M010601
R
Issue 8, revised 06/99
The Generator Controls Division of
Catalogue section 75
(MS5259)
AUTOSTART 710 (AS710S) series
PROGRAMMABLE GENERATOR CONTROLLER
The Autostart 710 provides the control features needed for
the automatic start, load transfer and shutdown of a
standby generator or pump. Microprocessor technology
allows the Autostart 710 to be programmed for use in a
wide range of engine and generator control applications.
Key features
·
Automatic or manual operation, selected by key-switch
or optional rotary switch.
·
32 character, back-lit liquid crystal display (LCD), showing
operating mode, system status, timer information,
generator RPM/Hz., oil pressure and engine temperature
·
·
Full programmability of engine control options, timers,
trip levels, fault options and input/output configurations
Comprehensive fault protection and alarm system:-
low oil pressure and high engine temperature alarms
(using analogue or switch sensors), engine overspeed
and underspeed, emergency stop, start fail, charge fail,
high and low battery voltage, 3 programmable fault inputs.
Product Specification
·
·
6 programmable outputs, each configurable to one
of over 30 function types.
Power supply:
Pin compatibility with Keystart 9700 range, allowing
standardisation of panel wiring
Operating voltage: steady state range
crank brown-out
5 – 40 V DC continuous,
to 0 V for <= 100 mSec
typically 150 mA
Current consumption
Operation
Inputs:
The AS710’s operating mode is selected by use of a 3
position switch:–
DC inputs (inputs 1 - 5, mains fail):
positive input voltage range
negative input voltage range
Generator AC input:
operating voltage range
frequency measurement range
Magnetic pickup:
operating voltage range
frequency measurement range
Outputs:
80% to 100% of battery +ve
–1V to +2V w.r.t. battery –ve
Off/reset. Removes power from the unit, disabling
the engine and resetting a latched fault condition.
Automatic start-up, load transfer and return to
standby in response to a mains fail or remote
start condition, with full fault protection.
90 – 300 V AC rms
0 – 99 Hz.
Manual start and stop of the generator, either
immediately on selecting manual mode or by
use of remote push button switches.
7 – 80 V AC rms
0 – 10 kHz
(all ratings for resistive load)
Green and amber LEDs around the switch indicate the
selection of Auto or Manual modes. On keyswitch versions,
the key is common to all units and is removable in the Off
and Auto positions only.
Start and fuel relays
+ ve DC (switched SPNO contact)
16A max. @ 24 V DC
– ve DC (open collector transistor)
250mA max. @ 33 V DC
– ve DC (switched SPNO contact)
5A max. @ 24 V DC
Programmable outputs 1 – 3
Programmable output 4
Control Outputs
The following outputs are provided:-
· Single pole, switched +ve relay outputs for the control
Programmable output 5
(default setting: common alarm)
Programmable output 6
(default setting: gen. contactor)
Auto & Manual outputs
Off/reset output
+ ve DC (switched SPNO contact)
5A max. @ 24 V DC
volt free SPNO relay contacts
5A max. @ 240 V AC
+ ve DC (switched), 250 mA max.
– ve DC (switched), 250 mA max.
of engine fuel and starter motor circuits.
· Switched +ve outputs for signalling auto and manual
modes, plus a –ve DC output for Off/reset.
· 6 function programmable outputs (see overleaf).
Fault Protection and Alarm System
General:
In Auto or Manual modes, Autostart shuts down and latches
out the generator on detection of low oil pressure, high engine
temperature, overspeed, start fail or emergency stop faults.
The Autostart may also be set up to shut down the generator
on a low generator frequency or speed condition.
Overall dimensions (W x H x D)
Panel cut-out size
Weight
Operating ambient temperature
Case sealing
96 x 96 x 162 mm
DIN standard 92 x 92 mm
approx. 650 g
–10 to +55 oC
IP22
3 additional inputs may be used with remote fault switches
(giving a ‘shutdown’ or ‘warning’ response), or as control
inputs with remote contacts or panel switches (see overleaf).
In order to consistently bring you the highest quality, full
featured products, we reserve the right to change our
specifications and designs at any time.
Non-latching, 'warning only' alarms are provided for high and
low battery volts, charge fail and mag. pickup fail conditions.