Liebert Network Card XDH User Manual

Precision Cooling  
For Business-Critical Continuity™  
Liebert® XDH™  
User Manual - 50 & 60Hz  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
5.9  
Connecting a Liebert XDH with Liebert XD Flex Pipe to an Operational Liebert  
XD System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19  
6.2  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURES  
Figure 1  
TABLES  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Liebert XDH Component Locations and Model Number Nomenclature  
1.0 LIEBERT XDH COMPONENT LOCATIONS AND MODEL NUMBER NOMENCLATURE  
Figure 1  
Liebert XDH component locations  
FRONT  
(Top View)  
Air  
Return  
Vents  
Controls  
Return Piping  
Connection -  
Bottom Circuit  
Return Piping  
Connection -  
Top Circuit  
Cooling  
Air Supply  
Vents  
Supply Piping  
Connection -  
Bottom Circuit  
Supply Piping  
Connection -  
Bottom Circuit  
REAR  
FRONT  
Upper  
Refrigeration  
Circuit  
FRONT  
(Bottom View)  
FRONT  
Lower  
Refrigeration  
Circuit  
Condensate Pan  
and Detection  
Option (also in  
bottom circuit)  
Condensate  
Detection  
Connections  
Casters  
(one at each  
corner)  
REAR  
Adjustable Foot  
(one at each corner)  
Electrical  
Connections  
Stabilizers (one  
at each corner)  
Figure 2  
Liebert XDH model number nomenclature  
Example: XDH32BK— —0  
XD  
H
32  
B
K
0
Liebert  
X-Treme heat  
density system  
20 = Model size  
32 = Model size  
K = 120V-1ph-60Hz  
S = 208-240-1ph-60Hz  
220-240-1ph-50Hz  
— = Domestic packaging  
E = Export packaging  
Revision level  
Horizontal row cooler  
B = Base unit  
— = Hard piped  
D = Condensate detection P = Pre-charged (one-shot) Coupling  
R = Removable Coupling  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Introduction  
2.0 INTRODUCTION  
2.1  
Product Description  
The Liebert XDH cooling module is designed to be placed within a row of server enclosures in a hot-  
aisle-cold-aisle arrangement. The Liebert XDH, available in a half-rack-width unit, is intended for  
use with a Liebert XD pumped refrigerant cooling system, supplied by either a Liebert XDP or Liebert  
XDC.  
Warmer air from the enclosures is drawn in through the rear of the Liebert XDH, cooled and blown  
into the cold aisle in a diffuse pattern. The cooling air is then drawn into the enclosures to cool the  
equipment.  
The Liebert XDH has dual refrigeration circuits, one in the upper half of the unit and the other in the  
lower half. This permits increasing and decreasing cooling levels in response to server room condi-  
tions. The dual refrigeration circuits permits interlaced connection of two Liebert XD refrigerant  
sources to enhance system reliability.  
Controls on the front of the Liebert XDH permit independent operation of the two banks of fans. Dual  
power connections ensure continued fan operation if one of two electrical sources fails.  
The Liebert XDH is intended for use in low-humidity environments and does not need a drain connec-  
tion. A condensate pan under each refrigeration unit collects the small amount of moisture expected  
in the server room. An optional, factory-installed condensate detection system is available. The Lie-  
bert XDH is available with uni-directional or bi-directional air diffusers.  
2.2  
2.3  
References  
This document must be used together with site specific documentation and documentation for other  
parts of the system.  
Pre-Installation Checks  
• Verify that the Liebert XDH voltage matches the available utility power. The serial tag with this  
information is accessible by opening the Liebert XDH’s rear door. The tag is on a shelf near the  
Liebert XDH’s midline.  
• Check the received materials to be sure all required assemblies and parts have been received. If  
you discover any external damage, report it to the shipping company and your local Liebert repre-  
sentative.  
2.4  
Parts Included With the Liebert XDH  
• User manual (this document)  
• Liebert XDH module  
• Power cords  
• Shipping/floor mounting brackets  
• Tie-down bracket assembly  
• Diffusers (top and bottom)  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Introduction  
2.5  
Installation Considerations  
The Liebert XDH is designed for placement within a row of computer cabinets in the data center in a  
hot-aisle-cold-aisle arrangement. The Liebert XDH is 12" (305mm) wide, so it takes up little space.  
For installation arrangement, see 4.2 - Installing the Liebert XDH Within the Enclosure Row.  
Be sure to follow all applicable codes.  
Determine whether the Liebert XDH includes the condensate detection option (factory-installed).  
This option will require separate low voltage connections to a monitoring unit. A front panel alarm  
and indicator alert the user to condensation inside the unit. To minimize the possibility of condensa-  
tion, insulate all piping between the Liebert XDH and the Liebert XDP or Liebert XDC.  
If the Liebert XDH is installed at the end of a row, Liebert recommends using uni-directional air dif-  
fusers to direct cooling air into the cold aisle, toward the equipment racks. If the Liebert XDH is  
installed between racks within a row, Liebert recommends using bi-directional air diffusers, directing  
the cooling air toward the equipment racks on either side of the Liebert XDH.  
Table 1  
Input Voltage  
Minimum Maximum  
-10% +10%  
Application limits  
Range of Return Air Conditions to Unit  
Dry Bulb Temperature  
Relative Humidity  
60° to 100°F (16° to 38°C)  
20% to 80%  
2.5.1 Room Preparation  
The room should be well-insulated and must have a sealed vapor barrier. The vapor barrier in the  
ceiling and walls can be a polyethylene film. Paint on concrete walls and floors should contain either  
rubber or plastic.  
NOTE  
The vapor barrier is the single most important requirement for maintaining environmental  
control in the conditioned space.  
Outside or fresh air should be kept to a minimum when temperature and humidity must be tightly  
controlled. Outside air adds to the cooling, heating, dehumidifying and humidifying loads of the site.  
Doors should be properly sealed to minimize leaks and should not contain ventilation grilles.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
General product information  
3.0 GENERAL PRODUCT INFORMATION  
3.1 Product/System Description  
The Liebert XDH is designed for placement within a row of computer cabinets in the data center in a  
hot-aisle-cold-aisle arrangement to maximize the Liebert XDH’s cooling: The unit takes in hot air  
through the rear from the hot aisle, cools the air by air-to-fluid heat exchangers and discharges the  
air through the front of the unit into the cold aisle.  
Chilled R-134a refrigerant is provided to the Liebert XDH by a Liebert XD Pumping unit (Liebert  
XDP) or by a Liebert XD Chiller (Liebert XDC). The Liebert XDH may be installed in a Liebert XD  
piping system that includes other Liebert XD cooling modules, such as the Liebert XDO, Liebert XDV  
or Liebert XD CoolFrame.  
Replaceable front panels on the Liebert XDH may be customized to match the appearance of various  
computer manufacturer’s equipment, allowing the Liebert XDH to blend in with adjacent server  
equipment and enclosures. Air diffusers are available to direct cooling air for more efficient cooling,  
depending on the Liebert XDH’s positioning in a row or at the end of a row.  
The Liebert XDH is not expected to produce any condensation because of its location, usually in the  
data center. A condensate pan is provided as a precaution. It does not have a drain fitting or other  
means of being emptied.  
A Liebert Liqui-tect moisture detection device and a contact-closure output are available as an option.  
These options detect condensation in the Liebert XDH’s catch pan and connect to a monitoring or  
alarm system. A front panel alarm and indicator alert the user to condensation inside the unit.  
The complete cooling system consists of Liebert XDH modules, Liebert XDP or Liebert XDC pumped  
refrigerant distribution units, power and signal cabling and interconnecting piping, see Figure 3  
below.  
Figure 3  
Liebert XDH hydraulic schematic  
Liebert XDC  
or  
Liebert XDP  
XD Cooling  
Module *  
Supply Lines  
(2 per unit)  
Pumped  
Refrigerant  
Return Lines  
(2 per unit)  
XD Cooling  
Module *  
Liebert XDC  
or  
Liebert XDP  
XD Cooling  
Module *  
Pumped  
Refrigerant  
XD Cooling  
Module *  
* XDCF, XDH, XDO  
or XDV  
3.2  
Checking and Unpacking  
When the Liebert XDH is delivered, inspect all items for either visible or concealed damage. Damage  
should be immediately reported to the carrier and a damage claim filed with a copy sent to Liebert or  
to your sales representative. If you later find any concealed damage, report it to the shipping company  
and your local Liebert representative.  
Check to be sure all required assemblies and parts have been received.  
The Liebert XDH is shipped in protective packaging and secured to a pallet (see Figure 5). Do not  
remove these protective items from the Liebert XDH before it is at the installation location. When  
unpacking and handling the Liebert XDH, exercise extra care to prevent damage.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
General product information  
3.3  
Equipment Inspection  
Upon arrival of the unit, and before unpacking, verify that the labeled equipment matches the Bill of  
Lading. Inspect all items for visible and concealed damage. Damage should be immediately reported  
to the carrier and a damage claim filed with a copy sent to Liebert Corporation or to your sales repre-  
sentative.  
3.3.1 Recyclable Packaging  
All material used to package this unit is recyclable. Please save for future use or  
dispose of the material appropriately.  
R
WARNING  
!
Risk of top-heavy unit falling over. Can cause death, injury and equipment damage.  
Read all of the following instructions before attempting to move, lift, remove packaging from  
the unit, or preparing unit for installation.  
CAUTION  
!
!
Risk of overhead interference. Can damage unit or structure.  
The unit may be too tall to fit through a doorway while on the skid. Measure the unit and  
doorway heights and refer to the installation plans before moving the unit to verify  
clearances.  
CAUTION  
Risk of sharp edges, splinters and exposed fasteners. Can cause personal injury.  
Only properly trained personnel wearing appropriate safety headgear, gloves, shoes and  
glasses should attempt to move, lift, remove packaging from, or prepare unit for installation.  
CAUTION  
!
!
Risk of damage from forklift. Can cause exterior and/or underside damage.  
Keep tines of the forklift level and at a height suitable to fit below the skid.  
CAUTION  
Risk of hazardous environments. Can cause unit damage.  
Keep the unit indoors and protected from dampness, freezing temperatures and contact  
damage.  
Figure 4  
Recommended unit handling equipment  
Pallet Jack  
Forklift  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
General product information  
3.3.2 Unit Handling  
If possible, transport the unit using a forklift or pallet jack.  
• If using a forklift or pallet jack, ensure that the fork tine length is suitable to safely move the  
packaged unit.  
• Liebert recommends keeping the unit in the protective packaging until it has been moved to the  
installation site.  
• When handling and unpacking the unit, exercise great care to prevent damage.  
• Do not lift the unit any higher than 6" (152mm) while moving it. If it must be lifted higher than 6"  
(152mm), exercise great care and keep all personnel who are not helping move the unit at least 20'  
(5m) away from the unit.  
• The Liebert XDH ships with four outrigger-style wheels to permit rolling it into position. Liebert  
recommends using a forklift or pallet jack to move the Liebert XDH as near as practical to its  
installation site before removing it from the shipping pallet.  
3.3.3 Unpacking the Unit  
1. Remove the exterior stretch-wrap packaging from around the unit, exposing the protective corner  
and side packaging planks.  
2. Remove the ramp, corner and side packaging planks from the unit, exposing the bag over the unit.  
Remove the bag when ready to install the Liebert XDH.  
Figure 5  
Removing shipping package  
Planks at the corners and on  
the sides protect the Liebert  
XDH during shipping  
Exterior stretch wrapping  
surrounds other protec-  
tive shipping features  
Leave the plastic bag on the unit  
until it is off the pallet and ready  
to be installed  
Ramp  
(secured to the Liebert XDH by a  
layer of shrink-wrap)  
NOTE:  
One ramp will be shipped per order.  
Ramp  
(removed from pallet)  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
General product information  
3.3.4 Taking the Unit off the Pallet  
WARNING  
!
Risk of unsecured unit rolling off pallet. Can cause equipment damage, injury or death.  
The Liebert XDH is on casters. Ensure that the unit/skid is located on a flat surface before  
loosening the hardware securing the Liebert XDH to its shipping pallet.  
The Liebert XDH ships with four outrigger-style wheels to permit rolling it into position for  
installation. Liebert recommends using a forklift or pallet jack to move the Liebert XDH as  
near as practical to its installation site before removing it from the shipping pallet.  
1. Locate the ramp that was shipped with the Liebert XDH (see Figure 5).  
2. Loosen the hex screw on the ramp and remove the metal bracket (see Figure 6).  
3. Rotate the metal bracket 180 degrees and insert the shortest slot of the metal bracket under the  
hex screw head and tighten the hex screw.  
4. Loosen the two hex screws on the skid.  
5. Align the ramp and the metal bracket with the skid. Ensure that the ramp is in contact with the  
skid (see Figure 7).  
6. Insert the opposite end of the metal bracket under the hex screws on the skid. (see Figure 7)  
7. Tighten the hex screws on the skid.  
8. Remove the six hex screws from each of the two tie-down brackets, one located on either end of the  
Liebert XDH. (see Figure 7).  
9. Remove the two tie-down brackets.  
10. At least two properly trained personnel may roll the Liebert XDH down the ramp and off the  
pallet onto a flat surface.  
Figure 6  
Prepare ramp to remove the Liebert XDH from shipping pallet  
Lag screw  
to secure bracket  
to ramp  
Metal  
Bracket  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
General product information  
Figure 7  
Attaching ramp, removing the Liebert XDH from pallet  
Tie-Down Bracket  
(removed from pallet)  
Bracket installed,  
securing ramp  
to shipping pallet  
Lag screw - 1 of 6  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Mechanical Considerations  
4.0 MECHANICAL CONSIDERATIONS  
4.1 Determining Placement in the Conditioned Space  
The Liebert XDH units should be placed among the cabinets that generate the greatest amount of  
heat. If heat loads are dispersed evenly throughout the room, the Liebert XDH modules may be  
spread out accordingly.  
The Liebert XDH is engineered to fit among computer enclosure cabinets. Figure 8, below, illustrates  
the unit’s dimensions.  
Figure 8  
Liebert XDH dimensions  
12"  
(305mm)  
80"  
(2032mm)  
78"  
(1981mm)  
FRONT  
42  
(1067mm)  
FRONT  
4.2  
Installing the Liebert XDH Within the Enclosure Row  
Built-in casters allow rolling the Liebert XDH into position for installation. Stabilizers reduce the like-  
lihood of the unit tipping over. These stabilizers must be removed before the unit is positioned in the  
row. Adjustable leveling feet prevent it from moving after positioning.  
Once positioned, the Liebert XDH must be secured either to the floor with the included shipping  
brackets or to an adjacent cabinet. An adjustable bracket (Liebert P/N 187642G1) for attaching the  
Liebert XDH to an adjacent cabinet is included with each unit.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Mechanical Considerations  
4.2.1 Airflow Direction  
If the Liebert XDH is installed at the end of a row, Liebert recommends using uni-directional air dif-  
fusers. The uni-directional diffusers are designed to blow cooling air to the left; the diffusers can be  
used for right air discharge by removing them from the Liebert XDH, turning them 180 degrees, then  
reattaching them to the Liebert XDH.  
If the Liebert XDH is installed between racks, Liebert recommends using bi-directional air diffusers.  
These diffusers blow air right and left, as well as to the front.  
Two diffusers were shipped with the Liebert XDH. If uni-directional diffusers were ordered, the dif-  
fuser with the part number 186458 is designed for installation on the upper half of the Liebert XDH.  
The other diffuser, for use on the lower half of the Liebert XDH, has the part number 186459. When  
installed in these positions, the diffusers will direct the airflow to the left.  
If directing the airflow in the opposite direction would improve cooling, the diffusers may be switched.  
Figure 9  
Liebert XDH placement in enclosure row  
Hot  
Aisle  
Cold  
Aisle  
Hot  
Aisle  
Cold  
Aisle  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Mechanical Considerations  
Install Air Diffusers for Best Airflow Direction  
1. Remove the top diffuser, Part # 186458, from its packaging.  
2. Check the top diffuser’s fittings and insertion holes on the Liebert XDH to determine how the  
diffuser should be installed—the diffuser may be attached only one way on the top half of the  
Liebert XDH.  
3. Rotate the diffuser 180 degrees and press it against the lower half of the Liebert XDH until it  
snaps into the fittings (see Figure 10).  
The vanes in the diffuser now point in the opposite direction.  
4. Repeat Steps 1 through 3 to install the bottom diffuser, Part # 186459, on the upper half of the  
Liebert XDH.  
Figure 10 Change airflow direction  
Top Diffuser, Part # 186459,  
may be rotated180 degrees  
and installed on the lower half  
of the Liebert XDH  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Piping  
5.0 PIPING  
5.1 European Union Fluorinated Greenhouse Gas Requirements  
Stationary air conditioning, refrigeration, heat pump equipments and stationary fire protection sys-  
tems in the European Community market and operating with fluorinated greenhouse gases (f-gas),  
such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (F-gas).  
The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the atmo-  
sphere.  
The F-Gas Regulation requires operators to use use all measures that are technically feasible and do  
not entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to  
recover f-gas before disposing of equipment, as well as during service and maintenance.  
Refer to the full regulation for additional details.  
5.2  
System Connection Configuration  
If possible, connect the Liebert XDH’s upper and lower refrigeration circuits to Liebert XDPs or Lie-  
bert XDCs in an interlaced configuration (see Figure 11). Interlacing the connection piping will keep  
one of the Liebert XDH’s circuits operating should one of the Liebert XDP or Liebert XDC units fail.  
However, in a system with just one Liebert XDP or Liebert XDC, connect Liebert XDH modules in a  
non-interlaced configuration (see Figure 12).  
Figure 11 Typical Liebert XDH piping—interlaced connections  
Liebert  
XDH  
Liebert  
XDH  
Liebert  
XDH  
Liebert  
XDH  
Unit 1  
Unit 2  
Unit 3  
Unit 4  
Liebert XDP /  
Liebert XDC #1  
Supply  
Liebert XDP/  
Liebert XDC #1  
Return  
Liebert XDP/  
Liebert XDC #1  
Supply  
Liebert XDP/  
Liebert XDC #2  
Return  
Liebert XDP/  
Liebert XDC #2  
Drawing is not to scale.  
Line sizes do NOT indicate  
piping sizes.  
Equipment racks not shown  
for clarity.  
Liebert XDP /  
Liebert XDC #2  
Liebert  
Liebert  
Liebert  
Liebert  
XDH  
XDH  
XDH  
XDH  
Unit 5  
Unit 6  
Unit 7  
Unit 8  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Piping  
Figure 12 Typical Liebert XDH piping—non-interlaced connection  
Liebert  
XDH  
Liebert  
XDH  
Liebert  
XDH  
Liebert  
XDH  
Unit 1  
Unit 2  
Unit 3  
Unit 4  
Liebert XDP /  
Liebert XDC #1  
Supply  
Liebert XDP/  
Liebert XDC #1  
Return  
Liebert XDP/  
Liebert XDC #1  
Supply  
Liebert XDP/  
Liebert XDC #2  
Return  
Liebert XDP/  
Liebert XDC #2  
Drawing is not to scale .  
Line sizes do NOT indicate  
piping sizes .  
Equipment racks not shown  
for clarity.  
Liebert XDP /  
Liebert XDC #2  
Liebert  
Liebert  
Liebert  
Liebert  
XDH  
XDH  
XDH  
XDH  
Unit 5  
Unit 6  
Unit 7  
Unit 8  
Figure 13 Direct system configuration—hydraulic system schematic  
Direct Liebert XD System Configuration  
Pumping and control are performed by Liebert XDC.  
Liebert  
Liebert  
Liebert XD  
Cooling Module *  
Heat  
XDC Coolant  
Supply Piping  
Return Piping  
Rejection  
Chiller  
Pumped  
Refrigerant  
Liebert XD  
Cooling Module *  
Liebert  
XDC Coolant  
Chiller  
Liebert XD  
Cooling Module *  
Pumped  
Refrigerant  
* Liebert XDCF,  
Liebert XDH, Liebert  
XDO or Liebert XDV  
Liebert XD  
Cooling Module *  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Piping  
Figure 14 Indirect system configuration—hydraulic system schematic  
Indirect XD  
System Configuration  
Liebert XDPs pump refrigerant to cooling modules, isolate the  
refrigerant circuit from the building’s chilled water supply with an  
internal heat exchanger and maintain refrigerant above the dew point.  
Building  
Chilled  
Water  
Liebert  
XDP  
Liebert XD  
Cooling Module *  
Supply Piping  
Pumped  
Refrigerant  
Return Piping  
Liebert XD  
Cooling Module *  
* Liebert XDCF,  
Liebert XDH, Liebert  
XDO or Liebert XDV  
Liebert XD  
Cooling Module *  
Liebert  
XDP  
Pumped  
Refrigerant  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Piping  
5.3  
Connection Methods and Points  
Refer to site specific drawings for general locations of the piping connections. For Liebert XDH con-  
nection locations, refer also to Figure 16.  
The assembly and connection means used for piping in the Liebert XD system are the same as those  
used in conventional refrigeration systems. Observe all standard practices during installation and  
startup to prevent damage and contamination.  
Supply piping connection is 1/2" OD copper pipe, and return piping connection is 7/8" OD copper. Both  
supply and return fittings may be supplied with optional one-shot connections. These fittings contain  
pressurized R-134a refrigerant inside the Liebert XDH.  
The Liebert XDH has supply and return piping access on the top of each module.  
Figure 15 Hard pipe connection diagram  
Return Main  
(seen from end )  
2-1/8" O.D.  
Recommended Arc  
or 2-5/8" O.D.  
Acceptable Arc  
Supply Main  
(seen from end )  
1-1/8" O.D.  
or 1-3/8" O.D.  
7/8” Refrigerant-Grade  
Full-Port Ball Valve  
Field-Supplied and  
Field-Installed  
1/2” Refrigerant-Grade  
Full-Port Ball Valve  
Field-Supplied and  
Field- Installed  
Copper Tubing  
Total length of each  
line from Liebert XDH  
to Main; not to exceed  
72" (1829mm)  
Supply  
to Cooling  
Return from  
Refer to Table 2 for details.  
Module  
Cooling Module  
Top of  
Liebert XDH  
Rear of  
Liebert XDH  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Piping  
5.4  
Piping Considerations—Hard-Piped Connections  
Refrigerant enters and exits the Liebert XDH through connections on the top of the unit (see  
The supply piping for each refrigeration circuit is 1/2" OD copper pipe. The return piping for each cir-  
cuit is 7/8" OD copper. Each Liebert XDH has two supply connections and two return connections, one  
for each refrigeration circuit.  
The Liebert XDH units that are intended for hard-piping connections will have copper caps soldered  
in place and a holding charge of nitrogen.  
Figure 16 Supply and return—hard-piping connections  
Top of Liebert XDH  
6"  
(153mm)  
3-5/8"  
(92mm)  
1/2" Supply, Upper  
Refrigeration Circuit  
7/8" Return, Upper  
Refrigeration  
Circuit  
1-3/8" (35mm)  
Detail “A”  
2-1/8"  
(54mm)  
4-1/8"  
(105mm)  
5"  
(127mm)  
Rear of  
Liebert XDH  
Rear of Liebert XDH  
7/8" Return, Lower  
Refrigeration Circuit  
1/2" Supply, Lower  
Refrigeration Circuit  
Detail "A"  
5.4.1 Venting the Holding Charge and Connecting to Mains  
After the piping for the supply and return mains has been installed, the Liebert XDH units may be  
connected. The Liebert XDH is shipped with a low-pressure holding charge (about 30 psi) of nitrogen to  
prevent oxidation and moisture. Holding charges must be vented from the upper refrigeration circuit and  
from the lower refrigeration circuit.  
To vent the holding charge:  
1. Find the four Schrader valves that retain the nitrogen holding charge in the Liebert XDH. The  
valves are inside the rear door, one on each supply line and one on each return line. Three are  
near the top of the Liebert XDH; one Schrader valve is in the bottom half of the Liebert XDH.  
2. Vent the holding charge in the upper refrigeration circuit by depressing the pin in a Schrader  
valve on either the supply or return line for that circuit. (The upper circuit’s lines are on the left  
side of the unit.)  
3. Replace and secure the cap on the Schrader valve that was opened.  
4. Vent the holding charge in the lower refrigeration circuit by depressing the pin in a Schrader  
valve on either the supply or return line for that circuit. (The lower circuit’s lines are on the right  
side of the unit.)  
5. Replace and secure the cap on the Schrader valve that was opened.  
6. Use a torch to unsweat the caps on unit’s piping connections.  
7. Pipe the Liebert XDH’s supply and return connections to the mains. See 5.4.2 - Brazing  
Preparations for precautions about connecting the Liebert XDH to the piping mains.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Piping  
5.4.2 Brazing Preparations  
After the holding charge has been vented, a torch can be used to remove the caps over the ends of the  
supply and return lines.  
The assembly and connection means used for piping in the Liebert XD system are similar to those  
used for conventional refrigeration systems. All piping should be installed with high-temperature  
brazed joints. Soft soldering is not recommended.  
During brazing, the lines must be filled with flowing dry nitrogen to prevent excessive oxidation and  
scale formation inside the piping. Prevailing good refrigeration practices must be employed for piping  
supports, leak testing, dehydration and charging. Failure to use good system practices may result in  
damage to the system. Refer to the ASHRAE refrigeration handbook for general good-practice refrig-  
eration.  
5.5  
Connection Methods for Hard Pipe  
The assembly and connection means used for piping in the Liebert XD system are the same as those  
used in conventional refrigeration systems. Observe all standard practices during installation and  
startup to prevent damage and contamination.  
5.6  
Recommended Piping Size  
Connect the main pipes between the Liebert XDH branch piping and the Liebert XDP or Liebert XDC  
according to Table 2. Elbows and restrictions must be minimized to ensure good fluid flow.  
Please see Table 2 below for recommended pipe sizes and Figure 3 for piping segment locations.  
Table 2  
Branch piping sizes for pumped refrigerant loop  
Pipe Function  
Size / Equivalent Pipe Length  
1/2" OD (0.430" ID) for lengths up to 10 feet (3m)  
From Liebert XDH supply to supply line of  
Liebert XDP/Liebert XDC  
7/8" OD(0.545" ID) for lengths over 10 feet but less than 25 feet (3-7.6m)  
7/8" OD(0.545" ID) for lengths up to 10 feet (3m)  
From Liebert XDH return to return line of  
Liebert XDP/Liebert XDC  
1-1/8" OD(1.025" ID) for lengths over 10 but less than 25 feet (3-7.6m)  
NOTE  
To minimize the amount of pumped refrigerant required, do NOT oversize the piping.  
5.6.1 Connecting Methods—One-Shot Connections  
CAUTION  
!
Risk of sudden refrigerant discharge. Can cause loss of charge and minor injury.  
If the optional precharged option is chosen, the Liebert XDH is shipped with a full charge of  
R-134a refrigerant under pressure. Do not remove the pipe caps or plugs before the unit is  
ready for connection to Liebert XD Piping.  
Supply and return fittings on the precharged Liebert XDH units are one-shot connections. Do  
not disconnect one-shot connections after they have been connected. Disconnection will  
release pressurized R-134a refrigerant from the Liebert XDH.  
The assembly and connection means used for piping in the Liebert XD system are the same as those  
used in conventional refrigeration systems. Observe all standard practices during installation and  
startup to prevent damage and contamination.  
Both supply and return fittings may be supplied with optional, one-shot connections. These fittings  
contain pressurized R-134a refrigerant inside the Liebert XDH.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Piping  
Figure 17 Piping location and connecting sizes for pre-charged units  
6"  
(153mm)  
3-5/8"  
(92mm)  
1/2" Supply, Upper  
Refrigeration Circuit  
7/8" Return, Upper  
Refrigeration  
Circuit  
1-3/8" (35mm)  
2-1/8"  
(54mm)  
4-1/8"  
(105mm)  
5"  
(127mm)  
Rear of Liebert XDH  
7/8" Return, Lower  
Refrigeration Circuit  
1/2" Supply, Lower  
Refrigeration Circuit  
5.7  
Field Installation of Liebert XD Flex Pipe Kit on the Liebert XDH  
Liebert XD Flex Pipe kits are available in lengths of 4, 6, 8 and 10 feet (1.2, 1.8,2.4 and 3 meters).  
Connection style to the unit end may be straight or 90 degrees. Connection to the prefab piping  
assembly is a threaded coupler. For data on acquiring the correct kit for your installation, see  
Figure 18 Liebert XD Flex Pipe dimensions—straight and 90-degree connections  
Connection  
to Prefabricated  
Piping assembly  
Connection  
to Prefabricated  
Piping assembly  
90-Degree  
Connection  
Length  
4, 6, 8 or 10 feet  
(1.2, 1.8, 2.4 or 3 meters)  
Length  
4, 6, 8 or 10 feet  
(1.2, 1.8, 2.4 or 3 meters)  
Straight Connection  
90° Connection to Liebert XD Cooling Unit  
(One-Shot Coupling)  
Connection to Liebert XD Cooling Unit  
(One-Shot Coupling)  
DPN000780  
Pg. 1, Rev. 1  
DPN000780  
Pg. 2, Rev. 1  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Piping  
5.8  
Connecting Liebert XD Flex Pipes to Liebert XDH Modules  
CAUTION  
!
Risk of high pressure refrigerant discharge. May cause injury and air pollution.  
Do not disconnect one-shot refrigerant connections after they have been connected.  
Disconnection will release pressurized R-134a refrigerant from the Liebert XDH.  
1. Remove the caps on the supply and return lines on the top of the Liebert XDH.  
2. Lubricate the threads, diaphragm and O-ring with one or two drops of mineral oil.  
3. Connect the line-set coupling finger-tight.  
4. Make sure the Schrader valve is properly oriented; refer to the label on the top of the Liebert  
XDH.  
5. Hold the backup hex nut with a wrench while tightening the swivel nut.  
6. Tighten the swivel nut on the female coupling until it is seated or a definite resistance is felt.  
7. Once a definite bottoming resistance is felt (as in metal to metal), place a mark lengthwise from  
the swivel nut to the backup hex and tighten the swivel nut on the female coupling an additional  
1/4 turn.  
8. Tighten the supply fittings to 35-45ft/lb (47-61Nm).  
9. Tighten the return fittings to 55-65ft/lb (74-88Nm).  
10. Mark the female and male coupler with for future reference.  
5.8.1 Header System  
The Liebert XDH module system with optional flexible piping requires use of the Liebert XD prefabri-  
cated piping assembly. The prefabricated piping is compatible with the Liebert XD Flex Pipe required  
to attach to the Liebert XDH modules. For the details on piping connection locations, see Figure 16.  
For additional information, refer to the Liebert X-treme Density System Design Manual, SL-16655.  
5.9  
Connecting a Liebert XDH with Liebert XD Flex Pipe to an Operational Liebert XD  
System  
NOTE  
Before connecting the Liebert XDH with Liebert XD Flex Pipe to the prefabricated piping  
mains, check the entire system for leaks.  
Check the holding charge in the Liebert XDH to ensure that the unit has no leaks.  
Read all instructions before beginning installation.  
Tools Required  
• Two adjustable wrenches, with a maximum adjustment size of 2-1/2 inches  
• Screwdriver, Phillips or blade type  
NOTE  
This operation requires two people.  
1. Determine the port location of the supply and return piping overhead  
2. Make sure the service valve for each port is closed  
3. Remove cap for only the required ports. Do not remove caps from the unused ports.  
4. Once Step 3 has been completed, remove the pipe plugs that are supplied on the Liebert XD Flex  
Pipe.  
5. Use system refrigerant to lubricate the face of the male coupling half, including the poppet valve  
face and the stainless steel delta ring.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Piping  
Figure 19 Liebert XD prefabricated piping assembly  
Return Main  
Service Valve, typical  
(all ports)  
Supply Main  
Threaded Cap  
(Typical)  
6. Thread the return couplers together. The return couplers are the larger of the couplers.  
7. Use one of the adjustable wrenches to hold the fixed side of the female coupler on the Liebert XDH  
stationary. With the other adjustable wrench, tighten the collar onto the coupler.  
Tighten these only until the force required to tighten abruptly increases. See Figure 20.  
NOTICE  
Do not overtighten the couplers. Overtightening of couplers will damage the couplers.  
Figure 20 Detail view of Liebert XD Flex Pipe and prefabricated piping port  
Service Valve  
Note:  
Make sure the valve  
is closed before attaching  
Liebert Flex Pipe to the system.  
Supply Side Torque Range for  
1/2" coupler is 22.1 to 25.8 lb/ft (30-35Nm)  
Tighten collar  
with wrench.  
DO NOT  
Return Side Torque Range for  
1" coupler is 59 to 62.7 lb/ft (80-85Nm)  
OVERTIGHTEN!  
Hold threaded coupler here  
with a wrench to keep the  
pipe stationary while tightening  
collar with another wrench.  
Liebert Flex Pipe  
8. Repeat Steps 6 and 7 for the smaller couplers (supply line).  
9. Once the supply and return connections are completed, open the return service valves, then open  
the supply service valves.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Piping  
Figure 21 Liebert XD system with prefabricated piping assembly and Liebert XD Flex Pipe  
Return Service Valve  
Make sure valve is  
open after system  
leak check  
Supply Service Valve  
Make sure valve is  
open after system  
leak check  
Return  
Main  
Supply Main  
Return Liebert  
Flex Pipe  
Supply Liebert Flex Pipe  
5.10 Disconnecting a Liebert XDH With Liebert XD Flex Pipe From a Liebert XD System  
CAUTION  
!
Risk of sudden discharge of pressurized refrigerant. Can cause equipment damage or injury.  
Do not disconnect threaded refrigerant couplers at the unit cabinet end without relieving  
system pressure. Reclaim any refrigerant during removal of unit from system.  
NOTICE  
Before uninstalling a Liebert XDH with Liebert Flex Pipe from the prefabricated piping  
mains: Close the supply service valve, wait approximately two minutes, then close the return  
service valve.  
Read all instructions before beginning.  
Tools Required  
• Two adjustable wrenches, maximum adjustment size of 2-1/2 inches  
• Phillips head #2 screwdriver  
1. Close the service valves in the supply line to the Liebert XDH (smaller couplers).  
2. Close the service valves in the return lines to the Liebert XDH (larger couplers).  
3. Locate and have ready the caps and plugs for both ends of the supply and return couplers.  
4. Loosen the female supply couplers from the male supply couplers (smaller couplers). This  
requires two adjustable wrenches. Refer to Figure 20.  
5. The Liebert XDH side of the female couplers must be held stationary while the collars on the  
couplers are being loosened. Refer to Figure 20.  
6. Disconnect the couplers.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Piping  
Figure 22 Profile view of the Liebert XD system  
Service  
Valve  
Return  
Line  
Supply  
Line  
7. Place the protective dust cap and plug back onto both ends of the couplers on the Liebert XDH  
and the port pipe.  
Figure 23 Piping mains without Liebert XDH and Liebert XD Flex Pipe  
8. Repeat Steps 5 through 7 for the return couplers (larger couplers).  
9. Carefully lay the Liebert XD Flex Pipe aside.  
CAUTION  
!
Risk of tubing kinks. Can cause permanent damage to the Liebert XD Flex Pipes.  
Do not fold or bend Liebert XD Flex Pipe.  
5.11 Insulation  
To minimize the possibility of condensation, insulate all piping between the Liebert XDH and the Lie-  
bert XDP or Liebert XDC.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Electrical  
6.0 ELECTRICAL  
The unit must be installed in accordance with national wiring regulations. Refer to the unit’s serial  
tag for electrical requirements. Refer to Table 3 for details.  
WARNING  
!
Risk of electric shock. Can cause death or injury.  
Disconnect both electric power cords before working within the unit.  
6.1  
Connecting High Voltage Wiring  
The Liebert XDH requires single-phase power for normal operation. The unit ships with two power  
cords, each 10 feet (3m) long with NEMA 5-15 plugs, which connect to common, three-prong outlets  
(see Figure 24).  
The XDH will function properly with only one power cord. The second power cord permits connection  
to a separate power source to increase reliability—If one power source fails, the cord connected to the  
remaining, live power source will power both banks of fans.  
To attach the power cords, clip the plastic hangers attaching the cords to the Liebert XDH. Press the  
appropriate end of each cord onto the electrical inlet. Attach the strain-relievers onto the power cords  
and press the assemblies into the cable exit slots.  
Figure 24 Liebert XDH electrical connections  
60Hz MODELS ONLY  
Field wiring connections  
at terminal strip to be NEC  
Class 2. Use switch contacts  
with 75VA minimum rating.  
50Hz MODELS ONLY  
Field wiring connections  
at terminal strip for safety extra  
low voltage circuits only. Use  
switch contacts rated 75VA  
minimum, 24VAC maximum.  
IEC Primary  
Power Inlet  
IEC Secondary  
Power Inlet  
Condensate Detection  
Dry Contacts-Low Voltage  
Connections  
(Upper Circuit 84, 85)  
Condensate Detection  
Dry Contacts-Low Voltage  
Connections  
(Lower Circuit 82, 83)  
Rear of Liebert XDH  
Panel Removed for Clarity  
Power Cord Strain Relievers  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Electrical  
6.2  
Connecting Low Voltage Wiring—Optional  
Low voltage connections to the Liebert XDH are available only on units with the optional condensate  
detection feature. The low voltage connections are on the left side of the cabinet, in the rear, near the  
power connections (see Figure 24). These dry contacts can to be connected to a monitoring unit, such  
®
as Liebert’s SiteScan . For location of the entry points for the condensate detection wiring, see  
For units equipped with condensate detection, make low voltage connections according to site-specific  
drawings.  
The Liebert Liqui-tect condensate detection unit is available only as a factory-installed option.  
Figure 25 Condensate wiring entry points  
Top of  
Liebert XDH  
Detail  
Area  
Rear of Liebert XDH  
Condensate  
Detection  
Wiring Ports  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installation Checklist and System Fill for Startup  
7.0 INSTALLATION CHECKLIST AND SYSTEM FILL FOR STARTUP  
7.1  
Checklist for Proper Installation  
___ 1. The Liebert XDH module is properly mounted.  
___ 2. Power cords connected to electrical supply.  
___ 3. For Liebert XDH units with coupler option: Flex piping connections to prefabricated header  
assembly are secure and according to specifications.  
___ 4. For Liebert XDH units with coupler option: Check for holding charge of R-134a.  
___ 5. Low voltage wiring to optional condensate detection on the Liebert XDH.  
___ 6. Piping from Liebert XDP to Liebert XDH, with isolation valves piped to each Liebert XDH.  
___ 7. Piping insulated.  
___ 8. Start the Liebert XDH to ensure proper operation (see 8.1 - Start the Liebert XDH).  
___ 9. Shut down the Liebert XDH.  
7.2  
Charging with Refrigerant and Starting the Liebert XD System  
The Liebert XD System must be completely installed before it is charged with refrigerant. After  
installation is complete, refer to the Liebert XDP or Liebert XDC user manual for instructions on  
charging the Liebert XDH with refrigerant and starting the system. The complete Liebert XD system  
includes all Liebert XDH, XDO and XDV units, a Liebert XDC or Liebert XDP unit and any other  
connected equipment.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Operation  
8.0 OPERATION  
The Liebert XDH’s controls are on the front of the unit at the Liebert XDH’s midline for easy access.  
Each switch controls the operation of one bank of three fans (see Figure 26). The separate switches  
permit the use of only one bank of fans at a time, reducing the airflow if the Liebert XDH’s full cooling  
capacity is not needed.  
NOTE  
At least one of the Liebert XDH’s banks of fans must be turned on before either the Liebert XDP  
or Liebert XDC is switched on.  
At least one of the Liebert XDH’s banks of fans must be operating at all times that the Liebert  
XDP or Liebert XDC is operating. Operating either the Liebert XDP or the Liebert XDC without  
at least one of the Liebert XDH’s banks of fans rotating may cause a system malfunction.  
Figure 26 Fan switches  
Upper Fan Bank Switch  
Lower Fan Bank Switch  
8.1  
Start the Liebert XDH  
The Liebert XDH’s fans must be on before starting the Liebert XDP or Liebert XDC that will supply  
refrigerant to the Liebert XDHs.  
To start the Liebert XDH, press either of the rocker switches to turn on one or both of the Liebert  
XDH’s banks of fans. Pressing the left switch starts the fans in the upper half of the Liebert XDH; the  
right switch, the lower fans.  
The refrigerant sources, either Liebert XDP or Liebert XDC, must be started separately.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Maintenance  
9.0 MAINTENANCE  
Minimal maintenance is required to keep the Liebert XDH operating at optimal levels. The unit  
should be cleaned and checked for damage and worn parts. Suggested maintenance includes:  
• Cooling fins—Clean any dust and debris from the cooling fins, taking care not to bend them  
• Circulating fans—Clean any dust from the fans.  
9.1  
Internal Access  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
System contains hazardous electrical voltage. Disconnect both power cords from the electrical  
supply outlets or from the receptacles on the back of the Liebert XDH before working within.  
• Turn off the two fan switches on the front of the Liebert XDH (see Figure 26).  
The conditions required for sensitive electronic equipment should preclude the accumulation of appre-  
ciable amounts of dust in the Liebert XDH. Most of that small amount should be found on the coils,  
which are accessible by opening the rear door of the unit. The fans, on the front may be cleaned by  
removing the front grilles, which are secured with snap-on connections.  
The rear door and the fan tray on the front of the Liebert XDH are easily removed for maintenance. (A  
wiring diagram is provided on the center shelf.)  
9.2  
Fluorinated Greenhouse Gas Requirements  
Stationary air conditioning, refrigeration, heat pump equipments and stationary fire protection sys-  
tems in the European Community market and operating with fluorinated greenhouse gases (f-gas),  
such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (F-gas).  
The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the atmo-  
sphere.  
The F-Gas Regulation requires operators to use use all measures that are technically feasible and do  
not entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to  
recover f-gas during equipment service and maintenance and before disposing of equipment.  
Refer to the full regulation for additional details.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Maintenance  
9.3  
Remove Fan Tray  
WARNING  
!
Risk of electric shock. Can cause injury or death.  
System contains hazardous electrical voltage. Disconnect both power cords from the electrical  
supply outlets or from the receptacles on the back of the Liebert XDH before working within.  
• Turn off the two fan switches on the front of the Liebert XDH (see Figure 26).  
1. Ensure that all electrical power to the Liebert XDH has been shut off before beginning to remove  
the fan tray.  
2. Remove four bolts on the Liebert XDH fan tray (see Figure 27).  
3. Lift the tray out of the unit to install the new tray.  
Reverse the steps above to install a new fan tray. Be certain to align the connectors, including the  
electricity connector, when installing the new fan tray.  
Figure 27 Remove fan tray  
Remove four bolts  
securing the fan tray  
to the front of the XDH  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Specifications  
10.0 SPECIFICATIONS  
Table 3  
Liebert XDH specifications  
XDH20DKP-0  
XDH20DK--0  
XDH20BKP-0  
XDH20BK--0  
XDH20DKPE0  
XDH20DK-E0  
XDH20BKPE0  
XDH20BK-E0  
(60Hz)  
XDH32DKP-0  
XDH32DK--0  
XDH32BKP-0  
XDH32BK--0  
XDH32DKPE0  
XDH32DK-E0  
XDH32BKPE0  
XDH32BK-E0  
(60Hz)  
XDH20DSP-0  
XDH20DS--0  
XDH20BSP-0  
XDH20BS--0  
XDH20DSPE0  
XDH20DS-E0  
XDH20BSPE0  
XDH20BS-E0  
(50/60Hz)  
XDH32DSP-0  
XDH32DS--0  
XDH32BSP-0  
XDH32BS--0  
XDH32DSPE0  
XDH32DS-E0  
XDH32BSPE0  
XDH32BS-E0  
(50/60Hz)  
Models  
XDH20, 60Hz Nominal (98ºF [37°C] EAT): 22kW/6.3 Tons  
XDH20, 60Hz Maximum(105ºF [40°C] EAT): 25.5kW/7.3 Tons  
XDH20, 50Hz Nominal (98ºF [37°C] EAT): 19kW / 5.4 Tons  
XDH20, 50Hz Maximum(116ºF [47°C] EAT): 25.5kW/7.3 Tons  
Cooling Capacity  
XDH32, 60Hz Nominal (98ºF [37°C] EAT): 30kW/8.5 Tons  
XDH32, 60Hz Maximum(105ºF [40°C] EAT): 34.5kW/7.3 Tons  
XDH32, 50Hz Nominal (98ºF [37°C] EAT): 27kW / 7.7 Tons  
XDH32, 50Hz Maximum(108ºF [42°C] EAT): 34.5kW/7.3 Tons  
Capacity rating is @ 55ºF (13ºC) Entering Fluid Temperature and 50ºF (10ºC) or lower dew  
point  
Conditions  
Electrical Requirements  
Input  
220-240V-1ph-50Hz, CE /  
120V-1ph-60Hz  
208-240V-1ph-60Hz, CSA  
Two IEC320-C14 power inlets and two IEC  
power cords with NEMA 5-15P connectors  
Two IEC320-C14 power inlets and two IEC  
power cords with IEC320-C14 receptacles  
Input Power Connections  
Full Load Amps  
5
10  
2.5  
5
Power Consumption,  
Nominal, Watts  
600  
1200  
575  
1150  
Dimensions, inches (mm)  
Height—Unit Only  
78 (1981)  
80 (2032)  
Height—Including  
Pipe Connections  
Width  
Depth  
12 (305)  
42 (1067)  
Weight, lb (kg)  
Unit Only  
233 (106)  
317 (144)  
246 (112)  
330 (150)  
233 (106)  
317 (144)  
246 (112)  
330 (150)  
Shipping Weight  
6
Number of Fans  
Airflow, Nominal,  
ft /min (m /hr)  
2500 (4248)  
81 dBa  
4000 (6796)  
86 dBa  
2428 (4125)  
81 dBa  
3850 (6541)  
86 dBa  
3
3
Audible Noise,  
Sound Power  
Pipe Connections  
Refrigerant Supply  
Refrigerant Return  
Serviceable Parts  
1/2" OD, Cu (optional 1/2" threaded one-shot coupling on the unit)  
7/8" OD, Cu (optional 7/8" threaded one-shot coupling on the unit)  
Fans and electrical components  
Cabinet Exterior Finish  
Black, matte finish, heat-fused powder coat  
Condensate Sensing (factory-installed)  
Dry contact outgoing signal (24VAC - 1A maximum)  
Options  
One-shot style flex pipe connections  
Uni-directional or bi-directional air diffusers  
Agency  
Approvals  
CSA 60Hz  
CE 50Hz, CSA 50/60Hz  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Specifications  
Table 4  
Liebert XD Flex Pipe assemblies, supply and return  
Minimum Bend Radius  
inches (mm)  
Liebert P/N  
Straight Connection  
Assembly  
Liebert P/N  
90-Degree Connection  
Assembly  
Length  
ft (m)  
Description  
Supply  
Return  
186566G1  
186566G2  
186566G3  
186566G4  
186565G1  
186565G2  
186565G3  
186565G4  
6 (1.8)  
10 (3.0)  
8 (2.5)  
4 (1.2)  
Liebert XD Flex  
Pipe Kit  
7 (178)  
9 (229)  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ensuring The High Availability  
Of Mission-Critical Data And Applications.  
Technical Support / Service  
Web Site  
Emerson Network Power, the global leader in enabling business-critical  
continuity, ensures network resiliency and adaptability through  
a family of technologies—including Liebert power and cooling  
technologies—that protect and support business-critical systems.  
Liebert solutions employ an adaptive architecture that responds  
to changes in criticality, density and capacity. Enterprises benefit  
from greater IT system availability, operational flexibility and  
reduced capital equipment and operating costs.  
Monitoring  
800-222-5877  
Outside the US: 614-841-6755  
Single-Phase UPS  
800-222-5877  
Outside the US: 614-841-6755  
Three-Phase UPS  
800-543-2378  
Environmental Systems  
800-543-2778  
Outside the United States  
614-888-0246  
Locations  
United States  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
Europe  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD) Italy  
+39 049 9719 111  
Fax: +39 049 5841 257  
Asia  
7/F, Dah Sing Financial Centre  
108 Gloucester Road, Wanchai  
Hong Kong  
While every precaution has been taken to ensure the accuracy  
and completeness of this literature, Liebert Corporation assumes no  
responsibility and disclaims all liability for damages resulting from use of  
this information or for any errors or omissions.  
© 2008 Liebert Corporation  
All rights reserved throughout the world. Specifications subject to change  
without notice.  
852 2572220  
Fax: 852 28029250  
® Liebert is a registered trademark of Liebert Corporation.  
All names referred to are trademarks  
or registered trademarks of their respective owners.  
SL-17210_REV08_05-08  
Emerson Network Power.  
The global leader in enabling Business-Critical Continuity.  
EmersonNetworkPower.com  
AC Power  
Connectivity  
DC Power  
Embedded Computing  
Embedded Power  
Monitoring  
Outside Plant  
Racks & Integrated Cabinets  
Power Switching & Controls  
Services  
Precision Cooling  
Surge Protection  
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.  
©2008 Emerson Electric Co.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Lenmar Enterprises Battery Charger PRO744 User Manual
Lenovo Tablet N3S2PUK User Manual
LG Electronics Range LRG3091ST SB SW User Manual
Life Fitness Treadmill 5500 HR User Manual
Lightolier Indoor Furnishings 1113IE User Manual
Lindy Network Card 51143 User Manual
Loewe Flat Panel Television L 26 DVB T C CI User Manual
Makita Saw LS1040F User Manual
Maytag Clothes Dryer MEDE500VF0 User Manual
Melissa Hot Beverage Maker 245065 User Manual