TM
CENTURION
Configurable Controller
Installation and
Operations Manual
TM
CE-05171N
Effective 05-13-05
Section 50
(00-02-0590)
CE-05171N page 1 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
1.0 WARNING AND LIMITED WARRANTY..................................................................................2
2.0 OVERVIEW.........................................................................................................................................5
Basic Components and Key Features of the C3 Series.....................................................................................5
Optional Components....................................................................................................................................5
3.0 INPUT/OUTPUT TYPES................................................................................................................6
3.1 Input/Output Types and Specifications for the Centurion C3-1...................................................................6
3.1.1 Digital Inputs (DI)..........................................................................................................................6
3.1.2 Analog Inputs (AI) ........................................................................................................................7
3.1.3 Thermocouple Inputs (TC)...........................................................................................................7
3.1.4 Magnetic Pickup (MPU)...............................................................................................................8
3.1.5 Digital Outputs (DO).....................................................................................................................8
3.1.6 Types and Specifications for the Optional Analog Output on the Centurion C3-1 -A....................9
Analog Outputs (AO).............................................................................................................................9
3.2 Input/Output Types and Specifications for the Optional C3-2 Expansion Module to the Centurion C3-1.........9
3.2.1 Analog Inputs (AI)........................................................................................................................ 9
3.2.2 Thermocouple Inputs (TC)......................................................................................................... 10
3.2.3 Analog Outputs (AO)..................................................................................................................10
4.0 HAZARDOUS AREA OPERATION......................................................................................... 10
5.0 HARDWARE INSTALLATION AND WIRING..................................................................... 11
5.1 Mounting the Centurion Controller.........................................................................................................11
5.2 Mounting the Centurion C3-3 Display.....................................................................................................11
5.3 Power Supply Wiring.............................................................................................................................11
Power........................................................................................................................................................11
Centurion C3-1 I/O Module................................................................................................................... 11
Centurion C3-2 Optional Expansion Module...........................................................................................11
5.4 Wiring the Centurion C3-3 Display.........................................................................................................12
5.5 Wiring the Centurion C3-1/C3-2.........................................................................................................13/14
6.0 USING C3-3 DISPLAY TO VIEW AND CONFIGURE
THE CENTURION CONTROLLER SETTINGS.............................................................................15
6.1 Features.............................................................................................................................................. 15
6.1.1 Keypad Description and Navigation..........................................................................15/16/17/18
6.1.2 Display Context........................................................................................................................19
6.1.3 Numeric Entry..........................................................................................................................19
6.2 Operational Screens............................................................................................................................. 20
6.2.1 Default Operating Screen......................................................................................................... 20
6.2.2 F W Murphy Logo Screen........................................................................................................ 20
6.2.3 Corporate and Version Information Screen.............................................................................. 20
6.2.4 Shutdown History Screen........................................................................................................ 21
6.2.5 Event History Screen................................................................................................................21
6.2.4 Active Alarms Screen............................................................................................................... 21
6.2.5 Gage Display........................................................................................................................... 22
6.2.6 Line By Line............................................................................................................................ 22
6.2.7 Custom PID Screen............................................................................................................22/23
6.3 Setup Screens and Menus.....................................................................................................................23
6.3.1 Password Screen.....................................................................................................................23
6.3.2 Digital Input..............................................................................................................................24
6.3.3 Digital Output...........................................................................................................................24
6.3.4 Analog Input........................................................................................................................24/25
6.3.5 Analog Output.....................................................................................................................25/26
TTD-98055N page 3 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
6.3.6 Thermocouple Input................................................................................................................26
6.3.7 General Timer Setup...............................................................................................................27
6.3.8 Maintenance Timer Setup.......................................................................................................28
6.3.9 Set points Setup.....................................................................................................................29
6.3.10 Control Output Setup.......................................................................................................29/30
6.3.11 PID Setup.............................................................................................................................30
6.3.12 Initial RPM Setup.................................................................................................................. 31
6.3.13 Miscellaneous Setup.............................................................................................................31
6.3.14 Lube No Flow Set Up........................................................................................................... 32
6.3.15 Lube No Flow Status............................................................................................................ 32
6.3.16 Super User Menu............................................................................................................ 32/33
6.3.17 Configuration Download (Download Only Screen)................................................................. 33
6.3.18 Display Board Status.............................................................................................................33
6.3.19 Digital Input Status................................................................................................................ 34
6.3.20 Digital Output Status............................................................................................................. 34
6.3.21 Analog Input Status...............................................................................................................34
6.3.22 Analog Output Status.......................................................................................................34/35
6.3.23 Thermocouple Status............................................................................................................ 35
6.3.24 Communication Status.....................................................................................................35/36
6.3.25 PID Diagnostics.....................................................................................................................36
6.4 Additional Navigational Aids................................................................................................................ 37
6.4.1 Function Key........................................................................................................................... 37
6.4.2 Help Key................................................................................................................................. 37
7.0 COMMUNICATIONS...................................................................................................................37
7.1 Communication Ports.......................................................................................................................... 37
Port 1 (SERIAL)................................................................................................................................37
Port 2 (SERIAL)................................................................................................................................37
Port 2 (USB).....................................................................................................................................38
Port 3 (CAN).....................................................................................................................................38
7.2 Downloading Configurations and Firmware Updates............................................................................. 38
7.2.1 Boot Loader...........................................................................................................................38
7.2.2 Downloading Configurations Via C3-3 Display........................................................................ 38
Special 35 Jump Code................................................................................................................... 38
7.2.3 Downloading Configurations Via MConfigPro Software...........................................................39
7.2.4 Pass Through.........................................................................................................................39
7.2.5 Downloading Firmware Updates to the C3-3 Display..............................................................39
Special 35 Jump Code....................................................................................................................39
Super User Menu............................................................................................................................39
7.2.6 Error Messages...................................................................................................................... 40
7.3 Modbus Protocol.................................................................................................................................41
7.4 Features of Transferring Data in Modbus.............................................................................................. 41
7.5 Modbus Register Address Listings........................................................................................................ 41
8.0 GLOSSARY.....................................................................................................................................42
9.0 APPENDICES.................................................................................................................................43
9.1 Back Panel LED Description................................................................................................................. 43
9.2 Controller Accuracies, and Tolerances ............................................................................................... 43
9.3 Restrictions on Numeric Values in Gage and PID Monitor Screens.......................................................... 43
9.4 Set Up Sheet....................................................................................................................................... 43
9.0 How to Order................................................................................................................................ 44
TTD-98055N page 4 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
2.0 Overview
The Centurion configurable controller is a control and monitoring system expressly designed to meet the requirements of
three specific kinds of applications: Screw and Reciprocating Compressors, and Pumps. To that end, it is able to satisfy
the particular needs and inevitable variations that exist in real world applications because the Centurion controller is enor-
mously flexible and configurable within fixed parameters. The Centurion controller is a system designed to monitor, con-
trol, protect, and optimize small to medium sized gas operated compressors and pumps in the field by monitoring set
points and digital, analog, and thermocouple input points and providing the logic to take corrective and/or proactive
steps to maintain proper operation. The Centurion controller also allows for controlled shut down and no-flow monitoring
as well as expanded and auto start up, and engine control capabilities, which are so critical to the systems the Centurion
controller is designed to protect.
The Centurion controller provides real-time data via communications ports to a connected display and/or supervisory
system. This advanced system offers multiple options for remote communications and operation including HMI's, PLC's,
PC’s, and SCADA systems. The industry standard Modbus protocol means greater support for a wide variety of commu-
nication equipment including radio and satellite communications systems.
The heart of the Centurion system is the Main Input/Output (I/O) Module, known as C3-1, which can be mounted on a
standard DIN rail. While it is designed to work with any Modbus (Master) compliant HMI (Human Machine Interface) or
with no operator interface at all, it is optimally configured and field-configurable through MConfigPro, powerful software
developed to configure the controller. Parameters can be modified through C3-3 Display, F W Murphy’s specially pro-
grammed controller display, in the field without special need for laptop or software.
TM
Basic Components and Key Features of the C3 Series
The C3 Series consists of a Display Module, a Main I/O Module, and optional Expansion I/O Module. No special cables
are required. The Centurion system is designed for use within a weatherproof enclosure only.
■ Display Module (C3-3 Head): 128 x 64 LCD graphic display; (-40 to 85) °C
■ Main I/O Module (C3-1):
• 32 Digital Inputs (DI)
• 10 Digital Outputs (DO)
• Separate direct input for Analog and Thermocouple inputs:
– 12 AI on the Centurion C3-1
– 8 TC on the Centurion C3-1
• 1 Magnetic Pickup (MPU).
• C3-1-A: Same as C3-1, plus two (2) Analog Output (AO).
■ Expansion I/O Module (C3-2) as required: 8 AI, 8 TC, and 4 AO
Optional Components:
The C3-1 hardware may be configured with 2 analog outputs and it may be augmented through an Expansion Module
(C3-2) which provides analog outputs and additional analog and thermocouple inputs.
C3-1-A with Analog Outputs:
■ 2 Analog Outputs
C3-2 Expansion:
■ 8 Analog Inputs
■ 8 Thermocouple Inputs
■ 4 Analog Outputs
CE-05171N page 5 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
3.0 Input/Output Types
3.1 Input/Output Types and Specifications for the Centurion C3-1
Optional
Analog Outputs
(AO) See 3.1.6
Digital Outputs
(DO) See 3.1.5
CAN
J1939
Communications
(RS4232, 485, USB)
Magnetic Pickup
(MPU) See 3.1.4
C3-1
Thermocouple Inputs
(TC) See 3.1.3
Analog Inputs
(AI) See 3.1.2
Digital Inputs
(DI) See 3.1.1
3.1.1 Digital Inputs (DI)
Number of Devices: 32
Device Types: Discrete Input, Normally Open (N/O) or Normally Closed (N/C),
active high/active low, non-incendive.
There is one screw terminal connector for each digital input.
Terminals 30 to 61 are DI terminals.
Green LEDs give visual indication of active input signal.
C3-1
Digital Inputs
CE-05171N page 6 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
3.1.2 Analog Inputs (AI)
Number of Devices: 12
Device Types: Analog Input, (4 to 20) mA or (0 to 5) V, 10 bit hardware.
There is one screw terminal connector for each analog input.
Terminals 18 to 29 are AI terminals.
C3-1
Analog Inputs
3.1.3 Thermocouple Inputs (TC)
Number of Devices: 8
Device Types: Thermocouple Input, Type J or K, 12 bit hardware.
Open Thermocouple Detection: Drives terminal reading high (max of scale).
Automatic Cold Junction Compensation is built-in.
There are two screw terminal connectors for each thermocouple.
Terminals 1 to 16 are TC terminals where White or Yellow indicate positive inputs and Red indicates negative inputs.
An additional terminal connector is provided, identified as SHD, which isolates thermocouple shields. This con-
nection, at terminal 17, is intended to be wired to an isolated bus bar for thermocouple shield wires. If ground-
ed thermocouples are used, the shied terminal should not be connected.
C3-1
Thermocouple Inputs
CE-05171N page 7 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
3.1.4 Magnetic Pickup (MPU)
Number of Devices: 1
Device Types: Magnetic Pickup or MPU, (5 to 120) Vrms, (30 to 10k) Hz.
There are two screw terminal connectors for the Magnetic Pickup .
Terminals 64 and 65 are MPU terminals.
Magnetic Pickup
C3-1
3.1.5 Digital Outputs (DO)
Number of Devices: 10
Device Types: Discrete Output, Normally Open (N/O) or Normally Closed (N/C)
● Four (4) relay outputs, form C, dry contacts
● Four (4) FETs (high speed)
● Two (2) IGBTs (high power)
There are three screw terminal connectors for each relay output and two screw terminal connectors for each
FET and IGBT output.
Terminals 70 to 81 are for the four relay terminals.
Terminals 82 to 89 are for the four FET terminals.
Terminals 90 to 93 are for the two IGBT terminals.
Green LEDs give a visual indication of active output signal.
Warning: A heat sink is attached to the cover using acorn style nuts. The surface area around these fasteners can
become very hot. Avoid contact.
Digital Outputs
C3-1
CE-05171N page 8 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
3.1.6 Types and Specifications for the Optional Analog Output on the Centurion C3-1 -A
Analog Outputs (AO)
Number of Devices: 2
Device Types: Analog Output, (4 to 20) mA or (0-5)V, 16 bit hardware
There are two screw terminal connectors for each analog output.
The AO optional module is added to the C3-1 at the factory inside the DIN enclosure. While these terminals are
present on all models the feature may not be installed.
Optional Analog Outputs
C3-1-A
3.2 Input/Output Types and Specifications for the Optional C3-2 Expansion Module to the Centurion C3-1
3.2.1 Analog Inputs (AI)
Number of Devices: 8
Device Types: Analog Input, (4 to 20) mA or (0 to 5) V, 12 bit hardware.
There is one screw terminal connector for each analog input.
Terminals 126 to 133 are AI terminals.
C3-2
Analog Inputs
TTD-98055N page 9 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
3.2.2 Thermocouple Inputs (TC)
Number of Devices: 8
Device Types: Thermocouple Input, Type J or K, 12 bit hardware
Open Thermocouple Detection: Drives channel reading high (max of scale).
There are two screw terminal connectors for each thermocouple input.
Terminals 109 to 124 are TC channels where White or Yellow indicate positive inputs and Red indicates negative inputs.
An additional terminal connector is provided, identified as SHD, which isolates thermocouple shields. This con-
nection, at terminal 125, is intended to be wired to an isolated bus bar for thermocouple shield wires. If ground-
ed thermocouples are used, the shied terminal should not be connected.
C3-2
Thermocouple Inputs
3.2.3 Analog Outputs (AO)
Number of Devices: 4
Device Types: Analog Output, (4 to 20) mA or (0-5) V, 16 bit hardware
There are two screw terminal connectors for each analog output.
Terminals 137 to 144 are AO terminals.
Analog Outputs
C3-2
4.0 Hazardous Area Operation
The Centurion approvals for CSA, CLASS 1, DIVISION 2, Groups B, C and D are pending.
Explosion hazard – Do not disconnect the equipment unless the power has been switched off, or the area is
Warning:
known to be non-hazardous.
TTD-98055N page 10 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
5.0 Hardware Installation and Wiring
5.1 Mounting the Centurion Controller
The Centurion can be mounted vertically or horizontally on a standard DIN rail. Three clamp type feet along the bottom of
the controller attach to the DIN rail, however, rail stops are recommended to prevent sliding.
2-1/2 in.
(64 mm)
13-1/8 in. (333 mm)
MOUNTING
BRACKET DETAIL
C3-1 Mounting
Bracket
DIN Type
Mounting Rail
C3-1
To Panel
5.2 Mounting the Centurion C3-3 Display
The Centurion C3-3 Display can be mounted in the same hole cutout of other Murphy display modules. Four screws
attached the display bezel to the mounting surface.
6-1/2 in. (165 mm)
2-1/8 in. (54 mm)
6.0 in. (152 mm)
5.50 in.
(140 mm)
6-1/2 in.
(165 mm)
5-1/4 in.
(134 mm)
3 in. (76 mm)
0.156 in. (4 mm) dia. 4 places
Power Hook Up
5.3 Power Supply Wiring
Power
Centurion C3-1 I/O Module
Requirements: (10 to 32) VDC: 30W (Max)
C3-1
There are two screw terminal connectors for power hookup at
terminals 62 and 63, labeled B+ and B- respectively.
Centurion C3-2 Optional Expansion Module
Requirements: (10 to 32) VDC
Power Hook Up
There are three screw terminal connectors for power hookup
at terminals 134 to 136, labeled B+, B- and B- respectively.
C3-2
TTD-98055N page 11 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
5.4 Wiring the Centurion C3-3 Display
TTD-98055N page 12 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
5.5 Wiring the Centurion C3-1/C3-2
TTD-98055N page 13 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
5.5 Wiring the Centurion C3-1/C3-2 (continued)
TTD-98055N page 14 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
6.0 Using the C3-3 Display to View and Configure the Centurion
Controller Settings
The Murphy C3-3 Display module is a highly integrated opera-
tor interface specially programmed to complement and sup-
port Centurion controller. The primary purpose of C3-3
Display is to display operational and configuration parameters
and provide access to modify the configuration parameters
stored in the Centurion controller.
6.1 Features
• Power
– 10 - 32 VDC (LED active indication)
– Storage power able to withstand 12V crank
• Package and Design
– Same 5 x 5 design as annunciators
– 12 key keypad
• Familiar annunciator keys
• Easy navigation keys
– 128 x 64 graphic backlit display
– Configurable using PC Software
– Field Upgradeable (flash bootloader)
• Communications
– LED active indication for each port
– RS232/485 (Modbus Master)
– RS232/485/USB 1.1 Compliant Port
• Download Configuration/Monitoring
• Approvals
– Approvals for CSA, CLASS 1, DIVISION 2, Groups B, C and D are pending.
6.1.1 Keypad Description and Navigation
The keypad for the C3-3 Display has 12 keys. The
following table generally describes the keys and
their function for each of the three screen types:
COOLER TEMPERATURE
105° F
___________________________________
LOW ENGINE OIL LEVEL
___________________________________
REMOTE
WARMUP
▼▲
0000.3H
B2 TIME-140
• Operating status screens
• Setup screens (Password required)
• Edit screens (Password required)
ESC
ACK
Fn
Many of the keys have a modified action relative to
the current location of the cursor and the current
page being displayed.
SETUP
ENTER
HOME
RESET
RUN
STOP
TIMER
“ 0”
TEST
CE-05171N page 15 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
HOME
Operating Status Screen
HOME
Allows the user to get to the first line of the current screen, or if pressed again, to get to the default
operating status screen.
Set Up Screen
Allows the user to get to the first line of the current screen
Edit Screen
No associated action.
ESC/ACK
ESC
ACK
Operating Status Screen
Acknowledge the active message/alarm that is currently displayed in the Alarm Banner.
Acknowledges all active messages and alarms displayed in the Active Alarm Screen.
Set Up Screen
Exit Setup mode.
Edit Screen
Exit without saving changes to the current configuration.
Fn (Function Key)
Operating Status Screen
Fn
Enter “Function mode” and display a dialog box with additional available functions. Automatically can-
cels upon moving to the next mode, or if no subsequent function is chosen within five seconds.
Set Up Screen
Enter “Function mode” and display a dialog box with additional available functions. Automatically can-
cels upon moving to the next mode, or if no subsequent function is chosen within five seconds.
SETUP/ENTER
Operating Status Screen
Enter Setup Mode.
SETUP
ENTER
Set Up Screen
Enter Edit mode or Sub-menu.
Edit Screen
Accept and save changes made to a current parameter before exiting Edit mode.
RESET
Operating Status Screen
RESET
Reset any active timers and alarms/faults.
Set Up Screen
No associated action.
Edit Screen
No associated action.
CE-05171N page 16 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
RUN/STOP
Operating Status Screen
RUN
STOP
Initiate or cancel a start sequence.
Set Up Screen
No associated action in either Shutdown mode, or Remote mode on standby. Initiate stop sequence
when held for two seconds, if equipment is running.
Edit Screen
No associated action.
ARROW UP
Operating Status Screen
Scroll up one line. Automatically repeats if held down continuously until reaching the first line.
For history screens, scrolls up one history (for example: Shutdown or Event).
Set Up Screen
Scroll up one line. Automatically repeats if held down continuously until reaching the first line.
Edit Screen
Increment the digit selected by the cursor (from 0 to 9). The user will not be allowed to increment the
selected digit if it would result in exceeding range limits.
ARROW DOWN
Operating Status Screen
Scroll down one line. Automatically repeats if held down continuously until reaching the final line.
For history screens, scrolls down one history (i.e. Shutdown or Event).
Set Up Screen
Scroll down one line. Automatically repeats if held down continuously until reaching the final line.
Edit Screen
Decrement the digit selected by the cursor (from 0 to 9). The user will not be allowed to decrement the
selected digit if it would result in exceeding range limits.
ARROW LEFT
Operating Status Screen
Display previous screen. Automatically repeats if held down continuously until reaching the first screen.
Set Up Screen
Display previous screen. This key has no action when in a sub-menu.
Edit Screen
Move the cursor to the previous digit.
CE-05171N page 17 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
ARROW RIGHT
Operating Status Screen
Display next screen. Automatically repeats if held down continuously until reaching the final screen.
Set Up Screen
Display next screen. This key has no action when in a sub-menu.
Edit Screen
Move the cursor to the next digit.
TEST
Operating Status Screen
TEST
Enter test mode and start test timer. This is not applicable in Shutdown mode.
Set Up Screen
No associated action.
Edit Screen
No associated action.
TIMER “0”
Operating Status Screen
TIMER
“ 0”
Zero displayed timer (Global Timers, State Timers, etc.)
Set Up Screen
No associated action.
Edit Screen
No associated action.
CE-05171N page 18 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
6.1.2 Display Context
The graphic LCD displays are organized around operating status screens and setup screens. The actual number of status
screens will be related to the total number of end devices configured for the controller. In either screen set, ten (10) lines
are visible at a time; with up and down arrow characters indicating more lines are available on the page. Also, for both
screen sets, navigation between screens is accomplished by pressing the left or right arrow keys.
TM
C
Operational/Process
Information Area
COMP. OIL PRESS.
SUCTION PRESS.
74 PSI
35.3 PSI
265 PSI
270 PSI
105° F
Status Area
DISCHARGE PRESS.
DISC. PRESS. TARGET
COMP OIL TEMP
ALARM
DISC. TEMPERATURE
COOLER TEMPERATURE
___________________________________
130° F
105° F
LOW ENGINE OIL LEVEL
___________________________________
REMOTE
WARMUP
▼▲
0000.3H
B2 TIME-140
STATUS
HOURS
STATE
NAVIGATION
TIMER
6.1.3 Numeric Entry
The C3-3 Display uses a different approach to enter values than previous Murphy controllers. Instead of holding
in the arrow keys until the desired number is displayed, the Centurion display allows individual editing of each
position of the desired number. This is accomplished by entering the Edit Mode and using the UP/DOWN arrow
keys (1) to adjust the number above the blinking cursor (2) between 0 and 9. To edit another position, simply use
the LEFT/RIGHT (3) arrow keys to move the cursor to that position (4) and repeat the edit process until the
desired number is displayed.
In this way, values are “built” rather than “scrolled” through. Some digits may not be allowed to increment if it
would result in exceeding range limits. Values which can be positive or negative will have a sign ( ) to the left of
the number. To change the sign value simply move the cursor to the sign using the LEFT arrow key and “toggle”
between + and – using the U and DOWN arrow keys. If the range of the value will exceed range limits the sign
may not be allowed to change. In this case, try reducing the numebr by decrementing the left most digit by one
or more and attempt to change the sign again.
In some instances, a word rather than a value is represented in the Edit Mode. This works like the sign value as
an ON/OFF or YES/NO prompt where the value is “toggled” between choices using the UP/DOWn arrow keys.
The value is not active in the controller until the ENTER key has been pressed to send the value to the controller.
Pressing the ESC key will discard any changes and keep the original value prior to entering the Edit Mode.
(4)
(2)
(3)
(1)
O
W
O
M
LEFT and RIGHT
UP and DOWN
F
___
__________
___________
___
_
_
__________
___________
P
___________
00000
00001
_________
▼▲
E
L
Blinking Cursor
Blinking Cursor
CE-05171N page 19 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
6.2 Operational Screens
In addition to the set up screens reviewed in Section 7.3, the C3-3 Display offers a number of operational displays.
On the Operating Status screens, the two bottom lines display the state, hours, mode and active timer status.
This information is key to understanding the “status” of the controller.
Mode refers to the Operating Mode of the controller and can be LOCAL or REMOTE. Depending on the configuration
active in the controller, the operation may differ depending on what Mode the controller is currently displaying.
NOTE:
The Mode can be changed by pressing certain keys, if the configuration allows for REMOTE mode.
Pressing RESET or RUN/STOP is a Local function and will change the Mode to Local if it is in REMOTE.
Pressing Fn before pressing RESET or RUN/STOP is a REMOTE function and will change the Mode to REMOTE if it is in LOCAL.
6.2.1 Default Operating Screen
After turning on the power, the user will view the F W Murphy logo screen for three seconds before the next
screen displays, which is a software-configured default operating screen. The MConfigPro software allows
users to configure up to five screens with controller I/O groupings. Possible custom screen types that may have
been configured as a default operating screen, or which may be also displayed, include:
a) Custom Line by Line allows process data to be displayed in a list format with description and value.
b) Custom Gage allows user to display four (4) most important pieces of data on a 2 x 2 table in larger font.
c) Custom PID up to 4 PID screens.
For more information on configuring the optional screens through the MConfigPro software, please refer to the
Centurion Controller Programming Manual.
6.2.2 F W Murphy Logo Screen
The F W Murphy Logo is the first screen in the sequence of
TM
Display screens and can be viewed by holding down the left
arrow until scrolling left ceases.
C
Logo Screen
6.2.3. Corporate and Version Information Screen
Following the F W Murphy Logo screen is the F W Murphy
TM
C
corporate contact information which also lists firmware version
information for the Centurion C3-3 Display, the C3-1 I/O
Module and the MConfigPro Software.
FW MURPHY - MVIEW
WWW.FWMURPHY.COM
(918) 317-4100
DISPLAY VER
CONTROLLER VERSION
MCONFIG PRO VER
XI.XI.XI
XI.XI.XI
XI.XI.XI
Info Screen
CE-05171N page 20 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
6.2.4. Shutdown History Screen
The history of the last twenty shutdowns is displayed on this
screen, with the most recent at the top of the list and the old-
est at the bottom.
Each event is displayed with the shutdown label on one line
and the hour meter reading on the following line. Pressing the
up/down arrows will scroll up/down one shutdown at a time
rather than one line at a time.
The “1 / 3” at the right end of the top line means the user is
viewing shutdown one of a total of three stored. The newest
shutdown will always be number one and it will push the older
shutdowns further down the list.
TM
C
SHUTDOWN HISTORY
1/3
___________________________________
PANEL ESD
00059:16:09
LOW SUCT PRESS
00059:15:11
OVERCRANK
00054:04:40
Shutdown History Sreen
6.2.5 Event History Screen
The user easily can view the events (alarms, etc.) logged
before and after a shutdown of interest.
There will be a maximum of thirty two events in this history
and beyond that a new event will cause the oldest event to be
discarded.
TM
C
EVENT HISTORY
1/3
___________________________________
PANEL ESD
00059:16:09
PANEL RESET
00059:15:58
LOW SUCT PRESS
00059:15:11
Event History Sreen
6.2.4 Active Alarms Screen
TM
C
All active alarms and warnings will be displayed on this screen.
The top line is the screen heading and the next six lines dis-
play alarms. If there are more than six active alarms, there will
be up/down arrow icons at the bottom of the screen and the
user can press the up/down arrow keys to scroll up or down.
Unacknowledged alarms will be preceded by a musical note
character and acknowledged alarms will have a bar through
the staff of the note.
ACTIVE ALARMS
___________________________________
LOW SUCT PRESS
LOW BATTERY VOLTS
___________________________________
ACK-ACK ALL ALARMS
Pressing ACK on this screen will acknowledge all active alarms.
Alarms Screen
This screen shows the alarm annunciation as it will appear on a
status screen.
TM
C
COMP. OIL PRESS.
SUCTION PRESS.
74 PSI
35.3 PSI
265 PSI
270 PSI
105° F
The alarm message(s) will overwrite the bottom line of the active
screen area and then briefly clear once a second. This will con-
tinue until it is acknowledged with the ACK, key unless it is a
self-clearing alarm. If there is more than one unacknowledged
alarm active, each alarm will be displayed for one second each
until acknowledged. The ACK key will acknowledge the alarm
currently displayed. Pressing the Fn key followed by the ACK
key will switch to the Alarms screen.
DISCHARGE PRESS.
DISC. PRESS. TARGET
COMP OIL TEMP
DISC. TEMPERATURE
COOLER TEMPERATURE
130° F
105° F
___________________________________
LOW ENGINE OIL LEVEL
___________________________________
REMOTE
WARMUP
▼▲
0000.3H
B2 TIME-140
Operating Status Screen 3
CE-05171N page 21 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
6.2.5 Gage Display
This is an example of a custom gage display. Configured soft-
ware orders the data as needed. This display provides larger
characters for easier viewing as well as a means to prominently
display items of interest. Unacknowledged alarms will overwrite
the bottom half of the lower two gage boxes. The two bottom
lines are used to display the mode, hours, state and active
timer status.
TM
WTR TEMP
145
C
OIL PRS
42
PSI
VDC
°F
BATTERY
ENG SPEED
13.7
1250
RPM
___________________________________
REMOTE
WARMUP
0000.5H
B2 TIME=140
Custom Gage Sreen
6.2.6 Line By Line
This is an example of a line by line status screen for engine
parameters.
The MConfigPro software orders the available data as
needed.
Notice that there are no up/down arrows at the bottom of the
screen because there are no additional lines to be displayed
on this screen.
TM
C
ENGINE SPEED
1140 RPM
47 PSI
7.5 ‘HG
130° F
92° F
ENGINE OIL PRESS.
INTAKE MFD PRESS.
JKT WTR TEMP
AUX WTR TEMP
___________________________________
REMOTE
WARMUP
0000.3H
B2 TIME-140
Operating Status Screen 1
This is an example of a line by line status screen with more
parameters.
If the parameters do not fit on a single screen, up/down arrow
icons at the bottom of the screen can be used to scroll up or
down. The two bottom lines are used to display the mode,
hours, state and active timer status.
TM
C
COMP. OIL PRESS.
SUCTION PRESS.
74 PSI
35.3 PSI
265 PSI
270 PSI
105° F
DISCHARGE PRESS.
DISC. PRESS. TARGET
COMP OIL TEMP
DISC. TEMPERATURE
COOLER TEMPERATURE
AMBIENT TEMPERATURE
130° F
105° F
91° F
___________________________________
REMOTE
WARMUP
▼▲
0000.3H
B2 TIME-140
Operating Status Screen 2
6.2.7 Custom PID Screen
The user may choose to display any configured PID functions
in this convenient format. The control output will be displayed
as a percentage of the range. The bottom two lines are used
to display the mode, hours, state and active timer status.
TM
C
SETPOINT
75 PSI
75%
65 PSI
75%
LINE PRESSURE
CONTROL OUTPUT
SUCTION PID
80%
___________________________________
REMOTE
WARMUP
▼▲
0000.3H
B2 TIME=140
CUSTOM PID Sreen
CE-05171N page 22 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
6.3 Setup Screens and Menus
6.3.1 Password Screen
Some settings are password protected, including the setup screens.
This is the first screen seen when the SETUP/ENTER key is pressed.
TM
C
The password need only be entered once during any editing
session. The password will reset when the editing session is
exited, or is timed-out due to keyboard inactivity.
The cursor begins at the last digit on the right. The user can
adjust the value of each digit with the up/down arrows while
the left/right arrows are used to select the digit to edit.
ENTER PASSWORD
FOR SETUP MENUS
___________________________________
_
___________________________________
00000
Passwords are assigned using the MConfigPro software and each
digit can range from zero to nine (except the first digit on the left)
for a total range of 00000 to 65535 for the complete password.
▼▲
ENTER-ACCEPT
ESC-CANCEL
The user will not be allowed to increment the selected digit if it
would result in exceeding range limits.
Password Screen
There are three separate levels of passwords to accommodate
several security needs:
• “Standard” password – Allows access to every feature
except the Super User menu. Valid Standard passwords
can be zero or any number between 100 and 65535. If the
Standard password is set to zero, the result is that anyone
can have read/write access to setup menus.
• “Super User” password – Adds the Super User menu to the
Standard menus. Valid Super User passwords can be in the
range of 100 to 65535. The Super User password can not
be the same as the Standard password.
TM
C
• “Download Only” password – This Special 35 Jump Code
allows access to a download menu and is set to a fixed
value of 35. This allows a configuration to be downloaded in
the event that the current passwords are lost or no initial
configuration has been downloaded.
SUPER USER MENU
___________________________________
COM FAIL DISABLE
SETUP T/O DISABLE
CONFIG FAIL DISABLE
RESET FAULT HISTORY
If the Standard password is not zero and a password of all zeroes
is entered, the user will have “view only” access.
RESET EVENT HISTORY
___________________________________
NO
___________________________________
Inactivity Timeout: Setup procedures must be started and
completed in a timely manner. Note that after 3 minutes
without activity, the keypad returns the default operational
screen and a password must be re-entered to return to the
setup and edit menus.
▼▲ ENTER-EDIT
MORE MENUS
Super User Menu Screen
TM
C
CONFIRATION DOWNLOAD
___________________________________
COM 1 CONFIG DOWNLOAD
COM 2 CONFIG DOWNLOAD
USB CONFIG DOWNLOAD
FIRMWARE DOWNLOAD
___________________________________
NO
___________________________________
▼▲
ENTER-EDIT
Download Only Screen
CE-05171N page 23 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
6.3.2 Digital Input
Digital Input: For up to 32 configured Digital Input devices,
the user may select whether an input is normally open (N/O),
or normally closed (N/C).
TM
C
DIGITAL INPUTS
___________________________________
DIGITAL INPUT 1
DIGITAL INPUT 2
DIGITAL INPUT 3
DIGITAL INPUT 4
DIGITAL INPUT 5
___________________________________
D_IN_01 N/0
___________________________________
▼▲ ENTER-EDIT
MORE MENUS
Digital Inputs Setup Screen 1
TM
C
DIGITAL INPUTS
___________________________________
DIGITAL INPUT 1
DIGITAL INPUT 2
DIGITAL INPUT 3
DIGITAL INPUT 4
DIGITAL INPUT 5
___________________________________
D_IN_01
N/0
___________________________________
ENTER-ACCEPT
▼▲ MODIFY SELECTION
Digital Inputs Setup Screen 2
6.3.3 Digital Output
Digital Output: For up to 10 configured Digital Output
devices, the user may select whether an output is normally
open (N/O), or normally closed (N/C).
TM
C
DIGITAL OUTPUTS SETUP
___________________________________
DIGITAL OUTPUT 1
DIGITAL OUTPUT 2
DIGITAL OUTPUT 3
DIGITAL OUTPUT 4
DIGITAL OUTPUT 5
___________________________________
R_OUT_01 N/O
___________________________________
▼▲ ENTER-EDIT
MORE MENUS
Digital Outputs Setup Screen 1
6.3.4 AnalogCInput
For up to 20 configured Analog Input devices, the user may edit
TM
a)
b)
Moving Average Samples. (1, 2, 4).
Determine Raw Count Offset, the lowest reading
expected from the device.
ANALOG INPUTS SETUP
___________________________________
ANALOG INPUT 1
ANALOG INPUT 2
ANALOG INPUT 3
ANALOG INPUT 4
c)
d)
Determine Raw Count Span, the span from the lowest
to highest reading expected from the device.
Apply the appropriate Minimum engineering scale. In
most cases, 0% addresses a typical application and it
is the Centurion’s default value.
ANALOG INPUT 5
___________________________________
AN_IN_01
___________________________________
e)
Apply the appropriate Maximum engineering scale.
In most cases, 100% addresses a typical application
and it is the Centurion’s default value.
▼▲ ENTER-SUBMENU
MORE MENUS
Analog Inputs Setup Screen 1
CE-05171N page 24 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
TM
C
ANALOG INPUT 1 SETUP
___________________________________
MOVING AVERAGE SAMPLES
RAW COUNT OFFSET
RAW COUNT SPAN
MINIMUM
MAXIMUM
___________________________________
(1,2,OR 4)
1
___________________________________
▼▲
ENTER-EDIT
ESC EXIT THIS MENU
Analog Input 1 Setup Screen
TM
C
ANALOG INPUT 1 SETUP
___________________________________
MOVING AVERAGE SAMPLES
RAW COUNT OFFSET
RAW COUNT SPAN
MINIMUM
MAXIMUM
___________________________________
(1,2,OR 4)
1
___________________________________
–
▼▲
ENTER-ACCEPT
ESC-CANCEL
Analog Input 1 Setup Screen
6.3.5 Analog Output
User may edit:
a) Raw Count Offset, the lowest reading expected from
TM
C
the device.
ANALOG OUTPUTS SETUP
___________________________________
b) Determine Raw Count Span, the span from the lowest
to highest reading expected from the device.
c) Apply the appropriate Minimum engineering scale. In
most cases, 0% addresses a typical application and it is
the Centurion’s default value.
ANALOG OUTPUT 1
ANALOG OUTPUT 2
ANALOG OUTPUT 3
ANALOG OUTPUT 4
ANALOG OUTPUT 5
___________________________________
AN_OUT_01
___________________________________
d)
Apply the appropriate Maximum engineering scale.
In most cases, 100% addresses a typical application
and it is the Centurion’s default value.
▼▲
ENTER-SUBMENU
MORE MENUS
Analog Output Setup Screen
TM
C
ANALOG OUTPUTS 1 SETUP
___________________________________
RAW COUNT OFFSET
RAW COUNT SPAN
MINIMUM
MAXIMUM
___________________________________
00000
___________________________________
▼▲
ENTER-EDIT
ESC-EXIT THIS MENU
Analog Output 1 Setup Screen
CE-05171N page 25 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
TM
C
ANALOG OUTPUTS 1 SETUP
___________________________________
RAW COUNT OFFSET
RAW COUNT SPAN
MINIMUM
MAXIMUM
___________________________________
00000
_
___________________________________
▼▲
ENTER-ACCEPT
ESC-CANCEL
Analog Output 1 Setup Screen 1
6.3.6 Thermocouple Input
User may:
a)
TM
C
Identify whether the calibration Type should be set to J or K.
b) Assign the Offset value.
THERMOCOUPLE SETUP
___________________________________
THERMOCOUPLE 1
THERMOCOUPLE 2
THERMOCOUPLE 3
THERMOCOUPLE 4
THERMOCOUPLE 5
___________________________________
TC1
___________________________________
▼▲
ENTER-SUBMENU
MOORE MENUS
Thermocouple Setup Screen
TM
C
THERMOCOUPLE 1 SETUP
___________________________________
THERMOCOUPLE TYPE
THERMOCOUPLE OFFSET
___________________________________
(J OR K)
J
___________________________________
▼▲
ENTER-EDIT
ESC-EXIT THIS MENU
Thermocouple 1 Setup Screen
TM
C
THERMOCOUPLE 1 SETUP
___________________________________
THERMOCOUPLE OFFSET
___________________________________
- 00015
___________________________________
▼▲
ENTER-ACCEPT
ESC-CANCEL
Thermocouple 1 Setup Screen 1
CE-05171N page 26 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
6.3.7 General Timer Setup
User may edit all general purpose timers. Generally, global timers
affect engine operation. They also help define an event.
TM
C
B1 TIMER
B2 TIMER
C TIMER
a)
B1: All event types can be associated with, and locked out
by, a Bx timer. B1 is the first global timer used for delaying
an event condition detection. The timer starts in a running
State (10 – 13) depending on which have been marked ‘In
Use’. B1 is also known as the “Lockout Timer.”
B2: The second global timer used for delaying an event
condition detection. B2 is also known as a secondary
“Lockout Timer.”
C: The delay allowing a clear reading before beginning
testing for the arming of Class C events. The default and
typical time for most applications is 2 seconds.
S: Users have up to five (5) options to assign additional
special global timers to signals. The Sx timers begin con-
currently with the Bx timers.
___________________________________
GENERAL TIMER SETUP
S1 TIMER
S2 TIMER
___________________________________
b)
c)
d)
(0 - 999)
00060
___________________________________
▼▲ ENTER-EDIT
MORE MENU
General Timer Setup Screen
e) No Flow: The global delay used for delaying the triggering of
a No Flow event. This global no flow timer is enabled after
B1 expires, and begins timing after any of the no flow transi-
tion times configured in the digital input dialog expires.
f) Test: Time given to allow for maintenance testing of end
devices without triggering a fault or shutdown condition.
The timer initiates when switched to test mode.
g) Ignition Off Delay: Time delay before the assigned ignition
output turns off. This is typically used to burn remaining
fuel vapors after the fuel valve is turned off.
h) Ignition On Delay: Time delay before the assigned ignition
output turns on. This is typically used to delay ignition
until engine crank rollover can occur.
i) Fuel On Delay: Time delay before the assigned fuel valve
output is turns on. This is typically used to delay fuel until
ignition has been turned on.
CE-05171N page 27 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
6.3.8 Maintenance Timer Setup
The user may access and edit the ten (10) maintenance set-
tings for timer duration. The user may also access and reset
all timer duration and time remaining settings. Note that while
these are configured through MConfigPro, they must be man-
ually initiated, or restarted, in C3-3 Display. All maintenance
timer units are in hours.
TM
C
MAINTENANCE TIMER SETUP
___________________________________
MAINTENANCE TIMER 1
MAINTENANCE TIMER 2
MAINTENANCE TIMER 3
MAINTENANCE TIMER 4
MAINTENANCE TIMER 5
___________________________________
CHANGE OIL
___________________________________
▼▲
ENTER-SUBMENU
MORE MENUS
Maintenance Timer Setup Screen
TM
C
MAINTENANCE TIMER SETUP
___________________________________
TIMER DURATION
TIME REMAINING
___________________________________
CHANGE OIL
00100
___________________________________
▼▲
ENTER-EDIT
ESC-EXIT THIS MENU
Maint_1 Setup Screen
TM
C
MAINTENANCE TIMER SETUP
___________________________________
TIME REMAINING
___________________________________
CHANGE OIL
00091
___________________________________
▼▲
RESET-RESET TIMER
ESC-EXIT THIS MENU
Maint_1 Setup Screen 1
CE-05171N page 28 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
6.3.9 Set poiCnts Setup
User can edit any of the 128 set points that are configured.
Set points further configure analog inputs and thermocouple
inputs by defining a threshold, exception or any other out-of-
limit event that may require action. Multiple set points are
often applied to a process and they may be configured as
often as needed to meet changing conditions.
TM
SETPOINTS SETUP
___________________________________
SETPOINTS 1-16
SETPOINTS 17-32
SETPOINTS 33-48
SETPOINTS 49-64
Common alarm and shutdown set points a user might have
configured include:
SETPOINTS 65-80
___________________________________
___________________________________
High Shutdown
Low warning
Open Warning
High Warning
Low Shutdown
▼▲
ENTER-SUBMENU
MORE MENUS
Setpoints Setup Screen
A user might also have configured other set point settings
which are not used to indicate alarm or shutdown. For exam-
ple, a set point provides a less flexible, but simpler alternative
to controlling the pump’s start and stop functions.
TM
C
SETPOINTS SETUP
___________________________________
SETPOINTS 1
SETPOINTS 2
SETPOINTS 3
To edit a configured set point:
SETPOINTS 4
a) Assign numeric threshold that if crossed, triggers the set point.
b) Adjust the sign of the threshold value as plus (+) or minus (-) by
moving the cursor to the sign symbol position and use the up
and down keys to toggle the sign.
SETPOINTS 5
___________________________________
LO SUCT PRS
0008.0
___________________________________
▼▲
ENTER-EDIT
ESC-EXIT THIS MENU
For more on Set Points, please refer to the Centurion
Configurable Controller Programming Manual.
Setpoint Setup Screen 1
6.3.10 Control Output Setup
The Centurion controller allows users to define up to eight (8)
outputs to augment control not otherwise defined.
TM
C
CONTROL OUTPUT 1 SETUP
___________________________________
The Centurion controller can be configured through MConfigPro
software to define an analog output, a digital output, a single
pulsed digital output, or two pulsed digital outputs.
CONTROL OUTPUT 1
CONTROL OUTPUT 2
CONTROL OUTPUT 3
CONTROL OUTPUT 4
Note that Control Outputs 1 through 4, are directly related to
Proportional Integral Derivative (PID) calculation loops and are
further defined in the PID dialog screens described in Section
6.3.11. For example, PID 1 is assigned its control from
Control Output 1, PID 2 from Control Output 2, and so on.
CONTROL OUTPUT 5
___________________________________
THROTTLE
___________________________________
▼▲
ENTER-MENU
MORE MENU
If the configured output is a pulsed cycle, the user may edit
those behaviors by following the available steps:
a) Assign value to Increase Max On Time. (Set limit of maxi-
mum on-time for Increase pulses.)
b) Assign value to Increase Off Time. (Set fixed off-time for
Increase pulses.)
Control Output Setup Screen
TM
C
CONTROL OUTPUT 1 SETUP
___________________________________
c) Assign value to Increase Changeover On Time. (Set fixed
on-time for single pulse on direction change for Increase).
d) Assign value to Increase Changeover Off Time. (Set fixed
off-time for single pulse on direction change for Increase).
INC MAX ON TIME
INC OFF TIME
INC CHANGEOVER ON TIME
INC CHANGEOVER OFF TIME
DEC MAX ON TIME
___________________________________
e)
Assign value to Decrease Max On Time. (Set limit of maxi-
mum on-time for Decrease pulses.)
01000
___________________________________
▼▲
ENTER-EDIT
f) Assign value to Decrease Off Time. (Set fixed off-time for
Decrease pulses.)
ESC-EXIT THIS MENU
g) Assign value to Decrease Changeover On Time. (Set fixed on-
time for single pulse on direction change for Decrease).
Control Output 1 Setup Screen
CE-05171N page 29 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
h)
Assign value to Decrease Changeover Off Time. (Set fixed
off-time for single pulse on direction change for Decrease).
For more on Control Output, please refer to the Centurion
Configurable Controller Programming Manual.
6.3.11 PID Setup
Users may view and edit up to four (4) MConfigPro software con-
figured Proportional Integral Derivative (PID) calculation loops.
A PID provides a constant feed back loop, in which the PID
can correct for a measured process variable against a
desired set point, output the corrective action to the process
and wait for and recalculate the next measurement.
TM
C
PID SETUP
___________________________________
PID 1
PID 2
PID 3
PID 4
The ultimate goal of the PID is to reduce the error to zero.
___________________________________
PID 1
_
___ _______________________________
During the time a PID is enabled, the PID always overrides a
control output. Recall that PID 1 is assigned its control from
control output 1, PID 2 from control output 2, and so on.
▼▲
ENTER-SUBMENU
MORE MENUS
PID Setup Screen
To View and Edit PID Settings:
1) Over Ride Ramp Time: Assign a time interval value to wait
before making the next adjustment.
TM
C
2) Over Rid Ramp Amount: Determine the increments in a
given direction (positive or negative) that the set point
should be altered to regain balanced processes. In the
example of the discharge and suction pressure application,
this value would indicate how much the PID should resist
its goal in reaching the set point.
3) Ramp Time: Assign a time interval for the PID to calculate error.
4) Over Ride Max Change: Assign a maximum allowed
change. This represents the total amount of change
allowed into or out of the ramp amount from the set point.
The maximum change value should be large enough to
effect change.
PID 1 SETUP
___________________________________
OVERRIDE RAMP TIME
OVERRIDE RAMP AMOUNT
RAMP TIME
MAX % OF CHANGE
SETPOINT
___________________________________
00004
___________________________________
▼▲
ENTER-EDIT
ESC-EXIT THIS MENU
PID 1 Setup Screen
5) Set Point: Assign the desired goal—the target feedback
base value.
6)
DeadBand: Assign a value around the set point during
which the PID will not calculate error.
7)
Minimum Output: Assign a percentage as minimum output.
8) Maximum Output: Assign a percentage as maximum output.
9)
Proportional: Adjust the output by a value that is propor-
tional to the change of error.
10)
Integral: To prevent the PID from oscillating or over-
shooting the set point, assign a value to “reset” the system
to produce zero error, or nudge the process variable to the
set point. This value is typically set to zero.
11)
Derivative: Assign a value to the rate of change of error.
This value is typically set to zero.
12) Max Override Change: Assign a percentage rate of
change over which would cause harm to the system.
For more on PID, please refer to the Centurion Configurable
Controller Programming Manual.
CE-05171N page 30 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
6.3.12 Initial RPM Setup
a)
b)
c)
d)
Assign value for Warmup RPM.
Assign value for Wait to Load RPM.
Assign value for Run Loaded RPM.
Assign value for Cooldown RPM.
TM
C
INITIAL RPM SETUP
___________________________________
WARMUP RPM
WAIT FOR LOAD RPM
RUN LOADED RPM
COOLDOWN RPM
___________________________________
00600
___________________________________
▼▲ ENTER-EDIT
MORE MENUS
Initial RPM Setup Screen
6.3.13 Miscellaneous Setup
User can access and edit the miscellaneous settings.
a) Crank Attempts: Define a value for number of crank
attempts after which an over-crank sequence will be trig-
gered in the Event logic.
b) Controller Slave Address: Provide the value for the Modbus
Address Port. The factory default is 1.
TM
C
MISCELLANEOUS SETUP
___________________________________
NUMBER OF CRANK ATTEMPTS
PORT 1 SLAVE ADDRESS
PORT 1 RS432/RS485
PORT 1 RESPONSE DELAY
c) Port 1 Mode: Select Communication Port 1 as RS232, or RS485.
d) Port 1 Reply Delay: To ensure sufficient time for the
Modbus reply, assign appropriate time value for Delay
Modbus Reply Port 1.
PORT 1 BAUD RATE
___________________________________
00003
___________________________________
▼▲ ENTER-EDIT
MORE MENUS
e) Port 1 Baud Rate: Select appropriate transmission baud rate
f) Port 2 Mode: Select Communication Port 2 as RS232, or RS485.
Miscellaneous Setup Screen
g)
Port 2 Reply Delay: To ensure sufficient time for the
Modbus reply, assign appropriate time value for Delay
Modbus Reply Port 2.
h) Port 2 Baud Rate: Select appropriate transmission baud rate
i) Flywheel Teeth: Define a value for Flywheel Teeth used to
calculate RPM.
The following cold temperature offset values should only be adjusted by personnel with a full working knowledge of the
Centurion in conjunction with calibrated reference equipment.
j) Core Cold Temp Offset: Enter a non-zero Value for Core
Temperature Adjustment (in tenths) to adjust the temperature
readings for all Thermocouple inputs on both the Main I/O Module
(C3-1). Entering a non-zero value will adjust the Cold Junction
Compensation reading used to calculate temperature.
k)
Exp Cold Temp Offset: Enter a non-zero Value for
Expansion Board Temperature Adjustment (in tenths) to
adjust the temperature readings for all Thermocouple inputs
on Expansion I/O (C3-2). Entering a non-zero value will
adjust the Cold Junction Compensation reading used to cal-
culate temperature.
l)
Hour Meter: The user may make hour meter adjustments.
The range is 0 – 65535 hours.
CE-05171N page 31 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
6.3.14 Lube CNo Flow Set Up
User can view and edit Lube No Flow set up. There are two
levels to this menu as there are two possible adjustments per
No-Flow input. The user will select an input from the first menu
and press Setup/Enter. This will display the submenu for the
selected digital input if it is used for No-Flow monitoring.
Otherwise, the text label on the left side of the edit box will dis-
play “NOT IN USE”, and pressing Enter will have no effect.
At the submenu level, the user may adjust the expected tran-
sition frequency and the total cycles count (which relates to
the wear rate of the sensor).
TM
LUBE NO-FLOW SETUP
___________________________________
NO-FLOW INPUT # 1
NO-FLOW INPUT # 2
NO-FLOW INPUT # 3
NO-FLOW INPUT # 4
NO-FLOW INPUT # 5
___________________________________
DI_1 NF
___________________________________
▼▲ ENTER-SUBMENU
MORE MENUS
C Lube No-Flow Setup Screen
TM
NO-FLOW INPUT # 1 SETUP
___________________________________
CYCLE TIME (SEC)
TOTAL CYCLES (X100)
___________________________________
00010
___________________________________
▼▲
ENTER-EDIT
ESC-EXIT THIS MENU
No-Flow # 1 Setup Screen
6.3.15 Lube CNo Flow Status
The user may view information about the No-Flow inputs. If a
digital input is designated for use as a No-Flow input, it will
display how much time elapsed before the last transition, and
how much time has elapsed since that transition. If the input
is not designated as a No-Flow input, there will be zeros dis-
played. Both values have a maximum value of 999.
TM
LUBE NO-FLOW STATUS
___________________________________
CYCLE TIME-INPUT # 1
CYCLE TIME-INPUT # 2
CYCLE TIME-INPUT # 3
CYCLE TIME-INPUT # 4
CYCLE TIME-INPUT # 5
___________________________________
PREV 0 CURR 0
___________________________________
▼▲
CYCLE TIMER (SEC)
MORE MENUS
Lube No-Flow Status Screen
6.3.16 Super User Menu
The Super User menu will only be visible if the Super User
password has been entered.
TM
C
The first three selections (a – c) allow the user to temporarily
override the default behavior of the display. It may be helpful
to turn off a fault annunciation screen that prevents the view-
ing of information on operating status screens.
SUPER USER MENU
___________________________________
COM FAIL DISABLE
SETUP T/O DISABLE
CONFIG FAIL DISABLE
RESET FAULT HISTORY
a)
b)
c)
Com Fail Disable
Set up T/O Disable
Config Fail disable
RESET EVENT HISTORY
___________________________________
NO
___________________________________
▼▲ ENTER-EDIT
MORE MENUS
Note that the reset history commands do not permanently switch
to Yes when entered, but instead toggle back to NO after sending
the command to the controller.
Super User Menu Screen
CE-05171N page 32 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
TM
Also, the message “History Cleared” will be displayed until another
key is pressed.
C
SUPER USER MENU
___________________________________
d)
e)
Reset Fault History
Reset Event History
RESET FAULT HISTORY
RESET EVENT HISTORY
P1 PU/PD
P1 TERMINATION
P2 PU/PD
The P1 and P2 signify Communication Port 1 and
Communication Port 2 and are for setting up the RS485 inter-
faces on the display’s serial ports. PU/PD designates the
pull-up and pull-down resistors.
___________________________________
HISTORY CLEARED
NO
___________________________________
f)
g)
h)
P1 PU/PD
P2 Termination
P2 PU/PD
▼▲ ENTER-EDIT
MORE MENUS
Super User Menu Screen 2
i)
P2 Termination
New configurations can be downloaded to the display by
selecting the desired connection here. After enabling the
download, download progress is indicated on the left side of
the edit box as a percentage complete. After selecting Yes for
download, and until No is selected after download is com-
plete, only the Enter key will be active. See Section 6.2 for fur-
ther details about downloading configurations.
TM
C
SUPER USER MENU
___________________________________
COM 1 CONFIG DOWNLOAD
COM 2 CONFIG DOWNLOAD
USB CONFIG DOWNLOAD
FACTORY AUTO TEST
FIRMWARE DOWNLOAD
j) Com 1 Config Download
___________________________________
k) Com2 Config Download
l) USB Config Download
28%
YES
___________________________________
▼▲
ENTER-EDIT
m) Factory Auto Test: For factory use ONLY.
n) Firmware Download: A firmware update mode screen will
remain until the unit has been reset by remote command or a
power cycle. See Section 7.2.5 for downloading new firmware.
Super User Menu Screen 3
6.3.17 Configuration Download (Download Only Screen)
This menu allows for download only and can be accessed
through the Special Jump Code 35. It is the only screen
available by entering the password 35.
TM
C
CONFIRATION DOWNLOAD
___________________________________
a) Com 1 Config Download: Selecting Yes initiates configu-
ration download through Communication Port 1.
b) Com2 Config Download: Selecting Yes initiates configu-
ration download through Communication Port 2.
COM 1 CONFIG DOWNLOAD
COM 2 CONFIG DOWNLOAD
USB CONFIG DOWNLOAD
FIRMWARE DOWNLOAD
___________________________________
c)
USB Config Download: Selecting Yes initiates configura-
tion download through USB port.
NO
___________________________________
▼▲
ENTER-EDIT
d)
Firmware Download: Selecting Yes Initiates the download.
Download Only Screen
6.3.18 Display Board Status
The user may view diagnostic information that reflects the
operating conditions of the C3-3 Display only. The Heater
PWM% refers to the LCD heater which only operates in cold
temperature conditions. The reset source indicates the cause
of the last reset. Possible causes for reset include external
reset, power-up, brown-out and watch dog.
TM
C
MVIEW BOARD STATUS
___________________________________
BATTERY VOLTS
BOARD CURRENT
TEMPERATURE
HEATER PWM %
a)
b)
c)
d)
e)
Battery Volts
Board Current
Temperature
Heater PWM %
Reset Source
RESET SOURCE
___________________________________
23.3 VDC
___________________________________
MORE MENUS
MView Board Status Screen
CE-05171N page 33 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
6.3.19 DigitalCInput Status
The user can see the state of each digital input in a table—
whether it is open or closed.
TM
DIGITAL INPUT STATUS
___________________________________
X=CLOSED
O=OPEN
___________________________________
1 X 0 0 X X X 0 0 8
___________________________________
9 0 0 0 X X X X X 16
___________________________________
17 0 0 0 0 0 0 0 0 24
___________________________________
25 0 0 0 0 0 0 0 0 32
___________________________________
MORE MENUS
Diagnostico-Digital Inputs Screen
6.3.20 DigitaCl Output Status
For each of the devices configured as In Use, the user can
see the state of each output and has the ability to Force an
output for the purpose of testing. A force is associated with a
timeout so that it will be automatically cancelled when return-
ing to normal operation.
TM
DIGITAL OUTPUT STATUS
___________________________________
DIGITAL OUTPUT 1
DIGITAL OUTPUT 2
DIGITAL OUTPUT 3
DIGITAL OUTPUT 4
DIGITAL OUTPUT 5
___________________________________
DO 1 FLT LAMP
OFF
___________________________________
▼▲ ENTER-EDIT
MORE MENUS
Diagnostic-Digital Outputs State Screen
6.3.21 Analog Input Status
The user can view the raw counts of the analog inputs for
troubleshooting.
TM
C
ANALOG INPUT STATUS
___________________________________
ANALOG INPUT 1
ANALOG INPUT 2
ANALOG INPUT 3
ANALOG INPUT 4
ANALOG INPUT 5
___________________________________
AI 1 SUCT PRS
00000
___________________________________
▼▲
MORE MENUS
Diagnostic-Analog Inputs Screen
6.3.22 Analog Output Status
The user can see the state of each output, and if in Test
mode, has the ability to Force an output for the purpose of
testing. Analog outputs under the control of PID or other
Control Output settings cannot be forced. To force a PID
controlled output, place the PID in Manual mode and operate
the manual output value.
TM
C
ANALOG OUTPUT STATUS
___________________________________
ANALOG OUTPUT 1
ANALOG OUTPUT 2
ANALOG OUTPUT 3
ANALOG OUTPUT 4
ANALOG OUTPUT 5
___________________________________
AI 1 ENG SPEED
030.00
___________________________________
▼▲ ENTER-EDIT
MORE MENUS
Diagnostic Analog-Outputs Status Screen
CE-05171N page 34 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
TM
C
ANALOG OUTPUT STATUS
___________________________________
ANALOG OUTPUT 1
ANALOG OUTPUT 2
ANALOG OUTPUT 3
ANALOG OUTPUT 4
ANALOG OUTPUT 5
___________________________________
AI 1 ENG SPEED
030.00
___________________________________
MUST BE IN TEST MODE
ESC-CANCEL
Diagnostic Analog-Outputs Status Screen 2
TM
C
ANALOG OUTPUT STATUS
___________________________________
ANALOG OUTPUT 1
ANALOG OUTPUT 2
ANALOG OUTPUT 3
ANALOG OUTPUT 4
ANALOG OUTPUT 5
___________________________________
AI 1 ENG SPEED
030.00
___________________________________
▲▼
ENTER-EDIT
MORE MENUS (TEST MODE)
Diagnostic Analog-Outputs Status Screen 3
6.3.23 Thermocouple Status
The user may view the raw counts of the thermocouple inputs
for troubleshooting.
TM
C
THERMOCOUPLE STATUS
___________________________________
THERMOCOUPLE 1
THERMOCOUPLE 2
THERMOCOUPLE 3
THERMOCOUPLE 4
THERMOCOUPLE 5
___________________________________
TH 1
00000
___________________________________
▲▼
MORE MENUS
Diagnostic Thermocouples Screen
6.3.24 Communication Status
Users may view the statistics for both of the display unit serial
ports, including Modbus requests and responses.
a) P1 Receive Count
TM
C
COMMUNICATION STATUS
___________________________________
b)
c)
d)
e)
P1 Transmit Count
P1 Frame Errors
P1 HW Overruns
P2 SW Overruns
P1 RECEIVE COUNT
P1 TRANSMIT COUNT
P1 FRAME ERRORS
P1 HW OVERRUNS
P1 SW OVERRUNS
___________________________________
f) P2 Receive Count
g)
02340
___________________________________
▲▼
P2 Transmit Count
h) P2 Frame Errors
MORE MENUS
i)
j)
P2 HW Overruns
P2 SW Overruns
Communication Status Screen 1
CE-05171N page 35 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
k)
l)
m)
n)
o)
p)
q)
Modbus Requests
Modbus Responses
Modbus Exceptions
Modbus Invalid Response
Modbus No Response
Clear Statistics
TM
C
COMMUNICATION STATUS
___________________________________
MODBUS REGISTER
Modbus Register
___________________________________
REG: 40001
VAL: 00000
___________________________________
▲▼ ENTER-EDIT
MORE MENUS
Communication Status Screen 2
TM
C
COMMUNICATION STATUS
___________________________________
MODBUS REGISTER
___________________________________
REGISTER: 40001
_
___________________________________
▲▼
ENTER-ACCEPT
ESD-CANCEL
Communication Status Screen 3
6.3.25 PID Diagnostics
For each of four (4) configured PIDs, user may select to edit:
a) Display PID Bar Graph: To monitor the results of modify-
ing the PID components.
TM
C
PID DIAGNOSTICS
___________________________________
b) Proportional: To modify the proportional component.
c) Integral: To modify the integral component.
d) Derivative: To modify the derivative component.
e) Auto/Manual: To set to manual mode to allow the corre-
sponding Control Output setting to be adjusted.
f) Set Output (Manual):
PID 1
PID 2
PID 3
PID 4
___________________________________
PID 1
___________________________________
▲▼
ENTER-SUBMENU
MORE MENUS
Diagnostic PIDs Screen
TM
TM
C
C
SETPOINT
75 PSI
PID 1 OPTIONS
___________________________________
75%
65 PSI
75%
DISPLAY PID BAR GRAPH
PROPORTIONAL
INTEGRAL
LINE PRESSURE
CONTROL OUTPUT
SUCTION PID
DERIVATIVE
80%
AUTO/MANUAL
___________________________________
___________________________________
NO
___________________________________
▲▼
ENTER-SUBMENU
MORE MENUS
ESC-EXIT
Diagnostic PIDs Sreen 3
Diagnostic PIDs Screen 2
CE-05171N page 36 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
6.4 Additional Navigational Aids
6.4.1 Function Key
Pressing the Function (Fn) key from any screen will display a
dialog box on the bottom half of the screen. All available func-
tion key commands will be displayed there. The user can then
press a single key for the available commands.
TM
C
FW MURPHY - MVIEW
WWW.FWMURPHY.COM
(918) 317-4100
In this case, the user can select from a help screen, the alarms
screen or issue a remote mode command. If the Fn key is not
followed by another key press in five seconds, function mode
will time out and the dialog box will go away restoring the previ-
ous screen.
Note: In all cases the Fn key options will be context sensitive.
Some options will only be available from certain screens or
under certain conditions.
___________________________________________________
Fn-EXIT
HOME-HELP
ACK-ALARMS SCREEN
REMOTE MODE COMMANDS:
RESET AND RUN/STOP
Fn Key Dialog Box Screen
6.4.2 Help Key
This is the help screen the user will see by pressing the HOME
key from the Fn dialog box or by pressing the Fn key followed
by the HOME key from a normal screen.
TM
C
PRESS ANY KEY TO EXIT
___________________________________
-MOVES SCREEN TO SCREEN
▲▼ -MOVES LINE TO LINE
HOME-TOP LINE OF SCREEN
HOME AGAIN-MAIN SCREEN
Help Screen
7.0 Communications
7.1 Communication Ports
Port 1 (SERIAL)
Port 1 is intended as the primary port for the local device, the C3-3 Display, and should be utilized for C3-3 Display
in order for the boot loader mode to properly execute in pass-thru mode.
Interface: Refer to the Sequence of Operations to determine how the communication port has been configured.
Protocol: Modbus (Slave)
Connection: There are three (3) screw terminal connectors for RS485.
These are identified as A, B, and SHD.
There are three (3) screw terminal connectors for RS232.
These are identified as RX, TX, and DTR.
SHD is common for both ports.
Port 2 (SERIAL)
Interface: Refer to the Sequence of Operations to determine how the communication port has been configured.
INSERT DIAGRAM? RICK NOTES ON PREVIOUS MARKUP
Protocol: Modbus (Slave), Proprietary (Binary)
Connection: There are three (3) screw terminal connectors for RS485.
These are identified as A, B, and SHD.
There are three (3) screw terminal connectors for RS232.
These are identified as RX, TX, and DTR.
SHD is common for both ports.
Modbus Slave Address Configuration: The operator may assign a unique Modbus address to each controller
(slave) unit that may be in the system. This allows the master controller to differentiate between the modules. For
example, to name the controller address 21, place the shunts on LK1, LK4, and LK16 (1 + 4 +16 = 21). Typically,
this configuration is set to (1) by the factory.
CE-05171N page 37 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
Port 2 (USB)
Interface: USB 1.1 Compliant Port capable of emulating RS232 communications via royalty free PC driver.
Protocol/Services: Modbus (Slave), Proprietary (Binary)
Connection: There is a USB Type B connector (see graphic).
Automatic selection of USB is provided when a signal is detected on the USB Type B connector.
Port 3 (CAN)
Protocol/Services: Proprietary (Binary)
Connection: There are three (3) screw terminal connectors for CAN. These are identified as HI, LOW, and SHD.
On C3-1 Main I/O Module
Located next to the USB connector is the CAN OK (COP). When in the boot loader the COP LED does not flash.
When the program is running properly the COP LED will flash on and off every 0.5 seconds.
If the checksum in the configuration file does not match the calculated checksum of the file, then the program
will flash the COP LED 3 times at 0.5 second intervals and then stay off for 1.5 seconds.
On the C3-2 Expansion I/O Module
When the program is running properly the COP LED will flash on and off every 0.5 seconds.
7.2 Downloading Configurations and Firmware Updates
Users will need to download configurations from the controller, as well as be able to receive occasional firmware
version updates from Murphy.
7.2.1 Boot Loader
It is necessary for the Centurion controller to enter boot loader mode in order to receive downloads for a
firmware update, and if configuration between the devices needs to be synchronized. During boot loader mode
the Centurion is able to transmit and receive configuration updates to and from the MConfigPro software and
transmit configuration updates to C3-3 Display through Pass Through.
Communications will operate according to default state parameters for configuration transfers. During boot
loader mode, the transfer rate is 9600, N, 8, 1 and assumes a serial communication port setting of RS485 or a
USB connection.
Due to the Modbus strings of code, the controller recognizes whether the bootloader is for a configuration, or
firmware update.
In order for the Centurion configurable controller to enter boot loader mode, the jumpers are removed during
power up (power cycled). The C3-3 Display and third party HMI devices will not receive a response to polls on
Port 1 while the boot loader is active.
Power on the Centurion must be cycled with the jumper installed to resume normal operation, or run mode.
7.2.2 Downlooading Configurations Via C3-3 Display
All configuration downloads will use a baud rate of 9600. The
Com 1 selection will use the hardware setup of the current
configuration. The Com 2 selection is a fixed hardware setup
for RS485. Selecting USB for configuration download con-
nects the USB adapter to Com 2 internally.
TM
C
CONFIRATION DOWNLOAD
___________________________________
COM 1 CONFIG DOWNLOAD
COM 2 CONFIG DOWNLOAD
USB CONFIG DOWNLOAD
FIRMWARE DOWNLOAD
All normal communication with the controller is stopped while
in download mode.
___________________________________
NO
___________________________________
The display will indicate the transfer is complete by displaying 100%.
▼▲
ENTER-EDIT
Special 35 Jump Code
In the case that no configuration has been downloaded, or a
password has been lost, C3-3 Display allows a “Download Only”
password that will allow access to the download menu.
Download Only Screen
The password is set to a fixed value of 35.
CE-05171N page 38 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
7.2.3 Downloading Configurations Via MConfigPro Software
The Centurion makes it easy for a user to download a configuration through the MConfigPro software.
1.
From the Options menu of the MConfigPro software, choose the Options tab to identify the ports that the
users PC can detect, and select the appropriate port that the user’s PC will use to communicate with the
C3-3 Display or Centurion controller. Set the individual port parameters.
2.
Through the Tools menu the user may choose to upload, or download as needed.
7.2.4 Pass Through
During boot loader, the Centurion controller allows users to remain connected to both the PC and the C3-3
Display and update the two devices with a single connection.
During a download from the MConfigPro software, the user downloads to the C3-3 Display without entering
boot loader mode and upon transferring the message, the Centurion controller is directed to accept the mes-
sage through one port (Port 2) and pass it through another port (Port 1) directly to the C3-3 Display, as if the PC
and C3-3 Display were directly connected.
7.2.5 Downloading Firmware Updates to the C3-3 Display
Firmware updates for the C3-3 Display require a USB con-
TM
C
nection. While boot loader mode for the display is not
required for configuration downloads, it is required for
firmware updates.
FIRMWARE UPDATE MODE
POWER AND COM LINK
The bootloader can be entered by menu selection if the USB
cable is currently connected, otherwise the C3-3 Display will
MUST BE MAINTAINED
reset and restart the current application firmware. Optionally,
the bootloader can be entered by connecting the USB cable
and cycling power. (This method will leave the display blank
while in the bootloader.)
Firmware Download Screen
Upon entry to the bootloader, all communication to the con-
troller will stop. There is a red status LED below the USB con-
nector that will blink three times and then remain on while the
bootloader is active.
While a file is being transferred, the Com 2 transmit LED will
appear to be lit continuously. A successful download should
complete in approximately five minutes.
Special 35 Jump Code
C3-3 Display allows a “Download Only” password that will allow
access to the download menu. The password is set to a fixed
value of 35. Once at the Download Only screen on the C3-3
Display, the user will select to download a firmware update.
Super User Menu
Super users will use the super user menu to download
firmware updates.
All normal communication with the controller is stopped while
in download mode.
The display will indicate the transfer is complete by displaying 100%.
CE-05171N page 39 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
7.2.6 Error Messages
There may be occasion when an invalid configuration error might display because the configuration between the
Centurion controller and its devices are out of synch--that is to say the checksums do not match. In fact, the
invalid configuration screen will appear briefly after downloading configurations until comparisons are made.
Field testers may decide to ignore the message, if the user knows that the changes are not critical. The user may
direct the error message to be ignored through a setting at the super user (password protected) menu. At CONFIG
FAIL DISABLE, the user would select Yes to ignore the data mismatch.
The setting is temporary as once power is cycled on the Display, the error message will continue until
comparisons between the devices yield no configuration mismatch.
However, if the user knows of changes that might have resulted from changes made fine tuning in the field and
wants to synchronize the data, he may choose to do so and there are a couple of options available.
● A super user could choose to also download the configuration from the super user menu on C3-3
Display.
● A user who without access to the super user menu could activate the download through the Special
Jump Code 35.
This screen indicates that the controller is not responding to
poll requests. There are only two ways to exit this screen,
either by normal responses resuming or if the SETUP/ENTER
TM
C
key is pressed.
CONTROLLER COM FAIL!
This screen will be displayed when a configuration fault is
detected.
PRESS SETUP IF COM
Possible sources of the fault include a corrupt or missing con-
figuration in the display, a corrupt or missing configuration in
the controller or a mismatch of configurations in the display
and controller.
PORT SETTINGS NEED
TO BE MODIFIED.
Comm Fail Screen
Note that this error message does not always indicate a prob-
lem, but may only signify that initial comparisons between
devices do not match. This screen will appear briefly after
configuration downloads and may appear briefly after initial
communication is established until comparisons are com-
plete.
TM
C
INVALID CONFIGURATION
PRESS SETUP TO ACCESS
DOWNLOAD MENU
The fault can be resolved by downloading the proper configu-
ration to one or both devices.
Configuration Fault Screen
CE-05171N page 40 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
7.3 Modbus Protocol
The Centurion configurable controller was programmed with the Modbus protocol which is a system is based on
a “master” and “slave” relationship. With Modbus protocol, the master and slave are able to continue to com-
municate with each other through defined messages over a variety of network types. The master initiates the
queries or commands, and the slave responds to the query with a message or takes action based on the query.
In this case, the master is either MConfig (or another Modbus client software), or C3-3 Display, but never both
simultaneously as there can only ever be a single Modbus master.
The Centurion system communicates through Modbus using Remote Terminal Unit (RTU) transmission mode to
maximize data processing.
As with all numeric data defined within Modbus, the programming is limited to accepting integers (whole num-
bers only, no decimals). This is important whenever a decimal point is defined for analog inputs.
For example, for the controller to properly read “100.0” with an implied decimal point of 1, the user would need
to enter “1000” and 1000 would be stored in the appropriate Modbus register. From the C3-3 Display, the value
will be represented with a decimal in the fixed position.
For additional information, please refer to the Centurion Configurable Controller Programming Manual.
7.4 Features of Transferring Data in Modbus
Note that text visible in the MConfigPro software and on the C3-3 Display is not stored in the Centurion con-
troller. Except for the version description in the Version and Security dialog for each configuration file, descrip-
tions assigned in the configuration are not stored in the Centurion controller. Descriptions for various I/O and
processes are downloaded to the C3-3 Display and reside as a configuration in that device only. Configurations
of the C3-3 are one way only.
Parameter changes made in the C3-3 Display are actually communicated to the Centurion controller where the
logic resides. No changes made through the C3-3 Display affect the C3-3 Display configuration as the display
merely reads from, and writes to the Centurion main I/O module. As such, the display can write numeric para-
meters to the controller.
7.5 Modbus Register Address Listings
For a complete MODBUS address map, please refer to The Centurion MODBUS reference document.
CE-05171N page 41 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
8.0 Glossary
Analog Input
Terminals A18 to A29 are analog inputs on the C3-1 Centurion main I/O module. Accepts
voltage signals within the range of (0 to 5) VDC or (4 to 20) mA and are compared to con-
troller set points or events.
Boot loader
Means by which the Centurion controller communicates with C3-3 Display and MConfigPro
to receive and transfer new or updated configurations and firmware; and ensure data and
configuration synchronization.
Controller Set points
User defines normal operating range for the controller to optimize the equipment. Set
points can also define some other threshold, exception or event that may require action.
Multiple set points are often applied to a process and they may be manipulated as needed
to meet changing conditions.
Dead band
Digital Input
The user set range at which input may fluctuate without the controller taking any action.
The range may be fixed or variable.
Terminals 30 to 61 are the digital input channels. User selects whether digital input is nor-
mally open (N/O), or normally closed (N/C). Users may also associate these inputs with
transition times for indicating no-flow conditions on divider blocks.
Event
Defines the action required by the controller in response to any number of parameters.
Event actions range from simple alarm message to emergency shutdown (ESD).
Magnetic Pick Up
Maximum
Terminals 64 to 65 are for magnetic pick up.
Maximum of engineering applied scale to the Offset and Span.
Minimum of engineering applied scale to the Offset and Span.
Minimum
No-Flow
Designed to protect against compressor or engine failures, the controller monitors the cycle
time of lubrication system cycles and if that cycle time falls under a user assigned value, the
controller will activate a defined associated action.
Offset
User defined value to correct for known variance in the raw data.
In States, the first logical step in start up.
Panel Ready
Permissive
A process condition, (Digital Input or Analog Set point), that must be met in order for the
engine to start.
Signal
An electrical quantity of voltage or current that is used to represent or signify some other
physical quantity.
Span
The difference between the full scale output and the offset as raw data.
A time delay function to prevent premature start up.
Start Delay
State
Predefined parameter of logical steps needed to successfully start and maintain an engine.
Terminal Emulator Allows a user to modify the firmware to allow upload or download of a record to either the C3-3
display or the controller. Always download a configuration after a firmware change.
Thermocouple
A device for measuring temperature consisting of two dissimilar metals of high purity for an
accurate temperature/voltage relationship. User defines whether the calibration is J or K.
Terminals 1 to 17 are for thermocouple inputs.
CE-05171N page 42 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
9.0 Appendices
9.1 Back Panel LED Description
There are a total of seven (7) LED indicators on the back panel, labeled as follows:
(Port 1)
TX
RX
– Turned on while Port 1 is transmitting data.
– Turned on while Port 1 is receiving data.
(Port 2)
TX
RX
– Turned on while Port 2 is transmitting data.
– Turned on while Port 2 is receiving data.
USB LINK
– Turns on while there is a USB connection to a computer.
STAT 1
–Turns on for one half second and then turns off for one half second, repeating as long as there is a valid
configuration running.
Note: This indicator is not active while the bootloader is running.
STAT 2 – This LED is only active while the bootloader is running. It flashes briefly three times when the bootloader
starts up and then stays on until leaving the bootloader.
9.2 Controller Accuracies, and Tolerances
Refer to the Centurion Configurable Controller Specification Sheet for a detailed breakdown of specifications.
9.3 Restrictions on Numeric Values in Gage and PID Monitor Screens
Due to a combination of the limited space and the spirit of the design objectives, there are certain restrictions
imposed upon the formatted size of numbers in C3-3 Display screens.
● Positive numbers with no decimals can be displayed with up to four digits.
● Negative numbers are limited to three digits.
● Numbers of either sign with a decimal place are limited to three digits.
● Numbers with more than two decimal places will not be displayed at all, but will be replaced with dashes.
If a number with decimals is larger than the imposed limits, the display algorithm will attempt to adjust the precision
so as to display as many of the most significant digits as possible.
9.4 Set Up Sheet
Refer to The Centurion Configuration Worksheet for a detailed workbook to document field changes to configuration
parameters.
CE-05171N page 43 of 44
Download from Www.Somanuals.com. All Manuals Search And Download.
How To Order
Selecting a Centurion Configurable Controller C3 Series Model:
1. Specify one C3-1 Main I/O Module from Table A
Table A: C3-1 Main module Options
Model
C3-1
C3-1-A
Specifications
no analog outputs
two analog outputs
Main I/O Module
Model: C3-1
2. Specify one (optional) C3-2 Expansion I/O Module
Expansion I/O Module
Model: C3-2
(optional)
The minimum system requirements:
C3-1 Main I/O Module
3. Specify one (optional) C3-3 Display Module
Display capable of Modbus communications
The Murphy C3-3 Display Module is a highly integrated
HMI for use with the C3 Series system and is
recommended for most customers.
Display Module
Model: C3-3
(optional)
Some systems may require additional I/O which is
available on the C3-2 Expansion I/O Module.*
* Only one C3-2 Expansion I/O Module can be used with each C3 System.
Accessories
Configuration Software
MConfig Pro - Configuration software for modifying sequence of operation, set points, timers,
faults, and *displays for Centurion. Includes file transfer utilities for configuration
and firmware upgrades.
* Display configuration and other settings for display are only for use with the C3-3 Display Module
Replacement Parts and Assemblies
C3-1 Plug Kit
C3-2 Plug Kit
C3-3 Plug Kit
Choke
(00000504)
(00000505)
(00000543)
(50000774)
Printed Replacement Terminal Plugs for Centurion (C3-1) Main I/O Module
Printed Replacement Terminal Plugs for Centurion (C3-2) Expansion I/O Module
Printed Replacement Terminal Plugs for Centurion (C3-3) Display Module
Ignition Noise (Choke) Filter
CONTROL S YS TEM S & S ERVICES DIVIS ION
P.O. Box 1819; Rosenberg, Texas 77471; USA
+1 281 633 4500 fax +1 281 633 4588
e-mail sales@fwmurphy.com
FRAN K W . M URP HY, LTD.
Church Rd.; Laverstock, Salisbury SP1 1QZ; U.K.
+44 1722 410055 fax +44 1722 410088
e-mail sales@fwmurphy.co.uk
www.fwmurphy.co.uk
FW Murphy
P.O. Box 470248
Tulsa, Oklahoma 74147 USA
+1 918 317 4100 fax +1 918 317 4266
e-mail sales@fwmurphy.com
M URP HY DE M EXICO, S . A. DE C. V.
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje
San Luis Potosí, S.L.P.; México 78384
+52 444 8206264 fax +52 444 8206336
Villahermosa Office +52 993 3162117
e-mail ventas@murphymex.com.mx
Printed in U.S.A.
w w w . f w m u r p h y . c o m
www.murphymex.com.mx
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.
CE-05171N page 44 of 44