RP V-I&S
IN STALLATIO N & SERVICE M AN UAL
POWERED VENT GAS WATER HEATER GENERAL INFORMATION
WARNING
This gas-fired water heater’s design is certified by CSA International under the
American National Standard Z21.10.1 - (as indicated on the rating plate) and
CSA 4.1-M - (as indicated on the rating plate).
If the information in these instructions is not followed exactly,
a fire or explosion may result causing property damage, personal
injury or death.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable, combustible, or
corrosive vapors and liquids in the vicinity of this or any other
appliance.
This water heater must be installed in accordance with local codes or, in the
absence of local codes, theNational Fuel Gas Code, ANSIZ223.1-Latest Edition)
and/or in Canada CAN/CGA B149 Installation Codes (Latest Editions). The
warranty for this water heater is in effect only when the water heater is
installed, adjusted, and operated in accordance with these Installation and
Operating Instructions. The manufacturer will not be held liable for any damage
resulting from alteration and/or failure to comply with these instructions.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any telephone
in your building.
This water heater is not design certified for installation in a mobile home. Such
an installation may create a hazardous condition and will nullify the warranty.
• Immediately call your gas supplier from a neighbor’s
telephone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
CAUTION
Incorrect operation of this appliance may create a hazard to
life and property and will nullify the warranty.
Installation and service must be performed by a qualified installer,
service agency or the gas supplier.
For your family’s comfort, safety and convenience we recommend Do not use this appliance if any part has been submerged in water. You should
contact a qualified service technician to inspect the appliance and to replace
any part of the control system including the combination gas control which has
been submerged in water.
water heaters to be installed and serviced by a plumbing
professional.
TABLE OF CONTENTS
GENERAL INFORMATION............................................................ 1
INSTALLATION........................................................................ 2
Locating The Water Heater ................................................ 2
Minimum Clearances .......................................................... 3
Venting .............................................................................. 3
Specifications for
DANGER
Do not store or use gasoline or other flammable, combustible,
or corrosive vapors and liquids in the vicinity of this or any
other appliance.
48 Gal, 65,000 BTU input (189.3 L, 19.1 kW/ Hr)
65 Gal, 65,000 BTU input (246.1 L, 19.1 kW/ Hr)
75 Gal, 76,000 BTU input (283.9 L, 22.3 kW/ Hr) ............. 4
Specifications for
40 Gal, 40,000 BTU input (151.4 L, 11.7 kW/ Hr)
48 Gal, 40,000 BTU input (189.3 L, 11.7 kW/ Hr) ............. 5
Combustion Air Supply .............................................................. 7
Water Connections .................................................................... 8
Gas Connections ........................................................................ 9
Electrical Connections ................................................................ 9
Wiring Diagram for
IMPORTANT
Before proceeding, please inspect the water heater and components for
possible damage. DO NOTinstall any damaged components. If damage is
evident then please contact the supplier where the water heater was
purchased or the manufacturer listed on the rating plate for replacement
parts.
Make sure that you check the rating plate and combination gas control on the
water heater to be certain that the type of gas being supplied corresponds with
the marking on the rating plate and combination gas control.
48 Gal, 65,000 BTU input (189.3 L, 19.1 kW/ Hr)
65 Gal, 65,000 BTU input (246.1 L, 19.1 kW/ Hr)
75 Gal, 76,000 BTU input (283.9 L, 22.3 kW/ Hr) ............. 10
Wiring Diagram for
A sacrificial anode is used to extend tank life. The removal of this anode, for
any reason, will nullify the warranty. In areas where water is unusually active,
an odor may occur at the hot water faucet due to a reaction between the
sacrificial anode and the impurities in the water. If this should happen, an
alternative anode may be purchased from the supplier that installed this water
heater. This will minimize the odor while protecting the tank. Additionally, the
water heater should be flushed with appropriate dissolvers to eliminate any
bacteria.
40 Gal, 40,000 BTU input (151.4 L, 11.7 kW/ Hr)
48 Gal, 40,000 BTU input (189.3 L, 11.7 kW/ Hr) ............. 11
GENERAL OPERATION ................................................................ 9
Lighting and Shutdown Instructions ..................................... 12
Thermostat Adjustment ......................................................... 12
Burner Flame Check ................................................................ 12
MAINTENANCE ........................................................................... 13
INSTALLATION INSTRUCTIONS FOR POTABLE WATER AND
SPACE HEATING ......................................................................... 14
VENT PIPE PREPARATION AND JOINING .................................... 14
1
Download from Www.Somanuals.com. All Manuals Search And Download.
RP V-I&S
76,000 BTU (283.9 L - 22.3 kW/ Hr) models. Part II will cover
venting specifications for 40 Gal - 40,000 BTU (151.4 L - 11.7 kW/
Hr) and 48 gal - 40,000 BTU (181.7 L - 11.7 kW/ Hr) models. Refer
to the rating plate located on the water heater for correct model
identification.
In order to effectively control condensate from adversely affecting the
mechanical components of the water heater several methods may be employed:
1. For horizontal installations the vent pipe can be installed with a downward
slope (not less than 1/8" nor greater than 1/2” per foot maximum) and
away from the blower motor.
The National Fuel Gas Code ANSI Z223.1-(Latest Edition), CGA/CAN B149
Installation Code, and local codes have specific requirements for the location
of the vent terminals on vertical walls. The guide lines listed below are from
the National Fuel Gas Code. Consult the local codes, and/or National Fuel Gas
Code ANSI Z223.1-(Latest Edition), or CGA/CAN B149 Installation Code to
determine if there are any additions or changes to the following specifications.
2. In order to prevent condensate from draining back into the blower (vertical
or horizontal runs), a fitting and drain hose is available as a condensate
trap kit (see Table 1 for service part numbers). The all rubber fitting with
drain outlet mounts directly to the blower motor outlet and is secured with
two hose clamps (one to the blower motor outlet and the other to the vent
connector). The plastic tubing is provided to drain any accumulated
condensate away from the water heater and to a suitable drain. The kit
comes complete with instructions for proper installation of the fitting.
(A) The vent terminal must terminate at least 3 feet (.91 m) above any
forced air inlet duct located within 10 feet (3 m). Exception: This
provision shall not apply to the combustion air intake of a direct vent
appliance.
(B) The vent terminal must terminate at least 4 feet (1.2m) below, 4 feet
(1.2 m) horizontally from, or 1 foot (0.31 m) above any door, window,
gravity air inlet into the building.
Table - 1
Model
Service Part
DRV1200
2" (5.1 cm) Blower Outlet (exhaust)
3" (7.6 cm) Blower Outlet (exhaust)
DRV1201
(C) The bottom of the vent terminal must be located at least 1 foot
(0.31 m) above ground and above the anticipated snow level.
(D) The vent terminal must not terminate over a public walkway or over an
area where condensate or vapor could create a nuisance or hazard
or could be detrimental to the operation of regulators, relief valve, or
other equipment.
(E) The water heater location must provide easy access for the entire
length of the vent connector.
(F) The vent system must be inspected at least once a year to ensure
against leakage of exhaust products.
3. In order to prevent condensate from draining back into the blower (vertical
or horizontal runs), a drain tee and condensate trap can be installed in the
horizontal vent as close as practical to the blower vent connection (see
Figure1). The condensate disposal tube should be installed to drain any
accumulated condensate away from the water heater and to a suitable
drain. The drain tee and condensate hose should be available through
your local distributor.
Exceptions For Installations in Canada:
(A) The vent terminal must be located at least 1 foot (0.31 m) from any
window or door which can be opened in any building, any non-mechanical
air supply inlet to any building, or the combustion air to any inlet other
appliance.
(B) The vent terminal must be located at least 6 feet (1.8 m) from any
mechanical air supply inlet to the building.
(C) The vent terminal must not terminate above a meter/ regulator
assembly within 3 feet (0.91 m) horizontally of the vertical center line
of the regulator and must be at least 6 feet (1.8 m) from any gas
service regulator vent outlet.
(D) The vent terminal must be at least 7 feet (2.1 m) above a paved
sidewalk or a paved driveway located on public property.
(E) The vent terminal must not terminate above a paved sidewalk or a
paved driveway, which is located on private adjacent property.
Figure 1
Part I - Venting Specifications for:
48 Gallon, 65,000 BTU input (181.7 L, 19.1 kW/ Hr)
65 Gallon, 65,000 BTU input (246.1 L, 19.1 kW/ Hr)
75 Gallon, 76,000 BTU input (283.9 L, 22.3 kW/ Hr)
VENTING SYSTEM CONDENSATION
Condensate formation does not occur in all installations of power vented
heaters, but should be protected against on installations where condensation
can form in the venting system.
This water heater is a power vented appliance and is designed to vent its
products of combustion through 3" (7.6 cm) or 4" (10.2 cm) diameter Schedule
40 (solid or cellular core) PVC pipe to the outdoors. This water heater may be
either vented through the wall or vertically through the roof. Use a 3" (7.6 cm)
Formation of condensation in the venting system of Power Vented water
heaters is dependent upon installation conditions including, but not limited to: to 4" (10.2 cm) reducer to connect to the vent outlet when using 4" (10.2 cm)
PVC. Table 2 lists the maximum vent lengths for this water heater using 3" (7.6
cm) PVC. If possible, locate the water heater so that the venting length and
number of elbows are kept to the minimum distance necessary to reach the
outside. If the installation requires venting lengths that exceed the lengths
listed for 3" (7.6 cm) PVC in Table 2, then use 4" (10.2 cm) PVC for the vent
connector. Table 3 lists the venting distances allowed with 4" (10.2 cm)
1. Ambient temperature and humidity of installation location;
2. Ambient temperature and humidity of venting space; vent distance and
slope;
3. And product usage.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
RP V-I&S
diameter PVC pipe. When venting with 4" (10.2 cm) PVC, use a 4" (10.2 cm) to
3" (7.6 cm) reducer to exit through the building wall with 3" (7.6 cm) PVC. Use
the 3" (7.6 cm) vent terminal supplied with the water heater to terminate on
the outside of the building. If the length of 3" (7.6 cm) PVC needed to go
through the wall is greater than 14" (35.5 cm), use 4" (10.2 cm) to go through
the wall and reduce to 3" (7.6 cm) PVC immediately after exiting the outside
wall. Refer to the venting illustrations on the following pages. Make sure the
vent pipe terminal elbow fitting is at least 1" (2.5 cm) away from the edge of
the wall.
IMPORTANT
All of the Venting connections must be leak checked with a soap and
water solution upon initial start up of the water heater. Any leaks
must be repaired before continuing operation of the water heater.
NOTE: ABS or CPVC pipes may be substituted for PVC pipe. Do not
mix ABS and PVC pipe in the same installation.
THROUGH THE WALL VENTING:
TABLE - 2
Cut a 3-1/2 inch(8.9 cm) diameter hole in the wall at the point where the vent
connector is going to pass through the wall. Use the proper cement to secure
the 90° vent terminal provided with the water heater to the vent connector.
The distance between the edge of the 90° vent terminal and the exterior wall
(see Figure 3) must be 1 inch(2.5 cm). Use the proper cement and assembly
procedures to secure the vent connector joints between the terminal and the
blower outlet. Provide support brackets for every 3 feet (.91 m) of horizontal
vent.
VENT CONNECTOR LENGTHS FOR 3" (7.6 cm) DIAMETER PVC
Terminating
# of 90° Elbows
(excluding vent
terminal)
Maximum
Length
Minimum
Length
ThroughtheWall
ThroughtheWall
ThroughtheWall
ThroughtheWall
ThroughtheRoof
ThroughtheRoof
Through the Roof
ThroughtheRoof
1
2
3
4
1
2
3
4
40 ft(12.2 m)
35 ft(10.7 m)
30 ft(9.1 m)
25 ft(7.6 m)
40 ft(12.2 m)
35 ft(10.7 m)
30 ft(9.1 m)
25 ft(7.6 m)
2 ft(.6 m)
3 ft(.9 m)
5 ft(1.5 m)
8 ft(2.4 m)
2 ft(.6 m)
3 ft(.9 m)
5 ft(1.5 m)
8 ft(2.4 m)
TABLE - 3
VENT CONNECTOR LENGTHS FOR 4" (10.1 cm) DIAMETER PVC
Terminating
# of 90° Elbows Maximum
Minimum
Length
(excluding vent
terminal)
Length
ThroughtheWall
ThroughtheWall
ThroughtheWall
ThroughtheWall
Through the Wal
ThroughtheRoof
Through the Roof
ThroughtheRoof
ThroughtheRoof
ThroughtheRoof
1
2
3
4
5
1
2
3
4
5
70 ft(21.3 m)
65 ft(19.8 m)
60 ft(18.3 m)
55 ft(16.8 m)
50 ft(15.3 m)
70 ft(21.3 m)
65 ft(19.8 m)
60 ft(18.3 m)
55 ft(16.8 m)
50 ft(15.3 m)
2 ft(.6 m)
3 ft(.9 m)
5 ft(1.5 m)
8 ft(2.4 m)
12 ft(3.6 m)
2 ft(.6 m)
Figure 3
3 ft(.9 m)
5 ft(1.5 m)
8 ft(2.4 m)
12 ft(3.6 m)
THROUGH THE ROOF VENTING: (VERTICAL VENTING)
Cut the necessary holes through the roof and ceiling and install the vent
connector as shown in Figure 4. Make sure that the installation meets the local
codes and/or The National Fuel Gas Code ANSI Z223.1 (Latest Edition) or CGA/
CAN B149 Installation Code.
NOTE: When using 4" (10.1 cm) PVC, use a 4" (10.1 cm) to 3" (7.6
cm) reducer and exit the building wall with 3"(7.6 cm) PVC using the
3" (7.6 cm) 90° vent terminal supplied. Two 45° elbows are equivalent
to one 90° elbow.
Figure 2
Figure 4
4
Download from Www.Somanuals.com. All Manuals Search And Download.
RP V-I&S
NOTE: For installations requiring both horizontal and vertical runs, of the water heater, the following guidelines must be followed. Refer to the
the following rule must be followed: Total number of feet of straight venting tables below for maximum distances for the altitudes in your location.
pipe (both horizontally and vertically) must not exceed the allowable
length listed in the “Through The Wall” section of the table for total
number of elbows used. Also: Total number ofvertical feet of straight
pipe must not exceed the allowable length listed in the “Through
The Roof” section of the table for total number of elbows used. For
angular rises in venting, any angle that is greater than or equal to
45° from the horizontal should be considered a vertical rise.
TABLE - 6
HIGH ALTITUDE LENGTHS
Max. venting
Altitude
above
sea level
Max. venting
length reduction length reduction water heater
Modifications to
from tables
2 & 4
from tables
3 & 5
0-3,000 ft
(0-914.5m)
No reduction
in vent length
required
No reduction
in vent length
required
None
THROUGH THE WALL VENTING WITH LOW GROUND CLEARANCE:
When venting cannot exit through the wall at a height greater than or equal to
12" (30.5 cm) above the ground, or anticipated snow level, the installation
must be modified as shown below (see Figure 5). Refer to Table 4 for maximum
venting lengths using 3" (7.6 cm) PVC or Table 5 for maximum lengths using 4"
(10.1 cm) PVC.
over 3,000-
10,000 ft
No reduction
in vent length
(914.5-3048m) required
Requires high altitude
Kit. Call the supplier or
the manufacturer
No reduction
in vent length
required
Pa rt II - Ve n tin g Sp e cifica tio n s fo r:
40 Gallon, 40,000 BTU input (151.4 L, 11.7 kW/ Hr)
48 Gallon, 40,000 BTU input (189.3 L, 11.7 kW/ Hr)
Figure 5
This water heater is a power vented appliance and is designed to vent its
products of combustion through 2" (5.1 cm) or 3" (7.6 cm) diameter Schedule
40 (solid or cellular core) PVC pipe to the outdoors. The water heater may be
either vented through the wall or vertically through the roof. Use a 3" (7.6 cm)
to 2" (5.1 cm) reducer to connect to the vent outlet when using 3" (7.6 cm)
PVC. Apply PVC cement at PVC locations. Table 7 lists the maximum vent
lengths for this water heater using 2" (5.1 cm) PVC. If possible, locate the
water heater so that the venting length and number of elbows are kept to the
minimum distance necessary to reach the outside. If the installation requires
venting lengths that exceed the lengths listed for 2" (5.1 cm) PVC in Table 7
then use 3" (7.6 cm) PVC for the vent connector. Table 8 lists the venting
distances allowed with 3" (7.6 cm) diameter PVC pipe. When venting with 3"
(7.6 cm) PVC, use a 3" (7.6 cm) to 2" (5.1 cm) reducer to exit through the
building wall with 2" (5.1 cm) PVC. Use the 2" (5.1 cm) vent terminal supplied
with the water heater to terminate on the outside of the building. If the length
of the 2" (5.1 cm)needed to go through the wall is greater than 14" (35.6 cm),
use 3" (7.6 cm) PVC to go through the wall and reduce to 2" (5.1 cm) PVC
immediately after exiting the outside wall. Refer to the venting illustrations on
the following pages. Make sure the vent pipe terminal is at least 1" (2.5 cm)
away from the edge of the wall. To vent horizontally with zero (0) elbows,
remove 3 screws from blower housing and rotate the blower housing 90°
clockwise (see Figure 7). Replace the three (3) screws once blower housing
rotation is complete.
TABLE - 4
3" (7.6 cm) PVC VENT CONNECTOR LENGTHS FROM INSIDE WALL
FOR LOW GROUND CLEARANCE INSTALLATIONS
Terminating
# of
Elbows
Maximum
Length
Minimum
Length
(2) 90° Elbows with (1) 90° Elbow
(2) 90° Elbows with (1) 90° Elbow
(2) 90° Elbows with (1) 90° Elbow
(2) 90° Elbows with (1) 90° Elbow
1
2
3
4
30 ft(9.1 m)
25 ft(7.6 m)
20 ft(6.1 m)
15 ft(4.6 m)
5 ft(1.5 m)
6 ft(2 m)
8 ft(2.5 m)
10 ft(3 m)
TABLE - 7
TABLE - 5
VENT CONNECTOR LENGTHS FOR 2" (5.1cm) DIAMETER PVC
4" (10.1 cm) VENT CONNECTOR LENGTHS FROM INSIDE WALL
Terminating
# of 90° Elbows
(excluding vent
terminal)
Maximum
Length
Minimum
Length
FOR LOW GROUND CLEARANCE INSTALLATIONS
Terminating (Reduce 4" to 3") # of
(Reduce 10.1 cm to 7.6 cm) Elbows
Maximum
Length
Minimum
Length
Through the Wall
Through the Wall
Through the Wall
Through the Wall
Through the Wall
Through the Roof
Through the Roof
Through the Roof
Through the Roof
Through the Roof
0
1
2
3
4
0
1
2
3
4
45 ft(13.7m)
40 ft(12.2m)
35 ft(10.7m)
3 0 ft(9.2 m)
25 ft(7.6 m)
31 ft(9.5 m)
28 ft(8.5 m)
25 ft(7.6 m)
22 ft(6.7 m)
19 ft(5.8 m)
2 ft(.6 m)
2 ft(.6 m)
2 ft(.6 m)
2 ft(.6 m)
3 ft(.9 m)
3 ft(.9 m)
3 ft(.9 m)
3 ft(.9 m)
3 ft(.9 m)
4 ft(1.2 m)
(2) 90° Elbows with (1) 90° Elbow
(2) 90° Elbows with (1) 90° Elbow
(2) 90° Elbows with (1) 90° Elbow
(2) 90° Elbows with (1) 90° Elbow
(2) 90° Elbows with (1) 90° Elbow
1
2
3
4
5
60 ft(18.3 m)
10 ft(3 m)
55 ft(16.8 m) 12 ft(3.7 m)
50 ft(15.2 m) 15 ft(4.6 m)
45 ft(13.7 m) 18 ft(5.5 m)
40 ft(12.2 m) 22 ft(6.7 m)
HIGH ALTITUDE INSTALLATIONS FOR ELEVATIONS OVER
3,000 FEET (914.5 m) ABOVE SEA LEVEL
The capacity of the induced draft blower declines with increasing altitude due to
a reduction in the air density. In order to assure safe and reliable performance
5
Download from Www.Somanuals.com. All Manuals Search And Download.
RP V-I&S
distance between the edge of the 45° vent terminal and the exterior wall (see
Figure 8) must be at least 1 inch (2.5 cm). Use the proper cement and
assembly procedures to secure the vent connector joints between the terminal
and the blower outlet. Provide support brackets for every 3 feet (0.91 m) of
horizontal vent.
TABLE - 8
VENT CONNECTOR LENGTHS FOR 3" (7.6 cm) DIAMETER PVC
Terminating
# of 90° Elbows
(excluding vent
Maximum
Length
Minimum
Length
terminal)
Through the Wall
Through the Wall
Through the Wall
Through the Wall
Through the Wall
Through the Wall
Through the Roof
Through the Roof
Through the Roof
Through the Roof
Through the Roof
0
1
105 ft(32.0 m) 10 ft(3.1 m)
1100 ft (30.5 m) 10 ft(3.1 m)
95 ft(29.0 m) 10 ft(3.1 m)
90 ft(27.5 m) 10 ft(3.1 m)
85 ft(26.0 m) 10 ft(3.1 m)
80 ft(24.4 m) 10 ft(3.1 m)
Fig u re 8
2
3
4
5
0
1
2
3
4
55 ft(16.8 m)
50 ft(15.3 m)
45 ft(13.7 m)
40 ft(12.2 m)
35 ft(10.7 m)
5 ft(1.5 m)
5 ft(1.5 m)
5 ft(1.5 m)
5 ft(1.5 m)
5 ft(1.5 m)
NOTE: When using 3"(7.6 cm) PVC, use a 3" (7.6 cm) to 2" (5.1 cm)
reducer and exit the building wall with 2"(5.1 cm) PVC using the 2"
(5.1 cm) 45° vent terminal supplied. Two 45° elbows are equivalent
to one 90° elbow. Each 90° elbow is equivalent to 5 feet (1.5 m) of
THROUGH THE ROOF VENTING: (VERTICAL VENTING)
Cut the necessary holes through the roof and ceiling and install the vent
connector as shown in (Figure 9). Make sure that the installation meets the
local codes and/or The National Fuel Gas Code ANSI Z223.1 (Latest Edition) or
CGA/CAN B149 Installation Code.
straight vent pipe.
Fig u re 6
IMPORTANT
Fig u re 9
All of the Venting connections must be leak checked with a soap and water
solution upon initial start up of the water heater. Any leaks must be repaired
before continuing operation of the water heater.
THROUGH THE WALL VENTING WITH LOW GROUND CLEARANCE:
When venting cannot exit through the wall at a height greater than or equal to
12" (30.5 cm) from the ground or from the anticipated snow level, then the
installation must be modified as shown below see Figure 10. Refer to Table 9
for maximum venting lengths using 2" (5.1 cm) PVC or Table 10 for maximum
lengths using 3" (7.6 cm) PVC.
NOTE: ABS or CPVC pipes may be substituted for PVC pipe. Do not
mix ABS and PVC pipe in the same installation.
Fig u re 7
Fig u re 1 0
THROUGH THE WALL VENTING:
Cut a 2 ½ inch (6.4 cm) diameter hole in the wall at the point where the vent
connector is going to pass through the wall. Use the proper cement to secure
the 45° vent terminal provided with the water heater to the vent connector. The
6
Download from Www.Somanuals.com. All Manuals Search And Download.
RP V-I&S
NOTE: For installations requiring both horizontal and vertical runs,
the following rule must be followed: Total number of feet of straight
pipe (both horizontally and vertically) must not exceed the allowable
length listed in the “Through The Wall” section of the table for total
number of elbows used. Also: Total number ofvertical feet of straight
pipe must not exceed the allowable length listed in the “Through The
Roof” section of the table for total number of elbows used. For
angular rises in venting, any angle that is greater than or equal to
45° from the horizontal should be considered a vertical rise.
COMBUSTION AIR SUPPLY
WARNING
Liquefied petroleum gases/propane gas are heavier than air and will remain
at floor level if there is a leak. Basements, crawl spaces, closets and areas
below ground level will serve as pockets for accumulation of leaking gas.
Before lighting, smell all around the appliance area for gas. Be sure to smell
next to the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any telephone
in your building.
• Immediately call your gas supplier from a neighbor’s
telephone. Follow the gas supplier’s instructions.
TABLE - 9
2" (5.1 cm) PVC VENT CONNECTOR LENGTHS FROM INSIDE WALL
FOR LOW GROUND CLEARANCE INSTALLATIONS
Terminating
# of
Elbows
Maximum
Length
Minimum
Length
• If you cannot reach your gas supplier, call the fire department.
DO NOT OPERATE APPLIANCE UNTIL LEAKAGE IS CORRECTED!
(2) 90° Elbows with Vent Terminal
(2) 90° Elbows with Vent Terminal
(2) 90° Elbows with Vent Terminal
(2) 90° Elbows with Vent Terminal
(2) 90° Elbows with Vent Terminal
0
1
2
3
4
35 ft(10.7 m)
30 ft(9.2 m)
25 ft(7.6 m)
20 ft(6.1 m)
15 ft(4.6 m)
2 ft(.6 m)
2 ft(.6 m)
2 ft(.6 m)
3 ft(.9 m)
4 ft(1.2 m)
IMPORTANT
The flow of combustion and ventilating air must not be obstructed.
Provide adequate air for combustion and ventilation. An insufficient supply of
air will cause recirculation of combustion products resulting in air contamination
that may be hazardous to life. Such a condition often will result in a yellow,
luminous burner flame, causing carbon build up or sooting of the combustion
chamber, burners, and flue tubes with possible damage to the heater.
TABLE - 10
3" (7.6 cm) VENT CONNECTOR LENGTHS FROM INSIDE WALL
FOR LOW GROUND CLEARANCE INSTALLATIONS
Terminating (Reduce 3" to 2") # of
(Reduce 7.6 cm to 5.1 cm) Elbows
Maximum
Length
Minimum
Length
(2) 90° Elbows with (1) 90° Elbow
(2) 90° Elbows with Vent Terminal
(2) 90° Elbows with Vent Terminal
(2) 90° Elbows with Vent Terminal
(2) 90° Elbows with Vent Terminal
(2) 90° Elbows with Vent Terminal
(2) 90° Elbows with Vent Terminal
1
0
1
2
3
4
5
60 ft(18.3 m)
10 ft(3 m)
When an exhaust fan is installed in the same room with a heater, sufficient
openings for air must be provided in the walls. Undersized openings will cause
air to be drawn into the room through the chimney, causing recirculation of
combustion products.
90 ft(27.5 m) 10 ft(3.1 m)
85 ft (25.9 m) 10 ft(3.1 m)
80 ft(24.4 m) 10 ft(3.1 m)
75 ft(22.9 m) 10 ft(3.1 m)
70 ft(21.4 m) 10 ft(3.1 m)
65 ft(19.8 m) 12 ft(3.7 m)
Unconfined Spaces
In unconfined spaces in buildings, infiltration may be adequate to provide air
for combustion, ventilation, and dilution of flue gases. However, in buildings of
tight construction (for example, weather stripping, heavily insulated, caulked,
vapor barrier, etc.), additional air may need to be provided using the methods
described under CONFINED SPACES: All Air From Outdoors or Specially Engineered
Installations.
HIGH ALTITUDE INSTALLATIONS FOR ELEVATIONS OVER 2,000 FEET
(610 m) ABOVE SEA LEVEL
The capacity of the induced draft blower declines with increasing altitude due to
a reduction in the air density. In order to assure safe and reliable performance
of the water heater, the following guidelines must be followed. Refer to the
venting tables below for maximum distances for the altitudes in your location.
Confined Spaces
Confined spaces are spaces defined as having less than 50 ft.3/1000 BTU
3
(1.4 m /0.29 kw-hr).
TABLE - 11
All Air From Inside the Building: The confined space must be provided
with two permanent openings communicating directly with an additional room(s)
of sufficient volume so that the combined volume of all spaces meets the
criteria for an unconfined space. The total input of all gas utilization equipment
installed in the combined space must be considered in making this determination.
Each opening must have a minimum free area of 1 square inch per 1000 BTU
HIGH ALTITUDE VENT CONNECTOR MODIFICATIONS
Altitude above
Maximum venting
length reduction
tables 7 & 9
Maximum venting
sea level
length reduction
tables 8 & 10
0 - 2,000 ft
(0 - 610 m)
No reduction in vent
length required
No reduction in vent
length required
2
(6.5 cm /0.29 kw) per hour of the total input rating of all gas utilization
equipment in the confined space, but not less than 100 square inches (645
cm ). One opening must be within 12 inches(31 cm) of the top and one within
12 inches (31 cm) of the bottom of the enclosure.
over 2,000 - 5,000ft
(over 610 - 1524 m)
Reduce maximum vent
length by 20 ft(6.1 m)
No reduction in vent
length required
2
over 5,000 - 8,000 ft Use only 3" (7.6 cm)
(over 1524 - 2439 m) PVC (Tables 8 & 10)
No reduction in vent
length required
All Air From Outdoors: The confined space must be provided with two
permanent openings, one commencing within 12 inches(31 cm) of the top and
one commencing within 12 inches (31 cm) from the bottom of the enclosure.
The openings must communicate directly, or by ducts, with the outdoors or
spaces (crawl or attic) that freely communicate with the outdoors.
over 8,000 - 10,000 ft Use only 3" (7.6 cm)
(over 2439 - 2540 m) PVC (Tables 8 & 10)
Reduce maximum vent
length by 20 ft(6.1 m)
7
Download from Www.Somanuals.com. All Manuals Search And Download.
RP V-I&S
1. When directly communicating with the outdoors, each opening must have
2
WARNING
a minimum free area of 1 square inch per 4000 BTU(6.5 cm /1.2 kw) per
For protection against excessive temperatures and pressure, install
temperature and pressure protective equipment required by local codes,
but not less than a combination temperature and pressure relief valve
certified by a nationally recognized testing laboratory that maintains
periodic inspection of production of listed equipment or materials as
meeting the requirements of the Standard for Relief Valves and Automatic
Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22 or the
Standard CAN1-4.4. Temperature and Pressure and the StandardCAN1-
4.4, Temperature, Pressure, Temperature and Pressure Relief Valves
and Vacuum Relief Valves. The combination temperature and pressure
relief valve shall be marked with a maximum set pressure not to
exceed the maximum working pressure of the water heater. The
combination temperature and pressure relief valve shall also have an
hourly rated temperature steam BTU discharge capacity not less than
the hourly rating of the water heater.
hour of total input rating of all equipment in the enclosure.
2. When communicating with the outdoors through vertical ducts, each
opening must have a minimum free area of 1 square inch per 4000 BTU
2
(6.5 cm /1.2 kw) per hour of total input rating of all equipment in the
enclosure.
3. When communicating with the outdoors through horizontal ducts, each
opening must have a minimum free area of 1 square inch per 2000 BTU
2
(6.5 cm /0.6 kw) per hour of total input rating of all equipment in the
enclosure.
4. When ducts are used, they must be of the same cross-sectional area as
the free area of the openings to which they connect. The minimum
dimension of rectangular air ducts must be not less than 3 inches
(7.5 cm).
Install the combination temperature and pressure relief valve into the
opening provided and marked for this purpose on the water heater.
Specially Engineered Installations
The requirements noted under CONFINED SPACES above must not necessarily
govern when special engineering, approved by the authority having jurisdiction,
provides an adequate supply of air for combustion, ventilation, and dilution of
flue gases.
Note: Some models may already be equipped or supplied with a
combination temperature and pressure relief valve. Verify that the
combination temperature and pressure relief valve complies with local
codes. If the combination temperature and pressure relief valve does
not comply with local codes, replace it with one that does. Follow the
installation instructions above on this page.
WATER CONNECTIONS
Install a discharge line so that water discharged from the combination
temperature and pressure relief valve will exit within six (6) inches
(15.2 cm) above, or any distance below the structural floor and cannot
contact any live electrical part. The discharge line is to be installed to
allow for complete drainage of both the combination temperature and
pressure relief valve and the discharge line. The discharge opening
must not be subjected to blockage or freezing. DO NOTthread, plug
or cap the discharge line. It is recommended that a minimum clearance
of four (4) inches (10.2 cm) be provided on the side of the water
heater for servicing and maintenance of the combination temperature
and pressure relief valve.
Note:
BEFORE PROCEEDING WITH THE INSTALLATION, CLOSE THE MAIN WATER SUPPLY VALVE.
After shutting off the main water supply, open a faucet to relieve the water line
pressure to prevent any water from leaking out of the pipes while making the
water connections to the water heater. After the pressure has been relieved,
close the faucet. The COLD water inlet and HOT water outlet are identified on
the top of the water heater. The fittings at the cold water inlet and hot water
outlet are dielectric waterway fittings with 3/4" NPT male thread. Make the
proper plumbing connections between the water heater and the plumbing
system to the house. Install a shut-off valve in the cold water supply line.
Do not place a valve between the combination temperature and pressure
relief valve and the tank.
CAUTION
If sweat fittings are to be usedDO NOT applyheattothenipplesontopofthe
water heater. Sweat the tubing to the adapter before fitting the adapter to the
waterconnections.Itisimperativethatheatisnotappliedtothenipplescontaining
a plastic liner.
WARNING
Hydrogen gas can be produced in an operating water heater that
has not had water drawn from the tank for a long period of time
(generally two weeks or more). Hydrogen gas is extremely
flammable. To prevent the possibility of injury under these conditions,
we recommend the hot water faucet to be open for several minutes
at the kitchen sink before you use any electrical appliance which is
connected to the hot water system. If hydrogen is present, there
will be an unsual sound such as air escaping through the pipes as hot
water begins to flow. Do not smoke or have open flame near the
WARNING
FAILURE TO INSTALL AND MAINTAIN A NEW, LISTED 3/ 4” X 3/ 4”
TEMPERATURE AND PRESSURE RELIEF VALVE WILL RELEASE THE
MANUFACTURER FROM ANY CLAIM THAT MIGHT RESULT FROM
EXCESSIVE TEMPERATURE AND PRESSURES.
If this water heater is installed in a closed water supply system, such as one
having a back-flow preventer in the cold water supply, provisions must be made
faucet at the time it is open.
to control thermal expansion. DO NOToperate this water heater in a closed This water heater can deliver scalding temperature water at any faucet in the
system without provisions for controlling thermal expansion. Your water supplier system. Be careful whenever using hot water to avoid scalding injury. Certain
or local plumbing inspector should be contacted on how to control this situation appliances such as dishwashers and automatic clothes washers may require
increased temperature water. By setting the thermostat on this water heater to
After installation of the water lines, open the main water supply valve and fill obtain the increased temperature water required by these appliances, you
the water heater. While the water heater is filling, open several hot water may create the potential for scald injury. To protect against injury, install an
faucets to allow air to escape from the water system. When a steady stream anti-scald tempering valve in the water system. This valve will reduce point of
of water flows through the faucets, close them and check all water connections discharge temperature by mixing cold and hot water in branch supply lines.
for possible leaks. NEVER OPERATE THE WATER HEATER WITHOUT Such valves are available from the local plumbing supplier. Please consult with
FIRST BEING CERTAIN IT IS FILLED WITH WATER.
a plumbing professional.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
RP V-I&S
ELECTRICAL CONNECTIONS
All electrical wiring and connections must be in accordance with the National
Electric Code ANSI/NFPA No. 70 (latest edition), or the Canadian Electrical
Code C22.1 (latest edition) and any local codes which may apply. The water
heater must be electrically grounded.
If a flexible line cord and plug is permitted by local code, then provide a (3)
three wire grounding type receptacle within 6 feet (1.9 m) of the water heater
and use the flexible cord provided. Do not plug the line cord into a receptacle
that can have its power supply interrupted by a switch that is used to turn on
and off lights.
If wiring in conduit is required, remove the flexible line cord from the jacket and
install a 1/2" electrical conduit connector and connect 110/120 volt power
source. Connect the hot, neutral, and ground leads of the electrical supply to
the corresponding locations that were connected to the flexible line cord.
CAUTION
Turn off or disconnect the electrical power supply to the water heater
before servicing. Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
GAS CONNECTIONS
The gas supply lines must meet all requirements of the National Fuel Gas Code
ANSI Z223.1-(Latest Edition) and/or in Canada CAN/CGA B149 Installation
Codes - (Latest Editions).
The wiring diagram for the 48 gal, 65,000 BTU (181.7 L, 19.1 Kw/Hr), 65 gal,
65,000 BTU (246.1 L, 19.1 Kw/Hr) and 75 gal, 76,000 BTU input (283.9 L, 22.3
Kw/Hr) models is located in (Figure 11) on page 10. The wiring diagram for the
40 gal, 40,000 BTU (151.4 L, 11.7 Kw/Hr) and 48 gal, 40,000 BTU (181.7 L,
11.7 Kw/Hr) models are located in Figure 12 on page 11. Refer to the rating
plate located on the water heater for correct model identification.
The minimum permissible gas supply pressure for the purpose of input
adjustment is 1.5" water column (.37 kPa) above the operating manifold
pressure for natural gas and 1.0" (0.25 kPa) water column for L.P. gas. See the
rating plate and combination gas control for the manifold pressure and gas
type.The maximum permissible gas supply pressure is 14.0" water column(3.5
kPa) for natural gas and liquefied petroleum gases/propane gas.
GENERAL OPERATION
WARNING
Waterheatersareheatproducingappliances.Toavoiddamageorinjurytheremust
benomaterialsstoredagainstthewaterheaterorvent-airintakesystemandproper
care must be taken to avoid unnecessary contact (especially by children) with the
1. Connect this water heater only to the type of gas (Natural or Propane
gas) as shown on the rating plate. Use clean 1/2 inch black iron pipe.
(Dirt and scale from the pipe can enter the combination control and
cause it to malfunction). The inlet gas line must have a minimum length
of 3" (7.6 cm) drip leg (sediment trap) installed as close to the water
heater’s combination gas control as possible. A ground joint union must
be installed in the gas supply line feeding the water heater to permit
servicing of the water heater. Compounds used on the threaded joints of
the gas piping must be resistant to the action of liquefied petroleum
gases/propane gas.
water heater and vent-air intake components. UNDER NO CIRCUMSTANCES
SHALL FLAMMABLE MATERIALS, SUCH AS GASOLINE OR PAINT
THINNER BE USED OR STORED IN THE VICINITY OF THIS WATER HEATER,
VENT-AIR INTAKE SYSTEM OR IN ANY LOCATION FROM WHICH FUMES
COULD REACH THE WATER HEATER OR VENT-AIR INTAKE SYSTEM.
TO FILL THE WATER HEATER
1. Close the water heater drain valve by turning the stem clockwise.
2. Open the cold water supply shut-off valve.
3. Open several hot water faucets to allow air to escape from the system.
4. When a steady stream of water flows from the faucets, the water heater is
filled. Close the faucets and check for water leaks at the water heater drain
valve, combination temperature and pressure relief valve and the hot and
cold water connections.
2. This water heater and its gas connection must be leak tested before
placing the water heater in operation. Check for gas leaks with a soap
and water solution and a brush or a commercial leak detector fluid.
NEVER USE A MATCH OR OPEN FLAME FOR TESTING!
3. While checking for leaks care must be taken to prevent solution from
contacting the electrical connections at the control. If electrical connections
at the control become wet, they must be thoroughly dried before
attempting to operate the water heater.
TO DRAIN THE WATER HEATER
Should it become necessary to completely drain the water heater, make sure
you follow the steps below:
1. Shut off the gas supply to the water heater.
2. Turn off/disconnect all electric power to the water heater.
3. Close the cold water supply shut-off valve.
4. Open the drain valve on the water heater by turning the stem
counter-clockwise. The drain valve has threads on the end that will allow the
connection of a standard hose coupling.
5. Open a hot water faucet to allow air to enter the system.
To refill the water heater, refer to “To Fill the Water Heater.”
CAUTION
Thewaterheaterandindividualshutoffvalvemustbedisconnectedfromthegas
supplypipingsystemduringanypressuretestingofthesystemattestpressuresin
excess of ½ psi (3.5kPa). The water heater must be isolated from the gas supply
piping system by closing its manual shutoff valve during any pressure testing of
the gas supply system at test pressures equal to or les than ½ psi (3.5kPa). The
supply line must be capped when not connected to the water heater.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
RP V-I&S
Figure 11
10
Download from Www.Somanuals.com. All Manuals Search And Download.
RP V-I&S
Figure 12
11
Download from Www.Somanuals.com. All Manuals Search And Download.
RP V-I&S
FOR YOUR SAFETY READ BEFORE LIGHTING
Figure 13
WARNING: If you do not follow these instructions exactly, a fire or explosion
may result causing property damage, personal injury or loss of life.
A. This appliance is equipped with an ignition device which automatically
lights the pilot. Do not try to light the pilot by hand.
TEMPERATURE DIAL
B. BEFORE OPERATING smell all around the appliance area for gas. Be
sure to smell next to the floor because some gas is heavier than air and
will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any telephone in your
building.
• Immediately call your gas supplier from a neighbor’s phone. Follow
the gas supplier’s instructions.
TEMPERATURE SETTING
APPROXIMATELY
120°F (49°C)
• If you cannot reach your gas supplier, call the fire department.
DANGER
C. Use only your hand to push in or turn the gas control knob. Never use
tools. If the knob will not push in or turn by hand, don’t try to repair it,
call a qualified service technician. Force or attempted repair may result
in a fire or explosion.
Hotter water increases the risk of scald injury. Scalding may occur
within five (5) seconds at a temperature setting of 135°F (57°C). To
protect against hot water injury, install an anti-scald tempering valve
in the water system. This valve will reduce point of discharge
temperature by mixing cold and hot water in branch water lines. A
licensed plumbing professional or local plumbing authority should be
consulted.
D. Do not use this appliance if any part has been under water, immediately
call a qualified service technician to inspect the appliance and to replace
any part of the control system and any gas control which has been
under water.
Note: This water heater is equipped with an energy cut out device to
prevent overheating. Should overheating occur or the gas supply fail
to shut off, turn off the manual gas control valve to the appliance and
call a qualified service technician.
OPERATING INSTRUCTIONS
1. Stop! Read the safety information above on this label.
2. Turn off all electric power to appliance.
Note: Whenever the water heater is filled with cold water, condensate
will form on the cool tank surface and drops of water will fall on the hot
burner and combustion chamber surfaces producing a “sizzling” noise.
Condensation is normal and does not indicate a leak. It will disappear
when the tank becomes heated.
3. Set the thermostat to the lowest setting.
4. This appliance is equipped with on ignition device which automatically
lights the pilot. Do not try to light the pilot by hand.
5. Slide the switch on the left side of the gas valve to the “OFF” position.
6. Wait five (5) minutes to clear out any gas. Then smell for gas,
including near the floor. If you smell gas, STOP! Follow “B” in the
safety information above on this table. If you don’t smell gas, go to the
next step.
7. Slide the switch on the left side of the gas valve to the “ON” position.
8. Set thermostat to desired setting.
BURNER FLAME CHECK
9. Turn on all electric power to the appliance.
10. If the appliance will not operate, follow the instructiolns “To Turn Off Gas
To Appliance” and call your service technician or gas supplier.
Cast Iron Burner: At the time of installation and at periodic intervals (not
more than 6 months), a visual check of the main burner and pilot flames
should be made to determine if they are burning properly. For ideal operation,
the gas and air must be properly proportioned. The proper air-gas mixture is
obtained by adjusting the air shutter on the mixer face of the main burner (See
Figure 14). To adjust for proper burning, loosen the air shutter nut (if provided),
rotate shutter to close the opening in the burner then slowly rotate the shutter
until the yellow tips disappear and the flame becomes blue. On 75 gallon
models fired on LPG or propane, adjust the air shutter as described above until
the yellow flame is minimized (note-the burner flame may contain a mixture of
yellow and blue). Tighten the air shutter nut. Too much air will cause the flame
to lift off the burner ports and create noisy operation. Too little air will result in
soot formation. The main burner flame should light smoothly from the pilot.
TO TURN OFF GAS TO APPLIANCE
1. Turn off all electric power to the appliance.
2. Set the thermostat to lowest setting.
3. Slide the switch on the left side of the gas valve to the “OFF” position.
THERMOSTAT ADJUSTMENT
CAUTION
Before adjusting thermostat(s), turn off power supply to the water heater.
The thermostat dial is adjusted to approximately 120°F when shipped from the
factory. When adjusting the thermostat, it should be remembered that lower
temperature settings are more energy efficient. The thermostat cover, on the
right side of the gas valve, must be removed when the thermostat is adjusted.
To adjust the thermostat turn the dial colckwise with a screwdriver until the
minimum acceptable temperture is set. It is suggested that the starting point
setting not exceed the 120°F (49°C) or “HOT” setting on the thermostat.
Steel Burner: These models are equipped with self adjusting air mixture and
do not have an adjustable air shutter (See Figure 14). At periodic intervals a
visual check of the main burner and pilot flames should be made to determine
if they are burning properly. The main burner flame should light smoothly from
the pilot.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
RP V-I&S
5. Annually remove the inner door and main burner assembly to clean orifices
and related parts of any dirt or other foreign material. Inspect the burner
ports for obstructions or debris and clean with a wire brush as needed. Wire
brush and/or vacuum clean the combustion chamber as needed to remove
scale deposits and debris. NOTE: It is imperative for proper operation of
the water heater that the inner door be replaced in the original location.
Fig u re 1 4
WARNING
When lifting lever of the combination temperature and
pressure relief valve, hot water will be released under
pressure. Be careful that any released water does not result
in bodily injury or property damage.
7. At least once a year, check the combination temperature and pressure
relief valve to ensure that the valve has not become encrusted with lime.
Lift the lever at the top of the valve several times until the valve seats
properly without leaking and operates freely.
8. Monthly drain off a gallon of water to remove silt and sediment.
MAINTENANCE
WARNING
WARNING! THIS WATER MAY BE HOT.
Water heaters are heat producing appliances. To avoid damage or injury there
shallbenomaterialsstoredagainstthewaterheaterorvent-airintakesystem,
and proper care shall be taken to avoid unnecessary contact (especially by
children) with the water heater and vent-air intake system. UNDER NO
CIRCUMSTANCES SHALL FLAMMABLE MATERIALS, SUCH AS GASOLINE
OR PAINT THINNER BE USED OR STORED IN THE VICINITY OF THIS
WATER HEATER, VENT-AIR INTAKE SYSTEM OR IN ANY LOCATION
FROM WHICH FUMES COULD REACH THE WATER HEATER OR
VENT-AIR INTAKE SYSTEM.
9. If the combination temperature and pressure relief valve on the appliance
discharges periodically, this may be due to thermal expansion in a closed
water supply system. Contact the water supplier or local plumbing inspector
on how to correct this situation. Do not plug the combination
temperature and pressure relief valve outlet.
10. A combination sacrificial anode rod/hot water outlet nipple has been
installed to extend tank life.The anode rod should be inspected periodically
(every 2 years) and replaced when necessary to prolong tank life. Water
conditions in your area will influence the time interval for inspection and
replacement of the anode rod. Contact the plumbing professional who
installed the water heater or the manufacturer listed on the rating plate
for anode replacement information. The use of a water softener may
increase the speed of anode consumption. More frequent inspection of the
anode is needed when using softened (or phosphate treated) water.
IMPORTANT
The water heater should be inspected at a minimum annually by a
qualified service technician for damaged components and/ or joints
not sealed. DO NOT operate this water heater if any part is found
damaged or if any joint is found not sealed.
The following maintenance should be performed by a qualified service technician
at the minimum periodic intervals suggested below. In some installations, the
maintenance interval may be more frequent depending on the amount of use
and the operating conditions of the water heater. Regular inspection and
maintenance of the water heater and vent-air intake system will help to ensure
safe and reliable operation.
11. The induced draft blower has sealed motor bearings and does not require
adding oil.
CAUTION
FOR YOUR SAFETY, DO NOT ATTEMPT REPAIR OF COMBINATION GAS
CONTROL, BURNERS OR GAS PIPING. REFER REPAIRS TO A QUALIFIED
SERVICE TECHNICIAN.
1. Annually check the operation of the thermostat.
Contact your supplier or plumbing professional for replacement parts or contact
the company at the address given on the rating plate of the water heater.
2. The flow of combustion and ventilation air MUST NOT be restricted. Clear
the combustion air openings of any dirt, dust, or other restrictions. WARNING!
The ventilation air system may be HOT.
Provide the part name, model and serial numbers of the water heater when
ordering parts.
3. At all times keep the water heater area clear and free from combustible
materials, gasoline and other flammable vapors and liquids.
4. Bi-annually conduct a visual check of the main and pilot burner flames to
determine that they are burning properly. See Burner Flame Check section
on page 12. If sooting or other burner anomalies are evident, shut down
the water heater by turning off the gas per the instructions listed in this
manual or as listed on the water heater.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
RP V-I&S
THE FOLLOWING INSTRUCTIONS ARE FOR INSTALLATION OF:
GAS WATER HEATERS SUITABLE FOR WATER (POTABLE) HEATING AND SPACE HEATING
1. All piping components connected to this water heater for space heating applications must be suitable for use with potable water.
2. Toxic chemicals, such as those used for boiler treatment, must not be introduced into potable water used for space heating.
3. This water heater must not be connected to an existing heating system or component(s) previously used with a non-potable water heating
appliance.
4. When the system requires water for space heating at temperatures higher than required for other means, a tempering valve must be installed to
temper the water for those uses in order to reduce the scald hazard potential.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
RP V-I&S
d) Cementing must be done quickly to avoid over-drying before joining.
VENT PIPE PREPARATION AND JOINING
i) Apply one coat to the outside end of the pipe at a width
Most failures in PVC, CPVC or ABS systems result from improper preparation and
joining of pipe and fittings. The guidelines below must be followed when
installing the venting system. If you have any question about the application
or installation of the PVC, CPVC or ABS venting system, contact the manufacturer,
supplier, or your plumbing professional.
slightly greater than the depth of the socket.
ii) Apply a coat around the inside of the fitting socket.
iii) Apply a second coat around the end of the pipe.
4) Joining
1) Specific cleaners, solvents, primers and cements are available for PVC,
CPVC and ABS pipe. Be sure these materials match the type of pipe to be
installed. Never use all-purpose cements, commercial glues and adhesives
or ABS cement to join PVC or CPVC pipe and fittings.
a) Joints should be made immediately after cement is applied.
b) After fully inserting pipe into fitting socket, give pipe about ¼ turn
to help spread cement evenly. Hold joint together for about 15 to
20 seconds.
a) CLEANERS, SOLVENTS, PRIMERS AND CEMENTS ARE
FLAMMABLE. Do not store or use these materials near
heat or open flame, or in the vicinity of other appliances.
c) Remove excess cement from around pipe and fitting with a clean
rag.
2) Use proper cutting, deburring and applicator tools to ensure proper
d) Cement drying times may vary. Be sure to allow for the
preparation and joining of pipe and fittings.
recommended drying time before disturbing joints.
a) Cutting Tools
For more specific and detailed information about the above, contact the
manufacturer, supplier, or competent professional.
i) A square cut must be achieved with a miter box saw or pipe
cutter to ensure a proper mating with the female. If a pipe
cutter is used, the burr created at the outer edge of the pipe
must be removed.
b) Deburring Tools
i) A file, knife or plastic deburring tool can be used to remove
burrs. Burrs must be removed from the inside and outside
edges of the pipe to ensure a proper seal.
c) Applicator Tools
i) A pure bristle paintbrush or roller may be used to apply
cement. Prompt application of the cement is important due
its fast drying properties.
3) Inspection, Cleaning, Priming and Cementing
a) Inspect the pipe inside and out for dirt, dust, moisture or grease
etc. Check pipe and fittings for splits or cracks and replace if
necessary.
b) Clean pipe and fittings are imperative for proper joining. Following
cutting and deburring, wipe away any foreign material with a clean
dry rag. If wiping fails to thoroughly clean surfaces, chemical
cleaning is necessary.
c) Primer must be applied to the pipe surface and fitting socket with
a natural bristle brush. This serves to soften and prepare the PVC or
CPVC for cementing.
15