PSPA722
LUXPRO PSPA722
INSTALLATION AND OPERATING INSTRUCTIONS
52071
®
1
COMPATIBILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
ELECTRICAL RATINGS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
TOOLS REQUIRED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
REMOVAL OF OLD UNIT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
MOUNTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
6.2.1 WEEKDAY PROGRAMMING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2
6.2.2 WEEKEND PROGRAMMING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3
6.3
6.4
7
FAN PROGRAMMING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
COPY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ADVANCED FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
KEYBOARD LOCK. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
FILTER MONITOR. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4
4.1
4.2
4.3
4.4
4.5
7.1
7.2
7.2.1 FILTER USAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
7.2.2 FILTER LIMIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.5.1 TERMINAL DESCRIPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4.5.2 CONNECTING THE WIRES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
7.3
7.4
7.5
ENERGY USAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
CALIBRATION OFFSET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.6
5
COMPLETING YOUR INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . 3
OPERATING BASICS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
UP/DOWN CHANGE KEYS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
SET DAY AND TIME. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
TEMPERATURE CONTROL MODES. . . . . . . . . . . . . . . . . . . . . . . . . 4
7.5.1 HARDWARE RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7.5.2 SOFTWARE RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.1
5.2
5.3
7.6
TEMPERATURE VARIATION / SWING . . . . . . . . . . . . . . . . . . . . . . . 8
7.6.1 SWING 1
7.6.2 SWING 2
-
-
1st STAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2nd STAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.3.1 HEAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
5.3.2 COOL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
5.3.3 AUTO CHANGE (AUTO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
5.3.4 OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
7.7
8
DEAD BAND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
SETUP OPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
MINIMUM RUN TIME J3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
CLOCK FORMAT J4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
TEMPERATURE DISPLAY FORMAT (F/C DISPLAY) J5 . . . . . . 9
SMART RECOVERY J6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
GAS/ELECTRIC MODE J7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
REPOSITIONING JUMPERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
BATTERIES/MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
BATTERY INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
TECHNICAL ASSISTANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-11
USER PROGRAM TABLE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
JUMPER TABLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
8.1
8.2
8.3
8.4
8.5
8.6
9
5.4
5.5
5.6
5.7
DEFAULT PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
HOLD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
OVERRIDE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
FAN MODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5.7.1 AUTO. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5.7.2 ON. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5.7.3 CLEAN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
9.1
10
11
12
13
14
5.8
5.9
6
DISPLAY ILLUMINATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
AUDIBLE BEEP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
PROGRAMMING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
DEFAULT TEMPERATURE PROGRAM. . . . . . . . . . . . . . . . . . . . . . . 5
EDITING HEAT OR COOL PROGRAMS . . . . . . . . . . . . . . . . . . . . . . 5
6.1
6.2
WARNING: Use Energizer® or DURACELL® Alkaline Batteries Only.
Energizer® is a registered trademark of Eveready Battery Company, Inc.
DURACELL® is a registered trademark of The Gillette Company, Inc.
●
Download from Www.Somanuals.com. All Manuals Search And Download.
●
Do not install it where there are unusual heating
N O T E : If you are mounting the base to a soft material like
plasterboard or if you are using the old mounting holes, the
screws may not hold. Drill a 3/16-in. (4.8mm) hole at each
screw location, and insert the plastic anchors provided. Then
mount the base as described below.
conditions, such as: in direct sunlight; near a lamp,
television, radiator, register, or fireplace; near hot water
pipes in a wall; near a stove on the other side of a wall.
●
Do not locate in unusual cooling conditions, such as:
on a wall separating an unheated room; or in a draft from
a stairwell, door, or window.
4.5 WIRING
10. Using the terminal descriptions below, wiring
diagrams on pages 10-11, and your labels, determine
appropriate wiring for you system.
11. If you are unsure or need assistance, call the LUX
Technical Assistance Dept.
●
Do not locate in a damp area. This can lead to
corrosion that will shorten thermostat life.
●
Do not install the unit until all construction work and
painting has been completed.
(see TECHNICAL ASSISTANCE.)
4.5.1 TERMINAL DESCRIPTIONS
W A R N I N G:
●
Read instructions carefully before removing any wiring
from an existing thermostat.
RH: Provides power for heating terminals.
RC: Provides power for cooling and fan terminals.
B: Energized at any time the unit is in Heat mode.
O: Energized at any time the unit is in Cool mode.
W1: Energized while the thermostat is calling for a first
stage of heat.
W2: Energized when the thermostat is calling for a
second stage of heat.
Y1: Energized while the thermostat is calling for a first
stage of cooling.
Y2: Energized when the thermostat is calling for a
second stage of cooling.
G: The fan terminal is energized at any time the
thermostat attempts to turn the blower on.
C: Usage of this terminal permits the thermostat to be
powered by the system, instead of (or in addition
to) batteries alone.
●
Label wires before they are removed.
●
When removing wires from their terminals, ignore the
color of the wires since they may not comply with any
standard.
4.3 REMOVAL OF OLD UNIT
1. Switch electricity to the furnace and air conditioner
OFF; then proceed with the following steps.
2. Remove cover from old thermostat. Most are snap-on
types and simply pull off. Some have locking screws on
the side. These must be loosened.
3. Note the letters printed near the terminals. Attach
labels (enclosed) to each wire for identification. Label and
remove wires one at a time. Make sure the wires do not
fall back inside the wall.
4. Loosen all screws on the old thermostat and remove it
from the wall.
4.4 MOUNTING
5. Strip insulation 3/8 in. (9.5mm) from wire ends and
clean off any corrosion.
4.5.2 CONNECTING THE WIRES
12. Loosen wire clamp screws just enough to slide wire
under the black top part of the clamp.
13. Connect stripped wire ends, by
trapping it between its black clamp and
brass terminal. Then tighten its terminal
screw.
6. Fill wall opening with non-combustible insulation to
prevent drafts from affecting the thermostat.
7. With each thumb on a release tab at the bottom of the
body, and fingers over the top of the unit. Release the
unit from its base plate by squeezing the tabs into the
body.
14. Tape the ends of any unused wires.
4.6 COMPLETING YOUR INSTALLATION
8. Separate the unit from its base plate by pulling the
body outward at its bottom.
15. Install two new Energizer® or DURACELL® "AA" size
alkaline batteries at this time. For instructions, refer to
BATTERIES/MAINTENANCE.
C A U T I O N:
●
Be careful not to drop the unit or disturb electronic parts.
16. Configure your thermostat at this time. Refer to
SETUP OPTIONS.
●
Leave the door closed while the body is being removed
from the base.
17. Install your thermostat on its base. To do this hang
the top of the unit by the tabs on the base, then snap the
bottom of the unit into place. Do not use unnecessary
force. If the body does not snap into place easily, remove
the body, re-hang it from the tabs and try again.
18. Turn the power back on to your heating and/or air
conditioning system.
9. Route the wires through the open areas in the base
plate above the terminals. Hold the base against the wall,
with the wires coming through. Position the base for the
best appearance (to hide any marks from an old
thermostat). Attach the base to the wall with the two
screws provided.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
19. Verify that the system and its fan are operating
properly. When set to a high temperature, the heating
system should provide warm air after a short time.
Likewise a cooling system should provide cool air after a
short time. Usually sound from the furnace and air
conditioning units can be heard while they are running.
The rush of moving air should be heard within a short
time after either has been started.
5.3.2 COOL
●
Use COOL mode to control your air conditioner,
cooling your home.
●
In COOL mode, COOL is displayed right of the set
temperature.
●
While cooling is active, COOL will flash
If a second stage of cooling is called for the flashing
●
rate increases.
20. Your installation is now complete.
5.3.3 AUTO CHANGE (AUTO)
●
Use AUTO CHANGE mode to allow your thermostat to
5 OPERATING BASICS
switch between HEAT and COOL modes automatically.
Slide the mode switch to AUTO and AUTO CHANGE will
be displayed above the set temperature. You can
determine whether your thermostat is in HEAT or COOL
mode by whether HEAT or COOL is visible in the set
temperature area of the units display. Initially HEAT or
COOL may not be active until a determination is made
that HEAT or COOL is necessary.
5.1 UP/DOWN CHANGE KEYS
These are the two upper keys just right of the units
display. They are used to adjust set temperatures, and
make other setting changes.
●
Pressing these keys once will adjust a setting one step
in the associated direction.
●
If there are many choices for a value, usually that
●
The programmed temperature for a given mode will be
setting will advance while holding one of these keys.
Some settings though, must be changed one press at a
time.
used as the set temperature for that mode.
●
Pressing the UP/DOWN keys at the same time will
force the unit to change modes and make the
programmed set temperature the new set temperature.
5.2 SET DAY AND TIME
To set the correct time after the unit has been unpowered
or after reset:
5.3.4 OFF
●
Slide the MODE switch to OFF when no heating or
●
Open the door on the front of the thermostat.
cooling is desired. Heating and cooling will be disabled,
and the set temperature side of the display will be empty.
●
Rotate the dial to SET DAY/TIME. The abbreviation for
the day of week will flash.
●
●
●
●
5.4 DEFAULT PROGRAM
Use the UP key to advance to the current day.
Press NEXT to adjust the time. Time will flash.
Use the UP/DOWN keys to set the time.
●
As supplied from the factory, your thermostat will use
its default program for temperature control. This program
and all other settings maybe restored to their default
values via a SOFTWARE RESET. Please refer to DEFAULT
TEMPERATURE PROGRAM for program times and
temperatures.
Pressing NEXT again will toggle from Set Time to Set
Day, or vice versa.
●
Return the dial to its RUN position.
5.3 TEMPERATURE CONTROL MODES
5.5 HOLD
When a unit has first been powered up with the dial in
the RUN position, your thermostat will begin to control
your heating and/or air conditioning system according to
it's default program. There is a 4-position slide switch to
change temperature control modes. Slide the switch to
the mode you would like to use.
Hold is the simplest method to maintain fixed set
temperatures.
●
Press HOLD once to enter permanent temperature
HOLD while in RUN or OVERRIDE. HOLD will be
displayed above the set temperature in the display.
●
Pressing this button again will toggle HOLD off and
5.3.1 HEAT
return to RUN and the programmed set temperature.
●
Use HEAT mode to control your furnace and warm
Changing system mode or rotating the SPEED DIAL®
●
your home.
will also cancel a HOLD.
●
In HEAT mode, HEAT is displayed right of the set
5.6 OVERRIDE
temperature.
During RUN, set temperatures may be temporarily altered
from their programmed values. Immediately after a set
temperature has been altered, the 2-hour default duration
may be adjusted within the range from 1 to 4 hours. The
temporary set temperature(s) will be used for the
duration of the OVERRIDE.
●
While heating is active, HEAT will flash
If a second stage of heat is called for the flashing rate
●
increases.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
●
Press either the UP or DOWN key. The current modes
5.9 AUDIBLE BEEP
set temperature will begin to flash.
When a key is pressed, the thermostat will emit an
audible beep. The beep will terminate within 1/2 second
while a button is held.
●
Adjust the set temperature as desired.
After a few seconds the default 2-hour duration will
●
flash in the time area of the display.
6 PROGRAMMING
●
Adjust the duration in 15-minute increments, from
6.1 DEFAULT TEMPERATURE PROGRAM
between 1 to 4 hours.
As supplied from the factory, the following program will
be used for temperature control in RUN MODE. This
program and all other software settings maybe restored
to their default values via a SOFTWARE RESET.
●
When the duration stops flashing, the OVERRIDE has
been initiated and the Set Temperature side of the display
will show OVERRIDE
●
The adjusted temperature will remain the set
Period
Morning
Day
Evening
Night
Heat Mode
Cool Mode
temperature in the current mode for the duration of the
OVERRIDE. Then temperature settings return to their
program values.
6:00 AM 70°F (21°C)
8:00 AM 62°F (17°C)
6:00 PM 70°F (21°C)
10:00 PM 62°F (17°C)
6:00 AM 78°F (26°C)
8:00 AM 85°F (29°C)
6:00 PM 78°F (26°C)
10:00 PM 82°F (29°C)
●
OVERRIDE may be cancelled by initiating a HOLD and
then canceling it, changing the position of the mode
switch, or rotating the SPEED DIAL®
6.2 EDITING HEAT OR COOL PROGRAMS
5.7 FAN MODES
You can change any preset times and/or temperatures to
suit your schedule for each day of the week. The four
periods each day are named Morning (MORN), Day,
Evening (EVE), and Night (NITE).
The FAN switch controls which of three fan modes your
thermostat is to use. These modes are AUTO, CLEAN,
and ON.
5.7.1 AUTO
AUTO mode runs the fan only to fulfill your heating and
cooling requirements.
6.2.1 WEEKDAY PROGRAMMING
5.7.2 ON
To change the HEAT or COOL program:
●
ON mode runs your system fan continuously.
Set HEAT COOL, or AUTO with the mode switch
,
5.7.3 CLEAN CYCLE®
●
Rotate dial to SET WEEKDAY PROGRAMS
PROGRAM Mo MORN and START AT will be
displayed, with the SET TIME flashing.
.
,
,
LUX’s Clean Cycle® allows you to program a forced air
system to flow air through your system’s filter, cleaning
the air in your home, even when heating or cooling is not
being utilized. In CLEAN mode the fan maintains the
programmed minimum run time; it may run additional
time as required to maintain temperature control. The
algorithm used avoids additional fan time when the
minimum run time has been met over the last hour
through temperature control. Minimum fan run times are
met by running one third the hourly requirement at
twenty minute intervals. The default minimum fan run
time is 15 minutes per hour.
Programming is performed in the following order.
1 Mo Morn Start Time
2 Mo Morn Heat Set Temperature
3 Mo Morn Cool Set Temperature
4 Mo Day Start Time
5 Mo Day Heat Set Temperature
6 …and so on until Fri Nite is fully programmed at
which point pressing NEXT again will begin the list at Mo
Morn Start Time.
●
Use the UP/DOWN keys to change the start time for
5.8 DISPLAY ILLUMINATION
this period. Press UP/DOWN buttons to change the time
in 15 minute increments. Hold UP/DOWN button to
change the time at rate of 60 minutes/second.
For visibility in the dark, your LUX thermostat
incorporates an attractive electro-luminescent display
backlight.
●
One period ends at the start time of the next period.
●
Press the light bulb button right of the display to
The end of one period may not be any closer to the
beginning of the next period than one 15 minute
increment. Moving a start time too close to the next start
time results in the latter time being pushed ahead too.
Press NEXT to accept the displayed start time and
advance to the HEAT SET TEMPERATURE, it will flash to
show that it may be edited.
illuminate.
●
Pressing this or other buttons will keep the display
illuminated.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
●
The HEAT SET TEMPERATURE will be displayed on the (period) will all be visible. Current start time will flash in
right side of the display with the HEAT indicator visible.
time area.
●
Edit the HEAT SET TEMPERATURE, then press NEXT
Programming is performed in the following order.
1. Mo Morn Start Time
to accept and advance to the COOL SET TEMPERATURE,
it will flash to show that it may be edited.
2. Mo Morn Minimum ON Time
●
There is a minimum value that must be maintained
3. Mo Day Start Time
4. Mo Day Minimum ON Time
5. …and so on until Sun Night is fully programmed at
which point pressing NEXT again will begin the list at Mo
Morn Start Time.
between the HEAT SET TEMPERATURE and COOL SET
TEMPERATURE. That value is called the Dead band. Its
default is 3°F. It is programmable and may be changed
See ADVANCED FEATURES. If you move the heat set
temperature to close to the cool set temperature the cool
set temperature will move away from the heat set
temperature to maintain the dead band. Conversely the
heat set temperature will move if you adjust the cool set
temperature too close.
●
Press UP/DOWN to change start time for this period in
15 minute increments. Hold UP/DOWN button to change
the time at rate of 60 minutes/second
●
Press the NEXT to accept the start time, and advance
●
to set minimum fan on time per hour. Current minimum
Edit the COOL SET TEMPERATURE, then press NEXT
fan run time will flash with MIN/HR
.
to accept and advance to the next period
●
●
Press UP/DOWN to alter the minimum ON Time
When you have changed the Cool set temperature to
setting by 3 minutes. Time can be adjusted from 0 to
minutes to 60 minutes in increments of 3 minutes. Set 0
MIN/HR to allow AUTO control for particular periods
while CLEAN is used in others. Set the fan duration to 60
MIN/HR to run the fan continuously for this period.
your desired the temperature, press NEXT to advance to
the next period. Its start time will be flashing indicating
that it is under edit.
●
When all the periods for a day have been set, the start
time for the next weekday Morning period will be
displayed to begin editing the settings for that day.
●
Press NEXT to advance to the next period. After the
●
four program periods of day have been programmed,,
pressing NEXT will advance to the following days MORN
period.
Complete programming for all weekdays and rotate the
dial back to RUN to accept all current values and end the
programming session.
6.2.2 WEEKEND PROGRAMMING
Weekend programming is identical to weekday
programming except that you must rotate the dial to SET
WEEKEND PROGRAMS and the sequence of days that
you may program is Sa and Su, then repeating this two
day sequence.
6.3 CLEAN CYCLE® (IAQ FAN PROGRAMMING)
Clean Cycle® programming is similar to temperature
programming. It has four consecutive periods, which are
independent of the four temperature periods. The default
setting for your systems fans CLEAN CYCLE® program
requires it to run at least 15 minutes per hour.
Default Program periods are:
●
One period ends at the start time of the next period.
The end of one period may not be any closer to the
beginning of the next period than one 15 minute
increment. Moving a start time to close to the next start
time results in the latter time being pushed ahead too.
●
Rotate the dial away from the SET FAN
PROGRAMS/AIR FILTER position to exit fan
programming.
6.4 COPY
Pressing COPY will copy the previous days temperature
or fan program into the current day and advance the
thermostat to the beginning of next day.
7 ADVANCED FEATURES
Default Periods
MORN
DAY
Time
7.1 KEYBOARD LOCK
es NE
6:00 AM (6:00)
8:00 AM (8:00)
6:00 PM (18:00)
10:00 PM (22:00)
This sequence of keys will lock and
unlock all settings and programs. When locked, a
EVE
padlock icon will be visible above the time / temperature
area of the display.
NIGHT
To edit the CLEAN CYCLE® program:
●
Move Fan switch to CLEAN
.
●
Rotate the dial to AIR FILTER
●
●
Press HOLD for 2 seconds.
PROGRAM FAN, START AT, MO (day) and MORN
,
6
Download from Www.Somanuals.com. All Manuals Search And Download.
thermostat has activated heating and cooling with six
separate timers. They measure:
●
Today's cumulative heating time
●
Yesterdays cumulative heating time
●
Total cumulative heating time
●
Today's cumulative cooling time
●
Yesterdays cumulative cooling time
●
Total cumulative cooling time
To view HEAT or COOL energy usage:
7.2 FILTER MONITOR
●
Slide the mode switch to HEAT or COOL
.
Your thermostat can alert you that your system’s air filter
should be changed, by displaying FILTER in the time
temperature display area once the system’s fan has run
the number of hours specified by this setting’s limit. The
presence of the word FILTER on the screen will not effect
the operation of the thermostat. If equipped, the filter is
located in your heating/cooling equipment.
●
Rotate the dial to the ENERGY USAGE position, to
review today's usage. HRS USAGE Mode and Current
,
Day are all shown along with the usage value.
●
Press NEXT to review yesterday's usage.
Press NEXT again to review Total usage. The Total
●
timer may be changed to zero by pressing UP or DOWN
while Total time is displayed. To restore count, press UP
or DOWN again.
7.2.1 FILTER USAGE
To view the number of hours the thermostat has
activated the fan since the last timer reset:
●
To finish review and/or reset of this modes energy
monitor, rotate the dial to another mode, the current
values will be the values retained in memory. Leave the
value at 0 to reset the cumulative timer.
●
Rotate the dial to the AIR FILTER position. The current
filter usage will be shown with HRS FILTER
●
To reset the timer to 0. press UP or DOWN once.
7.4 CALIBRATION OFFSET
Pressing UP or DOWN again will toggle between 0 and
the current value. The value in display when you exit this
mode will be the value retained in memory. Leave the
value at 0 to reset the timer.
Your thermostat is accurately calibrated at the factory to
within 1°F An offset value up to 5°F may be added to
the temperature value that the thermostat measures. This
may allow you to match this thermostat to another. To
change this offset from its default value of 0:
●
To exit the AIR FILTER mode, rotate the dial to another
position.
●
Open the door on the front of the thermostat.
7.2.2 FILTER LIMIT
●
Rotate the dial to SET DAY/TIME
.
This general rule will provide you with a good estimate of
your filter’s life in hours. Assume that the fan will run at
1/3 duty cycle or 8 hours per day. Common 90 day filters
are then good for 90*24/3=720 hours of use. This is the
default limit value. Setting the filter counter limit to 0000
will disable the change filter indicator. Valid entries are
from 0 to 2000hrs.
●
Simultaneously press NEXT and HOLD. The
Temperature Offset value will flash.
●
Use the UP/DOWN keys to adjust the offset value.
Return the dial to its RUN position to accept the new
●
value.
7.5 RESET
To set the number of hours of filter use before
replacement is indicated:
Your thermostat has two RESET buttons. The Software
RESET is on the front of the thermostat behind the door.
It is labeled RESET. HARDWARE RESET is on the rear of
the circuit board.
●
Rotate the dial to the AIR FILTER position. The current
filter usage will be shown with HRS FILTER
●
7.5.1 HARDWARE RESET
Hold NEXT for 2 seconds. The Filter limit will be
Use this small white button labeled H_RST after
changing Setup Option Jumper positions to effect the
changes. The Hardware RESET turns Heat, Air and Fan
off, resets the units' clock, and reads the Setup Option
jumper positions, before initiating normal operation.
displayed.
●
Refer to your Air Filter package to determine your
filters recommended life. If given in days, multiply by 8 to
find the recommended setting in hours of filter usage.
●
Use UP/DOWN keys to adjust the filter limit in 10 hour
increments to the recommended value.
7.5.2 SOFTWARE RESET
●
Rotate the dial to RUN finish this setting.
Use this feature to make all settings and programs their
default values The Software RESET button turns Heat, Air
and Fan off, resets the units' clock, and reads the Setup
7.3 ENERGY USAGE
Your thermostat records the total number of hours the
7
Download from Www.Somanuals.com. All Manuals Search And Download.
●
Option jumper positions. It then makes all settings and
programs their default values before initiating normal
operation.
N O T E: Pressing this button will overwrite your program and
install the default values of all temperature programs and
setup values into the unit’s nonvolatile memory. To ease
reprogramming later, record your thermostat’s programs and
settings in the table provided before using this button. (See
Page 12.)
Select one of the 9 values from 025 to 225 with the
UP/DOWN buttons. The smallest setting of 025 provides
the most accurate temperature control, and the system
will cycle on/off the most frequently. The largest setting
of 225 provides the widest temperature differential, and
the system will cycle on/off less frequently.
Return the SPEED DIAL® to RUN
●
7.7 DEAD BAND
When using Auto-Changeover, dead band provides a
disallowed temperature range between the maximum
heat set temperature and minimum cool set temperature.
dead band may be set from 1 to 6 degrees. With auto-
changeover active, dead band set to 3°F and heat set to
70°F the minimum allowed cool set temperature will be
73°F. If the cool set temperature is lowered, then the heat
set temperature will be lowered by the same amount
maintaining the 3°F dead band.
7.6 TEMPERATURE VARIATION / SWING
Your thermostat works by turning your heating or cooling
system on and off whenever the room temperature varies
a certain number of degrees from the set-point
temperature. This variation is the "swing." Your system
should cycle on about 3 to 6 times per hour. A smaller
swing number increases the number of cycles, so room
temperature is more constant. A larger swing number
decreases the number of cycles, saving energy in most
cases.
To change this setting:
Set SPEED DIAL® to RUN
Set MODE to AUTO
Press NEXT and COPY simultaneously for 2 seconds.
●
●
7.6.1 SWING 1 - 1st STAGE
This setting controls when the heating or cooling turns
on and off.
●
The display shows SET DEAD BAND, while the
●
Time/Temperature section flashes the current setting.
Swing 1 sets the temperature variation that the system
●
allows above and below the set temperature before
switching the heating or cooling unit on and off.
To change this value:
Use UP/DOWN keys to adjust the DEAD BAND in 1
degree increments.
●
Press and release NEXT to return to RUN. Or, after 30
Rotate the SPEED DIAL® to ENERGY USAGE
Press NEXT and HOLD simultaneously. The
●
seconds the unit will automatically revert to RUN mode.
8 SETUP OPTIONS
There are five jumpers; each controls a setting depending
on its position. Jumpers are located on the rear of the
thermostats circuit board. For reference there a table of
settings and jumper positions printed there as well. They
are described here from J3, the rightmost jumper, to J7,
the leftmost jumper.
●
Temperature section of the display shows SET TEMP
SWING and denoting that you are setting SWING 1.
1
The Time section flashes the current setting.
●
Select one of the 9 values from 025 to 225 with the
UP/DOWN buttons. The smallest setting of 025 provides
the most accurate temperature control, and the system
will cycle on/off the most frequently. The largest setting
of 225 provides the widest temperature differential, and
the system will cycle on/off less frequently.
8.1 MINIMUM RUN TIME J3
The position of J3 sets the minimum length of time that
the thermostat must remain with HEAT or COOL either
On or Off, before it will automatically switch to the
alternate On or Off state. This Delay prevents rapid
cycling of your system and provides equipment
protection for cooling units. Switch position OFF is a 5
minute delay, and ON is a 2 minute delay. 5 minutes is
the default setting, and is good for most applications. If
you feel that your system is trying to cycle more rapidly
than every 5 minutes, you may try the 2 minute setting.
Return the SPEED DIAL® to RUN
●
7.6.2 SWING 2 - 2nd STAGE
This setting controls when the second stage of heating or
cooling turns on and off. It controls the temperature
variation the system allows above and below Swing 1's
limit before calling for a second stage. Once a second
stage is activated, it will remain on until the set
temperature has been reached.
To change this value:
8.2 CLOCK FORMAT J4
Rotate the SPEED DIAL® to ENERGY USAGE
●
The time shown on the thermostats clock may be
displayed in 12 or 24-hour format. Set this option to your
preference.
●
Press NEXT and COPY simultaneously. The
Temperature section of the display shows SET TEMP
SWING and
2
denoting that you are setting SWING 2.
The Time section flashes the current setting.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
8.3 TEMPERATURE DISPLAY FORMAT
(F/C DISPLAY) J5
Temperature may be displayed in Fahrenheit or Celsius
with this option.
battery symbol appears in the display
9.1 BATTERY INSTALLATION
1. Remove fresh batteries from their carton.
2. Remove body of thermostat from the wall as described
in installation.
8.4 SMART RECOVERY J6
3. Remove the used batteries if present and replace them
within 90 seconds to avoid having to reset the day and
time.
Smart Recovery allows your HVAC system to attempt to
recover from a setback period and reach your desired
comfort temperature by the beginning of your
programmed comfort period. This jumper allows you to
choose whether to use Smart Recovery.
4. Install two new "AA" size Energizer® or Duracell®
alkaline batteries. Observe the polarity marking shown in
the battery compartment.
●
An initial Smart Recovery will start 1/2 hour before the
programmed comfort temperature.
W A R N I N G:
●
Maximum Smart recovery time is one hour.
Replace your thermostat’s batteries with new Energizer or
Duracell alkaline batteries at least once a year or when the
battery symbol appears in the display. Use of high quality
alkaline batteries is absolutely required for your thermostat
to operate properly.
●
If enabled, Smart Recovery will initiate if:
●
Recovery is valid, from an evening setback to morning
comfort or day setback to evening comfort period
●
In Heat mode the set temperature of the comfort
period must be higher than the setback period
5. Re-hang on it's base plate as described in installation.
10 TECHNICAL ASSISTANCE
●
In Cool mode the set temperature of the comfort
period must be lower than the setback period
If you have any problems installing or using this thermostat,
please carefully and thoroughly review the instruction
manual. If you require assistance, please contact our
Technical Assistance Department at 856-234-8803 during
regular business hours between 8:00AM and 4:30PM
Eastern Standard Time, Monday through Friday. You can
also receive technical assistance online anytime day or night
answers to the most common technical questions, and also
permits you to email your questions to our technical support
staff at your convenience.
8.5 GAS/ELECTRIC MODE J7
This setting changes how the system’s blower fan (if
applicable) is controlled while in HEAT mode, and with
the Fan switch in the AUTO position. This setting does
not affect fan operation while in COOL mode. When set
to “Gas”, the fan is controlled solely by the heating
system itself. When set to “Electric”, the fan is controlled
directly by the thermostat. NOTE: If your blower fan does
not operate properly after installation, move the Gas /
Electric option to the “Electric” setting.
8.6 REPOSITIONING JUMPERS
11 WARRANTY
Use the table on Page 12 to determine the jumper
position corresponding to the option you desire. The
table is also printed on the circuit board. If necessary
change the jumper position by pulling it straight off the
pins it covers. Replace the jumper over one pin for
OPEN, or both pins for CLOSED. When all changes have
been made, press the Hardware Reset Button. See
HARDWARE RESET.
Limited Warranty: If this unit fails because of defects in
materials or workmanship within three years of the date of
original purchase, LUX will, at its option, repair or replace it.
This warranty does not cover damage by accident, misuse,
or failure to follow installation instructions. Implied
warranties are limited in duration to three years from the
date of original purchase. Some states do not allow
limitations on how long an implied warranty lasts, so the
above limitation may not apply to you. Please return
malfunctioning or defective units to the location from which
the purchase was made, along with proof of purchase.
Please refer to “TECHNICAL ASSISTANCE” before returning
thermostat. Purchaser assumes all risks and liability for
incidental and consequential damage resulting from
installation and use of this unit. Some states do not allow
the exclusion of incidental or consequential damages, so the
above exclusion may not apply to you. This warranty gives
you specific legal rights and you may also have other rights
which vary from state to state. Applicable in the U.S.A. and
Canada only.
These jumpers are located inside the thermostat on the
rear of its circuit board. To access them remove the unit
from the wall by pressing up on the thumb latch at the
bottom of thermostat, and swinging the body up and
away to separate them.
To change a setting, the jumper must be repositioned and
a Hardware reset must be performed. See HARDWARE
RESET.
9 BATTERIES/MAINTENANCE
Depending on your installation, your unit may require
batteries to control your HVAC system. Replace your
thermostats batteries at least once a year or when the
9
Download from Www.Somanuals.com. All Manuals Search And Download.
12 WIRING DIAGRAMS
TYPICAL 2 OR 3 WIRE HEAT ONLY HOOKUP
24V AC AND MILIVOLT SYSTEMS
G
B
W2 Y2
O
W1 Y1 RC RH
C
WIRING DIAGRAM NOTES
1. Dashed lines are optional.
JUMPER
SYSTEM
COMMON
2. Optional common wire
allows system to power
thermostat.
PROVIDED
Omit fan connections
for two wire systems.
3. Use “B” or “O” wire - but
not both in heat pump
systems. Generally neither
are required in a
GAS
XFMR
FAN
VALVE
AC LINE
conventional system.
4. If “Y” and “C” wires are
both present, then “C” is a
common wire.
5. If a “B” wire in your
system is a common wire
then connecting it to the B
terminal may cause damage
to your system.
TYPICAL SINGLE STAGE
COOL ONLY HOOKUP
G
B
W2 Y2
O
W1 Y1 RC RH
C
JUMPER
6. The PSPA722 is not
compatible with Heat Pump
Systems.
PROVIDED
SYSTEM
COMMON
COMPRESSOR
FAN
XFMR
AC LINE
WARNING: THIS IS A LOW
VOLTAGE THERMOSTAT
(24 volts). A SERIOUS
RISK OF FIRE EXISTS IF
YOU CONNECT THIS
TYPICAL 24V AC 4 WIRE HOOKUP
SINGLE STAGE HEAT AND COOL
THERMOSTAT TO A LINE
VOLTAGE APPLICATION
(typically 115 or 230 volts).
IF UNCERTAIN ABOUT THE
VOLTAGE CONSULT A
PROFESSIONAL
G
B
W2 Y2
O
W1 Y1 RC RH
C
JUMPER
SYSTEM
PROVIDED
COMMON
ELECTRICIAN.
GAS
VALVE
COMPRESSOR
XFMR 1
FAN
AC LINE
10
Download from Www.Somanuals.com. All Manuals Search And Download.
TYPICAL 24V AC 5 WIRE HOOKUP
SINGLE STAGE HEAT AND COOL
2 TRANSFORMER
G
B
W2 Y2
O
W1 Y1 RC RH
C
WIRING DIAGRAM NOTES
1. Dashed lines are optional.
JUMPER
REMOVED
2. Optional common wire
allows system to power
thermostat.
COOL
COMMON
HEAT
3. Use “B” or “O” wire - but
not both in heat pump
systems. Generally neither
are required in a
COMMON
GAS
COOL
COMPRESSOR
XFMR
HEAT
XFMR
FAN
VALVE
conventional system.
AC LINE AC LINE
4. If “Y” and “C” wires are
both present, then “C” is a
common wire.
5. If a “B” wire in your
system is a common wire
then connecting it to the B
terminal may cause damage
to your system.
6. The PSPA722 is not
compatible with Heat Pump
Systems.
TYPICAL 24V MULTI-STAGE
HOOKUP
G
B
W2 Y2
O
W1 Y1 RC RH
C
JUMPER
PROVIDED
SYSTEM
COMMON
COMPRESSOR
HEAT
WARNING: THIS IS A LOW
VOLTAGE THERMOSTAT
(24 volts). A SERIOUS
RISK OF FIRE EXISTS IF
YOU CONNECT THIS
XFMR
FAN
STAGE 2 STAGE 1 STAGE 2 STAGE 1
AC LINE
THERMOSTAT TO A LINE
VOLTAGE APPLICATION
(typically 115 or 230 volts).
IF UNCERTAIN ABOUT THE
VOLTAGE CONSULT A
PROFESSIONAL
ELECTRICIAN.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
13 USER PROGRAM TABLE
To ease reprogramming later, record your thermostat’s
programs and settings in the table provided below.
HEAT
COOL
DAY
PERIOD
TIME TEMP. TIME TEMP.
MORN
DAY
EVE
THURS
HEAT
COOL
DAY
PERIOD
NIGHT
MORN
DAY
TIME TEMP. TIME TEMP.
MORN
DAY
EVE
MON
FRI
SAT
SUN
EVE
NIGHT
MORN
DAY
NIGHT
MORN
DAY
TUES
WED
EVE
EVE
NIGHT
MORN
DAY
NIGHT
MORN
DAY
EVE
EVE
NIGHT
NIGHT
14 JUMPER TABLE
BATTERY COMPARTMENT
BACK OF THERMOSTAT BODY
WITH COVER REMOVED
J7 J6 J5 J4 J3
JUMPERS
MOUNTED ON
CIRCUIT BOARD
H_RST
OPEN CLOSE
2 MIN 5 MIN
J3
24 HR 12 HR J4
C
F
J5
S/R ON S/R OFF J6
ELECT GAS J7
MERCURY WARNING AND RECYCLING NOTICE:
Mercury is considered to be a hazardous material. If this product is replacing a
thermostat that contains mercury in a sealed tube, contact your local waste
management authority for instructions regarding recycling and proper disposal. It
may be unlawful in your state to place it in the trash.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
|