AC Power
For Business-Critical Continuity™
Liebert® GXT3-10000T220™
User Manual, 10kVA, 50/60 Hz, 120/208/220V
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
INTRODUCTION AND SYSTEM DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Device Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
UNPACKING THE UPS AND SITE PREPARATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Required Setup Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Unpacking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Environmental Conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Access to Area. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Floor Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Inventory List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Electrical preparations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Suggested Cable Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
External Protection and Isolating Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
External Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Connecting Utility and Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Terminal Blocks for UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.6.1 Input and Output Connection Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Connecting Power Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
External Battery Cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.2.1 Controls and Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.2.2 Battery Setup Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.2.3 Warning Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.2.4 Fault Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Initial UPS Startup Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
UPS Shutdown Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Maintenance Bypass Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Return from Maintenance Bypass. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Maintenance Breaker, Off Position. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Self-Tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.8.1 Lamp Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.8.2 Battery Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
i
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Test, Replacement and Disposal of Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Communication Interface Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Dry Contact. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.2.1 Any Mode Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.2.2 Battery Mode Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.2.3 On Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.2.4 Low Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.3
Liebert IntelliSlot® Communication Cards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.3.1 Liebert MultiLink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Remote Emergency Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
®
®
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
PRODUCT WARRANTY REGISTRATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
FIGURES
Figure 1
Figure 2
Liebert GXT3-10000T220 control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
®
™
Liebert GXT3-10000T220 front and rear views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Side view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Single source input supply—input and output connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Dual source input supply—input and output connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Hardwire terminals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Liebert GXT3-10000T220 with External Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
System block diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 10 Control Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 11 Menu tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 12 Dry contact pin layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
TABLES
Table 9
Overview of UPS devices and batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Connection data * . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Displayed text—system block and main menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Battery setup parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Warning indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Fault indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Replacement battery pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Troubleshooting guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Liebert® GXT3™ specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table 10 Battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
™
Table 11 Typical battery run times for the Liebert® GXT3-10000T230 . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
ii
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions. Read all safety and operating instructions before
operating the uninterruptible power system (UPS). Adhere to all warnings on the unit and in this
manual. Follow all operating and user instructions. This equipment must be operated only by
individuals who are properly trained and qualified.
This product is designed for commercial/industrial use only. It is not intended for use with life support
and other designated “critical” devices. Maximum load must not exceed that shown on the UPS rating
label. The UPS is designed for data processing equipment. If uncertain, consult your dealer or local
Emerson Network Power representative.
This UPS is designed for use on a properly earthed (grounded), 208 or 220 VAC, 50Hz or 60Hz supply,
for installation by qualified personnel. A qualified electrician must review and approve customer-
supplied wiring, circuit breakers and intended loads and verify correct input, output and earth
connections to ensure compliance with technical standards and local electrical codes of practice.
Installation instructions and warning notices only for use by properly trained and qualified personnel
are located after the UPS operator instructions in this manual.
Install the UPS in a clean environment, free from moisture, flammable liquids, gases and corrosive
substances.
This UPS contains no user-serviceable parts except the internal battery pack. The UPS On/Off
push buttons do not electrically isolate internal parts. Under no circumstances attempt to gain access
internally due to the risk of electric shock or burn.
Do not continue to use the UPS if the front panel indications are not in accordance with these
operating instructions or the UPS performance alters in use. Refer all faults to your dealer.
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and
the required precautions. Keep unauthorized personnel away from the batteries. Proper disposal of
batteries is required. Refer to your local laws and regulations for disposal requirements.
Never block or insert any object into the ventilation holes or other openings.
DO NOT CONNECT equipment that could overload the UPS or demand DC current from the UPS,
for example: electric drills, vacuum cleaners, laser printers, hair dryers or any appliance using
halfwave rectification.
WARNING
precautions should be observed before replacing the battery pack:
!
The battery can present a risk of electrical shock and high short circuit current. The following
• Wear rubber gloves and boots
• Remove rings, watches and other metal objects.
• Use tools with insulated handles.
• Do not lay tools or other metal objects on the batteries.
• If the battery kit is damaged in any way or shows signs of leakage, contact your local Emer-
son representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
• Handle, transport and recycle batteries in accordance with local regulations.
• Even when all switches and interrupters are open, hazardous voltages are present within
the UPS; any operation that requires protective panels to be opened or removed may be car-
ried out by Emerson-authorized technical personnel only.
1
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING
!
!
Although the Liebert® GXT3™ has been designed and manufactured to ensure safety,
improper use can result in electrical shock or fire. To ensure safety, observe the following
precautions:
• Turn Off and isolate the Liebert GXT3 before cleaning it. Use only a soft cloth; never use
liquid or aerosol cleaners.
• Never block or insert any objects into the ventilation holes or other openings of the UPS.
• Do not place the Liebert GXT3 power cord where it might be damaged.
CAUTION
®
• When installed in EU countries, the Liebert GXT3-10000T220™ is not intended to operate
with isolated neutral (IT systems). Neutral connector must be present and connected to the
UPS.
the utility. To isolate completely from the utility, the power cables must be disconnected.
• In case of interruption of the utility voltage, the integrated battery maintains the power
supply to the user equipment.
• Lay all cables so that nobody can stand on them or trip over them. When connecting the
• In emergencies (e.g., damaged case, controls or power cables, penetration of liquids or for-
eign matter), switch off the device and contact the appropriate customer service representa-
tive.
• Do not connect equipment that will overload the UPS (e.g., laser printers or vacuum clean-
ers) or demand DC-current (e.g., half-wave rectifiers).
• The sum of the leakage currents (protective conductor current) of the UPS and the con-
nected devices exceeds 3.5 mA for all ratings of the UPS. Ground (earth) connection is
essential before connecting supply.
• Data transmission lines should not be connected or disconnected during a thunderstorm.
circuit will immediately shut down the UPS output.
• When installed in EU countries, an Emergency Switching Device (E.S.D.) must be fitted
downstream of the UPS for the wiring installation safety to comply with the European Har-
monized Document HD384-4-46 S1.
• Maintenance bypass breaker is for the use of service personnel only. The breaker is on the
rear of the unit. To operate the breaker, the captive screw must be loosened and the guard
must be lifted out of position.
2
Download from Www.Somanuals.com. All Manuals Search And Download.
Leakage Current
WARNING
!
Connect the ground (earth) safety conductor before connecting any other cables.
ELECTROMAGNETIC COMPATIBILITY—The Liebert® GXT3™ complies with the limits for a
Class A Digital Device, Pursuant to Part 15 of FCC rules. Operation is subject to the following
conditions:
• This device may not cause harmful interference
• This device must accept any interference received, including interference that may cause
undesired operation. Operating this device in a residential area is likely to cause harmful
interference that users must correct at their own expense.
The Liebert GXT3 series complies with the requirements of EMC Directive 2004/108/EC and the
published technical standards. Continued compliance requires installation in accordance with these
instructions and use of accessories approved by Emerson.
NOTICE
Operating the Liebert GXT3 in residential areas may cause radio interference that the user
must to correct at his own expense.
Information for the Protection of the Environment
UPS SERVICING—This UPS makes use of components dangerous for the environment (electronic
cards, electronic components). The components removed must be taken to specialized collection and
disposal centers.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction and System Description
1.0 INTRODUCTION AND SYSTEM DESCRIPTION
Congratulations on your choice of the Liebert® GXT3™-10000T220 UPS. It provides conditioned power
to microcomputers and other sensitive electronic equipment.
When generated, AC power is clean and stable. However, during transmission and distribution it is
subject to voltage sags, spikes and complete power failure that may interrupt computer operations,
cause data loss and damage equipment. The Liebert GXT3-10000T220 protects equipment from these
disturbances.
The Liebert GXT3-10000T220 is an on-line UPS. An on-line UPS continuously conditions and
regulates its output voltage whether utility power is present or not. It supplies connected equipment
with clean sinewave power. Sensitive electronic equipment operates best from sinewave power.
The liquid crystal display is used for controlling operation of the UPS, as well as monitoring its
status, condition, alarm status and history. For ease of use, the Liebert GXT3-10000T220 features a
light-emitting diode (LED) display to indicate operational status. It also provides self-diagnostic tests,
a combination On/Alarm Silence/Battery Test button, a Standby button, user configurable program
and two levels of alarms when the unit is operating on battery.
The Liebert GXT3-10000T220 has an interface port for communication between the UPS and a
network server or other computer system. This port provides detailed operating information including
voltages, currents and alarm status to the host system when used in conjunction with Liebert’s
®
MultiLink software. Liebert MultiLink software may also control UPS operation remotely.
CAUTION
!
This UPS may be operated only by properly trained and qualified personnel.
Figure 1 Liebert GXT3-10000T220 control panel
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction and System Description
1.1
Device Overview
The following table provides an overview of the various versions of the device:
Table 1 Overview of UPS devices and batteries
Type Model #
UPS with Integrated Battery Liebert GXT3-10000T220
Nominal power
10000VA/90000W
—
™
®
™
Battery Cabinet
Liebert GXT3-240TBATTCE
®
™
Figure 2 Liebert GXT3-10000T220 front and rear views
Control Panel
Liquid Crystal
Display
Push Button
Controls
Ventilation
Louvers
External
Battery
Connector
Maintenance
Bypass Breaker
(cover removed
for clarity)
®
Liebert IntelliSlot
Communication
Card slot
Input
Circuit
Breaker
USB Port
Dry Contacts
Bypass
Circuit
Breaker
REPO
Output
Circuit
Breaker
Hardwire Input
and Output
Connectors
(Protective
Cover Shown)
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Unpacking the UPS and Site Preparation
2.0 UNPACKING THE UPS AND SITE PREPARATION
2.1
Inspection
Upon receiving your Liebert® GXT3-10000T220™, examine the packaging for any signs of
mishandling or damage. While removing shipping materials, inspect the UPS for damage. If any
damage is noted, notify your local Liebert representative and your carrier.
2.2
Required Setup Equipment
The following tools are required to set up your Liebert GXT3-10000T220:
• pallet jack
• utility knife or scissors
• screwdrivers—Phillips and straight blade
2.3
Unpacking
Exercise care when removing the packaging to avoid damaging the UPS. Check all packaging to
WARNING
pallet, use at least two persons.
!
The UPS is heavy and will roll when on an incline. When removing the unit from its shipping
1. Using a pallet jack, move the Liebert GXT3-10000T220 near its installation site.
2. Unlock all the snaps securing the shipping case to the shipping pallet.
3. Lift the shipping case off the UPS.
4. Remove the EPE packing cushions from around the Liebert GXT3-10000T220.
5. Remove the ramp from the front and slip into the slot on the front of the shipping pallet.
6. Roll the UPS off the shipping pallet.
Figure 3 Unpacking
Packing Cushion
(EPE)
Plywood
Case
GXT3 T220
UPS
Ramp in slot
on shipping pallet
Ramp
Unlock
Storage
If the UPS will be stored, it must be placed indoors in a clean, dry area. Protect all the equipment,
including its batteries, from extreme temperatures, high humidity, spills and other damaging
Handling
The equipment must be kept upright at all times and handled with care. It may be damaged if
dropped or subjected to severe impact.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Unpacking the UPS and Site Preparation
2.4
Environmental Conditions
Install the Liebert® GXT3™ indoors in a controlled environment where it cannot be accidentally
turned off. Place it on a level, even surface in an area with unrestricted airflow around the unit. The
installation location must be free of water, flammable liquids, gases, corrosives and other conductive
contaminants. Maintain a minimum clearance of 100mm (4 inches) in the front and rear of the UPS.
Maintain an ambient temperature range of 0 to 40°C (32 -104°F).
NOTE
UPS operation in sustained temperatures outside the range of 15-25°C (59°-77°F) will reduce
battery life.
2.5
Access to Area
The area where the Liebert GXT3-10000T220 is to be placed must have sufficient space for
installation procedures and for routine maintenance. The UPS is narrow enough to pass through
standard doorways.
2.6
2.7
Floor Loading
Ensure that the floor where the UPS will be installed will support the unit’s weight (see Table 9 for
the unit’s weight).
Inventory List
• CD containing:
• Liebert MultiLink® shutdown software
• Configuration Software
• User Manual
• Terminal Block Communication terminals
• Floor-mount brackets
• Warnings, safety instructions booklet and WEEE recycling sheet (ISO 14001 compliance)
• USB cable
• Hardwire terminal block cover plate and mounting screws
• Single input bypass jumper
• Battery cabinets contain one DC power cable
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
3.0 INSTALLATION
3.1 Electrical preparations
Before beginning installation, the input source must be isolated and locked out to prevent connection
during installation. The input circuit breaker on the rear of the UPS must be in the Off position.
WARNING
applicable safety standards.
!
Installation may be carried out only by qualified technicians and in conformity with the
WARNING
!
Electric shock hazard: Even when the unit is disconnected from the utility, hazardous voltage
may still be supplied by the battery. Both poles must be disconnected before any work is
performed inside the UPS.
WARNING
immediately upon application of AC input.
!
If the Maintenance Bypass Breaker is in the Bypass position, output power is available
3.2
Suggested Cable Sizes
Table 2
Connection data *
®
Units
Liebert GXT3-10000T220™
Description
2
Connector size
AWG (mm )
Arms
6 (10)
56*
Max input current
2
Input cable size (∅ and neutral)
Max output current
AWG (mm )
6 (10)
56*
Arms
2
Output cable size (∅ and neutral) AWG (mm )
6 (10)
6 (10)
10 (113)
2
Ground (Earth) Cable Size
AWG (mm )
Terminal Torque
lb-in (Ncm)
*
Cable must be 90°C copper wire
NOTE
To reduce electromagnetic interference:
• Enclose input and output cables to the UPS in separate metal conduits.
• Use shielded communication cables and route separately from power cables
3.3
External Protection and Isolating Devices
An external 70A disconnect switch must be installed upstream of the UPS to protect power cabling
and provide a means of isolating the UPS from utility.
WARNING
system as the UPS, even when these are located at a distance from the area.
!
The following label must be displayed on all switching devices installed in the same electrical
ENSURE THAT THE UNINTERRUPTIBLE POWER SYSTEM IS ISOLATED BEFORE
WORKING ON THIS CIRCUIT
CAUTION
!
A disconnect switch must be provided by others for AC output circuit. To reduce the risk of
fire, connect only to a circuit provided with branch circuit overcurrent protection for 70A
rating in accordance with the National Electric Code, ANSI/NFPA 70.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
3.4
External Electrical Connections
The external electrical connections may be accessed by removing the protective panel on the rear of
your cabling, based on local electrical codes.
WARNING
!
Before removing electric protective panel, ensure that the UPS is isolated.
Figure 4 Side view
Rear Panel
Cable Entry Cover
NOTE
Once installation has been completed, adjust leveling feet to prevent the UPS from moving.
3.5
3.6
Connecting Utility and Load
Connect the utility supply to the input terminals of the UPS. If the Liebert GXT3-10000T220™ is
®
supplied by single-phase utility, connect the live phase to input L1.
Terminal Blocks for UPS
CAUTION
!
Power is connected through the input breaker, even when the UPS is in bypass mode.
Opening the input breaker when in bypass mode will disconnect output power to the
connected load.
Figure 5 Single source input supply—input and output connections
UPS Input ~
Bypass Input ~
L1 L2
Output ~
X2 X3
BYP L1
L2
GET X1
X4
120
208
220
Single Feed
Jumper
120
0
240
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Figure 6 Dual source input supply—input and output connections
UPS Input ~
Bypass Input ~
L1 L2
Output ~
X2 X3
BYP L1
L2
GET X1
X4
120
208
220
UPS Feed
Bypass Feed
120
0
240
Figure 7 Hardwire terminals
Jumper
removed
for clarity
3.6.1 Input and Output Connection Requirements
• Any 120V loads must be distributed evenly between X1-X2, X1-X4 and X4-X2. Do not connect
loads between X3-X2 or between X3-X4—these are not standard voltages.
• The single-phase isolation output transformer is a separately derived source. The output Neutral
(X2) is bonded to Ground within the UPS cabinet. No other bonding wire is needed.
• Install a Grounding Electrode Terminal (GET) to the nearest grounding electrode in the building
grounding electrode system. If the grounding electrode conductor must be protected, non-metallic
conduit is recommended. If metal conduit must be used, bond both ends of the conduit to the
grounding electrode conductor. Conduit is not an acceptable grounding electrode conductor.
• The utility may be derived from a single-phase or three-phase source. The line-to-ground voltages
are dependent on the grounding of the utility and do not affect the output voltages. Do not use a
floating AC source.
• With dual input source configuration, both sources are tied together within the UPS cabinet. Two
additional ground screw terminals are supplied for use as needed.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
3.7
Connecting Power Cables
1. Open the UPS input breaker.
2. Open the UPS bypass breaker.
3. Set the maintenance breaker to the Bypass position.
4. Remove the electrical connection protective panel, if installed, from the rear UPS panel.
• If the bypass input is to be supplied separately, connect the bypass source to the corresponding
bypass terminals.
• If the UPS is supplied from a single feed, connect the factory-supplied jumper between terminal
UPS Input-BYP and Bypass Input-L1.
3.8
External Battery Cabinets
®
Up to four external battery cabinets may be connected to the Liebert GXT3-10000T220™. A cable to
connect the battery cabinet and the Liebert GXT3-10000T220 is supplied with each battery cabinet.
Open the breaker before making battery cable connections.
Plug one end of this cable into the UPS and the other end into the battery cabinet—slotted fittings on
each end ensure that the connection is properly made. If your UPS has an integrated battery, a
compensating current may occur during connection. Once both ends of the cable have been connected,
the circuit breaker on the external battery cabinet must be closed.
Figure 8 Liebert GXT3-10000T220 with External Battery Cabinet
Battery Breaker
(Liebert GXT3-240TVBATTCE)
External Battery Cabinet
Connector for
Liebert GXT3-240TVBATTCE
additional cabinet
External
Battery
Cabinet
Connector
UPS
Rear View
External
Battery
Cabinet
Rear View
CAUTION
!
Battery maintenance must be performed only by authorized personnel who are properly
trained and qualified.
External battery cabinets are hot-swappable; they can be replaced during normal UPS
operation.
DO NOT connect or disconnect batteries when the UPS is in Battery Mode.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
4.0 OPERATION
4.1
Block Diagram
®
The Liebert GXT3-10000T220™ consists of the following main components:
• 2 utility inputs with separate breakers—utility and bypass
• rectifier/booster, inverter and charger
• electronic bypass
• 2-position Maintenance Bypass Breaker—UPS and BYPASS
• integrated battery
Figure 9 System block diagram
Input
Output
Dynamic
Bypass
V bp
X1
X3
Rectifier/
PFC
DC-to-DC
Converter
TVSS &
EMI/RFI
Filters
Isolation
Transformer
L1
N
L1
N
Inverter
X4
X2
Battery
Charger
Battery
G
G
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
4.2
Control Panel
The Control Panel’s LCD and buttons are used to initiate various UPS operations, tests and
commands and to view the status of the UPS.
By pressing the Menu Up or Menu Down and Enter keys , it is possible to scroll through the
Figure 10 Control Panel
Fault
LED
Battery UPS On
LED LED
Bypass
LED
LCD
Escape key
Enter key
Menu Up key
Menu Down key
4.2.1 Controls and Messages
Lighted LEDs
• UPS ON—UPS is in normal, online operation
• BYPASS—Load is supplied by the utility via automatic bypass
• BATTERY—Load is supported by the battery
• FAULT—A problem has developed within the UPS
Flashing LED
When the BYPASS LED is flashing, the utility is out of tolerance.
NOTICE
Risk of loss of power to connected load. Can cause equipment damage.
Never switch the UPS Off or switch from Online to Bypass in this status, because the load
would no longer be supplied.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Figure 11 Menu tree
Turn UPS
On/Off
Battery
Test
Alarm
Control
Control
Status
Battery
Test
Battery
Test
Contrast
Set
Battery
Test
Audible
Alarm
Output
Voltage
Start
Window
Parallel
Menu
Battery
Pack
System
Status
Battery
Test
Main
Interval
Setup
DC Start
UPS
Address
Parallel
Model
Tag
Number
Language
Event Log
Clear
Log
Types
IP
About
Version
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Table 3
Displayed text—system block and main menu
Item # and Name
Description
Measure
value
Unit
Output Volt
Output Freq
V
0.1Hz
Output
Current
A
Output Watt
Output VA
W
VA
Output Load
Input Volt
%
Status Menu
V
L2 Input Volt
L3 Input Volt
Input Freq
N/A
N/A
0.1Hz
Back Voltage
Batt Capacity
Backup Time
Run Time
V
%
min:sec
day:hr:min:sec
Tag Number
Setting item
Setting (level 1)
Disable/Enable
208/220/230/240V
Audible alarm
Output voltage
Battery pack
Battery Test interval
DC start
1
1-3
Setup Menu
Disable/Enable
00000-99999
Tag Number
Language
English/French/Spanish/German/Italian/ Russian
*
Event and time
Logging
Menu
Clear event log
* : Max 4 fault event record
®
™
Type of UPS
Internet IP
Liebert GXT 10KVA
Liebert GXT3-10000T220 Capacity 10KVA
Firmware
Version
Web: www.liebert.com
Software
version
Display Firmware
version
DSP Firmware version
10kVA UPS Self testing
please wait
Start Window
Main Menu
Wait about 6 sec
Control
Status
Setup
Log
About
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Table 3
Displayed text—system block and main menu (continued)
Item # and Name
Description
Turn UPS ON/OFF
Turn UPS to ONLINE
Turn UPS to BYPASS
Turn UPS to shutdown
Turn UPS to no output
Alarm ON
Alarm control
Batt Test
Control
Menu
Alarm OFF
Batt Test
Cancel Battery Test
Battery Test Report
Darker
Contrast
Lighter
Test in
progress
Test to Low-Battery
Test OK!
Test fail
Cancel Battery test
Battery Test report
Battery
Test Report
Test stop by
user
Test
unknown
4.2.2 Battery Setup Parameters
Table 4
Battery setup parameters
Internal Battery Quantity External Quantity 12V Battery
Parameter (X = Integrated)
Battery Cabinets
Blocks in Sum
1
2
3
X
X
X
—
1
20
60
2
100
4.2.3 Warning Indicators
If a warning indication appears, the UPS continues to operate. The warning message alternates with
UPS mode once a second.
The various possible warning indicators are listed in the following table:
Table 5
Warning indicators
Warning
Cause
Corrective steps
1
2
4
Batt undervolt.
Utility failure
Over temp. 65
N/A
N/A
Reduce load
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
4.2.4 Fault Indicators
If a fault occurs, the UPS automatically switches to BYPASS mode, ONLY in case of a battery
disconnect fault will the original operating mode be maintained. The fault message alternates with
UPS mode once a second, the red Fault LED illuminates on the control panel and the buzzer sounds
continuously. If a fault occurs, proceed as follows:
Buzzer alarm operation—The buzzer alarm can be switched On or Off.
Clear fault—Present fault condition can be reset if fault condition is cleared, either automatically or
by the operator/technician.
Fault information—A maximum of 4 fault events may be displayed in this window. All fault
displays include: the nature of the fault event, and the time it occurred; the time is relative to the
UPS operating time.
Display faults—The various possible fault indicators are listed in the following table.
Table 6
Fault
1.
Fault indicators
Cause
Corrective steps
Call customer service
Call customer service
Reduce load
DC BUS fault
Inverter fault
2.
3.
Overtemperature
Batt over volt.
4.
Call customer service
5.
Batt. mode overload Reduce load
6.
Output overload
Output short
Reduce load
7.
Call customer service
Call customer service
Check battery connector
Call customer service
NA
8.
Fan lock fault
Batt. Disconnect
Charger failure
ESD activated
Parallel fault
9.
10.
11.
12.
13.
14.
Call customer service
Call customer service
Call customer service
Internal fault
Output failure
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
4.3
Initial UPS Startup Procedure
1. Inspect all power connections to ensure they are correct and secure.
2. Open external circuit breakers/fused disconnects to the connected loads.
3. Close all upstream circuit breakers and fused disconnects.
4. Use a voltmeter to verify proper input voltage is present on the UPS and Bypass input terminals.
5. Close the input breakers on the rear panel of the UPS (UPS input and Bypass input).
6. Turn the Maintenance Bypass Breaker to the Bypass position (remove the cover plate if
attached).
7. Use a voltmeter to verify that the proper output voltage is present on the UPS output terminals.
8. Turn the Maintenance Bypass Breaker to the Off position and reinstall the cover plate..
NOTE
The maintenance bypass breaker cover must be installed behind the captive screw and the
screw must be tightened for the UPS to operate on inverter mode.
9. Use a voltmeter to verify the output voltage is NOT present on UPS output terminals.
10. Use the LCD display and control buttons to start the UPS, refer to 4.2.1 - Controls and
11. Use a voltmeter to verify proper output voltage is present on UPS output terminals. See Table 9
for range.
CAUTION
!
Before reinstalling the hardwire terminal protective panel, follow the shutdown procedure in
12. Open all upstream circuit breakers and fused disconnects.
13. Reinstall the hardwire terminal protective panel.
4.4
UPS Shutdown Procedure
NOTE
Carrying out this procedure will interrupt the supply to the load.
1. Press the Menu button, select Control and press the Enter key
.
2. Select Turn UPS On/Off and press the Enter key
.
The LCD displays Turn UPS to BYPASS.
3. Press the Enter key
to switch off the inverter.
4. Open any external circuit breakers/fused disconnects connecting the load (if present).
5. Switch both Input circuit breakers to the Off position.
6. Ensure all circuit breakers/fused disconnects upstream of the UPS are open.
7. Ensure that all LEDs on the control panel are extinguished.
The UPS is now completely shut down.
4.5
Maintenance Bypass Procedure
1. Press the Menu button, select Control and press the Enter key
2. Select Turn UPS On/Off and press the Enter key
The LCD displays Turn UPS to BYPASS. The UPS is now on Internal Bypass Mode.
.
.
4. Remove the safety cover from the Maintenance Bypass Breaker and turn UPS to BYPASS.
NOTE
At this point the load is no longer protected against interruptions and disturbances on the
utility supply.
The UPS is now in Maintenance Bypass Mode. The Bypass LED on the front panel is illuminated
(amber) and the load is supplied directly from the utility.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
4.6
Return from Maintenance Bypass
1. Ensure all switches and circuit breakers upstream of the UPS are closed.
2. Ensure that both input circuit breakers are in the On position.
3. Turn the Maintenance breaker from BYPASS to UPS and replace the cover.
The load now is supplied via electronic bypass.
4. Press the Menu button, select Control and press the Enter key
.
5. Select Turn UPS On/Off and press the Enter key
.
The LCD displays Turn UPS to ONLINE.
6. Press the Enter key
to switch on the inverter.
The UPS is now in online operation.
4.7
4.8
Maintenance Breaker, Off Position
• Move the breaker to the Off position to transfer the load from the UPS to utility.
WARNING
!
The output breaker on this unit does not protect every output configuration. Power to the load
the output breaker in the output configuration.)
Self-Tests
4.8.1 Lamp Test
NOTE
This test involves putting the Liebert® GXT3-10000T220™ into bypass mode. The load is not
protected against any utility disturbances or interruptions while the UPS is in bypass mode.
1. With the Liebert GXT3-10000T220 connected to the utility, press the Menu button, select Control
and press OK.
2. Select Turn UPS On/Off and press OK.
3. The LCD will show Turn UPS to BYPASS.
4. Press OK to off the inverter to Bypass mode.
5. A single acoustic signal confirms the operation.
6. Select Turn UPS On/Off and press OK to place the UPS back in Normal Mode operation. The UPS
performs the test during Start-up.
4.8.2 Battery Test
NOTE
During the test an acoustic signal will be heard as though the device is operating in battery
mode.
1. Press the Menu button.
2. Select SETUP and press OK.
3. Select BATT TEST and press OK.
A single acoustic signal confirms the operation and the load will be supplied by the battery.
If the test is successful, the BATT LED will stop flashing and the UPS will return to Line mode. If the
UPS circuitry detects a battery malfunction, Liebert GXT3-10000T220 will display an alarm (see
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
5.0 MAINTENANCE
5.1
Test, Replacement and Disposal of Batteries
The Liebert® GXT3™ is designed to allow the user to replace the internal battery pack safely. Refer to
Table 7 for internal battery pack part numbers for Liebert GXT3 UPS and Liebert External Battery
Cabinets:
Table 7
Replacement battery pack
Replacement Internal Battery
Quantity
Required
Unit Type and Model #
Pack Model Number
Liebert UPS GXT3-10000T220
GXT3-240BATKIT
2
2
Liebert External Battery Cabinet
GXT3-240VBATTCE
GXT3-240BATKIT
Read all safety cautions before proceeding. Contact your local dealer or Emerson representative to
obtain the part number and pricing of the appropriate replacement battery pack.
Disposal of the UPS and batteries should be carried out by a certified disposal company—observe all
local regulations and laws. Lead-acid batteries are classified as harmful toxic waste and as such the
law demands that they be disposed of by an authorized recycling centre.
The typical battery lifecycle is 3 to 5 years at an ambient temperature of 25 C, but is also dependent
on the frequency and duration of utility failures.
ascertain the general condition of the batteries and ensure maximum run time.
5.2
5.3
Storage
For extended storage at ambient temperatures cooler than 25°C (77°F), the batteries should be
charged for 24 hours once every six months.
Connect the UPS to a utility outlet socket having a ground (earth) connection and ensure the
miniature circuit breaker is closed. If charging batteries with fixed utility connections, make
After 24 hours, disconnect the UPS from the utility supply.
Cleaning
The UPS may be cleaned by wiping it off with a dry cloth. Do not use liquids or solvents.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Communication
6.0 COMMUNICATION
6.1
Communication Interface Port
The Liebert® GXT3™ UPS has a terminal block on the rear of the UPS unit. Several signals are
provided on this port and are assigned as follows.
6.2
Dry Contact
Figure 12 Dry contact pin layout
1
2
3
4
(Low Battery Warning)
(Any Mode Shutdown)
(On- Battery Warning)
(Battery Mode Shutdown)
6.2.1 Any Mode Shutdown
The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier,
inverter and static switch so that there is no power to the loads.
Any Mode Shutdown can be operated locally or remotely:
• Local Any Mode Shutdown can be performed by shorting the pins in Set 3.
• Remote Any Mode Shutdown can be performed using a switch connected to the pins in Set 3 and
mounted at a remote location.
Activation of the Any Mode Shutdown will be logged as an event in the event history log.
NOTE
Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown.
The current limited source (+12VDC, 50mA) will be available from UPS.
The connection to UPS for remote connection will be via terminal block connector.
Any Mode Shutdown wiring must conform to all national, regional and local wiring codes and
laws.
WARNING
!
When the Auto-enable output option is selected and the UPS output is disabled using the pins
in Set 3, the Liebert GXT3-G’s output can turn On automatically and without warning if the
connection of the pins in Set 3 is changed.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Communication
6.2.2 Battery Mode Shutdown
Battery Mode Shutdown permits shutting down the UPS by turning off the rectifier, inverter and
static switch so that there is no power to the load when the UPS is On Battery. The auxiliary power
for the UPS will still be active.
Battery Mode Shutdown can be performed locally or remotely:
• Local Battery Mode shutdown can be performed by shorting the pins in Set 4.
• Remote Battery Mode Shutdown can be performed using a switch connected to the pins in Set 4
and mounted at remote location.
Activation of the Battery Mode Shutdown will be logged as an event in the event history log.
NOTE
Remote Power Off will be performed by NO contact.
The current limited source (+12VDC, 50mA) will be available from UPS.
The connection to the Liebert® GXT3™ for remote connection will be via terminal block
connector.
Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes
and laws.
This signal must last for 1.5 seconds or longer.
A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute
shutdown timer. This timer cannot be stopped once triggered. If the utility power returns
during this countdown, the Liebert GXT3 will still shut down and must remain shut down for
10 seconds. Whether the UPS turns back On when the power is restored depends on the
auto-restart setting.
6.2.3 On Battery
On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power
from the battery this dry contact will be closed.
6.2.4 Low Battery
Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power
from the battery and has reached the Low Battery Warning time selected in the configuration
program, this dry contact will be closed.
NOTE
The rated values for the dry contacts are:
• Rated Voltage: 30V (AC or DC)
• Rated Current: 300mA
®
6.3
Liebert IntelliSlot Communication Cards
The Liebert IntelliSlot port accepts three optional cards:
• Liebert IntelliSlot SNMP Card
• Liebert IntelliSlot Relay Card
• Liebert IntelliSlot 485 Card.
The Liebert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the
network.
The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications
and delivers support for built-in shutdown for AS/400 systems.
The Liebert IntelliSlot 485 Card is used to connect the UPS and computer system.
Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink®, the
UPS or any additional ancillary product for the Liebert GXT3. These instructions are available at
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Communication
6.3.1 Liebert® MultiLink®
Liebert MultiLink continually monitors the UPS and can shut down your computer or server in the
event of an extended power failure.
®
Liebert MultiLink can also be configured for use without the USB cable when the Liebert IntelliSlot
SNMP/Web card is installed in the UPS. Additionally, Liebert MultiLink can be configured to
coordinate shutdown across the network with other computers running Liebert MultiLink when you
purchase a Liebert MultiLink License Kit. For more information about the Liebert IntelliSlot
contact your local dealer or Emerson representative.
Several option cards are available for use in the Liebert IntelliSlot port of the Liebert GXT3™. The
Liebert IntelliSlot SNMP/Web Card provides SNMP and Web-based monitoring and control of the
UPS across the network.
The Liebert IntelliSlot MultiPort 4 Card allows installing Liebert MultiLink software on four
computers and coordinate shutdown in the event of a power failure.
The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom wired applications
and delivers support for built-in shutdown for AS/400 systems.
CAUTION
!
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables
should be shielded and run separate from all other power cables, where applicable.
6.4
Remote Emergency Power Off
The UPS is equipped with a Remote Emergency Power Off (REPO) connector.
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS
input feeder breaker to remove all sources of power to the UPS and connected equipment to comply
with national and local wiring codes and regulations.
REPO switch connection diagram
UPS ships with REPO jumper
installed allowing the UPS
to operate
Opening the REPO connection will disable the UPS.
Manual restart using the front panel is required after
the REPO connection is closed again.
1
2
1
2
Normally closed switch system
(fail-safe)
CAUTION
!
To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should
be shielded and run separately from power cables.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
7.0 TROUBLESHOOTING
If any technical problems should occur, check the following before contacting Liebert® technical
support:
• Is the utility voltage present at the UPS input?
• Has the input fuse blown or have the circuit breakers tripped?
• Has the UPS startup procedure been followed correctly?
When contacting Liebert technical support, have the following information available:
• Device model number
• Serial number (from the nameplate)
• Exact description of the problem (what loads are being operated, does the problem occur regularly
or sporadically, etc.)
For descriptions of the indicators mentioned in the following table, see 4.2.1 - Controls and
Table 8
Troubleshooting guide
Problem
Possible Cause
Solution
Switch on utility breaker
Utility mains switched off
Have utility mains inspected by a qualified
technician
No display
No alarm
No mains voltage present
(UPS switched Off)
Replace with fuse of same type or switch on circuit
breaker. If the problem persists, contact technical
support.
Input fuse blown or input
circuit breaker tripped
UPS on LED does not light up,
alarm beeps sound at intervals
No utility mains voltage
present
Have utility mains inspected by a qualified
technician
UPS on LED does not illuminate
when utility mains voltage present,
acoustic alarm active at intervals
Replace with fuse of same type or switch on circuit
breaker. If the problem persists, contact technical
support
Input fuse defective or input
circuit breaker tripped
UPS error
Contact technical support
FAULT LED illuminates, alarm
sounding constantly
Overheating
Decrease ambient temperature
The battery breaker is open,
in the OFF position
Move the battery breaker to the ON position
Batteries are not fully charged and test backup time. If the problem persists,
contact technical support.
Battery Run time less than specified
Batteries are defective
Contact technical support
Charging device is defective
Overload at UPS output
Contact technical support
OVERLOAD message displayed
Reduce load to the permissible value
Check whether the correct cable has been used
(standard modem/null modem cables are not
permissible)
Wrong serial connection
cable
No communication between UPS
and PC
Interface on the PC is being
used by another process or is
defective
Check whether other software/service is accessing
the interface on the PC; try selecting a different
serial interface
Interference on the data cable Lay cable differently/Reinstall cabling
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
8.0 SPECIFICATIONS
Table 9
Model Rating, VA (W)
Dimensions, in. (mm)
Unit, W x D x H
Liebert® GXT3™ specifications
10,000 (9000)
31.5 x 11.81 x 26.57 (800 x 300 x 675)
41.8 x 16.7 x 34 (1062 x 426 x 866)
Shipping, W x D x H
Weight, lb (kg)
Unit
308 (140)
428 (194)
Shipping
Input AC Parameters
Nominal Operating Frequency
50 or 60Hz (Factory Default = 60)
120/208 at 120 degrees
120 / 208 / 220 / 240
Factory Default VAC
User-Configurable VAC
Operating Voltage Range
Without Battery Operation
100 - 185 ±5VAC
280
Maximum Allowable VAC
Input Frequency
Without Battery Operation
40 - 70Hz
Input Power Connection
BYP, L1, L2, GND
Output AC Parameters
Factory Default, VAC
208
Hardwire Terminal Block
Output Connections
Output: (GEC, X1, X2, X3, X4, GND) Bypass: L1, L2, GND
Frequency
Waveform
50Hz or 60Hz, Nominal
Sinewave
>200% for 5 cycles; 151 - 200% for 1 second; 131-150% 10 seconds;
105 - 130% 1 minute
Main Mode Overload
Battery Parameters
Type
Quantity x V
Valve-regulated, non-spillable, lead acid
20 x 12V
Battery Mfr. / Part #
CSB HR1234R or Panasonic UP-RW1245
See Table 11
Backup Time
Recharge Time (Internal Batteries)
Bypass Protection Limits
Maximum Bypass Current
Disable Bypass Operation
Re-Enable Bypass Operation
Disable Bypass Operation
Environmental
3 hr. to 90% capacity after full discharge into 100% load
50A
If input voltage exceeds ±10% of the nominal voltage
If input voltage returns to within ±8% of nominal output voltage
When the input frequency prevents synchronous operation
32 to 86 (0 to 30) with 0.9 pf
86 to 104 (30 to 40) with 0.8pf
Operating Temperature, °F (°C)
Storage Temperature, °F (°C)
Transportation, °F (°C)
Relative Humidity
Operating Elevation
Audible Noise
5 to 122 (-15 to 50)
0-95% non-condensing
Up to 3281 ft (1000m) at 80°F (27°C) without derating
<55 dBA at 3.3ft (1m) from rear; <50 dBA at 3.3ft (1m) from front or sides
Agency
Safety
UL 1778, c-UL
FCC Part 15, Subpart B, Class A
IEC/EN 61000-4-5, ANSI C62.41 (for North America)
ISTA Procedure 1B
RFI/EMI
Surge Immunity
Transportation
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
Table 10 Battery cabinet specifications
GXT3-240TBATTCE
Model Number
Dimensions, W x D x H, in. (mm)
Unit
31.5 x 11.81 x 26.57 (800 x 300 x 675)
41.8 x 16.7 x 34 (1062 x 426 x 866)
Shipping
Weight, lb (kg)
Unit
Shipping
243 (110)
309 (140)
Internal Battery Parameters
Type
Valve-regulated, non-spillable, lead acid
2 x 20 x 12V
Quantity x V
Battery Manufacturer, Part #
CSB HR1234R or Panasonic UP-RW1245
Temperature Limits, Batteries Only,
°F (°C)
32 to 104 (0 to 40)
Backup Time
Environmental
See Table 11
Operating Temp, °F (°C)
Storage Temp
32 to 80 (0 to 27)
5 to 104 (-15 to 40)
5 to 122 (-15 to 50)
0-95% non-condensing
Transportation Temp, °F (°C)
Relative Humidity
Operating Elevation
Agency
Up to 3281 ft (1000m) at 80°F (27°C) without derating
Safety
UL 1778, c-UL Listed
ISTA Procedure 1B
Transportation
™
Table 11
Typical battery run times for the Liebert® GXT3-10000T230
Load %
Number of Batteries,
Battery Cabinets
10%
20%
30%
40%
50%
60%
70%
80%
90% 100%
Internal Battery
81
39
22
15
11
8
6
5
4
3
Internal Battery + 1
External Battery Cabinet
190
316
127
162
81
60
46
82
39
69
32
52
26
48
22
18
Internal Battery + 2
External Battery Cabinets
136
106
44
39
Approximate discharge times are at 77°F (25°C) with a 100% resistive load.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Warranty Registration
9.0 PRODUCT WARRANTY REGISTRATION
To register for warranty protection:
• Visit the Quick Links section of Liebert’s Web site at:
• Click on Product Warranty Registration and fill in the form.
If you have any questions, please contact us at:
• US: 800-222-5877
• Outside the US: 614-841-6755
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Ensuring The High Availability
Of Mission-Critical Data And Applications.
Emerson Network Power, a business of Emerson (NYSE:EMR),
is the global leader in enabling Business-Critical Continuity™
from grid to chip for telecommunication networks, data centers,
health care and industrial facilities. Emerson Network Power
provides innovative solutions and expertise in areas including
AC and DC power and precision cooling systems, embedded
computing and power, integrated racks and enclosures,
power switching and controls, infrastructure management,
and connectivity. All solutions are supported globally by local
Emerson Network Power service technicians. Liebert AC power,
precision cooling and monitoring products and services
from Emerson Network Power deliver Efficiency Without
Compromise™ by helping customers optimize their data center
infrastructure to reduce costs and deliver high availability.
Technical Support / Service
Web Site
Monitoring
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
© 2010 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change
without notice.
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks
Fax: +63 2 730 9572
or registered trademarks of their respective owners.
SL-23187_REV1_04-12
Emerson Network Power.
The global leader in enabling Business-Critical Continuity™
EmersonNetworkPower.com
AC Power
Connectivity
DC Power
Embedded Computing
Outside Plant
Racks & Integrated Cabinets
Embedded Power
Power Switching & Controls
Precision Cooling
Services
Infrastructure Management & Monitoring
Surge Protection
Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies.
©2010 Emerson Electric Co.
Download from Www.Somanuals.com. All Manuals Search And Download.
|