Liebert Power Supply 208V User Manual

POWER AVAILABILITY  
USER MANUAL  
UPStation GXT 2U™  
2700VA  
208V  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters . . . 5  
Rectifier/Power Factor Correction (PFC) Circuit . . . . . . . . . . . . . . . . . . 5  
Load/Battery Level Indicators (4 Green, 1 Amber) . . . . . . . . . . . . . . . 15  
Output Voltage Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16  
OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Normal Mode Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Bypass Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Battery Mode Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Battery Recharge Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19  
GXT 2U Configuration Program Abilities . . . . . . . . . . . . . . . . . . . . . . . 22  
What You Will Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
BATTERY CABINET SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 31  
BATTERY RUN TIMES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32  
Product Warranty Registration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT SAFETY INSTRUCTIONS  
WARNING  
!
Opening or removing the cover may expose you to lethal  
voltages within this unit even when it is apparently not  
operating and the input wiring is disconnected from the  
electrical source. Observe all cautions and warnings in this  
manual. Failure to do so MAY result in serious injury or  
death. Refer all UPS and battery service to qualified service  
personnel. Do not attempt to service this product yourself.  
Never work alone.  
SAVE THESE INSTRUCTIONS  
This manual contains important safety instructions. Read all safety, instal-  
lation, and operating instructions before operating the Uninterruptible  
Power System (UPS). Adhere to all warnings on the unit and in this man-  
ual. Follow all operating and user instructions. Individuals without previ-  
ous training can install and operate this equipment.  
It is not intended for use with life support and other designated “critical”  
devices. Maximum load must not exceed that shown on the UPS rating  
label. The UPS is designed for data processing equipment. If uncertain,  
consult your local dealer or Liebert representative.  
This UPS is designed for use on a properly grounded (earthed), 50Hz or  
60Hz, 208V supply (programmable for 200, 208, 220, 230, and 240VAC  
output). Installation instructions and warning notices are located in this  
manual.  
ELECTROMAGNETIC COMPATIBILITY—The GXT 2U™ Series com-  
plies with the limits for a CLASS A DIGITAL DEVICE, PURSUANT TO  
Part 15 of FCC rules. Operation is subject to the following two conditions:  
(1) This device may not cause harmful interference, and (2) this device  
must accept any interference received, including interference that may  
cause undesired operation. Operating this device in a residential area is  
likely to cause harmful interference that users must correct at their own  
expense.  
Operate the UPS in an indoor environment only in an ambient tempera-  
ture range of 32°F to +104°F (0°C to +40°C). Install it in a clean environ-  
ment, free from moisture, flammable liquids, gases and corrosive  
substances.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
This UPS contains no user serviceable parts except the internal battery  
pack. The UPS ON/Standby push buttons do not electrically isolate inter-  
nal parts. Under no circumstances attempt to gain access internally other  
than to replace the batteries due to risk of electric shock or burn. Do not  
continue to use the UPS if the front panel indications are not in accor-  
dance with these operating instructions or if the UPS performance alters  
in use. Refer all faults to your local dealer, Liebert representative or the  
Liebert Worldwide Support Group.  
Servicing of batteries should be performed or supervised by personnel  
knowledgeable of batteries and the required precautions. Keep unautho-  
rized personnel away from the batteries. PROPER DISPOSAL OF BAT-  
TERIES IS REQUIRED. REFER TO YOUR LOCAL LAWS AND  
REGULATIONS FOR BATTERY DISPOSAL REQUIREMENTS.  
Never block or insert any object into the ventilation holes or other open-  
ings of the UPS.  
DO NOT CONNECT equipment that could overload the UPS or demand  
half-wave rectification from the UPS, for example: electric drills, vacuum  
cleaners, laser printers or hairdryers.  
Storing magnetic media on top of the UPS may result in data loss or cor-  
ruption.  
Turn the UPS off and isolate the UPS before cleaning; use only a soft  
cloth, never liquid or aerosol cleaners. Keep the front and rear vents free  
of dust accumulation that could restrict airflow.  
When replacing batteries, replace with the same Liebert authorized  
replacement battery kits.  
CAUTION  
!
Do not dispose of battery or batteries in a fire. The battery  
may explode.  
Do not open or mutilate the battery or batteries. Released  
electrolyte is harmful to skin and eyes. It may be toxic.  
CAUTION  
!
A battery can present a risk of electrical shock and high  
short circuit current. The following precautions should be  
observed when working on batteries:  
• Remove watches, rings, and other metal objects.  
• Use tools with insulated handles.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
GLOSSARY OF SYMBOLS  
Risk of electrical shock  
Indicates caution followed by important instructions  
AC input  
AC output  
Requests the user to consult the manual  
i
Indicates the unit contains a valve-regulated lead acid  
battery  
Recycle  
DC voltage  
Equipment grounding conductor  
Bonded to ground  
AC voltage  
ON  
Standby  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INTRODUCTION  
Congratulations on your choice of the Liebert UPStation GXT 2U™  
Uninterruptible Power System (UPS). It provides conditioned power to  
microcomputers and other sensitive electronic equipment.  
Upon generation, AC power is clean and stable. However, during trans-  
mission and distribution it may be subject to voltage sags, spikes, or com-  
plete power failure that may interrupt computer operations, cause data  
loss, or even damage equipment. The UPStation GXT 2U protects equip-  
ment from these disturbances.  
The UPStation GXT 2U is rated for 2700 VA, 1890 watts. Complete model  
specifications appear at the end of this manual.  
The UPStation GXT 2U is a compact, “on-line” UPS. An on-line UPS con-  
tinuously conditions and regulates its output voltage, whether utility power  
is present or not. It supplies connected equipment with clean sinewave  
power. Sensitive electronic equipment operates best from sinewave  
power.  
For ease of use, the UPStation GXT 2U features a light-emitting diode  
(LED) display to indicate either load percentage or battery capacity  
depending upon the mode of operation. It also provides self-diagnostic  
tests, a combination ON/Alarm Silence/Manual Battery Test button, a  
Standby button, user configurable program, and two levels of alarms  
when the unit is operating on battery.  
The UPStation GXT 2U has an interface port for communication between  
the UPS and a network server or other computer systems. This port pro-  
vides detailed operating information including voltages, currents, and  
alarm status to the host system when used in conjunction with Liebert  
MultiLink™ software. MultiLink software can also remotely control UPS  
operation.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
MAJOR COMPONENTS  
Input  
Output  
Dynamic  
Bypass  
TVSS &  
EMI/RFI  
Filters  
Rectifier  
/PFC  
Inverter  
L1  
L1  
DC to DC  
Converter  
Battery  
Charger  
Battery  
L2  
G
L2  
G
TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI  
FILTERS  
These UPS components provide surge protection and filter both electro-  
magnetic interference (EMI) and radio frequency interference (RFI). They  
minimize any surges or interference present in the utility line and keep the  
sensitive equipment protected.  
RECTIFIER/POWER FACTOR CORRECTION (PFC) CIRCUIT  
In normal operation, the rectifier/power factor correction (PFC) circuit con-  
verts utility AC power to regulated DC power for use by the inverter while  
ensuring that the waveshape of the input current used by the UPS is near  
ideal. Extracting this sinewave input current achieves two objectives:  
The utility power is used as efficiently as possible by the UPS.  
The amount of distortion reflected on the utility is reduced.  
This results in cleaner power being available to other devices in the build-  
ing not being protected by the UPStation GXT 2U.  
INVERTER  
In normal operation, the inverter utilizes the DC output of the power factor  
correction circuit and inverts it into precise, regulated sinewave AC power.  
Upon a utility power failure, the inverter receives its required energy from  
the battery through the DC to DC converter. In both modes of operation,  
the UPS inverter is on-line and continuously generating clean, precise,  
regulated AC output power.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
BATTERY CHARGER  
The battery charger utilizes energy from the utility power and precisely  
regulates it to continuously “float charge” the batteries. The batteries are  
being charged whenever the UPStation GXT 2U is plugged in, even when  
the UPS is not turned on.  
DC TO DC CONVERTER  
The DC to DC converter utilizes energy from the battery system and  
raises the DC voltage to the optimum operating voltage for the inverter.  
This allows the inverter to operate continuously at its optimum efficiency  
and voltage, thus increasing reliability.  
BATTERY  
The UPStation GXT 2U utilizes valve-regulated, nonspillable, flame retar-  
dant, lead acid batteries. To maintain battery design life, operate the UPS  
in an ambient temperature of 68°F to 77°F (20°C to 25°C). Optional exter-  
nal battery cabinets are available to extend battery run times.  
DYNAMIC BYPASS  
The UPStation GXT 2U provides an alternate path for utility power to the  
connected load in the unlikely event of a UPS malfunction. Should the  
UPS have an overload, overtemperature, or UPS failure condition, the  
UPS automatically transfers the connected load to bypass. Bypass opera-  
tion is indicated by an audible alarm and illuminated amber Bypass LED  
(other LEDs may be illuminated to indicate the diagnosed problem). To  
manually transfer the connected load from the inverter to bypass, press  
the Standby button once.  
NOTE  
The bypass power path does NOT protect the connected  
equipment from disturbances on the utility supply.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
GXT 2U (REAR VIEW)  
®
Intellislot  
Port  
DB-9  
Communications Port  
Cooling  
Fans  
AC Input  
(L6-20)  
Input Circuit  
Breaker  
(20 amp)  
External  
Battery  
Connector  
Output  
Receptacle  
(L6-20R)  
Support  
Base  
Output  
Receptacles  
(L6-15R)  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
INSTALLATION  
PREPARATION  
1. Visually inspect the UPS for freight damage. Report damage to the  
carrier and your local dealer or Liebert representative.  
CAUTION  
!
The UPS is heavy (see Specifications section). Take proper  
precautions when lifting or moving it.  
2. Decide where to place the GXT 2U. Install the UPS indoors in a con-  
trolled environment, where it cannot be accidentally turned off. Place  
it in an area of unrestricted airflow around the unit, away from water,  
flammable liquids, gases, corrosives, and conductive contaminants.  
Maintain a minimum clearance of 4 inches (100mm) in the front and  
rear of the UPS. Maintain an ambient temperature range of 32°F to  
104°F (0°C to 40°C).  
NOTE  
UPS operation in temperatures above 77°F (25°C) reduces  
battery life.  
3. The GXT 2U may be installed in either a tower configuration or in a  
rack, depending on available space and use considerations. Deter-  
mine the type of installation and follow the appropriate instructions in  
either Tower UPS Installation or Rack-Mount UPS Conversion  
and Installation.  
TOWER UPS INSTALLATION  
When using the GXT 2U in a tower configuration, use the included sup-  
port base (shown below, left) to stabilize the UPS.  
If any battery cabinets are added, they will include spacers to accommo-  
date the additional cabinets (shown below, right).  
Support base  
Spacers added to support  
base to accommodate  
additional battery cabinets  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
RACK-MOUNT UPS CONVERSION AND INSTALLATION  
NOTE  
When rack mounted, the UPS must be supported by a shelf,  
brackets or slide rails on each side. The rack mount handles  
WILL NOT support the weight of the UPS. They are used to  
move the UPS into and out of the rack.  
1. For slide rail installations, first remove the top/side fin. Slide the  
top/side fin forward, then lift it up to remove. If desired, install the  
optional rack mount handles that were shipped with the UPS.  
U
PStation  
G
XT  
+
AC  
IN  
PU  
T
BA  
TT  
ER  
Y
UP  
S
ON  
BY  
PA  
SS  
Optional rack mount handles  
Securing hardware and slide rails are sold separately. Contact your  
local dealer or Liebert representative for these additional options and  
any assistance needed.  
2. Unpack the two (2) rack-  
Return  
mounting bracket assemblies  
and mounting hardware from  
the rack-mounting kit  
flanges  
Retaining  
latches  
(P/N: RMKIT18-32). Bracket  
assemblies are interchange-  
able between left-hand or  
right-hand. Remove inner  
member of each bracket  
assembly as shown at right by  
extending it to its outermost  
position, depressing the  
retaining latch and then pulling  
inner member from bracket  
assembly.  
Rear  
members  
Front  
members  
Inner  
members  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. Determine the height position inside the rack enclosure where you  
want to mount the UPS or battery cabinet.  
CAUTION  
!
Reduce risk of tipping the rack enclosure by placing UPS or  
battery cabinet in the lowest possible rack position.  
Install rear member of each  
bracket assembly into rack  
enclosure with two (2) M5  
screws provided in this kit.  
(See figure at right.) Return  
flanges on bracket assembly  
fit to the inside of rack mount-  
ing rails. Insert screws loosely  
(finger-tight) into top and bot-  
tom holes of return flange on  
rear member. Extend bracket  
assembly by sliding front  
M5 screws  
Front rack  
mounting rails  
Rear rack  
mounting  
rails  
M5 screws  
member forward until it touches the front rack mounting rail. Insert  
two (2) M5 screws loosely (finger-tight) into top and bottom holes of  
return flange on each front member. Make sure bracket assemblies  
are at the same mounting height on all four (4) rack mounting rails.  
4. Locate eight (8) M4 screws  
and eight (8) M4 nuts from  
hardware pack in this kit.  
M4 nuts  
M4  
screws  
Each nut has a locking, nylon  
insert that begins gripping the  
screw when it is halfway tight.  
Make sure to tighten nut and  
screw completely to assure  
locking action. Fasten rear  
member and front member  
together using four (4) screws  
and four (4) nuts per bracket  
assembly as shown in the fig-  
ures at right. For maximum  
support, locate fasteners for  
each bracket assembly as far  
apart as possible, depending  
on rack depth, while still join-  
ing both members (See fig-  
ures at right). Check  
18" rack  
depth  
M4 nuts  
M4  
M4 nuts  
screws  
32" rack  
depth  
M4 nuts  
alignment of bracket assemblies and TIGHTEN ALL SCREWS  
FROM STEPS 3 and 4.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Prepare the UPS or battery cab-  
inet (the “equipment”) for rack  
mounting by following instruc-  
tions in the equipment’s user  
manual. The equipment may  
require additional parts to be  
added or parts to be removed  
for rack mounting. After it is pre-  
pared, lay equipment in rack-  
mounting position. Fasten inner  
members from Step 2 to the  
equipment on both sides as  
shown in the figure at right with  
(8) M4 screws provided in this  
kit. Make sure retaining latch is  
near the rear of the equipment  
as shown in the figure at right.  
M4  
screws  
Retaining  
latch  
UPS or battery  
cabinet  
Front  
M4  
screws  
6. Open grease packet pro-  
vided in this kit. Apply a 1"  
long bead of grease four  
Apply  
grease  
UPS or  
battery  
cabinet  
(4) places inside the bot-  
tom, curved tracks of front  
members as shown at  
right. The grease will allow  
the equipment to slide into  
the bracket assemblies  
more easily.  
Apply  
grease  
(inside)  
CAUTION  
!
Lifting equipment into rack may be a two-person job,  
depending on weight of equipment. See equipment’s user  
manual.  
7. Insert the equipment, with inner members attached from Step 5, into  
bracket assemblies by inserting top and bottom edges of inner mem-  
bers into the top and bottom, curved tracks of front members and slid-  
ing the equipment into rack (see figure in Step 6). Ends of inner  
members are tapered to allow rear of the equipment to be angled  
upward before insertion, if space allows.  
Then the rear, bottom edges of inner  
members can be placed into front edge  
of bottom tracks, and the front of the  
equipment can be tipped up into hori-  
zontal position to insert the top edges of  
inner members before sliding the equip-  
ment into rack (see figure at right). The equipment should move  
smoothly into bracket assemblies. If not, recheck alignment of front  
and rear members from Steps 3 and 4.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. Secure front of the equipment to rack mounting rails to prevent the  
equipment from sliding out of position. If securing holes are provided  
on front of the equipment that align with the center holes on return  
flange of front members, you can use the four (4) extra M5 screws  
provided in this kit to secure the equipment. Otherwise, the equip-  
ment should be secured to front of rack mounting rails with four (4)  
customer-supplied fasteners.  
9. To orient the display for horizon-  
Horizontal overlay  
for rack UPS  
Vertical  
overlay  
for  
tower  
UPS  
tal viewing, remove the front  
plastic bezel by pulling forward  
evenly on both sides. The unit  
has two front panel overlays.  
Remove the outer overlay (used  
for tower installation). This  
reveals a horizontally oriented  
front panel overlay for rack  
mounting. Snap the front bezel  
back into place.  
BPYAS  
USPON  
10. Once the UPS is installed in the  
rack, the load may be con-  
nected. Ensure the load equip-  
ment is turned off; plug all loads  
into the output receptacles on  
the rear of the UPS.  
BPYAS  
+
BTAERY  
USPON  
USPationGXT  
ACINPUT  
+
BTAERY  
USPationGXT  
ACINPUT  
11. Plug the UPS into a dedicated  
wall receptacle properly pro-  
tected by a circuit breaker or  
fuse in accordance with national  
and local electrical codes. Use a 20 amp rated device for the 2700VA,  
208V unit. The wall receptacle must be grounded.  
12. Turn ON the UPS by pressing the ON button; then turn on the con-  
nected load equipment. The UPS is now providing conditioned power  
to your equipment.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXTERNAL BATTERY CABINET INSTALLATION  
Optional Liebert external battery cabinets may be connected to the UPS  
to provide additional battery run time. External battery cabinets are  
designed to be placed all on one side of the UPS or stacked beneath the  
UPS. There is no limit to the number of external battery cabinets that can  
be used but each cabinet will increase the battery recharge time.  
CAUTION  
!
The external battery cabinet(s) are heavy (see  
Specifications section). External battery cabinets can be  
used in rack-mount or tower configuration. Take proper  
precautions when lifting them.  
1. Visually inspect the external battery cabinet for freight damage. Report  
damage to the carrier and your local dealer or Liebert representative.  
2. For slide rail installations, first remove the top/side fin. Top/side fin  
slides forward and then lift up to remove. Optional rack-mount han-  
dles are shipped with the external battery cabinet and may be  
installed at this time if desired.  
3. Securing hardware and slide rails are sold separately. Please contact  
your local dealer or Liebert representative for these additional options  
and any assistance needed. Fasten the slides into position with the  
screws per the instructions included with the slide rails.  
4. Use the enclosed support bases for the  
tower option to prevent tip-over. One  
additional set of support base extensions  
ships with each external battery cabinet.  
5. Connect the supplied external battery cab-  
inet cable to the rear of the external bat-  
tery cabinet, then to the rear of the UPS.  
6. Turn ON the battery breaker on the  
rear of the external battery cabinet.  
7. The UPS is now equipped with addi-  
tional backup battery run time. For  
approximate battery run times, refer to  
the Battery Run Times charts in this  
manual.  
NOTE  
You must use the included Configuration Program to specify  
the number of external battery cabinets connected to the UPS.  
For more information, see Configuration Program on  
page 22.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
CONTROLS AND INDICATORS  
All LEDs illuminated  
for illustrative purposes only.  
ON/Alarm Silence/Manual Battery Test Button  
This button controls output power to connected load(s) and has  
three functions:  
• ON  
• Alarm Silence  
• Manual Battery Test  
ON - Pressing this button will start up the UPS in order to provide condi-  
tioned and protected power.  
Alarm Silence - To silence alarms, press this button for at least one sec-  
ond. After the alarm is silenced, the UPStation GXT 2U will reactivate the  
alarm system to alert of additional problems.  
NOTE  
The LOW BATTERY and BYPASS reminder alarms  
CANNOT be silenced.  
Manual Battery Test - To initiate a manual battery test, press the ON but-  
ton for at least one second while operating from utility power with no  
alarm conditions present.  
• If only three of the five Battery LEDs illuminate, allow the UPS to  
recharge the batteries for 24 hours.  
• After 24 hours, retest the batteries.  
• After the batteries have been retested, if only three of the five Battery  
LEDs illuminate, contact your local dealer, Liebert representative or  
Liebert Worldwide Support Group.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Standby/Manual Bypass Button  
This button controls output power to connected load(s) and has  
dual functions: Standby and Manual Bypass.  
CAUTION  
!
While the UPS is in Normal Mode operation, pressing the  
Standby/ Manual Bypass button once will put the UPS into  
Bypass Mode.  
Once the UPS is in Bypass Mode operation, press the  
Standby/ Manual Bypass button two distinct times (for about  
one second each time) to turn off the UPS. Perform all  
necessary shutdown procedures on connected loads before  
turning off the UPS.  
Load/Battery Level Indicators (4 Green, 1 Amber)  
The load/battery level indicators have dual functions. During normal mode  
operation LED indicators display the approximate electrical load placed  
upon the UPS; and during battery mode operation LED indicators display  
approximate battery capacity.  
The UPStation GXT 2U is equipped with automatic and remote battery  
test features. The automatic test occurs every 14 days (this option is user  
configurable) if utility has not been interrupted. Should the battery fail this  
test, the red Fault indicator LED along with the A and C diagnostic LEDs  
will illuminate and an alarm will sound (refer to Troubleshooting section).  
The remote test feature functions with MultiLink 3 software and can  
remotely initiate the battery test.  
Fault Indicator LED (Red)  
The Fault indicator LED is illuminated if the UPS has detected a problem.  
Also, one or more of the load/battery level indicators may be illuminated  
(refer to Troubleshooting section).  
Bypass Indicator LED (Amber)  
The Bypass indicator LED is illuminated when the UPS is operating from  
bypass power. An alarm will sound indicating the UPS detected a prob-  
lem, or the manual bypass function has been activated.  
UPS ON Indicator LED (Green)  
The UPS ON indicator LED is illuminated when the UPS inverter is oper-  
ating and supplying power to your connected loads.  
Battery Indicator LED (Amber)  
The Battery indicator LED is illuminated when the UPS is operating on  
battery.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
AC Input Indicator LED (Green)  
The AC Input indicator LED is illuminated when utility power is available  
and within the input specifications.  
Output Voltage Selection  
The Output Voltage is user configurable and is designed to allow select-  
ing or changing the desired output voltage to match the utility via the  
GXT 2U Configuration Program provided with the UPS. The settings to  
choose from are 200, 208, 220, 230, and 240 VAC output. The factory  
default setting is 208 VAC.  
CAUTION  
!
Never change the voltage settings while the UPS is ON and  
powering connected loads.  
NOTE  
Setting output voltage to 200 VAC will cause the UPS unit to  
be derated to 2400 VA, 1680 watts.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
OPERATING INSTRUCTIONS  
NORMAL MODE OPERATION  
During normal operation, util-  
ity power provides energy to  
the UPS. The filters, power  
factor correction circuit and the  
inverter process this power to  
provide computer grade power  
to connected loads. The UPS  
maintains the batteries in a  
fully charged state.  
AC INPUT BATTERY UPS ON BYPASS  
Normal Mode Operation at 26-50%  
The four green load level LEDs indicate an approximate level of load in  
25% increments. If the UPS becomes loaded beyond full rating, the fifth  
(amber) LED indicator will illuminate and the UPS will sound an audible  
alarm. The display template indicates the percentage of load (26-50% of  
load shown in the example above) on the UPS output.  
BYPASS MODE OPERATION  
Bypass mode occurs when the  
OFF button is pressed once  
while the UPS is in Normal  
Mode. During bypass opera-  
tion, utility power provides  
energy to the UPS. The utility  
power bypasses the inverter  
AC INPUT BATTERY UPS ON BYPASS  
and provides power for the  
connected load.  
Bypass Mode Operation at 26-50%  
The four green load level LEDs indicate an approximate level of load in  
25% increments. If the UPS becomes loaded beyond full rating, the fifth  
(amber) LED indicator will illuminate and the UPS will sound an audible  
alarm. The display template indicates the percentage of load (26-50% of  
load shown in the example above) on the UPS output.  
CAUTION  
!
Turning OFF the UPS while in bypass mode will result in  
loss of output power.  
BATTERY MODE OPERATION  
Battery mode occurs in event  
of an extreme input voltage  
condition or complete utility  
failure. The battery system  
supplies power through the  
DC to DC converter to the  
AC INPUT BATTERY UPS ON BYPASS  
inverter to generate power  
for the connected load.  
Battery Mode Operation at 80-61%  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
During battery mode an alarm sounds every 10 seconds. This will change  
to two beeps every 5 seconds when the battery runs low (approximately  
2 minutes remaining, but this is user configurable). The AC Input LED will  
extinguish, and the Battery LED will illuminate to warn that a utility prob-  
lem has occurred. Each battery level indicator represents a 20% capacity  
level. As capacity decreases, fewer indicators remain illuminated. Refer to  
Troubleshooting section.  
For approximate battery run times, refer to the Battery Run Times charts  
in this manual. These times are approximates based on resistive load and  
an ambient temperature of 77°F (25°C). To increase this time, turn off  
non-essential pieces of equipment (such as idle computers and monitors)  
or add the optional external battery cabinet.  
CAUTION  
!
Turning OFF the UPS while in battery mode will result in  
loss of output power.  
BATTERY RECHARGE MODE  
Once utility power is restored, the UPS resumes normal operation. At this  
time, the Battery Charger begins recharging.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
COMMUNICATIONS  
COMMUNICATIONS INTERFACE PORT  
The UPStation GXT 2U UPS has a standard DB-9 serial port female con-  
nector located on the rear of the UPS unit. Several signals are provided  
on this port and are assigned as follows:  
Pin  
Assignment Description  
1
2
3
4
5
6
7
8
9
Low Battery (open collector)  
UPS TxD (typical RS-232 levels)  
UPS RxD (typical RS-232 levels)  
Remote Shutdown (5-12VDC, 10-24 mA max); battery operation  
Common  
Remote Shutdown (short to pin 5); all modes of operation  
Low Battery (open emitter)  
Utility Fail (open emitter)  
Utility Fail (open collector)  
Pin Assignment  
Collector to Emitter*  
Open  
Collector  
6
7
8
9
(+)  
(-)  
330 Ohms  
Open  
Emitter  
1
2
3
4
5
* Maximum voltage and current on pins 1, 7, 8, and 9 is 60VDC; 10.0 mA.  
PINS 4 & 5 - REMOTE SHUTDOWN ON BATTERY  
1. This pin is functional only when the UPS is in battery mode. If the  
UPS is being powered by the utility, Pin 4 will ignore any signal on this  
pin.  
2. Pin 4 requires a 5-12 VDC signal to shutdown. This normally comes  
form the serial port using Liebert’s contact closure cable. It cannot be  
used with just a contact closure unless the relay is used to switch a  
voltage source. A 5-12 VDC signal for 1.5 seconds or greater is  
required to signal a shutdown. Signals for less than 1.5 seconds will  
be ignored. After Pin 4 receives a shutdown signal for 1.5 seconds,  
the command cannot be canceled.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
3. A battery shutdown signal on Pin 4 will NOT cause an immediate  
shutdown. A shutdown signal will start a 2-minute shutdown timer.  
The timer cannot be stopped. After 2 minutes, the UPS will shut  
down.  
4. If the utility returns during the 2-minute timer countdown, the shut-  
down timer will continue until the end of 2 minutes and the UPS will  
turn OFF. The UPS must remain OFF for at least 10 seconds even if  
AC input power returns before the UPS turns OFF. This serves to  
reset and restart the server.  
Whether the UPS turns back ON when power is restored depends on the  
auto-restart setting: enabled or disabled.  
If the auto-restart is disabled, the UPS will not restart after performing the  
2-minute shutdown delay.  
PINS 5 & 6 - ANY-MODE SHUTDOWN  
1. Pin 6 of the 9-pin communication connector is used for “Any-Mode  
Shutdown” of the UPS output. This control input may be used in spe-  
cial applications to disable the UPS output power—both Inverter and  
Bypass.  
2. The Options tab allows the behavior of the Any-Mode Shutdown fea-  
ture to be modified. When the program opens, or the REFRESH but-  
ton is pressed, the UPS setting is read by the configuration program  
and displayed.  
Auto-Enable Output  
WARNING  
!
Note that when this option is selected and the UPS output  
is disabled using Pin 6, the UPS output can turn on  
automatically and without warning if the Pin 6 connection  
is changed.  
Pin 6 Logic  
WARNING  
!
DO NOT CHANGE THIS OPTION from the factory default  
setting unless you are ready to install a normally-closed  
connection between Pins 5 & 6. This connection must be  
maintained to use the UPS or to use the configuration  
program again, including the ability to change the UPS  
setting back to the default setting using the configuration  
program via a serial communication link.  
If version 1.6 (or later) is used with an earlier GXT 2U model (with an ear-  
lier UPS firmware version), the Any-Mode Shutdown features cannot be  
changed.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
If the configuration program is used with an earlier UPS model (with an  
earlier UPS firmware version) that does not support the modification of  
these settings, the Options tab will display a reminder of the factory  
default settings. These cannot be changed.  
UPS INTELLIGENT COMMUNICATIONS  
The UPStation GXT 2U is equipped with an Intellislot port to provide  
®
advanced communication and monitoring options.  
Liebert’s MultiLink software continually monitors the UPS and can shut  
down your computer or server in the event of an extended power failure.  
MultiLink can also be configured for use without the serial cable when the  
Intellislot SNMP/Web card is installed in the UPS. Additionally, MultiLink  
can be configured to coordinate shutdown across the network with other  
computers running MultiLink when you purchase a MultiLink License Kit.  
For more information about the Intellislot SNMP/Web Card and MultiLink  
dealer or Liebert representative.  
Several option cards are available for use in the Intellislot port of the  
UPStation GXT 2U. The Intellislot SNMP/Web Card provides SNMP and  
Web-based monitoring and control of the UPS across the network.  
The Intellislot MultiPort 4 Card allows you to install MultiLink software on  
four computers and coordinate shutdown in the event of a power failure.  
The Intellislot Relay Card provides dry contact relay outputs for custom-  
wired applications and delivers support for built-in shutdown for AS/400  
systems.  
CAUTION  
!
To maintain safety (SELV) barriers and for electromagnetic  
compatibility, signal cables should be segregated and run  
separate from all other power cables, where applicable.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
CONFIGURATION PROGRAM  
This is a new feature included with the new UPStation GXT 2U line. Sev-  
eral UPS settings that were previously not available or required custom  
manufacturing may now be modified using this program. For most users,  
the factory default settings will be adequate. This manual illustrates the  
features available for modification, as well as the factory default setting.  
NOTE  
The UPS must be turned off—and not powering connected equip-  
ment—before you make any changes to configuration settings.  
While the UPS is in Normal Mode operation, press the OFF  
button once to put the UPS into Bypass Mode.  
Once the UPS is in Bypass Mode operation, press and release  
the OFF button two distinct times (for about a second each  
time) to turn off the UPS.  
GXT 2U CONFIGURATION PROGRAM ABILITIES  
Select one of five output voltages to match voltages found around  
the world.  
Enable/Disable Auto-Restart.  
Select frequency converter operation with a fixed output frequency  
of 50 or 60 Hz.  
Set the Low Battery Warning alarm time from 2 to 30 minutes.  
Enable/Disable the Auto-Battery test.  
Set the Auto-Battery test to 7, 14, 21, or 28 days.  
Select the number of external battery cabinets connected to the  
UPS to adjust the remaining run time calculations reported by Lie-  
bert software products.  
Modify the shutdown setting of DB-9 pin 6 (for information on pin  
assignments, see Communications on page 19).  
NOTE  
This program is compatible with UPS models beginning with  
“GXT2-”, as in “GXT2-2700RT208.” It is not compatible with  
earlier versions of UPStation GXT UPS.  
What You Will Need  
In addition to the GXT 2U UPS, you will need the configuration program dis-  
kette and serial cable (beige or tan, 3-wire: GND, TX, RX; straight through  
2-2, 3-3, 5-5) included in the UPS accessory box. The BLACK ML9P9S  
CONTACT CLOSURE communication cable IS NOT compatible with the  
®
®
®
configuration program. A Windows 95 , 98 , or NT computer—desktop or  
laptop—is also required to set up and run the configuration program.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
MAINTENANCE  
The UPStation GXT 2U requires very little maintenance. The batteries are  
valve-regulated, nonspillable, flame retardant, lead acid, and should be  
kept charged to obtain their designed life. The UPS continuously charges  
the batteries when connected to the utility supply.  
When storing the UPS for any length of time, it is recommended to plug  
the UPS in for at least 24 hours every four to six months to ensure full  
recharge of the batteries.  
The UPStation GXT 2U is designed to allow the user to safely replace the  
internal batteries. Read the safety cautions before proceeding. Contact  
your local dealer or Liebert representative to obtain the appropriate  
replacement battery kit part number and pricing.  
BATTERY REPLACEMENT  
CAUTION  
!
A battery can present a risk of electrical shock and high  
short circuit current. The following precautions should be  
observed before replacing the batteries:  
• Remove rings, watches, or other metal objects.  
• Use a Phillips (crosshead) screwdriver with insulated  
grips.  
• Do not lay tools or other metal objects on top of the batter-  
ies.  
• If the battery replacement kit is damaged in any way or  
shows signs of leakage, contact your local dealer or Liebert  
representative immediately.  
• Do not dispose of batteries in a fire. The batteries may  
explode.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Internal Battery Replacement Procedures  
1. Gently remove the front plastic bezel cover from the UPS.  
2. Loosen and remove the four screws on the front battery door. Lay the  
battery door aside for reassembly.  
3. Gently pull battery wiring out and disconnect the two slotted battery  
connectors.  
4. Grasp the battery pack assembly, and pull it out of the front of the  
UPS.  
5. Unpack the new battery assembly taking care not to destroy the pack-  
ing. Compare new and old battery assemblies to make sure they are  
the same. If so, proceed with Step 6; otherwise STOP and contact  
your local dealer, Liebert representative, or the Liebert Worldwide  
Support Group.  
6. Line up and slide in the new replacement battery pack.  
7. Reconnect the two slotted battery connectors and gently push the  
battery wiring and battery pack assembly back into the UPS.  
8. Reattach the front battery door with the four screws.  
9. Reattach the front plastic bezel cover to the UPS.  
NOTE  
These are hot-swappable replacement batteries. However,  
caution should be exercised because during this procedure the  
load is unprotected from disturbances and power outages.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
TROUBLESHOOTING  
The information below indicates various symptoms a user may encounter  
in the event the UPStation GXT 2U develops a problem. Use this informa-  
tion to determine whether external factors caused the problem and how to  
remedy the situation.  
1. The Fault indicator will illuminate, indicating the UPS detected a  
problem.  
2. An alarm will sound, alerting that the UPS requires attention.  
3. One or more additional load/battery level LED indicators will be illumi-  
nated to provide a diagnostic aid to the operator, as described below:  
This example shows the UPS  
Fault  
on bypass due to output overload.  
E
BYPASS  
D
UPS ON  
C
B
BATTERY  
A
AC  
INPUT  
A
B
C
D
E
Fault  
AC INPUT BATTERY UPS ON BYPASS  
LOAD/BATTERY  
LEVEL INDICATORS  
LED status Diagnosis/Audible alarm  
All LEDs  
A LED  
B LED  
C LED  
D LED  
E LED  
On bypass due to output overload; beep every half-second  
On bypass due to overtemperature condition; beep every 4 sec.  
On bypass due to DC bus overvoltage; beep every 4 sec.  
On bypass due to control power supply failure; beep every 4 sec.  
On bypass due to PFC failure; beep every 4 sec.  
On bypass due to inverter failure; beep every 4 sec.  
A&C LEDs UPS failed battery test; long beep every minute  
UPS shutdown due to command from communication port  
(SNMP); no beep  
C&E LEDs  
Battery LED Internal Battery source not available (continuous horn). Check  
Flashing  
battery connection, completely power down and reboot UPS.  
AC LED  
Flashing  
Line-to-neutral reversal in the AC input power supply or a loss of  
proper grounding; continuous horn and UPS will not start.  
Bypass LED Utility power voltage or frequency is out of tolerance; bypass is  
Flashing unavailable.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Under fault conditions, the Fault indicators will be illuminated indefinitely  
while battery charger is operational, or for a maximum of 5 minutes while  
battery charger is not operational.  
If a problem persists, consult your local dealer, Liebert representative or  
contact the Liebert Worldwide Support Group. Please have the UPS  
model number and serial number available at the time of your inquiry.  
Troubleshooting Guide  
Problem  
Cause  
Solution  
UPS fails to start  
when the ON  
button is pressed.  
UPS is short circuited or  
overloaded.  
Ensure UPS is OFF.  
Disconnect all loads and  
ensure nothing is lodged in  
output receptacles. Ensure  
loads are not defective or  
shorted internally.  
Battery indicator  
LED is illuminated.  
UPS not plugged in.  
UPS is operating from  
battery mode, make certain  
UPS is securely plugged  
into the wall receptacle.  
UPS input protection fuse  
has blown/opened.  
UPS is operating from  
battery mode. Save data  
and close applications.  
Replace UPS input fuse,  
then restart UPS.  
Utility voltage out of UPS  
input range.  
UPS is operating from  
battery mode. Save data  
and close applications.  
Ensure utility supply voltage  
is within acceptable limits  
for UPS.  
UPS has reduced Batteries are not fully  
Keep UPS plugged in  
continuously at least 24  
hours to recharge batteries.  
battery time.  
charged.  
UPS is overloaded.  
Check load level display  
and reduce the load on the  
UPS.  
Batteries may not be able to Replace batteries. Contact  
hold a full charge due to  
age.  
your local dealer, Liebert  
representative or the Liebert  
Worldwide Support Group  
for replacement battery kit.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide (Continued)  
Problem  
Cause  
Solution  
Fault and Bypass UPS overloaded or load  
Check load level display  
and remove non-essential  
loads. Recalculate the load  
and reduce number of loads  
connected to UPS. Check  
load equipment for faults.  
indicator LEDs  
and all load level  
LEDs are  
equipment is faulty.  
illuminated.  
Fault and Bypass UPS internal fan has a  
Ensure UPS is not  
overloaded, ventilation  
openings not blocked, or  
indicator LEDs  
and diagnostic  
LED A are  
problem or UPS shutdown  
due to temperature  
condition. Load is on bypass room ambient temperature  
illuminated.  
power.  
is not excessive. Wait 30  
minutes to allow UPS to  
cool, then restart UPS. If  
UPS does not restart,  
contact your local dealer,  
Liebert representative or the  
Liebert Worldwide Support  
Group.  
Fault and Bypass UPS internal DC bus  
UPS requires service.  
Contact your local dealer,  
Liebert representative or the  
Liebert Worldwide Support  
Group.  
indicator LEDs  
and diagnostic  
LED B are  
overvoltage.  
illuminated.  
Fault and Bypass UPS control power supply  
UPS requires service.  
Contact your local dealer,  
Liebert representative or the  
Liebert Worldwide Support  
Group.  
indicator LEDs  
and diagnostic  
LED C are  
fault.  
illuminated.  
Fault and Bypass UPS PFC (Power Factor  
UPS requires service.  
Contact your local dealer,  
Liebert representative or the  
Liebert Worldwide Support  
Group.  
indicator LEDs  
and diagnostic  
LED D are  
Correction Circuit) fault.  
illuminated.  
Fault and Bypass UPS inverter fault.  
indicator LEDs  
and diagnostic  
LED E are  
illuminated.  
UPS requires service.  
Contact your local dealer,  
Liebert Representative or  
the Liebert Worldwide  
Support Group.  
Fault indicator  
LED and  
diagnostic LED A  
and C are  
UPS failed the battery test.  
Replace batteries. Contact  
your local dealer, Liebert  
representative or the Liebert  
Worldwide Support Group.  
illuminated.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting Guide (Continued)  
Problem  
Cause  
Solution  
Fault and Bypass UPS shutdown due to a  
Your UPS has received a  
signal or command from the  
attached computer. If this  
was inadvertent, ensure the  
communication cable used  
is correct for your system.  
For assistance, contact your  
local dealer, Liebert  
indicator LEDs  
and diagnostic  
LED C and E are  
illuminated.  
command from the  
communications port(s).  
representative or the Liebert  
Worldwide Support Group.  
AC LED is  
flashing.  
UPS detected a line-to-  
neutral reversal or a loss of electrician to verify site  
proper grounding;  
Contact a qualified  
wiring.  
continuous horn and UPS  
will not start.This is active  
only when power is first  
applied to the input. Once  
the UPS is running, the AC  
LED will not start flashing,  
even if the input wiring is  
changed.  
Battery LED is  
flashing.  
Battery source is not  
available; continuous horn.  
Check battery connections,  
completely power down and  
restart UPS.  
NOTE: If the battery circuit  
opens while the UPS is  
running, it will be detected  
when the next battery test is  
performed.  
Bypass LED is  
flashing.  
Bypass voltage is present,  
but is disabled for use  
because the voltage or  
frequency is outside  
acceptable limits.  
The AC input powers the  
PFC input and serves as the  
bypass source. If the AC is  
present but the voltage or  
frequency exceeds the  
acceptable range for safe  
operation with a load, the  
bypass will be disabled and  
this LED will flash, indicating  
that the bypass is  
unavailable.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Alarm Conditions  
Condition  
Battery Mode  
Alarm  
One short beep every 10 seconds;  
(utility failure)  
more than 2 minutes of run time remaining  
Low Battery  
Two short beeps every 5 seconds;  
less than 2 minutes of run time remaining  
Output Overload  
(bypass)  
One short beep every half second  
A one-second beep every 4 seconds  
A one-second beep every 4 seconds  
A one-second beep every 4 seconds  
Overtemperature  
(bypass)  
DC Bus Overvoltage  
(bypass)  
Control Power Supply  
Failure (bypass)  
PFC Failure (bypass)  
Inverter Failure  
A one-second beep every 4 seconds  
A one-second beep every 4 seconds  
A 2-second beep every minute  
Battery Test Failure  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPECIFICATIONS  
Model Number  
GXT2-2700RT208  
2700VA/1890W  
Model Rating  
DIMENSIONS: in. (mm)  
Unit - W x D x H: in. (mm)  
3.5 x 24.2 x 17 (87 x 618 x 430)  
Shipping - W x D x H: in. (mm) 10.5 x 27.2 x 23 (268 x 692 x 585)  
WEIGHT lbs (kg)  
Unit: lbs (kg)  
75.2 (34.1)  
84.9 (38.5)  
Shipping: lbs (kg)  
INPUT AC PARAMETERS  
Voltage Range (typical)  
100% - 90% loading  
90% - 70% loading  
70% - 30% loading  
30% - 0% loading  
208 VAC nominal; variable based on output load  
176 VAC/280 VAC  
159 VAC/280 VAC  
139 VAC/280 VAC  
119 VAC/280 VAC  
Frequency  
40 - 70 Hz; Auto Sensing  
10 ft. attached w/ NEMA L6-20 plug  
Input Power Cord  
OUTPUT AC PARAMETERS  
Output Receptacles  
(2) NEMA L6-15R  
(1) NEMA L6-20R  
Voltage  
200/208/220/230/240 (user configurable) VAC; ±3%  
Frequency  
50 Hz or 60 Hz  
Waveform  
Sinewave  
Main Mode Overload  
200% for 8 cycles; 130% for 10 seconds with transfer  
to bypass  
BATTERY PARAMETERS  
Type  
Valve-regulated, nonspillable, flame retardant, lead acid  
6 x 12V x 9.0 AH  
Qty x V x Rating  
Battery Mfg/Part #  
Panasonic/ UP-VW1245P1  
Yuasa/ REW 45-12 FR  
Back-Up Time  
Recharge Time  
See Battery Run Times charts  
5 Hours to 95% capacity after full discharge into 100%  
load (Internal Batteries Only)  
ENVIRONMENTAL  
Operating Temp  
Storage Temp  
+32°F to +104°F (0°C to +40°C)  
+5°F to +122°F (-15°C to +50°C)  
0% to 95%, non-condensing  
Relative Humidity  
Operating Elevation  
Up to 10,000 ft. (3000 m) at 104°F (40°C)  
without derating  
Storage Elevation  
Audible Noise  
50,000 ft. (15,000 m) maximum  
<55 dBA, at 1 meter from the rear  
<50 dBA, at 1 meter from the front or sides  
AGENCY  
Safety  
UL 1778, c-UL Listed (Suitable for computer room  
applications)  
RFI/EMI  
FCC Part 15, Subpart B, Class A  
IEEE 587 Category A & B  
ISTA Procedure 1A  
Surge Immunity  
Transportation  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
BATTERY CABINET SPECIFICATIONS  
Model Number  
GXT2-72VBATT  
Used w/ UPS Model  
DIMENSIONS in (mm)  
Unit - W x D x H in. (mm)  
GXT2-2700RT208  
3.5 x 24.2 x 17 (87 x 618 x 430)  
Shipping - W x D x H in. (mm) 10.5 x 27.2 x 23 (268 x 692 x 585)  
WEIGHT lbs (kg)  
Unit: lbs (kg)  
93.6 (42.5)  
Shipping: lbs (kg)  
BATTERY PARAMETERS  
Type  
102.5 (46.5)  
Valve-regulated, nonspillable, flame retardant, lead acid  
2 x 6 x 12V x 9.0 AH  
Qty x V x Rating  
Battery Mfg/Part #  
Panasonic/UP-VW1245P1  
Yuasa/REW 45-12 FR  
Back-Up Time  
ENVIRONMENTAL  
Operating Temp  
Storage Temp  
See Battery Run Times charts  
+32°F to +104°F (0°C to +40°C)  
+5°F to +122°F (-15°C to +50°C)  
0% to 95%, non-condensing  
Relative Humidity  
Operating Elevation  
Up to 10,000 ft. (3000 m) at 104°F (40°C)  
without derating  
Storage Elevation  
AGENCY  
50,000 ft. (15,000 m) maximum  
Safety  
UL 1778, c-UL Listed (Suitable for computer room  
applications)  
RFI/EMI  
FCC Part 15, Subpart B, Class A  
ISTA Procedure 1A  
Transportation  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
BATTERY RUN TIMES  
Load %  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
Estimated Time  
91  
46  
30  
21  
16  
11  
9
8
7
5
364  
184  
120  
84  
64  
44  
36  
32  
Internal Battery  
(minutes)  
Internal Battery  
+ 1 External Battery  
Cabinet (minutes)  
28  
20  
728  
368  
240  
168  
128  
88  
72  
64  
56  
40  
1092  
552  
360  
252  
192  
132  
108  
96  
Internal Battery  
+ 2 External Battery  
Cabinets (minutes)  
Internal Battery  
+ 3 External Battery  
Cabinets (minutes)  
84  
60  
1456  
736  
480  
336  
256  
176  
144  
128  
112  
80  
Internal Battery  
+ 4 External Battery  
Cabinets (minutes)  
Note: Approximate discharge times are in minutes and at 77°F (25°C) with a 100% resistive load.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
PRODUCT WARRANTY REGISTRATION  
To register for warranty protection:  
Visit the Quick Links section of our Web site at:  
Click on Product Warranty Registration and fill in the form.  
If you have any questions, please contact us at:  
US: 800-222-5877  
Outside the US: 614-841-6755  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
POWER AVAILABILITY  
UPStation GXT 2U™  
USER MANUAL  
Technical Support/Service  
The Company Behind the Products  
Web Site  
Monitoring  
800-222-5877  
With over a million installations around the globe,  
Liebert is the world leader in computer protection  
systems. Since its founding in 1965, Liebert has  
Outside the US: 614-841-6755  
developed  
a
complete range of support and  
protection systems for sensitive electronics:  
Single-Phase UPS  
800-222-5877  
Environmental systems—close-control air  
conditioning from 1 to 60 tons  
Outside the US: 614-841-6755  
Power conditioning and UPS with power  
ranges from 300 VA to more than 1000 kVA  
Integrated systems that provide both  
environmental and power protection in  
single, flexible package  
Three-Phase UPS  
800-543-2378  
Environmental Systems  
a
800-543-2778  
Outside the United States  
Monitoring and control—from systems of any  
size or location, on-site or remote  
Service and support through more than 100  
service centers around the world and a 24/7  
Customer Response Center  
614-888-0246  
Locations  
United States  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
While every precaution has been taken to ensure  
the accuracy and completeness of this literature,  
Liebert Corporation assumes no responsibility and  
disclaims all liability for damages resulting from use  
of this information or for any errors or omissions.  
Italy  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD)  
+39 049 9719 111  
Fax: +39 049 5841 257  
Asia  
23F, Allied Kajima Bldg.  
138 Gloucester Road  
Wanchai  
© 2003 Liebert Corporation  
All rights reserved throughout the world.  
Specifications subject to change without notice.  
Hong Kong  
+852 2 572 2201  
Fax: +852 2 831 0114  
® Liebert and the Liebert logo are registered  
trademarks of Liebert Corporation. All names  
referred to are trademarks or registered  
trademarks of their respective owners.  
SL-23154 (6/03) Rev. 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  

KWC Plumbing Product K28H12000099 User Manual
Kyocera All in One Printer Data Security Kit B For Copier User Manual
Lasko Fan 2530 User Manual
Learning Resources Building Set LER 1909 User Manual
Lincoln Electric Welding System AC 1500 User Manual
LST Smoke Alarm SIM016 3 User Manual
Lux Products Thermostat PSPLV512 User Manual
Makita Cordless Saw XSH01X User Manual
Masterbuilt Charcoal Grill 20040311 User Manual
Master Lock Portable Generator HWI3000 MGH3000 MGH4000C MGH4000CI MGH5000C MGH5000CI MGH5000CIE MGH6000C MGH6000CI MGH7000C MGH7000CI MGH10000 User Manual