M011101
R
Issue 6, revised 06/99
The Generator Controls Division of
Catalogue section 75
(MS5258)
AUTOSTART 705 (AS705S series)
PROGRAMMABLE GENERATOR CONTROLLER
The Autostart 705 provides the control features for the
automatic or manual starting, load transfer and shutdown of
a standby diesel generator or pump. The AS705 is a micro-
processor based controller, giving full programmability of
timers, trip levels and control options, with front facia LEDs
for the indication of generator status and faults.
Key features
·
·
·
·
Automatic or manual operation, selected by rotary switch
(key-switch available as an option).
17 LED status and fault indicators, including 5 LEDs
for custom programming and labelling
RS232 communications link for engine monitoring,
control and Autostart programming from local PC
Comprehensive fault protection and alarm system:–
low oil pressure, high engine temperature, overspeed,
underspeed, charge fail, emergency stop, start fail, high
and low battery voltage, 3 programmable fault inputs.
Product Specification
Power supply:
·
·
·
6 programmable outputs, allowing remote signalling
and control of over 30 different functions.
Operating voltage: steady state range
crank brown-out
Current consumption
5 – 40 V DC continuous
to 0V for <= 100 mSec
typically 150 mA
Pin compatibility with Autostart 710 and Keystart 9700
ranges, allowing standardisation of panel wiring.
Inputs:
96 x 96mm DIN standard, front panel mounted case
DC inputs (inputs 1 - 5, remote start)
positive input voltage range
negative input voltage range
Generator AC input:-
Operation
80% to 100% of battery +ve
–1V to +2V w.r.t. battery –ve
Autostart’s operating mode is selected by use of its
3 position front facia switch:–
operating voltage range
frequency measurement range
Magnetic pickup:-
operating voltage range
frequency measurement range
90 – 300 V AC rms
0 – 99 Hz.
Off/reset. Disables the engine and resets a
latched fault condition.
Automatic start-up, load transfer and return to
standby in response to a mains fail or remote
start condition, with full fault protection.
7 – 80 V AC rms
0 to 10 kHz
Outputs:
(all ratings for resistive load)
Manual start and stop of the generator, either
immediately on selecting manual mode or by
use of remote push button switches.
Start and fuel relays
+ ve DC (switched SPNO contact)
rated 16A max. @ 24V DC
– ve DC (open collector transistor)
rated 250mA max. @ 33 VDC
– ve DC (switched SPNO contact)
rated 5A max. @ 24V DC
Programmable outputs 1 – 3
Programmable output 4
Green and amber LEDs around the switch indicate the
selection of Auto and Manual modes. On keyswitch
versions, the key is common to all units and may be
removed in the Off and Auto positions only.
Programmable output 5
(default setting: Common Alarm)
Programmable output 6
(default setting: Gen. contactor)
Auto & Manual outputs
+ ve DC (switched SPNO contact)
rated 5A max. @ 24V DC
Control Outputs
The following are provided:-
volt free SPNO contacts
rated 5A max. @ 240V AC
+ ve DC, 250mA max.
· Single pole, switched +ve relay outputs for the control
of engine fuel and starter motor circuits.
· Switched +ve outputs for signalling auto and manual
Off/reset output
– ve DC, 250mA max.
modes, plus a –ve DC output for Off/reset.
Physical:
· 6 function programmable outputs (see overleaf).
Fault Protection and Alarm System
Overall dimensions (W x H x D)
Panel cut-out size
Weight
Operating ambient temperature
Case sealing
96 x 96 x 162 mm
DIN standard 92 x 92 mm
approx. 650 g
In Auto or Manual modes, Autostart will shut down and latch
out the generator on detection of low oil pressure, high
engine temperature, overspeed, start fail or emergency
stop faults. The Autostart may also be set up to shut down
the generator on low generator frequency or speed.
–10 to +55 oC
IP22
3 additional inputs may be used with remote fault switches
(giving a ‘shutdown’ or ‘warning’ response), or as control
inputs with remote contacts or panel switches (see overleaf).
In order to consistently bring you the highest quality,
full featured products, we reserve the right to change our
specifications and designs at any time.
Non-latching, 'warning only' alarms are fitted for high and
low battery volts, charge fail and mag. pickup fail conditions.
Download from Www.Somanuals.com. All Manuals Search And Download.
|