Liebert Network Card XDK User Manual

Precision Cooling  
For Business-Critical Continuity™  
Liebert XDKRack Enclosure With Integrated Water-Based Cooling  
User Manual–17kW  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
8.2  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURES  
Figure 1  
TABLES  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
1.0 INTRODUCTION  
The Liebert XDK provides the dissipation of heat loads up to 17kW.  
The server rack is closed to the installation area, that means no heat load will dissipate to the envi-  
ronment. (see also chapter 2.) The cooling is provided by a closed cooling system via an air-to-water  
heat exchanger. The cooling capacity adapts to the heat load.  
19" (483mm) rails are designed for components as well as rails and shelves.  
Cable entry is possible from the bottom and from the top.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operating Conditions  
2.0 OPERATING CONDITIONS  
2.1 Proper Application  
The XDK is a water-cooled enclosure and is intended for removing heat from electronic equipment  
inside the cabinet. The cooling system in the cabinet is thermally independent of the room air. Water  
is used to cool equipment installed in the XDK. No additional cooling of the server room is required.  
NOTE  
Under certain conditions, a small amount of heat, (approximately 0.5kW), can escape into the  
room.  
CAUTION  
!
Risk of improper operation. Can cause equipment damage. For reliable function of the XDK,  
cold water must be available in the correct amount, and at the correct temperature and  
pressure. Observe water quality specified in VGB-R 455 P. (see 8.0 - Water Purity  
Table 1  
General operating data  
50°F to 95°F (10°C to 35°C)  
(other temperatures upon request)  
Ambient temperature  
Absolute humidity in the installation location  
Water temperature, supply  
Water temperature, return  
Water connection  
8g H O/ kg air maximum  
2
54°F (12°C); other temperatures upon request  
64°F (18°C); other temperatures upon request  
from below  
Condensed water connection  
Nominal voltage  
from below  
200V to 264V (50Hz and 60 Hz)  
145 PSI (10 bar)  
Maximum operating pressure  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Description  
3.0 DESCRIPTION  
3.1 General function  
The modular design facilitates the installation of 19-inch-wide equipment of varying depth.  
Heat produced by equipment in the cabinet, such as servers, is removed by the cold water system  
integrated into the server cabinet. The cooling system is isolated from the server area, protecting the  
sensitive equipment from water damage.  
The cooling system comprises a high-performance air/water heat exchanger, fans with fan control  
unit, fan-speed according to heat load.  
The air circuit is closed such that no heat is emitted to the environment.  
CAUTION  
!
Risk of improper operation. Can cause equipment damage.  
The XDK works only if cold server feed air and heated server outlet air are fully separated.  
Height units not in use must be sealed with blanking panels.  
Figure 1  
Cooling airflow, top view  
Air Duct  
Warm Warm  
Warm  
Server  
Cold  
Warm  
Air  
Separation  
Cold  
Front  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Description  
3.2  
Principle of Cooling Operation  
Figure 2  
Cooling airflow, side view  
Fan  
Bank  
Rear  
of  
XDK  
Front  
of  
XDK  
19" Equipment  
Air / Water  
Heat Exchanger  
Cold Water Supply  
Side of XDK  
Air that has been heated by the servers to 95°F (35°C), for example, is circulated to a specially  
designed air/water heat exchanger by high-performance fans. The heated air is cooled to 68-77°F  
(20-25°C) and fed to the front of the server.  
The server fans can draw in the air and feed it over internal components.  
Cold water is provided by a separate Liebert XD Pumping unit.  
A condensate tray with a 5/8" outlet is below the heat exchanger.  
NOTE  
If the rear door (with fans) is opened, the front door must be opened. If the front door is opened,  
it is not necessary to open the rear door.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Description  
Table 2  
Technical data  
Housing material Aluminium sheet, sheet steel, galvanized and coated  
Operating Temperature range 50°F to 95°F (10°C to 35°C)  
Abs. atmospheric humidity 8g / kg maximum  
Temperature difference across server approx. 15K  
Noise level 55 dB(A) sound pressure at a distance of 3 ft. (1m)  
Useful load 2204 lb (1000kg)  
Cold Water  
Cooling capacity 17kW  
Supply temperature 54°F (12°C) (other temperatures upon consultation)  
Return temperature 64°F to 72°F (18°C to 22°C) (other temperatures upon consultation)  
Max. operating pressure 145 PSI (10 bar)  
Water supply connection 1"  
3.2.1 Data Overview—XDK  
Table 3  
XDK general data  
Nominal Cooling Capacity  
Height, in (mm)  
Width, in (mm)  
Depth, in (mm)  
17kW @ 54°F (12°C) EFT  
86.6 (2200)  
31.5 (800)  
47 (1200)  
Usable Height for Electronic  
Equipment  
40 U  
Maximum Electronic  
Equipment Depth, in (mm)  
29 (740)  
68/98 (20/37  
Electronic Equipment  
Air Temperature, In/Out, °F (°C)  
Weight, Empty, lb (kg)  
Maximum Weight, Filled  
683 (310)  
2,800 (1310)  
Maximum Operating  
Water Pressure, psi (bar)  
145 (10)  
3
Water Flow Rate, GPM (m /h)  
10.7 (2.44)  
10 (0.7)  
1
Water Pressure Drop, psi (bar)  
Water Connections, in  
3
Maximum Air Flow, CFM ( m /h) 1800 (3,100)  
Sound Pressure Level  
Input Voltage  
55 dB(A) at 3 ft (1m)  
200-264 V, 1 ph, 50/60 Hz  
1400W  
Maximum Power Draw  
Options  
Leveling Feet or Casters  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Description  
3.3  
Control  
The server cabinet temperature is controlled by the fan control board  
A temperature sensor continuously measures the temperature of the server cabinet (server feed air).  
The air circulation flow rate is controlled by the fan speed according to the current thermal load.  
At temperatures lower than 70°F (21°C) fans rotate at 75% of maximum speed.  
Between 68°F and 73°F (20 and 23°C), speed increases proportionally to the temperature up to 96% of  
maximum speed.  
The failure of the temperature sensor set the fans to maximum speed.  
The water flow rate is controlled by a three-way valve depending on thermal load. In case of failure,  
the valve opens and the all the chilled water flows through the heat exchanger.  
From 61°F to 66°F (16°C to 19°C), the three-way valve controls the water flow rate from 0% to 100% of  
the nominal flow rate.  
The programming of the control is factory-set and protected with a password.  
The failure of the temperature sensor or one of the fans will set off an alarm using a potential free  
contact.  
The outgoing alarms with potential free contact are:  
• sensor error  
• fan malfunction  
• high-temperature / low-temperature  
The fans are automatically shut down if the server cabinet rear door is opened.  
3.4  
Automatic Door Opening  
Figure 3  
XDK door and automatic opening mechanism  
Gas pressure spring  
Upper magnet  
and retaining  
plate  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Description  
3.4.1 Function  
Front and rear door are kept closed with two electromagnets. The door will be pushed open smoothly  
by a gas pressure spring if power to the electromagnets fails.  
If the doors are opened, the thermal load can escape into the room, preventing the servers from over-  
heating.  
The inflow of air with water droplets can also be prevented (Door opening due to humidity alarm).  
When the rear door is opened, the fans shut down automatically.  
Figure 4  
Door locking mechanisms, opening switch  
Upper and lower  
transport-lock  
screw  
Door opening switch  
with LED (green)  
3.4.2 Initial Commissioning:  
___ 1. Loosen the upper and lower transport lock screw  
___ 2. Connect inlet power to the power supply (See 3.4.3 - Manual Closing.)  
NOTE  
If the power supply fails during initial commissioning, the front door opens automatically. If  
the transport lock screws are reinstalled, both transport lock screws must be reinserted or the  
door could be damaged  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Description  
3.4.3 Manual Closing  
1. Press LED switch for electromagnet activation  
2. The LED lights up  
3. Push door evenly shut. Both magnetic locks must latch.  
3.4.4 Manual Opening  
1. Press LED switch - green LED doesn’t light  
2. Rack door opens itself  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Equipment Inspection, Handling And Storage  
4.0 EQUIPMENT INSPECTION, HANDLING AND STORAGE  
Upon arrival of the unit, and before unpacking, verify that the labeled equipment matches the bill of  
lading. Inspect all items for damage, either visible or concealed. Damage should be immediately  
reported to the carrier and a damage claim filed with a copy sent to your local sales representative.  
4.1  
Packaging Material  
All material used to package this unit is recyclable. Please save for future use or  
dispose of the material appropriately.  
R
SAFETY INFORMATION  
WARNING  
!
Risk of top-heavy unit falling over. Improper handling can cause equipment damage, injury or  
death! Read all of the following instructions before attempting to move, lift, remove packaging  
from or preparing unit for installation.  
WARNING  
!
Risk of sharp edges, splinters and exposed fasteners. Can cause personal injury.  
Only properly trained personnel wearing appropriate safety headgear, gloves, shoes and  
glasses should attempt to move, lift, remove packaging from or prepare unit for installation.  
CAUTION  
!
!
Risk of overhead interference. Can cause unit and/or structure damage.  
Refer to the installation plans prior to moving the unit to verify clearances.  
CAUTION  
Risk of damage from fork lift! Improper handling with the forklift can cause exterior and/or  
underside damage! Keep tines of the fork lift level and at a height suitable to fit below the  
skid.  
4.2  
Handling  
When possible, transport the unit using a forklift or pallet jack. Otherwise use a crane with belts or  
cables.  
• When using a forklift or pallet jack, make sure the forks (if adjustable) are spread to the widest  
allowable distance that will fit under the skid.  
• Ensure that the fork length is suitable for the unit length.  
• When using a forklift while moving the packaged XDK, do not lift it higher than 6" (152mm).  
• If circumstances require the XDK to be lifted higher than 6" (152mm), great care must be exer-  
cised. Personnel not involved in moving the unit must be at least 20' (5m) from the lift point of the  
unit.  
• Belts or cables must be used when the XDK is moved with a crane.  
• The XDK’s net weight is 749 lb. (340 kg).  
• Avoid twisting the housing or other damage during handling.  
• Ensure that the XDK’s doors are closed prior to lifting.  
• Do not stand under an XDK while it is suspended.  
• Hooks used to attach to the unit must be of appropriate tensile strength.  
• The XDK must not be lifted at an angle.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Equipment Inspection, Handling And Storage  
4.3  
4.4  
Storage  
• If the XDK’s packaging has been removed, cover it with tarpaulins to protect against particulates,  
such as sand and dust, and from moisture.  
• Keep storage temperature between -22°F and 104°F (-30°C and +40°C).  
• The heat exchanger must be completely drained to prevent the risk of freezing damage.  
• When stored for more than 12 months, turn fans by hand to check the fan bearings prior to instal-  
lation.  
Returning the Unit in Case of Damage  
If the XDK is not returned in its original packaging, the packaging used for return must comply with  
the following:  
• There must be at least 1-3/16" (30mm) space between the unit and the packaging.  
• Footprint of the skid shall extend at least 2-1/2" (64mm) from the perimeter of the unit.  
• The XDK must be attached to the skid using original metal brackets or steel banding.  
If steel banding is used to hold unit to the skid, place reinforced protective material between the  
banding and the XDK.  
• Ensure proper shipping information is affixed to the exterior of the packaging.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installation and Commissioning  
5.0 INSTALLATION AND COMMISSIONING  
5.1  
Preparation for Installation  
CAUTION  
!
Risk of improper installation. Can cause equipment damage.  
Before installing the unit, a number of points must be checked for safety and to ensure the  
correct function of the server cabinet. Take care when performing these checks to ensure that  
the unit functions correctly.  
CAUTION  
!
Risk of improper installation. Can cause equipment damage.  
The XDK must be installed on a level surface. For this reason, check the horizontal alignment  
with a spirit level prior to starting installation. The floor must be able to support a rack load  
of 307 lb/ft² (1500 kg/m²) (with installed equipment per XDK).  
To achieve good air circulation, ensure that there is no packaging material or other equipment that  
could hinder or prevent air circulation in the area of the equipment, in the area of the heat exchanger,  
in the air inlet or in the air outlet.  
5.2  
Positioning the XDK  
After positioning, the XDK’s feet must be adjusted to make the cabinet vertical. When positioned the  
doors must close easily.  
5.2.1 Remove Recirculation Air Duct Transport Lock  
The Liebert XDK is shipped without the gas pressure springs for the front and rear automatic door  
openers installed. The springs should be installed according to separate instructions before the Lie-  
bert XDK is connected and turned on.  
After positioning, remove the transport lock screws at the sides of the recirculation air duct (see  
The recirculation air duct may be pulled out to remove items that fall into the heat exchanger tray.  
Figure 5  
Remove the transport lock screws  
Remove both screws  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Installation and Commissioning  
5.3  
Water Connection  
The heat exchanger can be pulled out for servicing  
Water pipes should be connected so that the heat exchanger can be pulled out when the connection is  
undone. If the heat exchanger is connected to the water circuit using threaded fittings, the pipe fitting  
must be supported on tightening.  
Before commissioning the server cabinet, the pipe connections should be checked for leaks according  
to local codes.  
5.3.1 Preparing Heat Exchanger for Initial Commissioning  
Check the mechanical installation and the supply pipe connection.  
Figure 6  
Heat exchanger access  
Remove this air duct  
for bleeding, draining the  
heat exchanger and  
checking the valve  
1. Carefully bleed heat exchanger when filling the system.  
2. Open the air bleed valve until the water coming out has no bubbles.  
3. Close this valve after bleeding.  
Figure 7  
Control valve  
Air bleed valve  
Water return  
Water supply  
Drain valve  
4. If necessary, retighten threaded fittings.  
5. After an extended period without use, and particularly in case of risk of freezing temperatures,  
the heat exchanger and the supply pipe must be drained of all fluid.  
6. Drain completely by blowing out with compressed air and remove all bleed and drain plugs.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Installation and Commissioning  
Figure 8  
Heat exchanger  
27-3/8"  
(695mm)  
33-7/16"  
(850mm)  
Space  
for  
Cabling  
9-7/8"  
(150mm)  
2"  
(50mm)  
2"  
(50mm)  
Top View  
Figure 9  
Heat exchanger connection  
Water return  
Water supply  
Liebert recommends insulating the cold water pipes with waterproof insulation to prevent condensa-  
tion and losses.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installation and Commissioning  
Figure 10 Bottom plate with cutouts  
Sealed Cable Cutout  
Rear  
Network  
Cable  
Entry  
Cutout for  
Water Pipes  
Condensed  
Water Cutouts  
Front  
Cable and pipe openings must be sealed air-tight on completion of work.  
5.4  
Condensed Water Connection  
If the XDK is operated below dew point, condensed water may occur. As standard there is a water con-  
nection, 5/8" diameter, in the condensed water tray for drainage.  
Preparations for Connecting  
Step 1):  
Remove  
the air  
duct  
Condensate  
connection  
Step 2):  
Remove  
the cap  
Step 4.)  
Move and snap the  
nipple with hose  
into the hole  
Step 3.)  
Connect the  
nipple with a drain  
hose 5/8"  
When connecting to the condensate tray, ensure that the condensed water pipe is connected to a self-  
filling siphon with return protection and that the condensate drain is properly sloped.  
The height of the siphon must be designed for an underpressure or overpressure of 0.11psi (800 Pa) so  
that air is not drawn into or blown out of the waste pipe.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installation and Commissioning  
The condensate drain is not pressurized; a condensate pump can be used.  
5.5  
Electrical Connection  
The wiring diagram is enclosed in the unit.  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
Disconnect all local and remote electric power supplies before working within. Prior to  
beginning installation, shut down the server cabinet, disconnect it and secure it against  
unauthorized startup.  
As soon as all preparations for installation have been made, you can start electrical installation.  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
Disconnect all local and remote electric power supplies before working within.  
The XDK unit must be connected by a licensed and qualified electrician only. Ensure that the  
server cabinet is electrically isolated for the duration of the connection operation and is  
secured against unauthorized startup  
Check whether voltage and frequency at installation site as well as fuse ratings match the specifica-  
tions on the rating plate.  
To connect the unit to the power supply:  
1. Shut down the server cabinet.  
2. See the wiring diagram for information on the connections to be made.  
3. Connect the supply cable in the computer room.  
4. Check the secure connection of the earth wire.  
To return the server cabinet to operation, switch on the fuse-protected power supply.  
NOTE  
The unit's fans will rotate clockwise.  
5.6  
Sealing the Cabinet  
To ensure the optimal cooling function the cabinet must be sealed:  
• Pipe entrances should be cut into the foam and properly closed with a extra foam if required.  
• Cable entrances should be closed with the pivoting plate and foamed material.  
• Air flows on the warm and cold sides of the cabinet must be separated from each other.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Servicing and Maintenance  
6.0 SERVICING AND MAINTENANCE  
WARNING  
!
Risk of high speed rotating fan blades. Can cause serious injury.  
Disconnect all local and remote electric powers supplies and assure that fan blades have  
stopped rotating before working within the unit.  
WARNING  
!
!
Risk of electric shock. Can cause injury or death.  
Disconnect all local and remote electric power supplies before working within the unit.  
CAUTION  
Risk of explosive discharge of water under pressure. Can cause injury or equipment damage.  
Shut off the water supply and relieve pressure before working with piping.  
NOTE  
Service and maintenance work must be performed only by properly trained personnel and in  
accordance with applicable regulations as well as with manufacturers’ specifications.  
NOTE  
Use only original spare parts that have been tested and approved by the manufacturer. If  
necessary, request a comprehensive spare parts list from the manufacturer. For cleaning, use  
commercially available cleaning agents only. Follow the stipulated safety measures and do not  
use any tools that may cause scratching or tools for scraping (surfaces will be irreversibly  
damaged).  
6.1  
General Inspection on Fans—Annual  
• Check for unusual bearing noises. (Check for excessive bearing play.)  
6.1.1 Fan Replacement  
The expected service life is approximately 40,000 operating hours at a temperature of 40°C (104°F).  
1. Remove the housing cover from the unit (with earth cable).  
2. Determine which fan has failed.  
3. Check the surface temperature of the fan and switch off the circuit breaker.  
4. Disconnect supply cable at the fan terminal block.  
5. Loosen the four fastening nuts for the fan to be replaced.  
6. Remove the failed fan.  
Figure 11 Replacing a fan  
One of four  
fastening nuts  
Step 3:  
Disconnect  
supply cable  
at the fan  
terminal  
Slot to  
insert  
wrench to  
remove  
nut  
block  
Step 4: Undo  
the four  
fastening  
nuts  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Servicing and Maintenance  
Reinstall the fan by reversing the steps to remove the fan.  
1. Tighten the fan fastening bolts.  
2. Connect the power supply cable to the fan.  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
Reconnect the earth ground cable to the sheet metal panel to prevent a potentially hazardous  
open circuit in case of loose or disconnected electrical wiring or a fan motor short circuit.  
3. Switch on the circuit breaker.  
4. Dispose of the old fans correctly.  
6.2  
Inspect the Heat Exchanger—Annual  
The efficiency of heat exchangers is sharply reduced by dirt and debris; retaining high efficiency  
requires regular cleaning. Use a vacuum cleaner, compressed air or a soft brush to clean the fins.  
Do not bend the fins during cleaning—this will interfere with proper air flow through the unit.  
• Check heat exchanger on air side for soiling, damage and corrosion.  
• Check feed and return for correct function.  
• If necessary clean the air side.  
• Regularly check odor trap (external) for correct function.  
• Heat exchanger can be pulled out for improved cleaning.  
• Regularly visually inspect the water circuit for leaks.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Servicing and Maintenance  
6.3  
Replacing the Heat Exchanger  
Figure 12 Heat exchanger replacement  
Step 1: Lift the air  
duct off the flange  
to remove it.  
Step 4: Remove screws  
Step 5: Pull  
out the heat  
exchanger  
Step 2:  
Remove  
the grounding  
cable  
Step 3:  
Remove condensate  
connection  
Reinstall the heat exchanger by reversing the reverse order of removal.  
NOTE  
Regularly check the condensed water drain and clean if necessary  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Dismantling and Disposal  
7.0 DISMANTLING AND DISPOSAL  
The XDK may be dismantled by qualified personnel only.  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
Disconnect all local and remote electric power supplies before working within the unit.  
Disconnect the unit from the external water circuit by closing the shutoff valves and drain the unit’s  
water circuit.  
Transport the unit as described in 4.0 - equipment Inspection, Handling And Storage, using a  
lifting device with sufficient load-bearing capacity.  
Dispose of the air conditioner in accordance with the locally applicable disposal and safety instruc-  
tions. Liebert recommends using a specialist recycling organization.  
All parts can be stripped down and consist of:  
• aluminium, steel, brass, copper  
• labelled plastic parts  
• electronic parts  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Water Purity Requirements  
8.0 WATER PURITY REQUIREMENTS  
To ensure the maximum service life of the air/water heat exchangers, water must comply with the  
VGB water regulations (VGB-R 455 P). The water used must be soft enough to prevent deposits, but it  
must not be so soft that heat exchanger corrosion occurs.  
The following table contains the most important impurities and methods for removing them.  
Table 4  
Prevalent impurities and removal methods  
Water Impurity  
Method of Removal  
Mechanical pre-treatment (dp < 1 mm)  
Excessive hardness  
Filtering the water  
Soften the water using ion exchange  
Moderate content of mechanical impurities and hardness formers Addition of dispersing or stabilizing agents  
Moderate content of chemical impurities  
Biological impurities (bacteria and algae)  
Addition of passivation agents and inhibitors  
Addition of biocides  
It is recommended to achieve the following hydrological data as far as possible:  
Table 5 Suggested hydrologic levels  
Hydrological Data  
Suggested Units  
Amount  
pH values  
7 - 8.5  
Carbonate hardness  
Free carbon dioxide  
Bound carbon dioxide  
Aggressive carbon dioxide  
Sulfides  
>3 <8  
8 - 15  
8 - 15  
0
°dH  
3
3
3
3
3
3
3
3
3
3
3
3
mg/dm  
mg/dm  
mg/dm  
mg/dm  
mg/dm  
mg/dm  
mg/dm  
mg/dm  
mg/dm  
mg/dm  
mg/dm  
mg/dm  
< 10  
< 50  
< 250  
< 10  
< 7  
Oxygen  
Chloride ions  
Sulfate ions  
Nitrates and nitrides  
CSB  
< 5  
Ammonia  
< 5  
Iron  
< 0.2  
< 0.2  
< 2200  
< 500  
< 25  
< 3  
Manganese  
Conductivity  
μS/cm  
3
Solid evaporation residue  
Potassium permanganate consumption  
Suspended matter  
(Partial flow cleaning is recommended)  
(Continuous cleaning)  
mg/dm  
mg/dm  
mg/dm  
mg/dm  
mg/dm  
3
3
3
3
> 3 < 15  
> 15  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Water Purity Requirements  
8.1  
Unit Installation Checklist  
___ 1. Check unit for damage on delivery  
___ 2. Check for level floor  
___ 3. Check maximum floor load  
___ 4. XDK feet adjusted, if applicable  
___ 5. XDK is level  
___ 6. No remains of packaging in the XDK  
___ 7. All installation tools removed  
___ 8. Cable entries into the unit correct and air-tight  
___ 9. Cable connections checked  
___ 10. Cold water connection does not leak  
___ 11. Pressure test performed  
___ 12. Water circuit bled  
___ 13. Water flow rate adjusted  
___ 14. Condensed water pipe clear  
___ 15. Water system odor trap in order  
___ 16. Heat exchanger tray connected to condensed water pipe  
___ 17. Fan function checked  
___ 18. All front panels closed (separation of air flows)  
Comments  
Signature  
Checker  
Date  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Water Purity Requirements  
8.2  
Commissioning Certificate  
Table 6  
XDK – Commissioning certificate  
General Data  
Client/Setup Site  
Client Name  
Client Address  
Contact Persons  
Phone Number  
Setup Site / Room Number  
Table 7  
Nominal values at setup site  
Air Humidity  
at Setup Site  
% Relative Humidity  
°C (°F)  
Ambient  
Temperature  
Nominal Values  
at Setup Site  
Temperature  
°F (°C)  
50  
59  
64  
66  
68  
70  
72  
73  
75  
77  
79  
81  
82  
86  
95  
(10) (15) (18) (19) (20) (21) (22 (23 (24 (25 (26 (27 (28 (30 (35  
Maximum Relative  
Humidity %  
100  
76  
62  
58  
55  
52  
48  
46  
43  
40  
38  
36  
34  
30  
23  
Nominal values kept  
___ 1. Yes  
___ 2. No  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Water Purity Requirements  
Configuration  
Table 8  
Type of cabinet  
XDK 17kW  
Cabinet Number  
Serial Number  
Date Shipped  
Fan  
Type  
Table 9  
Control of status  
General Condition  
Load Carrying Capacity Checked  
Level Alignment Checked  
Transportation Damages of Cabinet  
Comments  
Yes  
Yes  
Yes  
No  
No  
No  
Damages on Heat Exchanger/Connections  
Front Door Closing Easily  
Comments:  
Yes  
Yes  
No  
No  
Rear Door Closing Easily  
Comments:  
Yes  
Yes  
No  
No  
Cable Entries Closed  
Comments  
Condensate Drain Open / Connected  
Comments  
Yes  
No  
Trap Filled Up  
Yes  
Yes  
Yes  
Yes  
No  
No  
No  
No  
Packaging Removed  
Installation Tools Removed  
Air Separation  
(Front Panels Closed)  
Cable Entries Air Tight  
Yes  
No  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Water Purity Requirements  
Table 10 Cold water facility on site  
Cold Water  
XDK Connected To  
Water Temperature  
Feed  
°C/°F  
Return  
Return  
Water Pressure  
Feed  
Pa  
PSI (Pa)  
PSI (Pa)  
Water Differential Pressure  
Table 11  
Electrical data / documents  
Wiring Scheme Attached  
Comments  
Yes  
No  
Cable Connections Checked:  
Yes  
Yes  
No  
No  
Electrical Acceptance Certificate  
by Approved Staff  
Comments  
.
Table 12 Function check  
Function of All Fans  
(Air Blowing Direction)  
Yes  
Yes  
No  
No  
Fans Shut Down When Rear Door  
is Opened  
Comments  
Function Three Way Valve  
Comments  
Yes  
Yes  
No  
No  
Door Opens When ____ °F (°C) is  
Reached  
Comments  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Water Purity Requirements  
Table 12 Function check (continued)  
Malfunction Indicator Function  
Comments  
Yes  
Yes  
No  
No  
Condensate Occurrence at Heat  
Exchanger  
Comments  
Pressure Test Water Circuit  
Water Flow Rate Adjusted  
Yes  
Yes  
No  
Flow Rate  
GPM  
(Possible Only Externally)  
Water Feed  
°F (°C)  
°F (°C)  
Water Return  
Air Temperature in the Cabinet  
At The Heat Exchanger Inlet  
Air Temperature in the Cabinet  
At the Heat Exchanger Outlet  
°F (°C)  
°F (°C)  
Commissioning performed by day to day operating.  
Correctness of function check protocol certified by:  
Approved Staff  
Client  
Date  
Signature  
Signature  
Date  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Water Purity Requirements  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ensuring The High Availability  
0f Mission-Critical Data And Applications.  
Technical Support / Service  
Web Site  
Emerson Network Power, the global leader in enabling business-critical  
continuity, ensures network resiliency and adaptability through  
a family of technologies—including Liebert power and cooling  
technologies—that protect and support business-critical systems.  
Liebert solutions employ an adaptive architecture that responds  
to changes in criticality, density and capacity. Enterprises benefit  
from greater IT system availability, operational flexibility and  
reduced capital equipment and operating costs.  
Monitoring  
800-222-5877  
Outside the US: 614-841-6755  
Single-Phase UPS  
800-222-5877  
Outside the US: 614-841-6755  
Three-Phase UPS  
800-543-2378  
Environmental Systems  
800-543-2778  
Outside the United States  
614-888-0246  
Locations  
United States  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
Europe  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD) Italy  
+39 049 9719 111  
Fax: +39 049 5841 257  
Asia  
7/F, Dah Sing Financial Centre  
108 Gloucester Road, Wanchai  
Hong Kong  
While every precaution has been taken to ensure the accuracy  
and completeness of this literature, Liebert Corporation assumes no  
responsibility and disclaims all liability for damages resulting from use of  
this information or for any errors or omissions.  
© 2007 Liebert Corporation  
All rights reserved throughout the world. Specifications subject to change  
without notice.  
852 2572220  
Fax: 852 28029250  
® Liebert and the Liebert logo are registered trademarks of Liebert  
Corporation. All names referred to are trademarks  
or registered trademarks of their respective owners.  
SL-16681_REV0_04-07  
Emerson Network Power.  
The global leader in enabling Business-Critical Continuity.  
EmersonNetworkPower.com  
AC Power  
Connectivity  
DC Power  
Embedded Computing  
Embedded Power  
Monitoring  
Outside Plant  
Racks & Integrated Cabinets  
Power Switching & Controls  
Services  
Precision Cooling  
Surge Protection  
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.  
©2007 Emerson Electric Co.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Krown Manufacturing Amplified Phone KR2812 User Manual
Learning Resources Baby Toy LER0100 User Manual
Lindy Home Theater Server Personal Server User Manual
LST Smoke Alarm HT 11003 User Manual
Master Bilt Refrigerator DMS 48 User Manual
Maxell Cassette Player IBX 2 User Manual
McCulloch Trimmer 250CXL User Manual
Melissa Styling Iron 635 069 User Manual
Melissa Waffle Iron 243054 User Manual
Memorex DVD Player MVDP1101 User Manual