product and company names mentioned herein are trademarks or trade names of their respective companies.  
For patents covering National Instruments products, refer to the appropriate location: Help»Patents in your software,  
the patents.txt file on your CD, or ni.com/patents.  
© 2002–2007 National Instruments Corp. All rights reserved.  
373354C-01  
Aug07  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Miele Dishwasher G 5810 User Manual
Minolta Film Camera XG A User Manual
National Instruments Automobile 372139B 01 User Manual
National Instruments Computer Accessories 3x User Manual
NEC Cell Phone NDA 24300 User Manual
NEC Computer Monitor EA191M BK User Manual
Northern Industrial Tools Washer M1578112A User Manual
OEM Systems Switch VX 100 User Manual
Omron Blood Pressure Monitor R53 User Manual
Outback Power Systems Power Supply FX2012MT User Manual