Liebert Blowtorch SL 14050 User Manual

SGH Steam  
Generating Humidifier  
Installation and  
Operation Guide  
IMPORTANT: Read and save this guide for future  
reference. This guide to be left with equipment owner.  
SL-14050  
Form # 99-428 Rev. 1 / 150-1633 Rev. A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Report any discrepancy immediately.  
INSTALLATION  
BASIC HUMIDIFIER CONFIGURATION  
RECEIVING & UNPACKING EQUIPMENT  
Liebert humidifier model SGH has a right side  
electrical compartment. Each electrical compartment  
has a hinge-down front door which is removable from  
any partially or fully opened position. Each electrical  
compartment has a screw-mounted right side cover  
which can also be removed for ease of electrical  
connection. For safety, the door when closed keeps  
the side cover from being removed.  
1. Check packing slip to ensure ALL material has  
been delivered.  
2. All material shortages are to be reported to  
Liebert within 48 hours from receipt of goods.  
Liebert assumes no responsibility for any  
material shortages beyond this period.  
3. Inspect shipping boxes for damage and note  
on shipping waybill accordingly.  
Single units have a plumbing compartment  
attached to the left side of the electrical. Double units  
have a second plumbing compartment. Each  
plumbing compartment has a hinge-down front door  
which is not intended to be removed. For safety, the  
door must be closed in order to engage the lock. To  
avoid any danger, never operate the humidifier with a  
door off. For safety, each door when closed engages  
its own safety interlock switch. All switches must be  
engaged before the unit will operate.  
4. After unpacking, inspect equipment for  
damage and if damage is found, notify the  
shipper promptly.  
5. All Liebert products are shipped on an F.O.B.  
factory basis. Any and all damage, breakage  
or loss claims are to be made directly to the  
shipping company.  
To open the doors, unlock key, lift door up slightly  
and pull top of door forward. Door will hinge 180  
degrees and hang straight down. To remove door,  
swing door parallel to floor. Then lift up slightly and  
out. To reinstall door, hold parallel to floor and insert  
hinge pins at bottom. The door can then be closed.  
PRE-INSTALLATION CHECKPOINT  
1. Ensure that available voltage and phase  
corresponds with humidifier voltage and phase  
as indicated on humidifier’s nameplate label  
(see Figure #1).  
Figure #2  
Clearance Requirements  
Figure #1  
SGH Series Humidifier  
WALL  
Condensate  
Return  
Steam  
Outlet  
WITHOUT BLOWER PACK  
TOP VIEW  
MIN. 36"SIDE  
CLEARANCE  
RECOMMENDED.  
SEENOTE.  
NOTE: LOCAL AND NATIONAL  
CODES MAY DEVIATE. PLEASE  
CONSULT APPLICABLE CODES  
FOR CLEARANCE REQUIREMENTS  
IN ALL CASES.  
MIN. 36"  
FRONTAL  
CLEARANCE.  
Power And  
Control  
Wiring  
Nameplate  
Label  
Drain  
Water  
Supply  
LOCATION & MOUNTING  
2. Ensure that the dedicated external disconnect  
is of sufficient size to handle the rated amps  
as indicated on the nameplate label. Refer to  
local codes.  
HUMIDIFIERS  
SGH humidifiers are designed to mount on a  
suitable wall or vertical surface. Do not sit on floor due  
- 1 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
to clearances required for plumbing, electrical, and  
control entrances. The clearance dimensions shown  
in this manual are for reference only and are the  
minimum required for maintenance of the humidifier.  
Local and National Codes should be consulted prior to  
final location and installation of the humidifier. Liebert  
can not accept responsibility for installation code  
violations.  
In addition, install a minimum of 2 field  
supplied fasteners in the holes provided in the  
back of the unit to prevent the unit from being  
bumped off the wall bracket.  
6. Make sure humidifier is level.  
7. DO NOT mount humidifier on hot surfaces.  
1. Location of the humidifier should be below and  
as close as possible to the steam distributor  
location as possible.  
8. If humidifiers are mounted on roof, a  
thermostatically ventilated weatherproof  
cabinet by others should be used. Consult  
factory.  
2. For front and side clearance requirements (for  
access during installation, maintenance and  
troubleshooting), see Figure #2.  
9. DO NOT mount humidifiers in an area where  
freezing may occur.  
3. If possible, DO NOT locate humidifier any  
further than absolutely necessary from steam  
distributor location, as net output will be  
reduced as a result of heat loss through steam  
hose. Also, increased static pressure may  
cause operational problems and necessitate  
use of the fill cup extension kit and other  
components.  
10. DO NOT mount humidifiers on vibrating  
surface.  
BLOWER PACKS  
1. Blower packs are an optional accessory used  
to directly distribute steam to localized areas  
(such as computer rooms) or in structures that  
do not have a built-in air distribution system.  
4. Where possible, mount humidifier at a height  
convenient for servicing.  
Figure #4  
Built On Blower Pack  
5. Wall mounting bracket provided should be  
securely attached horizontally and open edge  
upwards, using field-supplied fasteners. Use  
a minimum of 3 - #12 x 3" long wood screws,  
or better, into a vertical structural surface. If  
any spacer material is used between the  
bracket and the structural material such as  
drywall, increase fastener length accordingly.  
Built-In  
Supply Air  
Grille  
Optional  
Built-On  
Blower Pack  
Built-In Steam  
Distributor  
Single  
Circuit  
Humidifier  
Figure #3  
Wall Bracket Mounting Detail  
WALL  
7.7”  
(19.6 cm)  
FASTENWALLBRACKET  
(FACTORYSUPPLIED)TO  
WALLUSING ANCHORBOLTS  
(3) SUPPLIEDBYOTHERS  
Power And  
Control  
Wiring  
See Figure #6 for mounting clearances.  
2. Blower packs are available integrally-mounted  
on humidifier (built-on blower pack, BOBP,  
see Figure #4) or detached and field-piped  
and wired to humidifier (remote mounted  
blower pack RMBP, see Figure #5).  
- 2 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Figure #5  
Figure #6  
Overhead and Frontal Clearances for Blower  
Packs  
Remote Mounted Blower Packs (SGBP)  
WALL  
SIDE  
FRONT  
SGH  
Model  
Min.  
Min. Overhead  
Clearance  
Min. Front  
Clearance  
inches (cm)  
3.2”  
(8 cm)  
Number  
of Blower inches (cm)  
Packs  
010  
020  
050  
100  
200  
1
1
1
1
2
18 (45)  
18 (45)  
36 (91)  
48 (122)  
42 (122)  
30 (76)  
36 (91)  
POWER AND  
CONTROL  
CONDENSATE  
STEAM  
WIRING FROM  
HUMIDIFIER  
84 (213)  
156 (396)  
156 (396)  
See Figure #6 for mounting clearances.  
3. All SGH blower packs consist of a steel  
cabinet containing: blower/motor powered by  
voltage directly from the humidifier, fuse, relay,  
speed select switch, stainless steel steam  
distributor, supply air grille with adjustable  
louvers, and built-in manual reset safety  
thermostat to turn off the humidifier if the  
blower pack gets overheated. Control  
thermostat, mounted on the steam distributor,  
starts the fan when steam is generated. When  
supply voltage differs from voltage required to  
run blower motor, blower pack will contain a  
proper transformer. All blower packs provide  
intake air filters.  
*Remote mounted only. Four remote mounted blower  
packs are recommended on the 200 model.  
Nominal conditions 72ºF, 35% RH.  
STEAM DISTRIBUTORS  
1. Each cylinder requires its own steam line  
and at least one distributor (do not join two  
or more cylinders to one larger steam line).  
Any cylinders steam line may be divided into  
multiple branches to feed more than one  
distributor. Steam supply line teesare  
common copper fittings that are available for  
this purpose.  
4. Refer to Figure #6 for overhead and frontal  
clearances required for blower packs.  
Minimum clearance for the sides of the  
Blower Pack unit is 12 inches. Dimensions  
apply to both built-on and remote-mounted  
versions of blower packs.  
2. Steam distributor locations are typically as  
follows: supply air duct, return air duct, air  
handling unit. Proper location should  
consider: air temperature, relative humidity  
before the distributor, air velocity, dimensions  
of the location, amount of steam being  
introduced into the duct, downstream  
obstructions, and surfaces vulnerable to  
wetting.  
5. Mount remote blower pack(s) using factory  
supplied wall mounting bracket, see Figure #5,  
with clearance as recommended in Figure #6.  
6. Steam distributor on the built-on and remote  
blower packs have a hot surface that could  
result in burns if touched. If space allows, we  
recommend mounting at least 8 feet above the  
floor.  
3. When steam distributors are located in a duct,  
they should be in a straight section of duct at  
least 6 feet (2 meters) from any elbow or  
obstruction. If the duct or plenum conditions  
result in poor absorption distance  
7. Do not use blower packs as ducted blowers.  
The air volume from a blower pack is not  
sufficient to absorb the steam generated.  
characteristics, please consult your local  
representative or the factory. See Figure #7.  
4. Steam distributors should always span the  
width of the air stream. Multiple steam  
distributors, arranged in a bank, can  
minimize absorption distance.  
8. Pipe the steam line as stated in the STEAM  
LINE section on page 6.  
- 3 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Figure #7  
Steam Distributor Location  
downward slope to the distributor will result in  
poor condensate drainage and spittingof  
condensate in duct. See Figure #9.  
6'  
Min.  
Figure #9  
Leveling Distributor  
6'  
Min.  
Wrong  
Mount Steam Distributor  
At Least 6' (2 M) From Elbow  
Multiple Steam Distributors  
Can Reduce This Distance  
Support  
(If Needed)  
Correct  
Always  
Mount  
Level  
5. Exercise extreme caution when installing in  
fiber glass or internally lined ducts.  
6. High positive or negative static pressure ducts  
or plenums have special requirements. High  
positive static pressure ducts may require the  
unit to be fitted with a fill cup extension kit.  
High negative static pressure ducts will likely  
require the drain rate of the humidifier to be  
increased to compensate for the reduced  
drainage caused by the suction.  
Wrong  
Figure #10  
Distributor Support  
7. Vertical downflow ducts may induce an  
artificial static pressure necessitating a fill cup  
extension kit.  
3/8" Threaded Rod  
(Field Supplied)  
8.  
Low temperature ducts below 60 F (15 C),  
shallow ducts, or branch ducts might require  
the use of a field supplied condensate drain  
pan below the steam distributor. See Figure  
#8.  
Figure #8  
Condensate Drain Pan  
Hex Nut  
Duct  
Steam Distributor  
Factory Attached  
SHALLOW DUCT  
DRAIN PAN  
TO DRAIN  
Figure #11  
T-BAR CEILING  
Cutting Duct for Mounting  
BRANCH DUCT  
1.  
2.  
3.  
DRAIN PAN  
9. The steam distributor mounting plate is  
perpendicular to the steam distributor. When  
the mounting plate is attached to the side of  
the duct, the distributor is level. An upward or  
1. Steam Distributor Mounting Plate  
2. Cut Hole In Duct For Insertion Using Template  
3. Mount With Four Sheet Metal Screws  
- 4 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10. Any distributor longer than 3 feet (1 meter)  
should be supported at its end with a threaded  
rod through top or bottom of duct. See Figure  
#10.  
below is proportioned accordingly. See Figure  
#14. For short steam absorption systems see  
Figure #13.  
Figure #14  
11. It is recommended that single distributors are  
mounted near the bottom of the duct to ensure  
the steam is dispersed into the majority of the  
air flow. See Figure #12.  
Multiple Steam Distributors for Better Mixing  
MIN. H = 16"  
8"  
4"  
4"  
4"  
4"  
4"  
Figure #12  
Single Steam Distributor Installation  
2/5  
H
2/5  
1/5  
Min. W = 12"  
H 20"  
W 17"  
1/3  
1/3  
1/3  
PLUMBING  
12. Using duct mounting template provided, cut a  
hole in side of duct just large enough to admit  
steam manifold and condensate drain pipe  
assembly. Use four sheet metal screws to  
attach mounting plate to side of duct. See  
Figure #11 and #12.  
All water supply and drain line connections  
should be installed in accordance with local  
plumbing codes.  
WATER SUPPLY LINE  
1. Humidifier is intended to operate on potable  
(cold) tap water.  
13. With multiple steam distributors, the top steam  
distributor should be at least 8" below top of  
duct to avoid possible condensation on  
2. If the raw water is very hard, Liebert can  
provide longer cylinder life on softened water.  
However, softened water is more conductive  
and more corrosive. Some hardware and/or  
software changes may be required, at time of  
order or in the field. Consult local  
surface of duct. The remainder of space  
Figure #13  
Multiple Steam Distributors  
representative.  
3. DO NOT use a hot water supply to humidifier.  
Minerals will adhere more easily to surfaces  
and the fill valves small flow regulating orifice  
could become plugged.  
8"  
Steam Header  
4. Standard fill valves are sized for water  
pressure ranging from 30 to 150 psig. For  
other pressures, consult local representative.  
This pressure should be measured at the  
humidifier if the water pressure is suspect.  
- 5 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
5. ALWAYS supply and install a shut off valve in  
the water supply line dedicated to the  
humidifier to facilitate servicing. Use ½" OD  
copper to within 4 feet of the humidifier.  
Reduce copper to 3/8" OD and connect to the  
factory-supplied 3/8" olive compression fitting  
under the humidifier.  
codes prohibit it. Route to a floor drain or  
equivalent for safety reasons, since drain  
water from humidifier can be very hot.  
3. Keep drain lines as short as possible. Keep  
drain lines sloped down, not level and not  
up since low spots in drain lines will  
accumulate sediment and cause backup.  
The drain line should be 1" O.D. copper pipe  
or larger. Do not use plastic pipe for drain  
lines.  
DRAIN LINE  
1. Humidifier is equipped with a 7/8" O.D.  
unthreaded drain outlet on underside of drain  
canal on bottom of the humidifier (see Figure  
#15). A supplied reducer (see Figure #16)or  
equivalent shall be installed on the drain line.  
It will prevent backup in the drain pan and in  
the cylinder due to partially blocked or badly  
installed drain lines. This prevents rusting of  
the drain pan and arcing due to  
STEAM LINE  
1. Steam lines for SGH models 010 through 020  
require a minimum 7/8" O.D. (nominal 3/4")  
copper pipe. For steam runs longer than 20 ft  
use insulated nominal 1" copper to ensure the  
draining of condensate.  
over-concentration. The drain canal has been  
improved to prevent backup despite long or  
gently sloped drain lines but it can not  
2. Field-supplied hard copper with ½" thick  
snap-on insulation is recommended for  
steam supply, with Liebert supplied steam  
hose coupling used to make connection to  
cylinder. See Figure #17.  
compensate for flat or uphill runs.  
Figure #15  
Drain Line Connection  
Figure #17  
B
Steam Line Connection  
Bottom View  
Clamp To Steam Distributor  
Or Remote Blower Pack  
Field Supplied  
Insulated Hard  
Copper Pipe  
Or Flexible  
Steam Hose  
A
See Section On  
Available  
Wall  
Condensate  
Trap  
From Factory  
Return Line  
MODEL  
010-020  
050-100  
200 LEFT  
200 RIGHT  
A in. (mm)  
1.0 (25)  
2.2 (55)  
2.2 (55)  
2.2 (55)  
B in. (Mm)  
5.0 (127)  
6.2 (158)  
6.2 (158)  
19.6 (498)  
Figure #16  
Figure #18  
Sloping the Steam Line  
Min. 10 Degree Slope  
FactorySupplied  
Taperedcutis  
recommended  
ClampAnd  
7/8"I.D. Hose  
Air Gap  
Min. 12"  
Copper Reducer  
(11/4-3/4”)To  
Serve AsFunnel  
Drain. Factory  
supplied.  
Trap  
* See Section On  
Condensate  
Return Line  
3/4Copper Pipe  
(NotSupplied)  
NOTE: Steam hose should not reach bottom of the funnel.  
In the event the building drain is plugged this becomes an  
overflow point.  
2. The drain line should not end in a sink used  
frequently by personnel, or where plumbing  
NOTE: Trap must be 3' minimum down from steam distributor.  
If not, condensate must be routed to drain.  
- 6 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
3. Liebert steam supply hose or field-supplied  
piping should be sloped downwards from the  
steam distributors to the humidifier. Slope  
should be at least 2" in 12" to promote  
condensate runback. See Figure #18. If this  
slope is not possible, condensate must be  
removed before the distributor. See Figure  
#19.  
6. To ensure odor-free steam, always use Liebert  
steam hose. Check steam hose and hose  
couplings periodically for cracks, breaks,  
kinks. Replace as required. DO NOT  
substitute hose. Liebert is not responsible for  
health effects or damage from substitute hose.  
7. Steam lines for SGH 050 through 200 require  
1-5/8" O.D. (nominal 1-1/2") copper pipe. For  
steam runs longer than 40 ft use insulated  
nominal 2" copper to ensure the draining of  
condensate.  
Figure #19  
Long Steam Lines  
8. Do not use steel or plastic pipe for steam  
distribution, or hose other than Liebert  
supplied. Substitution will void warranty.  
9. If steam line is routed below steam distributor  
or if the steam distributor is lower than the  
humidifier, a condensate trap teewill be  
required to remove water at this low point.  
Run condensate from trap to nearest drain  
lower than the distributor. See Figure #21.  
Condensate To Drain  
Figure #21  
4. Minimize the length of steam line and keep it  
as straight as possible, minimizing bends.  
Also, avoid using 90 elbows. Wherever  
possible, use long radius turns (using tube  
bender on oversized copper or pairs of 45  
elbows). This will reduce the condensate  
generated by heat loss. This will also reduce  
the back pressure and avoid the need to  
buy/install an accessory Fill Cup Extension Kit.  
See Figure #22.  
Condensate Tee at any Low Point in Steam Line  
NOT ACCEPTABLE  
WITHOUT TRAP "TEE"  
DUCT  
OBSTRUCTION  
HUMIDIFIER  
5. Ensure that the steam hose does not kink or  
sag. The steam hose becomes more flexible  
when hot. The hose should be supported to  
prevent water traps. Only use steam hose for  
connections or steam lined runs of 5 feet or  
less. See Figure #20.  
TO FLOOR  
CONDENSATE "TEE"  
DRAIN  
AT LOW POINT IN  
STEAM HOSE  
CONSULT FACTORY  
CREATE A FALSE LOW POINT TO REMOVE  
CONDENSATE WHENEVER THE  
STEAM LINE MUST APPROACH THE  
DISTRIBUTOR FROM ABOVE.  
Figure #20  
Steam Hose Routing  
AVOID WATER TRAPS  
AVOID KINKS  
10. All built-on blower packs are factory-fitted with  
all steam hose connections. No further work  
is required.  
11. Do not run steam line more than 1 foot per  
lb/hr output. Example, 10 lbs/hr should not  
have a steam run longer than 10 feet. If long  
runs are unavoidable, the humidifier should be  
sized larger to compensate for condensate  
losses and insulated copper should definitely  
be used.  
PROPER  
SLOPE  
GENTLE  
SWEEPING  
TURNS  
- 7 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES - FILL CUP EXTENSION KIT(S)  
condensate hose with clamps is supplied with  
Lieberts steam distributors to serve as a  
flexible coupling. DO NOT direct solder field  
copper condensate line to steam distributors.  
1. The SGH humidifier is an electrode humidifier.  
It produces steam at atmospheric pressure.  
Pressure head must develop to push steam  
through supply line and into air duct.  
2. Always incorporate a trap in routing of  
condensate return line. Condensate that  
accumulates in trap will prevent possibility of  
steam escaping. Depth of trap must exceed  
duct static pressure by 2 inches of water  
column. See Figure #23.  
2. Combined resistance of duct positive static  
pressure and steam line resistance creates a  
small pressure head in steam cylinder. Total  
amount of positive static pressure head is  
reflected directly by water column differential  
that develops between water in the fill cup  
hose feeding cylinder and water level in  
cylinder.  
Figure #23  
Trap to Prevent Steam in Condensate Line  
3. Standard dimensions of humidifier limit static  
that can be tolerated before water will be  
pushed high enough to spill over into overflow  
tube in fill cup assembly.  
4. To increase allowable water column (allowable  
positive static pressure) an accessory Fill Cup  
Extension Kit is available from Liebert. See  
Figure #22.  
3 FEET MINIMUM  
TRAP  
Figure #22  
Fill Cup Extension Kit to Overcome Static Pressure  
CONDENSATE TRAP  
DEPTH OF TRAP  
MUST BE 2" MORE THAN  
DUCT STATIC PRESSURE  
OF WATER COLUMN  
FILL CUP BRACKET  
FILL CUP  
OVERFLOWHOSE  
3. Condensate return line can not be run back to  
fill cup if humidifier is within 36" of being level  
with steam distributor. See Figure #18.  
HOSEFROMFILLVALVE  
FILL HOSE TO  
CYLINDER  
4. If steam distributor is mounted level with or  
below humidifier, condensate line must be  
routed to nearest floor drain or to a  
condensate pump (available from Liebert).  
See Figure #24.  
Figure #24  
Drain Pump (if necessary)  
Humidifier  
CONDENSATE RETURN LINE  
Drain Line  
1. Each steam distributor has a built-in  
condensate return (3/8" O.D. copper tubing).  
Flexible condensate return hose (3/8" I.D.)  
available from Liebert, is recommended for  
routing condensate back into humidifiers fill  
cup. Note: A short length of 3/8" O.D. copper  
tubing is supplied by Liebert for use when  
routing condensate hose back to humidifiers  
fill cup. Similarly, a short length of 3/8" I.D.  
Line  
Drain  
Pump  
Floor  
Surface  
5. Provide a Utrap in condensate line even  
when distributor is located in return air  
plenum. It stops a suction action from  
- 8 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
impeding condensate flow when duct  
pressures are below atmosphere.  
on the steam distributor, starts the fan when  
steam is generated.  
6. The condensate line can go to either of two  
large holes in the fill cup cover on top of  
humidifier.  
3. All blower packs have high efficiency blowers  
to minimize the frontal and overhead  
clearance required to absorb the steam.  
7. It is not necessary to return the condensate to  
the humidifier.  
4. All built-on blower packs are factory wired to  
humidifier. Primary voltage wiring to  
humidifier, as described in electrical primary  
voltage supply wiring, is all that is required to  
power humidifier and blower packs.  
8. Long condensate runs (more than twenty feet)  
should be sloped well and be constructed out  
of ½" nominal copper pipe to ensure flow.  
5. Remote mounted blower packs require field  
wiring between two primary voltage terminal  
blocks and two low voltage control (class 1  
circuit wiring required) terminal strips; one of  
each located in humidifier and remote blower  
pack cabinet. To properly access the primary  
block on the humidifier, it may be necessary to  
remove the side. To connect the primary and  
control (class 1 circuit wiring required) wiring,  
the wiring is fed through the knockouts  
ELECTRICAL  
PRIMARY VOLTAGE SUPPLY WIRING TO  
HUMIDIFIER  
1. Check and ensure that available voltage and  
phase corresponds with operating voltage and  
phase of humidifier as indicated on the  
humidifier nameplate label (see Figure #1).  
provided in the bottom of the blower pack.  
The terminal block and strip are accessed by  
removing the blower pack cover.  
2. Ensure that an adequate power supply is  
available to carry full humidifier amperage  
drawn as specified by rated amps on the  
humidifier nameplate label refer to local codes.  
6. Field wiring of remote blower packs must  
conform to national and local electrical codes.  
Refer to wiring diagram supplied inside the  
humidifier.  
3. A dedicated external disconnect must be  
installed. Do not exceed the maximum circuit  
protection amps as indicated on the  
nameplate label.  
7. Use approved wire for power connection from  
two pole terminal block of remote blower pack  
to additional two pole terminal block inside  
electrical section of humidifier.  
4. Connect ground wire to cabinet ground clamp.  
Do not use neutral wire of four wire supply as  
ground.  
8. Use approved wire to connect from ground  
clamp of remote mounted blower pack to  
ground clamp provided in the electrical section  
of humidifier.  
5. Single phase humidifiers may be run on three  
phase power, but load may unbalance power  
grid.  
LOW VOLTAGE CONTROL WIRING  
On-Off Controls  
6. External wiring sizes must be in accordance  
with NEC and/or CEC and existing local  
electrical codes and by-laws.  
Figure #25  
External Wiring of On/Off Controls  
PRIMARY VOLTAGE SUPPLY WIRING FROM  
HUMIDIFIER(S) TO BLOWER PACKS  
A
B
C
1. All blower packs are wired (by factory if  
built-on, by others if remote mounted) to be  
powered from the humidifier.  
EXTERNAL  
8
10  
INTERNAL  
2. As a safety feature, blower packs come  
equipped with a manual reset safety  
thermostat and relay built into the blower pack  
cabinet. The manual reset thermostat turns  
off the humidifier if the blower pack gets  
overheated. The control thermostat, mounted  
Controls are available from Liebert as accessories.  
If controls were not ordered with humidifier, they must  
be purchased supplied by others. The following  
- 9 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
information is relevant to all controls, factory supplied  
or otherwise.  
or down stream from distributor. Mount it  
where airs humidity and temperature are  
uniform and representative of spaces being  
humidified.  
A, B and C (described below) are to be wired in  
series (only one path for current) across terminals 8  
and 10 on the low voltage control terminal strip, or  
replaced with a jumper wire for constant operation  
(see Figure #27). Caution: If any control field wiring  
touches ground metal unit, safeties will be bypassed.  
3. Mount duct high limit humidistat  
downstream of steam distributors far enough  
that, under normal humidity and air flow  
conditions, steam will have been fully  
absorbed (typically at least 10 feet). It must  
be located to sense high humidity only when  
uniform and representative air is  
A - Wall or Duct Mounted Control On/Off  
Humidistat: Wired to make on drop in humidity, break  
on rise to setpoint. Set to desired % RH. Can be a  
make/break set of contacts from a Building Automation  
System.  
over-humidified or approaching saturation.  
4. Mount duct air-proving switch so that it is  
able to sense air flow or lack of it. Wire it to  
make when air flow is sensed and break when  
air flow fails. Mount prior to distributor.  
B - Duct Mounted Safety High Limit On/Off  
Humidistat (if used): Wired to make on drop in  
humidity, break on rise to safety setpoint. Set to  
approximately 85% RH as a safety to help prevent  
saturation and wetting in the duct.  
5. Check operation of all on/off controls before  
starting humidifier.  
C - Duct Mounted Safety Air-Proving On/Off  
Switch (if used): Wired to make when sensing air  
flow, break when no air flow. Used as a safety to  
prevent saturation when no air flow.  
6. Calibration of controls (on/off or modulation) in  
the field may be necessary due to shipping  
and handling. Verify humidistat accuracy  
before commissioning system.  
1. Liebert offers various versions of A, B and C to  
suit each application. In general, A is  
essential, whereas B and C are highly  
recommended in ducted applications.  
OPTIONAL MODULATION (CONTINUOUS  
CONTROLS) (see Figure #28)  
1. Read on/off controls section first since it is  
necessary to all control systems.  
2. Field wiring from humidistat to humidifier and  
between devices should be 18 AWG or  
heavier and kept as short as possible.  
2. Virtually any modulation (continuous control)  
external hardware by others (as long as it has  
%RH setpoint circuitry) may be interfaced with  
pre-specified factory-configured SGH pc  
board via the control terminal strip.  
3. Low voltage control terminal strips are  
provided in the electrical compartment.  
Internal sides are factory wired. External  
sides are to be field wired.  
3. Modulation (continuous control) by others for  
use with SGH humidifiers involves one of  
several control wiring diagrams. In all cases,  
modulating signal interfaces through control  
terminal strip to main pc board inside  
humidifier.  
4. Each humidifier is supplied with a wiring  
diagram inside.  
CONTROL INSTALLATION  
Figure #26  
Typical Modulation Wiring  
1. Mount any wall humidistat (control or high  
limit) over standard electrical box at height  
similar to typical thermostat. Any wall  
humidistat should be in location  
VariesWithEach  
ModulationOption  
SeeLiebertSupplied  
ExternalWiringDiagram  
representative of overall space being  
humidified and not in path of blower pack or  
air supply grille. Do not mount on a outside  
wall where temperature fluctuation can affect  
control response.  
A
B
C
External  
2. Mount duct humidistat in location  
8
10  
32 30  
representative of overall air humidity, usually  
return duct. Do not mount it directly in front of  
steam distributor or in turbulent or mixing zone  
Internal  
_
y
- 10 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. The modulation signal must increase from  
minimum toward maximum as sensed RH  
(actual RH) drops below desired RH (%RH  
setpoint). In response, humidifiers steam  
output will increase from minimum toward  
maximum. When humidifiers steam output  
(lbs/hr) matches humidification load (lbs/hr),  
modulation signal will stabilize.  
and the humidifier starts its operation. The controller  
waits 10 seconds before energizing the on-board  
relays. When the relays energize, heating voltage is  
delivered to the cylinder. After a 30 second delay, the  
fill valve is activated (if the output from the cylinder is  
below 100 %). If controller detects increase of  
amperage above allowed range, the unit will activate  
drain valve for 2 seconds.  
5. Field-wiring connections for modulation control  
are to be made to external side of terminals 30  
and 32 on humidifiers control terminal strip.  
Always refer to the external controls wiring  
diagram factory supplied with each Liebert  
modulation control option.  
During operation, the controller measures the rate  
at which water is converted to steam and thus the  
mineral content of water inside the cylinder. When this  
rate exceeds the design optimum, a drain of the  
cylinder takes place. The amount of water drained is  
just enough to keep the contained water at design  
levels.  
6. Varying dc Voltage Modulation Signal  
Powered by Others: SGH humidifier can be  
factory configured to accept the following vdc  
signals: 0-10 vdc, or 2-10 vdc. Wire  
according to Liebert supplied external wiring  
diagram that comes with each modulation  
option. To share the signal with more than  
one humidifier, wire in parallel to each  
humidifier. If a different signal is desired  
consult factory.  
During start up, when mineral content in the water  
is low, water will reach the top of the cylinder at which  
point the yellow indicator light will come on. This is  
normal operation with a fresh cylinder. After a period of  
time the water level will drop and the yellow light will  
turn off.  
High water level in the cylinder also indicates that  
the cylinder is near the end of its service life as  
electrodes become coated with minerals. The yellow  
light coming on more often would be the first indication  
of approaching the end of the cylinder life.  
7. Varying dc milliAmp (mA) Modulation  
Signal Powered by Others: SGH humidifier  
can be factory-configured to accept a standard  
dc mA signal, if pre-specified. Wire according  
to Liebert supplied external wiring diagram  
that comes with each modulation option.  
Choose from 0-20 dc mA or 4-20 dc mA. To  
share the signal with more than one humidifier  
consult factory.  
SGH OPERATION  
END OF CYLINDER LIFE  
When the cylinder is used up and water level can  
no longer stabilize below full cylinder (due to fully  
coated electrodes), the yellow light will flash in 4 pulse  
cycles. At this time the control board interrupts steam  
production and switches the green indicator lamp off.  
The disposable cylinder must be replaced.  
OPTIONAL MODULATION (CONTINUOUS  
CONTROL) PACKAGES BY LIEBERT  
Modulation (continuous control) packagesare  
offered as accessories by Liebert.  
It is wise to keep a new replacement cylinder on  
hand to avoid downtime when it becomes time to  
change the disposable cylinder.  
OPERATION  
MANUAL CAPACITY ADJUSTMENT  
On/Off Controls  
INTRODUCTION  
When the humidifier is first turned on, the  
controller starts with a self test procedure, which takes  
about 10 seconds. The test consists of activating for a  
short time the drain valve, fill valve, and power relays.  
The sound of the working solenoids is an indication of  
valves operation. Green and yellow lights flash during  
this time.  
The SGH humidifier is rated in lbs/hr of steam  
output capacity. Set to 100%, it will operate at full  
output until the humidistat has sensed that the  
humidity has reached setpoint. Then it will stop the  
humidifier by breaking control circuit 8-10.  
If the humidifier is oversized, the humidistat will be  
quickly satisfied and stop the humidifier. As humidity  
level drops the humidistat calls again. It is quickly  
If there is no call for humidity, the humidifier is  
standing by and green light flashes. When control loop  
is closed ( Figure #13), the green light is steady on  
- 11 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
satisfied and stops again. The resultant short-cycling  
is easily overcome.  
using a screwdriver, press the reset button (marked  
with a red dot) inside the blower packs.  
A manual capacity adjustment potentiometer  
(pot) is provided on the SGH main pc board for that  
purpose. It is marked CAPACITY ADJUSTand is  
adjustable from 25 to 100% of rating.  
Units are also equipped with speed select switch.  
The switch is located on the right-hand side of the  
blower, inside the blower pack. To access the switch,  
remove right-hand side intake air filter.  
Modulation Control  
To avoid condensation on the cabinet parts, run  
blower pack on high speed when humidifier delivers  
more than 50 lbs/hr of steam.  
The SGH humidifier, utilizing modulation control,  
does not have the same problems of over sizing. It  
reacts to the modulation signal and varies its capacity  
automatically. However, if you wish to turn down the  
capacity, use the manual capacity adjustment  
potentiometer (pot).  
OTHER POTENTIOMETERS  
Do not adjust any other potentiometers (pots) on  
the pc board(s). They are factory-set and not meant to  
be user-set.  
DETECTING WATER SUPPLY DEFICIENCY  
Knowing how long it normally takes to fill each size  
steam cylinder, each humidifiers pc board is factory  
configured to an acceptable maximum filling time. If it  
is filling too slowly, when the time expires the  
electronics stops the humidifier. To indicate this, the  
green light goes out and the yellow light goes on.  
REMOTE INDICATION  
Every SGH comes factory wired as a set of dry  
contacts at 61-20 on the control terminal strip. The  
user can connect an indicator externally to 61-20. It  
will automatically be activated any time a fault is  
detected.  
DOUBLE UNIT OPERATION  
Turn both switches on. If there is a demand for  
humidity, the green status lamp will indicate that the  
circuit is operating.  
BLOWER PACK OPERATION  
Blower packs are equipped with a control  
thermostat mounted on the steam distributor. As soon  
as humidifier generates steam, the contact is closed  
and the fan is started. When steam is no longer being  
generated, the fan cuts out with a delay.  
If blower packs get overheated (malfunction of the  
air circulation), the manual reset safety thermostat  
interrupts the steam generation. To reset, switch off  
the humidifier and wait until the steam distributor cools  
down. Then remove left-hand side intake air filter and,  
- 12 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
LIMITED WARRANTY  
Liebert Corporation (hereinafter collectively referred to as THE COMPANY),  
warrant for a period of two years from date of shipment, that THE COMPANYs  
manufactured and assembled products, not otherwise expressly warranted (with the  
exception of the cylinder) are free from defects in material and workmanship. No  
warranty is made against corrosion, deterioration, or suitability of substituted materials  
used as a result of compliance with government regulations.  
THE COMPANYs obligations and liabilities under this warranty are limited to  
furnishing replacement parts to the customer, F.O.B. THE COMPANYs factory,  
providing the defective part(s) is returned freight prepaid by the customer. Parts used  
for repairs are warranted for the balance of the term of the warranty on the original  
humidifier or 90 days, whichever is longer.  
The warranties set forth herein are in lieu of all other warranties expressed or  
implied by law. No liability whatsoever shall be attached to THE COMPANY until said  
products have been paid for in full and then said liability shall be limited to the original  
purchase price for the product. Any further warranty must be in writing, signed by an  
officer of THE COMPANY.  
THE COMPANYs limited warranty on accessories, not of Lieberts manufacture,  
such as controls, humidistats, pumps, etc. is limited to the warranty of the original  
equipment manufacturer from date of original shipment of humidifier.  
THE COMPANY makes no warranty and assumes no liability unless the  
equipment is installed in strict accordance with a copy of the catalog and installation  
manual in effect at the date of purchase and by a contractor approved by THE  
COMPANY to install such equipment.  
THE COMPANY makes no warranty and assumes no liability whatsoever for  
consequential damage or damage resulting directly from misapplication, incorrect sizing  
or lack of proper maintenance of the equipment.  
THE COMPANY retains the right to change the design, specification and  
performance criteria of its products without notice or obligation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Model # :_________________________  
Serial # :__________________________  
Cylinder # :_________________________  
Cylinder Last Replaced:  
_________________________  
MTH/DAY/YR  
_________________________  
MTH/DAY/YR  
_________________________  
MTH/DAY/YR  
LIEBERT CORPORATION  
1050 Dearborn Drive, P.O. Box 29186  
Columbus, Ohio 43229  
LR-35859  
Listed  
Humidifier  
E65185  
Tel: (614) 888-0246 Fax: (614) 841-6882  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Lennox Hearth Door 38ABF User Manual
Lenoxx Electronics Stereo System SL 6703 User Manual
Link electronic Network Router 860 XL165V User Manual
Lochinvar Water Heater 51 211 User Manual
Mackie Musical Instrument De Esser User Manual
Makita Pole Saw 4604D User Manual
MartinLogan Speaker System On Wall Off Wall Theatre User Manual
M Audio Car Speaker BX8A User Manual
Maytag Dryer Accessories W10550279C User Manual
Maytag Range MGR6751BD User Manual