POWER AVAILABILITY
USER MANUAL
UPStation GXT 2U™
2700VA
208V
Download from Www.Somanuals.com. All Manuals Search And Download.
Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters . . . 5
Rectifier/Power Factor Correction (PFC) Circuit . . . . . . . . . . . . . . . . . . 5
Inverter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
DC to DC Converter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Dynamic Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
GXT 2U (Rear View) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Rack-Mount UPS Conversion and Installation. . . . . . . . . . . . . . . . . . . . 9
ON/Alarm Silence/Manual Battery Test Button . . . . . . . . . . . . . . . . . . 14
Load/Battery Level Indicators (4 Green, 1 Amber) . . . . . . . . . . . . . . . 15
AC Input Indicator LED (Green). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Output Voltage Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Normal Mode Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Bypass Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Battery Mode Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Battery Recharge Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
i
Download from Www.Somanuals.com. All Manuals Search And Download.
COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Communications Interface Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Auto-Enable Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Pin 6 Logic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
GXT 2U Configuration Program Abilities . . . . . . . . . . . . . . . . . . . . . . . 22
What You Will Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
BATTERY CABINET SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 31
BATTERY RUN TIMES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Product Warranty Registration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
ii
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT SAFETY INSTRUCTIONS
WARNING
!
Opening or removing the cover may expose you to lethal
voltages within this unit even when it is apparently not
operating and the input wiring is disconnected from the
electrical source. Observe all cautions and warnings in this
manual. Failure to do so MAY result in serious injury or
death. Refer all UPS and battery service to qualified service
personnel. Do not attempt to service this product yourself.
Never work alone.
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions. Read all safety, instal-
lation, and operating instructions before operating the Uninterruptible
Power System (UPS). Adhere to all warnings on the unit and in this man-
ual. Follow all operating and user instructions. Individuals without previ-
ous training can install and operate this equipment.
It is not intended for use with life support and other designated “critical”
devices. Maximum load must not exceed that shown on the UPS rating
label. The UPS is designed for data processing equipment. If uncertain,
consult your local dealer or Liebert representative.
This UPS is designed for use on a properly grounded (earthed), 50Hz or
60Hz, 208V supply (programmable for 200, 208, 220, 230, and 240VAC
output). Installation instructions and warning notices are located in this
manual.
ELECTROMAGNETIC COMPATIBILITY—The GXT 2U™ Series com-
plies with the limits for a CLASS A DIGITAL DEVICE, PURSUANT TO
Part 15 of FCC rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) this device
must accept any interference received, including interference that may
cause undesired operation. Operating this device in a residential area is
likely to cause harmful interference that users must correct at their own
expense.
Operate the UPS in an indoor environment only in an ambient tempera-
ture range of 32°F to +104°F (0°C to +40°C). Install it in a clean environ-
ment, free from moisture, flammable liquids, gases and corrosive
substances.
1
Download from Www.Somanuals.com. All Manuals Search And Download.
This UPS contains no user serviceable parts except the internal battery
pack. The UPS ON/Standby push buttons do not electrically isolate inter-
nal parts. Under no circumstances attempt to gain access internally other
than to replace the batteries due to risk of electric shock or burn. Do not
continue to use the UPS if the front panel indications are not in accor-
dance with these operating instructions or if the UPS performance alters
in use. Refer all faults to your local dealer, Liebert representative or the
Liebert Worldwide Support Group.
Servicing of batteries should be performed or supervised by personnel
knowledgeable of batteries and the required precautions. Keep unautho-
rized personnel away from the batteries. PROPER DISPOSAL OF BAT-
TERIES IS REQUIRED. REFER TO YOUR LOCAL LAWS AND
REGULATIONS FOR BATTERY DISPOSAL REQUIREMENTS.
Never block or insert any object into the ventilation holes or other open-
ings of the UPS.
DO NOT CONNECT equipment that could overload the UPS or demand
half-wave rectification from the UPS, for example: electric drills, vacuum
cleaners, laser printers or hairdryers.
Storing magnetic media on top of the UPS may result in data loss or cor-
ruption.
Turn the UPS off and isolate the UPS before cleaning; use only a soft
cloth, never liquid or aerosol cleaners. Keep the front and rear vents free
of dust accumulation that could restrict airflow.
When replacing batteries, replace with the same Liebert authorized
replacement battery kits.
CAUTION
!
Do not dispose of battery or batteries in a fire. The battery
may explode.
Do not open or mutilate the battery or batteries. Released
electrolyte is harmful to skin and eyes. It may be toxic.
CAUTION
!
A battery can present a risk of electrical shock and high
short circuit current. The following precautions should be
observed when working on batteries:
• Remove watches, rings, and other metal objects.
• Use tools with insulated handles.
2
Download from Www.Somanuals.com. All Manuals Search And Download.
GLOSSARY OF SYMBOLS
•
Risk of electrical shock
Indicates caution followed by important instructions
AC input
AC output
Requests the user to consult the manual
i
Indicates the unit contains a valve-regulated lead acid
battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
ON
Standby
3
Download from Www.Somanuals.com. All Manuals Search And Download.
INTRODUCTION
Congratulations on your choice of the Liebert UPStation GXT 2U™
Uninterruptible Power System (UPS). It provides conditioned power to
microcomputers and other sensitive electronic equipment.
Upon generation, AC power is clean and stable. However, during trans-
mission and distribution it may be subject to voltage sags, spikes, or com-
plete power failure that may interrupt computer operations, cause data
loss, or even damage equipment. The UPStation GXT 2U protects equip-
ment from these disturbances.
The UPStation GXT 2U is rated for 2700 VA, 1890 watts. Complete model
specifications appear at the end of this manual.
The UPStation GXT 2U is a compact, “on-line” UPS. An on-line UPS con-
tinuously conditions and regulates its output voltage, whether utility power
is present or not. It supplies connected equipment with clean sinewave
power. Sensitive electronic equipment operates best from sinewave
power.
For ease of use, the UPStation GXT 2U features a light-emitting diode
(LED) display to indicate either load percentage or battery capacity
depending upon the mode of operation. It also provides self-diagnostic
tests, a combination ON/Alarm Silence/Manual Battery Test button, a
Standby button, user configurable program, and two levels of alarms
when the unit is operating on battery.
The UPStation GXT 2U has an interface port for communication between
the UPS and a network server or other computer systems. This port pro-
vides detailed operating information including voltages, currents, and
alarm status to the host system when used in conjunction with Liebert
MultiLink™ software. MultiLink software can also remotely control UPS
operation.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
MAJOR COMPONENTS
Input
Output
Dynamic
Bypass
TVSS &
EMI/RFI
Filters
Rectifier
/PFC
Inverter
L1
L1
DC to DC
Converter
Battery
Charger
Battery
L2
G
L2
G
TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI
FILTERS
These UPS components provide surge protection and filter both electro-
magnetic interference (EMI) and radio frequency interference (RFI). They
minimize any surges or interference present in the utility line and keep the
sensitive equipment protected.
RECTIFIER/POWER FACTOR CORRECTION (PFC) CIRCUIT
In normal operation, the rectifier/power factor correction (PFC) circuit con-
verts utility AC power to regulated DC power for use by the inverter while
ensuring that the waveshape of the input current used by the UPS is near
ideal. Extracting this sinewave input current achieves two objectives:
•
•
The utility power is used as efficiently as possible by the UPS.
The amount of distortion reflected on the utility is reduced.
This results in cleaner power being available to other devices in the build-
ing not being protected by the UPStation GXT 2U.
INVERTER
In normal operation, the inverter utilizes the DC output of the power factor
correction circuit and inverts it into precise, regulated sinewave AC power.
Upon a utility power failure, the inverter receives its required energy from
the battery through the DC to DC converter. In both modes of operation,
the UPS inverter is on-line and continuously generating clean, precise,
regulated AC output power.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
BATTERY CHARGER
The battery charger utilizes energy from the utility power and precisely
regulates it to continuously “float charge” the batteries. The batteries are
being charged whenever the UPStation GXT 2U is plugged in, even when
the UPS is not turned on.
DC TO DC CONVERTER
The DC to DC converter utilizes energy from the battery system and
raises the DC voltage to the optimum operating voltage for the inverter.
This allows the inverter to operate continuously at its optimum efficiency
and voltage, thus increasing reliability.
BATTERY
The UPStation GXT 2U utilizes valve-regulated, nonspillable, flame retar-
dant, lead acid batteries. To maintain battery design life, operate the UPS
in an ambient temperature of 68°F to 77°F (20°C to 25°C). Optional exter-
nal battery cabinets are available to extend battery run times.
DYNAMIC BYPASS
The UPStation GXT 2U provides an alternate path for utility power to the
connected load in the unlikely event of a UPS malfunction. Should the
UPS have an overload, overtemperature, or UPS failure condition, the
UPS automatically transfers the connected load to bypass. Bypass opera-
tion is indicated by an audible alarm and illuminated amber Bypass LED
(other LEDs may be illuminated to indicate the diagnosed problem). To
manually transfer the connected load from the inverter to bypass, press
the Standby button once.
NOTE
The bypass power path does NOT protect the connected
equipment from disturbances on the utility supply.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLATION
PREPARATION
1. Visually inspect the UPS for freight damage. Report damage to the
carrier and your local dealer or Liebert representative.
CAUTION
!
The UPS is heavy (see Specifications section). Take proper
precautions when lifting or moving it.
2. Decide where to place the GXT 2U. Install the UPS indoors in a con-
trolled environment, where it cannot be accidentally turned off. Place
it in an area of unrestricted airflow around the unit, away from water,
flammable liquids, gases, corrosives, and conductive contaminants.
Maintain a minimum clearance of 4 inches (100mm) in the front and
rear of the UPS. Maintain an ambient temperature range of 32°F to
104°F (0°C to 40°C).
NOTE
UPS operation in temperatures above 77°F (25°C) reduces
battery life.
3. The GXT 2U may be installed in either a tower configuration or in a
rack, depending on available space and use considerations. Deter-
mine the type of installation and follow the appropriate instructions in
either Tower UPS Installation or Rack-Mount UPS Conversion
and Installation.
TOWER UPS INSTALLATION
When using the GXT 2U in a tower configuration, use the included sup-
port base (shown below, left) to stabilize the UPS.
If any battery cabinets are added, they will include spacers to accommo-
date the additional cabinets (shown below, right).
Support base
Spacers added to support
base to accommodate
additional battery cabinets
8
Download from Www.Somanuals.com. All Manuals Search And Download.
RACK-MOUNT UPS CONVERSION AND INSTALLATION
NOTE
When rack mounted, the UPS must be supported by a shelf,
brackets or slide rails on each side. The rack mount handles
WILL NOT support the weight of the UPS. They are used to
move the UPS into and out of the rack.
1. For slide rail installations, first remove the top/side fin. Slide the
top/side fin forward, then lift it up to remove. If desired, install the
optional rack mount handles that were shipped with the UPS.
U
PStation
G
XT
–
+
AC
IN
PU
T
BA
TT
ER
Y
UP
S
ON
BY
PA
SS
Optional rack mount handles
Securing hardware and slide rails are sold separately. Contact your
local dealer or Liebert representative for these additional options and
any assistance needed.
2. Unpack the two (2) rack-
Return
mounting bracket assemblies
and mounting hardware from
the rack-mounting kit
flanges
Retaining
latches
(P/N: RMKIT18-32). Bracket
assemblies are interchange-
able between left-hand or
right-hand. Remove inner
member of each bracket
assembly as shown at right by
extending it to its outermost
position, depressing the
retaining latch and then pulling
inner member from bracket
assembly.
Rear
members
Front
members
Inner
members
9
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Determine the height position inside the rack enclosure where you
want to mount the UPS or battery cabinet.
CAUTION
!
Reduce risk of tipping the rack enclosure by placing UPS or
battery cabinet in the lowest possible rack position.
Install rear member of each
bracket assembly into rack
enclosure with two (2) M5
screws provided in this kit.
(See figure at right.) Return
flanges on bracket assembly
fit to the inside of rack mount-
ing rails. Insert screws loosely
(finger-tight) into top and bot-
tom holes of return flange on
rear member. Extend bracket
assembly by sliding front
M5 screws
Front rack
mounting rails
Rear rack
mounting
rails
M5 screws
member forward until it touches the front rack mounting rail. Insert
two (2) M5 screws loosely (finger-tight) into top and bottom holes of
return flange on each front member. Make sure bracket assemblies
are at the same mounting height on all four (4) rack mounting rails.
4. Locate eight (8) M4 screws
and eight (8) M4 nuts from
hardware pack in this kit.
M4 nuts
M4
screws
Each nut has a locking, nylon
insert that begins gripping the
screw when it is halfway tight.
Make sure to tighten nut and
screw completely to assure
locking action. Fasten rear
member and front member
together using four (4) screws
and four (4) nuts per bracket
assembly as shown in the fig-
ures at right. For maximum
support, locate fasteners for
each bracket assembly as far
apart as possible, depending
on rack depth, while still join-
ing both members (See fig-
ures at right). Check
18" rack
depth
M4 nuts
M4
M4 nuts
screws
32" rack
depth
M4 nuts
alignment of bracket assemblies and TIGHTEN ALL SCREWS
FROM STEPS 3 and 4.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Prepare the UPS or battery cab-
inet (the “equipment”) for rack
mounting by following instruc-
tions in the equipment’s user
manual. The equipment may
require additional parts to be
added or parts to be removed
for rack mounting. After it is pre-
pared, lay equipment in rack-
mounting position. Fasten inner
members from Step 2 to the
equipment on both sides as
shown in the figure at right with
(8) M4 screws provided in this
kit. Make sure retaining latch is
near the rear of the equipment
as shown in the figure at right.
M4
screws
Retaining
latch
UPS or battery
cabinet
Front
M4
screws
6. Open grease packet pro-
vided in this kit. Apply a 1"
long bead of grease four
Apply
grease
UPS or
battery
cabinet
(4) places inside the bot-
tom, curved tracks of front
members as shown at
right. The grease will allow
the equipment to slide into
the bracket assemblies
more easily.
Apply
grease
(inside)
CAUTION
!
Lifting equipment into rack may be a two-person job,
depending on weight of equipment. See equipment’s user
manual.
7. Insert the equipment, with inner members attached from Step 5, into
bracket assemblies by inserting top and bottom edges of inner mem-
bers into the top and bottom, curved tracks of front members and slid-
ing the equipment into rack (see figure in Step 6). Ends of inner
members are tapered to allow rear of the equipment to be angled
upward before insertion, if space allows.
Then the rear, bottom edges of inner
members can be placed into front edge
of bottom tracks, and the front of the
equipment can be tipped up into hori-
zontal position to insert the top edges of
inner members before sliding the equip-
ment into rack (see figure at right). The equipment should move
smoothly into bracket assemblies. If not, recheck alignment of front
and rear members from Steps 3 and 4.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
8. Secure front of the equipment to rack mounting rails to prevent the
equipment from sliding out of position. If securing holes are provided
on front of the equipment that align with the center holes on return
flange of front members, you can use the four (4) extra M5 screws
provided in this kit to secure the equipment. Otherwise, the equip-
ment should be secured to front of rack mounting rails with four (4)
customer-supplied fasteners.
9. To orient the display for horizon-
Horizontal overlay
for rack UPS
Vertical
overlay
for
tower
UPS
tal viewing, remove the front
plastic bezel by pulling forward
evenly on both sides. The unit
has two front panel overlays.
Remove the outer overlay (used
for tower installation). This
reveals a horizontally oriented
front panel overlay for rack
mounting. Snap the front bezel
back into place.
BPYAS
USPON
10. Once the UPS is installed in the
rack, the load may be con-
nected. Ensure the load equip-
ment is turned off; plug all loads
into the output receptacles on
the rear of the UPS.
BPYAS
+
–
BTAERY
USPON
USPationGXT
ACINPUT
+
–
BTAERY
USPationGXT
ACINPUT
11. Plug the UPS into a dedicated
wall receptacle properly pro-
tected by a circuit breaker or
fuse in accordance with national
and local electrical codes. Use a 20 amp rated device for the 2700VA,
208V unit. The wall receptacle must be grounded.
12. Turn ON the UPS by pressing the ON button; then turn on the con-
nected load equipment. The UPS is now providing conditioned power
to your equipment.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
EXTERNAL BATTERY CABINET INSTALLATION
to provide additional battery run time. External battery cabinets are
designed to be placed all on one side of the UPS or stacked beneath the
UPS. There is no limit to the number of external battery cabinets that can
be used but each cabinet will increase the battery recharge time.
CAUTION
!
The external battery cabinet(s) are heavy (see
Specifications section). External battery cabinets can be
used in rack-mount or tower configuration. Take proper
precautions when lifting them.
1. Visually inspect the external battery cabinet for freight damage. Report
damage to the carrier and your local dealer or Liebert representative.
2. For slide rail installations, first remove the top/side fin. Top/side fin
slides forward and then lift up to remove. Optional rack-mount han-
dles are shipped with the external battery cabinet and may be
installed at this time if desired.
3. Securing hardware and slide rails are sold separately. Please contact
your local dealer or Liebert representative for these additional options
and any assistance needed. Fasten the slides into position with the
screws per the instructions included with the slide rails.
4. Use the enclosed support bases for the
tower option to prevent tip-over. One
additional set of support base extensions
ships with each external battery cabinet.
5. Connect the supplied external battery cab-
inet cable to the rear of the external bat-
tery cabinet, then to the rear of the UPS.
6. Turn ON the battery breaker on the
rear of the external battery cabinet.
7. The UPS is now equipped with addi-
tional backup battery run time. For
approximate battery run times, refer to
manual.
NOTE
You must use the included Configuration Program to specify
the number of external battery cabinets connected to the UPS.
For more information, see Configuration Program on
page 22.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
CONTROLS AND INDICATORS
All LEDs illuminated
for illustrative purposes only.
ON/Alarm Silence/Manual Battery Test Button
This button controls output power to connected load(s) and has
three functions:
• ON
• Alarm Silence
• Manual Battery Test
ON - Pressing this button will start up the UPS in order to provide condi-
tioned and protected power.
Alarm Silence - To silence alarms, press this button for at least one sec-
ond. After the alarm is silenced, the UPStation GXT 2U will reactivate the
alarm system to alert of additional problems.
NOTE
The LOW BATTERY and BYPASS reminder alarms
CANNOT be silenced.
Manual Battery Test - To initiate a manual battery test, press the ON but-
ton for at least one second while operating from utility power with no
alarm conditions present.
• If only three of the five Battery LEDs illuminate, allow the UPS to
recharge the batteries for 24 hours.
• After 24 hours, retest the batteries.
• After the batteries have been retested, if only three of the five Battery
LEDs illuminate, contact your local dealer, Liebert representative or
Liebert Worldwide Support Group.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Standby/Manual Bypass Button
This button controls output power to connected load(s) and has
dual functions: Standby and Manual Bypass.
CAUTION
!
While the UPS is in Normal Mode operation, pressing the
Standby/ Manual Bypass button once will put the UPS into
Bypass Mode.
Once the UPS is in Bypass Mode operation, press the
Standby/ Manual Bypass button two distinct times (for about
one second each time) to turn off the UPS. Perform all
necessary shutdown procedures on connected loads before
turning off the UPS.
Load/Battery Level Indicators (4 Green, 1 Amber)
The load/battery level indicators have dual functions. During normal mode
operation LED indicators display the approximate electrical load placed
upon the UPS; and during battery mode operation LED indicators display
approximate battery capacity.
The UPStation GXT 2U is equipped with automatic and remote battery
test features. The automatic test occurs every 14 days (this option is user
configurable) if utility has not been interrupted. Should the battery fail this
will illuminate and an alarm will sound (refer to Troubleshooting section).
The remote test feature functions with MultiLink 3 software and can
remotely initiate the battery test.
Fault Indicator LED (Red)
The Fault indicator LED is illuminated if the UPS has detected a problem.
Also, one or more of the load/battery level indicators may be illuminated
(refer to Troubleshooting section).
Bypass Indicator LED (Amber)
The Bypass indicator LED is illuminated when the UPS is operating from
bypass power. An alarm will sound indicating the UPS detected a prob-
lem, or the manual bypass function has been activated.
UPS ON Indicator LED (Green)
The UPS ON indicator LED is illuminated when the UPS inverter is oper-
ating and supplying power to your connected loads.
Battery Indicator LED (Amber)
The Battery indicator LED is illuminated when the UPS is operating on
battery.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
AC Input Indicator LED (Green)
The AC Input indicator LED is illuminated when utility power is available
and within the input specifications.
Output Voltage Selection
The Output Voltage is user configurable and is designed to allow select-
ing or changing the desired output voltage to match the utility via the
GXT 2U Configuration Program provided with the UPS. The settings to
choose from are 200, 208, 220, 230, and 240 VAC output. The factory
default setting is 208 VAC.
CAUTION
!
Never change the voltage settings while the UPS is ON and
powering connected loads.
NOTE
Setting output voltage to 200 VAC will cause the UPS unit to
be derated to 2400 VA, 1680 watts.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING INSTRUCTIONS
NORMAL MODE OPERATION
During normal operation, util-
ity power provides energy to
the UPS. The filters, power
factor correction circuit and the
inverter process this power to
provide computer grade power
to connected loads. The UPS
maintains the batteries in a
fully charged state.
AC INPUT BATTERY UPS ON BYPASS
Normal Mode Operation at 26-50%
The four green load level LEDs indicate an approximate level of load in
25% increments. If the UPS becomes loaded beyond full rating, the fifth
(amber) LED indicator will illuminate and the UPS will sound an audible
alarm. The display template indicates the percentage of load (26-50% of
load shown in the example above) on the UPS output.
BYPASS MODE OPERATION
Bypass mode occurs when the
OFF button is pressed once
while the UPS is in Normal
Mode. During bypass opera-
tion, utility power provides
energy to the UPS. The utility
power bypasses the inverter
AC INPUT BATTERY UPS ON BYPASS
and provides power for the
connected load.
Bypass Mode Operation at 26-50%
The four green load level LEDs indicate an approximate level of load in
25% increments. If the UPS becomes loaded beyond full rating, the fifth
(amber) LED indicator will illuminate and the UPS will sound an audible
alarm. The display template indicates the percentage of load (26-50% of
load shown in the example above) on the UPS output.
CAUTION
!
Turning OFF the UPS while in bypass mode will result in
loss of output power.
BATTERY MODE OPERATION
Battery mode occurs in event
of an extreme input voltage
condition or complete utility
failure. The battery system
supplies power through the
DC to DC converter to the
AC INPUT BATTERY UPS ON BYPASS
inverter to generate power
for the connected load.
Battery Mode Operation at 80-61%
17
Download from Www.Somanuals.com. All Manuals Search And Download.
During battery mode an alarm sounds every 10 seconds. This will change
to two beeps every 5 seconds when the battery runs low (approximately
2 minutes remaining, but this is user configurable). The AC Input LED will
extinguish, and the Battery LED will illuminate to warn that a utility prob-
lem has occurred. Each battery level indicator represents a 20% capacity
level. As capacity decreases, fewer indicators remain illuminated. Refer to
Troubleshooting section.
For approximate battery run times, refer to the Battery Run Times charts
in this manual. These times are approximates based on resistive load and
an ambient temperature of 77°F (25°C). To increase this time, turn off
non-essential pieces of equipment (such as idle computers and monitors)
or add the optional external battery cabinet.
CAUTION
!
Turning OFF the UPS while in battery mode will result in
loss of output power.
BATTERY RECHARGE MODE
Once utility power is restored, the UPS resumes normal operation. At this
time, the Battery Charger begins recharging.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
COMMUNICATIONS
COMMUNICATIONS INTERFACE PORT
The UPStation GXT 2U UPS has a standard DB-9 serial port female con-
nector located on the rear of the UPS unit. Several signals are provided
on this port and are assigned as follows:
Pin
Assignment Description
1
2
3
4
5
6
7
8
9
Low Battery (open collector)
UPS TxD (typical RS-232 levels)
UPS RxD (typical RS-232 levels)
Remote Shutdown (5-12VDC, 10-24 mA max); battery operation
Common
Remote Shutdown (short to pin 5); all modes of operation
Low Battery (open emitter)
Utility Fail (open emitter)
Utility Fail (open collector)
Pin Assignment
Collector to Emitter*
Open
Collector
6
7
8
9
(+)
(-)
330 Ohms
Open
Emitter
1
2
3
4
5
* Maximum voltage and current on pins 1, 7, 8, and 9 is 60VDC; 10.0 mA.
PINS 4 & 5 - REMOTE SHUTDOWN ON BATTERY
1. This pin is functional only when the UPS is in battery mode. If the
UPS is being powered by the utility, Pin 4 will ignore any signal on this
pin.
2. Pin 4 requires a 5-12 VDC signal to shutdown. This normally comes
form the serial port using Liebert’s contact closure cable. It cannot be
used with just a contact closure unless the relay is used to switch a
voltage source. A 5-12 VDC signal for 1.5 seconds or greater is
required to signal a shutdown. Signals for less than 1.5 seconds will
be ignored. After Pin 4 receives a shutdown signal for 1.5 seconds,
the command cannot be canceled.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
3. A battery shutdown signal on Pin 4 will NOT cause an immediate
shutdown. A shutdown signal will start a 2-minute shutdown timer.
The timer cannot be stopped. After 2 minutes, the UPS will shut
down.
4. If the utility returns during the 2-minute timer countdown, the shut-
down timer will continue until the end of 2 minutes and the UPS will
turn OFF. The UPS must remain OFF for at least 10 seconds even if
AC input power returns before the UPS turns OFF. This serves to
reset and restart the server.
Whether the UPS turns back ON when power is restored depends on the
auto-restart setting: enabled or disabled.
If the auto-restart is disabled, the UPS will not restart after performing the
2-minute shutdown delay.
PINS 5 & 6 - ANY-MODE SHUTDOWN
1. Pin 6 of the 9-pin communication connector is used for “Any-Mode
Shutdown” of the UPS output. This control input may be used in spe-
cial applications to disable the UPS output power—both Inverter and
Bypass.
2. The Options tab allows the behavior of the Any-Mode Shutdown fea-
ture to be modified. When the program opens, or the REFRESH but-
ton is pressed, the UPS setting is read by the configuration program
and displayed.
Auto-Enable Output
WARNING
!
Note that when this option is selected and the UPS output
is disabled using Pin 6, the UPS output can turn on
automatically and without warning if the Pin 6 connection
is changed.
Pin 6 Logic
WARNING
!
DO NOT CHANGE THIS OPTION from the factory default
setting unless you are ready to install a normally-closed
connection between Pins 5 & 6. This connection must be
maintained to use the UPS or to use the configuration
program again, including the ability to change the UPS
setting back to the default setting using the configuration
program via a serial communication link.
If version 1.6 (or later) is used with an earlier GXT 2U model (with an ear-
lier UPS firmware version), the Any-Mode Shutdown features cannot be
changed.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
If the configuration program is used with an earlier UPS model (with an
earlier UPS firmware version) that does not support the modification of
these settings, the Options tab will display a reminder of the factory
default settings. These cannot be changed.
UPS INTELLIGENT COMMUNICATIONS
The UPStation GXT 2U is equipped with an Intellislot port to provide
®
advanced communication and monitoring options.
Liebert’s MultiLink software continually monitors the UPS and can shut
down your computer or server in the event of an extended power failure.
MultiLink can also be configured for use without the serial cable when the
Intellislot SNMP/Web card is installed in the UPS. Additionally, MultiLink
can be configured to coordinate shutdown across the network with other
computers running MultiLink when you purchase a MultiLink License Kit.
For more information about the Intellislot SNMP/Web Card and MultiLink
dealer or Liebert representative.
Several option cards are available for use in the Intellislot port of the
UPStation GXT 2U. The Intellislot SNMP/Web Card provides SNMP and
Web-based monitoring and control of the UPS across the network.
The Intellislot MultiPort 4 Card allows you to install MultiLink software on
four computers and coordinate shutdown in the event of a power failure.
The Intellislot Relay Card provides dry contact relay outputs for custom-
wired applications and delivers support for built-in shutdown for AS/400
systems.
CAUTION
!
To maintain safety (SELV) barriers and for electromagnetic
compatibility, signal cables should be segregated and run
separate from all other power cables, where applicable.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
CONFIGURATION PROGRAM
This is a new feature included with the new UPStation GXT 2U line. Sev-
eral UPS settings that were previously not available or required custom
manufacturing may now be modified using this program. For most users,
the factory default settings will be adequate. This manual illustrates the
features available for modification, as well as the factory default setting.
NOTE
The UPS must be turned off—and not powering connected equip-
ment—before you make any changes to configuration settings.
While the UPS is in Normal Mode operation, press the OFF
button once to put the UPS into Bypass Mode.
Once the UPS is in Bypass Mode operation, press and release
the OFF button two distinct times (for about a second each
time) to turn off the UPS.
GXT 2U CONFIGURATION PROGRAM ABILITIES
•
Select one of five output voltages to match voltages found around
the world.
•
•
Enable/Disable Auto-Restart.
Select frequency converter operation with a fixed output frequency
of 50 or 60 Hz.
•
•
•
•
Set the Low Battery Warning alarm time from 2 to 30 minutes.
Enable/Disable the Auto-Battery test.
Set the Auto-Battery test to 7, 14, 21, or 28 days.
Select the number of external battery cabinets connected to the
UPS to adjust the remaining run time calculations reported by Lie-
bert software products.
•
Modify the shutdown setting of DB-9 pin 6 (for information on pin
assignments, see Communications on page 19).
NOTE
This program is compatible with UPS models beginning with
“GXT2-”, as in “GXT2-2700RT208.” It is not compatible with
earlier versions of UPStation GXT UPS.
What You Will Need
In addition to the GXT 2U UPS, you will need the configuration program dis-
kette and serial cable (beige or tan, 3-wire: GND, TX, RX; straight through
2-2, 3-3, 5-5) included in the UPS accessory box. The BLACK ML9P9S
CONTACT CLOSURE communication cable IS NOT compatible with the
®
®
®
configuration program. A Windows 95 , 98 , or NT computer—desktop or
laptop—is also required to set up and run the configuration program.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
MAINTENANCE
The UPStation GXT 2U requires very little maintenance. The batteries are
valve-regulated, nonspillable, flame retardant, lead acid, and should be
kept charged to obtain their designed life. The UPS continuously charges
the batteries when connected to the utility supply.
When storing the UPS for any length of time, it is recommended to plug
the UPS in for at least 24 hours every four to six months to ensure full
recharge of the batteries.
The UPStation GXT 2U is designed to allow the user to safely replace the
internal batteries. Read the safety cautions before proceeding. Contact
your local dealer or Liebert representative to obtain the appropriate
replacement battery kit part number and pricing.
BATTERY REPLACEMENT
CAUTION
!
A battery can present a risk of electrical shock and high
short circuit current. The following precautions should be
observed before replacing the batteries:
• Remove rings, watches, or other metal objects.
• Use a Phillips (crosshead) screwdriver with insulated
grips.
• Do not lay tools or other metal objects on top of the batter-
ies.
• If the battery replacement kit is damaged in any way or
shows signs of leakage, contact your local dealer or Liebert
representative immediately.
• Do not dispose of batteries in a fire. The batteries may
explode.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Internal Battery Replacement Procedures
1. Gently remove the front plastic bezel cover from the UPS.
2. Loosen and remove the four screws on the front battery door. Lay the
battery door aside for reassembly.
3. Gently pull battery wiring out and disconnect the two slotted battery
connectors.
4. Grasp the battery pack assembly, and pull it out of the front of the
UPS.
5. Unpack the new battery assembly taking care not to destroy the pack-
ing. Compare new and old battery assemblies to make sure they are
the same. If so, proceed with Step 6; otherwise STOP and contact
your local dealer, Liebert representative, or the Liebert Worldwide
Support Group.
6. Line up and slide in the new replacement battery pack.
7. Reconnect the two slotted battery connectors and gently push the
battery wiring and battery pack assembly back into the UPS.
8. Reattach the front battery door with the four screws.
9. Reattach the front plastic bezel cover to the UPS.
NOTE
These are hot-swappable replacement batteries. However,
caution should be exercised because during this procedure the
load is unprotected from disturbances and power outages.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING
The information below indicates various symptoms a user may encounter
in the event the UPStation GXT 2U develops a problem. Use this informa-
tion to determine whether external factors caused the problem and how to
remedy the situation.
1. The Fault indicator will illuminate, indicating the UPS detected a
problem.
2. An alarm will sound, alerting that the UPS requires attention.
3. One or more additional load/battery level LED indicators will be illumi-
nated to provide a diagnostic aid to the operator, as described below:
This example shows the UPS
Fault
on bypass due to output overload.
E
BYPASS
D
UPS ON
C
B
BATTERY
A
AC
INPUT
A
B
C
D
E
Fault
AC INPUT BATTERY UPS ON BYPASS
LOAD/BATTERY
LEVEL INDICATORS
LED status Diagnosis/Audible alarm
All LEDs
A LED
B LED
C LED
D LED
E LED
On bypass due to output overload; beep every half-second
On bypass due to overtemperature condition; beep every 4 sec.
On bypass due to DC bus overvoltage; beep every 4 sec.
On bypass due to control power supply failure; beep every 4 sec.
On bypass due to PFC failure; beep every 4 sec.
On bypass due to inverter failure; beep every 4 sec.
A&C LEDs UPS failed battery test; long beep every minute
UPS shutdown due to command from communication port
(SNMP); no beep
C&E LEDs
Battery LED Internal Battery source not available (continuous horn). Check
Flashing
battery connection, completely power down and reboot UPS.
AC LED
Flashing
Line-to-neutral reversal in the AC input power supply or a loss of
proper grounding; continuous horn and UPS will not start.
Bypass LED Utility power voltage or frequency is out of tolerance; bypass is
Flashing unavailable.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Under fault conditions, the Fault indicators will be illuminated indefinitely
while battery charger is operational, or for a maximum of 5 minutes while
battery charger is not operational.
If a problem persists, consult your local dealer, Liebert representative or
contact the Liebert Worldwide Support Group. Please have the UPS
model number and serial number available at the time of your inquiry.
Troubleshooting Guide
Problem
Cause
Solution
UPS fails to start
when the ON
button is pressed.
UPS is short circuited or
overloaded.
Ensure UPS is OFF.
Disconnect all loads and
ensure nothing is lodged in
output receptacles. Ensure
loads are not defective or
shorted internally.
Battery indicator
LED is illuminated.
UPS not plugged in.
UPS is operating from
battery mode, make certain
UPS is securely plugged
into the wall receptacle.
UPS input protection fuse
has blown/opened.
UPS is operating from
battery mode. Save data
and close applications.
Replace UPS input fuse,
then restart UPS.
Utility voltage out of UPS
input range.
UPS is operating from
battery mode. Save data
and close applications.
Ensure utility supply voltage
is within acceptable limits
for UPS.
UPS has reduced Batteries are not fully
Keep UPS plugged in
continuously at least 24
hours to recharge batteries.
battery time.
charged.
UPS is overloaded.
Check load level display
and reduce the load on the
UPS.
Batteries may not be able to Replace batteries. Contact
hold a full charge due to
age.
your local dealer, Liebert
representative or the Liebert
Worldwide Support Group
for replacement battery kit.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide (Continued)
Problem
Cause
Solution
Fault and Bypass UPS overloaded or load
Check load level display
and remove non-essential
loads. Recalculate the load
and reduce number of loads
connected to UPS. Check
load equipment for faults.
indicator LEDs
and all load level
LEDs are
equipment is faulty.
illuminated.
Fault and Bypass UPS internal fan has a
Ensure UPS is not
overloaded, ventilation
openings not blocked, or
indicator LEDs
and diagnostic
LED A are
problem or UPS shutdown
due to temperature
condition. Load is on bypass room ambient temperature
illuminated.
power.
is not excessive. Wait 30
minutes to allow UPS to
cool, then restart UPS. If
UPS does not restart,
contact your local dealer,
Liebert representative or the
Liebert Worldwide Support
Group.
Fault and Bypass UPS internal DC bus
UPS requires service.
Contact your local dealer,
Liebert representative or the
Liebert Worldwide Support
Group.
indicator LEDs
and diagnostic
LED B are
overvoltage.
illuminated.
Fault and Bypass UPS control power supply
UPS requires service.
Contact your local dealer,
Liebert representative or the
Liebert Worldwide Support
Group.
indicator LEDs
and diagnostic
LED C are
fault.
illuminated.
Fault and Bypass UPS PFC (Power Factor
UPS requires service.
Contact your local dealer,
Liebert representative or the
Liebert Worldwide Support
Group.
indicator LEDs
and diagnostic
LED D are
Correction Circuit) fault.
illuminated.
Fault and Bypass UPS inverter fault.
indicator LEDs
and diagnostic
LED E are
illuminated.
UPS requires service.
Contact your local dealer,
Liebert Representative or
the Liebert Worldwide
Support Group.
Fault indicator
LED and
diagnostic LED A
and C are
UPS failed the battery test.
Replace batteries. Contact
your local dealer, Liebert
representative or the Liebert
Worldwide Support Group.
illuminated.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting Guide (Continued)
Problem
Cause
Solution
Fault and Bypass UPS shutdown due to a
Your UPS has received a
signal or command from the
attached computer. If this
was inadvertent, ensure the
communication cable used
is correct for your system.
For assistance, contact your
local dealer, Liebert
indicator LEDs
and diagnostic
LED C and E are
illuminated.
command from the
communications port(s).
representative or the Liebert
Worldwide Support Group.
AC LED is
flashing.
UPS detected a line-to-
neutral reversal or a loss of electrician to verify site
proper grounding;
Contact a qualified
wiring.
continuous horn and UPS
will not start.This is active
only when power is first
applied to the input. Once
the UPS is running, the AC
LED will not start flashing,
even if the input wiring is
changed.
Battery LED is
flashing.
Battery source is not
available; continuous horn.
Check battery connections,
completely power down and
restart UPS.
NOTE: If the battery circuit
opens while the UPS is
running, it will be detected
when the next battery test is
performed.
Bypass LED is
flashing.
Bypass voltage is present,
but is disabled for use
because the voltage or
frequency is outside
acceptable limits.
The AC input powers the
PFC input and serves as the
bypass source. If the AC is
present but the voltage or
frequency exceeds the
acceptable range for safe
operation with a load, the
bypass will be disabled and
this LED will flash, indicating
that the bypass is
unavailable.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Alarm Conditions
Condition
Battery Mode
Alarm
One short beep every 10 seconds;
(utility failure)
more than 2 minutes of run time remaining
Low Battery
Two short beeps every 5 seconds;
less than 2 minutes of run time remaining
Output Overload
(bypass)
One short beep every half second
A one-second beep every 4 seconds
A one-second beep every 4 seconds
A one-second beep every 4 seconds
Overtemperature
(bypass)
DC Bus Overvoltage
(bypass)
Control Power Supply
Failure (bypass)
PFC Failure (bypass)
Inverter Failure
A one-second beep every 4 seconds
A one-second beep every 4 seconds
A 2-second beep every minute
Battery Test Failure
29
Download from Www.Somanuals.com. All Manuals Search And Download.
SPECIFICATIONS
Model Number
GXT2-2700RT208
2700VA/1890W
Model Rating
DIMENSIONS: in. (mm)
Unit - W x D x H: in. (mm)
3.5 x 24.2 x 17 (87 x 618 x 430)
Shipping - W x D x H: in. (mm) 10.5 x 27.2 x 23 (268 x 692 x 585)
WEIGHT lbs (kg)
Unit: lbs (kg)
75.2 (34.1)
84.9 (38.5)
Shipping: lbs (kg)
INPUT AC PARAMETERS
Voltage Range (typical)
100% - 90% loading
90% - 70% loading
70% - 30% loading
30% - 0% loading
208 VAC nominal; variable based on output load
176 VAC/280 VAC
159 VAC/280 VAC
139 VAC/280 VAC
119 VAC/280 VAC
Frequency
40 - 70 Hz; Auto Sensing
10 ft. attached w/ NEMA L6-20 plug
Input Power Cord
OUTPUT AC PARAMETERS
Output Receptacles
(2) NEMA L6-15R
(1) NEMA L6-20R
Voltage
200/208/220/230/240 (user configurable) VAC; ±3%
Frequency
50 Hz or 60 Hz
Waveform
Sinewave
Main Mode Overload
200% for 8 cycles; 130% for 10 seconds with transfer
to bypass
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, flame retardant, lead acid
6 x 12V x 9.0 AH
Qty x V x Rating
Battery Mfg/Part #
Panasonic/ UP-VW1245P1
Yuasa/ REW 45-12 FR
Back-Up Time
Recharge Time
See Battery Run Times charts
5 Hours to 95% capacity after full discharge into 100%
load (Internal Batteries Only)
ENVIRONMENTAL
Operating Temp
Storage Temp
+32°F to +104°F (0°C to +40°C)
+5°F to +122°F (-15°C to +50°C)
0% to 95%, non-condensing
Relative Humidity
Operating Elevation
Up to 10,000 ft. (3000 m) at 104°F (40°C)
without derating
Storage Elevation
Audible Noise
50,000 ft. (15,000 m) maximum
<55 dBA, at 1 meter from the rear
<50 dBA, at 1 meter from the front or sides
AGENCY
Safety
UL 1778, c-UL Listed (Suitable for computer room
applications)
RFI/EMI
FCC Part 15, Subpart B, Class A
IEEE 587 Category A & B
ISTA Procedure 1A
Surge Immunity
Transportation
30
Download from Www.Somanuals.com. All Manuals Search And Download.
BATTERY CABINET SPECIFICATIONS
Model Number
GXT2-72VBATT
Used w/ UPS Model
DIMENSIONS in (mm)
Unit - W x D x H in. (mm)
GXT2-2700RT208
3.5 x 24.2 x 17 (87 x 618 x 430)
Shipping - W x D x H in. (mm) 10.5 x 27.2 x 23 (268 x 692 x 585)
WEIGHT lbs (kg)
Unit: lbs (kg)
93.6 (42.5)
Shipping: lbs (kg)
BATTERY PARAMETERS
Type
102.5 (46.5)
Valve-regulated, nonspillable, flame retardant, lead acid
2 x 6 x 12V x 9.0 AH
Qty x V x Rating
Battery Mfg/Part #
Panasonic/UP-VW1245P1
Yuasa/REW 45-12 FR
Back-Up Time
ENVIRONMENTAL
Operating Temp
Storage Temp
See Battery Run Times charts
+32°F to +104°F (0°C to +40°C)
+5°F to +122°F (-15°C to +50°C)
0% to 95%, non-condensing
Relative Humidity
Operating Elevation
Up to 10,000 ft. (3000 m) at 104°F (40°C)
without derating
Storage Elevation
AGENCY
50,000 ft. (15,000 m) maximum
Safety
UL 1778, c-UL Listed (Suitable for computer room
applications)
RFI/EMI
FCC Part 15, Subpart B, Class A
ISTA Procedure 1A
Transportation
31
Download from Www.Somanuals.com. All Manuals Search And Download.
BATTERY RUN TIMES
Load %
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Estimated Time
91
46
30
21
16
11
9
8
7
5
364
184
120
84
64
44
36
32
Internal Battery
(minutes)
Internal Battery
+ 1 External Battery
Cabinet (minutes)
28
20
728
368
240
168
128
88
72
64
56
40
1092
552
360
252
192
132
108
96
Internal Battery
+ 2 External Battery
Cabinets (minutes)
Internal Battery
+ 3 External Battery
Cabinets (minutes)
84
60
1456
736
480
336
256
176
144
128
112
80
Internal Battery
+ 4 External Battery
Cabinets (minutes)
Note: Approximate discharge times are in minutes and at 77°F (25°C) with a 100% resistive load.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
PRODUCT WARRANTY REGISTRATION
To register for warranty protection:
•
Visit the Quick Links section of our Web site at:
•
Click on Product Warranty Registration and fill in the form.
If you have any questions, please contact us at:
US: 800-222-5877
Outside the US: 614-841-6755
33
Download from Www.Somanuals.com. All Manuals Search And Download.
34
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
POWER AVAILABILITY
UPStation GXT 2U™
USER MANUAL
Technical Support/Service
The Company Behind the Products
Web Site
Monitoring
800-222-5877
With over a million installations around the globe,
Liebert is the world leader in computer protection
systems. Since its founding in 1965, Liebert has
Outside the US: 614-841-6755
developed
a
complete range of support and
protection systems for sensitive electronics:
Single-Phase UPS
800-222-5877
•
•
•
Environmental systems—close-control air
conditioning from 1 to 60 tons
Outside the US: 614-841-6755
Power conditioning and UPS with power
ranges from 300 VA to more than 1000 kVA
Integrated systems that provide both
environmental and power protection in
single, flexible package
Three-Phase UPS
800-543-2378
Environmental Systems
a
800-543-2778
Outside the United States
•
•
Monitoring and control—from systems of any
size or location, on-site or remote
Service and support through more than 100
service centers around the world and a 24/7
Customer Response Center
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
While every precaution has been taken to ensure
the accuracy and completeness of this literature,
Liebert Corporation assumes no responsibility and
disclaims all liability for damages resulting from use
of this information or for any errors or omissions.
Italy
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
+39 049 9719 111
Fax: +39 049 5841 257
Asia
23F, Allied Kajima Bldg.
138 Gloucester Road
Wanchai
© 2003 Liebert Corporation
All rights reserved throughout the world.
Specifications subject to change without notice.
Hong Kong
+852 2 572 2201
Fax: +852 2 831 0114
® Liebert and the Liebert logo are registered
trademarks of Liebert Corporation. All names
referred to are trademarks or registered
trademarks of their respective owners.
SL-23154 (6/03) Rev. 1
Download from Www.Somanuals.com. All Manuals Search And Download.
|