Liebert Power Supply GXT3 10000T220 User Manual

AC Power  
For Business-Critical Continuity™  
Liebert® GXT3-10000T220™  
User Manual, 10kVA, 50/60 Hz, 120/208/220V  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.3  
Liebert IntelliSlot® Communication Cards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
6.3.1 Liebert MultiLink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
®
®
FIGURES  
Figure 1  
Figure 2  
®
Liebert GXT3-10000T220 front and rear views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
TABLES  
Table 9  
Liebert® GXT3specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
Table 11 Typical battery run times for the Liebert® GXT3-10000T230 . . . . . . . . . . . . . . . . . . . . . . . . . . . 26  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE INSTRUCTIONS  
This manual contains important safety instructions. Read all safety and operating instructions before  
operating the uninterruptible power system (UPS). Adhere to all warnings on the unit and in this  
manual. Follow all operating and user instructions. This equipment must be operated only by  
individuals who are properly trained and qualified.  
This product is designed for commercial/industrial use only. It is not intended for use with life support  
and other designated “critical” devices. Maximum load must not exceed that shown on the UPS rating  
label. The UPS is designed for data processing equipment. If uncertain, consult your dealer or local  
Emerson Network Power representative.  
This UPS is designed for use on a properly earthed (grounded), 208 or 220 VAC, 50Hz or 60Hz supply,  
for installation by qualified personnel. A qualified electrician must review and approve customer-  
supplied wiring, circuit breakers and intended loads and verify correct input, output and earth  
connections to ensure compliance with technical standards and local electrical codes of practice.  
Installation instructions and warning notices only for use by properly trained and qualified personnel  
are located after the UPS operator instructions in this manual.  
Install the UPS in a clean environment, free from moisture, flammable liquids, gases and corrosive  
substances.  
This UPS contains no user-serviceable parts except the internal battery pack. The UPS On/Off  
push buttons do not electrically isolate internal parts. Under no circumstances attempt to gain access  
internally due to the risk of electric shock or burn.  
Do not continue to use the UPS if the front panel indications are not in accordance with these  
operating instructions or the UPS performance alters in use. Refer all faults to your dealer.  
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and  
the required precautions. Keep unauthorized personnel away from the batteries. Proper disposal of  
batteries is required. Refer to your local laws and regulations for disposal requirements.  
Never block or insert any object into the ventilation holes or other openings.  
DO NOT CONNECT equipment that could overload the UPS or demand DC current from the UPS,  
for example: electric drills, vacuum cleaners, laser printers, hair dryers or any appliance using  
halfwave rectification.  
WARNING  
precautions should be observed before replacing the battery pack:  
!
The battery can present a risk of electrical shock and high short circuit current. The following  
• Wear rubber gloves and boots  
• Remove rings, watches and other metal objects.  
• Use tools with insulated handles.  
• Do not lay tools or other metal objects on the batteries.  
• If the battery kit is damaged in any way or shows signs of leakage, contact your local Emer-  
son representative immediately.  
• Do not dispose of batteries in a fire. The batteries may explode.  
• Handle, transport and recycle batteries in accordance with local regulations.  
• Even when all switches and interrupters are open, hazardous voltages are present within  
the UPS; any operation that requires protective panels to be opened or removed may be car-  
ried out by Emerson-authorized technical personnel only.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
WARNING  
!
!
Although the Liebert® GXT3has been designed and manufactured to ensure safety,  
improper use can result in electrical shock or fire. To ensure safety, observe the following  
precautions:  
• Turn Off and isolate the Liebert GXT3 before cleaning it. Use only a soft cloth; never use  
liquid or aerosol cleaners.  
• Never block or insert any objects into the ventilation holes or other openings of the UPS.  
• Do not place the Liebert GXT3 power cord where it might be damaged.  
CAUTION  
®
• When installed in EU countries, the Liebert GXT3-10000T220is not intended to operate  
with isolated neutral (IT systems). Neutral connector must be present and connected to the  
UPS.  
• Even with all buttons OFF (see 4.2 - Control Panel) the device (UPS) is not isolated from  
the utility. To isolate completely from the utility, the power cables must be disconnected.  
• In case of interruption of the utility voltage, the integrated battery maintains the power  
supply to the user equipment.  
• Lay all cables so that nobody can stand on them or trip over them. When connecting the  
UPS to the power supply, follow the instructions in 3.0 - Installation.  
• In emergencies (e.g., damaged case, controls or power cables, penetration of liquids or for-  
eign matter), switch off the device and contact the appropriate customer service representa-  
tive.  
• Do not connect equipment that will overload the UPS (e.g., laser printers or vacuum clean-  
ers) or demand DC-current (e.g., half-wave rectifiers).  
• When cleaning the unit, follow the instructions in 5.0 - Maintenance.  
• The sum of the leakage currents (protective conductor current) of the UPS and the con-  
nected devices exceeds 3.5 mA for all ratings of the UPS. Ground (earth) connection is  
essential before connecting supply.  
• Data transmission lines should not be connected or disconnected during a thunderstorm.  
• Emergency Power Off (EPO) input is on the rear of the unit (see 6.4 - Remote Emergency  
Power Off and 3.6 - Terminal Blocks for UPS). When this connection is open, the logic  
circuit will immediately shut down the UPS output.  
• When installed in EU countries, an Emergency Switching Device (E.S.D.) must be fitted  
downstream of the UPS for the wiring installation safety to comply with the European Har-  
monized Document HD384-4-46 S1.  
• Maintenance bypass breaker is for the use of service personnel only. The breaker is on the  
rear of the unit. To operate the breaker, the captive screw must be loosened and the guard  
must be lifted out of position.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
Leakage Current  
WARNING  
!
Connect the ground (earth) safety conductor before connecting any other cables.  
ELECTROMAGNETIC COMPATIBILITY—The Liebert® GXT3complies with the limits for a  
Class A Digital Device, Pursuant to Part 15 of FCC rules. Operation is subject to the following  
conditions:  
• This device may not cause harmful interference  
• This device must accept any interference received, including interference that may cause  
undesired operation. Operating this device in a residential area is likely to cause harmful  
interference that users must correct at their own expense.  
The Liebert GXT3 series complies with the requirements of EMC Directive 2004/108/EC and the  
published technical standards. Continued compliance requires installation in accordance with these  
instructions and use of accessories approved by Emerson.  
NOTICE  
Operating the Liebert GXT3 in residential areas may cause radio interference that the user  
must to correct at his own expense.  
Information for the Protection of the Environment  
UPS SERVICING—This UPS makes use of components dangerous for the environment (electronic  
cards, electronic components). The components removed must be taken to specialized collection and  
disposal centers.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction and System Description  
1.0 INTRODUCTION AND SYSTEM DESCRIPTION  
Congratulations on your choice of the Liebert® GXT3-10000T220 UPS. It provides conditioned power  
to microcomputers and other sensitive electronic equipment.  
When generated, AC power is clean and stable. However, during transmission and distribution it is  
subject to voltage sags, spikes and complete power failure that may interrupt computer operations,  
cause data loss and damage equipment. The Liebert GXT3-10000T220 protects equipment from these  
disturbances.  
The Liebert GXT3-10000T220 is an on-line UPS. An on-line UPS continuously conditions and  
regulates its output voltage whether utility power is present or not. It supplies connected equipment  
with clean sinewave power. Sensitive electronic equipment operates best from sinewave power.  
The liquid crystal display is used for controlling operation of the UPS, as well as monitoring its  
status, condition, alarm status and history. For ease of use, the Liebert GXT3-10000T220 features a  
light-emitting diode (LED) display to indicate operational status. It also provides self-diagnostic tests,  
a combination On/Alarm Silence/Battery Test button, a Standby button, user configurable program  
and two levels of alarms when the unit is operating on battery.  
The Liebert GXT3-10000T220 has an interface port for communication between the UPS and a  
network server or other computer system. This port provides detailed operating information including  
voltages, currents and alarm status to the host system when used in conjunction with Liebert’s  
®
MultiLink software. Liebert MultiLink software may also control UPS operation remotely.  
CAUTION  
!
This UPS may be operated only by properly trained and qualified personnel.  
Figure 1 Liebert GXT3-10000T220 control panel  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Introduction and System Description  
1.1  
Device Overview  
The following table provides an overview of the various versions of the device:  
Table 1 Overview of UPS devices and batteries  
Type Model #  
UPS with Integrated Battery Liebert GXT3-10000T220  
Nominal power  
10000VA/90000W  
®
Battery Cabinet  
Liebert GXT3-240TBATTCE  
®
Figure 2 Liebert GXT3-10000T220 front and rear views  
Control Panel  
Liquid Crystal  
Display  
Push Button  
Controls  
Ventilation  
Louvers  
External  
Battery  
Connector  
Maintenance  
Bypass Breaker  
(cover removed  
for clarity)  
®
Liebert IntelliSlot  
Communication  
Card slot  
Input  
Circuit  
Breaker  
USB Port  
Dry Contacts  
Bypass  
Circuit  
Breaker  
REPO  
Output  
Circuit  
Breaker  
Hardwire Input  
and Output  
Connectors  
(Protective  
Cover Shown)  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Unpacking the UPS and Site Preparation  
2.0 UNPACKING THE UPS AND SITE PREPARATION  
2.1  
Inspection  
Upon receiving your Liebert® GXT3-10000T220, examine the packaging for any signs of  
mishandling or damage. While removing shipping materials, inspect the UPS for damage. If any  
damage is noted, notify your local Liebert representative and your carrier.  
2.2  
Required Setup Equipment  
The following tools are required to set up your Liebert GXT3-10000T220:  
• pallet jack  
• utility knife or scissors  
• screwdrivers—Phillips and straight blade  
2.3  
Unpacking  
Exercise care when removing the packaging to avoid damaging the UPS. Check all packaging to  
ensure that no items are discarded. Remove the packaging following the sequence in Figure 3.  
WARNING  
pallet, use at least two persons.  
!
The UPS is heavy and will roll when on an incline. When removing the unit from its shipping  
1. Using a pallet jack, move the Liebert GXT3-10000T220 near its installation site.  
2. Unlock all the snaps securing the shipping case to the shipping pallet.  
3. Lift the shipping case off the UPS.  
4. Remove the EPE packing cushions from around the Liebert GXT3-10000T220.  
5. Remove the ramp from the front and slip into the slot on the front of the shipping pallet.  
6. Roll the UPS off the shipping pallet.  
Figure 3 Unpacking  
Packing Cushion  
(EPE)  
Plywood  
Case  
GXT3 T220  
UPS  
Ramp in slot  
on shipping pallet  
Ramp  
Unlock  
Storage  
If the UPS will be stored, it must be placed indoors in a clean, dry area. Protect all the equipment,  
including its batteries, from extreme temperatures, high humidity, spills and other damaging  
conditions. Refer to Table 9 for permissible environmental conditions for storage.  
Handling  
The equipment must be kept upright at all times and handled with care. It may be damaged if  
dropped or subjected to severe impact.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Unpacking the UPS and Site Preparation  
2.4  
Environmental Conditions  
Install the Liebert® GXT3indoors in a controlled environment where it cannot be accidentally  
turned off. Place it on a level, even surface in an area with unrestricted airflow around the unit. The  
installation location must be free of water, flammable liquids, gases, corrosives and other conductive  
contaminants. Maintain a minimum clearance of 100mm (4 inches) in the front and rear of the UPS.  
Maintain an ambient temperature range of 0 to 40°C (32 -104°F).  
See 8.0 - Specifications for acceptable environmental conditions.  
NOTE  
UPS operation in sustained temperatures outside the range of 15-25°C (59°-77°F) will reduce  
battery life.  
2.5  
Access to Area  
The area where the Liebert GXT3-10000T220 is to be placed must have sufficient space for  
installation procedures and for routine maintenance. The UPS is narrow enough to pass through  
standard doorways.  
2.6  
2.7  
Floor Loading  
Ensure that the floor where the UPS will be installed will support the unit’s weight (see Table 9 for  
the unit’s weight).  
Inventory List  
• CD containing:  
• Liebert MultiLink® shutdown software  
• Configuration Software  
• User Manual  
• Terminal Block Communication terminals  
• Floor-mount brackets  
• Warnings, safety instructions booklet and WEEE recycling sheet (ISO 14001 compliance)  
• USB cable  
• Hardwire terminal block cover plate and mounting screws  
• Single input bypass jumper  
• Battery cabinets contain one DC power cable  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Installation  
3.0 INSTALLATION  
3.1 Electrical preparations  
Before beginning installation, the input source must be isolated and locked out to prevent connection  
during installation. The input circuit breaker on the rear of the UPS must be in the Off position.  
WARNING  
applicable safety standards.  
!
Installation may be carried out only by qualified technicians and in conformity with the  
WARNING  
!
Electric shock hazard: Even when the unit is disconnected from the utility, hazardous voltage  
may still be supplied by the battery. Both poles must be disconnected before any work is  
performed inside the UPS.  
WARNING  
immediately upon application of AC input.  
!
If the Maintenance Bypass Breaker is in the Bypass position, output power is available  
3.2  
Suggested Cable Sizes  
Table 2  
Connection data *  
®
Units  
Liebert GXT3-10000T220™  
Description  
2
Connector size  
AWG (mm )  
Arms  
6 (10)  
56*  
Max input current  
2
Input cable size (and neutral)  
Max output current  
AWG (mm )  
6 (10)  
56*  
Arms  
2
Output cable size (and neutral) AWG (mm )  
6 (10)  
6 (10)  
10 (113)  
2
Ground (Earth) Cable Size  
AWG (mm )  
Terminal Torque  
lb-in (Ncm)  
*
Cable must be 90°C copper wire  
NOTE  
To reduce electromagnetic interference:  
• Enclose input and output cables to the UPS in separate metal conduits.  
• Use shielded communication cables and route separately from power cables  
3.3  
External Protection and Isolating Devices  
An external 70A disconnect switch must be installed upstream of the UPS to protect power cabling  
and provide a means of isolating the UPS from utility.  
WARNING  
system as the UPS, even when these are located at a distance from the area.  
!
The following label must be displayed on all switching devices installed in the same electrical  
ENSURE THAT THE UNINTERRUPTIBLE POWER SYSTEM IS ISOLATED BEFORE  
WORKING ON THIS CIRCUIT  
CAUTION  
!
A disconnect switch must be provided by others for AC output circuit. To reduce the risk of  
fire, connect only to a circuit provided with branch circuit overcurrent protection for 70A  
rating in accordance with the National Electric Code, ANSI/NFPA 70.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Installation  
3.4  
External Electrical Connections  
The external electrical connections may be accessed by removing the protective panel on the rear of  
the UPS (see Figure 2) (panel ships loose from factory). Select a conduit knockout appropriate for  
your cabling, based on local electrical codes.  
WARNING  
!
Before removing electric protective panel, ensure that the UPS is isolated.  
Figure 4 Side view  
Rear Panel  
Cable Entry Cover  
NOTE  
Once installation has been completed, adjust leveling feet to prevent the UPS from moving.  
3.5  
3.6  
Connecting Utility and Load  
Connect the utility supply to the input terminals of the UPS. If the Liebert GXT3-10000T220is  
®
supplied by single-phase utility, connect the live phase to input L1.  
Terminal Blocks for UPS  
CAUTION  
!
Power is connected through the input breaker, even when the UPS is in bypass mode.  
Opening the input breaker when in bypass mode will disconnect output power to the  
connected load.  
Figure 5 Single source input supply—input and output connections  
UPS Input ~  
Bypass Input ~  
L1 L2  
Output ~  
X2 X3  
BYP L1  
L2  
GET X1  
X4  
120  
208  
220  
Single Feed  
Jumper  
120  
0
240  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Installation  
Figure 6 Dual source input supply—input and output connections  
UPS Input ~  
Bypass Input ~  
L1 L2  
Output ~  
X2 X3  
BYP L1  
L2  
GET X1  
X4  
120  
208  
220  
UPS Feed  
Bypass Feed  
120  
0
240  
Figure 7 Hardwire terminals  
Jumper  
removed  
for clarity  
3.6.1 Input and Output Connection Requirements  
• Any 120V loads must be distributed evenly between X1-X2, X1-X4 and X4-X2. Do not connect  
loads between X3-X2 or between X3-X4—these are not standard voltages.  
• The single-phase isolation output transformer is a separately derived source. The output Neutral  
(X2) is bonded to Ground within the UPS cabinet. No other bonding wire is needed.  
• Install a Grounding Electrode Terminal (GET) to the nearest grounding electrode in the building  
grounding electrode system. If the grounding electrode conductor must be protected, non-metallic  
conduit is recommended. If metal conduit must be used, bond both ends of the conduit to the  
grounding electrode conductor. Conduit is not an acceptable grounding electrode conductor.  
• The utility may be derived from a single-phase or three-phase source. The line-to-ground voltages  
are dependent on the grounding of the utility and do not affect the output voltages. Do not use a  
floating AC source.  
• With dual input source configuration, both sources are tied together within the UPS cabinet. Two  
additional ground screw terminals are supplied for use as needed.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installation  
3.7  
Connecting Power Cables  
1. Open the UPS input breaker.  
2. Open the UPS bypass breaker.  
3. Set the maintenance breaker to the Bypass position.  
4. Remove the electrical connection protective panel, if installed, from the rear UPS panel.  
5. Connect loads to the output terminals as illustrated in Figure 7.  
6. Connect the utility to the corresponding input terminals (see Figure 7).  
• If the bypass input is to be supplied separately, connect the bypass source to the corresponding  
bypass terminals.  
• If the UPS is supplied from a single feed, connect the factory-supplied jumper between terminal  
UPS Input-BYP and Bypass Input-L1.  
3.8  
External Battery Cabinets  
®
Up to four external battery cabinets may be connected to the Liebert GXT3-10000T220. A cable to  
connect the battery cabinet and the Liebert GXT3-10000T220 is supplied with each battery cabinet.  
Open the breaker before making battery cable connections.  
Plug one end of this cable into the UPS and the other end into the battery cabinet—slotted fittings on  
each end ensure that the connection is properly made. If your UPS has an integrated battery, a  
compensating current may occur during connection. Once both ends of the cable have been connected,  
the circuit breaker on the external battery cabinet must be closed.  
Figure 8 Liebert GXT3-10000T220 with External Battery Cabinet  
Battery Breaker  
(Liebert GXT3-240TVBATTCE)  
External Battery Cabinet  
Connector for  
Liebert GXT3-240TVBATTCE  
additional cabinet  
External  
Battery  
Cabinet  
Connector  
UPS  
Rear View  
External  
Battery  
Cabinet  
Rear View  
CAUTION  
!
Battery maintenance must be performed only by authorized personnel who are properly  
trained and qualified.  
External battery cabinets are hot-swappable; they can be replaced during normal UPS  
operation.  
DO NOT connect or disconnect batteries when the UPS is in Battery Mode.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Operation  
4.0 OPERATION  
4.1  
Block Diagram  
®
The Liebert GXT3-10000T220consists of the following main components:  
• 2 utility inputs with separate breakers—utility and bypass  
• rectifier/booster, inverter and charger  
• electronic bypass  
• 2-position Maintenance Bypass Breaker—UPS and BYPASS  
• integrated battery  
Figure 9 System block diagram  
Input  
Output  
Dynamic  
Bypass  
V bp  
X1  
X3  
Rectifier/  
PFC  
DC-to-DC  
Converter  
TVSS &  
EMI/RFI  
Filters  
Isolation  
Transformer  
L1  
N
L1  
N
Inverter  
X4  
X2  
Battery  
Charger  
Battery  
G
G
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Operation  
4.2  
Control Panel  
The Control Panel’s LCD and buttons are used to initiate various UPS operations, tests and  
commands and to view the status of the UPS.  
By pressing the Menu Up or Menu Down and Enter keys , it is possible to scroll through the  
various menus. For details, see 4.2.1 - Controls and Messages and Figure 11.  
Figure 10 Control Panel  
Fault  
LED  
Battery UPS On  
LED LED  
Bypass  
LED  
LCD  
Escape key  
Enter key  
Menu Up key  
Menu Down key  
4.2.1 Controls and Messages  
Lighted LEDs  
• UPS ON—UPS is in normal, online operation  
• BYPASS—Load is supplied by the utility via automatic bypass  
• BATTERY—Load is supported by the battery  
• FAULT—A problem has developed within the UPS  
Flashing LED  
When the BYPASS LED is flashing, the utility is out of tolerance.  
NOTICE  
Risk of loss of power to connected load. Can cause equipment damage.  
Never switch the UPS Off or switch from Online to Bypass in this status, because the load  
would no longer be supplied.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Operation  
Figure 11 Menu tree  
Turn UPS  
On/Off  
Battery  
Test  
Alarm  
Control  
Control  
Status  
Battery  
Test  
Battery  
Test  
Contrast  
Set  
Battery  
Test  
Audible  
Alarm  
Output  
Voltage  
Start  
Window  
Parallel  
Menu  
Battery  
Pack  
System  
Status  
Battery  
Test  
Main  
Interval  
Setup  
DC Start  
UPS  
Address  
Parallel  
Model  
Tag  
Number  
Language  
Event Log  
Clear  
Log  
Types  
IP  
About  
Version  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
Table 3  
Displayed text—system block and main menu  
Item # and Name  
Description  
Measure  
value  
Unit  
Output Volt  
Output Freq  
V
0.1Hz  
Output  
Current  
A
Output Watt  
Output VA  
W
VA  
Output Load  
Input Volt  
%
Status Menu  
V
L2 Input Volt  
L3 Input Volt  
Input Freq  
N/A  
N/A  
0.1Hz  
Back Voltage  
Batt Capacity  
Backup Time  
Run Time  
V
%
min:sec  
day:hr:min:sec  
Tag Number  
Setting item  
Setting (level 1)  
Disable/Enable  
208/220/230/240V  
Audible alarm  
Output voltage  
Battery pack  
Battery Test interval  
DC start  
1
1-3  
Setup Menu  
Disable/Enable  
00000-99999  
Tag Number  
Language  
English/French/Spanish/German/Italian/ Russian  
*
Event and time  
Logging  
Menu  
Clear event log  
* : Max 4 fault event record  
®
Type of UPS  
Internet IP  
Liebert GXT 10KVA  
Liebert GXT3-10000T220 Capacity 10KVA  
Firmware  
Version  
Software  
version  
Display Firmware  
version  
DSP Firmware version  
10kVA UPS Self testing  
please wait  
Start Window  
Main Menu  
Wait about 6 sec  
Control  
Status  
Setup  
Log  
About  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
Table 3  
Displayed text—system block and main menu (continued)  
Item # and Name  
Description  
Turn UPS ON/OFF  
Turn UPS to ONLINE  
Turn UPS to BYPASS  
Turn UPS to shutdown  
Turn UPS to no output  
Alarm ON  
Alarm control  
Batt Test  
Control  
Menu  
Alarm OFF  
Batt Test  
Cancel Battery Test  
Battery Test Report  
Darker  
Contrast  
Lighter  
Test in  
progress  
Test to Low-Battery  
Test OK!  
Test fail  
Cancel Battery test  
Battery Test report  
Battery  
Test Report  
Test stop by  
user  
Test  
unknown  
1. For setup parameters regarding battery pack quantity, refer to 4.2.2 - Battery Setup Parameters  
4.2.2 Battery Setup Parameters  
Table 4  
Battery setup parameters  
Internal Battery Quantity External Quantity 12V Battery  
Parameter (X = Integrated)  
Battery Cabinets  
Blocks in Sum  
1
2
3
X
X
X
1
20  
60  
2
100  
4.2.3 Warning Indicators  
If a warning indication appears, the UPS continues to operate. The warning message alternates with  
UPS mode once a second.  
The various possible warning indicators are listed in the following table:  
Table 5  
Warning indicators  
Warning  
Cause  
Corrective steps  
1
2
4
Batt undervolt.  
Utility failure  
Over temp. 65  
N/A  
N/A  
Reduce load  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Operation  
4.2.4 Fault Indicators  
If a fault occurs, the UPS automatically switches to BYPASS mode, ONLY in case of a battery  
disconnect fault will the original operating mode be maintained. The fault message alternates with  
UPS mode once a second, the red Fault LED illuminates on the control panel and the buzzer sounds  
continuously. If a fault occurs, proceed as follows:  
Buzzer alarm operation—The buzzer alarm can be switched On or Off.  
Clear fault—Present fault condition can be reset if fault condition is cleared, either automatically or  
by the operator/technician.  
Fault information—A maximum of 4 fault events may be displayed in this window. All fault  
displays include: the nature of the fault event, and the time it occurred; the time is relative to the  
UPS operating time.  
Display faults—The various possible fault indicators are listed in the following table.  
Table 6  
Fault  
1.  
Fault indicators  
Cause  
Corrective steps  
Call customer service  
Call customer service  
Reduce load  
DC BUS fault  
Inverter fault  
2.  
3.  
Overtemperature  
Batt over volt.  
4.  
Call customer service  
5.  
Batt. mode overload Reduce load  
6.  
Output overload  
Output short  
Reduce load  
7.  
Call customer service  
Call customer service  
Check battery connector  
Call customer service  
NA  
8.  
Fan lock fault  
Batt. Disconnect  
Charger failure  
ESD activated  
Parallel fault  
9.  
10.  
11.  
12.  
13.  
14.  
Call customer service  
Call customer service  
Call customer service  
Internal fault  
Output failure  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operation  
4.3  
Initial UPS Startup Procedure  
1. Inspect all power connections to ensure they are correct and secure.  
2. Open external circuit breakers/fused disconnects to the connected loads.  
3. Close all upstream circuit breakers and fused disconnects.  
4. Use a voltmeter to verify proper input voltage is present on the UPS and Bypass input terminals.  
See Table 9 for the range.  
5. Close the input breakers on the rear panel of the UPS (UPS input and Bypass input).  
6. Turn the Maintenance Bypass Breaker to the Bypass position (remove the cover plate if  
attached).  
7. Use a voltmeter to verify that the proper output voltage is present on the UPS output terminals.  
See Table 9 for the range.  
8. Turn the Maintenance Bypass Breaker to the Off position and reinstall the cover plate..  
NOTE  
The maintenance bypass breaker cover must be installed behind the captive screw and the  
screw must be tightened for the UPS to operate on inverter mode.  
9. Use a voltmeter to verify the output voltage is NOT present on UPS output terminals.  
10. Use the LCD display and control buttons to start the UPS, refer to 4.2.1 - Controls and  
11. Use a voltmeter to verify proper output voltage is present on UPS output terminals. See Table 9  
for range.  
CAUTION  
!
Before reinstalling the hardwire terminal protective panel, follow the shutdown procedure in  
12. Open all upstream circuit breakers and fused disconnects.  
13. Reinstall the hardwire terminal protective panel.  
4.4  
UPS Shutdown Procedure  
NOTE  
Carrying out this procedure will interrupt the supply to the load.  
1. Press the Menu button, select Control and press the Enter key  
.
2. Select Turn UPS On/Off and press the Enter key  
.
The LCD displays Turn UPS to BYPASS.  
3. Press the Enter key  
to switch off the inverter.  
4. Open any external circuit breakers/fused disconnects connecting the load (if present).  
5. Switch both Input circuit breakers to the Off position.  
6. Ensure all circuit breakers/fused disconnects upstream of the UPS are open.  
7. Ensure that all LEDs on the control panel are extinguished.  
The UPS is now completely shut down.  
4.5  
Maintenance Bypass Procedure  
1. Press the Menu button, select Control and press the Enter key  
2. Select Turn UPS On/Off and press the Enter key  
The LCD displays Turn UPS to BYPASS. The UPS is now on Internal Bypass Mode.  
3. Press the Enter key to switch off the inverter (see Figure 10).  
.
.
4. Remove the safety cover from the Maintenance Bypass Breaker and turn UPS to BYPASS.  
NOTE  
At this point the load is no longer protected against interruptions and disturbances on the  
utility supply.  
The UPS is now in Maintenance Bypass Mode. The Bypass LED on the front panel is illuminated  
(amber) and the load is supplied directly from the utility.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Operation  
4.6  
Return from Maintenance Bypass  
1. Ensure all switches and circuit breakers upstream of the UPS are closed.  
2. Ensure that both input circuit breakers are in the On position.  
3. Turn the Maintenance breaker from BYPASS to UPS and replace the cover.  
The load now is supplied via electronic bypass.  
4. Press the Menu button, select Control and press the Enter key  
.
5. Select Turn UPS On/Off and press the Enter key  
.
The LCD displays Turn UPS to ONLINE.  
6. Press the Enter key  
to switch on the inverter.  
The UPS is now in online operation.  
4.7  
4.8  
Maintenance Breaker, Off Position  
• Move the breaker to the Off position to transfer the load from the UPS to utility.  
WARNING  
!
The output breaker on this unit does not protect every output configuration. Power to the load  
could be supplied immediately when the output is enabled. (Figure 9 illustrates the location of  
the output breaker in the output configuration.)  
Self-Tests  
4.8.1 Lamp Test  
NOTE  
This test involves putting the Liebert® GXT3-10000T220into bypass mode. The load is not  
protected against any utility disturbances or interruptions while the UPS is in bypass mode.  
1. With the Liebert GXT3-10000T220 connected to the utility, press the Menu button, select Control  
and press OK.  
2. Select Turn UPS On/Off and press OK.  
3. The LCD will show Turn UPS to BYPASS.  
4. Press OK to off the inverter to Bypass mode.  
5. A single acoustic signal confirms the operation.  
6. Select Turn UPS On/Off and press OK to place the UPS back in Normal Mode operation. The UPS  
performs the test during Start-up.  
4.8.2 Battery Test  
NOTE  
During the test an acoustic signal will be heard as though the device is operating in battery  
mode.  
1. Press the Menu button.  
2. Select SETUP and press OK.  
3. Select BATT TEST and press OK.  
A single acoustic signal confirms the operation and the load will be supplied by the battery.  
If the test is successful, the BATT LED will stop flashing and the UPS will return to Line mode. If the  
UPS circuitry detects a battery malfunction, Liebert GXT3-10000T220 will display an alarm (see  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Maintenance  
5.0 MAINTENANCE  
5.1  
Test, Replacement and Disposal of Batteries  
The Liebert® GXT3is designed to allow the user to replace the internal battery pack safely. Refer to  
Table 7 for internal battery pack part numbers for Liebert GXT3 UPS and Liebert External Battery  
Cabinets:  
Table 7  
Replacement battery pack  
Replacement Internal Battery  
Quantity  
Required  
Unit Type and Model #  
Pack Model Number  
Liebert UPS GXT3-10000T220  
GXT3-240BATKIT  
2
2
Liebert External Battery Cabinet  
GXT3-240VBATTCE  
GXT3-240BATKIT  
Read all safety cautions before proceeding. Contact your local dealer or Emerson representative to  
obtain the part number and pricing of the appropriate replacement battery pack.  
Disposal of the UPS and batteries should be carried out by a certified disposal company—observe all  
local regulations and laws. Lead-acid batteries are classified as harmful toxic waste and as such the  
law demands that they be disposed of by an authorized recycling centre.  
The typical battery lifecycle is 3 to 5 years at an ambient temperature of 25 C, but is also dependent  
on the frequency and duration of utility failures.  
The BATTERY TEST (see 4.8.2 - Battery Test) should be run periodically (6 to 12 months) to  
ascertain the general condition of the batteries and ensure maximum run time.  
5.2  
5.3  
Storage  
For extended storage at ambient temperatures cooler than 25°C (77°F), the batteries should be  
charged for 24 hours once every six months.  
Connect the UPS to a utility outlet socket having a ground (earth) connection and ensure the  
miniature circuit breaker is closed. If charging batteries with fixed utility connections, make  
connections in accordance with 3.0 - Installation.  
After 24 hours, disconnect the UPS from the utility supply.  
Cleaning  
The UPS may be cleaned by wiping it off with a dry cloth. Do not use liquids or solvents.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Communication  
6.0 COMMUNICATION  
6.1  
Communication Interface Port  
The Liebert® GXT3UPS has a terminal block on the rear of the UPS unit. Several signals are  
provided on this port and are assigned as follows.  
6.2  
Dry Contact  
The Dry Contact includes eight pins, as shown and defined in Figure 12.  
Figure 12 Dry contact pin layout  
1
2
3
4
(Low Battery Warning)  
(Any Mode Shutdown)  
(On- Battery Warning)  
(Battery Mode Shutdown)  
6.2.1 Any Mode Shutdown  
The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier,  
inverter and static switch so that there is no power to the loads.  
Any Mode Shutdown can be operated locally or remotely:  
• Local Any Mode Shutdown can be performed by shorting the pins in Set 3.  
• Remote Any Mode Shutdown can be performed using a switch connected to the pins in Set 3 and  
mounted at a remote location.  
Activation of the Any Mode Shutdown will be logged as an event in the event history log.  
NOTE  
Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown.  
The current limited source (+12VDC, 50mA) will be available from UPS.  
The connection to UPS for remote connection will be via terminal block connector.  
Any Mode Shutdown wiring must conform to all national, regional and local wiring codes and  
laws.  
WARNING  
!
When the Auto-enable output option is selected and the UPS output is disabled using the pins  
in Set 3, the Liebert GXT3-G’s output can turn On automatically and without warning if the  
connection of the pins in Set 3 is changed.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Communication  
6.2.2 Battery Mode Shutdown  
Battery Mode Shutdown permits shutting down the UPS by turning off the rectifier, inverter and  
static switch so that there is no power to the load when the UPS is On Battery. The auxiliary power  
for the UPS will still be active.  
Battery Mode Shutdown can be performed locally or remotely:  
• Local Battery Mode shutdown can be performed by shorting the pins in Set 4.  
• Remote Battery Mode Shutdown can be performed using a switch connected to the pins in Set 4  
and mounted at remote location.  
Activation of the Battery Mode Shutdown will be logged as an event in the event history log.  
NOTE  
Remote Power Off will be performed by NO contact.  
The current limited source (+12VDC, 50mA) will be available from UPS.  
The connection to the Liebert® GXT3for remote connection will be via terminal block  
connector.  
Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes  
and laws.  
This signal must last for 1.5 seconds or longer.  
A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute  
shutdown timer. This timer cannot be stopped once triggered. If the utility power returns  
during this countdown, the Liebert GXT3 will still shut down and must remain shut down for  
10 seconds. Whether the UPS turns back On when the power is restored depends on the  
auto-restart setting.  
6.2.3 On Battery  
On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power  
from the battery this dry contact will be closed.  
6.2.4 Low Battery  
Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power  
from the battery and has reached the Low Battery Warning time selected in the configuration  
program, this dry contact will be closed.  
NOTE  
The rated values for the dry contacts are:  
• Rated Voltage: 30V (AC or DC)  
• Rated Current: 300mA  
®
6.3  
Liebert IntelliSlot Communication Cards  
The Liebert IntelliSlot port accepts three optional cards:  
• Liebert IntelliSlot SNMP Card  
• Liebert IntelliSlot Relay Card  
• Liebert IntelliSlot 485 Card.  
The Liebert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the  
network.  
The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications  
and delivers support for built-in shutdown for AS/400 systems.  
The Liebert IntelliSlot 485 Card is used to connect the UPS and computer system.  
Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink®, the  
UPS or any additional ancillary product for the Liebert GXT3. These instructions are available at  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Communication  
6.3.1 Liebert® MultiLink®  
Liebert MultiLink continually monitors the UPS and can shut down your computer or server in the  
event of an extended power failure.  
®
Liebert MultiLink can also be configured for use without the USB cable when the Liebert IntelliSlot  
SNMP/Web card is installed in the UPS. Additionally, Liebert MultiLink can be configured to  
coordinate shutdown across the network with other computers running Liebert MultiLink when you  
purchase a Liebert MultiLink License Kit. For more information about the Liebert IntelliSlot  
SNMP/Web Card and Liebert MultiLink License Kits, visit our Web site (www.liebert.com) or  
contact your local dealer or Emerson representative.  
Several option cards are available for use in the Liebert IntelliSlot port of the Liebert GXT3. The  
Liebert IntelliSlot SNMP/Web Card provides SNMP and Web-based monitoring and control of the  
UPS across the network.  
The Liebert IntelliSlot MultiPort 4 Card allows installing Liebert MultiLink software on four  
computers and coordinate shutdown in the event of a power failure.  
The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom wired applications  
and delivers support for built-in shutdown for AS/400 systems.  
CAUTION  
!
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables  
should be shielded and run separate from all other power cables, where applicable.  
6.4  
Remote Emergency Power Off  
The UPS is equipped with a Remote Emergency Power Off (REPO) connector.  
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS  
input feeder breaker to remove all sources of power to the UPS and connected equipment to comply  
with national and local wiring codes and regulations.  
REPO switch connection diagram  
UPS ships with REPO jumper  
installed allowing the UPS  
to operate  
Opening the REPO connection will disable the UPS.  
Manual restart using the front panel is required after  
the REPO connection is closed again.  
1
2
1
2
Normally closed switch system  
(fail-safe)  
CAUTION  
!
To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should  
be shielded and run separately from power cables.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Troubleshooting  
7.0 TROUBLESHOOTING  
If any technical problems should occur, check the following before contacting Liebert® technical  
support:  
• Is the utility voltage present at the UPS input?  
• Has the input fuse blown or have the circuit breakers tripped?  
• Has the UPS startup procedure been followed correctly?  
When contacting Liebert technical support, have the following information available:  
• Device model number  
• Serial number (from the nameplate)  
• Exact description of the problem (what loads are being operated, does the problem occur regularly  
or sporadically, etc.)  
For descriptions of the indicators mentioned in the following table, see 4.2.1 - Controls and  
Table 8  
Troubleshooting guide  
Problem  
Possible Cause  
Solution  
Switch on utility breaker  
Utility mains switched off  
Have utility mains inspected by a qualified  
technician  
No display  
No alarm  
No mains voltage present  
(UPS switched Off)  
Replace with fuse of same type or switch on circuit  
breaker. If the problem persists, contact technical  
support.  
Input fuse blown or input  
circuit breaker tripped  
UPS on LED does not light up,  
alarm beeps sound at intervals  
No utility mains voltage  
present  
Have utility mains inspected by a qualified  
technician  
UPS on LED does not illuminate  
when utility mains voltage present,  
acoustic alarm active at intervals  
Replace with fuse of same type or switch on circuit  
breaker. If the problem persists, contact technical  
support  
Input fuse defective or input  
circuit breaker tripped  
UPS error  
Contact technical support  
FAULT LED illuminates, alarm  
sounding constantly  
Overheating  
Decrease ambient temperature  
The battery breaker is open,  
in the OFF position  
Move the battery breaker to the ON position  
Charge batteries (see Battery Test on page 19)  
Batteries are not fully charged and test backup time. If the problem persists,  
contact technical support.  
Battery Run time less than specified  
Batteries are defective  
Contact technical support  
Charging device is defective  
Overload at UPS output  
Contact technical support  
OVERLOAD message displayed  
Reduce load to the permissible value  
Check whether the correct cable has been used  
(standard modem/null modem cables are not  
permissible)  
Wrong serial connection  
cable  
No communication between UPS  
and PC  
Interface on the PC is being  
used by another process or is  
defective  
Check whether other software/service is accessing  
the interface on the PC; try selecting a different  
serial interface  
Interference on the data cable Lay cable differently/Reinstall cabling  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Specifications  
8.0 SPECIFICATIONS  
Table 9  
Model Rating, VA (W)  
Dimensions, in. (mm)  
Unit, W x D x H  
Liebert® GXT3specifications  
10,000 (9000)  
31.5 x 11.81 x 26.57 (800 x 300 x 675)  
41.8 x 16.7 x 34 (1062 x 426 x 866)  
Shipping, W x D x H  
Weight, lb (kg)  
Unit  
308 (140)  
428 (194)  
Shipping  
Input AC Parameters  
Nominal Operating Frequency  
50 or 60Hz (Factory Default = 60)  
120/208 at 120 degrees  
120 / 208 / 220 / 240  
Factory Default VAC  
User-Configurable VAC  
Operating Voltage Range  
Without Battery Operation  
100 - 185 ±5VAC  
280  
Maximum Allowable VAC  
Input Frequency  
Without Battery Operation  
40 - 70Hz  
Input Power Connection  
BYP, L1, L2, GND  
Output AC Parameters  
Factory Default, VAC  
208  
Hardwire Terminal Block  
Output Connections  
Output: (GEC, X1, X2, X3, X4, GND) Bypass: L1, L2, GND  
Frequency  
Waveform  
50Hz or 60Hz, Nominal  
Sinewave  
>200% for 5 cycles; 151 - 200% for 1 second; 131-150% 10 seconds;  
105 - 130% 1 minute  
Main Mode Overload  
Battery Parameters  
Type  
Quantity x V  
Valve-regulated, non-spillable, lead acid  
20 x 12V  
Battery Mfr. / Part #  
CSB HR1234R or Panasonic UP-RW1245  
Backup Time  
Recharge Time (Internal Batteries)  
Bypass Protection Limits  
Maximum Bypass Current  
Disable Bypass Operation  
Re-Enable Bypass Operation  
Disable Bypass Operation  
Environmental  
3 hr. to 90% capacity after full discharge into 100% load  
50A  
If input voltage exceeds ±10% of the nominal voltage  
If input voltage returns to within ±8% of nominal output voltage  
When the input frequency prevents synchronous operation  
32 to 86 (0 to 30) with 0.9 pf  
86 to 104 (30 to 40) with 0.8pf  
Operating Temperature, °F (°C)  
Storage Temperature, °F (°C)  
Transportation, °F (°C)  
Relative Humidity  
Operating Elevation  
Audible Noise  
5 to 122 (-15 to 50)  
0-95% non-condensing  
Up to 3281 ft (1000m) at 80°F (27°C) without derating  
<55 dBA at 3.3ft (1m) from rear; <50 dBA at 3.3ft (1m) from front or sides  
Agency  
Safety  
UL 1778, c-UL  
FCC Part 15, Subpart B, Class A  
IEC/EN 61000-4-5, ANSI C62.41 (for North America)  
ISTA Procedure 1B  
RFI/EMI  
Surge Immunity  
Transportation  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Specifications  
Table 10 Battery cabinet specifications  
GXT3-240TBATTCE  
Model Number  
Dimensions, W x D x H, in. (mm)  
Unit  
31.5 x 11.81 x 26.57 (800 x 300 x 675)  
41.8 x 16.7 x 34 (1062 x 426 x 866)  
Shipping  
Weight, lb (kg)  
Unit  
Shipping  
243 (110)  
309 (140)  
Internal Battery Parameters  
Type  
Valve-regulated, non-spillable, lead acid  
2 x 20 x 12V  
Quantity x V  
Battery Manufacturer, Part #  
CSB HR1234R or Panasonic UP-RW1245  
Temperature Limits, Batteries Only,  
°F (°C)  
32 to 104 (0 to 40)  
Backup Time  
Environmental  
Operating Temp, °F (°C)  
Storage Temp  
32 to 80 (0 to 27)  
5 to 104 (-15 to 40)  
5 to 122 (-15 to 50)  
0-95% non-condensing  
Transportation Temp, °F (°C)  
Relative Humidity  
Operating Elevation  
Agency  
Up to 3281 ft (1000m) at 80°F (27°C) without derating  
Safety  
UL 1778, c-UL Listed  
ISTA Procedure 1B  
Transportation  
Table 11  
Typical battery run times for the Liebert® GXT3-10000T230  
Load %  
Number of Batteries,  
Battery Cabinets  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90% 100%  
Internal Battery  
81  
39  
22  
15  
11  
8
6
5
4
3
Internal Battery + 1  
External Battery Cabinet  
190  
316  
127  
162  
81  
60  
46  
82  
39  
69  
32  
52  
26  
48  
22  
18  
Internal Battery + 2  
External Battery Cabinets  
136  
106  
44  
39  
Approximate discharge times are at 77°F (25°C) with a 100% resistive load.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Product Warranty Registration  
9.0 PRODUCT WARRANTY REGISTRATION  
To register for warranty protection:  
• Visit the Quick Links section of Liebert’s Web site at:  
• Click on Product Warranty Registration and fill in the form.  
If you have any questions, please contact us at:  
• US: 800-222-5877  
• Outside the US: 614-841-6755  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Ensuring The High Availability  
Of Mission-Critical Data And Applications.  
Emerson Network Power, a business of Emerson (NYSE:EMR),  
is the global leader in enabling Business-Critical Continuity™  
from grid to chip for telecommunication networks, data centers,  
health care and industrial facilities. Emerson Network Power  
provides innovative solutions and expertise in areas including  
AC and DC power and precision cooling systems, embedded  
computing and power, integrated racks and enclosures,  
power switching and controls, infrastructure management,  
and connectivity. All solutions are supported globally by local  
Emerson Network Power service technicians. Liebert AC power,  
precision cooling and monitoring products and services  
from Emerson Network Power deliver Efficiency Without  
Compromiseby helping customers optimize their data center  
infrastructure to reduce costs and deliver high availability.  
Technical Support / Service  
Web Site  
Monitoring  
800-222-5877  
Outside North America: +00800 1155 4499  
Single-Phase UPS & Server Cabinets  
800-222-5877  
Outside North America: +00800 1155 4499  
Three-Phase UPS & Power Systems  
800-543-2378  
Outside North America: 614-841-6598  
Environmental Systems  
800-543-2778  
Outside the United States: 614-888-0246  
Locations  
United States  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
Europe  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD) Italy  
+39 049 9719 111  
Fax: +39 049 5841 257  
While every precaution has been taken to ensure the accuracy  
and completeness of this literature, Liebert Corporation assumes no  
responsibility and disclaims all liability for damages resulting from use of  
this information or for any errors or omissions.  
© 2010 Liebert Corporation  
All rights reserved throughout the world. Specifications subject to change  
without notice.  
Asia  
29/F, The Orient Square Building  
F. Ortigas Jr. Road, Ortigas Center  
Pasig City 1605  
Philippines  
+63 2 687 6615  
® Liebert is a registered trademark of Liebert Corporation.  
All names referred to are trademarks  
Fax: +63 2 730 9572  
or registered trademarks of their respective owners.  
SL-23187_REV1_04-12  
Emerson Network Power.  
The global leader in enabling Business-Critical Continuity™  
EmersonNetworkPower.com  
AC Power  
Connectivity  
DC Power  
Embedded Computing  
Outside Plant  
Racks & Integrated Cabinets  
Embedded Power  
Power Switching & Controls  
Precision Cooling  
Services  
Infrastructure Management & Monitoring  
Surge Protection  
Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies.  
©2010 Emerson Electric Co.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Kyocera Cell Phone Blade User Manual
Lennox International Inc Furnace G20 User Manual
Lexicon Stereo Amplifier CX 5 User Manual
LG Electronics Cell Phone VX9200Maroon User Manual
LG Electronics Server PCS100R User Manual
LG Electronics Washer WM1333H User Manual
Listen Technologies Stereo System LA 140 User Manual
Magnavox Flat Panel Television 20MF605T User Manual
Mazda Automobile 2005 6 SPORTS SEDAN User Manual
Metra Electronics Automobile Accessories 99 7402 User Manual