FBP Series Fluorescent Emergency Ballast
FBP750-4P
Page 1 of 1
One or Two Lamp Operation 4-Pin Fluorescent Lamps 750 Lumens
9.4”
(23.8 cm)
1.5”
(3.8 cm)
2.4”
Nickel Cadmium Battery
(6.1 cm)
Complete Fixture consists of ballast unit. Select options and accessories below.
Model #
FBP750-4P
Max. Lumens
750
Lamp Operation
One or Two 4-Pin Fluorescent (without integral starter)
Lamp Operation and Performance
Features
1. Lamp Operation: Operates the following lamp types: T4 Compact Fluorescent
(4-pin base), 13W - 42W twin, quad and triple twin-tube without integral
starter. See Lamp Operation and Performance table for specific lamp perfor-
mance and operation.
Non-Emer. Emer. Op.
Max.
Lumen
Output
Max.
Lumen
Output
Emer
Lamp
Operation
Lamp
Type
Base
Type
Watt.
13
2. Illumination: Provides 90 minutes of emergency illumination, and produces a
maximum of 750 lumens initial emergency light output.
F13DBX/4P
F18DBX/4P
F26DBX/4P
F18TBX/4P
F26TBX/4P
F32TBX/4P
F42TBX/T4
F18BX
G24Q-1
G24Q-2
900
425
575
700
525
725
750
750
400
550
750
650
650
One or Two
One or Two
One or Two
One or Two
One or Two
One or Two
One
18
1150
1710
1200
1800
2200
3200
1250
1800
2850
3150
2850
3. Housing: Constructed of 20 gauge steel with a high temperature powder
coat finish. Housing allows for frame mounting on most recessed luminaires.
Housing includes 2’ lengths of flex conduit attached on each end.
4. Electronics: 120/277 VAC dual voltage input with surge-protected, solid-
state circuitry. Charging system is complete with AC indicator lamp and test
switch.
5. Battery: Maintenance free, sealed nickel cadmium battery has an estimated
service life of 10 years, and an operating temperature range of 32°F (0°C) to
131°F (55°C)
26
G24Q-3
18
GX24Q-2
GX24Q-3
GX24Q-3
26
32
42 GX24Q-4P
18 2G11 4 Pin
One or Two
One or Two
One or Two
One
F27/24BX/RS 27 2G11 4 Pin
F39/36BX/RS 39 2G11 4 Pin
F40/30BX/RS 40 2G11 4 Pin
6. Input Power Requirements: 3.5 watts max.
7. Warranty: Electronics: 2 years; Battery: 2 years.
Code Compliance
F382D/4P
38
GR10Q-4
One or Two
UL 924 listed. UL damp location listing optional.
Options
EX = Special Input Transformer for 220 VAC/50 Hz, 240 VAC/50Hz. Contact
factory for other input voltages and frequencies.
DL = UL Damp Location Listing
Notes:
1. Maximum non-emergency lumen output can vary based on lamp manufacturer, ambient operating
temperature, and ballast manufacturer.
2. Maximum emergency lumen output is based on total output of one or two lamps, and can vary
based on lamp manufacturer and ambient operating temperature.
3. Maximum emergency lumen output is supported for a full 90 minutes of operation.
4. Consult factory for compatibility, operation and performance of lamp types not listed.
Accessories
CCAPS = Wire bundle cover for mounting external to luminaire.
RT = Remote Test Switch.
Job Information
Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
Lightolier is a Philips group brand