MGE UPS Systems Power Supply EX 11 RT 31 User Manual

MGE UPS SYSTEMS  
Comet  
EX 5 RT 3:1  
EX 7 RT 3:1  
EX 11 RT 3:1  
Installation and user  
manual  
R
E
D
I
V
O
R
P
R
E
W
O
P
E
L
B
I
T
P
U
R
R
E
T
N
I
N
U
E
H
T
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
1. Presentation  
1.1 Standard configurations .............................................................................................................. 5  
Tower configuration ......................................................................................................................... 5  
Rack configuration .......................................................................................................................... 5  
1.2 Rear panels.................................................................................................................................... 6  
Power module Comet EX 5 RT / EX 7 RT / EX 11 RT .................................................................... 6  
Battery module Comet EXB 7 RT / EXB 11 RT............................................................................... 6  
1.3 Display and control panel ............................................................................................................ 7  
1.4 Options .......................................................................................................................................... 7  
Rack mounting kits.......................................................................................................................... 7  
Transformer for galvanic isolation or earthing arrangement change .............................................. 8  
Battery extensions for UPS backup times up to 60 minutes ........................................................... 9  
CLA module (Long backup time charger) for backup times from 2 to 8 hours ................................ 9  
Modules integration system .......................................................................................................... 10  
Battery module with Remote Emergency Power Off function (REPO) ......................................... 10  
Battery extension cable (1,8 m / 6 ft) ............................................................................................ 10  
2. Installation  
2.1 Unpacking and parts check ....................................................................................................... 11  
Power module ............................................................................................................................... 11  
Battery module .............................................................................................................................. 11  
2.2 Installation in tower configuration ............................................................................................ 12  
2.3 Installation in rack configuration .............................................................................................. 13  
Adjustment of the orientation of the logo and control panels ........................................................ 13  
Battery module rack mounting (optional rail required) .................................................................. 13  
Power or battery module rack mounting (optional rail required) ................................................... 14  
2.4 Communication ports ................................................................................................................. 16  
Connection to the RS232 communication port ............................................................................. 16  
Connection to the communications port by relays ........................................................................ 16  
Remote Power Off communication port ........................................................................................ 17  
Installation of communication cards (optional, standard with the Network Pack version)............. 17  
2.5 Installation depending on the system earthing arrangement (SEA) ...................................... 18  
UPS with common Normal and Bypass AC inputs........................................................................ 18  
UPS with separate Normal and Bypass AC inputs ....................................................................... 18  
UPS with separate Normal and Bypass AC inputs, supplied by separate sources....................... 19  
Frequency converter (without Bypass AC input)........................................................................... 19  
Hot standby ................................................................................................................................... 19  
2.6 Required protective devices and cable cross-sections .......................................................... 20  
Recommended upstream protection ............................................................................................. 20  
Recommended downstream protection ........................................................................................ 20  
Required cable cross-section........................................................................................................ 20  
2.7 Connections of input/output power cables .............................................................................. 21  
UPS with common Normal and Bypass AC sources..................................................................... 21  
UPS with separate Normal and Bypass AC sources .................................................................... 22  
Frequency converter ..................................................................................................................... 23  
Connection of battery cables ........................................................................................................ 24  
Connection of galvanic isolation transformer ................................................................................ 24  
Connection of CLA module ........................................................................................................... 25  
34007724EN/AA - Page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
3. Operation  
3.1 Initial start up .............................................................................................................................. 26  
UPS personalisation ..................................................................................................................... 26  
Accessing personalisation with front panel buttons ...................................................................... 26  
Access to the personalisation through external software.............................................................. 27  
3.2 Final start up sequence .............................................................................................................. 27  
3.3 Operating modes ........................................................................................................................ 28  
Normal (double conversion) mode ................................................................................................ 28  
Eco mode ...................................................................................................................................... 28  
3.4 Operation on battery power ....................................................................................................... 29  
Transfer to battery power .............................................................................................................. 29  
Threshold for the low-battery warning........................................................................................... 29  
End of backup time ....................................................................................................................... 29  
3.5 Return of Normal AC source ...................................................................................................... 29  
3.6 Shut down.................................................................................................................................... 30  
4. Maintenance  
4.1 Troubleshooting .......................................................................................................................... 31  
4.2 Hot-swapping the power module .............................................................................................. 32  
Disconnecting the power module .................................................................................................. 32  
Reconnecting the power module .................................................................................................. 33  
4.3 Hot-swapping the battery module ............................................................................................. 33  
Disconnecting the battery module................................................................................................. 33  
Reconnecting the battery module ................................................................................................. 33  
4.4 Training center ............................................................................................................................ 34  
5. Appendices  
5.1 Technical specifications............................................................................................................. 35  
Electrical characteristics ............................................................................................................... 35  
Thermal characteristics ................................................................................................................. 38  
5.2 Glossary....................................................................................................................................... 38  
Page 4 - 34007724EN/AA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Presentation  
1.1 Standard configurations  
Tower configuration  
Dimensions in mm/inches  
(H x W x D)  
Comet EX 5 RT  
444 x 131 x 635  
Comet EX 7 RT  
Comet EX 11 RT  
Comet EXB 7 RT  
Comet EXB 11 RT  
17.49" x 5.16" x 25"  
T
R
B
X
E
T
Weight in kg/lbs  
R
1
1
X
E
Comet EX 5 RT  
Comet EX 7 RT  
22.5 / 49.6  
N
O
F
F
O
Comet EX 11 RT  
Comet EXB 7 RT  
Comet EXB 11 RT  
27.5 / 60.6  
64.5 / 142  
68.5 / 151  
m
co  
s.  
up  
ge  
.m  
w
w
w
Battery module  
m
co  
s.  
up  
ge  
.m  
w
w
w
(Comet EXB 7 RT / EXB 11 RT)  
Power module  
(Comet EX 5 RT / EX 7 RT / EX11 RT)  
Rack configuration  
Power module (Comet EX 5 RT / EX 7 RT / EX11 RT)  
Dimensions in mm/inches  
(H x W x D)  
Comet EX 5 RT  
Comet EX 7 RT  
Comet EX 11 RT  
Comet EXB 7 RT  
Comet EXB 11 RT  
131 (3U) x 444 x 635  
5.16" (3U) x 17.49" x 25"  
Weight in kg/lbs  
T
R
1
1
X
E
Comet EX 5 RT  
Comet EX 7 RT  
22.5 / 49.6  
ON  
F
Comet EX 11 RT  
Comet EXB 7 RT  
Comet EXB 11 RT  
27.5 / 60.6  
64.5 / 142  
68.5 / 151  
OF  
om  
s.c  
up  
ge  
w.m  
ww  
T
R
B
X
E
om  
s.c  
up  
ge  
w.m  
ww  
Battery module  
(Comet EXB 7 RT / EXB 11 RT)  
34007724EN/AA - Page 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Presentation  
1.2 Rear panels  
Power module Comet EX 5 RT / EX 7 RT / EX 11 RT  
Slot for communication cards.  
1
2
1
Communication port by relays.  
2
3
4
5
Remote Emergency Power Off communication port (REPO).  
Connectors for automatic detection of battery module(s).  
RS232 communications port.  
3
4
5
6
Battery module connectors (to the UPS or to other battery  
modules).  
6
7
7
8
Manual Bypass switch.  
Output terminal block.  
9
Normal AC source circuit-breaker.  
Normal AC source terminal block.  
Bypass AC source terminal block.  
10  
9
10  
11  
8
11  
Battery module Comet EXB 7 RT / EXB 11 RT  
Connectors for automatic detection of battery module(s).  
4
6
Battery module connectors (to the UPS or to other battery  
modules).  
12 Battery circuit breaker.  
4
6
12  
Page 6 - 34007724EN/AA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Presentation  
1.3 Display and control panel  
13  
14  
15  
16  
Load protected LED.  
13  
14  
Operation on battery LED.  
E X 1 1 R T 3:1  
15 Operation on bypass LED.  
Fault LED.  
16  
17  
Alphanumeric display.  
UPS OFF button.  
18  
17  
LOAD LEVEL  
4 kW / 5 kVA  
19 20  
Function buttons (scroll up / scroll  
down).  
21 UPS ON button (or function button in  
OFF  
ON  
personalisation mode).  
18  
19  
20  
21  
1.4 Options  
Rack mounting kits  
Telescopic rails for Power module mounting in 19" enclosure with mounting hardware  
(Part number 68001)  
Ear hangup.  
22  
23  
22  
Rear bracket system for transportation.  
23  
24  
24  
Telescopic rails, 639 mm to 1005 mm  
length (27.36" to 39.96").  
25  
25 Input/Output box bracket system.  
Telescopic rails for Battery module mounting in 19" enclosure with mounting hardware  
(Part number 68002)  
Ear hangup.  
22  
23  
22  
Rear bracket system for transportation.  
23  
25  
24  
Telescopic rails, 639 mm to 1005 mm  
length (27.36" to 39.96").  
34007724EN/AA - Page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Presentation  
Transformer for galvanic isolation or earthing arrangement change  
(Part number 68003)  
This module is necessary either when a downstream neutral system from the UPS upstream is required, or when a  
different power source connects the automatic bypass for higher availability.  
er  
rm  
fo  
ns  
ra  
T
T
R
X
E
Example of EX RT transformer connected upstream for Comet EX RT galvanic isolation  
Battery module (Comet EXB RT)  
Power module  
(Comet EX 5 RT / EX 7 RT / EX 11 RT)  
Transformer module (Comet EX RT)  
Normal AC input  
UPS output to load  
Bypass AC input  
Page 8 - 34007724EN/AA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Presentation  
Battery extensions for UPS backup times up to 60 minutes (at full load)  
Comet EX RT offers a standard backup time of 5/9 minutes at full load.  
To increase backup time, it is possible to connect Comet EXB 7 RT / EXB 11 RT modules to the UPSs.  
Battery extensions for Comet EX 5 RT, Comet EX 7 RT or Comet EX 11 RT  
Comet EX 5/7 RT  
+ EXB 7 RT  
/
Comet EX 11 RT  
+ EXB 11 RT  
Comet  
EXB 7 RT  
/
Comet  
EXB 11 RT  
Comet  
EXB 7 RT  
/
Comet  
EXB 11 RT  
Comet  
EXB 7 RT  
/
Comet  
EXB 11 RT  
Comet  
EXB 7 RT  
/
Comet  
EXB 11 RT  
Comet  
EXB 7 RT  
/
Comet  
EXB 11 RT  
+
+
+
+
+
5 kVA:  
9 min  
7 min  
5 min  
26 min  
42 min  
60 min  
72 min  
87 min  
7 kVA:  
20 min  
14 min  
32 min  
22 min  
45 min  
30 min  
57 min  
42 min  
70 min  
53 min  
11 kVA:  
CLA module (Long backup time charger) for backup times from 2 to 8 hours  
(Part number 68004)  
Very long backup times, from 2 to 8 hours at full load, require a Comet EX RT CLA module.  
Comet  
Comet  
EX RT CLA  
EX 5 RT /  
EX 7 RT /  
EX 11 RT  
50A  
~
Battery backup time  
Recommended batteries for:  
Comet EX7 RT  
Comet EX11 RT  
100 Ah  
Comet EX5 RT  
2 hours  
4 hours  
8 hours  
50 Ah  
65 Ah  
100 Ah  
130 Ah  
200 Ah  
200 Ah  
260 Ah  
400 Ah  
Total battery voltage : 240 V DC (20 x 12V DC).  
The battery capacity must be set within the UPS (5 Ah increment possible, see UPS Personalisation section).  
34007724EN/AA - Page 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Presentation  
Modules integration system (Part number 68005)  
Modules integration system for extended  
backup time configurations to conveniently  
stack and secure up to 8 modules on the  
same cart (swivel wheels with brakes,  
leveling feet, seismic side panels, plates to  
lock modules and screws included).  
R
T
B
E
X
Transformer module  
Power module  
m
s.co  
eup  
.mg  
www  
R
T
1
1
E
X
ON  
OFF  
m
s.co  
eup  
.mg  
www  
R
R
R
R
T
T
T
T
E
E
E
E
X
X
X
X
B
m
s.co  
eup  
.mg  
www  
B
B
B
m
s.co  
eup  
.mg  
www  
m
s.co  
eup  
.mg  
www  
Batteries modules  
m
m
m
s.co  
s.co  
s.co  
eup  
eup  
eup  
.mg  
.mg  
.mg  
www  
www  
www  
R
B
T
E
X
R
B
T
E
X
Battery module with Remote Emergency Power Off function (REPO)  
Part number:  
EXB 7 RT EPO: 68079.  
EXB 11 RT EPO: 68119.  
12 Battery circuit breaker with Remote Emergency Power OFF shunt trip.  
Battery extension cable (1,8 m / 6 ft, Part number 68006)  
This extended battery cable will be used instead of the standard battery cable when battery modules are distant from each  
other (located in two different enclosures, for instance).  
Page 10 - 34007724EN/AA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
2.1 Unpacking and parts check  
Power module  
T
R
1
1
X
E
23  
22  
24  
30  
26  
31  
25  
IP=  
MAC=00E0D8FF855E  
Card Settings  
100  
10  
UPS  
data  
Reset  
1 2  
ON  
RS232 Download  
ETHERNET  
RS232  
66074  
Battery module  
T
R
B
X
E
28  
27  
29  
24  
32  
25  
22 Two sets of tower stands.  
27 Tower stand expanders.  
23 RS232 communications cable.  
28 Battery cable.  
Product documentation.  
Battery communication cable.  
24  
29  
30  
31  
25 Telescopic rails for rack enclosure with  
mounting hardware (optional, or standard with  
Network Pack version).  
Input/Output junction box (with 11 insulated ferrules).  
Network Management card (optional, or standard in Network  
Pack version).  
26 Solution-Pac power management suite CD-  
32 Bezel screw driver.  
ROM.  
Packaging must be destroyed according to waste management standards. Recycling icons are displayed for easy  
selection.  
A dangerous voltage is present inside the power module and the battery module. Any operations to be carried out  
on these modules must be done so by qualified staff.  
34007724EN/AA - Page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
2.2 Installation in tower configuration  
Use the tower stand template provided with the battery module.  
2
2
1
1
T
R
B
X
E
T
R
1
1
X
E
N
O
F
F
O
m
co  
s.  
up  
ge  
.m  
w
w
w
m
co  
s.  
up  
ge  
.m  
w
w
w
3
3
4
4
4
4
Follow steps 1 to 4 to adjust the tower stands for the upright position.  
Page 12 - 34007724EN/AA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
2.3 Installation in rack configuration  
We recommend to mount the battery module first, then mount the power module above the battery module.  
Adjustment of the orientation of the logo and control panels  
T
R
1
1
X
E
E
X
O
F
1
F
1
R
T
N
O
w
w
O
FF  
O
w
.
N
m
g
m
.co  
e
ps  
eu  
mg  
w.  
u
ww  
p
s
.
c
o
m
E
X
O
F
1
F
1
4
6
R
T
1
3
w
w
w
.
m
O
g
e
N
u
p
s
.
c
o
m
2
5
T
R
m
1
s.  
co  
1
up  
ge  
X
.m  
E
w
ww  
N
O
FF  
O
Battery module rack mounting (optional rails required, part number: 68002)  
The battery module is very heavy. To ease its rack integration, we strongly recommend to remove the battery trays as  
explained below:  
2
T
R
B
X
E
2
1
1
x 6  
1
3
3
4
4
34007724EN/AA - Page 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
5
6
Power or battery module rack mounting (optional rails required, part number: 68001)  
Follow steps 1 to 4 for rack mounting the UPS onto the rails.  
3
3
3
1
4
3
2
4
1
The rails and the necessary mounting hardware are supplied by MGE UPS SYSTEMS.  
Note for step 1: it is possible to adjust the position of both front mounting ears.  
Page 14 - 34007724EN/AA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
Rear bracket system (included with rail kits, part numbers 68001 and 68002)  
To be used if you need to move the rack  
enclosure with UPS already rack-mounted  
inside.  
1
1
3
2
2
Input/output junction box bracket system (included with power module rail kit, part number 68001)  
This bracket will maintain the Input/Output box at the rear of the rack enclosure when hot-swapping the power module.  
It will then be easier to slide the replacement module into the connectors of the Input/Output box.  
1
2
4
4
3
34007724EN/AA - Page 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
2.4 Communication ports  
Comet EX RT provides 3 communication methods that can be used simultaneously:  
The COM port provides RS232 communications using MGE UPS SYSTEMS SHUT protocol. Compatible with most power  
management software applications available into the enclosed Solution Pac CD-Rom.  
The output contact port is used for basic signaling or for protection of IT systems like IBM iSeries (formerly AS400) and  
more.  
The slot is compatible with any MGE UPS SYSTEMS communication card (check www.mgeups.com web site for the  
complete list of compatible cards).  
Connection to the RS 232 communication port  
1 - Connect the RS 232 23 communications  
cable to the serial port on the computer.  
23  
2 - Connect the other end of the  
communications cable 23 to the RS 232  
5
communications port on the UPS.  
The UPS can now communicate with various  
MGE UPS SYSTEMS power management  
application software. Please note that the  
configuration software is included with  
Personal Solution Pac for Windows.  
5
Connection to the communication port by relays 2  
Pin 1, 2: not used,  
Pin 3: Remote Power Off signal (5 to 27 V DC, 10 mA max),  
Pin 4: Operation on mains (not on battery),  
Pin 5: User common,  
5
4
3
2
1
9
8
7
6
Pin 6: Operation on automatic by-pass,  
Pin 7: Low battery,  
n.c. n.o.  
n.o.  
n.o.  
n.o.  
Pin 8: Load protected,  
Pin 9: Operation on battery.  
common  
n.o.: contact normally open.  
n.c.: contact normally closed.  
When the status is active, the contact between the common (Pin 5) and the relevant information pin is closed.  
Output relays specifications  
Voltage: 48 V DC max,  
Current: 2 A max,  
Power: 62,5 VA, 30 W.  
Example: for 48 V DC, Imax=625 mA  
Page 16 - 34007724EN/AA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
Remote Power Off communication port 3  
Used in conjunction with the optional EPO battery module, this port enables total isolation of all power sources connected  
to the UPS in case of emergency (the cable is not provided).  
Remote power off contact normally open  
Remote power off contact normally closed  
RJ11  
RJ11  
6 5 4 3 2 1  
6 5 4 3 2 1  
5 V DC to 27 V DC  
5 V DC to 27 V DC  
Signal:  
- activation voltage: 5 V DC to 27 V DC.  
- current: 10 mA max.  
Installation of communication cards (optional, standard with the Network Pack version)  
Communication card.  
It is not necessary to shut down the UPS to  
install the communication card:  
1
IP=  
MAC=00E0D8FF855E  
Card Settings  
100  
10  
1 - Remove the slot cover secured by two  
screws.  
UPS  
data  
Reset  
1
ON  
2
RS232 Download  
ETHERNET  
RS232  
66074  
2 - Insert the card  
1
into the slot.  
3 - Secure the card with both screws.  
34007724EN/AA - Page 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
2.5 Installation depending on the system earthing arrangement (SEA)  
Comet EX must be fed from a 3-phase source with neutral.  
UPS with common Normal and Bypass AC inputs  
Main low-  
11  
voltage  
switchboard  
(MLVS)  
Bypass AC  
Normal AC  
load  
10  
8
Change in SEA between upstream and downstream or galvanic isolation required  
Main low-  
Bypass AC  
voltage  
11  
switchboard  
(MLVS)  
load  
10  
8
Normal AC  
UPS with separate Normal and Bypass AC inputs  
Main low-  
voltage  
Bypass AC  
11  
switchboard  
(MLVS)  
(*)  
10  
8
load  
Normal AC  
Change in SEA between upstream and downstream or galvanic isolation required  
Main low-  
Bypass AC  
voltage  
11  
10  
switchboard  
(MLVS)  
(*)  
load  
8
Normal AC  
(*): The transformer is not necessary if:  
Normal and Bypass AC inputs are connected to the same source,  
and wires cross sections and wires lengths on Normal and Bypass inputs are identical,  
and upstream protection is provided by only one switch with RCD (residual current device) for Normal and Bypass inputs.  
Page 18 - 34007724EN/AA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
UPS with separate Normal and Bypass AC inputs, supplied by separate sources  
Bypass AC  
MLVS 1  
11  
load  
MLVS 2  
10  
8
Normal AC  
Bypass AC  
or  
MLVS 1  
MLVS 2  
11  
load  
10  
8
Normal AC  
Change in SEA between upstream and downstream or galvanic isolation required  
Bypass AC  
11  
MLVS 1  
load  
10  
8
MLVS 2  
Normal AC  
Frequency converter (without Bypass AC input)  
Configuration used when the frequency of the application differs from the Mains (Example: marine requirements).  
Main low-  
voltage  
11  
10  
switchboard  
(MLVS)  
8
load  
Normal AC  
Hot stand by  
Configuration used to provide full redundancy (N+1) to critical loads.  
Main low-  
Bypass AC  
voltage  
11  
10  
switchboard  
(MLVS)  
8
Normal AC  
(*)  
(see page 18)  
11  
10  
Normal AC  
load  
8
34007724EN/AA - Page 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
2.6 Required protective devices and cable cross-sections  
Recommended upstream protection  
UPS  
power  
rating  
Common AC inputs  
Upstream circuit-breaker  
Normal / Bypass AC sources  
Separate AC inputs  
Upstream circuit-breaker  
Upstream circuit-breaker  
Bypass AC source  
Normal AC source  
C curve - 32A  
5 kVA  
7 kVA  
D curve - 40A  
D curve - 40A  
D curve - 63A  
D curve - 40A  
D curve - 40A  
D curve - 63A  
C curve - 32A  
11 kVA  
C curve - 63A  
Note: see the simplified diagrams in the appendix for common or separate AC inputs, indicating the positions of the  
protection devices, the characteristics of the internal UPS fuses and UPS line currents under overload conditions.  
Recommended downstream protection  
The indicated protection ensures  
Downstream  
UPS power  
rating  
discrimination for each output circuit  
downstream of the UPS, whether supplied  
by the Normal or the Bypass AC source.  
If these recommendations are not followed,  
protection discrimination is not achieved and  
may result in a potential power interruption  
to the connected devices.  
circuit breaker  
Z curve - 10A  
C curve - 4A  
Z curve - 10A  
C curve - 4A  
Z curve - 10A  
C curve - 6A  
5 kVA  
7 kVA  
11 kVA  
Note: see the simplified diagrams in the appendix for common or separate AC inputs, indicating the positions of the  
protection devices, the characteristics of the internal UPS fuses and UPS line currents under overload conditions.  
Required cable cross-sections  
Terminal-block cable capacity: 10 mm2, solid or stranded wire (maximum 13 mm2 or AWG 6).  
Capacity for earthing conductor: 10 mm2, solid or stranded wire (maximum 13 mm2 or AWG 6).  
Page 20 - 34007724EN/AA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
2.7 Connections of input/output power cables  
This type of connection must be carried out by qualified electrical personnel.  
Before carrying out any connection, check that the battery circuit breaker 12 and that the upstream protection devices  
(Normal and Bypass AC sources) are open ("0").  
Comet EX RT UPS always comes from factory with Normal and Bypass AC inputs already connected together, using a  
bridge.  
Use included insulated ferrules with stranded wires.  
UPS with common Normal and Bypass AC sources  
To access the connection terminal blocks,  
see section 1.2 "Rear panel":  
1 - Remove the terminal block cover  
(5 screws),  
t
u
tp  
u
N
O
L
t
u
p
n  
s
s
a
p
y
B
2 - Insert the Normal AC cable through the  
cable gland,  
2
L
t
u
2
N
p
In  
r
e
fi  
ti  
c
e
R
1
L
1
L
2
L
3
L
1
N
3 - Connect the 5 wires to the Normal AC  
terminal block,  
1
1
Always connect the earthing  
wire first.  
1
1
1
4 - Insert the output cable to the load  
through the output cable gland,  
5 - Connect the 3 wires to the output  
terminal block,  
6 - Refit the terminal block cover and tighten  
the cable glands,  
t
u
tp  
N
u
O
L
u
p
s
s
a
p
y
B
2
L
7 - Secure the junction Input/Output box to  
the rear of the power module by means of  
the 3 screws.  
t
u
2
N
p
In  
r
e
fi  
ti  
5
c
e
R
1
L
1
L
2
L
3
L
1
N
4
2
3
t
u
tp  
u
N
O
L
t
u
p
s
s
a
p
y
B
2
L
t
u
2
N
p
In  
r
e
fi  
ti  
c
e
R
1
L
1
L
2
L
3
L
1
N
6
6
6
6
6
7
L
A
M
R
O
N
φ
7
6074  
CardSetings  
dta  
UPS  
7
HRNET  
10  
Rset  
ON  
12  
RS32Dwnload  
MAC=0DF85E  
IP=  
34007724EN/AA - Page 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
UPS with separate Normal and Bypass AC sources  
1 - Remove the terminal block cover  
(5 screws),  
2 - Remove the bridge connected between  
L2 and L1,  
t
u
tp  
u
N
O
L
In  
s
s
a
p
y
B
3 - Insert the Normal AC cable through the  
cable gland,  
2
L
t
u
p
2
N
In  
r
e
fi  
ti  
c
e
R
1
L
1
L
2
L
3
L
1
N
2
4 - Connect the 5 wires to the Normal AC  
terminal block,  
1
1
Always connect the earthing  
wire first.  
1
1
1
5 - Insert the Output cable to the load  
through the Output cable gland,  
6 - Connect the 3 wires to the output  
terminal block,  
7 - Insert the Bypass cable through the cable  
gland,  
t
u
tp  
N
u
O
L
6
p
In  
s
s
a
p
y
B
2
L
8 - Connect the 3 wires to the Bypass AC  
terminal block,  
t
u
p
2
N
In  
r
ie  
tif  
c
e
R
1
L
1
L
2
L
3
L
1
N
8
9 - Refit the terminal block cover and tighten  
the cable glands,  
5
10 - Secure the junction Input/Output box to  
the rear of the power module by means of  
the 3 screws.  
4
7
3
t
u
tp  
u
N
O
L
In  
s
s
a
p
y
B
2
L
t
u
2
N
p
In  
r
e
fi  
ti  
c
e
R
1
L
1
L
2
L
3
L
1
N
9
9
9
9
9
10  
L
A
M
R
O
N
φ
10  
10  
6074  
CardSetings  
dta  
UPS  
HRNET  
10  
Rset  
ON  
12  
RS32Dwnload  
MAC=0DF85E  
IP=  
Page 22 - 34007724EN/AA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
Frequency converter  
1 - Remove the terminal block cover  
(5 screws),  
2 - Remove the bridge connected between  
L2 and L1,  
t
u
tp  
u
N
O
L
3 - Insert the Normal AC cable through the  
cable gland,  
p
n  
s
s
a
p
y
B
2
L
t
u
2
N
p
In  
r
e
fi  
ti  
c
e
R
1
L
1
L
2
L
3
L
1
N
2
4 - Connect the 5 wires to the Normal AC  
terminal block,  
1
1
Always connect the earthing  
wire first.  
1
1
1
5 - Insert the Output cable suppling the load  
through the Output cable gland,  
6 - Connect the 3 wires to output terminal  
block,  
t
u
tp  
u
N
O
L
Do not connect anything to the  
Bypass AC terminal block,  
u
p
s
s
a
p
y
B
2
L
6
t
u
p
2
N
In  
r
e
fi  
ti  
c
e
R
1
L
1
L
2
L
3
L
1
N
7 - Refit the terminal block cover and tighten  
the cable glands,  
5
8 - Secure the junction Input/Output box to  
the rear of the power module by means of  
the 3 screws.  
4
3
t
u
tp  
u
N
O
L
p
In  
s
s
a
p
y
B
2
L
t
u
p
2
N
In  
r
e
fi  
ti  
c
e
R
1
L
1
L
2
L
3
L
1
N
7
7
7
7
7
8
L
A
M
R
O
N
φ
8
6074  
CardSetings  
dta  
UPS  
8
HRNET  
10  
Rset  
ON  
12  
RS32Dwnload  
MAC=0DF85E  
IP=  
34007724EN/AA - Page 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
Connection of battery cables  
1 - Check that the battery circuit breaker 12  
is OFF ("0" position),  
4
2 - Connect the battery power cable 28 to  
29  
the connectors  
modules,  
6
of the power and battery  
3 - Connect the battery detection cable 29  
to the connectors  
battery modules,  
4
of the power and  
28  
6
12  
Connection of galvanic isolation transformer  
INPUT  
N
L
OUTPUT  
N
L
Transformer Input  
Transformer Output  
Output cable cross-section (not provided): 10 mm2, solid or stranded wire (maximum 13 mm2 or AWG 6).  
Input cable cross-section (not provided): 10 mm2, solid or stranded wire (maximum 13 mm2 or AWG 6).  
Page 24 - 34007724EN/AA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
Connection of CLA module  
29  
28  
BATTERY  
AC INPUT  
_
+
N
L
To battery  
AC Input  
Connect the battery cable 28 (provided with the CLA module) between the power module and the CLA module.  
Connect the cable 29 (provided with the CLA module) between the power module and the CLA module.  
Connect the battery:  
Cable cross-section (not provided): 10 mm2, solid or stranded wire (maximum 13 mm2 or AWG 6).  
Use a circuit-breaker (curve B, 50 A) for cable protection.  
Connect the input cable of the CLA module to the AC input:  
AC input cable cross-section (not provided) : 2,5 mm2.  
Use a circuit-breaker (curve C, 10 A) for cable protection.  
34007724EN/AA - Page 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Operation  
3.1 Initial start up  
Check that the manual bypass switch  
7
is on Normal position.  
to the "I" position.  
15  
Set the normal AC source circuit-breaker  
9
Set the battery circuit breaker 12 to the "I" position.  
The load is powered via the bypass AC source, but not protected  
by the UPS.  
PRESS ON  
Batteries are recharging, an eight-hour recharge period is  
necessary to get full backup time.  
LED 15 is ON.  
TO START UPS  
UPS personalisation  
If specific settings are required, it is recommended to enter the UPS personnalisation mode at this stage.  
It is possible to enter this mode through the front panel buttons or the Personal Solution-Pac software for Windows  
included in the MGE UPS SYSTEMS Solution-Pac power management suite CD-ROM.  
Accessing personalisation with front panel buttons  
Press "scroll up" 19 and "scroll down" 20 function buttons together  
for more than 3 seconds.  
UPS SET UP  
Press the function button 20 placed under the ENT word to enter the  
set up mode and follow the LCD messages using the buttons now  
defined as select keys.  
EXIT  
ENT  
OFF  
ON  
19  
20  
Local settings  
Factory setting  
English  
Options  
French, Spanish, German, Italian.  
Function  
Language  
International format  
US format (MM-DD-YYYY/HH:MM AM/PM).  
Date / time format  
(DD-MM-YYYY/HH:MM)  
Time in France  
Quick beeps  
MM-DD-YYYY/HH:MM adjustable.  
Slow beeps.  
Date / time change  
Audible alarm  
Output features  
Factory setting  
230 Volts AC  
Disabled  
Options  
200/208/220/240/250  
Enabled  
Comments  
Function  
Output voltage  
Bypass AC source disabled.  
Frequency converter  
Output frequency  
Auto ranging  
50/60 Hz  
User selectable under frequency converter  
mode.  
Disabled  
Disabled  
Enabled  
Enabled  
See glossary.  
Eco mode  
N+1 redundancy  
Hot standby  
(See section 2.5 "Hot standby").  
Industrial  
I/T Network  
(*)  
(*)  
Operating mode  
If the Bypass AC source is  
out of tolerances  
If the Bypass AC source is  
inside tolerances  
Transfer on Bypass AC  
source  
10 ms  
10 to 200 ms  
Break time calibration during load transfer  
on Bypass AC source out of tolerances.  
Break time  
(by steps of 10 ms)  
102%  
50/70%  
Overload level  
(*) : - Select "I/T Network" and "AC Bypass within tolerance" for computer loads.  
- Select "Industrial" and "AC Bypass out of tolerance" in case of absolute need for service continuity (with potential  
10 ms break).  
Page 26 - 34007724EN/AA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Operation  
ON/OFF features  
Factory setting  
Disabled  
Options  
Comments  
Function  
Cold start  
Enabled  
Disabled  
Start on battery.  
Enabled  
Enables automatic restart of the system even  
if normal AC source is restored before the end  
of the shutdown sequence.  
Forced reboot  
Enabled  
Disabled  
Enabled  
Disabled  
Enabled  
Disabled  
UPS restarts automatically  
Automatic restart  
Sleep mode  
when normal AC source is restored.  
Automatic shudown on battery if output load  
level < 10%.  
Enables consideration of shutdown or restart  
orders from software to be authorized.  
UPS ON/OFF by software  
Battery features  
Function  
Battery test  
Options  
Factory setting  
Comments  
Every week  
20%  
No test / daily / monthly  
0 to 100%  
Low battery signal  
Run time choice  
1% increment.  
From 50 to 400 Ah  
UPS reads # of battery  
modules connected  
Requires Comet EX RT CLA if using options  
(see section 1.4 "Battery extensions").  
Battery deep discharge  
protection  
Disabled  
Enabled  
If disabled, lost of  
MGE UPS SYSTEMS warranty.  
Use EXIT key when set up is completed.  
These parameters are only adjustable if UPS is OFF.  
Access to the personalisation through external software  
Insert the Solution-Pac CD ROM in your CD drive.  
At the first Navigator Screen, select "Installation" and follow the instructions to install Personal Solution-Pac for  
Windows.  
If nothing appears, launch startup.exe  
Then go to "Advanced settings" and "UPS settings".  
Please note that the Linux/Unix/MacOS versions of Personal Solution-Pac do not include this feature.  
3.2 Final start up sequence  
Press the ON button more than 3 seconds.  
After UPS internal test sequence, the green LED 13 goes on.  
During the restart, if the Bypass AC source is out of tolerance, the UPS will generate an output 10 ms calibrated  
break.  
34007724EN/AA - Page 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Operation  
3.3 Operating modes  
Normal (double conversion) mode  
This is the standard operating mode, set by default in the factory.  
Two possible choices.  
13  
1 - Normal AC source available:  
LED 13 is ON.  
The load is protected by the UPS.  
LOAD LEVEL  
4 kW / 5 kVA  
Scroll up 19 and scroll down 20 function buttons allow you to read  
the UPS measurements (Normal AC source voltage, Bypass AC source  
voltage, operating mode, battery capacity and UPS Serial Number).  
OFF  
ON  
19  
14  
20  
21  
2 - Normal AC source not available:  
LED 13 flashes.  
13  
LED 14 is ON.  
The audible alarm sounds intermittently.  
The load is supplied by the UPS from battery power.  
BACKUP TIME  
10 minutes  
Do not operate the manual Bypass switch  
the normal mode.  
7
when the UPS is in  
OFF  
ON  
ECO mode  
The main advantage of the Eco mode (see glossary) is that it reduces  
the consumption of electrical power.  
13  
15  
Three possible choices:  
1 - Bypass AC source available:  
LEDs 13 and 15 are ON.  
The load is supplied in ECO mode.  
ECO MODE  
4 kW / 5 kVA  
13  
2 - Bypass AC source not available:  
LED 13 is ON.  
The audio alarm sounds intermittently.  
The load is automatically supplied in Normal mode via the Normal AC  
input.  
13  
14  
3 - Both Normal and Bypass AC sources not available or out of  
tolerance:  
LED 13 is ON.  
LED 14 is ON.  
The audio alarm sounds intermittently.  
The load is supplied by the UPS from battery power.  
The display indicates the battery remaining backup time.  
Page 28 - 34007724EN/AA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Operation  
3.4 Operation on battery power  
The load continues to be protected by the UPS when the Normal AC source is not available. Power is supplied by the  
battery.  
Transfer to battery power  
LED 13 is ON.  
13  
14  
LED 14 is ON.  
The audio alarm beeps every 10 seconds.  
The load is supplied by the battery.  
The display indicates the battery remaining backup time.  
BACKUP TIME  
10 minutes  
OFF  
ON  
Threshold for the low-battery warning  
LED 13 is ON.  
13  
14  
LED 14 flashes.  
The audio alarm beeps every 3 seconds.  
Low battery warning on display. There is very little remaining battery  
backup time. Close all applications because UPS automatic shutdown is  
impending.  
BACKUP TIME  
2 minutes  
OFF  
ON  
End of backup time  
LED 13 and 14 are OFF.  
13  
14  
15  
The audio alarm is stopped.  
The load is transferred to the Bypass AC source if available. In this  
case, the LED 15 is ON.  
STOP  
END BACKUP TIME  
OFF  
ON  
3.5 Return of Normal AC source  
After an outage, the UPS restarts automatically when AC power is restored (unless this function has been disabled via UPS  
personalisation).  
34007724EN/AA - Page 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Operation  
3.6 Shut down  
15  
1 - Press the OFF button 18 more than 3 seconds.  
The load is no longer protected by the UPS. It is powered  
via the bypass AC source. If the UPS is set in frequency  
converter mode, the load will not be powered.  
If the bypass AC source is out of tolerance, the UPS will  
generate a 10 ms output calibrated break.  
LOAD LEVEL  
4 kW / 5 kVA  
2 - Set the battery circuit breaker(s) 12 to the "0" position.  
OFF  
ON  
3 - Set the Normal AC source circuit-breaker  
9
to the "0" position.  
4 - For a full shutdown of UPS and connected load, the upstream circuit  
breaker (not included) should be set to the "0" position.  
18  
12  
9
Page 30 - 34007724EN/AA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Maintenance  
4.1 Troubleshooting  
If any of LEDs 15 or 16 is on, there is an operating anomaly or an alarm.  
Use "scroll up" or "scroll down" function button to reset the audible alarm.  
Troubleshooting not requiring MGE UPS SYSTEMS after-sales support:  
Signification  
Correction  
Indication  
AC source is not connected  
to the correct terminals.  
Rewire correctly the normal AC source.  
Led 15 is on,  
the alphanumeric display shows:  
BAD CONNECTION  
REWIRE AC NORMAL  
Load supplied by bypass AC source.  
Push the ON button for more than 3  
seconds.  
Led 15 is on,  
the alphanumeric display shows:  
LOAD LEVEL  
Xx kW / XX KVA  
UPS overload.  
Check the power drawn by the equipment  
and disconnect any non-priority devices.  
Led 15 is on*,  
the alphanumeric display shows:  
THERMAL OVERLOAD  
1XX%  
Short circuit conditions on output devices.  
Check if any device is shorted or failed.  
Led 16 is on,  
the alphanumeric display shows:  
CURRENT OVERLOAD  
Junction of Input/Output box  
not correctly screwed.  
Check if the junction Input/Output box is  
correctly screwed (rear panel).  
Audible alarm is on,  
the alphanumeric display shows:  
I/O BOX REMOVED  
(*) : if bypass AC source available.  
Troubleshooting requiring MGE UPS SYSTEMS after-sales support:  
Signification  
Correction  
Indication  
Internal fault  
Follow the UPS replacement procedure (see  
section 4.3).  
Leds 15 * and 16 are on  
and audible alarm is on.  
The alphanumeric display shows:  
xxx FAULT  
and transfer of load  
on bypass AC source.  
Call the after sales support department.  
Battery fault during the battery test.  
Follow the battery replacement procedure  
(see section 4.3).  
Led 15 is on* and audible alarm is on.  
the alphanumeric display shows:  
BATTERY FAULT  
Call the after sales support department.  
Static switch failure.  
Follow the UPS replacement procedure (see  
section 4.3).  
Led 15 is on,  
the alphanumeric display shows:  
SHUTDOWN  
Call the after sales support department.  
STATIC SW FAILED  
UPS out of warranty.  
To extend warranty period or for UPS  
maintenance, call the local after sales  
section**.  
Audible alarm is on, and the alphanumeric  
display shows:  
END OF WARRANTY  
Batteries may have exceeded there rated life Call the local after sales support:  
period. Battery capacity is severely reduced. www.mgeups.com, "Contact Us" section**.  
Audible alarm is on, and the alphanumeric  
display shows:  
BATTERY CHECK  
(*): if bypass AC source is available.  
(**): to reset this alarm permanently, press both function buttons 19 and 20 for more than 3 seconds and access the  
LCM Setup menu.  
34007724EN/AA - Page 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Maintenance  
4.2 Hot-swapping the power module  
This operation can be performed without interrupting the load.  
Disconnecting the power module  
Stop the UPS with the OFF button 18 (press more than 3 seconds).  
Check if UPS is on bypass AC source:  
15  
led 15 is on (If led 15 is not on, do not turn the manual bypass and  
call the after sales support department).  
Turn the manual bypass switch  
7
to the BYPASS position.  
Switch the battery circuit breaker (s) 12 to the "0" position.  
XXX FAULT  
1CXXXXXXX  
Switch the Normal AC source circuit-breaker  
9
to the "0" position and  
wait 30 seconds.  
OFF  
ON  
Remove the three fixing screws to free the junction Input/Output box.  
Disconnect the battery cables 28 and 29 from the power module.  
The power module can be replaced.  
The connected equipment is powered by the Bypass AC source.  
18  
Tower configuration  
s
g
in  
tt  
e
S
rd  
a
C
S
ta  
P
U
d
0
1
E
a
5
0
0
1
5
8
F
4
7
F
8
0
6
=
0
E
D
6
IP  
0
0
=
C
2
3
A
2
S
R
M
t
e
s
e
R
2
N
T
E
1
O
N
R
HE  
T
E
d
a
lo  
n
w
o
D
2
3
2
S
R
29  
28  
7
φ
P
B
A
Y
S
S
9
12  
Rack configuration  
Page 32 - 34007724EN/AA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Maintenance  
Reconnecting the power module  
Secure the Input/Output junction box using the three screws.  
13  
15  
Reconnect the battery cables 28 and 29 to the power module.  
Switch the battery circuit breaker(s) 12 to the "I" position.  
Switch the Normal AC source circuit-breaker  
9
to the "I" position.  
Turn the manual bypass switch from the BYPASS to the NORMAL  
position.  
LOAD LEVEL  
4 kW / 5 kVA  
Check that the led 15 is on.  
Follow initial start up sequence (see section 3.1) in order to personalize  
the UPS.  
OFF  
ON  
Push the ON button 21 for more than 3 seconds.  
The green led 13 is on, and the connected equipment is now  
protected by the UPS.  
21  
4.3 Hot-swapping the battery module  
Disconnecting the battery module  
Switch the battery circuit breaker(s) 12 to the "0" position.  
29  
29  
28  
Disconnect the battery cables 28 and 29 from the power module.  
The battery module can be replaced. The connected equipment is  
powered by the UPS.  
It is also possible to replace battery trays instead of battery module.  
Contact your nearest after sales support service.  
To remove battery trays:  
First, switch the battery circuit breaker(s) to the "0" position.  
See section 2.3 and follow instructions to remove battery trays.  
28  
12  
Reconnecting the battery module  
Reconnect the battery cables 28 and 29 to the power module.  
Switch the battery circuit breaker(s) 12 to the "I" position.  
To reconnect battery trays:  
See section 2.3 and follow the reverse instructions.  
When battery module front panel is closed, connect the battery cables  
28 and 29 to the power module.  
Switch the battery circuit breaker(s) 12 to the "I" position.  
34007724EN/AA - Page 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Maintenance  
4.4 Training Center  
To allow you to use MGE UPS SYSTEMS products effectively and carry out basic maintenance, we offer a complete range  
of technical training courses in English and French.  
50 Hz Training Center:  
MGE UPS SYSTEMS  
140, Avenue Jean Kuntzmann  
Zirst - Montbonnot St Martin  
38334 - St Ismier Cedex - FRANCE  
Tel: (33) (0)4 76 18 34 14  
Fax: (33) (0)4 76 18 45 21  
On-line catalogue and registration.  
60 Hz Training Center:  
MGE UPS SYSTEMS  
1660, Scenic Avenue  
Costa Mesa, CA 92626, USA  
Tel: (1) 714 557 1637  
Fax: (1) 714 437 9072  
Page 34 - 34007724EN/AA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Appendices  
5.1 Technical specifications  
Electrical characteristics  
I/T network and industrial operating modes  
Industrial mode  
I/T network mode  
Same as I/T network mode, but the UPS does not  
return to normal mode if overload released.  
Load is transfered to Bypass AC source.  
Overload, and Bypass  
AC source in tolerance.  
UPS returns to normal mode if overload released.  
The UPS shuts down and load is not transfered to  
Load is transfered to Bypass AC source with 10  
Overload, and Bypass  
milliseconds output break. The UPS does not return to Bypass AC source.  
normal mode if overload released.  
AC source not in tolerance.  
Load is transfered to Bypass AC source, the UPS  
returns to normal mode if the short circuit is released  
The load remains powered by the UPS.  
The UPS shuts down after 3 minutes if the short  
Output short circuit and  
Bypass AC source in  
tolerance.  
by downstream circuit breaker action (see section 2.6). circuit remains.  
The load is transfered to Bypass AC source with 10  
The load remains powered by the UPS. The UPS  
Output short circuit and  
Bypass AC source not in  
tolerance.  
milliseconds output break. The UPS does not return to shuts down after 3 minutes if the short circuit  
normal mode if the short circuit is released by  
remains.  
downstream circuit breaker action (see section 2.6).  
Selection of protection devices  
UPS unit with common Normal and Bypass AC inputs  
11  
Upstream  
circuit breaker  
(not supplied)  
Downstream  
circuit breaker  
(not supplied)  
Normal AC  
source circuit Input  
Bypass AC  
Normal AC  
Output  
fuse  
breaker  
fuse  
10  
8
9
UPS unit with separate Normal and Bypass AC inputs  
Upstream  
circuit breaker  
(not supplied)  
Bypass AC  
11  
Upstream  
circuit breaker  
(not supplied)  
Downstream  
circuit breaker  
(not supplied)  
Normal AC  
source circuit  
breaker  
Input  
fuse  
Output  
fuse  
Normal AC  
10  
8
9
When sizing the upstream circuit breakers, the parameters presented below must be taken into account:  
Line current values  
Continuous current at 320 Volts  
and overload = 110 %  
Input fuse rating  
Output fuse rating  
Continuous current  
at 400/320 Volts and  
nominal load  
UPS  
power rating  
limited to 2 minutes  
11 A  
12 A  
21 A  
25 A  
25 A  
30 A  
80 A  
80 A  
9/10 A  
10/11 A  
15/19 A  
5 kVA  
7 kVA  
100 A  
11 kVA  
Discrimination of upstream/downstream protections mentioned in paragraph 2.6 is achieved for a 30 m cable length and  
10 mm2 cross section.  
Circuit breaker capacity must be selected according to the installation, length and cross section of cables.  
34007724EN/AA - Page 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Appendices  
Time/current curves for UPS Normal AC source circuit-breaker  
t (s)  
103  
102  
10  
1
-
1
2
10  
-
10  
I / In  
-
3
10  
0
1
2
3
4
5
6
7
8
9
10  
1,25 1,5  
Time/current curves for UPS input and output fuses  
t (s)  
t (s)  
104  
103  
103  
102  
102  
10  
10  
1
1
-
-
1
2
10  
-
-
1
2
10  
I (A)  
103  
10  
10  
102  
Intput fuses of  
Comet EX 11 RT : 30 A  
Intput fuses of  
10  
Comet EX 5 RT : 25 A  
Comet EX 7 RT : 25 A  
-
-
3
4
10  
I (A)  
104  
10  
10  
102  
103  
Output fuses of  
Comet EX 11 RT : 100 A  
Output fuses of  
Comet EX 5 RT : 80 A  
Comet EX 7 RT : 80 A  
Page 36 - 34007724EN/AA  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Appendices  
UPS Input / output characteristics  
Source  
Frequency  
Voltage  
320 to 465 Volts AC  
187 to 264 Volts AC*  
Normal AC source  
Bypass AC source  
Load output  
40 to 70 Hz  
48 to 52 Hz**  
50/60 Hz autoranging  
230 Volts AC (200/208/220/240/250 V are  
possible values)  
(or frequency converter)  
(*): depends on output voltage setting, can be modified by software.  
(**): set to +/- 4% by default, (1,2,4,8 are possible values), can be modified by software.  
Power supplied as a function of input voltage  
P/Pn  
100%  
70%  
U
250V 320V  
465V  
Permissible UPS overloads as a function of time  
P/Pn  
1.5  
1.25  
1.1  
1.02  
0.5s  
t
30s  
60s  
120s  
Short-circuit current provided by the UPS in Normal or Batterie mode  
Comet EX 5 RT : 110 A for 80 ms.  
Comet EX 7 RT : 110 A for 80 ms.  
Comet EX 11 RT : 150 A for 80 ms.  
Comet EX Transformer  
Nominal power  
11 kVA  
Nominal current  
63 A  
Input voltage  
160-280 Volts AC  
7 Volts at nominal load  
50/60 Hz (+/-10%)  
3.75 kV / 5 M ohms  
From 0° to +40°C  
95%  
Voltage drop  
Frequency  
Isolation (EN 61558-1-2-4)  
Operating temperature  
Max. operating rel. humidity  
Derating / altitude  
Dimensions HxWxD (tower)  
Dimensions HxWxD (rack 3U)  
Weight  
Pn-10% > 1000 m  
444 x 131 x 635 mm  
131 x 444 x 635 mm  
86.5 kg  
34007724EN/AA - Page 37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Appendices  
Comet EX RT CLA module  
AC input voltage: 160-280 Volts AC,  
Input frequency: 40-70 Hz,  
Battery charge current: 6 A DC,  
Recharge time to recover 90% of the rated backup time after discharge at full load:  
Configuration for  
4 hours backup time  
12 hours  
Configuration for  
8 hours backup time  
20 hours  
Configuration for  
2 hours backup time  
5 hours  
Comet EX 5 RT  
Comet EX 7 RT  
Comet EX 11 RT  
12 hours  
20 hours  
5 hours  
15 hours  
24 hours  
7 hours  
Thermal characteristics  
The operating temperature is 0 to 40°C (8 hours at 45°C), however optimum operation is within the +20 to +25°C range.  
Battery backup time is adversely affected by high and low temperatures. It is significantly reduced at temperatures under  
10°C. Above 25°C, battery service life is cut in half every 10°C. Above 40°C, battery manufacturers no longer guarantee  
operation due to the risk of thermal runaway.  
Air enters through the front and exits through the back.  
5.2 Glossary  
Backup time  
Time that the connected loads can operate on battery power.  
Bypass AC source  
ECO mode  
Source supplying the bypass line. The load can be transferred to the bypass line if an overload  
occurs on the UPS output, for maintenance or in the event of a malfunction.  
Operating mode by which the load is supplied directly by the AC source if it is within the  
tolerances defined by the user. This mode reduces the consumption of electrical power.  
Load  
Devices or systems connected to the UPS output.  
Manual bypass  
Rotary switch controlled by the user, used to connect the loads directly to the AC source.  
Transfer of the load to the manual bypass enables UPS maintenance without interrupting the  
supply of power to the connected loads.  
Normal (double conversion) mode  
The normal UPS operating mode in which the AC source supplies the UPS which in turn  
supplies the connected loads (after electronic double conversion).  
Normal AC source  
Relay contacts  
UPS  
Normal source of power for the UPS.  
Contacts supplying information to the user in the form of signals.  
Uninterruptible Power Supply.  
Page 38 - 34007724EN/AA  
Download from Www.Somanuals.com. All Manuals Search And Download.  

La Crosse Technology Portable Radio WD 3102U User Manual
Land Pride Tiller rta12 User Manual
Lenoxx Electronics CD Player CD 96 User Manual
Lindy Switch 32361 User Manual
Magnavox TV Converter Box TB110MW9 User Manual
Makita Impact Driver BTD140Z User Manual
Mattel Model Vehicle Y0276 User Manual
Maxtor Computer Drive 15K II User Manual
Maxtor Computer Drive 2160 User Manual
Memorex MP3 Player MC2862 User Manual