Precision Cooling
For Business-Critical Continuity™
Liebert XDK™ Rack Enclosure With Integrated Water-Based Cooling
User Manual–17kW
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . INSIDE FRONT COVER
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
OPERATING CONDITIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Proper Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
General function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Principle of Cooling Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.2.1 Data Overview—XDK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Automatic Door Opening . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.4.1 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.4.2 Initial Commissioning:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.4.3 Manual Closing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.4.4 Manual Opening . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
EQUIPMENT INSPECTION, HANDLING AND STORAGE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Packaging Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Returning the Unit in Case of Damage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
INSTALLATION AND COMMISSIONING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Preparation for Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Positioning the XDK. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.2.1 Remove Recirculation Air Duct Transport Lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Water Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3.1 Preparing Heat Exchanger for Initial Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Condensed Water Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Sealing the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
SERVICING AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
General Inspection on Fans—Annual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.1.1 Fan Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Inspect the Heat Exchanger—Annual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Replacing the Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
DISMANTLING AND DISPOSAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
8.2
WATER PURITY REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Unit Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Commissioning Certificate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
i
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURES
Figure 1
Cooling airflow, top view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Cooling airflow, side view. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
XDK door and automatic opening mechanism . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Door locking mechanisms, opening switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Remove the transport lock screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Heat exchanger access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Control valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Heat exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Heat exchanger connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 10 Bottom plate with cutouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 11 Replacing a fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 12 Heat exchanger replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
TABLES
General operating data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
XDK general data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Prevalent impurities and removal methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Suggested hydrologic levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
XDK – Commissioning certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Nominal values at setup site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Type of cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Control of status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Table 10 Cold water facility on site. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Table 11 Electrical data / documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Table 12 Function check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
ii
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
1.0 INTRODUCTION
The Liebert XDK provides the dissipation of heat loads up to 17kW.
The server rack is closed to the installation area, that means no heat load will dissipate to the envi-
ronment. (see also chapter 2.) The cooling is provided by a closed cooling system via an air-to-water
heat exchanger. The cooling capacity adapts to the heat load.
19" (483mm) rails are designed for components as well as rails and shelves.
Cable entry is possible from the bottom and from the top.
1
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Conditions
2.0 OPERATING CONDITIONS
2.1 Proper Application
The XDK is a water-cooled enclosure and is intended for removing heat from electronic equipment
inside the cabinet. The cooling system in the cabinet is thermally independent of the room air. Water
is used to cool equipment installed in the XDK. No additional cooling of the server room is required.
NOTE
Under certain conditions, a small amount of heat, (approximately 0.5kW), can escape into the
room.
CAUTION
!
Risk of improper operation. Can cause equipment damage. For reliable function of the XDK,
cold water must be available in the correct amount, and at the correct temperature and
pressure. Observe water quality specified in VGB-R 455 P. (see 8.0 - Water Purity
Requirements ).
Table 1
General operating data
50°F to 95°F (10°C to 35°C)
(other temperatures upon request)
Ambient temperature
Absolute humidity in the installation location
Water temperature, supply
Water temperature, return
Water connection
8g H O/ kg air maximum
2
54°F (12°C); other temperatures upon request
64°F (18°C); other temperatures upon request
from below
Condensed water connection
Nominal voltage
from below
200V to 264V (50Hz and 60 Hz)
145 PSI (10 bar)
Maximum operating pressure
2
Download from Www.Somanuals.com. All Manuals Search And Download.
Description
3.0 DESCRIPTION
3.1 General function
The modular design facilitates the installation of 19-inch-wide equipment of varying depth.
Heat produced by equipment in the cabinet, such as servers, is removed by the cold water system
integrated into the server cabinet. The cooling system is isolated from the server area, protecting the
sensitive equipment from water damage.
The cooling system comprises a high-performance air/water heat exchanger, fans with fan control
unit, fan-speed according to heat load.
The air circuit is closed such that no heat is emitted to the environment.
CAUTION
!
Risk of improper operation. Can cause equipment damage.
The XDK works only if cold server feed air and heated server outlet air are fully separated.
Height units not in use must be sealed with blanking panels.
Figure 1
Cooling airflow, top view
Air Duct
Warm Warm
Warm
Server
Cold
Warm
Air
Separation
Cold
Front
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Description
3.2
Principle of Cooling Operation
Figure 2
Cooling airflow, side view
Fan
Bank
Rear
of
XDK
Front
of
XDK
19" Equipment
Air / Water
Heat Exchanger
Cold Water Supply
Side of XDK
Air that has been heated by the servers to 95°F (35°C), for example, is circulated to a specially
designed air/water heat exchanger by high-performance fans. The heated air is cooled to 68-77°F
(20-25°C) and fed to the front of the server.
The server fans can draw in the air and feed it over internal components.
Cold water is provided by a separate Liebert XD Pumping unit.
A condensate tray with a 5/8" outlet is below the heat exchanger.
NOTE
If the rear door (with fans) is opened, the front door must be opened. If the front door is opened,
it is not necessary to open the rear door.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Description
Table 2
Technical data
Housing material Aluminium sheet, sheet steel, galvanized and coated
Operating Temperature range 50°F to 95°F (10°C to 35°C)
Abs. atmospheric humidity 8g / kg maximum
Temperature difference across server approx. 15K
Noise level 55 dB(A) sound pressure at a distance of 3 ft. (1m)
Useful load 2204 lb (1000kg)
Cold Water
Cooling capacity 17kW
Supply temperature 54°F (12°C) (other temperatures upon consultation)
Return temperature 64°F to 72°F (18°C to 22°C) (other temperatures upon consultation)
Max. operating pressure 145 PSI (10 bar)
Water supply connection 1"
3.2.1 Data Overview—XDK
Table 3
XDK general data
Nominal Cooling Capacity
Height, in (mm)
Width, in (mm)
Depth, in (mm)
17kW @ 54°F (12°C) EFT
86.6 (2200)
31.5 (800)
47 (1200)
Usable Height for Electronic
Equipment
40 U
Maximum Electronic
Equipment Depth, in (mm)
29 (740)
68/98 (20/37
Electronic Equipment
Air Temperature, In/Out, °F (°C)
Weight, Empty, lb (kg)
Maximum Weight, Filled
683 (310)
2,800 (1310)
Maximum Operating
Water Pressure, psi (bar)
145 (10)
3
Water Flow Rate, GPM (m /h)
10.7 (2.44)
10 (0.7)
1
Water Pressure Drop, psi (bar)
Water Connections, in
3
Maximum Air Flow, CFM ( m /h) 1800 (3,100)
Sound Pressure Level
Input Voltage
55 dB(A) at 3 ft (1m)
200-264 V, 1 ph, 50/60 Hz
1400W
Maximum Power Draw
Options
Leveling Feet or Casters
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Description
3.3
Control
The server cabinet temperature is controlled by the fan control board
A temperature sensor continuously measures the temperature of the server cabinet (server feed air).
The air circulation flow rate is controlled by the fan speed according to the current thermal load.
At temperatures lower than 70°F (21°C) fans rotate at 75% of maximum speed.
Between 68°F and 73°F (20 and 23°C), speed increases proportionally to the temperature up to 96% of
maximum speed.
The failure of the temperature sensor set the fans to maximum speed.
The water flow rate is controlled by a three-way valve depending on thermal load. In case of failure,
the valve opens and the all the chilled water flows through the heat exchanger.
From 61°F to 66°F (16°C to 19°C), the three-way valve controls the water flow rate from 0% to 100% of
the nominal flow rate.
The programming of the control is factory-set and protected with a password.
The failure of the temperature sensor or one of the fans will set off an alarm using a potential free
contact.
The outgoing alarms with potential free contact are:
• sensor error
• fan malfunction
• high-temperature / low-temperature
The fans are automatically shut down if the server cabinet rear door is opened.
3.4
Automatic Door Opening
Figure 3
XDK door and automatic opening mechanism
Gas pressure spring
Upper magnet
and retaining
plate
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Description
3.4.1 Function
Front and rear door are kept closed with two electromagnets. The door will be pushed open smoothly
by a gas pressure spring if power to the electromagnets fails.
If the doors are opened, the thermal load can escape into the room, preventing the servers from over-
heating.
The inflow of air with water droplets can also be prevented (Door opening due to humidity alarm).
When the rear door is opened, the fans shut down automatically.
Figure 4
Door locking mechanisms, opening switch
Upper and lower
transport-lock
screw
Door opening switch
with LED (green)
3.4.2 Initial Commissioning:
___ 1. Loosen the upper and lower transport lock screw
NOTE
If the power supply fails during initial commissioning, the front door opens automatically. If
the transport lock screws are reinstalled, both transport lock screws must be reinserted or the
door could be damaged
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Description
3.4.3 Manual Closing
1. Press LED switch for electromagnet activation
2. The LED lights up
3. Push door evenly shut. Both magnetic locks must latch.
3.4.4 Manual Opening
1. Press LED switch - green LED doesn’t light
2. Rack door opens itself
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Equipment Inspection, Handling And Storage
4.0 EQUIPMENT INSPECTION, HANDLING AND STORAGE
Upon arrival of the unit, and before unpacking, verify that the labeled equipment matches the bill of
lading. Inspect all items for damage, either visible or concealed. Damage should be immediately
reported to the carrier and a damage claim filed with a copy sent to your local sales representative.
4.1
Packaging Material
All material used to package this unit is recyclable. Please save for future use or
dispose of the material appropriately.
R
SAFETY INFORMATION
WARNING
!
Risk of top-heavy unit falling over. Improper handling can cause equipment damage, injury or
death! Read all of the following instructions before attempting to move, lift, remove packaging
from or preparing unit for installation.
WARNING
!
Risk of sharp edges, splinters and exposed fasteners. Can cause personal injury.
Only properly trained personnel wearing appropriate safety headgear, gloves, shoes and
glasses should attempt to move, lift, remove packaging from or prepare unit for installation.
CAUTION
!
!
Risk of overhead interference. Can cause unit and/or structure damage.
Refer to the installation plans prior to moving the unit to verify clearances.
CAUTION
Risk of damage from fork lift! Improper handling with the forklift can cause exterior and/or
underside damage! Keep tines of the fork lift level and at a height suitable to fit below the
skid.
4.2
Handling
When possible, transport the unit using a forklift or pallet jack. Otherwise use a crane with belts or
cables.
• When using a forklift or pallet jack, make sure the forks (if adjustable) are spread to the widest
allowable distance that will fit under the skid.
• Ensure that the fork length is suitable for the unit length.
• When using a forklift while moving the packaged XDK, do not lift it higher than 6" (152mm).
• If circumstances require the XDK to be lifted higher than 6" (152mm), great care must be exer-
cised. Personnel not involved in moving the unit must be at least 20' (5m) from the lift point of the
unit.
• Belts or cables must be used when the XDK is moved with a crane.
• The XDK’s net weight is 749 lb. (340 kg).
• Avoid twisting the housing or other damage during handling.
• Ensure that the XDK’s doors are closed prior to lifting.
• Do not stand under an XDK while it is suspended.
• Hooks used to attach to the unit must be of appropriate tensile strength.
• The XDK must not be lifted at an angle.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Equipment Inspection, Handling And Storage
4.3
4.4
Storage
• If the XDK’s packaging has been removed, cover it with tarpaulins to protect against particulates,
such as sand and dust, and from moisture.
• Keep storage temperature between -22°F and 104°F (-30°C and +40°C).
• The heat exchanger must be completely drained to prevent the risk of freezing damage.
• When stored for more than 12 months, turn fans by hand to check the fan bearings prior to instal-
lation.
Returning the Unit in Case of Damage
If the XDK is not returned in its original packaging, the packaging used for return must comply with
the following:
• There must be at least 1-3/16" (30mm) space between the unit and the packaging.
• Footprint of the skid shall extend at least 2-1/2" (64mm) from the perimeter of the unit.
• The XDK must be attached to the skid using original metal brackets or steel banding.
If steel banding is used to hold unit to the skid, place reinforced protective material between the
banding and the XDK.
• Ensure proper shipping information is affixed to the exterior of the packaging.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation and Commissioning
5.0 INSTALLATION AND COMMISSIONING
5.1
Preparation for Installation
CAUTION
!
Risk of improper installation. Can cause equipment damage.
Before installing the unit, a number of points must be checked for safety and to ensure the
correct function of the server cabinet. Take care when performing these checks to ensure that
the unit functions correctly.
CAUTION
!
Risk of improper installation. Can cause equipment damage.
The XDK must be installed on a level surface. For this reason, check the horizontal alignment
with a spirit level prior to starting installation. The floor must be able to support a rack load
of 307 lb/ft² (1500 kg/m²) (with installed equipment per XDK).
To achieve good air circulation, ensure that there is no packaging material or other equipment that
could hinder or prevent air circulation in the area of the equipment, in the area of the heat exchanger,
in the air inlet or in the air outlet.
5.2
Positioning the XDK
After positioning, the XDK’s feet must be adjusted to make the cabinet vertical. When positioned the
doors must close easily.
5.2.1 Remove Recirculation Air Duct Transport Lock
The Liebert XDK is shipped without the gas pressure springs for the front and rear automatic door
openers installed. The springs should be installed according to separate instructions before the Lie-
bert XDK is connected and turned on.
After positioning, remove the transport lock screws at the sides of the recirculation air duct (see
Figure 5).
The recirculation air duct may be pulled out to remove items that fall into the heat exchanger tray.
Figure 5
Remove the transport lock screws
Remove both screws
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation and Commissioning
5.3
Water Connection
The heat exchanger can be pulled out for servicing
Water pipes should be connected so that the heat exchanger can be pulled out when the connection is
undone. If the heat exchanger is connected to the water circuit using threaded fittings, the pipe fitting
must be supported on tightening.
Before commissioning the server cabinet, the pipe connections should be checked for leaks according
to local codes.
5.3.1 Preparing Heat Exchanger for Initial Commissioning
Check the mechanical installation and the supply pipe connection.
Figure 6
Heat exchanger access
Remove this air duct
for bleeding, draining the
heat exchanger and
checking the valve
1. Carefully bleed heat exchanger when filling the system.
2. Open the air bleed valve until the water coming out has no bubbles.
3. Close this valve after bleeding.
Figure 7
Control valve
Air bleed valve
Water return
Water supply
Drain valve
4. If necessary, retighten threaded fittings.
5. After an extended period without use, and particularly in case of risk of freezing temperatures,
the heat exchanger and the supply pipe must be drained of all fluid.
6. Drain completely by blowing out with compressed air and remove all bleed and drain plugs.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation and Commissioning
Figure 8
Heat exchanger
27-3/8"
(695mm)
33-7/16"
(850mm)
Space
for
Cabling
9-7/8"
(150mm)
2"
(50mm)
2"
(50mm)
Top View
Figure 9
Heat exchanger connection
Water return
Water supply
Liebert recommends insulating the cold water pipes with waterproof insulation to prevent condensa-
tion and losses.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation and Commissioning
Figure 10 Bottom plate with cutouts
Sealed Cable Cutout
Rear
Network
Cable
Entry
Cutout for
Water Pipes
Condensed
Water Cutouts
Front
Cable and pipe openings must be sealed air-tight on completion of work.
5.4
Condensed Water Connection
If the XDK is operated below dew point, condensed water may occur. As standard there is a water con-
nection, 5/8" diameter, in the condensed water tray for drainage.
Preparations for Connecting
Step 1):
Remove
the air
duct
Condensate
connection
Step 2):
Remove
the cap
Step 4.)
Move and snap the
nipple with hose
into the hole
Step 3.)
Connect the
nipple with a drain
hose 5/8"
When connecting to the condensate tray, ensure that the condensed water pipe is connected to a self-
filling siphon with return protection and that the condensate drain is properly sloped.
The height of the siphon must be designed for an underpressure or overpressure of 0.11psi (800 Pa) so
that air is not drawn into or blown out of the waste pipe.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation and Commissioning
The condensate drain is not pressurized; a condensate pump can be used.
5.5
Electrical Connection
The wiring diagram is enclosed in the unit.
WARNING
!
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working within. Prior to
beginning installation, shut down the server cabinet, disconnect it and secure it against
unauthorized startup.
As soon as all preparations for installation have been made, you can start electrical installation.
WARNING
!
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working within.
The XDK unit must be connected by a licensed and qualified electrician only. Ensure that the
server cabinet is electrically isolated for the duration of the connection operation and is
secured against unauthorized startup
Check whether voltage and frequency at installation site as well as fuse ratings match the specifica-
tions on the rating plate.
To connect the unit to the power supply:
1. Shut down the server cabinet.
2. See the wiring diagram for information on the connections to be made.
3. Connect the supply cable in the computer room.
4. Check the secure connection of the earth wire.
To return the server cabinet to operation, switch on the fuse-protected power supply.
NOTE
The unit's fans will rotate clockwise.
5.6
Sealing the Cabinet
To ensure the optimal cooling function the cabinet must be sealed:
• Pipe entrances should be cut into the foam and properly closed with a extra foam if required.
• Cable entrances should be closed with the pivoting plate and foamed material.
• Air flows on the warm and cold sides of the cabinet must be separated from each other.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Servicing and Maintenance
6.0 SERVICING AND MAINTENANCE
WARNING
!
Risk of high speed rotating fan blades. Can cause serious injury.
Disconnect all local and remote electric powers supplies and assure that fan blades have
stopped rotating before working within the unit.
WARNING
!
!
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working within the unit.
CAUTION
Risk of explosive discharge of water under pressure. Can cause injury or equipment damage.
Shut off the water supply and relieve pressure before working with piping.
NOTE
Service and maintenance work must be performed only by properly trained personnel and in
accordance with applicable regulations as well as with manufacturers’ specifications.
NOTE
Use only original spare parts that have been tested and approved by the manufacturer. If
necessary, request a comprehensive spare parts list from the manufacturer. For cleaning, use
commercially available cleaning agents only. Follow the stipulated safety measures and do not
use any tools that may cause scratching or tools for scraping (surfaces will be irreversibly
damaged).
6.1
General Inspection on Fans—Annual
• Check for unusual bearing noises. (Check for excessive bearing play.)
6.1.1 Fan Replacement
The expected service life is approximately 40,000 operating hours at a temperature of 40°C (104°F).
1. Remove the housing cover from the unit (with earth cable).
2. Determine which fan has failed.
3. Check the surface temperature of the fan and switch off the circuit breaker.
4. Disconnect supply cable at the fan terminal block.
5. Loosen the four fastening nuts for the fan to be replaced.
6. Remove the failed fan.
Figure 11 Replacing a fan
One of four
fastening nuts
Step 3:
Disconnect
supply cable
at the fan
terminal
Slot to
insert
wrench to
remove
nut
block
Step 4: Undo
the four
fastening
nuts
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Servicing and Maintenance
Reinstall the fan by reversing the steps to remove the fan.
1. Tighten the fan fastening bolts.
2. Connect the power supply cable to the fan.
WARNING
!
Risk of electric shock. Can cause injury or death.
Reconnect the earth ground cable to the sheet metal panel to prevent a potentially hazardous
open circuit in case of loose or disconnected electrical wiring or a fan motor short circuit.
3. Switch on the circuit breaker.
4. Dispose of the old fans correctly.
6.2
Inspect the Heat Exchanger—Annual
The efficiency of heat exchangers is sharply reduced by dirt and debris; retaining high efficiency
requires regular cleaning. Use a vacuum cleaner, compressed air or a soft brush to clean the fins.
Do not bend the fins during cleaning—this will interfere with proper air flow through the unit.
• Check heat exchanger on air side for soiling, damage and corrosion.
• Check feed and return for correct function.
• If necessary clean the air side.
• Regularly check odor trap (external) for correct function.
• Heat exchanger can be pulled out for improved cleaning.
• Regularly visually inspect the water circuit for leaks.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Servicing and Maintenance
6.3
Replacing the Heat Exchanger
Figure 12 Heat exchanger replacement
Step 1: Lift the air
duct off the flange
to remove it.
Step 4: Remove screws
Step 5: Pull
out the heat
exchanger
Step 2:
Remove
the grounding
cable
Step 3:
Remove condensate
connection
Reinstall the heat exchanger by reversing the reverse order of removal.
NOTE
Regularly check the condensed water drain and clean if necessary
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Dismantling and Disposal
7.0 DISMANTLING AND DISPOSAL
The XDK may be dismantled by qualified personnel only.
WARNING
!
Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power supplies before working within the unit.
Disconnect the unit from the external water circuit by closing the shutoff valves and drain the unit’s
water circuit.
lifting device with sufficient load-bearing capacity.
Dispose of the air conditioner in accordance with the locally applicable disposal and safety instruc-
tions. Liebert recommends using a specialist recycling organization.
All parts can be stripped down and consist of:
• aluminium, steel, brass, copper
• labelled plastic parts
• electronic parts
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Water Purity Requirements
8.0 WATER PURITY REQUIREMENTS
To ensure the maximum service life of the air/water heat exchangers, water must comply with the
VGB water regulations (VGB-R 455 P). The water used must be soft enough to prevent deposits, but it
must not be so soft that heat exchanger corrosion occurs.
The following table contains the most important impurities and methods for removing them.
Table 4
Prevalent impurities and removal methods
Water Impurity
Method of Removal
Mechanical pre-treatment (dp < 1 mm)
Excessive hardness
Filtering the water
Soften the water using ion exchange
Moderate content of mechanical impurities and hardness formers Addition of dispersing or stabilizing agents
Moderate content of chemical impurities
Biological impurities (bacteria and algae)
Addition of passivation agents and inhibitors
Addition of biocides
It is recommended to achieve the following hydrological data as far as possible:
Table 5 Suggested hydrologic levels
Hydrological Data
Suggested Units
Amount
pH values
7 - 8.5
Carbonate hardness
Free carbon dioxide
Bound carbon dioxide
Aggressive carbon dioxide
Sulfides
>3 <8
8 - 15
8 - 15
0
°dH
3
3
3
3
3
3
3
3
3
3
3
3
mg/dm
mg/dm
mg/dm
mg/dm
mg/dm
mg/dm
mg/dm
mg/dm
mg/dm
mg/dm
mg/dm
mg/dm
< 10
< 50
< 250
< 10
< 7
Oxygen
Chloride ions
Sulfate ions
Nitrates and nitrides
CSB
< 5
Ammonia
< 5
Iron
< 0.2
< 0.2
< 2200
< 500
< 25
< 3
Manganese
Conductivity
μS/cm
3
Solid evaporation residue
Potassium permanganate consumption
Suspended matter
(Partial flow cleaning is recommended)
(Continuous cleaning)
mg/dm
mg/dm
mg/dm
mg/dm
mg/dm
3
3
3
3
> 3 < 15
> 15
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Water Purity Requirements
8.1
Unit Installation Checklist
___ 1. Check unit for damage on delivery
___ 2. Check for level floor
___ 3. Check maximum floor load
___ 4. XDK feet adjusted, if applicable
___ 5. XDK is level
___ 6. No remains of packaging in the XDK
___ 7. All installation tools removed
___ 8. Cable entries into the unit correct and air-tight
___ 9. Cable connections checked
___ 10. Cold water connection does not leak
___ 11. Pressure test performed
___ 12. Water circuit bled
___ 13. Water flow rate adjusted
___ 14. Condensed water pipe clear
___ 15. Water system odor trap in order
___ 16. Heat exchanger tray connected to condensed water pipe
___ 17. Fan function checked
___ 18. All front panels closed (separation of air flows)
Comments
Signature
Checker
Date
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Water Purity Requirements
8.2
Commissioning Certificate
Table 6
XDK – Commissioning certificate
General Data
Client/Setup Site
Client Name
Client Address
Contact Persons
Phone Number
Setup Site / Room Number
Table 7
Nominal values at setup site
Air Humidity
at Setup Site
% Relative Humidity
°C (°F)
Ambient
Temperature
Nominal Values
at Setup Site
Temperature
°F (°C)
50
59
64
66
68
70
72
73
75
77
79
81
82
86
95
(10) (15) (18) (19) (20) (21) (22 (23 (24 (25 (26 (27 (28 (30 (35
Maximum Relative
Humidity %
100
76
62
58
55
52
48
46
43
40
38
36
34
30
23
Nominal values kept
___ 1. Yes
___ 2. No
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Water Purity Requirements
Configuration
Table 8
Type of cabinet
XDK 17kW
Cabinet Number
Serial Number
Date Shipped
Fan
Type
Table 9
Control of status
General Condition
Load Carrying Capacity Checked
Level Alignment Checked
Transportation Damages of Cabinet
Comments
Yes
Yes
Yes
No
No
No
Damages on Heat Exchanger/Connections
Front Door Closing Easily
Comments:
Yes
Yes
No
No
Rear Door Closing Easily
Comments:
Yes
Yes
No
No
Cable Entries Closed
Comments
Condensate Drain Open / Connected
Comments
Yes
No
Trap Filled Up
Yes
Yes
Yes
Yes
No
No
No
No
Packaging Removed
Installation Tools Removed
Air Separation
(Front Panels Closed)
Cable Entries Air Tight
Yes
No
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Water Purity Requirements
Table 10 Cold water facility on site
Cold Water
XDK Connected To
Water Temperature
Feed
°C/°F
Return
Return
Water Pressure
Feed
Pa
PSI (Pa)
PSI (Pa)
Water Differential Pressure
Table 11
Electrical data / documents
Wiring Scheme Attached
Comments
Yes
No
Cable Connections Checked:
Yes
Yes
No
No
Electrical Acceptance Certificate
by Approved Staff
Comments
.
Table 12 Function check
Function of All Fans
(Air Blowing Direction)
Yes
Yes
No
No
Fans Shut Down When Rear Door
is Opened
Comments
Function Three Way Valve
Comments
Yes
Yes
No
No
Door Opens When ____ °F (°C) is
Reached
Comments
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Water Purity Requirements
Table 12 Function check (continued)
Malfunction Indicator Function
Comments
Yes
Yes
No
No
Condensate Occurrence at Heat
Exchanger
Comments
Pressure Test Water Circuit
Water Flow Rate Adjusted
Yes
Yes
No
Flow Rate
GPM
(Possible Only Externally)
Water Feed
°F (°C)
°F (°C)
Water Return
Air Temperature in the Cabinet
At The Heat Exchanger Inlet
Air Temperature in the Cabinet
At the Heat Exchanger Outlet
°F (°C)
°F (°C)
Commissioning performed by day to day operating.
Correctness of function check protocol certified by:
Approved Staff
Client
Date
Signature
Signature
Date
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Water Purity Requirements
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Ensuring The High Availability
0f Mission-Critical Data And Applications.
Technical Support / Service
Web Site
Emerson Network Power, the global leader in enabling business-critical
continuity, ensures network resiliency and adaptability through
a family of technologies—including Liebert power and cooling
technologies—that protect and support business-critical systems.
Liebert solutions employ an adaptive architecture that responds
to changes in criticality, density and capacity. Enterprises benefit
from greater IT system availability, operational flexibility and
reduced capital equipment and operating costs.
Monitoring
800-222-5877
Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
© 2007 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change
without notice.
852 2572220
Fax: 852 28029250
® Liebert and the Liebert logo are registered trademarks of Liebert
Corporation. All names referred to are trademarks
or registered trademarks of their respective owners.
SL-16681_REV0_04-07
Emerson Network Power.
The global leader in enabling Business-Critical Continuity.
EmersonNetworkPower.com
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Racks & Integrated Cabinets
Power Switching & Controls
Services
Precision Cooling
Surge Protection
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2007 Emerson Electric Co.
Download from Www.Somanuals.com. All Manuals Search And Download.
|