MGE UPS SYSTEMS
Pulsar Evolution
1500 Tower/1500 Rack
1100 Tower/1100 Rack
800 Tower/800 Rack
500 Rack
Installation and user
manual
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
CAUTION: Safety of persons
◗
The UPS has its own internal power source (the battery). Consequently, the power outlets may be energized even if the UPS is
disconnected from the AC-power source.
◗
◗
Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified service personnel.
The UPS must be properly earthed. Measurements are required to ensure that the total leakage current of the UPS and the
protected equipment does not exceed 3.5 mA by checking their characteristics (maximum leakage current of the UPS = 2 mA).
The battery supplied with the UPS contains small amounts of toxic materials. To avoid accidents, the directives listed below
must be observed:
◗
-
-
-
-
Never burn the battery (risk of explosion).
Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).
Comply with all applicable regulations for the disposal of the battery.
Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high. Precautions must be
taken for all handling: remove watches, rings, bracelets and any other metal objects, use tools with insulated handles.
Do not lay tools or metal parts on top of batteries.
-
CAUTION: Product safety
◗
◗
The UPS connection instructions and operation described in the manual must be followed in the indicated order.
UPS must be connected to a nearby wall outlet that is easily accessible. The UPS can be disconnected from the AC-power
source by removing the power cord.
◗
Check that the indications on the rating plate correspond to your AC-power system and to the actual electrical consumption of
all the equipment to be connected to the UPS.
◗
◗
◗
◗
◗
◗
Never install the UPS near liquids or in an excessively damp environment.
Never let a foreign body penetrate inside the UPS.
Never block the ventilation grates of the UPS.
Never expose the UPS to direct sunlight or source of heat.
If the UPS must be stored prior to installation, storage must be in a dry place.
The admissible storage temperature range is -25ºC to +55ºC.
Special precautions
◗
◗
All handling operations will require at least two people (unpacking, installation in rack system).
Once installed and connected to the AC power source for the first time, the battery will start to charge. Full charging to obtain
the rated battery backup time requires at least 8 hours.
◗
Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be energized for a period of
24 hours, at least once every 6 months (for a normal storage temperature less than 25°C). This charges the battery, thus
avoiding possible irreversible damage. During the replacement of the battery module, it is imperative to use the same type and
number of element previously mounted in the UPS, in order to maintain an identical level of performance and safety. In case of
doubt, don’t hesitate to contact our after sales department (for more information, refer to the web site www.mgeups.com).
3400723200/AC - Page 3
Download from Www.Somanuals.com. All Manuals Search And Download.
Foreword
Using this document
Information may be found in two ways, using:
◗ the contents;
◗ the index.
Pictograms
Important instructions that must always be followed.
Information, advice, help.
Visual indication.
Action.
Audio indication.
In the illustrations on the following pages, the symbols below are used:
LED off.
LED on.
LED flashing.
Page 4 - 3400723200/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
1. Presentation
1.1 Overall view.................................................................................................................................. 7
Tower models ..................................................................................................................................7
Rack models ....................................................................................................................................7
1.2 Back .............................................................................................................................................. 8
1.3 Control panel..................................................................................................................................9
2. Installation
2.1 Unpacking and parts check ......................................................................................................10
Tower models ................................................................................................................................10
Rack models ..................................................................................................................................11
2.2 Installation ....................................................................................................................................12
Tower models ................................................................................................................................12
800/1100/1500 Rack models..........................................................................................................13
500 Rack model ............................................................................................................................14
2.3 Connecting the protected equipment ........................................................................................15
2.4 Connection to the RS232 or USB communications port (optional) ........................................16
2.5 Connection to the data-line protection port (optional)..............................................................16
2.6 Installation of the communications-card option ......................................................................17
3. Operation
3.1 Start-up..........................................................................................................................................18
3.2 Shift to booster or fader mode (during voltage variations in the AC-input power) ....................18
3.3 Operation on battery power (following failure of AC-input power) ............................................19
Transfer to battery power ..............................................................................................................19
Threshold for the low-battery warning............................................................................................19
3.4 Personalization (optional) ............................................................................................................20
Function..........................................................................................................................................20
ON / OFF conditions tab ................................................................................................................20
Battery tab......................................................................................................................................20
Voltage-thresholds tab ..................................................................................................................21
Sensitivity tab ................................................................................................................................21
3400723200/AC - Page 5
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
4. Maintenance
4.1 Trouble-shooting..........................................................................................................................22
4.2 Replacement of the battery module ..........................................................................................23
Tower models ................................................................................................................................23
Rack models ..................................................................................................................................25
5. Environment ....................................................................................................................................27
6. Appendices
6.1 Technical data
Simplified diagram..........................................................................................................................28
Technical characteristics ................................................................................................................29
Examples of battery backup times ................................................................................................30
6.2 Glossary........................................................................................................................................31
6.3 Index..............................................................................................................................................32
Page 6 - 3400723200/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Presentation
1.1 Overall view
Tower models
Dimensions in inches
(W x H x D)
D
Evolution 800 Tower
5.9 x 9.3 x 16.3
5.9 x 9.3 x 16.3
5.9 x 9.3 x 19
Evolution 1100 Tower
Evolution 1500 Tower
Weight in lbs
Evolution 800 Tower
Evolution 1100 Tower
Evolution 1500 XL Tower
23
25.4
33
H
P
U
L
S
A
R
Evolution
1
1
0
0
W
Rack models
Dimensions in inches
(W x H x D)
D
Evolution 500 Rack 17.2 (19”) x 1.7 (1U) x 13.9
Evolution 800 Rack 17.2 (19”) x 1.7 (1U) x 19.6
Evolution 1100 Rack 17.2 (19”) x 1.7 (1U) x 19.6
Evolution 1500 Rack 17.2 (19”) x 1.7 (1U) x 20.5
H
Weight in lbs
P
U
L
S
A
R
Evolution
W
1500 Rack
Evolution 500 Rack
Evolution 800 Rack
Evolution 1100 Rack
Evolution 1500 Rack
20
34
35
42
3400723200/AC - Page 7
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Presentation
1.2 Back
Pulsar Evolution 800 / 1100 / 1500 Tower
Pulsar Evolution:
1
2
3
USB communications port.
RS232 communications port.
Data-line protection.
V
ac OUT
I max 12A
4
5
6
2
2
1
2
1
Slot for communications-card option.
U.S. PA NO. 6,094,363
T
.
4
5
36Vdc, 9A
h
Pb
R
Mains
Netz
eseau
V
olt 120V~1O
mps 12A MAX
Hertz 50/60 Hz
A
1
R
Util
Volt 120V~1O
L
oad
Hertz 50/60 Hz
A
usg
W
/V 1000W/1440V
A
A
34Z5
U.P.S.
Receptacle for direct connection of
protected equipment.
344-50254-00
IN
OUT
Data line protection
8
7
6
7
Programmable receptacles (1 and 2).
Input circuit-breaker.
3
8
Connection to the utility.
Pulsar Evolution 500 / 800 / 1100 Rack
1
2
8
7
5
6
3
2
1
4
Pulsar Evolution 1500 Rack
T20A/125V
36Vdc, 9A
~
h
Vac OUT
I
max 12A
Programmable
R
1
2
Pb
34Z5
U.P.S.
U.S. PA No. 6,094,363
T
.
IN
OUT
A
C
I
nput
V
olt
mp
ertz 50/60
120V~1O
A
s
12A
M
AX
RS232
Data line protection
SITE WIRING
FAUL
H
Hz
AC
Output
V
olt
120V~1O
T
344-50248-00
H
e
r
t
z
5
0
/
6
0
Hz
/1440V
Vac IN
W
/
VA
1000W
A
1
2
4
8
7
2
1
3
5
6
Page 8 - 3400723200/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Presentation
1.3 Control panel
Illuminated ON/OFF button for the receptacles.
10
Operation on battery power.
UPS fault.
11
12
Battery fault.
Overload.
13
14
15
16
Group 1 programmable receptacles supplied with power.
Group 2 programmable receptacles supplied with power.
Booster or fader mode.
1
2
Bargraph indicating percent load at output.
17
%
%
18 Bargraph indicating the battery charge level.
76 to 100%.
51 to 75%.
26 to 50%.
0 to 25%.
3400723200/AC - Page 9
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
2.1 Unpacking and parts check
Tower models
20
21
22
23
24
R
A
tion
P
U
L
S
Evolu
1
1
0
0
RS232 communications cable for Windows Operating Systems. For Unix/Linux Operating Systems, please order for
free the following part number: 66090
21
22
23
24
USB communications cable.
CD-ROM with the Solution-Pac and UPS Driver software.
Product documentation.
Page 10 - 3400723200/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
Rack models
20
21
22
23
25
24
26
P
U
L
S
A
R
Evolution
1500 Rack
RS232 communications cable for Windows Operating Systems. For Unix/Linux Operating Systems, please order for
free the following part number: 66090
21
USB communications cable.
22
23
24
25
CD-ROM with the Solution-Pac and UPS Driver software.
Product documentation.
Telescopic rails for mounting in 19" bay with mounting hardware.
26 Securing system for equipment power cords.
3400723200/AC - Page 11
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
2.2 Installation
Tower models
P
U
L
S
A
R
Evolution
1
1
0
0
P
U
L
S
A
R
Evolution
1
1
0
0
Page 12 - 3400723200/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
800/1100/1500 Rack models
Follow steps 1 to 6 for rack mounting of the UPS on the rails.
2
1
6
2
2
4
3
5
2
P
U
L
S
A
R
Evolution
1500 Rack
6
5
3
The rails and the necessary mounting hardware are supplied by MGE UPS SYSTEMS.
For step 1, screw quantity shown is for 1500 VA. 800 and 1100 VA use two screws for each side.
3400723200/AC - Page 13
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
500 Rack model
Follow steps 1 to 3 for rack mounting of the UPS on the rails.
2
1
P
U
L
S
A
R
Evolution
1500 Rack
3
1
3
Floor Mount Configuration
Wall Mount Configuration
A
io
R
n
L
S
P
U
Evolut
1500 Rack
R
P
U
L
S
A
Evolution
1500 Rack
Page 14 - 3400723200/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
2.3 Connecting the protected equipment
A Pulsar Evolution 1500 tower UPS has been used below to illustrate the instructions. The principle is the same for all the
other tower and rack models.
Check that the indications on the rating plate on the back of the UPS correspond to your AC-power system and to
the actual electrical consumption of all the equipment to be connected to the UPS.
1 - Remove the power cord supplying the
equipment to be protected.
2 - Connect the power cord to the AC-power
Vac OUT
I max 12A
wall receptacle 8 .
3 - Connect the protected equipment to the
UPS using the cord 20 . Connect critical
loads to the two standard receptacles 5 and
any non-critical loads to the two program-
5
mable receptacles
6
(1 and 2).
2
1
2
If the UPS is connected to a
computer running MGE communi-
cations software, it is possible to
program the interruption of power
to the programmable receptacles
U.S. PAT. NO. 6,094,363
6
36Vdc, 9Ah
Pb
Reseau
Mains
Netz
Volt
120V~1O
Amps 12A MAX
Hertz 50/60 Hz
1
R
Util
Load
Ausg
V
olt
Hertz 50/60 Hz
W/V 1000W/1440V
120V~1O
A
A
34Z5
U.P.S.
344-50254-00
IN
OUT
6
during operation on battery
power, thus reserving backup
power for the critical loads.
ata line protection
8
4 - Lock the connections using the securing
system 26 (for rack models only).
20
As soon as the UPS is energized, the battery begins charging. Eight hours are required to charge to the full rated
backup time.
3400723200/AC - Page 15
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
A Pulsar Evolution 1500 tower UPS has been used below to illustrate the instructions. The principle is the same for all the
other tower and rack models.
2.4 Connection to the RS232 or USB communications port (optional)
The RS232 and USB communica-
tions ports cannot operate simulta-
neously.
21
V
ac OUT
I max 12A
1 - Connect the RS232 21 or USB 22 com-
munications cable to the serial port or the
USB port on the computer.
2
2
1
U.S. PA NO. 6,094,363
T
.
36Vdc, 9A
h
Pb
Mai
Netz
V
olt 120V~1O
mps 12A MAX
Hertz 50/60 Hz
A
1
R
Util
Volt 120V~1O
L
oad
22
Hertz 50/60 Hz
A
usg
W
/V 1000W/1440V
A
A
34Z5
U.P.S.
2 - Connect the other end of the communica-
344-50254-00
IN
OUT
tions cable 21 or 22 to the RS232
2
or
Data line protection
USB communications port on the UPS.
1
The UPS can now communicate with all
MGE UPS SYSTEMS supervision, set-up or
safety software.
2.5 Connection to the data-line protection port (optional)
The data-line protection function on the UPS
eliminates overvoltages flowing on the com-
puter-network lines.
V
ac OUT
I max 12A
Simply connect the line to be protected to the
UPS using the data-line protection connec-
tors (IN and OUT) as indicated opposite
(RJ45 cables not supplied).
2
U.S. PA NO. 6,094,363
T
.
36Vdc, 9Ah
Pb
R
Mains
Netz
eseau
V
olt 120V~1O
mps 12A MAX
Hertz 50/60 Hz
A
1
R
Util
V
o
l
t
1
2
0
V
~
1
O
L
oad
Hertz 50/60 Hz
W
Ausg
/VA 1000W/1440V
A
34Z5
U.P.S.
344-50254-00
IN
OUT
Data line
Page 16 - 3400723200/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Installation
2.6 Installation of the communications-card option
1 - Remove the slot cover 4 secured by two
screws.
4
2 - Insert the card in the slot.
V
ac OUT
I max 12A
Restricted-access slot for
the communications card
3 - Secure the card with the two screws.
2
U.S. PAT. NO. 6,094,363
36Vdc, 9Ah
Pb
R
Mains
Netz
eseau
V
olt
120V~1O
Amps 12A MAX
Hertz 50/60 Hz
1
R
Util
V
olt
Hertz 50/60 Hz
W/V 1000W/1440V
120V~1O
L
oad
Ausg
A
A
34Z5
U.P.S.
344-50254-00
IN
OUT
Data line protection
It is not necessary to shut down the UPS to install the communications card.
This operation must be carried out by qualified personnel.
3400723200/AC - Page 17
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Operation
3.1 Start-up
Press the ON / OFF button 10 .
The buzzer beeps and all the LEDs come ON.
The buzzer beeps twice during the self-test, then button 10 remains ON,
indicating that the receptacles are supplied with power.
- AC power is present: Only button 10 is ON. The protected equipment
is supplied by the AC-power source.
- AC power is absent: Button 10 and LED 11 are ON. The protected
equipment is supplied by the UPS, operating on battery power.
10
11
12
1
2
All the connected equipment is supplied with power.
%
%
If button 10 or LED 11 are not ON or if LED 12 is ON, there is a
fault (see section 4.1).
Note: The battery is charged as soon as the UPS is connected to the AC-power source, even if button 10 is in the OFF
position.
3.2 Shift to booster or fader mode
(during voltage variations in the AC-input power)
The booster and fader functions maintain the output voltage supplied by
the UPS within close tolerances around the rated value even if significant
voltage variations occur in the AC-input power. This avoids calling on bat-
tery power.
The values defining the voltage range may be set using the UPS Driver
software.
During operation in booster or fader mode, LED 16 is ON, signalling a
significant voltage variation in the AC-input power.
1
2
16
%
%
Page 18 - 3400723200/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Operation
3.3 Operation on battery power (following failure of AC-input power)
Transfer to battery power
The AC-input power is out of tolerances, LED 11 goes ON.
During operation on battery power, the buzzer beeps every ten seconds.
The equipment connected to the UPS is supplied by the battery.
11
1
2
%
%
Threshold for the low-battery warning
When the threshold is reached, the buzzer beeps every three seconds.
The low-battery warning threshold can be set by the user, with the “UPS
Driver” software.
There is very little remaining battery backup time. Close all applica-
tions because UPS automatic shutdown is imminent.
11
When the battery reaches the end of its backup time, the UPS shuts down
and all the LEDs go OFF.
1
2
The equipment is no longer supplied with power.
%
%
The UPS automatically restarts when power returns.
If the UPS does not restart, check that the “automatic restart when power returns” function has not been disabled (see sec-
tion 3.4 Personalization).
3400723200/AC - Page 19
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Operation
3.4 Personalization (optional)
Function
Personalization parameters can be set and modified using the UPS Driver software installed on a computer that is connect-
ed to the UPS (see section 2.4 Connection to the RS232 or USB communications port).
Check that the RS232 21 communications cable is connected.
UPS Driver installation:
1 - Insert the Solution-Pac CD-ROM containing the UPS Driver software in the drive of a PC running Windows.
2 - Open the Windows File manager or Explorer and select the CD-ROM drive.
3 - Double-click "\Emb\Evolutio\Config\upsdriv.exe".
Once UPS Driver has been installed, UPS parameters can be modified in a window containing a number of tabs, each pre-
senting a set of parameters :
ON / OFF conditions tab
Configurable function
Default setting
Enabled
Options
Disabled
Disabled
Disabled
Enabled
Disabled
Automatic restart
Cold start
Enabled
Forced reboot
Enabled
Energy saving
Disabled
Enabled
UPS ON / OFF via software
Battery tab
Configurable function
Interval between automatic battery tests
Low-battery warning threshold
Default setting
Options
Every day
Once a month
No test
Once a week
20% of the remaining battery back- 10 to 40% of the remaining battery
up time
backup time
Protection against deep discharges
Enabled
Disabled
Page 20 - 3400723200/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Operation
Voltage-thresholds tab
Configurable function
Default setting
120 V
Options
100 - 127 V
141 to 153 V
127 to 138 V
92 to 108 V
80 to 94 V
Output voltage on battery power
Upper threshold for transfer to battery power
Fader-mode cut-in threshold
151 V
132 V
Booster-mode cut-in threshold
102 V
Lower threshold for transfer to battery power
Maximum input-voltage range
89 V
Disabled
Enabled (1)
(1) Lower threshold for transfer to battery mode = 70 V
Sensitivity tab
Configurable function
Default setting
Options
UPS sensitivity level
Normal
High or low
For more information about these settings, refer to the Help function of the "UPS Driver" software.
3400723200/AC - Page 21
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Maintenance
4.1 Trouble-shooting
Troubleshooting not requiring MGE UPS SYSTEMS after-sales support (all versions)
Indication
Signification
Correction
LED 13 flashes and
the buzzer beeps once.
UPS overload. The power drawn by the connected
equipment exceeds UPS capacity.
Check the power drawn by the
equipment and disconnect any
non-priority devices.
LED 12 flashes.
A battery fault was detected during the automatic bat- Replace the battery module (see
tery test.
section 4.2).
Troubleshooting requiring MGE UPS SYSTEMS after-sales support
Indication
Signification
Correction
LED 12 goes ON and
UPS electronics have detected a UPS fault.
the buzzer sounds contin- ◗ The connected equipment is no longer supplied.
uously.
Call the after-sales support depart-
ment.
The equipment connected to the UPS is no
longer protected.
Page 22 - 3400723200/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Maintenance
4.2 Replacement of the battery module
Tower models
Safety rules
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and required
precautions. Keep unauthorized personnel away from batteries. Batteries constitute a danger (electrical shock,
burns). The short-circuit current may be very high. Precautions must be taken for all handling:
◗ remove all watches, rings, bracelets and any other metal objects;
◗ use tools with insulated handles.
Removal of the battery module
When replacing batteries, use the Battery Replacement Chart below to determine the correct battery.
This operation may be carried out with the UPS supplying power to the load.
A
- Unclip the small plate with the MGE
logo on the front panel of the UPS.
B
C
- Remove the two screws.
- Remove the left-hand side of the front
panel by pulling it slightly up and then for-
ward.
C
D
- Disconnect the battery module by
pulling apart the connectors (never pull on
the cables).
P
U
L
S
A
R
Evolution
1
1
0
0
B
A
Battery Replacement Chart
Component
Manufacturer Manufacturer’s
Catalog Number
6V 7,2A Bat (in 800VA Rack)
Panasonic
CSB
Panasonic
CSB
LC-R067R2CH1
GP1272F2
UP-RW0645CH1
HR1234wF2
12V 7,2A Bat (in 800VA Tower)
6V 9A Bat (in 1100VA Rack and 500VA)
12V 9A Bat (in 1100VA Tower)
D
3400723200/AC - Page 23
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Maintenance
E
- Remove the battery module by pulling
on the plastic tab and proceed with
replacement.
E
Installation of the new battery module
Carry out the above operation in reverse order.
◗ CAUTION: risk of electric arc when connecting the battery.
◗ To maintain an identical level of performance and safety, use a battery module identical to that previously
mounted in the UPS.
◗ Press the two parts of the battery connector tightly together to ensure proper connection.
Page 24 - 3400723200/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Maintenance
Rack models
Removal of the battery module
This operation may be carried out with the UPS supplying power to the load.
A
- Unclip the small plate with the MGE
logo on the front panel of the UPS.
B
C
- Remove the two screws.
- Remove the left-hand side of the front
panel by pulling it forward.
P
U
L
S
A
R
Evolution
1500 Rack
C
B
A
D
- Disconnect the battery module by
pulling apart the connectors (never pull on
the cables).
D
3400723200/AC - Page 25
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Maintenance
E
- Remove the cover.
E
F
- Remove the battery module by pulling
on the plastic tab and proceed with
replacement.
F
Installation of the new battery module
Carry out the above operation in reverse order.
◗ CAUTION: risk of electric arc when connecting the battery.
◗ To maintain an identical level of performance and safety, use a battery module identical to that previously
mounted in the UPS.
◗ Press the two parts of the battery connector tightly together to ensure proper connection.
Page 26 - 3400723200/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Environment
This product has been designed to respect the environment:
It does not contain CFCs or HCFCs.
UPS recycling at the end of service life:
MGE UPS SYSTEMS undertakes to recycle, by certified companies and in compliance with all applicable regulations, all
UPS products recovered at the end of their service life (contact your MGE branch office).
Packing:
UPS packing materials must be recycled in compliance with all applicable regulations.
WARNING:
This product contains lead-acid batteries. Lead is a dangerous substance for the environment if it is not properly recycled by
specialized companies.
3400723200/AC - Page 27
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Appendices
6.1 Technical data
Simplified diagram
Filter
Booster / fader transformer
Input
Output
Inverter
Charger
Battery
Page 28 - 3400723200/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Appendices
Technical characteristics
Pulsar Evolution
500
1500 Tower/1500 Rack
800 Tower/800 Rack 1100 Tower/1100 Rack
800 VA / 560 W 1100 VA / 700 W
Output rating
500 VA / 350 W
1500 VA / 1000 W
AC-input power
◗ Voltage
Single phase, 80 V to 153 V (1)
◗ Frequency
(2)
47 Hz to 70 Hz (50 Hz system) or 56.5 Hz to 70 Hz
(60 Hz system)
Output power (operation
on battery power)
◗ Voltage
Single-phase, 120 V (3) (+ 6% / - 10%)
50/60 Hz +/- 1 Hz
◗ Frequency
Battery (sealed lead-acid,
maintenance free)
◗ Tower models
3 x 12 V - 9 Ah,
6 x 6 V - 9 Ah
2 x 12 V - 7.2 Ah,
4 x 6 V - 7.2 Ah
2 x 12 V - 9 Ah,
4 x 6 V - 9 Ah
2 x 6 V - 9 Ah,
◗ Rack models
Environment
<40 dBA
0 to 35° C
20 to 90%
<40 dBA
0 to 40° C
20 to 90%
◗ Noise level (operation on
AC-input power)
◗ Operating temperature
◗ Relative humidity
(without condensation)
(1) The upper and lower thresholds may be set using the UPS Driver software.
(2) Or 40 Hz in low-sensitivity mode (may be set using the UPS Driver software).
(3) Adjustable from 100 to 127 V using the UPS Driver software.
3400723200/AC - Page 29
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Appendices
Examples of battery backup times
Pulsar Evolution 500
2 rack-optimized dense servers
1 router
1 hub
0
10
20
30
40
50
60
70
80
90 100 110 120 t (min)
Pulsar Evolution 800
3 rack-optimized dense servers
2 file/print servers
1 data server + 1 hub + 1 router
1 router
1 hub
0
10
20
30
40
50
60
70
80
90 100 110 120 t (min)
Pulsar Evolution 1100
3 rack-optimized dense servers
2 file/print servers
1 data server + 1 hub + 1 router
1 router
1 hub
0
10
20
30
40
50
60
70
80
90 100 110 120 t (min)
Pulsar Evolution 1500
5 rack-optimized dense servers
3 file/print servers
2 data servers + 1 hub + 1 router
1 router
0
10
20
30
40
50
60
70
80
90 100 110 120 t (min)
Page 30 - 3400723200/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Appendices
6.2 Glossary
Backup time
Time that the connected equipment can operate on battery power if AC-input power
fails.
Bargraph
Device on the front panel indicating the percent remaining backup time or the percent
load.
Booster mode
Automatic UPS operating mode whereby the input-power voltage is increased if it drops
below a value set in the personalization parameters, thus avoiding a battery discharge.
De-energized
Equipment
The UPS must be physically disconnected from the AC-input power.
Devices and systems connected to the UPS output.
Fader mode
Automatic UPS operating mode whereby the input-power voltage is decreased if it rises
above a value set in the personalization parameters, thus avoiding a battery discharge.
Input circuit breaker
Personalization
Circuit breaker protecting the upstream distribution system against UPS faults.
The parameters for a number of UPS functions may be modified using the UPS Driver
software to adapt UPS operation to user needs.
Programmable receptacles
Pulsar Evolution has two programmable receptacles. They may be used for sequential
start-up of protected equipment, shedding of non-critical loads during operation on
battery power or management of operating priorities to provide the most critical devices
with more backup time before battery power runs out. These receptacles may be
programmed using the Solution-Pac software on the CD-ROM supplied with the UPS.
Receptacles
Receptacle that allows you to connect the equipment you want to protect.
For UPS connection to a computer via the serial port.
RS232 communications port
Solution-Pac
MGE UPS SYSTEMS safety, set-up and supervision software suite on the CD-ROM
supplied with the UPS.
UPS
Uninterruptible Power Supply.
UPS Driver
Communications software on the CD-ROM supplied with the UPS. It may be used to
personalize the default settings.
USB communications port
For UPS connection to a computer via the USB port.
3400723200/AC - Page 31
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Appendices
6.3 Index
Booster mode ......................................................9, 18
Fader mode ........................................................9, 18
Sleep mode (automatic start) ..................................20
A
Automatic start ................................................................20
B
Bargraph............................................................................9
Battery
O
Overloads....................................................................9, 22
Backup time ............................................................30
End of backup time..................................................19
Fault ..........................................................................9
Personalization ........................................................20
Recycling ................................................................27
Replacement ..............................................22, 23, 24
Threshold for low-battery warning ..........................19
Transfer to battery power ....................................9, 19
P
Personalization ..............................................................20
Battery ....................................................................20
ON / OFF conditions ..............................................20
Output......................................................................21
Ports
RS232 ................................................................8, 16
USB ....................................................................8, 16
Programmable receptacles ..........................................8, 9
Buttons ..............................................................................9
Buzzer ............................................................................19
S
C
Safety..............................................................................23
Start-up ..........................................................................18
Circuit breakers
Battery circuit breaker................................................8
Input circuit breaker ..................................................8
Communication
T
Technical characteristics ................................................29
Temperature (excessive ambient) ..................................29
Cards ..................................................................8, 17
Ports ....................................................................8, 16
Connections
U
Data-line protection..................................................16
RS232 communications port ..................................16
USB communications port ......................................16
UPS Driver....................................................18, 19, 20, 29
UPS ON / OFF via software ..........................................20
W
D
Web site..........................................................................27
Weight ..............................................................................7
Dimensions........................................................................7
E
Environment ....................................................................27
F
Fault (UPS)........................................................................9
L
LEDs..................................................................................9
M
Mode
Page 32 - 3400723200/AC
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
1660 Scenic Avenue
Costa Mesa, CA 92626
USA
Download from Www.Somanuals.com. All Manuals Search And Download.
|