Product Description  
1.0 PRODUCT DESCRIPTION  
1.1 General Product Information  
1.1.1 Product/System Description  
Liebert’s XDP refrigerant distribution unit is an interface between the building chilled water system  
and the cooling modules in the Liebert XD system. It is designed to circulate and control refrigerant  
to the cooling modules that are in the room with heat-producing equipment. The Liebert XDP consists  
of a cabinet that includes a heat exchanger, circulating pump(s), control valve, receiver, controls,  
valves and piping.  
The Liebert XDP monitors room conditions and prevents coil condensation by maintaining the refrig-  
erant being pumped to the cooling modules at a temperature above the room’s dew point.  
All functions, such as switching pumps (if applicable), controlling refrigerant temperature, etc., are  
automatic.  
The Liebert XDP’s minimum recommended operating load is 20% of system nominal capacity. For  
example, a Liebert XDP160 60Hz system’s minimum load would be 32 kW. Loading below this value  
can unfavorably affect system operation. Consult factory for any loading below this recommendation.  
The Liebert XDP is rated for 160kW (546,000 BTU/H) of cooling.  
Figure 1  
Liebert XDP components  
Liebert XDP Unit  
Liebert XD Cooling Modules  
Control Valve  
Chilled Water  
Heat Exchanger  
Pumps  
Receiver  
1.2  
Equipment Inspection  
When the unit is delivered, inspect all items for visible and concealed damage. Damage should be  
immediately reported to the carrier and a damage claim filed with a copy sent to Liebert or to your  
sales representative.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Product Description  
1.3  
Equipment Handling  
WARNING  
!
Risk of unit falling over. Can cause injury or death.  
The Liebert XDP is top-heavy. Use extreme caution and care when moving and installing this  
unit.  
NOTE  
Personnel should be properly trained and certified to move and rig equipment.  
1.3.1 Handling With Skid  
• Always keep the unit upright, indoors and protected from damage.  
• If possible, transport the unit using a forklift truck. Otherwise use a crane with belts or cables. In  
either case, do NOT press on the top edges of the packaging.  
• If using a forklift, make sure the forks (if adjustable) are spread to the widest allowable distance  
to still fit under the skid.  
• When moving the skidded unit with a forklift truck, do not lift the unit any higher than  
6" (152mm) off the ground. If circumstances require the unit to be lifted higher than 6" (152mm),  
great care must be exercised and all by-standing personnel are to be no closer than 20 feet (6m)  
from the lift point of the unit.  
CAUTION  
!
Risk of structural interference. Can cause equipment or building damage.  
While on the skid, the unit is too tall (83" [2108mm] overall height) to fit through a standard  
doorway. Any attempt to move the unit, while skidded, through a standard doorway will  
cause damage to the unit and to the building.  
1.3.2 Removal from Skid  
Liebert recommends using dual hand trucks or a similar method to remove the Liebert XDP from the  
skid. This is to ensure that both ends of the unit are firmly secure and to provide a good means of unit  
mobility.  
1. Always keep the unit upright, indoors and protected from possible damage.  
2. Remove the exterior packaging. Leave the plastic bag over the Liebert XDP until the unit has  
been moved to its final location. The bag will protect the painted panels against scuffing.  
3. Remove two (2) corner tie-down brackets from one side of the unit, on a non-runner notch side of  
the pallet. Remove eight (8) lag bolts from two (2) end deck boards on the same end where the  
tie-down brackets were removed (refer to Figure 2).  
Figure 2  
Tie-down brackets and lag bolts to be removed  
Remove these 4 lag bolts  
to free deck boards  
Remove these 2  
tie-down brackets  
Remove these 4 lag bolts  
to free deck boards  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Product Description  
4. Remove the two (2) end deck boards from one end of the pallet and the attached, notched section  
of the center runners (refer to Figure 3).  
Figure 3  
Removing pallet boards for piano jack insertion  
Remove two deck boards ...  
... and center runner sections  
from one end of pallet.  
5. Place a piano jack with its forks snugly against the bottom of the unit and strap the Liebert XDP  
securely to the jack (refer to Figure 4).  
NOTE  
Place a mover’s blanket or other cushioning material between the piano jack and the  
unit’s side panels.  
Figure 4  
Liebert XDP strapped to piano jack  
Piano jack  
Strap secures the  
Liebert XDP to the jack  
Place cushioning material  
between the forks and the Liebert  
XDP to protect unit’s finish  
(cushion not shown for clarity)  
Piano jack’s forks should be  
snug against the Liebert XDP  
6. Repeat Steps 2, 4 and 5 for the opposite side of the unit. When these steps have been completed,  
the Liebert XDP will be supported by two piano jacks, one on either side.  
7. Remove all of the remaining lag bolts from one (1) of the pallet’s outside runners (see Figure 5).  
Figure 5  
Remove remaining lag bolts from one runner  
Remaining 6 lag bolts  
to remove  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Product Description  
8. Remove the runner from which all lag bolts have been removed (refer to Figure 6).  
Figure 6 Remove runner from pallet  
Slide this runner away  
from the Liebert XDP  
9. Using the pallet jacks, raise the secured unit to the highest point that the piano jacks will allow.  
Once the unit has been raised, slide the remainder of the pallet from under the Liebert XDP (see  
Figure 7). Lower the Liebert XDP so that its base is approximately 1" (25.4mm) off the ground.  
Figure 7  
Sliding pallet from under Liebert XDP  
Slide the remaining part of the pallet  
from under the Liebert XDP so the unit  
may be moved on the piano jacks.  
1.3.3 Removing Piano Jacks  
Once the unit has been moved to the installation location, Emerson Network Power recommends the  
following method to remove the piano jacks:  
1. Lower the unit as far as the piano jacks will allow.  
2. Undo all strapping holding the piano jacks to the unit.  
3. Remove all cushioning material used to protect the unit from the straps and the piano jacks.  
4. Use a pry bar or other lever to lift one side of the Liebert XDP enough to allow removal of the  
piano jack.  
5. Repeat Step 4 to remove the piano jack on the opposite side.  
6. Remove the plastic bag.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Product Description  
1.4  
Mechanical Considerations  
1.4.1 Positioning the Liebert XDP  
Install the Liebert XDP according to the site specific documentation and secure the unit to the floor.  
The Liebert XDP can be installed near a wall or another Liebert XDP. However, there must be at  
least 3 feet (92cm) clearance in front of the Liebert XDP as service access for components in the unit.  
For additional technical information, refer to the System Design and Configuration Document for the  
Liebert XD System, SL-16655. The document is available in electronic format at Liebert’s Web site,  
www.liebert.com, as well as from your local Emerson Network Power representative.  
Figure 8  
Dimensions  
B
A
Overall  
Overall  
C
Side Panel  
E
D
78"  
(1981mm)  
1" (25mm)  
5-1/2"  
(140mm)  
11"  
(279mm)  
Floor Cutout Dimensions  
D
The shaded area indicates  
Unit Base  
a recommended clearance  
of 36" (914mm) for component  
access.  
E
Unit Base  
DPN000767  
Pg. 2, Rev. 6  
Unit Dimensional Data  
Table 1  
Liebert XDP dimensions  
Dimensional Data inches (mm)  
Shipping Weight, lb (kg)  
Model  
50/60Hz  
A
B*  
C
D
E
Domestic  
990 (449)  
Export  
XDP160  
38 (965)  
34 (864)  
33-1/8 (841)  
33 (838)  
36 (914)  
1067 (484)  
* The dimension does not include the bezel of the disconnect switch.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Product Description  
Figure 9  
Piping access points  
To first cooling module  
or bypass flow controller **  
Install replaceable filter dryer assembly  
in liquid supply line B.  
* Orientation  
determined  
by installer.  
A - Return From Cooling Modules  
17-1/4"  
B - Supply to Cooling Modules  
(438mm)  
16-1/8"  
(410mm)  
10" (254mm)  
19"  
(483mm)  
Dimensions are  
approximate  
and subject to change  
without notice.  
C - Chilled Water Supply  
From Chilled Water Source  
D - Chilled Water Return  
To Chilled Water Source  
* Allow 8" (204mm) clearance for filter replacement.  
DPN000767  
Pg. 3, Rev. 6  
** To ensure ensure all refrigerant flow is filtered, install the filter dryer assembly  
between the discharge line of the Liebert XDP and the first bypass flow controller  
or the first cooling module.  
Table 2  
Model  
Unit piping outlet connection sizes, inches, OD Cu  
Pipe Connection Point  
50/60 Hz  
A
B
C
D
XDP160  
2-1/8  
1-1/8  
2-5/8  
2-5/8  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Product Description  
1.5  
1.6  
Electrical Information  
High Voltage Connections  
Make sure the actual supply voltage and frequency correspond to the voltage and frequency indicated  
on the Liebert XDP’s rating plate. The unit must be installed in accordance with national wiring reg-  
ulations.  
Connect cables for high voltage supply to the electrical box in the Liebert XDP according to Figure 12  
and make sure that the phases are correctly connected.  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
Disconnect all local and remote electric power before working within the unit.  
CAUTION  
!
Risk of sharp edges and heavy parts. Can cause injury or equipment damage.  
Wear gloves to prevent injury to hands.  
Damage to wiring or components may make unit unsafe to operate.  
Use caution when installing wiring to prevent damage to factory wiring.  
Install protective bushings in wiring knockouts as required.  
Do not disturb factory wiring or route field-installed wiring over electrical terminals.  
Use NEC Class 1 wiring for all hazardous voltage electrical power supplies.  
Check and retighten all wiring connections before starting.  
1.6.1 Connecting High-Voltage Cables  
1. Turn the Liebert XDP’s disconnect switch to the Off position (see Figure 10). Open the front  
doors and push down on the enclosure cover latch to open the hazardous voltage enclosure cover.  
Figure 10 Front view of Liebert XDP and electrical enclosure  
Status Lamps  
Disconnect  
User Interface  
Switch  
Enclosure Cover  
Latch  
Hazardous Voltage  
Enclosure Cover  
Front of Liebert XDP  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Product Description  
2. Determine which knockouts in the electrical enclosure will be used and remove them (see  
Figure 11 Electrical enclosure knockout locations for field wiring  
User Interface  
Liebert XD Module Condensate  
Connections (optional;  
(Wall Box) Wiring  
depends on features  
Temperature/Humidity  
Sensor Wiring  
supplied with Liebert XD Module)  
Alternate Knockout  
for Temperature/Humidity  
Sensor Wiring  
Enclosure Cover Not Shown for Clarity  
3. Route the input hazardous voltage electrical power wiring through the top left knockout (see  
Figure 11) to the disconnect switch L1, L2 and L3 (see Figures 12 and 13). Observe proper  
phasing.  
4. Connect the ground wire to the ground lug (see Figures 12 and 13), which is in the middle left of  
the enclosure.  
Figure 12 High voltage connections—60Hz  
Customer Power  
Connection  
Ground Lug  
Disconnect Switch  
Transformer 2  
Pump Fuse  
Blocks  
Power Block  
Control  
Fuse Blocks  
Transformer 1  
Pump Contactors  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Product Description  
Figure 13 High voltage connections—50Hz  
Customer Power  
Connection  
Ground Lug  
Disconnect Switch  
Transformer 2  
Pump Circuit  
Breakers  
Busbar  
Power Block  
Fuse Blocks  
Transformer 1  
Pump Contactors  
1.7  
Extra Low Voltage (ELV) Connections  
Extra Low Voltage power output is 30V and 100VA or less.  
1. Turn off all unit power before connecting cables or wires. Failure to do so may damage this  
equipment (refer to Figure 14).  
2. Route low voltage electrical connections through the appropriate knockouts as indicated below.  
3. User interface requires four thermostat-type wires (jacketed) connected to the control board (see  
Figure 14 Electrical enclosure knockout locations for Extra Low Voltage  
User Interface  
Liebert XD Module Condensate  
Connections (optional;  
(Wall Box) Wiring  
depends on features  
Temperature/Humidity  
Sensor Wiring  
supplied with Liebert XD Module)  
Alternate Knockout  
for Temperature/Humidity  
Sensor Wiring  
Enclosure Cover Not Shown for Clarity  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Product Description  
Field Connections—All Units  
• Connect the control display panel cable to terminal block TB3 terminals 1 through 4 on the Lie-  
bert XDP control board as shown (refer to Figure 15). The display panel may be mounted on the  
Liebert XDP’s front right door if the Liebert XDP is located in the area that it conditions. The dis-  
play panel must always be installed in the conditioned space.  
• Connect the provided remote temperature / humidity sensor extension cable to the  
factory-installed cable connected to P16 on the control board. Install the sensor in the higher-  
temperature portion of the cold aisle where the XD modules are located. Alternatively, it can be  
placed on the return air side of the primary air mover (e.g., Liebert Deluxe System/3 ) in the  
room if it represents the conditions where all the XD cooling modules are located. Do not install  
the sensor where ambient air may cause false readings, for example, near unsealed doors,  
windows and similar areas.  
Field Connections—Optional for All Units  
• Connect field wiring from the optional Liebert XD cooling module condensation detection circuit  
to terminal strip locations H2O (24) and XDOC (51).  
• Connect optional field wiring from remote devices to remote alarm device, common alarm output,  
site monitor and remote shutdown, if applicable. See terminal strip descriptions in Figure 15.  
Figure 15 Liebert XDP extra low voltage field connections points  
Temperature/Humidity Sensor  
Cable Provided with  
Temperature/Humidity Sensor Board  
Control Display Panel  
Four thermostatic wires  
to be connected toTB3  
Factory-Wired  
TS-3  
Temperature  
TS-4  
Sensor(s)  
TS-5  
TS-6  
H2O (24)  
RAD1 (50)  
XDOC (51)  
K3COM  
K3NO  
K3NCL  
37  
38  
77  
78  
Control wiring must be Class 2 and installed  
in accordance with the National Electrical Code (NEC)  
Requires shielded cable  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Piping  
2.0 PIPING  
2.1 European Union Fluorinated Greenhouse Gas Requirements  
Stationary air conditioning, refrigeration, heat pump equipments and stationary fire protection sys-  
tems in the European Community market and operating with fluorinated greenhouse gases (f-gas),  
such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (F-gas).  
The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the atmo-  
sphere.  
The F-Gas Regulation requires operators to use use all measures that are technically feasible and do  
not entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to  
recover f-gas before disposing of equipment, as well as during service and maintenance.  
Refer to the full regulation for additional details.  
2.2  
Connection Sizes  
The copper pipe connections on the Liebert XDP are:  
Building Chilled Water Supply 2-5/8" OD  
Building Chilled Water Return 2-5/8" OD  
Refrigerant Supply  
Refrigerant Return  
1-1/8" OD  
2-1/8" OD  
2.2.1 Recommended Pipe Size  
Connect the main pipes between the Liebert XDP and the Liebert XD cooling modules according to  
site specific documentation and the configuration guide for the Liebert XD system.  
Elbows and restrictions must be minimized to get good fluid flow.  
Table 3  
Supply, return pipe sizes for refrigerant loop  
Pipe Function  
Size / Equivalent Pipe Length  
1-1/8" OD for lengths up to 60 feet  
Liebert XDP supply line, from Liebert XDP supply  
to farthest Liebert XD cooling module  
1-3/8" OD for lengths over 60 but less than 175 feet  
2-1/8" OD for lengths up to 60 feet  
Liebert XDP return line, from farthest Liebert XD cooling  
module to Liebert XDP return  
2-5/8" OD for lengths over 60 but less than 175 feet  
1/2" OD for lengths up to 10 feet  
From any model Liebert XDO/Liebert XDH supply  
to supply line of Liebert XDP  
7/8" OD for lengths over 10 but less than 25 feet  
7/8" OD for lengths up to 10 feet  
From any model Liebert XDO/Liebert XDH return  
to return line of Liebert XDP  
1-1/8" OD for lengths over 10 but less than 25 feet  
1/2" OD for lengths up to 10 feet  
From any model Liebert XDV/Liebert XDCF supply  
to supply line of Liebert XDP  
5/8" OD for lengths over 10 but less than 35 feet  
5/8" OD for lengths up to 10 feet  
From any model Liebert XDV/Liebert XDCF return  
to return line of Liebert XDP  
7/8" OD for lengths over 10 but less than 35 feet  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Piping  
2.3  
Liebert XDP Interconnection with Liebert XD Cooling Modules  
All piping must be ASTM (American Society for Testing and Materials) Type L copper pipe.  
The Liebert XDP may be connected to Liebert XD cooling modules with either Liebert’s XD prefabri-  
cated piping assembly or with rigid, off-the-shelf piping. In either setup, piping for the Liebert XD  
system is arranged in a manner similar to piping for a chilled water system. Liebert XD cooling mod-  
ules are connected in parallel between main return and supply pipes going to and from the Liebert  
XDP/Liebert XDC. For piping details, refer to Liebert’s XD System Design Manual, SL-16655. The  
guidelines provided for pipe size must be strictly followed. Failure to size the main lines  
and connection lines adequately may result in reduced cooling capacity. The critical aspects  
of pipe sizing are related to refrigerant volume and pressure drop. Both must be minimized.  
Figure 16 Piping arrangement for Liebert XDP/Liebert XDC used with Liebert XD cooling modules  
All supply and  
return mains  
must be level with  
Liebert XD  
Cooling  
Modules  
Liebert XD  
Cooling  
Modules  
Liebert XD  
Cooling  
Modules  
Liebert XD  
Cooling  
Modules  
Liebert XD  
Cooling  
Modules  
or above the top  
of all Liebert  
XD modules  
SLOPE—The main supply and return lines to and from the Liebert XDP/Liebert XDC  
must be sloped downward toward the Liebert XDP/Liebert XDC at a rate of 1-2" per  
20 feet (25.4-51mm per 6m) of pipe run. Horizontal connector lines should also be  
sloped downward from the cooling modules toward the main supply and return lines.  
Liebert XDP/  
Liebert XDC  
2.4  
Piping Installation Method  
The assembly and connection means used for piping in the Liebert XD system are similar to that of  
conventional refrigeration systems. All piping should be installed with high-temperature brazed  
joints. Brazing material may be used, but soft soldering is not recommended. If brazing material is  
used, the lines being brazed MUST be filled with flowing dry nitrogen during brazing to prevent  
excessive oxidation and scale formation inside the piping. Prevailing good refrigeration practices  
should be employed for piping supports, leak testing, dehydration and charging.  
Insulate all piping lines to prevent condensation in applications where the dew point approaches the  
R-134a refrigerant temperature.  
2.4.1 Bypass Flow Controller  
Some installations require one or more bypass flow controller(s) to ensure that the Liebert XDP’s  
pumps operate within the optimum range. These devices are added to the field piping and simulate  
the flow of additional cooling modules.  
Each bypass flow controller should be installed with one shutoff valve to allow the controller to be dis-  
abled when cooling modules are added to a Liebert XD system.  
If bypass flow controllers are required, they should be connected between the main supply and the  
main return lines of the field piping. The connection points to the main supply and return lines should  
be in a convenient and accessible location between the Liebert XDP and the first Liebert XD module  
in the circuit. See Figures 17 and 18 for piping details of the bypass flow controller.  
Refer to Table 4 to determine the number of bypass flow controllers needed, based on the total nomi-  
nal cooling capacity of the cooling modules in each Liebert XD system.  
Table 4  
Bypass flow controllers for a Liebert XDP-based system  
Required Number  
of Bypass Flow Controllers  
Cooling Modules -  
Cumulative Model Size  
Liebert XDP  
32 to 63  
64 to 95  
3
2
1
0
96 to 127  
128 to 160  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Piping  
Figure 17 Bypass flow controller details, dimensions  
4
(102mm)  
7/8  
(22mm) ID  
Figure 18 Bypass flow controller arrangement  
Return  
Main  
7/8" Refrigerant Grade  
Full Port Ball Valve  
Field-Supplied and Field-Installed  
Flow Direction  
Bypass Flow Controller  
(Field-Installed)  
Supply  
Main  
Figure 19 Bypass flow controller piping  
Liebert XD  
Liebert XD  
Cooling  
Cooling  
Module #1  
Module #2  
Bypass Flow  
Controllers  
Coolant  
Supply  
Filter Dryer  
Assembly  
Coolant  
Return  
Liebert XDP  
or  
Liebert XDC  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Piping  
2.5  
Piping Details—Shut-Off/Isolation Valves  
To allow for maintenance of the Liebert XDP, isolation valves must be installed on the chilled water  
circuit (see Figure 20).  
Figure 20 General piping details  
Return  
Supply  
Return  
Supply  
Liebert  
XDP A  
Liebert  
XDP B  
Floor  
Isolation  
valves  
Isolation  
valves  
Building Chilled Water Supply  
Building Chilled Water Return  
2.5.1 Piping Installation Method  
All piping should be installed with high temperature brazed joints. Prevailing good refrigeration prac-  
tices should be employed for piping supports, leak testing, dehydration and charging. Emerson Net-  
work Power highly recommends venting the pressure relief of the Liebert XDP (located at the top of  
the receiver) outside of the conditioned space where it is open to the atmosphere.  
2.5.2 Piping Mains  
All refrigeration piping mains, both supply and return, should be installed with a downward pitch  
toward the Liebert XDP of 1-2" for every 20 feet (25.4-51mm per 6m) of pipe run.  
Install a 20-40 mesh strainer on the chilled water supply to the Liebert XDP. The strainer is needed  
to prevent particles in the chilled water from entering the heat exchanger of the Liebert XDP.  
2.5.3 Evacuation and Leak Check  
1. Open all service valves, including those located outside of the Liebert XDP.  
2. Place 150 psig (1034kPa; 10.34 bars) of dry nitrogen with a tracer of R-134a in the system.  
NOTICE  
Risk of overpressurization. Can cause equipment damage.  
Do not exceed 150 psig (1034 kPa; 10.34 bars) in the R-134a circuit.  
3. Check the system for leaks with a suitable leak finder  
4. After completion of the leak testing, release the test pressure (per local code) and connect to  
vacuum pump(s) at the Schrader valves.  
5. After four hours of pulling a deep vacuum, check the vacuum level and if it has not changed,  
break the vacuum with dry nitrogen.  
6. Pull a second vacuum to 250 microns or less. Recheck the vacuum level after 2 hours.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Piping  
2.6  
Checklist for Proper Installation  
___ 1. Unpack and check received material.  
___ 2. Position the Liebert XDP and secure it to the floor.  
___ 3. Wire high voltage connections.  
___ 4. Wire low voltage connections.  
___ 5. Connect the building chilled water piping to the Liebert XDP.  
___ 6. Connect the Liebert XD cooling module piping to the Liebert XDP.  
___ 7. Check the system for leaks.  
___ 8. Hold a vacuum on the system.  
___ 9. Charge the system with refrigerant.  
___ 10. Make sure that all piping has proper insulation.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Checklist for Liebert XDP Startup  
3.0 CHECKLIST FOR LIEBERT XDP STARTUP  
CAUTION  
!
Risk of piping and component rupture. May cause injury or equipment damage.  
Closing service valves may isolate liquid refrigerant, causing high pressure and rupture of  
piping. Do not close valves without following recommended procedures for repair,  
maintenance and replacement of components. Install pressure relief valves in field piping  
that may become isolated by service valves.  
NOTE  
Before any action that could cause a disturbance in the Liebert XD system’s cooling function is  
begun, the facility manager MUST be informed. In addition, after the action is taken and the  
work is finished, the facility manager MUST be informed  
1. Verify that bypass flow controllers were installed (if applicable), see Table 4.  
2. Check all isolation ball valves in the Liebert XDP and Liebert XD cooling module and verify that  
all are open.  
3. Check rotation of the Liebert XDP’s pumps.  
On 460V units only, use the rotation device provided—this device must be held against the  
pump housing—at the inspection screw prior to energizing the pumps—counterclockwise indi-  
cates proper rotation; clockwise indicates incorrect rotation.  
On 208V units only, view the LED indicator on the pump—Green indicates proper rotation;  
Green and Red indicate incorrect rotation.  
Table 5  
Liebert XDP pump light indicator—208V and 400V units  
Indicator Lights  
Description  
Green  
Off  
Red  
Off  
The electricity supply has been switched off or the pump has been cut out by the thermal switch.  
The electricity supply has been switched on. Normal operation.  
On  
Off  
On  
On  
The electricity supply has been switched on. The direction of rotation is wrong.  
4. Check rotation of fans on Liebert XD cooling module units.  
5. Verify that air is being discharged into the cold aisle.  
6. Confirm that the total calculated refrigerant R-134a amount has been properly charged into the  
7. Confirm that the remote temperature/humidity sensor provided has been installed in the correct  
location.  
The correct location is near the return side of a main air mover, such as a Liebert Deluxe  
System/3. If more than one Liebert XDP is installed, use a different location for each remote sen-  
sor for best temperature/humidity calculation.  
The Liebert XDP system is now ready to be turned ON.  
1. Turn On all of the Liebert XD cooling module fans.  
2. Turn the Liebert XDP On via its user interface (I/O button). Allow the system to attempt to start  
for at least 2 minutes.  
If the Liebert XDP pump cannot maintain flow and continues to switch over due to starting diffi-  
culties, proceed to Step 4 and refer to 6.0 - Troubleshooting.  
3. If constant flow is established, wait until the Liebert XDP has been operating for 10-15 minutes,  
then verify that the refrigerant level in the receiver sight glass is between the second and third  
level (see Figure 21). Add or remove charge, if necessary.  
4. Check pressure differential functionality:  
The Liebert XDP system should be On. If it is Off:  
a. Turn On the Liebert XD cooling module fans  
b. Turn the Liebert XDP On via user interface (I/O button).  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Checklist for Liebert XDP Startup  
If there is no “Loss of Flow” alarm present—This suggests that there is flow. Test the  
pressure differential by closing the ball valve on either the suction line or discharge line to  
stop the flow.  
This should prompt an alarm for “loss of flow on P1.” This alarm confirms that the switch has  
opened on low pressure (below 6 psi; 41kPa; 0.41 bars).  
If there is a “Loss of Flow” alarm present—This suggests that there is no flow. Verify  
that this is correctly annunciated by looking at the sight glass in the receiver. If a true no-flow  
condition exists, the level will not move.  
However, if there is flow, but the differential reading is faulty, the level will slowly  
drop, indicating flow, while the loss of flow alarm is annunciated.  
Check the pressure differential physically by making sure that the electrical connections are  
properly connected. Then check the pressure differential electrically by making sure that the  
unit has 24VAC across it.  
Figure 21 System R-134a liquid level  
Operation above sight glass#3 can  
make the system operate erratically  
and reduce cooling capacity- Reduce  
charge to recommended leve.l  
Recommended operating level  
Acceptable operating level  
For lightly loaded systems,  
the recommended operating  
level is sight glass#2.  
Operation below sight glass#1 may  
cause loss of flow or cooling. Add  
charge to reach recommended leve.l  
Sight Glasses 1, 2 & 3  
3.1  
Filling the Pumped Circuit—R-134a  
1. Connect a charging manifold to the service port of the receiver outlet valve.  
2. Purge the hoses.  
3. Calculate the amount of R-134a refrigerant needed to charge the system, using the values in  
Example. The section includes a worksheet to calculate system refrigerant charge requirements.  
4. Weigh in the calculated charge.  
5. After adding the calculated charge, allow the system to sit 15 to 30 minutes to reach equilibrium.  
Observe the refrigerant level through the sight glasses of the receiver. The level should be above  
the second sight glass at a minimum when the Liebert XDP is off.  
6. If the refrigerant level is improper, the charge must be adjusted.  
If the level is too high or too low, recalculate the required charge and reduce or increase the  
amount as needed to reach the proper level.  
NOTE  
All lengths in Tables 7, 8 and 9 are actual pipe lengths, not equivalent pipe lengths.  
NOTE  
System refrigerant volume calculations derived from Tables 6, 7, 8 and 9 are based on a fully  
loaded system. Additional charge may be required for lightly loaded systems.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Checklist for Liebert XDP Startup  
System R-134a charge for a Liebert XDP with any model Liebert XDH/Liebert  
Table 6  
XDO/Liebert XDV/Liebert XDCF  
Per Liebert XD Unit  
(Excludes Connector Lines  
to and from Liebert XD Cooling Module)  
Refrigerant Charge,  
lb (kg)  
157 lb. (65.7kg)  
3.55 lb. (0.66kg)  
2.32 lb. (1.05kg)  
5.32 lb. (2.41kg)  
1.41 lb. (0.64kg)  
Liebert XDP  
Liebert XDO  
Liebert XDV  
Liebert XDH  
Liebert XDCF  
Table 7  
System refrigerant charge for the supply and return mains  
Refrigerant Charge,  
lb/foot (kg/m)  
Supply/Return Main Length and Diameter  
0.45 (0.67)  
0.68 (1.01)  
0.28 (0.42)  
0.43 (0.64)  
Main supply actual length per 1-1/8" OD copper tubing  
Main supply actual length per 1-3/8" OD copper tubing  
Main return actual length per 2-1/8" OD copper tubing  
Main return actual length per 2-5/8" OD copper tubing  
Table 8  
R-134a refrigerant charge for hard-piped connector lines to and from any model  
Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF  
Refrigerant Charge,  
lb/foot (kg/m)  
Hard-Piped Connector Length and Diameter  
0.08 (0.12)  
1/2" OD Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF supply connector actual  
length  
0.13 (0.19)  
0.26 (0.39)  
0.02 (0.03)  
0.04 (0.06)  
0.04 (0.06)  
0.07 (0.1)  
5/8" OD copper tubing Liebert XDV/Liebert XDCF supply connector actual length  
7/8" OD Liebert XDO/Liebert XDH supply connector actual length "  
5/8" OD copper tubing Liebert XDV/Liebert XDCF return connector actual length  
7/8" OD copper tubing Liebert XDV/Liebert XDCF return connector actual length  
7/8" OD copper tubing Liebert XDH/Liebert XDO return connector actual length  
1-1/8" OD copper tubing Liebert XDH/Liebert XDO return connector actual length  
Table 9  
R-134a refrigerant charge for Flex Pipe connector lines to and from any model  
Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF  
Refrigerant Charge, lb. (kg) Metal Flex Pipe Connector Length  
Supply Line Diameter 1/2"  
0.3 lb. (0.14) 4 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply  
0.5 lb. (0.23) 6 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply  
0.7 lb. (0.32) 8 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply  
0.8 lb. (0.36) 10 ft. Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply  
Return Line Diameter 5/8"  
0.01 lb. (0.01) 4 ft. Flex Pipe existing Liebert XDV systems  
0.02 lb. (0.01) 6 ft. Flex Pipe existing Liebert XDV systems  
0.03 lb. (0.01) 8 ft. Flex Pipe existing Liebert XDV systems  
0.03 lb. (0.01) 10 ft. Flex Pipe existing Liebert XDV systems  
Return Line Diameter 1"  
0.13 lb. (0.05) 4 ft Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply  
0.2 lb. (0.09) 6 ft Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply  
0.27 lb. (0.12) 8 ft Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply  
0.33 lb. (0.15) 10 ft Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF supply  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Checklist for Liebert XDP Startup  
3.1.1 Calculating Refrigerant Charge—Example  
Using Tables 6, 7, 8 and 9, calculate the refrigerant charge of the individual sections of your Liebert  
XD system. Add the calculated charge amounts to determine the amount of R-134a refrigerant  
required for one system combining a Liebert XDP with Liebert XD cooling modules (Liebert XDCF,  
Liebert XDH, Liebert XDO and Liebert XDV). The example below combines one Liebert XDP with 20  
Liebert XDV8 cooling modules.  
Table 10 Calculating refrigerant charge—example  
Number of Units  
or Piping Length,  
feet  
Pounds Per  
Component  
Components  
Total, lb.  
157  
46.4  
45  
Liebert XDP  
1
157  
2.32  
0.45  
0.28  
0.8  
Liebert XDV8 Cooling Modules  
Supply Main, 1-1/8"  
20  
100  
100  
20  
Return Main, 2-1/8"  
28  
Liebert XDV 1/2" supply Liebert XD Flex Pipes  
Liebert XDV 5/8" return Liebert XD Flex Pipes  
16  
20  
0.03  
0.6  
Total  
293  
Table 11  
Worksheet to calculate refrigerant charge  
Number of Units  
or Piping Length  
Pounds Per  
Component  
Components  
Total  
Total  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Microprocessor Control  
4.0 MICROPROCESSOR CONTROL  
4.1 Feature Overview  
The microprocessor control for the Liebert XDP features an easy-to-use menu-driven LCD. The  
menus, control features and circuit board details are described in this section.  
Figure 22 User interface  
Up Arrow Key  
Status Display  
Down Arrow Key  
On/Off Key  
Alarm Silence Key  
Active alarms are displayed on the LCD screen and sound an audible beep. To silence an alarm, press  
the Alarm Silence/Help key as prompted on the display.  
Setpoints, DIP switch settings and other selections were made during factory testing of the unit based  
on typical operating conditions. (Other default selections were made according to options included  
with the unit.)  
ADJUST THE FACTORY DEFAULTS ONLY IF THEY DO NOT MEET YOUR SPECIFICATIONS.  
Allowable ranges are displayed by pressing the Help key. A password will be required (if enabled) to  
change setpoints, time delays, etc.  
The display normally shows the leaving refrigerant temperature on the first line and alternates  
between the dew point and the number of alarms present on the second line.  
4.1.1 Display  
To turn the unit On, press the On/Off (I/O) key after power is applied to the Liebert XDP.  
To turn the unit Off, press the On/Off (I/O) key before power is disconnected.  
Table 12 User interface keypad functions  
Keypad  
On/Off (I/O)  
Menu  
Function  
Turns the unit On or Off (top far left keypad)  
Enables the user to access the program menu to change setpoints, alarms, etc. (top near left)  
Raises the value of displayed parameter while in a set mode (set points, time, etc).(arrow, top  
near right)  
Up Arrow Key  
Escape (Esc)  
Alarm Silence  
Allows user to move back to a previous menu (top far right)  
If an alarm is present, press this key to silence the alarm. Help text will appear if this key is  
pressed when no alarm is present (bottom left)  
Down Arrow  
Key  
Lowers the value of displayed parameter while in a set mode (set points, time, etc).(arrow,  
bottom near right).  
After setting a control value, press ENTER to store the information in the microprocessor  
(bottom right).  
Enter  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Microprocessor Control  
4.2  
Controls  
The Microprocessor Control for the Liebert XDP features an easy-to-use, menu-driven liquid crystal  
display. The menus, control features and circuit board details are described in this section.  
4.2.1 Feature Overview  
The Liebert XDP maintains the refrigerant being pumped to Liebert XD cooling modules at a temper-  
ature above the room dew point, preventing condensation.  
4.3  
Main Menu  
Press the MENU key to display the Main Menu. The menu selections are:  
• SETPOINTS  
• STATUS  
• ACTIVE ALARMS  
• ALARM HISTORY  
• TIME  
• DATE  
• SETUP OPERATION  
• SETPT PASSWORD  
• SERVICE PASSWORD  
• CALIBRATE SENSOR  
• ALARM ENABLE  
• ALARM TIME DELAY  
• COM ALARM ENABLE  
• CUSTOM ALARMS  
• CUSTOM TEXT  
• DIAGNOSTICS  
• END OF MENU  
4.3.1 Viewing or Changing Settings  
To access a menu option:  
1. Use the Up or Down arrow keys to scroll to the menu option.  
2. Press the ENTER button to view the current setting.  
3. To change the setting, use the Up or Down arrow keys.  
4. Press ENTER to save the change.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Microprocessor Control  
4.3.2 SETPOINTS  
Selecting SETPOINTS from the Main Menu will reveal the following menu items:  
Table 13 Setpoint functions, default values and allowable ranges  
Menu Item Function Default, °F (°C) Range, °F (°C)  
MIN TEMP SP Minimum room temperature setpoint  
72 (22)  
55 (13)  
80 (27)  
65 (18)  
50-80 (10-27)  
35 to 95 (2-35)  
35 to 95 (2-35)  
35 to 95 (2-35)  
HI CW TEMP  
HI AIR TEMP  
LO AIR TEMP  
High chilled water temperature setpoint  
High room air temperature setpoint  
Low room air temperature setpoint  
*
For optimal cooling performance, the minimum temperature setpoint should be at least 1-2° below the expected temperature at  
the remote sensor, which may require additional consideration of the remote sensor location or minimum temperature setting. If  
the minimum temperature setpoint is set above the typical remote temperature sensor reading, this will reduce the Liebert XD  
cooling output and, in extreme cases, cause erratic Liebert XD performance.  
MIN TEMP SP  
Minimum Room Temperature Setpoint—This is used to keep the room temperature above the set-  
point. The Liebert XDP can lower the room temperature too much depending on the room dew point  
and load. This setpoint will back off the cooling to keep the room temperature above this temperature.  
NOTE  
This is not a true room temperature setpoint. The Liebert XDP has no heaters; it will try to cool  
as much as possible. If it is able to cool the room to this setpoint, it will back off its cooling  
capability to try to keep the room temperature at or above this setpoint.  
HIGH CW TEMP  
High Chilled Water Temperature Setpoint—There could be many reasons that the chilled water tem-  
perature is above this setpoint (e.g., chiller problem, control valve failure, etc.) This is the setpoint at  
which the HIGH CW TEMP alarm will be activated.  
HI AIR TEMP  
High Room Air Temperature Setpoint—This is the setpoint at which the HIGH REMOTE TEMP and  
HIGH LOCAL TEMP alarms will be activated.  
LOW AIR TEMP  
Low Room Air Temperature Setpoint—This is the setpoint at which the LOW REMOTE TEMP and  
LOW LOCAL TEMP alarms will be activated.  
4.3.3 STATUS  
The user can check the status of the control valve, pump operation, and refrigerant and chilled water  
temperature.  
CONTROL VALVE—0-100%  
PUMP 1—On/Off  
PUMP 2—On/Off  
REFRIG T—Refrigerant temperature 0-100° F  
CW TEMP—Chilled Water temperature 0-100° F  
4.3.4 ACTIVE ALARMS  
This submenu allows the user to review any present alarms. If no alarms are present, the screen will read  
“No Alarms Present.” If any alarms are occurring, the screen will display “Alarm XX of YY,” followed by  
the alarm text (“XX” is the reference number of the alarm shown, “YY” is the total number of alarms).  
If more than one alarm is present, use the Up or Down arrow keys to scroll through the alarms.  
4.3.5 ALARM HISTORY  
This submenu allows the user to review the 60 most-recent alarms. The first line of the screen will  
show the alarm number—01 being the newest—and the name of the alarm. The second line of the  
screen will show the most recent alarm’s date and the time in 24 hour format. Use the Up or Down  
arrow key to scroll through the alarm history list.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Microprocessor Control  
4.3.6 TIME  
To change the time, press ENTER to select the function, then use the Up or Down arrow key to  
change the first character, press ENTER to store, then press the Up or Down arrow key to change the  
second character, press ENTER to store, etc.  
NOTE  
The clock uses the 24-hour system (for example, 17:00 would be 5:00 PM). The date and time  
are kept current even when the control board is not powered.  
4.3.7 DATE  
To change the date, press ENTER, then use the Up or Down arrow key to change the first character,  
press ENTER to store, press the Up or Down arrow key to change the second character, etc.  
4.3.8 SETUP OPERATION  
NOTE  
None of these setpoints should be changed before consulting an Emerson Network Power  
representative. Changing any of these setpoints could drastically affect the system.  
Selecting Setpoint/Setup from the Main Menu will display the following selections:  
Table 14 Setup operation functions default values and allowable ranges.  
Menu Item  
Function  
Default  
Range  
0 to 9.9 min  
(0 = manual restart)  
RESTART  
Restart time delay  
Celsius or Fahrenheit  
0.1 min  
C/F DEGREES  
F
C or F  
3 - 120 sec  
3 - 120 sec  
5 - 120 sec  
Pump 1 / Pump 2  
NA  
PUMP START TD Pump start time delay  
10 sec  
10 sec  
5 sec  
Pump 1  
NA  
PUMP WAIT TD  
PUMP OFF TD  
LEAD PUMP  
DIPSWCH  
Pump wait time delay  
Pump off time delay  
Lead Pump  
DIP switch status  
Control valve travel time  
VALVE TIME  
60 sec  
50 - 250 sec  
Use the Up and Down arrow keys to scroll through the submenu, then press the ENTER button to access  
a function. To make changes or review the current setting, see 4.3.1 - Viewing or Changing Settings.  
NOTE  
Setpoints and system setup parameters are kept in non-volatile memory.  
RESTART TIME DELAY  
This function specifies the time for the unit to restart after main power is restored to the unit. If sev-  
eral systems are operating, the time delays should be set to different values to cause a sequential  
start. Delay can be set from 0.1 minutes (6 seconds) to 9.9 minutes. Setting the value to “NO!” will  
prevent the unit from restarting when power is restored. In this case, the unit must be restarted man-  
ually by pressing the “On/Off” key.  
To make changes or review the current setting, see 4.3.1 - Viewing or Changing Settings.  
C/F DEGREES  
The control can be selected to show readings and setpoints in either degrees Fahrenheit (F) or  
Celsius (C). To make changes or review the setting, see 4.3.1 - Viewing or Changing Settings.  
PUMP START TD  
The user may set a pump start time delay (in seconds) to ensure that refrigerant begins flowing when  
the pump starts. If refrigerant does not begin flowing before this delay expires, the pump will stop for  
a period that the user may also specify (see PUMP OFF TD). After this delay, the pump will again  
begin its startup sequence.  
To make changes or review the current setting, see 4.3.1 - Viewing or Changing Settings.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Microprocessor Control  
PUMP WAIT TD  
The user may set the pump wait time delay to prevent the pump from continuing to run when refrig-  
erant is not flowing. When the control detects a loss of refrigerant flow, the pump continues operating  
for the period specified in the PUMPWAIT TD.  
If refrigerant flow resumes during the specified interval, the pump will continue operating. If the wait  
time expires and refrigerant flow has not resumed, the pump will shut down, activate an alarm for  
loss of flow to the pump and the second pump will be started.  
To make changes or review the current setting, see 4.3.1 - Viewing or Changing Settings.  
PUMP OFF TD  
The user can set the amount of time a pump will remain off when refrigerant flow is interrupted or  
stops. After the time delay has expired, the control will try to start a pump—unless there is a problem  
with the building chilled water system or if the refrigerant temperature sensor has failed.  
To make changes or review the current setting, see 4.3.1 - Viewing or Changing Settings.  
LEAD PUMP  
The user can select which pump is the lead pump, either pump #1 or pump #2. For example, if  
pump #1 is selected, it will be the primary pump and will switch to the standby pump (the pump that  
is not selected) on a loss of flow after a programmed time delay has elapsed.  
To make changes or review the current setting, see 4.3.1 - Viewing or Changing Settings.  
DPSWCH  
This menu displays the status of the eight-position DIP switch on the Liebert XDP control board. If a  
selector is beside the numeral “1,” the switch is On. If a selector is beside the numeral “0,” the switch  
is Off. For proper operation, DIP switches 1-7 MUST be off and DIP switch 8 MUST be on.  
Table 15 Liebert XDP DIP switches and factory settings  
DIP Switch Factory Setting  
1
2
3
4
5
6
7
8
Off  
Off  
Off  
Off  
Off  
Off  
Off  
On = Liebert XDP; Off = Liebert XDWP  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Microprocessor Control  
VALVE TIME  
This value is the number of seconds it takes the control valve to travel from fully closed to fully open.  
If the control loses the analog feedback position from the control valve, the control will close the valve,  
then calculate how long to open the valve for the current call for cooling.  
For example, if VALVE TIME is set to 60 seconds and there is a 50% call for cooling, the valve will  
open for 30 seconds, leaving the valve halfway open. To make changes or review the current setting,  
Scroll through this submenu by using the Up or Down arrow key. To make changes or review the cur-  
For example, to change the DEWPOINT MARGIN:  
a. From the main Status display, press MENU.  
b. Scroll to the SETPOINTS using the Up or Down arrow key.  
c. Press ENTER to select the SETPOINTS submenu.  
d. Scroll to DEWPOINT MARGIN using the Up or Down arrow key.  
e. Press ENTER  
f. Use the Up arrow key to increase the value or use the Down arrow key to lower the value.  
g. Press ENTER to store.  
NOTE  
Setpoints and system setup parameters are kept in non-volatile memory.  
4.3.9 Password Security—SETPT PASSWORD and SERVICE PASSWORD  
Setpoints, setup operations and alarm settings may be secured with three-digit passwords to prevent  
unauthorized changes. The password function for SETPT PASSWORD and for SERVICE PASS-  
WORD is enabled by default. Passwords are enabled or disabled through DIP switch #8.  
• To enable the password security feature, open the user interface display cover and set  
DIP switch #8 to the Off position, then close the cover.  
• To disable the password security feature, open the user interface display cover and set  
DIP switch #8 to the On position, then close the cover.  
Change Password—SETPT PASSWORD  
The factory default SETPT PASSWORD is “123”—this password protects setpoints and some alarm  
settings. To change the SETPT PASSWORD:  
1. Press the MENU key to display the Main Menu.  
2. Use the Up or Down arrow keys to scroll to the SETPT PASSWORD function.  
3. Press ENTER to access the SETPT PASSWORD function. The LCD will display three zeros (000).  
4. Enter the present, three-digit password.  
a. Use the Up or Down arrow key to enter the first number.  
b. Press the ENTER button to select the second number in the password.  
c. Use the Up or Down arrow key to enter the second number.  
d. Enter the third number by repeating Steps b and c.  
e. Press the ENTER button to accept the password. The LCD will display the message  
PASSWORD OK.  
5. Press the ENTER button; the LCD displays the message ENTER NEW PSW and the current  
password. The first numeral will be selected.  
6. Use the Up or Down arrow key to enter the first number of the new password. Press the ENTER  
button to select the second numeral in the password.  
7. Use the Up or Down arrow key to enter the second number of the new password. Press the  
ENTER button to select the third numeral in the password.  
8. Use the Up or Down arrow key to enter the third number of the new password. Press the ENTER  
button to save the new password.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Microprocessor Control  
Change Password—SERVICE PASSWORD  
The factory default SERVICE PASSWORD is “123”—this password protects setup operations and  
more-critical alarm settings. To change the SERVICE PASSWORD:  
1. Press the MENU key to display the Main Menu.  
2. Use the Up or Down arrow key to scroll to the SERVICE PASSWORD function.  
3. Press ENTER to access the SERVICE PASSWORD function. The LCD will display three zeros (000).  
4. Enter the present, three-digit password.  
a. Use the Up or Down arrow key to enter the first number.  
b. Press the ENTER button to select the second number in the password.  
c. Use the Up or Down arrow key to enter the second number.  
d. Enter the third number by repeating Steps b and c.  
e. Press the ENTER button to accept the password. The LCD will display the message  
PASSWORD OK.  
5. Press the ENTER button; the LCD displays the message ENTER NEW PSW and the current  
password. The first numeral will be selected.  
6. Use the Up or Down arrow key to enter the first number of the new password. Press the ENTER  
button to select the second numeral in the password.  
7. Use the Up or Down arrow key to enter the second number of the new password. Press the  
ENTER button to select the third numeral in the password.  
8. Use the Up or Down arrow key to enter the third number of the new password. Press the ENTER  
button to save the new password.  
4.3.10 CALIBRATE SENSOR  
The local and the remote temperature and humidity sensors can be calibrated by selecting this menu  
item. The temperature sensor can be calibrated ± 5°F and the humidity sensor can be calibrated  
±10% RH. To prevent coil condensation that could damage the Liebert XDP, the sensors must be cali-  
brated to a known source.  
4.3.11 ALARM ENABLE  
Some alarms can be disabled or enabled as part of the user’s customized setup. An alarm that has  
been disabled will not report to the wall box beeper nor to the common alarm relay. Alarms are  
enabled by default.  
Use the Up or Down arrow key to select a particular alarm; “YES” enables the alarm, “NO” disables  
the alarm. Press ENTER to save the change.  
4.3.12 ALARM TIME DELAY  
Some alarms can be programmed with a time delay as a means of preventing nuisance alarms. This  
function specifies the amount of time an alarm must be present before the Liebert XDP recognizes  
and annunciates the alarm. If the alarm condition goes away before the time delay has expired, the  
alarm will not be recognized, and the time delay timer will be reset.  
4.3.13 COM ALARM ENABLE  
Each individual alarm can be selected to energize or not to energize the common alarm relay. If the  
energize common alarm function is set to YES, the relay is energized immediately as the alarm is  
annunciated and de-energized when the alarm condition goes away (only after the alarm has been  
recognized). If the alarm is completely DISABLED, the alarm has no effect on the common alarm  
relay.  
Use the Up or Down arrow key to scroll to a particular alarm, press the ENTER button to select it,  
then press the ENTER button to change the state (Yes or No).  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Microprocessor Control  
4.3.14 CUSTOM ALARMS  
This is the menu where the user selects the alarm message that will be displayed when there is an  
input to the customer alarm input on the control board. This menu has four choices: one user-defined  
custom message (see CUSTOM TEXT below for details) and three preprogrammed messages:  
• SMOKE DETECTED  
• CUSTOM 1 (default custom message. If the user enters a custom text message, that custom text  
will replace “CUSTOM 1.”)  
• WATER FLOW LOSS  
• STANDBY UNIT ON  
1. Press the ENTER button to access the menu  
2. Use the Up or Down arrow key to view the messages.  
3. Press the ENTER button to select the message to be displayed.  
4.3.15 CUSTOM TEXT  
This menu permits the user to set up a custom text message with a maximum length of 16 characters.  
The message may use any of the following characters or a blank space:  
ABCDEFGHIJKLMNOPQURSTUVWXYZ#%*-0123456789  
This custom text can be designated as the custom alarm text in the “CUSTOM ALARMS” menu (see  
CUSTOM ALARMS above). To define the message:  
1. Press the ENTER button to access the menu.  
2. Use the Up or Down arrow key to change the character with the pointer below it.  
3. Press the ENTER button to go to the next character.  
4. Repeat the steps for all characters in the message (maximum of 16 characters).  
5. Press the ENTER button to accept new custom text.  
4.3.16 DIAGNOSTICS  
This allows the user to perform checks on inputs, outputs, and conduct a test of the Liebert XDP con-  
trol board from the wall box.  
Entering the “TEST OUTPUTS” will interrupt system operation. Selecting “TEST INPUTS” or “TEST  
MICRO” will not interrupt system operation. Pressing ENTER and selecting “TEST OUTPUTS” will  
permit the user to toggle the following outputs On and Off:  
PUMP 1—On/Off  
PUMP 2—On/Off  
CTR VALVE XX.Xma—OPEN/CLOSE (control valve and 4-20mA feedback signal)  
GREEN LAMP—On/Off  
RED LAMP—On/Off  
COMMON ALARM—On/Off  
Pressing ENTER and selecting “TEST INPUTS” will permit the user to read the following inputs:  
INPUT POWER—On/Off  
CONDENSATION—On/Off (condensation detection)  
DIFF PRESSURE—On/Off (differential pressure switch)  
CUSTOMER ALARM—On/Off  
Pressing ENTER and selecting “TEST MICRO” will permit the user to test the microcontroller and  
associated circuitry on the Liebert XDP control board.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Alarm Descriptions and Solutions  
5.0 ALARM DESCRIPTIONS AND SOLUTIONS  
5.1  
Alarm Descriptions  
NOTE  
Alarms must be acknowledged before they can be reset. To acknowledge or silence an alarm,  
press the ALARM SILENCE / ? key.  
LOSS OF FLOW P1—Activated when Pump 1 is commanded to run and the differential pres-  
sure switch does not sense differential pressure (set at 6 psi; 41kPa; 0.41 bars). After attempting  
to start Pump 1 for 120 seconds (including time delays), the Liebert XDP will automatically  
switch to the other pump to establish flow.  
LOSS OF FLOW P2—Activated when Pump 2 is commanded to run and the differential pres-  
sure switch does not sense differential pressure (set at 6 psi; 41kPa; 0.41 bars). After attempting  
to start Pump 2 for 120 seconds (including time delays), the Liebert XDP will automatically  
switch to the other pump to establish flow.  
SHORT CYCLE—Activated when the Liebert XDP is trying to establish flow (differential pres-  
sure), and it is unable to do it. The Liebert XDP will attempt to establish flow for 4 minutes on  
each pump, for a total of 8 minutes. If this “cycling” occurs within 30 minutes and the Liebert  
XDP still does not establish flow, a SHORT CYCLE alarm will be present. This alarm will shut  
down the Liebert XDP. Main power (disconnect switch) must be turned Off, then back On to clear  
this alarm. The cycling time for the SHORT CYCLE alarm can be adjusted from the default of 30  
minutes; the range is from 10 minutes to 60 minutes.  
CONDENSATION!—Activated when water is detected at the Liebert XD cooling module (24VAC  
is applied to the condensation input on the control). When this alarm is active, the control will  
raise its refrigerant control point by 4°F (-16°C). Alarm will reset when the 24VAC signal ends or  
main power is removed.  
VALVE FAILURE—Activated when the chilled water control valve has been commanded by the  
control to open or close and no change is detected from the valve-position signal. The control will  
close the valve and then try to control the control valve based on its travel time. Main power (dis-  
connect switch) must be turned Off, then back On to clear this alarm.  
CUSTOMER ALRM—Activated when 24VAC signal is applied to the customer alarm input on  
the control board. Alarm will reset when the 24VAC signal is taken away.  
HIGH CW TEMP—Activated when entering chilled water temperature exceeds the user speci-  
fied setpoint. The alarm will reset itself when the entering chilled water temperature drops below  
the setpoint.  
FAILED CW SENSOR—Activated when the control stops receiving a signal from the entering  
chilled water temperature sensor. The alarm will reset itself when the temperature sensor signal  
is re-established.  
HIGH REMOTE TEMP & HIGH LOCAL TEMP—Activated when the remote or local temper-  
ature exceeds the user specified setpoint. The alarm will reset itself when the room temperature  
drops below the setpoint.  
LOW REMOTE TEMP & LOW LOCAL TEMP—Activated when the remote or local tempera-  
ture is below the user-specified setpoint. The alarm will reset itself when the room temperature  
raises above the setpoint.  
REMOTE SENS PROB—Activated when no signal is present from the remote temperature or  
humidity sensors. Alarm will reset when the temperature and humidity signals are re-estab-  
lished.  
LOCAL SENS PROB—Activated when no signal is present from the local temperature or  
humidity sensors or when communication with the display is lost. The alarm will reset when the  
temperature and humidity signals are re-established.  
HIGH REFRIG TEMP—Activated when the refrigerant temperature exceeds the user-specified  
setpoint. The alarm will reset itself when the refrigerant temperature drops below the setpoint.  
LOW REFRIG TEMP—Activated when the refrigerant temperature drops 1.5°F (1°C) below the  
refrigerant temperature control point. The alarm will reset itself if the refrigerant temperature  
rises before the control shuts down because of low refrigerant temperature.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Alarm Descriptions and Solutions  
REFRIG SENS FAIL—Activated when the control stops receiving a signal from the refrigerant  
temperature sensor. If this alarm becomes active, the control will close the control valve over a  
9-minute period. This alarm will shut down the Liebert XDP. Main power must be (disconnect  
switch) must be turned Off, then back On to clear this alarm.  
LOSS OF POWER—Activated when the unit is On and operational and 24VAC power to the con-  
trol is lost. This alarm will be emitted when power is restored to the control. The Liebert XDP will  
restart at a user-defined time delay after power is restored. The alarm will reset itself after 30  
seconds of run time.  
5.2  
5.3  
Red and Green Lamp Indicators  
• The Green lamp will be on only when The Liebert XDP is On and running with no alarms.  
• The Red lamp will be on if the unit is On and running with an active alarm, or if the unit is shut  
down because of a certain alarm.  
• The Red lamp will flash when an alarm is being annunciated. The Red lamp will stop flashing and  
the beeper in the display will stop beeping when the ALARM SILENCE / ? key is pressed.  
Alter Alarm Settings  
5.3.1 Enable or Disable Alarms  
At the user’s discretion, some alarms may be enabled or disabled. If an alarm is disabled, the alarm  
condition will not be monitored and will not trip, will not be in ACTIVE ALARMS, will not be in  
ALARM HISTORY and will not be annunciated.  
These alarms may be enabled or disabled:  
• LOSS OF FLOW P1—loss of refrigerant flow with Pump 1 alarm  
• LOSS OF FLOW P2—loss of refrigerant flow with Pump 2 alarm  
• VALVE FAILURE—chilled water control valve failure alarm  
• CUSTOMER—customer alarm  
• HI RMT TEMP—high remote temperature alarm  
• LO RMT TEMP—low remote temperature alarm  
• HI LCL TEMP—high local temperature alarm  
• LO LCL TEMP—low local temperature alarm  
To determine whether an alarm is enabled or disabled:  
1. Press the MENU key.  
2. Use the Up and Down arrow keys to move to the ALARM ENABLE menu.  
3. Press the ENTER key to access the menu. Use the Up and Down arrow keys to move through the  
menu and view which alarms are enabled or disabled. (“YES” means that the alarm is enabled,  
“NO” means that the alarm is disabled.)  
To change an alarm from enabled to disabled, or vice versa  
1. Determine whether the alarm is enabled or disabled (see above).  
2. Use the Up and Down arrow keys to scroll to the alarm to be changed.  
3. Press the ENTER key. (The control will ask for a service password if passwords are enabled. Use  
the Up and Down arrow keys and ENTER key to enter the three-digit password.)  
4. Press the ENTER key again to change the alarm.  
5. Press the ESC key two to three times to return to the main display.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Alarm Descriptions and Solutions  
5.3.2 Increase or Decrease Alarm Time Delays  
An alarm time delay is the time that the a condition must exist before the control activates an alarm  
for that condition. This can be used as a filter to prevent nuisance alarms from transient events.  
These alarms may have their time delays changed:  
• CUSTOMER—customer alarm  
• HIGH CW TEMP—high chilled water temperature alarm  
• HI RMT TEMP—high remote temperature alarm  
• LO RMT TEMP—low remote temperature alarm  
• HI LCL TEMP—high local temperature alarm  
• LO LCL TEMP—low local temperature alarm  
• LOW REFRIG TEMP—low refrigerant temperature alarm  
To view the time delay for an alarm:  
1. Press the MENU key.  
2. Use the Up and Down arrow keys to move to the ALARM TIME DELAY menu. Press the ENTER  
key to enter into the menu. Use the Up and Down arrow keys to move through the menu and view  
the alarm time delays.  
To change the time delay for an alarm:  
1. Press the ENTER key. (The control will ask for a service password if passwords are enabled. Use  
the Up and Down arrow keys and ENTER key to enter the three-digit password when prompted.)  
2. Press the ENTER key again on the alarm to select the alarm to be changed.  
3. Use the Up and Down arrow keys to change the alarm time delay.  
4. Press the ENTER key to record the change.  
5. Press the ESC key two to three times to return to the main display.  
5.4  
System Shutdown Causes  
Unit Is Off By Refrig Sens Fail  
The control has lost its signal from the refrigerant temperature sensor. The control has no way of  
controlling the refrigerant temperature, so the unit is shut off. Main power (disconnect switch)  
must be turned Off, then back On to clear this alarm.  
Unit Is Off By High CW Temp  
The entering chilled water temperature is too high to keep the refrigerant pump(s) running nor-  
mally. If there is a HIGH CW TEMP alarm and the refrigerant pump loses flow (differential pres-  
sure), the Liebert XDP will immediately attempt to restart the pumps and re-establish flow. If  
flow is still not established, then the Liebert XDP will go into a pre-chill mode. The Liebert XDP  
can attempt to start again only if the entering chilled water temperature drops below the HIGH  
CW TEMP setpoint.  
Unit Is Off By Pump Short Cycle  
The control was unable to get a pump started upon startup or after a loss of differential pressure.  
The control looks at the SHORT CYCLE time delay. If it cannot establish differential pressure  
within that amount of time, the unit is shut down. This time is adjustable through the SHORT  
CYCLE alarm time delay. Main power (disconnect switch) must be turned Off, then back On to  
clear this alarm.  
Unit Is Off By Low Refrig Temp  
The control was unable to raise the refrigerant temperature to the calculated refrigerant temper-  
ature control point. The unit is shut down because if the control cannot raise the refrigerant tem-  
perature to the calculated refrigerant temperature control point, water may condense on the  
refrigerant piping and receiving coils. Main power (disconnect switch) must be turned Off, then  
back On to clear this alarm.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Troubleshooting  
6.0 TROUBLESHOOTING  
Table 16 Troubleshooting the XDP  
Symptom  
Possible Cause  
Check or Remedy  
Check L1, L2 and L3 for rated voltage.  
Tighten connections.  
No main power  
Loose electrical connections  
Overloads tripped  
Pump will not energize  
Allow pump to cool. Check amp draw.  
Check circuit breaker to pump(s).  
See Table 5.  
Tripped circuit breaker  
Incorrect phase wiring  
Check and verify that there is supply chilled water to the  
Liebert XDP.  
No chilled water  
Isolation valve(s) on pump suction  
and/or discharge is closed.  
Open all isolation valves completely during normal  
operation.  
Check and verify that the chilled water temperature  
setpoint is at 50°F (10°C) or lower and that there is flow  
on the chilled water side.  
Pump will not run  
Supply chilled water is too high  
Check Liebert XD cooling module to make sure that they  
are On prior to starting the Liebert XDP.  
Liebert XD cooling modules are Off  
Check alarm(s) history on Liebert XDP. The Liebert XDP  
was operating below the dew point for a significant  
amount of time. Check humidity in conditioned space,  
lower humidity if necessary to allow Liebert XDP to  
operate at a lower temperature. (Disconnect must be  
switched to Off then back On to allow Liebert XDP to  
reset itself).  
Low Refrigerant Temperature (high  
dew point)  
Place the sensor on the RETURN AIR side of the primary  
air mover (e.g., Liebert Deluxe System 3). Do not install  
the sensor near unsealed doors, windows and similar  
areas.  
Incorrect location of  
temperature-humidity sensors  
Check both differential pressure settings. If not within  
6 psi, ±1 psi (41kPa, ±7kPa; 0.41 bars, ±0.07bars) then  
manually change accordingly.  
Pressure switch not making contact  
Not enough charge  
Check for adequate charge in system, refer to the User's  
Cavitation due to vapor in pump  
Worn motor bearings  
Pump noisy  
Replace pump  
Check humidity of room along with location of remote  
sensors. Make sure that the sensors are not located in a  
cold area where there is a lack of sufficient air flow.  
Low Refrigerant Temperature (High  
dew point)  
Liebert XDP (Pump)  
suddenly stops  
Clogged filter/dryer and/or impeller  
Loose pipe connections  
Clean out debris.  
Pipe rattle  
Check pipe connections  
Chilled water valve not  
working  
Check linkage for adjustment and be sure that it is tight on  
the valve.  
Motor operates but valve won't open  
No 24 VAC power to motor  
No signal from control  
Check for 24 VAC between P2-1 and P2-4.  
Check 24 VAC at P22-1 (close) or P22-3 (open).  
Unplug P22 completely off of the board. Jumper P22-5 to  
P2-4 for grounding, then jumper P22-1 to P2-1 to drive  
close. Remove jumper to close, and then jumper P22-3 to  
P2-1 to drive open. If motor fails to work, replace it.  
Actuator motors  
Motor not operating  
Check control panel for welded  
contactor contacts or welded  
overload contacts  
Motor burnout  
Replace defective components.  
Shorts or loose connections  
Faulty circuit board  
Check the wiring connections of the 24 VAC circuit.  
Replace the circuit board.  
Main 24 VAC fuse trips  
Unstable pump  
operation  
While pump is running R-134a receiver level must be  
within recommended levels (see Figure 21).  
R-134a pump loop is overcharged  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Maintenance  
7.0 MAINTENANCE  
The Liebert XD system components require little maintenance when proper fluid levels are main-  
tained and proper startup and operation procedures are followed. The following tasks should be per-  
formed at the intervals stated:  
1. Clean or replace chilled water strainer annually. Adjust accordingly based on purity of chilled  
water.  
2. Check sight glass level of receiver every 4-6 weeks. During normal operation, the level should be  
at or above the second sight glass.  
3. Check system for leaks every 4-6 weeks.  
7.1  
Fluorinated Greenhouse Gas Requirements  
Stationary air conditioning, refrigeration, heat pump equipments and stationary fire protection sys-  
tems in the European Community market and operating with fluorinated greenhouse gases (f-gas),  
such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (F-gas).  
The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the atmo-  
sphere.  
The F-Gas Regulation requires operators to use use all measures that are technically feasible and do  
not entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to  
recover f-gas during equipment service and maintenance and before disposing of equipment.  
Refer to the full regulation for additional details.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Specifications  
8.0 SPECIFICATIONS  
Table 17 Liebert XDP160 specifications  
Models  
XDP160RC--1  
XDP160RA--1  
XDP160RM--1  
140kW / 40 Tons, 50Hz  
160kW / 46 Tons, 60Hz  
Each capacity is based on 45ºF (7ºC) entering water temperature and  
140gpm (530lpm) water flow rate. Capacity is reduced when glycol mixtures  
are used in place of 100% water.  
Cooling Capacity, Nominal  
The Liebert XDP’s minimum recommended operating load is 20% of system  
nominal capacity. For example, a Liebert XDP160 60Hz system’s minimum  
load would be 32 kW. Loading below this value can unfavorably affect system  
operation. Consult factory for any loading below this recommendation.  
Minimum Load  
Electrical Requirements  
Input  
Full Load Amps  
Dimensions, inches (mm)  
208V/3ph/60Hz  
4A  
460V/3/ph60Hz  
2.1A  
380/415V/3ph/50Hz  
2.3A  
Height – Unit only  
Height – As shipped  
Width  
78 (1981)  
83 (2108)  
38 (965)  
34 (864)  
Depth  
Weight, lb (kg)  
Unit only  
821 (372)  
Shipping weight  
Domestic: 990 (449); Export: 1067 (484)  
Installed, with refrigerant and  
chilled water  
1038 (471)  
Pipe Connections  
Refrigerant supply to Liebert XD  
cooling module  
1-1/8" OD, Cu  
Refrigerant return from Liebert XD  
cooling module  
2-1/8" OD, Cu  
2-5/8" OD, Cu  
Chilled water supply and return  
2-way, 2" nominal; 35 PSIG close off pressure rating;  
150 PSIG maximum allowable pressure  
Control Valve  
Pressure Drop – Chilled Water  
Side  
20 psig (137kPa, 1.38bar), with 140 gpm (530lpm) water flow rate,  
control valve fully open  
Temperature Rise – Chilled  
Water Side at rated flow, °F (°C)  
8.0 (4.4)  
6.9 (3.8)  
Number of Liebert XD cooling units connected, maximum (minimum)  
Liebert XDCF10  
Liebert XDH20  
Liebert XDH32  
Liebert XDV8  
16 (4)  
8 (2)  
5 (1)  
20 (4)  
16 (4)  
10 (2)  
8 (2)  
Liebert XDV10  
Liebert XDO16  
Liebert XDO20  
Cabinet Exterior Finish  
Black, matte finish, heat-fused powder coat  
Operating Ambient  
Temperature, Maximum, °F (°C)  
86 (30)  
Agency  
Approvals  
CSA 60Hz  
CE 50Hz  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Ensuring The High Availability  
0f Mission-Critical Data And Applications.  
Technical Support / Service  
Web Site  
Emerson Network Power, the global leader in enabling business-critical  
continuity, ensures network resiliency and adaptability through  
a family of technologies—including Liebert power and cooling  
technologies—that protect and support business-critical systems.  
Liebert solutions employ an adaptive architecture that responds  
to changes in criticality, density and capacity. Enterprises benefit  
from greater IT system availability, operational flexibility and  
reduced capital equipment and operating costs.  
Monitoring  
800-222-5877  
Outside the US: 614-841-6755  
Single-Phase UPS  
800-222-5877  
Outside the US: 614-841-6755  
Three-Phase UPS  
800-543-2378  
Environmental Systems  
800-543-2778  
Outside the United States  
614-888-0246  
Locations  
United States  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
Europe  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD) Italy  
+39 049 9719 111  
Fax: +39 049 5841 257  
Asia  
7/F, Dah Sing Financial Centre  
108 Gloucester Road, Wanchai  
Hong Kong  
While every precaution has been taken to ensure the accuracy  
and completeness of this literature, Liebert Corporation assumes no  
responsibility and disclaims all liability for damages resulting from use of  
this information or for any errors or omissions.  
© 2008 Liebert Corporation  
All rights reserved throughout the world. Specifications subject to change  
without notice.  
852 2572220  
Fax: 852 28029250  
® Liebert is a registered trademark of Liebert Corporation.  
All names referred to are trademarks  
or registered trademarks of their respective owners.  
SL-16641_REV11_06-08  
Emerson Network Power.  
The global leader in enabling Business-Critical Continuity.  
EmersonNetworkPower.com  
AC Power  
Connectivity  
DC Power  
Embedded Computing  
Embedded Power  
Monitoring  
Outside Plant  
Racks & Integrated Cabinets  
Power Switching & Controls  
Services  
Precision Cooling  
Surge Protection  
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.  
©2008 Emerson Electric Co.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Lenovo Laptop B470E User Manual
Lenovo Server RD430 User Manual
LG Electronics Refrigerator LRSC 26910SW User Manual
Liebert Power Supply GXT2 3X1 User Manual
Lindy Computer Accessories 51245 User Manual
Makita Staple Gun T220D User Manual
Meade Telescope LXD75 User Manual
Memorex DVD Recorder E IDE User Manual
Meridian Data GPS Receiver Transplant CF LP GPS Receiver User Manual
Meyer Spreader 2636 User Manual