MGE UPS Systems Power Supply 3200RT User Manual

MGE UPS SYSTEMS,INC.  
Pulsar EX  
2200RT / 3200RT  
EXB 2200/3200 RT  
Installation and User  
Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
CAUTION: Safety of persons  
The UPS has its own internal power source (the battery). Consequently, the power outlets may be energized even if the UPS  
is disconnected from the AC-power source.  
Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified service personnel.  
The UPS must be properly earthed. Measurements are required to ensure that the total leakage current of the UPS and the  
protected equipment does not exceed 3.5 mA by checking their characteristics (maximum leakage current of the UPS = 2 mA).  
The battery supplied with the UPS contains small amounts of toxic materials. To avoid accidents, the directives listed below  
must be observed:  
-
-
-
-
Never burn the battery (risk of explosion).  
Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).  
Comply with all applicable regulations for the disposal of the battery.  
Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high. Precautions must be  
taken for all handling: remove watches, rings, bracelets and any other metal objects, use tools with insulated handles.  
Do not lay tools or metal parts on top of batteries.  
-
CAUTION: Product Safety  
The UPS connection instructions and operation described in the manual must be followed in the indicated order.  
UPS must be connected to a nearby wall outlet that is easily accessible. The UPS can be disconnected from the AC-power  
source by removing the power cord.  
Check that the indications on the rating plate correspond to your AC-power system and to the actual electrical consumption of  
all the equipment to be connected to the UPS.  
Never install the UPS near liquids or in an excessively damp environment.  
Never let a foreign body penetrate inside the UPS.  
Never block the ventilation grates of the UPS.  
Never expose the UPS to direct sunlight or source of heat.  
If the UPS must be stored prior to installation, storage must be in a dry place.  
The admissible storage temperature range is -25ºC to +55ºC.  
Special Precautions  
All handling operations will require at least two people (unpacking, installation in rack system).  
Once installed and connected to the AC power source for the first time, the battery will start to charge. Full charging to obtain  
the rated battery backup time requires at least 8 hours.  
Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be energized for a period of  
24 hours, at least once every 6 months (for a normal storage temperature less than 25°C). This charges the battery, thus  
avoiding possible irreversible damage. During the replacement of the battery module, it is imperative to use the same type and  
number of element previously mounted in the UPS, in order to maintain an identical level of performance and safety. In case of  
doubt, don’t hesitate to contact our after sales department (for more information, refer to the web site www.mgeups.com).  
3400753300/AE - Page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
How to use this document  
Using this document  
Information may be found primarily by consulting:  
The contents,  
The index.  
Icon Usage  
WARNING: Eminent hazard to personnel or equipment, information must always be followed.  
CAUTION: Hazard to personnel or equipment, information that must always be followed.  
Notes, tips and information, help.  
Important information, help.  
Visual indication.  
Action.  
Audio indication.  
In the illustrations on the following pages, the symbols below are used:  
LED off.  
LED on.  
LED flashing.  
Page 4 - 3400753300/AE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
1. Presentation  
1.1 System configurations ................................................................................................................7  
Rack setup ......................................................................................................................................7  
Tower setup ....................................................................................................................................7  
1.2 Rear panel ......................................................................................................................................8  
Pulsar EX 2200RT ........................................................................................................................8  
Pulsar EX 3200RT ........................................................................................................................8  
Pulsar EXB 2200/3200 RT ............................................................................................................8  
1.3 Control panel ................................................................................................................................9  
2. Installation  
2.1 Unpacking ....................................................................................................................................10  
2.2 Installation in rack position ........................................................................................................11  
2.3 Installation in tower position ....................................................................................................12  
2.4 Connection to the RS232 or USB communication port (optional) ........................................13  
2.5 Installation of the communication-card option ........................................................................13  
2.6 Connections ................................................................................................................................14  
3. Operation  
3.1 Start-up ........................................................................................................................................15  
3.2 LED indicators ............................................................................................................................15  
3.3 Operation on battery power (following failure of AC input power) ............................................16  
Transfer to battery power ..............................................................................................................16  
Threshold for the low-battery warning............................................................................................16  
End of backup time ........................................................................................................................16  
3.4 Personalization (optional) ............................................................................................................17  
Function..........................................................................................................................................17  
"ON / OFF conditions" tab..............................................................................................................17  
"Battery" tab ..................................................................................................................................17  
"Output" tab....................................................................................................................................18  
"Bypass" tab ..................................................................................................................................18  
3.5 UPS Shutdown ............................................................................................................................18  
3.6 UPS Remote Power Off ..............................................................................................................19  
3400753300/AE - Page 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
4. Maintenance  
4.1 Troubleshooting ..........................................................................................................................20  
4.2 Replacement of the battery modules ........................................................................................22  
5. Environment ....................................................................................................................................24  
6. Appendices  
6.1 Technical characteristics ..........................................................................................................25  
6.2 Glossary ......................................................................................................................................26  
6.3 Index ............................................................................................................................................27  
Page 6 - 3400753300/AE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Presentation  
1.1 System configurations  
Rack setup  
17.24 inches (19" Rack mount)  
25.75 inches (EX 2200RT)  
26.00 inches (EX 3200RT)  
3.75 inches  
(2U)  
R
P
E X  
U
L
S
A
BYPA  
SS  
2
1
%
%
%
8
0% 100%  
2
0
%
5
0
test  
com  
ps.  
geu  
w.m  
ww  
Model  
Part  
Number  
Weight  
(Ibs/kg)  
Pulsar EX 2200RT  
85220  
80.8 lbs (36.6 kg)  
82.7 lbs (37.5 kg)  
92.8 Ibs (42.0 kg)  
Pulsar EX 3200RT  
85320  
Tower setup  
Pulsar EXB 2200/3200 RT  
85000  
%
%
0
0
1
%
0
8
%
0
5
%
0
2
%
t
s
e
t
1
2
S
S
A
P
Y
B
S
A
R
L
P
E
U
X
om  
ps.c  
geu  
w.m  
ww  
3400753300/AE - Page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Presentation  
1.2 Rear panel  
Slot for communication-card option.  
RS232 communication port.  
USB communication port.  
1
2
Pulsar EX 2200RT  
5
3
8
9
10 11 12  
4
1
3
4
Upper two receptacles for connection  
to AC-power source.  
Lower two programmable receptacles  
(1 and 2).  
5
L5-20P Plug  
Output circuit breakers. (EX 3200RT)  
6
7
INPUT CABLE  
L5-20R Receptacle  
OUTPUT CABLE  
2
7
Input/Output power cords for direct  
connection of protected equipment.  
EX 2200RT-L5-20P/L5-20R; and  
EX 3200RT-L5-30P/L5-30R.  
Pulsar EX 3200RT  
8
9
10 11 12  
6
4
1
5
3
Connector for an additional battery  
module.  
8
9
Connector for automatic detection of an  
additional battery module.  
Pushbutton to test phase/neutral  
inversion of AC-power source.  
10  
11  
LED indicating Site Wiring Alarm  
Enable, with flashing and intermittent  
buzzer. Reset fault with rear panel  
button.  
L5-30P (Plug)  
INPUT CABLE  
2
L5-30R (Receptacle)  
OUTPUT CABLE  
7
Pulsar EXB 2200/3200 RT  
Connector for remote power off (RPO).  
12  
13  
14  
15  
Battery module connectors (to the UPS  
or to other battery modules).  
Connectors for automatic detection of  
additional battery modules.  
14  
15  
Circuit breaker for battery ON/OFF and  
protection.  
13  
13  
Page 8 - 3400753300/AE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Presentation  
1.3 Control panel  
BYPASS  
2
1
test  
%
%
20% 50% 80% 100%  
16  
17  
18  
19 20  
21  
22  
23  
24  
25  
26  
27  
ON / OFF.  
16  
17  
18  
19  
Operation on battery power.  
Operation in ON-LINE mode (backup power available).  
Operation on bypass (no backup power available).  
%
%
Alarms  
battery  
remaining  
load  
100%  
80%  
50%  
20%  
UPS  
27  
100%  
80%  
50%  
20%  
Status of programmable outlet 2:  
20  
21  
Supplied with power  
overload  
Status of programmable outlet 1:  
Status change in  
progress.  
Electronics  
fault  
26  
25  
24  
Lamp test or buzzer OFF.  
Forced transfer to bypass and back  
by pressing button 3 times in less  
than 5 seconds.  
22  
Battery  
fault *  
Press simultaneously at  
least 3 seconds to reset  
the “End of battery life”  
alarm.  
Site Wiring  
Fault  
23 Hold down to display  
percent load:  
(*) : flashing LED + buzzer: battery fault (battery must be replaced).  
flashing LED + long buzzer (once per hour): theoretical end of battery life (replacement recommended).  
3400753300/AE - Page 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
2.1 Unpacking  
31  
30  
32  
%
%
0
0
1
%
0
8
%
0
5
%
0
2
%
t
s
e
t
1
2
34  
S
S
A
P
Y
B
35  
 R
L
 S
 A
 U
E
X
P
36  
RS232 communication cable.  
30  
31  
32  
34  
35  
USB communication cable.  
Telescopic rails for mounting in 19" bay with mounting hardware.  
CD-ROM with the Solution-Pac and UPS Driver software.  
Product documentation.  
Two supports for the upright position.  
36  
Page 10 - 3400753300/AE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
2.2 Installation in rack position  
Follow steps A to D for rack mounting of the UPS on the rails. The rails and the necessary mounting hardware are supplied in  
the box along with the UPS (see item 32 on page 10).  
A. Secure Rails together with three screws (1).  
1
B. Attach frontal Rails to Rack front (2).  
3
C. Attach rearmost Rails to Rack rear (3).  
If using Stop-Notch (7) snap into rear rail.  
(refer to Quick Start for positioning details.)  
3
D. Attach both front brackets (4 & 5) to each  
side of UPS, and slide (mount) UPS into  
the Rack (6).  
2
6
2
5
7
Stop-Notch  
Snap from  
inside of rails  
4
5
CAUTION: Do not lean or place objects on top of unit at any time. Hazard of dismounting and disconnection can  
occur with units.  
NOTE: (For step 5) it is possible to adjust the position of the front fixing bracket.  
3400753300/AE - Page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
2.3 Installation in tower position  
Install the two supports for the upright position using provided hardware in the package.  
(see item 32 on page 10).  
Pull out the MGE Logo and Model plates, then rotate them as shown.  
%
%
0
0
1
%
0
8
%
0
5
%
0
2
%
t
s
e
t
1
2
S
S
A
P
Y
B
A
R
L
S
U
X
P
E
 R
m
.co  
ps  
geu  
w.m  
ww  
 L
S
 A
 U
P
Page 12 - 3400753300/AE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
2.4 Connection to the RS232 or USB communication port (optional)  
1. Connect the RS232 30 or USB 31  
communication cable to the serial port or  
the USB port on the computer.  
30  
2. Connect the other end of the communica-  
tion cable 30 or 31 to the RS232  
2
31  
or USB  
UPS.  
3
communication port on the  
The UPS can now communicate with all  
MGE UPS SYSTEMS, Inc. supervision,  
set-up or safety software.  
3
2
NOTE: The RS232 and USB communication ports cannot operate simultaneously.  
2.5 Installation of the communication-card option  
Slot for the  
communication  
card option.  
It is not necessary to shut down the UPS to  
install the communication card:  
1
1.Remove the slot  
two screws.  
1
cover secured by  
2.Insert the card in the slot.  
3.Secure the card with the two screws.  
L5-30P Plug  
INPUT CABLE  
L5-30R Receptacle  
OUTPUT CABLE  
3400753300/AE - Page 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
2.6 Connections  
CAUTION: Check that the indications on the rating plate (on the back of the UPS), correspond to your AC-power  
system, and to the actual electrical consumption of all the equipment to be connected to the UPS.  
1. Connect the input power cord  
7
to the  
4
AC-power wall-receptacle.  
2. Connect the protected equipment to the  
UPS. It is advised to connect priority  
loads to the outlets and/or power cord  
and any non-priority loads to the two  
5-20P  
4
programmable outlets  
5
(If the UPS is  
5
connected to a computer running MGE  
UPS SYSTEMS, Inc. communication  
software, it is possible to program the  
interruption of power to the two  
programmable outlets  
5
during  
operation on battery power, thus reserv-  
ing backup power for the priority loads).  
The battery begins charging the  
instant the UPS unit is connected  
to a power source. Eight hours are  
required to charge to the full rated  
backup time.  
4
7
Page 14 - 3400753300/AE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Operation  
3.1 Start-up  
The protected equipment connected to the UPS can be energized, whether AC input power is available or not.  
CAUTION:The AC input power source must be present when  
energizing for the first time.  
1. Press the ON / OFF button 16 .  
The buzzer beeps and all the LEDs go ON.  
The buzzer beeps twice, then:  
If AC input power is available, LED 18 goes ON, indicating  
operation in ON-LINE mode.  
1
S
S
BYPA  
2
If AC input power is not available and the UPS is configured for  
automatic restart mode, the buzzer beeps three times and LED 17  
goes ON, signalling operation on battery power.  
All connected equipment is energized.  
%
100%  
%
80  
%
50  
%
t
est  
20  
%
16  
17 18 25  
26 27  
NOTE: If LEDs 17 or 18 do not turn ON or if LEDs 25 to 27 flash,  
there is a fault (see section 4.1).  
3.2 LED indicators  
LEDs 24 to 27 provide three  
different indications:  
BYPASS  
2
1
1. Remaining backup time in percent  
(during normal operation).  
2. Percent load drawn by the protected  
test  
%
%
20% 50% 80% 100%  
equipment, when button 23 is pressed.  
3. Operating faults (flashing LED and  
beeps):  
27 Overload.  
26 UPS fault.  
24  
25 26 27  
16  
17 18 19 20 21  
22  
23  
25 Battery fault or end of life warning.  
24 Site wiring Fault  
Description of LED indicator status 20 and 21 for programmable outlets 1 and 2:  
OFF: the outlets are not supplied with power.  
Flashing: status change in progress.  
ON: the outlets are supplied with power.  
Outlets 1 and 2 can be remotely programmed and controlled.  
They may be used for sequential start-up of the protected applications, shedding of non-priority applications during  
operation on battery power, and priority management at the end of battery backup time to reserve the longest possible  
backup time for the most sensitive applications. These outlets are programmed using Solution Pac software.  
3400753300/AE - Page 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Operation  
3.3 Operation on battery power (following an AC input power failure)  
Transfer to battery power  
The AC-power source is outside tolerances, LED 17 is ON, the buzzer  
beeps three times.  
BYPASS  
2
1
The equipment connected to the UPS is supplied by the battery.  
test  
17  
Threshold for the low-battery warning  
The low-battery warning threshold can be set by the user, with the UPS  
Driver software (see section 3.4).  
BYPASS  
2
1
LED 17 flashes.  
The buzzer beeps every three seconds.  
test  
%
There is very little remaining battery backup time. Close all  
applications because UPS automatic shutdown is imminent.  
17  
End of backup time  
The buzzer sounds continuously.  
BYPASS  
Press button 22 to turn the buzzer OFF.  
2
1
The equipment is no longer supplied with power.  
test  
22  
The UPS goes to sleep mode at the end of the battery backup time, until complete shutdown, due to tripping of the  
battery-protection function against deep discharge.  
Return of AC input power:  
IMPORTANT: If, in spite of the return of AC input power, the UPS does not restart, check that the automatic-restart  
function (activated by return of AC input power) has not been disabled (see section 3.4).  
Page 16 - 3400753300/AE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Operation  
3.4 Personalization (optional)  
Function  
Personalization parameters can be set and modified using the UPS Driver software installed on a computer that is  
connected to the UPS (see section 2.4 Connection to the RS232 communication port).  
NOTE: Check that the RS232 30 cable is properly connected.  
UPS Driver installation:  
1. Insert the Solution-Pac CD-ROM containing the UPS Driver software into your computers CD ROM drive.  
2. Open the file Manager and select the CD-ROM drive.  
3. Launch "\Emb\Config\UPSDRVxx.exe" (xx = software version).  
IMPORTANT: You can download the software UPS Driver from the www.mgeups.com as well, or contact an  
MGE representative in your area. Once UPS Driver has been installed, the UPS parameters listed below can be  
modified.  
"ON / OFF conditions" tab  
Personalization function  
Default setting  
Enabled  
Options  
Disabled  
Disabled  
Disabled  
Enabled  
Disabled  
Automatic start  
Cold start (battery power)  
Forced shutdown  
Enabled  
Enabled  
Sleep mode  
Disabled  
Enabled  
UPS ON / OFF via software  
"Battery" tab  
Personalization function  
Default setting  
Options  
Once a day  
Once a month  
Automatic "Battery test" intervals  
"Low-battery warning" threshold  
Every weeks  
No test  
20% remaining  
battery backup time  
From 0% to 100% of the remaining  
battery backup time  
Protection against deep discharges  
Enabled  
Disabled  
3400753300/AE - Page 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Operation  
"Output" tab  
Personalization function  
Rated UPS voltage  
Default setting  
120 V  
Options  
100 V - 127 V  
Converter  
Frequency working mode  
Rated UPS frequency  
Autoselect  
F = 60 Hz  
50 Hz  
UPS tolerance for AC-power  
source frequency  
F
5%  
F
1% to 10%, in 1% steps  
Overload alarm threshold  
110%  
0 to 110%, in 10% steps  
UPS restart following short-circuit  
Disabled  
Enabled (click to add check)  
"Bypass" tab  
Default setting  
Enabled  
Options  
Personalization function  
Disabled (click to remove check)  
Enabled (click to add check)  
Transfer to bypass if overload  
Disabled  
Transfer to bypass following a fault, whatever the  
conditions on the AC-power source  
3.5 UPS shutdown  
Press button 16 (return to the OFF position).  
BYPASS  
2
1
The connected equipment is no longer supplied with power.  
test  
16  
Page 18 - 3400753300/AE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Operation  
3.6 UPS Remote Power Off (RPO)  
Pulsar EX RT's are equipped with a Remote Power Off function (RPO) that can cut power to all the devices connected to  
the UPS using a remote user-operated contact.  
The function is implemented by opening a contact connected to the two terminals of connector 12 on the back of the  
UPS.  
12  
37 38  
Installation and test of the remote power off function  
1. Check that the UPS is shut off and disconnected from the AC power source.  
2. Remove the RPO connector 12 by undoing the screws 37 .  
3. Connect an insulated dry contact (NC, 60 V DC, 30 V AC max., 20 mA max., cable size 0.75 mm) to the two terminals  
of the RPO connector 38 .  
4. Put the RPO connector 12 back in place on the back of the UPS.  
5. Connect the UPS to the AC-power source and restart it as indicated previously.  
6. Activate the RPO external contact to test the function.  
7. To return to normal operation, deactivate the RPO external contact and restart the UPS using button 16 (press OFF,  
then ON).  
3400753300/AE - Page 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Maintenance  
4.1 Troubleshooting  
If any of LEDs 25 , 26 or 27 flash, there is a operating anomaly or an alarm.  
NOTE: If a LED flashes, the bargraph data is no longer displayed.  
LED 27 flashes and UPS overload. Overload is too long or too high.  
Check the power drawn by the  
equipment and disconnect any  
non-priority devices.  
the buzzer beeps.  
If AC power is present and within tolerances, the  
UPS goes to bypass mode (supply directly by the  
AC-power source). LED 19 flashes.  
The buzzer beeps every second.  
If AC power is not present or not within tolerances,  
the connected applications are no longer supplied.  
The buzzer sounds continuously.  
LED 25 flashes and A battery fault was detected during the  
Check that the battery connector  
the buzzer beeps.  
automatic battery test.  
is fully pushed in.  
Replace battery module (see Maintenance section).  
LED 25 flashes and The battery has reached the theoretical end  
Reset the alarm by pressing  
buttons 22 and 23  
the buzzer emits a  
long beep once  
per hour.  
of its service life.  
simultaneously for 3 seconds.  
It is advised to replace both batteries at  
See the section on maintenance.  
the same time with the same rating  
as the original batteries.  
The yellow LED 24  
flashes, the red  
indicator light 11  
behind the UPS  
comes on and the  
buzzer sounds  
The function for monitoring the phase and neutral  
position of your electrical network has detected a  
reversal.  
Directly earthed neutral type  
networks: check the cabling  
of phase and neutral on your  
electrical network.  
For all other network types,  
de-activate the detection function  
(this function is only operational  
continuously.  
for directly earthed neutral electrical  
networks):  
Press for at least 5 seconds the  
pushbutton 10 behind the UPS  
(UPS stopped and connected to the  
network for less than 30 minutes).  
Page 20 - 3400753300/AE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Maintenance  
Indication  
Signification  
Correction  
The outlets are not supplied One of the protection circuit breakers  
6
for the  
Check that there is not a short-  
circuit on the outlets.  
with power, even though  
button 16 is ON  
outlets (on the back of the UPS) is open.  
Eliminate any overloads on the  
(3200 RT only).  
outlets by modifying the  
distribution of devices on the  
outlets.  
LED 26 flashes and  
the buzzer sounds  
continuously.  
UPS electronics have detected a UPS fault.  
Depending on the UPS personalization parameters  
(see section 3.4).  
Restart the UPS.  
There are two possibilities:  
The equipment connected to the UPS continues to Call the after-sales support  
be supplied, but directly from the AC-power source  
department.  
(via the automatic bypass (LED 19 ON).  
The connected equipment is no longer supplied.  
The equipment connected to the UPS is no  
longer protected.  
3400753300/AE - Page 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Maintenance  
4.2 Replacement of the battery modules  
CAUTION: Load will not be protected during this procedure!  
Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high.  
Precautions must be taken for all handling.  
Safety Rules:  
Remove all watches, rings, bracelets and any other metal objects that may come into contact with the battery modules.  
Use tools with insulated handles.  
Removal of the battery modules  
A
B
- Unclip the small plate with the MGE  
UPS SYSTEMS, Inc. Logo on the  
UPS front panel.  
- Remove the 2 screws.  
1
2
SS  
PA  
BY  
%
0%  
10  
%
80  
%
50  
0%  
R
A
2
%
S
L
t
tes  
U
P
E X  
B
A
m
co  
s.  
p
u
ge  
.m  
w
w
w
C
D
- Remove the left part of the front panel.  
- Disconnect the connector.  
1
2
SS  
PA  
BY  
%
0%  
10  
80%  
50%  
%
20  
%
st  
te  
D
R
A
S
L
U
P
E X  
C
Page 22 - 3400753300/AE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Maintenance  
E
F
- Remove the screws securing the  
battery cover.  
- Remove the cover.  
1
2
SS  
PA  
BY  
%
0%  
10  
%
80  
%
50  
%
20  
%
t
tes  
E
F
G
- Remove the two battery modules and  
proceed with replacement.  
1
2
SS  
PA  
BY  
%
0%  
10  
80%  
%
50  
%
20  
%
st  
te  
G
G
Reinstallation of the battery modules  
To reinstall the battery modules perform this procedure in reverse order e.g., “G”, “F”, “E”.  
To maintain an identical level of performance and safety, use battery modules identical to that previously  
mounted in the UPS.  
Press the two parts of the battery connector tightly together to ensure proper connection.  
3400753300/AE - Page 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Environment  
This product has been designed to respect the environment:  
It does not contain CFC's or HCFC's.  
UPS recycling at the end of service life:  
MGE UPS SYSTEMS, Inc. undertakes to recycle, by certified companies and in compliance with all applicable regulations,  
all UPS products recovered at the end of their service life (contact your MGE UPS SYSTEMS, Inc. branch office).  
Packing:  
UPS packing materials must be recycled in compliance with all applicable regulations.  
WARNING:  
This product contains lead-acid batteries. Lead is a dangerous substance for the environment if it is not properly recycled  
by specialized companies.  
MGE Customer Care Center  
Technical questions? If you encounter a problem while following the instructions in this manual, we recommend that you  
contact our Technical Support Group at 1 800 523-0142.  
?
RMA forms for service.  
Page 24 - 3400753300/AE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Appendices  
6.1 Technical characteristics  
AC/DC PFC  
CONVERTER  
DC/AC  
INVERTER  
SAFETY  
RELAY  
BYPASS  
RELAY  
AC INPUT  
EMI FILTER  
EMI FILTER  
AC OUTPUT  
BATTERY  
POWER  
DC/DC  
CHARGER  
SUPPLY  
PUSH PULL  
BATTERY  
Pulsar EX 2200RT  
Pulsar EX 3200RT  
Pulsar EXB  
2200/3200 RT  
Output power rating  
2200 VA / 1540 W  
3200 VA / 2080 W  
AC-input  
Voltage  
Frequency  
Power factor  
Runtime @ full load  
(1)  
Single phase, 60 V / 70 V / 80 V to 142 V  
50/60 Hz (auto-select)  
≥ 0.95  
20min -40min -60min -80min  
1EXB -2EXB -3EXB -4EXB  
Output specification  
Voltage  
Frequency  
Harmonic distortion  
Overload capability  
QUALITY  
(2)  
Single phase, 120 V 3%  
50/60 Hz 0.5%  
(3)  
Designed, Manufactured and  
marked under ISO 9001 quali-  
ty system.  
< 4% on linear load, < 6% on non linear load  
110% continuous, 130% 12s, > 130% 1.5s  
Battery (sealed lead-acid,  
maintenance free)  
72VDC - 18 Ah  
6 x 12 V - 9 Ah  
6 x 12 V - 7 Ah  
Environmental and safety  
Noise level  
Operating temperature  
Relative humidity  
Safety  
< 50 dBA  
0 to 40° C  
20 to 90% (without condensation)  
UL 1778 / cUL CSA 22.2 N°107.1  
FCC 47 CFR Part 15, class A  
UL, CSA  
UL, CSA  
FCC Class A  
UL , cUL  
EMC  
Agency markings  
(1) Input voltage correspond to 33% / 66% / 100% of the nominal power rating.  
(2) Adjustable from 100 V to 127 V using UPS Driver software.  
(3) Frequency converter mode may be set using the UPS Driver software.  
3400753300/AE - Page 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Appendices  
6.2 Glossary  
Authorized voltage range for  
Upper and lower voltage thresholds within which the UPS can operate on the automatic  
bypass in the event of a UPS fault or overload.  
transfer to bypass if fault or  
overload  
Automatic bypass  
Automatic switch controlled by the UPS, used to connect the equipment directly to the  
AC-power source in the event of a UPS failure or an overload.  
Automatic start following  
return of AC input power  
This function automatically starts the UPS when AC input power returns following  
shutdown at the end of the battery backup time. It can be enabled or disabled.  
Backup time  
Bargraph  
Time that the connected equipment can operate on battery power.  
Device on the front panel indicating the percent remaining backup time or the percent  
load.  
Battery test  
Dialog box  
Internal UPS test on battery status.  
A window in a computer program displayed for selection by the user of various options  
and parameter settings.  
Double conversion  
The power supplied to the connected equipment is completely regenerated by  
continuous double conversion, i.e. the AC power from the AC-power source is rectified  
(AC - DC), then converted back (DC - AC) to AC power.  
Equipment  
Devices or systems connected to the UPS output.  
Forced shutdown  
Ten-second interruption in the supply of power to the connected equipment following a  
system shutdown, even if AC input power returns during the interruption period.  
Percent load  
Ratio between the power drawn by the connected equipment and the total power that  
the UPS can supply.  
Personalization  
A number of UPS functions can be modified using the UPS Driver software to better  
meet the user’s needs.  
Programmable outlets  
Remote Power Off  
Start on battery power  
Outlets that can be automatically shed during operation on battery power (a shedding  
time delay may be programmed using Solution-Pac software.  
External dry contact can be used to stop the unit, during an emergency situation for  
example. All power is removed from the load.  
This function makes it possible to energize the connected equipment even when AC  
input power is not available (operation exclusively on battery power).  
UPS  
Uninterruptible Power Supply.  
UPS ON / OFF via software  
It is possible to enable or disable use of UPS ON / OFF controls by the computer-  
system protection software.  
Page 26 - 3400753300/AE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Appendices  
6.3 Index  
A
O
Automatic bypass....................................................9-18-20  
Automatic start ................................................................17  
ON LINE mode..................................................................9  
Overload ................................................................9-18-20  
B
P
Bargraph ......................................................................9-15  
Battery  
Personalization ..............................................................17  
Battery ....................................................................17  
By-pass ..................................................................18  
On/Off conditions ....................................................17  
Output......................................................................18  
Programmable outlets ..............................................8-9-15  
End of backup time..................................................16  
Fault......................................................................9-15  
Low-battery warning ................................................17  
Recycling ................................................................24  
Replacement ......................................................22-23  
Transfer to battery power ........................................16  
Buttons ..........................................................................8-9  
Buzzer........................................................................15-16  
Buzzer shutdown ..............................................................9  
R
Remote power off............................................................19  
S
Site Wiring Fault................................................................9  
Sleep mode ....................................................................17  
Automatic restart ................................................17-18  
Start-up............................................................................15  
C
Connection  
Additional battery module ........................................8  
Communication card ..............................................13  
RS 232 communication port....................................13  
USB communication port ........................................13  
Communication ............................................................8-13  
T
Technical characteristics ................................................25  
Transfer (forced) ..............................................................9  
D
Dimensions........................................................................7  
U
UPS Driver ....................................................................17  
UPS fault ..........................................................9-15-20-21  
UPS ON / OFF via software ..........................................17  
UPS shutdown................................................................18  
E
Environment ................................................................2-24  
W
F
Web site............................................................................2  
Weight ..............................................................................7  
Forced shutdown ............................................................17  
L
Lamp test..........................................................................9  
LEDs..............................................................................8-9  
3400753300/AE - Page 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MGE UPS SYSTEMS, INC.  
T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R  
1660 Scenic Avenue  
Costa Mesa, CA 92626, USA  
Main Number: 714 557-1636  
For service call:  
1 800 523-0142  
M
G
E
UPS SYSTEMS  
3400753300-AE  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Laser Digital Camera AO EZCAMEL T User Manual
Lennox International Inc Air Conditioner 15CHAX Series User Manual
Lenovo Computer Hardware Q180 User Manual
Lincoln Convection Oven 1100ADVSVC User Manual
Link electronic Network Router 862 XL1616HD 3 User Manual
Link electronic Stereo Amplifier LEI 555 User Manual
Linksys Network Card WET610N User Manual
Lochinvar Boiler WB50 thru 210 User Manual
Loewe Work Light Xelos 32 LED User Manual
Lowrance electronic GPS Receiver 988 0161 011 User Manual