MGE UPS Systems Power Supply 1100 Tower User Manual

MGE UPS SYSTEMS  
Pulsar Evolution  
1500 Tower/1500 Rack  
1100 Tower/1100 Rack  
800 Tower/800 Rack  
500 Rack  
Installation and user  
manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
CAUTION: Safety of persons  
The UPS has its own internal power source (the battery). Consequently, the power outlets may be energized even if the UPS is  
disconnected from the AC-power source.  
Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified service personnel.  
The UPS must be properly earthed. Measurements are required to ensure that the total leakage current of the UPS and the  
protected equipment does not exceed 3.5 mA by checking their characteristics (maximum leakage current of the UPS = 2 mA).  
The battery supplied with the UPS contains small amounts of toxic materials. To avoid accidents, the directives listed below  
must be observed:  
-
-
-
-
Never burn the battery (risk of explosion).  
Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).  
Comply with all applicable regulations for the disposal of the battery.  
Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high. Precautions must be  
taken for all handling: remove watches, rings, bracelets and any other metal objects, use tools with insulated handles.  
Do not lay tools or metal parts on top of batteries.  
-
CAUTION: Product safety  
The UPS connection instructions and operation described in the manual must be followed in the indicated order.  
UPS must be connected to a nearby wall outlet that is easily accessible. The UPS can be disconnected from the AC-power  
source by removing the power cord.  
Check that the indications on the rating plate correspond to your AC-power system and to the actual electrical consumption of  
all the equipment to be connected to the UPS.  
Never install the UPS near liquids or in an excessively damp environment.  
Never let a foreign body penetrate inside the UPS.  
Never block the ventilation grates of the UPS.  
Never expose the UPS to direct sunlight or source of heat.  
If the UPS must be stored prior to installation, storage must be in a dry place.  
The admissible storage temperature range is -25ºC to +55ºC.  
Special precautions  
All handling operations will require at least two people (unpacking, installation in rack system).  
Once installed and connected to the AC power source for the first time, the battery will start to charge. Full charging to obtain  
the rated battery backup time requires at least 8 hours.  
Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be energized for a period of  
24 hours, at least once every 6 months (for a normal storage temperature less than 25°C). This charges the battery, thus  
avoiding possible irreversible damage. During the replacement of the battery module, it is imperative to use the same type and  
number of element previously mounted in the UPS, in order to maintain an identical level of performance and safety. In case of  
doubt, don’t hesitate to contact our after sales department (for more information, refer to the web site www.mgeups.com).  
3400723200/AC - Page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Foreword  
Using this document  
Information may be found in two ways, using:  
the contents;  
the index.  
Pictograms  
Important instructions that must always be followed.  
Information, advice, help.  
Visual indication.  
Action.  
Audio indication.  
In the illustrations on the following pages, the symbols below are used:  
LED off.  
LED on.  
LED flashing.  
Page 4 - 3400723200/AC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
1. Presentation  
1.1 Overall view.................................................................................................................................. 7  
Tower models ..................................................................................................................................7  
Rack models ....................................................................................................................................7  
1.2 Back .............................................................................................................................................. 8  
1.3 Control panel..................................................................................................................................9  
2. Installation  
2.1 Unpacking and parts check ......................................................................................................10  
Tower models ................................................................................................................................10  
Rack models ..................................................................................................................................11  
2.2 Installation ....................................................................................................................................12  
Tower models ................................................................................................................................12  
800/1100/1500 Rack models..........................................................................................................13  
500 Rack model ............................................................................................................................14  
2.3 Connecting the protected equipment ........................................................................................15  
2.4 Connection to the RS232 or USB communications port (optional) ........................................16  
2.5 Connection to the data-line protection port (optional)..............................................................16  
2.6 Installation of the communications-card option ......................................................................17  
3. Operation  
3.1 Start-up..........................................................................................................................................18  
3.2 Shift to booster or fader mode (during voltage variations in the AC-input power) ....................18  
3.3 Operation on battery power (following failure of AC-input power) ............................................19  
Transfer to battery power ..............................................................................................................19  
Threshold for the low-battery warning............................................................................................19  
3.4 Personalization (optional) ............................................................................................................20  
Function..........................................................................................................................................20  
ON / OFF conditions tab ................................................................................................................20  
Battery tab......................................................................................................................................20  
Voltage-thresholds tab ..................................................................................................................21  
Sensitivity tab ................................................................................................................................21  
3400723200/AC - Page 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
4. Maintenance  
4.1 Trouble-shooting..........................................................................................................................22  
4.2 Replacement of the battery module ..........................................................................................23  
Tower models ................................................................................................................................23  
Rack models ..................................................................................................................................25  
5. Environment ....................................................................................................................................27  
6. Appendices  
6.1 Technical data  
Simplified diagram..........................................................................................................................28  
Technical characteristics ................................................................................................................29  
Examples of battery backup times ................................................................................................30  
6.2 Glossary........................................................................................................................................31  
6.3 Index..............................................................................................................................................32  
Page 6 - 3400723200/AC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Presentation  
1.1 Overall view  
Tower models  
Dimensions in inches  
(W x H x D)  
D
Evolution 800 Tower  
5.9 x 9.3 x 16.3  
5.9 x 9.3 x 16.3  
5.9 x 9.3 x 19  
Evolution 1100 Tower  
Evolution 1500 Tower  
Weight in lbs  
Evolution 800 Tower  
Evolution 1100 Tower  
Evolution 1500 XL Tower  
23  
25.4  
33  
H
P
U
L
S
A
R
Evolution  
1
1
0
0
W
Rack models  
Dimensions in inches  
(W x H x D)  
D
Evolution 500 Rack 17.2 (19”) x 1.7 (1U) x 13.9  
Evolution 800 Rack 17.2 (19”) x 1.7 (1U) x 19.6  
Evolution 1100 Rack 17.2 (19”) x 1.7 (1U) x 19.6  
Evolution 1500 Rack 17.2 (19”) x 1.7 (1U) x 20.5  
H
Weight in lbs  
P
U
L
S
A
R
Evolution  
W
1500 Rack  
Evolution 500 Rack  
Evolution 800 Rack  
Evolution 1100 Rack  
Evolution 1500 Rack  
20  
34  
35  
42  
3400723200/AC - Page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Presentation  
1.2 Back  
Pulsar Evolution 800 / 1100 / 1500 Tower  
Pulsar Evolution:  
1
2
3
USB communications port.  
RS232 communications port.  
Data-line protection.  
V
ac OUT  
I max 12A  
4
5
6
2
2
1
2
1
Slot for communications-card option.  
U.S. PA NO. 6,094,363  
T
.
4
5
36Vdc, 9A  
h
Pb  
R
Mains  
Netz  
eseau  
V
olt 120V~1O  
mps 12A MAX  
Hertz 50/60 Hz  
A
1
R
Util  
Volt 120V~1O  
L
oad  
Hertz 50/60 Hz  
A
usg  
W
/V 1000W/1440V  
A
A
34Z5  
U.P.S.  
Receptacle for direct connection of  
protected equipment.  
344-50254-00  
IN  
OUT  
Data line protection  
8
7
6
7
Programmable receptacles (1 and 2).  
Input circuit-breaker.  
3
8
Connection to the utility.  
Pulsar Evolution 500 / 800 / 1100 Rack  
1
2
8
7
5
6
3
2
1
4
Pulsar Evolution 1500 Rack  
T20A/125V  
36Vdc, 9A  
~
h
Vac OUT  
I
max 12A  
Programmable  
R
1
2
Pb  
34Z5  
U.P.S.  
U.S. PA No. 6,094,363  
T
.
IN  
OUT  
A
C
I
nput  
V
olt  
mp  
ertz 50/60  
120V~1O  
A
s
12A  
M
AX  
RS232  
Data line protection  
SITE WIRING  
FAUL  
H
Hz  
AC  
Output  
V
olt  
120V~1O  
T
344-50248-00  
H
e
r
t
z
5
0
/
6
0
Hz  
/1440V  
Vac IN  
W
/
VA  
1000W  
A
1
2
4
8
7
2
1
3
5
6
Page 8 - 3400723200/AC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Presentation  
1.3 Control panel  
Illuminated ON/OFF button for the receptacles.  
10  
Operation on battery power.  
UPS fault.  
11  
12  
Battery fault.  
Overload.  
13  
14  
15  
16  
Group 1 programmable receptacles supplied with power.  
Group 2 programmable receptacles supplied with power.  
Booster or fader mode.  
1
2
Bargraph indicating percent load at output.  
17  
%
%
18 Bargraph indicating the battery charge level.  
76 to 100%.  
51 to 75%.  
26 to 50%.  
0 to 25%.  
3400723200/AC - Page 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
2.1 Unpacking and parts check  
Tower models  
20  
21  
22  
23  
24  
R
A
tion  
P
U
L
S
Evolu  
1
1
0
0
RS232 communications cable for Windows Operating Systems. For Unix/Linux Operating Systems, please order for  
free the following part number: 66090  
21  
22  
23  
24  
USB communications cable.  
CD-ROM with the Solution-Pac and UPS Driver software.  
Product documentation.  
Page 10 - 3400723200/AC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
Rack models  
20  
21  
22  
23  
25  
24  
26  
P
U
L
S
A
R
Evolution  
1500 Rack  
RS232 communications cable for Windows Operating Systems. For Unix/Linux Operating Systems, please order for  
free the following part number: 66090  
21  
USB communications cable.  
22  
23  
24  
25  
CD-ROM with the Solution-Pac and UPS Driver software.  
Product documentation.  
Telescopic rails for mounting in 19" bay with mounting hardware.  
26 Securing system for equipment power cords.  
3400723200/AC - Page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
2.2 Installation  
Tower models  
P
U
L
S
A
R
Evolution  
1
1
0
0
P
U
L
S
A
R
Evolution  
1
1
0
0
Page 12 - 3400723200/AC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
800/1100/1500 Rack models  
Follow steps 1 to 6 for rack mounting of the UPS on the rails.  
2
1
6
2
2
4
3
5
2
P
U
L
S
A
R
Evolution  
1500 Rack  
6
5
3
The rails and the necessary mounting hardware are supplied by MGE UPS SYSTEMS.  
For step 1, screw quantity shown is for 1500 VA. 800 and 1100 VA use two screws for each side.  
3400723200/AC - Page 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
500 Rack model  
Follow steps 1 to 3 for rack mounting of the UPS on the rails.  
2
1
P
U
L
S
A
R
Evolution  
1500 Rack  
3
1
3
Floor Mount Configuration  
Wall Mount Configuration  
A
io  
R
n
L
S
P
U
Evolut  
1500 Rack  
R
P
U
L
S
A
Evolution  
1500 Rack  
Page 14 - 3400723200/AC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
2.3 Connecting the protected equipment  
A Pulsar Evolution 1500 tower UPS has been used below to illustrate the instructions. The principle is the same for all the  
other tower and rack models.  
Check that the indications on the rating plate on the back of the UPS correspond to your AC-power system and to  
the actual electrical consumption of all the equipment to be connected to the UPS.  
1 - Remove the power cord supplying the  
equipment to be protected.  
2 - Connect the power cord to the AC-power  
Vac OUT  
I max 12A  
wall receptacle 8 .  
3 - Connect the protected equipment to the  
UPS using the cord 20 . Connect critical  
loads to the two standard receptacles 5 and  
any non-critical loads to the two program-  
5
mable receptacles  
6
(1 and 2).  
2
1
2
If the UPS is connected to a  
computer running MGE communi-  
cations software, it is possible to  
program the interruption of power  
to the programmable receptacles  
U.S. PAT. NO. 6,094,363  
6
36Vdc, 9Ah  
Pb  
Reseau  
Mains  
Netz  
Volt  
120V~1O  
Amps 12A MAX  
Hertz 50/60 Hz  
1
R
Util  
Load  
Ausg  
V
olt  
Hertz 50/60 Hz  
W/V 1000W/1440V  
120V~1O  
A
A
34Z5  
U.P.S.  
344-50254-00  
IN  
OUT  
6
during operation on battery  
power, thus reserving backup  
power for the critical loads.  
ata line protection  
8
4 - Lock the connections using the securing  
system 26 (for rack models only).  
20  
As soon as the UPS is energized, the battery begins charging. Eight hours are required to charge to the full rated  
backup time.  
3400723200/AC - Page 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
A Pulsar Evolution 1500 tower UPS has been used below to illustrate the instructions. The principle is the same for all the  
other tower and rack models.  
2.4 Connection to the RS232 or USB communications port (optional)  
The RS232 and USB communica-  
tions ports cannot operate simulta-  
neously.  
21  
V
ac OUT  
I max 12A  
1 - Connect the RS232 21 or USB 22 com-  
munications cable to the serial port or the  
USB port on the computer.  
2
2
1
U.S. PA NO. 6,094,363  
T
.
36Vdc, 9A  
h
Pb  
Mai
Netz  
V
olt 120V~1O  
mps 12A MAX  
Hertz 50/60 Hz  
A
1
R
Util  
Volt 120V~1O  
L
oad  
22  
Hertz 50/60 Hz  
A
usg  
W
/V 1000W/1440V  
A
A
34Z5  
U.P.S.  
2 - Connect the other end of the communica-  
344-50254-00  
IN  
OUT  
tions cable 21 or 22 to the RS232  
2
or  
Data line protection  
USB communications port on the UPS.  
1
The UPS can now communicate with all  
MGE UPS SYSTEMS supervision, set-up or  
safety software.  
2.5 Connection to the data-line protection port (optional)  
The data-line protection function on the UPS  
eliminates overvoltages flowing on the com-  
puter-network lines.  
V
ac OUT  
I max 12A  
Simply connect the line to be protected to the  
UPS using the data-line protection connec-  
tors (IN and OUT) as indicated opposite  
(RJ45 cables not supplied).  
2
U.S. PA NO. 6,094,363  
T
.
36Vdc, 9Ah  
Pb  
R
Mains  
Netz  
eseau  
V
olt 120V~1O  
mps 12A MAX  
Hertz 50/60 Hz  
A
1
R
Util  
V
o
l
t
1
2
0
V
~
1
O
L
oad  
Hertz 50/60 Hz  
W
Ausg  
/VA 1000W/1440V  
A
34Z5  
U.P.S.  
344-50254-00  
IN  
OUT  
Data line
Page 16 - 3400723200/AC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Installation  
2.6 Installation of the communications-card option  
1 - Remove the slot cover 4 secured by two  
screws.  
4
2 - Insert the card in the slot.  
V
ac OUT  
I max 12A  
Restricted-access slot for  
the communications card  
3 - Secure the card with the two screws.  
2
U.S. PAT. NO. 6,094,363  
36Vdc, 9Ah  
Pb  
R
Mains  
Netz  
eseau  
V
olt  
120V~1O  
Amps 12A MAX  
Hertz 50/60 Hz  
1
R
Util  
V
olt  
Hertz 50/60 Hz  
W/V 1000W/1440V  
120V~1O  
L
oad  
Ausg  
A
A
34Z5  
U.P.S.  
344-50254-00  
IN  
OUT  
Data line protection  
It is not necessary to shut down the UPS to install the communications card.  
This operation must be carried out by qualified personnel.  
3400723200/AC - Page 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Operation  
3.1 Start-up  
Press the ON / OFF button 10 .  
The buzzer beeps and all the LEDs come ON.  
The buzzer beeps twice during the self-test, then button 10 remains ON,  
indicating that the receptacles are supplied with power.  
- AC power is present: Only button 10 is ON. The protected equipment  
is supplied by the AC-power source.  
- AC power is absent: Button 10 and LED 11 are ON. The protected  
equipment is supplied by the UPS, operating on battery power.  
10  
11  
12  
1
2
All the connected equipment is supplied with power.  
%
%
If button 10 or LED 11 are not ON or if LED 12 is ON, there is a  
fault (see section 4.1).  
Note: The battery is charged as soon as the UPS is connected to the AC-power source, even if button 10 is in the OFF  
position.  
3.2 Shift to booster or fader mode  
(during voltage variations in the AC-input power)  
The booster and fader functions maintain the output voltage supplied by  
the UPS within close tolerances around the rated value even if significant  
voltage variations occur in the AC-input power. This avoids calling on bat-  
tery power.  
The values defining the voltage range may be set using the UPS Driver  
software.  
During operation in booster or fader mode, LED 16 is ON, signalling a  
significant voltage variation in the AC-input power.  
1
2
16  
%
%
Page 18 - 3400723200/AC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Operation  
3.3 Operation on battery power (following failure of AC-input power)  
Transfer to battery power  
The AC-input power is out of tolerances, LED 11 goes ON.  
During operation on battery power, the buzzer beeps every ten seconds.  
The equipment connected to the UPS is supplied by the battery.  
11  
1
2
%
%
Threshold for the low-battery warning  
When the threshold is reached, the buzzer beeps every three seconds.  
The low-battery warning threshold can be set by the user, with the “UPS  
Driver” software.  
There is very little remaining battery backup time. Close all applica-  
tions because UPS automatic shutdown is imminent.  
11  
When the battery reaches the end of its backup time, the UPS shuts down  
and all the LEDs go OFF.  
1
2
The equipment is no longer supplied with power.  
%
%
The UPS automatically restarts when power returns.  
If the UPS does not restart, check that the “automatic restart when power returns” function has not been disabled (see sec-  
tion 3.4 Personalization).  
3400723200/AC - Page 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Operation  
3.4 Personalization (optional)  
Function  
Personalization parameters can be set and modified using the UPS Driver software installed on a computer that is connect-  
ed to the UPS (see section 2.4 Connection to the RS232 or USB communications port).  
Check that the RS232 21 communications cable is connected.  
UPS Driver installation:  
1 - Insert the Solution-Pac CD-ROM containing the UPS Driver software in the drive of a PC running Windows.  
2 - Open the Windows File manager or Explorer and select the CD-ROM drive.  
3 - Double-click "\Emb\Evolutio\Config\upsdriv.exe".  
Once UPS Driver has been installed, UPS parameters can be modified in a window containing a number of tabs, each pre-  
senting a set of parameters :  
ON / OFF conditions tab  
Configurable function  
Default setting  
Enabled  
Options  
Disabled  
Disabled  
Disabled  
Enabled  
Disabled  
Automatic restart  
Cold start  
Enabled  
Forced reboot  
Enabled  
Energy saving  
Disabled  
Enabled  
UPS ON / OFF via software  
Battery tab  
Configurable function  
Interval between automatic battery tests  
Low-battery warning threshold  
Default setting  
Options  
Every day  
Once a month  
No test  
Once a week  
20% of the remaining battery back- 10 to 40% of the remaining battery  
up time  
backup time  
Protection against deep discharges  
Enabled  
Disabled  
Page 20 - 3400723200/AC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Operation  
Voltage-thresholds tab  
Configurable function  
Default setting  
120 V  
Options  
100 - 127 V  
141 to 153 V  
127 to 138 V  
92 to 108 V  
80 to 94 V  
Output voltage on battery power  
Upper threshold for transfer to battery power  
Fader-mode cut-in threshold  
151 V  
132 V  
Booster-mode cut-in threshold  
102 V  
Lower threshold for transfer to battery power  
Maximum input-voltage range  
89 V  
Disabled  
Enabled (1)  
(1) Lower threshold for transfer to battery mode = 70 V  
Sensitivity tab  
Configurable function  
Default setting  
Options  
UPS sensitivity level  
Normal  
High or low  
For more information about these settings, refer to the Help function of the "UPS Driver" software.  
3400723200/AC - Page 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Maintenance  
4.1 Trouble-shooting  
Troubleshooting not requiring MGE UPS SYSTEMS after-sales support (all versions)  
Indication  
Signification  
Correction  
LED 13 flashes and  
the buzzer beeps once.  
UPS overload. The power drawn by the connected  
equipment exceeds UPS capacity.  
Check the power drawn by the  
equipment and disconnect any  
non-priority devices.  
LED 12 flashes.  
A battery fault was detected during the automatic bat- Replace the battery module (see  
tery test.  
section 4.2).  
Troubleshooting requiring MGE UPS SYSTEMS after-sales support  
Indication  
Signification  
Correction  
LED 12 goes ON and  
UPS electronics have detected a UPS fault.  
the buzzer sounds contin- The connected equipment is no longer supplied.  
uously.  
Call the after-sales support depart-  
ment.  
The equipment connected to the UPS is no  
longer protected.  
Page 22 - 3400723200/AC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Maintenance  
4.2 Replacement of the battery module  
Tower models  
Safety rules  
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and required  
precautions. Keep unauthorized personnel away from batteries. Batteries constitute a danger (electrical shock,  
burns). The short-circuit current may be very high. Precautions must be taken for all handling:  
remove all watches, rings, bracelets and any other metal objects;  
use tools with insulated handles.  
Removal of the battery module  
When replacing batteries, use the Battery Replacement Chart below to determine the correct battery.  
This operation may be carried out with the UPS supplying power to the load.  
A
- Unclip the small plate with the MGE  
logo on the front panel of the UPS.  
B
C
- Remove the two screws.  
- Remove the left-hand side of the front  
panel by pulling it slightly up and then for-  
ward.  
C
D
- Disconnect the battery module by  
pulling apart the connectors (never pull on  
the cables).  
P
U
L
S
A
R
Evolution  
1
1
0
0
B
A
Battery Replacement Chart  
Component  
Manufacturer Manufacturer’s  
Catalog Number  
6V 7,2A Bat (in 800VA Rack)  
Panasonic  
CSB  
Panasonic  
CSB  
LC-R067R2CH1  
GP1272F2  
UP-RW0645CH1  
HR1234wF2  
12V 7,2A Bat (in 800VA Tower)  
6V 9A Bat (in 1100VA Rack and 500VA)  
12V 9A Bat (in 1100VA Tower)  
D
3400723200/AC - Page 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Maintenance  
E
- Remove the battery module by pulling  
on the plastic tab and proceed with  
replacement.  
E
Installation of the new battery module  
Carry out the above operation in reverse order.  
CAUTION: risk of electric arc when connecting the battery.  
To maintain an identical level of performance and safety, use a battery module identical to that previously  
mounted in the UPS.  
Press the two parts of the battery connector tightly together to ensure proper connection.  
Page 24 - 3400723200/AC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Maintenance  
Rack models  
Removal of the battery module  
This operation may be carried out with the UPS supplying power to the load.  
A
- Unclip the small plate with the MGE  
logo on the front panel of the UPS.  
B
C
- Remove the two screws.  
- Remove the left-hand side of the front  
panel by pulling it forward.  
P
U
L
S
A
R
Evolution  
1500 Rack  
C
B
A
D
- Disconnect the battery module by  
pulling apart the connectors (never pull on  
the cables).  
D
3400723200/AC - Page 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Maintenance  
E
- Remove the cover.  
E
F
- Remove the battery module by pulling  
on the plastic tab and proceed with  
replacement.  
F
Installation of the new battery module  
Carry out the above operation in reverse order.  
CAUTION: risk of electric arc when connecting the battery.  
To maintain an identical level of performance and safety, use a battery module identical to that previously  
mounted in the UPS.  
Press the two parts of the battery connector tightly together to ensure proper connection.  
Page 26 - 3400723200/AC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Environment  
This product has been designed to respect the environment:  
It does not contain CFCs or HCFCs.  
UPS recycling at the end of service life:  
MGE UPS SYSTEMS undertakes to recycle, by certified companies and in compliance with all applicable regulations, all  
UPS products recovered at the end of their service life (contact your MGE branch office).  
Packing:  
UPS packing materials must be recycled in compliance with all applicable regulations.  
WARNING:  
This product contains lead-acid batteries. Lead is a dangerous substance for the environment if it is not properly recycled by  
specialized companies.  
3400723200/AC - Page 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Appendices  
6.1 Technical data  
Simplified diagram  
Filter  
Booster / fader transformer  
Input  
Output  
Inverter  
Charger  
Battery  
Page 28 - 3400723200/AC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Appendices  
Technical characteristics  
Pulsar Evolution  
500  
1500 Tower/1500 Rack  
800 Tower/800 Rack 1100 Tower/1100 Rack  
800 VA / 560 W 1100 VA / 700 W  
Output rating  
500 VA / 350 W  
1500 VA / 1000 W  
AC-input power  
Voltage  
Single phase, 80 V to 153 V (1)  
Frequency  
(2)  
47 Hz to 70 Hz (50 Hz system) or 56.5 Hz to 70 Hz  
(60 Hz system)  
Output power (operation  
on battery power)  
Voltage  
Single-phase, 120 V (3) (+ 6% / - 10%)  
50/60 Hz +/- 1 Hz  
Frequency  
Battery (sealed lead-acid,  
maintenance free)  
Tower models  
3 x 12 V - 9 Ah,  
6 x 6 V - 9 Ah  
2 x 12 V - 7.2 Ah,  
4 x 6 V - 7.2 Ah  
2 x 12 V - 9 Ah,  
4 x 6 V - 9 Ah  
2 x 6 V - 9 Ah,  
Rack models  
Environment  
<40 dBA  
0 to 35° C  
20 to 90%  
<40 dBA  
0 to 40° C  
20 to 90%  
Noise level (operation on  
AC-input power)  
Operating temperature  
Relative humidity  
(without condensation)  
(1) The upper and lower thresholds may be set using the UPS Driver software.  
(2) Or 40 Hz in low-sensitivity mode (may be set using the UPS Driver software).  
(3) Adjustable from 100 to 127 V using the UPS Driver software.  
3400723200/AC - Page 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Appendices  
Examples of battery backup times  
Pulsar Evolution 500  
2 rack-optimized dense servers  
1 router  
1 hub  
0
10  
20  
30  
40  
50  
60  
70  
80  
90 100 110 120 t (min)  
Pulsar Evolution 800  
3 rack-optimized dense servers  
2 file/print servers  
1 data server + 1 hub + 1 router  
1 router  
1 hub  
0
10  
20  
30  
40  
50  
60  
70  
80  
90 100 110 120 t (min)  
Pulsar Evolution 1100  
3 rack-optimized dense servers  
2 file/print servers  
1 data server + 1 hub + 1 router  
1 router  
1 hub  
0
10  
20  
30  
40  
50  
60  
70  
80  
90 100 110 120 t (min)  
Pulsar Evolution 1500  
5 rack-optimized dense servers  
3 file/print servers  
2 data servers + 1 hub + 1 router  
1 router  
0
10  
20  
30  
40  
50  
60  
70  
80  
90 100 110 120 t (min)  
Page 30 - 3400723200/AC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Appendices  
6.2 Glossary  
Backup time  
Time that the connected equipment can operate on battery power if AC-input power  
fails.  
Bargraph  
Device on the front panel indicating the percent remaining backup time or the percent  
load.  
Booster mode  
Automatic UPS operating mode whereby the input-power voltage is increased if it drops  
below a value set in the personalization parameters, thus avoiding a battery discharge.  
De-energized  
Equipment  
The UPS must be physically disconnected from the AC-input power.  
Devices and systems connected to the UPS output.  
Fader mode  
Automatic UPS operating mode whereby the input-power voltage is decreased if it rises  
above a value set in the personalization parameters, thus avoiding a battery discharge.  
Input circuit breaker  
Personalization  
Circuit breaker protecting the upstream distribution system against UPS faults.  
The parameters for a number of UPS functions may be modified using the UPS Driver  
software to adapt UPS operation to user needs.  
Programmable receptacles  
Pulsar Evolution has two programmable receptacles. They may be used for sequential  
start-up of protected equipment, shedding of non-critical loads during operation on  
battery power or management of operating priorities to provide the most critical devices  
with more backup time before battery power runs out. These receptacles may be  
programmed using the Solution-Pac software on the CD-ROM supplied with the UPS.  
Receptacles  
Receptacle that allows you to connect the equipment you want to protect.  
For UPS connection to a computer via the serial port.  
RS232 communications port  
Solution-Pac  
MGE UPS SYSTEMS safety, set-up and supervision software suite on the CD-ROM  
supplied with the UPS.  
UPS  
Uninterruptible Power Supply.  
UPS Driver  
Communications software on the CD-ROM supplied with the UPS. It may be used to  
personalize the default settings.  
USB communications port  
For UPS connection to a computer via the USB port.  
3400723200/AC - Page 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Appendices  
6.3 Index  
Booster mode ......................................................9, 18  
Fader mode ........................................................9, 18  
Sleep mode (automatic start) ..................................20  
A
Automatic start ................................................................20  
B
Bargraph............................................................................9  
Battery  
O
Overloads....................................................................9, 22  
Backup time ............................................................30  
End of backup time..................................................19  
Fault ..........................................................................9  
Personalization ........................................................20  
Recycling ................................................................27  
Replacement ..............................................22, 23, 24  
Threshold for low-battery warning ..........................19  
Transfer to battery power ....................................9, 19  
P
Personalization ..............................................................20  
Battery ....................................................................20  
ON / OFF conditions ..............................................20  
Output......................................................................21  
Ports  
RS232 ................................................................8, 16  
USB ....................................................................8, 16  
Programmable receptacles ..........................................8, 9  
Buttons ..............................................................................9  
Buzzer ............................................................................19  
S
C
Safety..............................................................................23  
Start-up ..........................................................................18  
Circuit breakers  
Battery circuit breaker................................................8  
Input circuit breaker ..................................................8  
Communication  
T
Technical characteristics ................................................29  
Temperature (excessive ambient) ..................................29  
Cards ..................................................................8, 17  
Ports ....................................................................8, 16  
Connections  
U
Data-line protection..................................................16  
RS232 communications port ..................................16  
USB communications port ......................................16  
UPS Driver....................................................18, 19, 20, 29  
UPS ON / OFF via software ..........................................20  
W
D
Web site..........................................................................27  
Weight ..............................................................................7  
Dimensions........................................................................7  
E
Environment ....................................................................27  
F
Fault (UPS)........................................................................9  
L
LEDs..................................................................................9  
M
Mode  
Page 32 - 3400723200/AC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1660 Scenic Avenue  
Costa Mesa, CA 92626  
USA  
Download from Www.Somanuals.com. All Manuals Search And Download.  

La Crosse Technology Clock WT 5350 User Manual
LG Electronics Clothes Dryer DLEX3001 User Manual
Life Fitness Exercise Bike CPO CLSX User Manual
Lindy Network Router 25130 User Manual
Lochinvar Water Heater CF 401 751 User Manual
Magnadyne Stereo Receiver M9900CD User Manual
Marantz Universal Remote RC5400 User Manual
Maytag Clothes Dryer W10240579B User Manual
MGE UPS Systems Power Supply EX10 User Manual
Microsoft Computer Hardware P2289A User Manual