		 Liebert DCP   
					STANDARD FEATURES   
					HEAT EXCHANGER - Brazed plate design with interwoven circuiting constructed of stainless steel plates, copper brazed.   
					PUMPS - Centrifugal type.   
					STANDARD CONTROL PROCESSOR -   
					The standard control system is microprocessor-based with an external LCD numerical display to allow   
					observation of specified settable functions. Normal operating conditions are indicated on the LCD display panel,   
					which is mounted to the unit. The control system also monitors unit operation and activates an alarm when any   
					of the specified factory preset conditions are exceeded.   
					CABINET AND FRAME -   
					Custom powder painted steel panels. A hinged control access panel opens to a second front panel, which is a   
					protected enclosure for all high voltage components. Frame is constructed of 14 gauge heli-arc welded tubular steel   
					and painted using an auto-deposition coating system.   
					Page 1/5   
					DPN002400   
					REV DATE 11/11   
					REV 0   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Liebert DCP   
					Liebert DCP   
					Bottom View   
					Drip Tray Dimensions   
					19.5”   
					3.9”   
					3.8”   
					3.1”   
					SECONDARY   
					IN   
					SECONDARY   
					OUT   
					7.2”   
					6.5”   
					BCW IN   
					BCW OUT   
					37”   
					Unit Piping Outlet Connection Sizes, inches, Od Cu   
					MODEL   
					50/60 HZ   
					DCP200   
					Pipe Connection Point   
					A 
					B 
					C 
					D 
					2-5/8   
					2-5/8   
					2-5/8   
					2-5/8   
					REV DATE 05/11   
					PAGE 4/6   
					Page 3/5   
					DPN002400   
					REV 0   
					REV DATE 11/11   
					REV 0   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Liebert DCP   
					Liebert DCP   
					Three phase electric service   
					not provided by Liebert   
					Monitoring panel   
					Factory installed unit   
					disconnect switch   
					Field supplied disconnect switch may   
					not be required, check local codes.   
					ELECTRIC CONDUIT KNOCKOUTS   
					On top of electric box. Knockout size   
					2 in (51 mm)   
					Three phase electric service   
					not provided by Liebert   
					THREE PHASE CONNECTION   
					Electric service connection terminals   
					CANBUS ISOLATOR   
					ALARM AND WARNING OUTPUT RELAYS   
					Field supplied 24V Class 2 wire for   
					special alarms.   
					EARTH GROUND LUG   
					Connection terminal for   
					field supplied earth   
					grounding wire.   
					(Not to exceed 1.0A @ 24v each.)   
					REMOTE UNIT SHUTDOWN   
					Factory installed disconnect switch   
					Replace existing jumper between terminals   
					37 & 38 with normally closed switch having   
					a minimum 50VA rating. Use field supplied   
					24V Class 2 wire.   
					Factory wired to components   
					on electric panel   
					SITE MONITORING CONNECTION   
					Terminals 77 (-) and 78 (+) are for   
					connection of a 2 wire, twisted pair,   
					communication cable (available from   
					Liebert or others) for optional Sitescan.   
					(see user's manual).   
					INTELLISLOTS®   
					Two Liebert Intellislots® for optional   
					OCWEB-LBDS or OC485-LBDS card.   
					60HZ COMPONETS SHOWN   
					NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.   
					REV DATE 05/11   
					PAGE 5/6   
					Page 4/5   
					DPN002400   
					REV 0   
					REV DATE 11/11   
					REV 0   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Liebert DCP   
					Liebert DCP   
					Liebert DCP Extra Low Voltage field connection points   
					TO P64 ON ICOM CONTROL BOARD   
					RED ETHERNET CABLE   
					TO P66 ON ICOM CONTROL BOARD   
					TERMINATION PLUG   
					TO REMOTE T/H SENSOR B   
					TO REMOTE T/H SENSOR A   
					COMMON WARNING OUTPUT   
					TO OPTIONAL   
					EXTERNAL   
					FOR CONTACTS INDICATING AN   
					ALARM CONDITION.   
					(MAX) 1.0AMP @ 24V   
					CONNECTIONS   
					P66 P67   
					P64   
					K11   
					K11   
					K11NO K11COM K11NC   
					TO REMOTE ALARM   
					CIRCUIT BY OTHERS   
					INPUT: REMOTE ALARM DEVICE   
					FOR INDICATION OF ALARM, WIRE   
					N.O. CONTACTS FROM REMOTE   
					ALARM DEVICE AS SHOWN.   
					UNIT DISPLAY(REARVIEW)   
					24   
					50   
					N.O. CONTACT BY OTHERS   
					FACTORY WIRED   
					TEMPERATURE SENSOR.   
					P67   
					INPUT: CONDENSATION   
					DETECTION   
					ALARM WHEN CLOSED.   
					DO NOT   
					USE   
					24   
					51   
					N.O. CONTACTS REQUIRED   
					INPUT: FAN BREAKER STATUS   
					1 
					ALARM WHEN CLOSED.   
					24   
					54   
					N.O. CONTACTS REQUIRED   
					COMMON ALARM OUTPUT   
					FOR CONTACTS INDICATING AN   
					ALARM CONDITION.   
					(MAX) 1.0AMP @ 24V   
					K3   
					K3   
					K3NO K3COM   
					K3NC   
					TO REMOTE ALARM   
					CIRCUIT BY OTHERS   
					1 
					INPUT: REMOTE SHUTDOWN   
					NOTES:   
					FOR SHUTDOWN OF CONTROL   
					CIRCUIT, REMOVE JUMPER   
					BETWEEN TERMINALS 37 & 38   
					AND REPLACE WITH N.C. CONTACT   
					1. CONTROL WIRING MUST BE CLASS 2 AND INSTALLED IN   
					ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC).   
					37   
					38   
					2. REQUIRES SHIELDED CABLE.   
					N.C. CONTACTS BY OTHERS   
					LIEBERT SITE MONITOR   
					FOR DIGITAL COMMUNICATIONS   
					WITH LIEBERT SITE MONITORS   
					ONLY. CONNECT 2 WIRE TWISTED   
					PAIR TO 77 & 78. ALSO SEE SITE   
					MONITOR INSTALLATION MANUAL.   
					2 
					77   
					78   
					(+)   
					R or W   
					(-)   
					BK   
					REV DATE 05/11   
					PAGE 6/6   
					Page 5/5   
					DPN002400   
					REV 0   
					REV DATE 11/11   
					REV 0   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				 |