Lennox International Inc Gas Heater Lennox Merit Series Gas Furnace Upflow Horizontal Air Discharge User Manual

INSTALLATION  
INSTRUCTIONS  
ML193UH  
E 2013 Lennox Industries Inc.  
Dallas, Texas, USA  
®
MERIT SERIES GAS FURNACE  
UPFLOW / HORIZONTAL AIR DISCHARGE  
507121-01  
08/2013  
Supersedes 06/2013  
Litho U.S.A.  
THIS MANUAL MUST BE LEFT WITH THE  
HOMEOWNER FOR FUTURE REFERENCE  
This is a safety alert symbol and should never be ignored.  
When you see this symbol on labels or in manuals, be alert  
to the potential for personal injury or death.  
CAUTION  
As with any mechanical equipment, personal injury  
can result from contact with sharp sheet metal  
edges. Be careful when you handle this equipment.  
AIR FLOW  
UPFLOW  
WARNING  
Improper installation, adjustment, alteration, service  
or maintenance can cause property damage, person-  
al injury or loss of life. Installation and service must  
be performed by a licensed professional HVAC in-  
staller (or equivalent), service agency or the gas sup-  
plier.  
HORIZONTAL RIGHT  
HORIZONTAL LEFT  
Table of Contents  
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
ML193UH Gas Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
Shipping and Packing List . . . . . . . . . . . . . . . . . . . . . . . . 3  
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
Use of Furnace as a Construction Heater . . . . . . . . . . . 4  
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Combustion, Dilution, Ventilation Air . . . . . . . . . . . . . . . 5  
Setting Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
Duct System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
Pipe and Fittings Specifications . . . . . . . . . . . . . . . . . . . 13  
Joint Cementing Procedure . . . . . . . . . . . . . . . . . . . . . . . 15  
Venting Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16  
Vent Piping Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37  
Integrated Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39  
Unit Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40  
Gas Pressure Measurement . . . . . . . . . . . . . . . . . . . . . . 41  
Proper Combustion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42  
High Altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42  
Testing For Combustion Air Non-Direct Vents . . . . . . . 44  
Other Unit Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . 45  
Twinning the ML193UH . . . . . . . . . . . . . . . . . . . . . . . . . . 45  
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46  
Repair Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47  
Start Up Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48  
08/13  
507121-01  
Page 1  
*P507121-01*  
*2P0813*  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ML193UH Gas Furnace  
Shipping and Packing List  
Package 1 of 1 contains  
The ML193UH Category IV gas furnace is shipped ready  
for installation in the upflow or horizontal position. The fur-  
nace is shipped with the bottom panel in place. The bottom  
panel must be removed if the unit is to be installed in hori-  
zontal or upflow applications with bottom return air.  
1 - Assembled ML193UH unit  
1 - Bag assembly containing the following:  
1 -Snap bushing  
1 -Snap plug  
The ML193UH can be installed as either a Direct Vent  
or a Non-Direct Vent gas central furnace.  
1 - Wire tie  
1 -Condensate trap  
The furnace is equipped for installation in natural gas ap-  
plications. A conversion kit (ordered separately) is required  
for use in propane/LP gas applications.  
1 -Condensate trap cap  
1 -Condensate trap clamp  
1 -2” diameter debris screen  
1 -3/4” Threaded street elbow  
Check equipment for shipping damage. If you find any  
damage, immediately contact the last carrier.  
NOTE - In Direct Vent installations, combustion air is taken  
from outdoors and flue gases are discharged outdoors. In  
Non-Direct Vent installations, combustion air is taken from  
indoors or ventilated attic or crawlspace and flue gases are  
involving roof termination.  
The following items may also be ordered separately:  
1 - Thermostat  
1 - Propane/LP changeover kit  
1 - Return air base kit  
DIRECT VENT INSTALLATION  
EXHAUST OUTLET  
COMBUSTION  
NON-DIRECT VENT  
INSTALLATION  
EXHAUST  
OUTLET  
1 - Horizontal suspension kit  
AIR INTAKE OUTSIDE  
OF HOUSE  
Safety Information  
WARNING  
Improper installation, adjustment, alteration, service  
or maintenance can cause property damage,  
personal injury or loss of life. Installation and service  
must be performed by a licensed professional in-  
staller (or equivalent), service agency or the gas sup-  
plier.  
COMBUSTION  
AIR INTAKE  
INSIDE  
OF HOUSE  
CAUTION  
As with any mechanical equipment, personal injury  
can result from contact with sharp sheet metal  
edges. Be careful when you handle this equipment.  
FIGURE 1  
NON-DIRECT VENT  
INSTALLATION  
NON-DIRECT VENT  
INSTALLATION  
EXHAUST  
OUTLET  
EXHAUST  
OUTLET  
DANGER  
Danger of explosion.  
There are circumstances in which odorant used with  
LP/propane gas can lose its scent. In case of a leak,  
LP/propane gas will settle close to the floor and may  
be difficult to smell. An LP/propane leak detector  
should be installed in all LP applications.  
COMBUSTION  
AIR INTAKE INSIDE  
VENTILATED  
COMBUSTION  
AIR INTAKE INSIDE  
VENTILATED  
CRAWL SPACE  
Use only the type of gas approved for use with this furnace.  
Refer to unit nameplate.  
ATTIC SPACE  
ML193UH units are CSA International certified to ANSI  
Z21.47 and CSA 2.3 standards.  
Building Codes  
In the USA, installation of gas furnaces must conform with  
local building codes. In the absence of local codes, units  
must be installed according to the current National Fuel  
Gas Code (ANSI‐Z223.1/NFPA 54). The National Fuel  
FIGURE 2  
Page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Gas Code is available from the following address:  
American National Standards Institute, Inc.  
11 West 42nd Street  
In Canada, all electrical wiring and grounding for the unit  
must be installed according to the current regulations of the  
Canadian Electrical Code Part I (CSA Standard C22.1)  
and/or local codes.  
New York, NY 10036  
In Canada, installation must conform with current National  
Standard of Canada CSA‐B149 Natural Gas and Propane  
Installation Codes, local plumbing or waste water codes  
and other applicable local codes.  
Heating Unit Installed Parallell to Air Handler Unit  
Dampers  
(open during heating operation only)  
In order to ensure proper unit operation in non-direct vent  
applications, combustion and ventilation air supply must be  
provided according to the current National Fuel Gas Code  
or CSA‐B149 standard.  
Gas Unit  
AIR FLOW  
AIR FLOW  
Installation Locations  
Air Handler Unit  
This furnace is CSA International certified for installation  
clearances to combustible material as listed on the unit  
service clearances must take precedence over fire protec-  
tion clearances.  
Dampers  
(open during cooling operation only)  
Heating Unit Installed Upstream of Cooling Coil  
NOTE - For installation on combustible floors, the furnace  
shall not be installed directly on carpeting, tile, or other  
combustible material other than wood flooring.  
AIR FLOW  
AIR FLOW  
Gas Unit  
Cooling Coil  
For installation in a residential garage, the furnace must be  
installed so that the burner(s) and the ignition source are  
located no less than 18 inches (457 mm) above the floor.  
The furnace must be located or protected to avoid physical  
damage by vehicles. When a furnace is installed in a public  
garage, hangar, or other building that has a hazardous at-  
mosphere, the furnace must be installed according to rec-  
ommended good practice requirements and current Na-  
tional Fuel Gas Code or CSA B149 standards.  
FIGURE 3  
NOTE - This furnace is designed for a minimum continuous  
return air temperature of 60°F (16°C) or an intermittent op-  
eration down to 55°F (13°C) dry bulb for cases where a  
night setback thermostat is used. Return air temperature  
must not exceed 85°F (29°C) dry bulb.  
The ML193UH furnace may be installed in alcoves, clos-  
ets, attics, basements, garages, crawl spaces and utility  
rooms in the upflow or horizontal position.  
NOTE - Furnace must be adjusted to obtain a temperature  
rise within the range specified on the unit nameplate. Fail-  
ure to do so may cause erratic limit operation and prema-  
ture heat exchanger failure.  
This furnace design has not been CSA certified for installa-  
tion in mobile homes, recreational vehicles, or outdoors.  
This ML193UH furnace must be installed so that its electri-  
cal components are protected from water.  
Use of Furnace as Construction Heater  
Lennox does not recommend the use of ML193UH units as  
a construction heater during any phase of construction.  
Very low return air temperatures, harmful vapors and op-  
eration of the unit with clogged or misplaced filters will dam-  
age the unit.  
Installed in Combination with a Cooling Coil  
shall be installed in parallel with, or on the upstream side of,  
cooling coils to avoid condensation in the heating compart-  
ment. With a parallel flow arrangement, a damper (or other  
means to control the flow of air) must adequately prevent  
chilled air from entering the furnace. If the damper is manu-  
ally operated, it must be equipped to prevent operation of  
either the heating or the cooling unit, unless it is in the full  
HEAT or COOL setting.  
ML193UH units may be used for heating of buildings or  
structures under construction, if the following conditions  
are met:  
D The vent system must be permanently installed per  
these installation instructions.  
D A room thermostat must control the furnace. The use of  
fixed jumpers that will provide continuous heating is not  
allowed.  
When installed, this furnace must be electrically grounded  
according to local codes. In addition, in the United States,  
installation must conform with the current National Electric  
Code, ANSI/NFPA No. 70. The National Electric Code  
(ANSI/NFPA No. 70) is available from the following ad-  
dress:  
D The return air duct must be provided and sealed to the  
furnace.  
D Return air temperature range between 60°F (16°C) and  
80°F (27°C) must be maintained.  
National Fire Protection Association  
1 Battery March Park  
Quincy, MA 02269  
D Air filters must be installed in the system and must be  
maintained during construction.  
Page 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
D Air filters must be replaced upon construction comple-  
tion.  
WARNING  
Product contains fiberglass wool.  
D The input rate and temperature rise must be set per the  
furnace rating plate.  
Disturbing the insulation in this product during  
installation, maintenance, or repair will expose you  
to fiberglass wool. Breathing this may cause lung  
cancer. (Fiberglass wool is known to the State of Cal-  
ifornia to cause cancer.)  
D One hundred percent (100%) outdoor air must be pro-  
vided for combustion air requirements during construc-  
tion. Temporary ducting may supply outdoor air to the  
furnace. Do not connect duct directly to the furnace.  
Size the temporary duct following these instructions in  
section for Combustion, Dilution and Ventilation Air in a  
confined space with air from outside.  
Fiberglass wool may also cause respiratory, skin,  
and eye irritation.  
To reduce exposure to this substance or for further  
information, consult material safety data sheets  
available from address shown below, or contact your  
supervisor.  
D The furnace heat exchanger, components, duct sys-  
tem, air filters and evaporator coils must be thoroughly  
cleaned following final construction clean-up.  
D All furnace operating conditions (including ignition, in-  
put rate, temperature rise and venting) must be verified  
according to these installation instructions.  
Lennox Industries Inc.  
P.O. Box 799900  
Dallas, TX 75379-9900  
The “A” coil drain pan is high quality engineering poly-  
mer with a maximum service temperature of 500° F.  
However, adequate space must be provided between  
the drain pan and the furnace heat exchanger. At least  
2” space is required for sectionalized heat exchanger  
and and 4” for drum-type or oil-fired furnace exchanger.  
Closer spacing may damage the drain pan and cause  
leaking.  
WARNING  
Insufficient combustion air can cause headaches,  
nausea, dizziness or asphyxiation. It will also cause  
excess water in the heat exchanger resulting in rust-  
ing and premature heat exchanger failure. Excessive  
exposure to contaminated combustion air will result  
in safety and performance related problems. Avoid  
exposure to the following substances in the com-  
bustion air supply:  
General  
Permanent wave solutions  
Chlorinated waxes and cleaners  
Chlorine base swimming pool chemicals  
Water softening chemicals  
De-icing salts or chemicals  
Carbon tetrachloride  
Halogen type refrigerants  
Cleaning solvents (such as perchloroethylene)  
Printing inks, paint removers, varnishes, etc.  
Hydrochloric acid  
These instructions are intended as a general guide and do  
not supersede local codes in any way. Consult authorities  
having jurisdiction before installation.  
In addition to the requirements outlined previously, the fol-  
lowing general recommendations must be considered  
when installing a ML193UH furnace:  
Place the furnace as close to the center of the air dis-  
tribution system as possible. The furnace should also be  
located close to the vent termination point.  
Cements and glues  
Antistatic fabric softeners for clothes dryers  
Masonry acid washing materials  
When the furnace is installed in non-direct vent applica-  
tions, do not install the furnace where drafts might blow  
directly into it. This could cause improper combustion  
and unsafe operation.  
Combustion, Dilution & Ventilation Air  
If the ML193UH is installed as a Non-Direct Vent Fur-  
When the furnace is installed in non-direct vent applica-  
tions, do not block the furnace combustion air opening  
with clothing, boxes, doors, etc. Air is needed for proper  
combustion and safe unit operation.  
nace, follow the guidelines in this section.  
NOTE - In Non-Direct Vent installations, combustion air is  
taken from indoors or ventilated attic or crawlspace and  
flue gases are discharged out-doors.  
When the furnace is installed in an attic or other insu-  
lated space, keep insulation away from the furnace.  
In the past, there was no problem in bringing in sufficient  
outdoor air for combustion. Infiltration provided all the air  
that was needed. In today's homes, tight construction prac-  
tices make it necessary to bring in air from outside for com-  
bustion. Take into account that exhaust fans, appliance  
vents, chimneys, and fireplaces force additional air that  
could be used for combustion out of the house. Unless out-  
side air is brought into the house for combustion, negative  
pressure (outside pressure is greater than inside pressure)  
When the furnace is installed in an unconditioned  
space, consider provisions required to prevent freezing  
of condensate drain system.  
CAUTION  
ML193UH unit should not be installed in areas nor-  
mally subject to freezing temperatures.  
Page 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
will build to the point that a downdraft can occur in the fur-  
nace vent pipe or chimney. As a result, combustion gases  
enter the living space creating a potentially dangerous situ-  
ation.  
infiltration. If the furnace is located in a building of tight  
construction with weather stripping and caulking around  
the windows and doors, follow the procedures in the Air  
from Outside section.  
In the absence of local codes concerning air for combus-  
tion and ventilation, use the guidelines and procedures in  
this section to install ML193UH furnaces to ensure efficient  
and safe operation. You must consider combustion air  
needs and requirements for exhaust vents and gas piping.  
A portion of this information has been reprinted with per-  
mission from the National Fuel Gas Code (ANSI-  
Z223.1/NFPA 54). This reprinted material is not the com-  
plete and official position of the ANSI on the referenced  
subject, which is represented only by the standard in its en-  
tirety.  
Confined Space  
A confined space is an area with a volume less than 50 cu-  
3
bic feet (1.42 m ) per 1,000 Btu (.29 kW) per hour of the  
com-bined input rating of all appliances installed in that  
space. This definition includes furnace closets or small  
equipment rooms.  
When the furnace is installed so that supply ducts carry air  
circulated by the furnace to areas outside the space con-  
taining the furnace, the return airmust be handled by ducts  
which are sealed to the furnace casing and which terminate  
outside the space containing the furnace. This is especially  
important when the furnace is mounted on a platform in a  
confined space such as a closet or small equipment room.  
Even a small leak around the base of the unit at the platform  
or at the return air duct connection can cause a potentially  
dangerous negative pressure condition. Air for combustion  
and ventilation can be brought into the confined space ei-  
ther from inside the building or from outside.  
In Canada, refer to the CSA B149 installation codes.  
CAUTION  
Do not install the furnace in a corrosive or contami-  
nated atmosphere. Meet all combustion and ventila-  
tion air requirements, as well as all local codes.  
All gas‐fired appliances require air for the combustion pro-  
cess. If sufficient combustion air is not available, the fur-  
nace or other appliance will operate inefficiently and un-  
safely. Enough air must be provided to meet the needs of  
all fuel-burning appliances and appliances such as ex-  
haust fans which force air out of the house. When fire-  
places, exhaust fans, or clothes dryers are used at the  
same time as the furnace, much more air is required to en-  
sure proper combustion and to prevent a downdraft. Insuf-  
ficient air causes incomplete combustion which can result  
in carbon monoxide.  
Air from Inside  
If the confined space that houses the furnace adjoins a  
space categorized as unconfined, air can be brought in by  
providing two permanent openings between the two  
spaces. Each opening must have a minimum free area of 1  
2
square inch (645 mm ) per 1,000 Btu (.29 kW) per hour of  
total input rating of all gas-fired equipment in the confined  
space. Each opening must be at least 100 square inches  
2
(64516 mm ). One opening shall be within 12 inches (305  
mm) of the top of the enclosure and one opening within 12  
In addition to providing combustion air, fresh outdoor air di-  
lutes contaminants in the indoor air. These contaminants  
may include bleaches, adhesives, detergents, solvents  
and other contaminants which can corrode furnace compo-  
nents.  
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM INSIDE  
ROOF TERMINATED  
EXHAUST PIPE  
The requirements for providing air for combustion and ven-  
tilation depend largely on whether the furnace is installed in  
an unconfined or a confined space.  
OPENINGS  
(To Adjacent  
Unconfined  
Space)  
Unconfined Space  
SIDE WALL  
TERMINATED  
EXHAUST PIPE  
(ALTERNATE  
LOCATION)  
ML193UH  
An unconfined space is an area such as a basement or  
large equipment room with a volume greater than 50 cubic  
3
feet (1.42 m ) per 1,000 Btu (.29 kW) per hour of the com-  
bined input rating of all appliances installed in that space.  
This space also includes adjacent rooms which are not  
separated by a door. Though an area may appear to be un-  
confined, it might be necessary to bring in outdoor air for  
combustion if the structure does not provide enough air by  
NOTE - Each opening shall have a free area of at least one square inch  
2
per 1,000 Btu (645mm per .29kW) per hour of the total input rating of  
all equipment in the enclosure, but not less than 100 square inches  
2).  
(64516mm.  
FIGURE 4  
Page 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Air from Outside  
EQUIPMENT IN CONFINED SPACE  
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)  
If air from outside is brought in for combustion and ventila-  
tion, the confined space shall be provided with two perma-  
nent openings. One opening shall be within 12” (305mm) of  
the top of the enclosure and one within 12” (305mm) of the  
bottom. These openings must communicate directly or by  
ducts with the outdoors or spaces (crawl or attic) that freely  
communicate with the outdoors or indirectly through verti-  
cal ducts. Each opening shall have a minimum free area of  
Roof Terminated  
Exhaust Pipe  
2
1 square inch per 4,000 Btu (645mm per 1.17kW) per hour  
of total input rating of all equipment in the enclosure. When  
communicating with the outdoors through horizontal ducts,  
each opening shall have a minimum free area of 1 square  
Inlet Air  
(Minimum  
12 in.(305mm)  
Above crawl  
space floor)  
Ventilation  
Louvers  
(Crawl space)  
Furnace  
2
inch per 2,000 Btu (645mm per .59kW) per total input rat-  
ing of all equipment in the enclosure (See figure 5). It is also  
permissible to bring in air for combustion from a ventilated  
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE  
(Inlet Air from Crawl Space and Outlet Air to Ouside)  
Coupling or  
*Intake Debris Screen Provided)  
3 in. to 2 in.  
Transition  
VENTILATION LOUVERS  
(Each end of attic)  
(Field Provided)  
ROOF TERMINATED  
EXHAUST PIPE  
NOTE-The inlet and outlet air openings shall each have a free area  
2
of at least one square inch per 4,000 Btu (645mm per 1.17kW) per  
hour of the total input rating of all equipment in the enclosure.  
OUTLET  
AIR  
FIGURE 7  
SIDE WALL  
TERMINATED  
EXHAUST PIPE  
(ALTERNATE  
LOCATION)  
FURNACE  
VENTILATION  
LOUVERS  
INLET  
AIR  
(For unheated  
crawl space)  
If air from outside is brought in for combustion and ventila-  
tion, the confined space must have two permanent open-  
ings. One opening shall be within 12 inches (305 mm) of the  
top of the enclosure and one opening within 12 inches (305  
mm) of the bottom. These openings must communicate di-  
rectly or by ducts with the outdoors or spaces (crawl or at-  
tic) that freely communicate with the outdoors or indirectly  
through vertical ducts. Each opening shall have a minimum  
NOTE-The inlet and outlet air openings shall each have a free area  
2
of at least one square inch per 4,000 Btu (645mm per 1.17kW) per  
hour of the total input rating of all equipment in the enclosure.  
FIGURE 5  
2
free area of 1 square inch (645 mm ) per 4,000 Btu (1.17  
EQUIPMENT IN CONFINED SPACE  
(Inlet Air from Ventilated Attic and Outlet Air to Outside)  
kW) per hour of total input rating of all equipment in the en-  
the outdoors through horizontal ducts, each opening shall  
have a minimum free area of 1 square inch (645 mm ) per  
2,000 Btu (.56 kW) per total input rating of all equipment in  
the enclosure. See figure 9.  
Ventilation Louvers  
2
Inlet Air  
Roof Terminated  
Exhaust Pipe  
(Minimum  
12 in.(305mm) Above  
attic floor)  
When ducts are used, they shall be of the same cross-sec-  
tional area as the free area of the openings to which they  
connect. The minimum dimension of rectangular air ducts  
shall be no less than 3 inches (75 mm). In calculating free  
area, the blocking effect of louvers, grilles, or screens must  
be considered. If the design and free area of protective cov-  
ering is not known for calculating the size opening required,  
it may be assumed that wood louvers will have 20 to 25 per-  
cent free area and metal louvers and grilles will have 60 to  
75 percent free area. Louvers and grilles must be fixed in  
the open position or interlocked with the equipment so that  
they are opened automatically during equipment opera-  
tion.  
*Intake Debris  
Screen  
(Provided)  
Furnace  
NOTE-The inlet and outlet air openings shall each have a free area  
of at least one square inch per 4,000 Btu (645mm per 1.17kW) per  
hour of the total input rating of all equipment in the enclosure.  
2
FIGURE 6  
Page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
leg). See figure 10. The bolt and washer must be re-  
moved before the furnace is placed into operation. Af-  
ter the bolt and washer have been removed, the rigid leg  
will not touch the blower housing.  
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE  
(All Air Through Ventilated Attic)  
ROOF TERMINATED  
EXHAUST PIPE  
VENTILATION LOUVERS  
(Each end of attic)  
ML193UH090P48C  
and ML193UH110P48C  
with 1/2 HP Blower Motor  
OUTLET  
AIR  
RIGID LEG  
(Remove shipping bolt  
and washer)  
INLET AIR  
(Ends 12” above  
bottom)  
SIDE WALL  
TERMINATED  
EXHAUST PIPE  
(ALTERNATE  
LOCATION)  
FURNACE  
NOTE-The inlet and outlet air openings shall each have a free area of  
2
FIGURE 10  
at least one square inch per 4,000 Btu (645mm per 1.17kW) per hour  
of the total input rating of all equipment in the enclosure.  
Installation - Setting Equipment  
FIGURE 8  
EQUIPMENT IN CONFINED SPACE -  
ALL AIR FROM OUTSIDE  
WARNING  
Do not connect the return air duct to the back of the  
furnace. Doing so will adversely affect the operation  
of the safety control devices, which could result in  
personal injury or death.  
ROOF TERMINATED  
EXHAUST PIPE  
OUTLET AIR  
WARNING  
Blower access panel must be securely in place when  
blower and burners are operating. Gas fumes, which  
could contain carbon monoxide, can be drawn into  
living space resulting in personal injury or death.  
FURNACE  
SIDE WALL  
TERMINATED  
EXHAUST PIPE  
(ALTERNATE  
LOCATION)  
INLET AIR  
Upflow Applications  
NOTE-Each air duct opening shall have a free area of at least one  
2
The ML193UH gas furnace can be installed as shipped in  
lect a location that allows for the required clearances that  
are listed on the unit nameplate. Also consider gas supply  
connections, electrical supply, vent connection, conden-  
sate trap and drain connections, and installation and ser-  
vice clearances [24 inches (610 mm) at unit front]. The unit  
must be level from side to side. Unit may be positioned from  
level to 1/2” toward the front to aid in draining. See figure  
square inch per 2,000 Btu (645mm per .59kW) per hour of the total  
input rating of all equipment in the enclosure. If the equipment room  
is located against an outside wall and the air openings communi-  
cate directly with the outdoors, each opening shall have a free area  
of at least 1 square inch per 4,000 Btu (645mm per 1.17kW) per  
hour of the total input rating of all other equipment in the enclosure.  
2
FIGURE 9  
Shipping Bolt Removal  
Units with 1/2 hp blower motor are equipped with three flex-  
ible legs and one rigid leg. The rigid leg is equipped with a  
shipping bolt and a flat white plastic washer (rather than the  
rubber mounting grommet used with a flexible mounting  
Allow for clearances to combustible materials as indicated  
on the unit nameplate.  
Page 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SETTING EQUIPMENT  
UPFLOW APPLICA-  
TION  
UNIT  
FRONT  
UNIT  
FRONT  
AIR FLOW  
AIR FLOW  
1/2”  
max.  
FRONT VIEW  
SIDE VIEW  
SIDE VIEW  
HORIZONTAL APPLICATION  
UNIT  
FRONT  
AIR FLOW  
1/2”  
max.  
END VIEW  
FRONT VIEW  
Unit must be level side-to-side. Unit may be positioned from level to 1/2” toward the front to aid in draining.  
FIGURE 11  
Page 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Return Air Guidelines  
WARNING  
Return air can be brought in through the bottom or either  
side of the furnace installed in an upflow application. If the  
furnace is installed on a platform with bottom return, make  
an airtight seal between the bottom of the furnace and the  
platform to ensure that the furnace operates properly and  
safely. The furnace is equipped with a removable bottom  
panel to facilitate installation.  
Improper installation of the furnace can result in per-  
sonal injury or death. Combustion and flue products  
must never be allowed to enter the return air system  
or air in the living space. Use sheet metal screws and  
joint tape to seal return air system to furnace.  
In platform installations with furnace return, the fur-  
nace should be sealed airtight to the return air ple-  
num. A door must never be used as a portion of the  
return air duct system. The base must provide a  
stable support and an airtight seal to the furnace. Al-  
low absolutely no sagging, cracks, gaps, etc.  
Markings are provided on both sides of the furnace cabinet  
for installations that require side return air. Cut the furnace  
cabinet at the maximum dimensions shown on page 2.  
For no reason should return and supply air duct sys-  
tems ever be connected to or from other heating de-  
vices such as a fireplace or stove, etc. Fire, explo-  
sion, carbon monoxide poisoning, personal injury  
and/or property damage could result.  
Refer to Engineering Handbook for additional information.  
ML193UH applications which include side return air  
and a condensate trap installed on the same side of the  
cabinet (trap can be installed remotely within 5 ft.) re-  
quire either a return air base or field-fabricated transi-  
tion to accommodate an optional IAQ accessory taller  
Installation Clearances  
Top  
Side Return Air  
(with transition and filter)  
Left Side  
Right Side  
20” X 25” X 1”  
(508mmX635mmX25mm)  
Bottom (Floor)  
1−1/2”  
Air Filter  
Top/Plenum  
*Front  
Back  
1 in. (25 mm)  
0
0
Sides  
0†  
0
Return  
Air  
Vent  
Plenum  
Floor  
0‡  
*Front clearance in alcove installation must be 24 in. (610 mm).  
Maintain a minimum of 24 in. (610 mm) for front service access.  
Allow proper clearances to accommodate condensate trap.  
For installations on a combustible floor, do not install the fur-  
nace directly on carpeting, tile or other combustible materials oth-  
er than wood flooring.  
Transition  
FIGURE 13  
FIGURE 12  
Page 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Optional Return Air Base  
(Upflow Applications Only)  
CONDENSATE  
TRAP  
FURNACE  
FRONT  
1 23 (584)  
Overall  
IF BASE  
IS USED  
3−1/4  
(83)  
1 Minimum  
11 (279)  
Maximum  
WITHOUT  
IAQ CABINET,  
A SINGLE  
RETURN AIR  
PLENUM  
(Maximum)  
INDOOR AIR  
QUALITY  
CABINET  
(PCO, Filter  
Cabinet, etc.)  
2
1 22−7/16  
(570)  
Overall  
1 Unit side return air  
Opening  
14 (356)  
MUST  
AIR FLOW  
(Maximum)  
COVER BOTH  
UNIT AND  
RETURN  
AIR BASE  
OPENINGS  
SIDE RETURN  
AIR OPENINGS  
(Either Side)  
5−5/8  
(143)  
7−1/4  
(184)  
23  
(584)  
OPTIONAL  
RETURN  
AIR BASE  
3/4  
(19)  
17−1/2 (446) B Width (50W98)  
21 (533) C Width (50W99)  
26−7/8  
(683)  
24−1/2 (622) D Width (51W00)  
SIDE VIEW  
FRONT VIEW  
NOTE- Optional side return air filter kits are not for use with return air base.  
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.  
Minimum unit side return air opening dimensions for units requiring 1800 cfm of air and over (W x H): 23 x 11 in. (584 x 279 mm).  
The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.  
Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air  
opening. The size of the opening must not extend beyond the markings on the furnace cabinet.  
2
To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.  
FIGURE 14  
Removing the Bottom Panel  
Removing the Bottom Panel  
Remove the two screws that secure the bottom cap to the  
furnace. Pivot the bottom cap down to release the bottom  
panel. Once the bottom panel has been removed, reinstall  
Horizontal Applications  
WARNING  
Do not install the furnace on its front or back.  
Screw  
Bottom Cap  
Bottom Panel  
FIGURE 15  
FIGURE 16  
Page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
The ML193UH furnace can be installed in horizontal ap-  
HORIZONTAL SUSPENSION KIT  
plications with either right- or left-hand air discharge.  
Refer to figure 17 for clearances in horizontal applications.  
Internal Brace  
(provided with kit)  
Metal Strap  
(typical)  
Horizontal Application  
Installation Clearances  
Bracket  
(typical)  
Right-Hand Discharge  
Left End  
Right End  
Air  
Flow  
Air  
Flow  
Air  
Flow  
Bottom (Floor)**  
Left-Hand Discharge  
Top  
FIGURE 18  
Left End  
Right End  
Air  
Flow  
Air  
Flow  
Bottom (Floor)**  
NOTE - When the furnace is installed on a platform or with  
the horizontal suspension kit in a crawlspace, it must be  
elevated enough to avoid water damage, accommodate  
drain trap and to allow the evaporator coil to drain.  
Top  
0
0
0
0
0
Front*  
Back  
Ends  
Vent  
Platform Installation of Horizontal Unit  
1 - Select location for unit keeping in mind service and  
Floor  
0‡  
2 - Construct a raised wooden frame and cover frame  
with a plywood sheet. If unit is installed above finished  
space, fabricate an auxiliary drain pan to be installed  
Leave 8 inches for service clearance below unit for  
condensate trap.  
*Front clearance in alcove installation must be 24 in. (610 mm).  
Maintain a minimum of 24 in. (610 mm) for front service access.  
**An 8” service clearance must be maintained below the unit to  
provide for servicing of the condensate trap.  
For installations on a combustible floor, do not install the fur-  
nace directly on carpeting, tile or other combustible materials oth-  
er than wood flooring.  
FIGURE 17  
3 - Provide a service platform in front of unit. When instal-  
ling the unit in a crawl space, a proper support platform  
may be created using cement blocks.  
Suspended Installation of Horizontal Unit  
This furnace may be installed in either an attic or a crawl-  
space. Either suspend the furnace from roof rafters or floor  
joists, as shown in figure 18, or install the furnace on a plat-  
form, as shown in figure 19. A horizontal suspension kit  
(51W10) may be ordered from Lennox or use equivalent.  
4 - Route auxiliary drain line so that water draining from  
this outlet will be easily noticed by the homeowner.  
5 - If necessary, run the condensate line into a conden-  
sate pump to meet drain line slope requirements. The  
pump must be rated for use with condensing furnaces.  
Protect the condensate discharge line from the pump  
to the outside to avoid freezing.  
NOTE - Heavy-gauge sheet metal straps may be used to  
suspend the unit from roof rafters or ceiling joists. When  
straps are used to suspend the unit in this way, support  
must be provided for both the ends. The straps must not in-  
terfere with the plenum or exhaust piping installation. Cool-  
ing coils and supply and return air plenums must be  
supported separately.  
6 - Continue with exhaust, condensate and intake piping  
installation according to instructions.  
Page 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Duct System  
*GAS CONNECTION  
INTAKE PIPE  
Use industry‐approved standards to size and install the  
supply and return air duct system. Refer to ACCA Manual  
D. This will result in a quiet and low‐static system that has  
uniform air distribution.  
EXHAUST PIPE  
NOTE - This furnace is not certified for operation in heating  
mode (indoor blower operating at selected heating speed)  
with an external static pressure which exceeds 0.5 inches  
w.c. Operation at these conditions may result in improper  
limit operation.  
Supply Air Plenum  
If the furnace is installed without a cooling coil, a removable  
access panel should be installed in the supply air duct. The  
access panel should be large enough to permit inspection  
of the heat exchanger. The furnace access panel must al-  
ways be in place when the furnace is operating and it must  
not allow leaks.  
RAISED  
PLATFORM  
SERVICE PLATFORM  
FIGURE 19  
Return Air -- Horizontal Applications  
Return air may be brought in only through the end of a fur-  
nace installed in the horizontal position. The furnace is  
equipped with a removable bottom panel to facilitate instal-  
Return Air Plenum  
NOTE - Return air must not be drawn from a room  
where this furnace, or any other gas-fueled appliance  
(i.e., water heater), or carbon monoxide-producing de-  
vice (i.e., wood fireplace) is installed.  
Filters  
When return air is drawn from a room, a negative pressure  
is created in the room. If a gas appliance is operating in a  
room with negative pressure, the flue products can be  
pulled back down the vent pipe and into the room. This re-  
verse flow of the flue gas may result in incomplete com-  
bustion and the formation of carbon monoxide gas. This  
raw gas or toxic fumes might then be distributed throughout  
the house by the furnace duct system.  
This unit is not equipped with a filter or rack. A field-pro-  
vided high velocity rated filter is required for the unit to oper-  
A filter must be in place whenever the unit is operating.  
IMPORTANT  
If a high-efficiency filter is being installed as part of  
this system to ensure better indoor air quality, the fil-  
ter must be properly sized. High-efficiency filters  
have a higher static pressure drop than standard-ef-  
ficiency glass/foam filters. If the pressure drop is too  
great, system capacity and performance may be re-  
duced. The pressure drop may also cause the limit to  
trip more frequently during the winter and the indoor  
coil to freeze in the summer, resulting in an increase  
in the number of service calls.  
Return air can be brought in through the bottom or either  
side of the furnace (return air brought into either side fur-  
nace allowed in upflow applications only). If a furnace with  
bottom return air is installed on a platform, make an airtight  
seal between the bottom of the furnace and the platform to  
ensure that the unit operates properly and safely. Use fi-  
berglass sealing strips, caulking, or equivalent sealing  
method between the plenum and the furnace cabinet to en-  
sure a tight seal. If a filter is installed, size the return air duct  
to fit the filter frame.  
Before using any filter with this system, check the  
specifications provided by the filter manufacturer  
against the data given in the appropriate Lennox  
Product Specifications bulletin. Additional informa-  
tion is provided in Service and Application Note  
ACC-00-2 (August 2000).  
Pipe & Fittings Specifications  
All pipe, fittings, primer and solvent cement must conform  
with American National Standard Institute and the Ameri-  
can Society for Testing and Materials (ANSI/ASTM) stan-  
dards. The solvent shall be free flowing and contain no  
lumps, undissolved particles or any foreign matter that ad-  
versely affects the joint strength or chemical resistance of  
the cement. The cement shall show no gelation, stratifica-  
tion, or separation that cannot be removed by stirring. Re-  
fer to the table 2 below for approved piping and fitting ma-  
terials.  
TABLE 1  
Filter Size  
Furnace  
Cabinet Width  
Side Return  
Bottom Return  
16 X 25 X 1 (1)  
20 X 25 X 1 (1)  
24 X 25 X 1 (1)  
17-1/2”  
21”  
16 X 25 X 1 (1)  
16 X 25 X 1 (1)  
16 X 25 X 1 (2)  
24-1/2”  
Page 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
CAUTION  
IMPORTANT  
Solvent cements for plastic pipe are flammable liq-  
uids and should be kept away from all sources of  
ignition. Do not use excessive amounts of solvent  
cement when making joints. Good ventilation should  
be maintained to reduce fire hazard and to minimize  
breathing of solvent vapors. Avoid contact of ce-  
ment with skin and eyes.  
ML193UH exhaust and intake connections are made  
of PVC. Use PVC primer and solvent cement when  
using PVC vent pipe. When using ABS vent pipe, use  
transitional solvent cement to make connections to  
the PVC fittings in the unit.  
Use PVC primer and solvent cement or ABS solvent ce-  
alternate, use all purpose cement, to bond ABS, PVC, or  
CPVC pipe when using fittings and pipe made of the same  
materials. Use transition solvent cement when bonding  
ABS to either PVC or CPVC.  
TABLE 2  
PIPING AND FITTINGS SPECIFICATIONS  
Schedule 40 PVC (Pipe)  
D1785  
F891  
Schedule 40 PVC (Cellular Core Pipe)  
Schedule 40 PVC (Fittings)  
D2466  
F441  
Low temperature solvent cement is recommended during  
cooler weather. Metal or plastic strapping may be used for  
vent pipe hangers. Uniformly apply a liberal coat of PVC  
primer for PVC or use a clean dry cloth for ABS to clean in-  
side socket surface of fitting and male end of pipe to depth  
of fitting socket.  
Schedule 40 CPVC (Pipe)  
Schedule 40 CPVC (Fittings)  
SDR-21 PVC or SDR-26 PVC (Pipe)  
SDR-21 CPVC or SDR-26 CPVC (Pipe)  
Schedule 40 ABS Cellular Core DWV (Pipe)  
Schedule 40 ABS (Pipe)  
F438  
D2241  
F442  
F628  
D1527  
D2468  
Canadian Applications Only - Pipe, fittings, primer and  
solvent cement used to vent (exhaust) this appliance must  
be certified to ULC S636 and supplied by a single  
manufacturer as part of an approved vent (exhaust) sys-  
tem. In addition, the first three feet of vent pipe from the fur-  
nace flue collar must be accessible for inspection.  
Schedule 40 ABS (Fittings)  
ABS-DWV (Drain Waste & Vent)  
(Pipe & Fittings)  
D2661  
D2665  
PVC-DWV (Drain Waste & Vent)  
Pipe & Fittings)  
ASTM  
SPECIFICATION  
PRIMER & SOLVENT CEMENT  
PVC & CPVC Primer  
PVC Solvent Cement  
CPVC Solvent Cement  
ABS Solvent Cement  
F656  
D2564  
F493  
D2235  
PVC/CPVC/ABS All Purpose Cement For  
Fittings & Pipe of the same material  
D2564, D2235, F493  
D3138  
ABS to PVC or CPVC Transition Solvent  
Cement  
CANADA PIPE & FITTING & SOLVENT  
CEMENT  
MARKING  
PVC & CPVC Pipe and Fittings  
PVC & CPVC Solvent Cement  
ULCS636  
ABS to PVC or CPVC Transition Cement  
Page 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TABLE 3  
OUTDOOR TERMINATION USAGE*  
STANDARD  
CONCENTRIC  
Flush-  
Mount  
Kit  
Wall Kit  
Wall Ring Kit  
2 inch  
1-1/2 inch  
2 inch  
3 inch  
Vent  
Pipe  
Dia. in.  
2 inch  
3 inch  
Input Size  
Field  
Fabricated  
51W11  
(US)  
51W12  
(CA)  
71M80  
(US)  
69M29  
(US)  
44W92  
(CA)  
44J40  
(US)  
81J20 (CA)  
22G44 (US)  
30G28 (CA)  
60L46 (US)  
44W93 (CA)  
15F74  
4
4
4
4
44W92  
(CA)  
4
3
1
1
5
2
2
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
3
1
1
5
2
2-1/2  
YES  
YES  
YES  
YES  
YES  
045  
070  
090  
3
1
1
5
2
3
YES  
YES  
YES  
YES  
YES  
3
1
1
5
2
2
YES  
YES  
YES  
YES  
YES  
3
1
1
5
2
2-1/2  
YES  
YES  
YES  
YES  
YES  
3
1
1
5
2
3
YES  
YES  
YES  
YES  
YES  
3
5
2
2-1/2  
3
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
3
5
YES  
YES  
3
5
YES  
YES  
5
2
YES  
YES  
YES  
YES  
YES  
5
2-1/2  
3
YES  
110  
135  
5
YES  
YES  
YES  
5
3
YES  
NOTE - Standard Terminations do not include any vent pipe or elbows external to the structure. Any vent pipe or elbows external to the structure must be included in total vent length  
calculations. See vent length tables.  
* Kits must be properly installed according to kit instructions.  
1
Requires field-provided outdoor 1-1/2” exhaust accelerator.  
Concentric kits 71M80 and 44W92 include 1-1/2” outdoor accelerator, when uses with 045 and 070 input models.  
2
3
Flush mount kits 51W11 and 51W12 includes 1-1/2 in. outdoor exhaust accelerator, required when used with 045, 070 and 090 input models.  
Termination kits 30G28, 44W92, 4493 and 81J20 are certified to ULC S636 for use in Canada only.  
4
5
4 - Test fit joint and mark depth of fitting on outside of  
pipe.  
Joint Cementing Procedure  
All cementing of joints should be done according to the  
5 - Uniformly apply a liberal coat of PVC primer for PVC or  
use a clean dry cloth for ABS to clean inside socket  
specifications outlined in ASTM D 2855.  
surface of fitting and male end of pipe to depth of fitting  
socket.  
NOTE - A sheet metal screw may be used to secure the in-  
take pipe to the connector, if desired. Use a drill or self tap-  
ping screw to make a pilot hole.  
NOTE - Time is critical at this stage. Do not allow prim-  
er to dry before applying cement.  
6 - Promptly apply solvent cement to end of pipe and in-  
side socket surface of fitting. Cement should be ap-  
plied lightly but uniformly to inside of socket. Take care  
to keep excess cement out of socket. Apply second  
coat to end of pipe.  
DANGER  
DANGER OF EXPLOSION!  
Fumes from PVC glue may ignite during system  
check. Allow fumes to dissipate for at least 5 minutes  
before placing unit into operation.  
7 - Immediately after applying last coat of cement to pipe,  
and while both inside socket surface and end of pipe  
are wet with cement, forcefully insert end of pipe into  
socket until it bottoms out. Turn PVC pipe 1/4 turn dur-  
ing assembly (but not after pipe is fully inserted) to dis-  
tribute cement evenly. DO NOT turn ABS or cellular  
core pipe.  
1 - Measure and cut vent pipe to desired length.  
2 - Debur and chamfer end of pipe, removing any ridges  
or rough edges. If end is not chamfered, edge of pipe  
may remove cement from fitting socket and result in a  
leaking joint.  
3 - Clean and dry surfaces to be joined.  
Page 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
NOTE - Assembly should be completed within 20 sec-  
onds after last application of cement. Hammer blows  
should not be used when inserting pipe.  
REPLACING FURNACE THAT  
WAS PART OF A COMMON  
VENT SYSTEM  
CHIMNEY  
OR GAS  
VENT  
(Check sizing  
for water  
heater only)  
8 - After assembly, wipe excess cement from pipe at end  
of fitting socket. A properly made joint will show a bead  
around its entire perimeter. Any gaps may indicate an  
improper assembly due to insufficient solvent.  
FURNACE  
(Replaced  
by ML193)  
WATER  
HEATER  
9 - Handle joints carefully until completely set.  
Venting Practices  
OPENINGS  
(To Adjacent  
Room)  
Piping Suspension Guidelines  
SCHEDULE 40  
PVC - 5'  
all other pipe* - 3'  
If an ML193UH furnace replaces a furnace which  
was commonly vented with another gas appliance,  
the size of the existing vent pipe for that gas ap-  
pliance must be checked. Without the heat of the  
original furnace flue products, the existing vent pipe  
is probably oversized for the single water heater or  
other appliance. The vent should be checked for  
proper draw with the remaining appliance.  
NOTE - Isolate piping at the point where it exits the outside wall or  
roof in order to prevent transmission of vibration to the structure.  
FIGURE 21  
Wall Thickness Guidelines  
24” maximum  
3/4” minimum  
Route piping to outside of structure. Continue with installa-  
tion following instructions given in piping termination sec-  
tion.  
Wall  
inside  
outside  
CAUTION  
Do not discharge exhaust into an existing stack or  
stack that also serves another gas appliance. If verti-  
cal discharge through an existing unused stack is re-  
quired, insert PVC pipe inside the stack until the end  
is even with the top or outlet end of the metal stack.  
FIGURE 20  
1 - In areas where piping penetrates joists or interior  
walls, hole must be large enough to allow clearance on  
all sides of pipe through center of hole using a hanger.  
CAUTION  
The exhaust vent pipe operates under positive pres-  
sure and must be completely sealed to prevent leak-  
age of combustion products into the living space.  
2 - When furnace is installed in a residence where unit is  
shut down for an extended period of time, such as a  
vacation home, make provisions for draining conden-  
sate collection trap and lines.  
Page 16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Use the following steps to correctly size vent pipe diameter.  
Vent Piping Guidelines  
The ML193UH can be installed as either a Non-Direct  
Vent or a Direct Vent gas central furnace.  
Piping Size Process  
NOTE - In Non‐Direct Vent installations, combustion air is  
taken from indoors and flue gases are discharged out-  
doors. In Direct Vent installations, combustion air is taken  
from outdoors and flue gases are discharged outdoors.  
What is the  
furnace capacity?  
045, 070, 090,  
110 or 135?  
Intake and exhaust pipe sizing -- Size pipe according to  
tables 4 and 5. Count all elbows inside and outside the  
home. Table 4 lists the minimum vent pipe lengths per-  
mitted. Table 5 lists the maximum pipe lengths permitted.  
1
2
Regardless of the diameter of pipe used, the standard roof  
and wall terminations described in section Exhaust Piping  
Terminations should be used. Exhaust vent termination  
pipe is sized to optimize the velocity of the exhaust gas as it  
Which style termination  
being used?  
Standard or concentric?  
In some applications which permit the use of several differ-  
ent sizes of vent pipe, a combination vent pipe may be  
used. Contact Lennox' Application Department for assis-  
tance in sizing vent pipe in these applications.  
Which needs  
most elbows?  
Intake or  
3
exhaust?  
NOTE - The exhaust collar on all models is sized to accom-  
modate 2” Schedule 40 vent pipe. In horizontal applica-  
tions, any transition to exhaust pipe larger than 2” must be  
made in vertical runs of the pipe. Therefore a 2” elbow must  
be added before the pipe is transitioned to any size larger  
than 2”. This elbow must be added to the elbow count used  
to determine acceptable vent lengths. Contact the Applica-  
tion Department for more information concerning sizing of  
vent systems which include multiple pipe sizes.  
How many elbows?  
Count all elbows inside  
and outside house.  
4
5
Desired pipe size?  
2”, 2-1/2”, 3”  
Exhaust Pipe  
Exhaust Pipe  
What is the altitude of  
the furnace installation?  
6
12” Min.  
Horizontal  
Gas Furnace  
12” max  
max intake or exhaust pipe  
length. Includes all vent  
pipe and elbows inside  
and outside the house.  
Of straight pipe  
7
NOTE - All horizontal runs of exhaust pipe must slope back to-  
ward unit. A minimum of 1/4” (6mm) drop for each 12” (305mm)  
of horizontal run is mandatory for drainage.  
NOTE - Exhaust pipe MUST be glued to furnace exhaust fittings.  
NOTE - Exhaust piping should be checked carefully to make  
sure there are no sags or low spots.  
FIGURE 23  
FIGURE 22  
TABLE 4  
MINIMUM VENT PIPE LENGTHS  
ML193UH  
MODEL  
MIN. VENT LENGTH*  
IMPORTANT  
Do not use screens or perforated metal in exhaust or  
intake terminations. Doing so will cause freeze-ups  
and may block the terminations.  
15 ft. or  
5 ft plus 2 elbows or  
10 ft plus 1 elbow  
045, 070, 090, 110  
135  
*Any approved termination may be added to the minimum length listed.  
Page 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TABLE 5  
Maximum Allowable Intake or Exhaust Vent Length in Feet  
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be  
same pipe size.  
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.  
Standard Termination at Elevation 0 - 10,000  
2” Pipe  
Model  
090  
44  
2-1/2” Pipe  
3” Pipe  
Model  
090  
118  
113  
108  
103  
98  
Number Of  
90° Elbows  
Used  
Model  
090  
68  
045  
81  
76  
71  
66  
61  
56  
51  
46  
41  
36  
070  
66  
61  
56  
51  
46  
41  
36  
31  
26  
21  
110  
24  
135  
045  
115  
110  
105  
100  
95  
070  
100  
95  
90  
85  
80  
75  
70  
65  
60  
55  
110  
43  
38  
33  
28  
23  
18  
13  
135  
045  
137  
132  
127  
122  
117  
112  
107  
102  
97  
070  
137  
132  
127  
122  
117  
112  
107  
102  
97  
110  
118  
113  
108  
103  
98  
135  
114  
109  
104  
99  
1
2
39  
19  
63  
3
34  
14  
58  
4
29  
53  
5
24  
48  
94  
n/a  
n/a  
6
19  
90  
43  
93  
93  
89  
7
14  
85  
38  
88  
88  
84  
n/a  
8
80  
33  
83  
83  
79  
9
75  
28  
78  
78  
74  
n/a  
n/a  
10  
70  
23  
92  
92  
73  
73  
69  
Concentric Termination Elevation 0 - 10,000  
2” Pipe  
Model  
090  
42  
2-1/2” Pipe  
3” Pipe  
Model  
090  
114  
109  
104  
99  
Number Of  
90° Elbows  
Usedl  
Model  
045  
73  
68  
63  
58  
53  
48  
43  
38  
33  
28  
070  
58  
53  
48  
43  
38  
33  
28  
23  
18  
13  
110  
22  
135  
045  
105  
100  
95  
070  
90  
85  
80  
75  
70  
65  
60  
55  
50  
45  
090  
64  
59  
54  
49  
44  
39  
34  
29  
24  
19  
110  
39  
34  
29  
24  
19  
14  
135  
045  
121  
116  
111  
106  
101  
96  
070  
121  
116  
111  
106  
101  
96  
110  
114  
109  
104  
99  
135  
105  
100  
95  
1
2
37  
17  
3
32  
12  
4
27  
90  
90  
5
22  
85  
94  
94  
85  
n/a  
n/a  
6
17  
80  
89  
89  
80  
7
12  
75  
91  
91  
84  
84  
75  
n/a  
8
70  
86  
86  
79  
79  
70  
n/a  
9
65  
81  
81  
74  
74  
65  
n/a  
10  
60  
76  
76  
69  
69  
60  
TABLE 6  
Maximum Allowable Exhaust Vent Lengths With Furnace Installed in a Closet or Basement Using Ventilated  
Attic or Crawl Space For Intake Air in Feet  
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.  
Standard Termination at Elevation 0 - 10,000  
2” Pipe  
Model  
090  
34  
2-1/2” Pipe  
3” Pipe  
Model  
090  
98  
Number Of  
90° Elbows  
Used  
Model  
090  
53  
045  
71  
66  
61  
56  
51  
46  
41  
36  
31  
070  
56  
51  
46  
41  
36  
31  
26  
21  
16  
110  
14  
9
135  
045  
100  
95  
90  
85  
80  
75  
70  
65  
60  
070  
95  
80  
75  
70  
65  
60  
55  
60  
45  
110  
28  
23  
18  
13  
8
135  
045  
117  
112  
107  
102  
97  
070  
117  
112  
107  
102  
97  
110  
98  
93  
88  
83  
78  
73  
68  
63  
58  
135  
94  
89  
84  
79  
74  
69  
64  
59  
54  
1
2
3
4
5
6
7
8
9
29  
48  
93  
24  
4
43  
88  
19  
38  
83  
14  
33  
78  
n/a  
n/a  
9
28  
3
92  
92  
73  
n/a  
4
23  
87  
87  
68  
18  
82  
82  
63  
n/a  
n/a  
13  
77  
77  
58  
Page 18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TYPICAL EXHAUST PIPE CONNECTIONS IN UPFLOW DIRECT OR  
NON-DIRECT VENT APPLICATIONS  
2”  
3”  
2”  
2”  
2”  
2”  
TRANSITION  
or  
or  
EXHAUST  
*2”  
DO NOT transition  
from smaller to larger  
pipe in horizontal runs  
of exhaust pipe.  
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.  
NOTE − Exhaust pipe and intake pipe must be the same diameter.  
FIGURE 24  
TYPICAL EXHAUST PIPE CONNECTIONS IN HORIZONTAL DIRECT OR  
NON-DIRECT VENT APPLICATIONS  
(RIGHT HAND DISCHARGE SHOWN)  
12” max.  
45°  
MAX  
45°  
MAX  
3”  
2”  
or  
TRANSITION  
2”  
*2”  
2”  
2”  
2”  
*2”  
SIDE VIEW  
EXHAUST  
DO NOT transition  
from smaller to larger  
pipe in horizontal runs  
of exhaust pipe.  
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.  
NOTE − Exhaust pipe and intake pipe must be the same diameter.  
FIGURE 25  
Page 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TYPICAL AIR INTAKE PIPE CONNECTIONS IN UPFLOW DIRECT VENT  
APPLICATIONS  
3”  
2”  
or  
TRANSITION  
2”  
2”  
AIR INTAKE  
*2”  
2”  
2”  
or  
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.  
NOTE − Intake and exhaust pipe must be the same diameter.  
FIGURE 26  
TYPICAL AIR INTAKE PIPE CONNECTIONS IN HORIZONTAL DIRECT VENT APPLICATIONS  
(RIGHT HAND DISCHARGE SHOWN)  
3”  
2”  
or  
2”  
TRANSITION  
*2”  
2”  
2”  
2”  
*2”  
AIR  
INTAKE  
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.  
NOTE − Intake and exhaust pipe must be the same diameter.  
FIGURE 27  
Page 20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Intake Piping  
TYPICAL AIR INTAKE PIPE CONNECTIONS  
HORIZONTAL NON−DIRECT VENT APPLICATIONS  
(Horizontal Right−Hand Air Discharge Application Shown)  
The ML193UH furnace may be installed in either direct  
vent or non-direct vent applications. In non-direct vent  
applications, when intake air will be drawn into the furnace  
from the surrounding space, the indoor air quality must be  
considered and guidelines listed in Combustion, Dilution  
and Ventilation Air section must be followed.  
PVC pipe  
coupling  
Follow the next two steps when installing the unit in Direct  
Vent applications, where combustion air is taken from  
outdoors and flue gases are discharged outdoors. The  
provided air intake screen must not be used in direct  
vent applications (outdoors).  
OR  
1 - Use transition solvent cement or a sheet metal screw  
to secure the intake pipe to the inlet air connector.  
INTAKE  
DEBRIS  
SCREEN  
(Provided)  
2 - Route piping to outside of structure. Continue with  
installation following instructions given in general  
guide lines for piping terminations and intake and ex-  
haust piping terminations for direct vent sections. Re-  
fer to table 5 for pipe sizes.  
NOTE - Debris screen may be positioned straight out  
(preferred) or with an elbow rotated to face down.  
TYPICAL AIR INTAKE PIPE CONNECTIONS  
UPFLOW NON−DIRECT  
FIGURE 29  
VENT APPLICATIONS  
Follow the next two steps when installing the unit in Non‐  
Direct Vent applications where combustion air is taken  
from indoors and flue gases are discharged outdoors.  
INTAKE  
DEBRIS  
SCREEN  
(Provided)  
1 - Use field-provided materials and the factory-provided  
air intake screen to route the intake piping as shown in  
(76mm) around the air intake opening. The air intake  
opening (with the protective screen) should always be  
directed forward or to either side in the upflow position,  
and either straight out or downward in the horizontal  
position.  
The air intake piping must not terminate too close  
to the flooring or a platform. Ensure that the intake  
air inlet will not be obstructed by loose insulation  
or other items that may clog the debris screen.  
ameter pipe is used, reduce to 2” diameter pipe at the  
termination point to accommodate the debris  
screen.Use a sheet metal screw to secure the intake  
pipe to the connector, if desired.  
NOTE - Debris screen and elbow may be rotated, so that  
screen may be positioned to face forward or to either side.  
3 - Use a sheet metal screw to secure the intake pipe to  
the connector, if desired.  
FIGURE 28  
Page 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
General Guidelines for Vent Terminations  
CAUTION  
In Non‐Direct Vent applications, combustion air is taken  
from indoors and the flue gases are discharged to the out-  
doors. The ML193UH is then classified as a non‐direct  
vent, Category IV gas furnace.  
If this unit is being installed in an application with  
combustion air coming in from a space serviced by  
an exhaust fan, power exhaust fan, or other device  
which may create a negative pressure in the space,  
take care when sizing the inlet air opening. The in-  
let air opening must be sized to accommodate the  
maximum volume of exhausted air as well as the  
maximum volume of combustion air required for  
all gas appliances serviced by this space.  
In Direct Vent applications, combustion air is taken from  
outdoors and the flue gases are discharged to the out-  
doors. The ML193UH is then classified as a direct vent,  
Category IV gas furnace.  
In both Non‐Direct Vent and Direct Vent applications, the  
vent termination is limited by local building codes. In the ab-  
sence of local codes, refer to the current National Fuel Gas  
Code ANSI Z223-1/NFPA 54 in U.S.A., and current CSA-  
B149 Natural Gas and Propane Installation Codes in Can-  
ada for details.  
EQUIPMENT IN CONFINED SPACE  
(Inlet Air from Ventilated Attic and Outlet Air to Outside)  
Ventilation Louvers  
Inlet Air  
Roof Terminated  
Exhaust Pipe  
(Minimum  
12 in.(305mm) Above  
attic floor)  
or 34. In addition, position termination so it is free from any  
obstructions and 12” above the average snow accumula-  
tion.  
*Intake Debris  
Screen  
(Provided)  
At vent termination, care must be taken to maintain  
protective coatings over building materials (prolonged  
exposure to exhaust condensate can destroy protective  
coatings). It is recommended that the exhaust outlet not be  
located within 6 feet (1.8m) of an outdoor AC unit because  
the condensate can damage the painted coating.  
Furnace  
NOTE-The inlet and outlet air openings shall each have a free area  
2
of at least one square inch per 4,000 Btu (645mm per 1.17kW) per  
hour of the total input rating of all equipment in the enclosure.  
length without insulation in unconditioned space during  
winter design temperatures below 32°F (0°C). If required  
exhaust pipe should be insulated with 1/2” (13mm) Arma-  
flex or equivalent. In extreme cold climate areas, 3/4”  
(19mm) Armaflex or equivalent may be necessary. Insula-  
tion must be protected from deterioration. Armaflex with  
UV protection is permissable. Basements or other en-  
closed areas that are not exposed to the outdoor ambient  
temperature and are above 32 degrees F (0°C) are to be  
considered conditioned spaces.  
FIGURE 30  
EQUIPMENT IN CONFINED SPACE  
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)  
Roof Terminated  
Exhaust Pipe  
Inlet Air  
(Minimum  
IMPORTANT  
Do not use screens or perforated metal in exhaust  
terminations. Doing so will cause freeze-ups and  
may block the terminations.  
12 in.(305mm)  
Above crawl  
space floor)  
Ventilation  
Louvers  
(Crawl space)  
Furnace  
Coupling or  
*Intake Debris Screen Provided)  
3 in. to 2 in.  
Transition  
IMPORTANT  
For Canadian Installations Only:  
(Field Provided)  
In accordance to CSA International B149 installation  
codes, the minimum allowed distance between the  
combustion air intake inlet and the exhaust outlet of  
other appliances shall not be less than 12 inches  
(305mm).  
NOTE-The inlet and outlet air openings shall each have a free area  
2
of at least one square inch per 4,000 Btu (645mm per 1.17kW) per  
hour of the total input rating of all equipment in the enclosure.  
FIGURE 31  
Page 22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TABLE 7  
Maximum Allowable Exhaust Vent Pipe Length (in ft.) Without Insulation In Unconditioned Space For  
Winter Design Temperatures Single - Stage High Efficiency Furnace  
Unit Input Size  
Winter Design  
1
Vent Pipe  
Diameter  
Temperatures °F (°C)  
045  
PVC  
26  
18  
14  
16  
12  
9
070  
PVC  
44  
090  
PVC  
44  
110  
PVC  
24  
135  
PVC  
N/A  
N/A  
60  
2 in.  
2-1/2 in.  
3 in.  
32 to 21  
(0 to -6)  
32  
50  
58  
26  
38  
55  
2 in  
28  
40  
24  
N/A  
N/A  
40  
20 to 1  
(-7 to -17)  
2-1/2 in.  
3 in.  
20  
30  
44  
16  
26  
32  
2 in.  
10  
8
20  
30  
24  
N/A  
N/A  
30  
0 to -20  
(-18 to -29)  
2-1/2 in.  
3 in.  
14  
20  
32  
4
10  
16  
26  
1
Refer to 99% Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook.  
NOTE - Maximum unisulated vent lengths listed may include the termination(vent pipe exterior to the structure) and cannot exceed 5 linear feet or the  
Conditioned  
Space  
Exhaust  
Pipe  
Pipe Insulation  
Intake  
Pipe  
Conditioned  
Space  
Unconditioned  
Space  
FIGURE 32  
Page 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
VENT TERMINATION CLEARANCES  
FOR NON-DIRECT VENT INSTALLATIONS IN THE USA AND CANADA  
INSIDE CORNER  
DETAIL  
G
H
A
D
E
B
L
B
Fixed  
Closed  
B
B
I
C
Operable  
Fixed  
Closed  
M
F
Operable  
K
J
A
B
AREA WHERE TERMINAL  
IS NOT PERMITTED  
AIR SUPPLY INLET  
VENT TERMINAL  
1
2
US Installations  
Canadian Installations  
A =  
Clearance above grade, veranda,  
porch, deck or balcony  
12 inches (305mm) or 12 in. (305mm)  
above average snow accumulation.  
12 inches (305mm) or 12 in. (305mm)  
above average snow accumulation.  
B =  
Clearance to window or  
door that may be opened  
6 inches (152mm) for appliances <10,000  
Btuh (3kw), 12 inches (305mm) for  
appliances > 10,000 Btuh (3kw) and  
<100,000 Btuh (30kw), 36 inches (.9m)  
for appliances > 100,000 Btuh (30kw)  
4 feet (1.2 m) below or to side of opening;  
1 foot (30cm) above opening  
C =  
D =  
Clearance to permanently  
closed window  
* 12”  
* 12”  
Vertical clearance to ventilated soffit  
located above the terminal within a  
horizontal distance of 2 feet (610 mm)  
from the center line of the terminal  
* Equal to or greater than soffit depth.  
* Equal to or greater than soffit depth.  
* Equal to or greater than soffit depth.  
* No minimum to outside corner  
E =  
F =  
Clearance to unventilated soffit  
Clearance to outside corner  
* Equal to or greater than soffit depth.  
* No minimum to outside corner  
*
*
*
*
G = Clearance to inside corner  
H = Clearance to each side of center line ex-  
tended above meter / regulator assembly  
3 feet (.9m) within a height 15 feet (4.5m) 3 feet (.9m) within a height 15 feet (4.5m)  
above the meter / regulator assembly  
*
above the meter / regulator assembly  
I =  
Clearance to service regulator  
vent outlet  
3 feet (.9m)  
* 3 feet (.9m)  
J =  
Clearance to non-mechanical air  
supply inlet to building or the com-  
bustion air inlet to any other ap-  
pliance  
6 inches (152mm) for appliances <10,000  
Btuh (3kw), 12 inches (305mm) for  
appliances > 10,000 Btuh (3kw) and  
<100,000 Btuh (30kw), 36 inches (.9m)  
for appliances > 100,000 Btuh (30kw)  
4 feet (1.2 m) below or to side of opening;  
1 foot (30 cm) above opening  
K =  
L =  
Clearance to mechanical air sup-  
ply inlet  
3 feet (.9m) above if within 10 feet  
(3m) horizontally  
6 feet (1.8m)  
Clearance above paved sidewalk or  
paved driveway located on public property  
7 feet (2.1m)†  
7 feet (2.1m)†  
M = Clearance under veranda, porch, deck or balcony  
12 inches (305mm)‡  
*12 inches (305mm)‡  
1
2
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code  
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code  
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA  
B149.1, clearance will be in accordance with local installation  
codes and the requirements of the gas supplier and these instal-  
lation instructions.”  
† A vent shall not terminate directly above a sidewalk or paved driveway that is  
located between two single family dwellings and serves both dwellings.  
‡ Permitted only if veranda, porch, deck or balcony is fully open  
on a minimum of two sides beneath the floor. Lennox recommends  
avoiding this location if possible.  
FIGURE 33  
Page 24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
VENT TERMINATION CLEARANCES  
FOR DIRECT VENT INSTALLATIONS IN THE USA AND CANADA  
INSIDE CORNER  
DETAIL  
G
H
A
D
E
B
L
B
Fixed  
Closed  
B
B
I
C
Operable  
Fixed  
Closed  
M
F
Operable  
K
J
A
B
AREA WHERE TERMINAL  
IS NOT PERMITTED  
AIR SUPPLY INLET  
VENT TERMINAL  
1
2
US Installations  
Canadian Installations  
A =  
Clearance above grade, veranda,  
porch, deck or balcony  
12 inches (305mm) or 12 in. (305mm)  
above average snow accumulation.  
12 inches (305mm) or 12 in. (305mm)  
above average snow accumulation.  
B =  
Clearance to window or  
door that may be opened  
6 inches (152mm) for appliances <10,000 6 inches (152mm) for appliances <10,000  
Btuh (3kw), 9 inches (228mm) for ap-  
pliances > 10,000 Btuh (3kw) and <50,000  
Btuh (15 kw), 12 inches (305mm) for ap-  
pliances > 50,000 Btuh (15kw)  
Btuh (3kw), 12 inches (305mm) for  
appliances > 10,000 Btuh (3kw) and  
<100,000 Btuh (30kw), 36 inches (.9m)  
for appliances > 100,000 Btuh (30kw)  
* 12”  
C =  
D =  
Clearance to permanently  
closed window  
* 12”  
Vertical clearance to ventilated soffit  
located above the terminal within a  
horizontal distance of 2 feet (610mm)  
from the center line of the terminal  
* Equal to or greater than soffit depth  
* Equal to or greater than soffit depth  
* Equal to or greater than soffit depth  
* Equal to or greater than soffit depth  
* No minimum to outside corner  
E =  
F =  
G =  
Clearance to unventilated soffit  
Clearance to outside corner  
Clearance to inside corner  
* No minimum to outside corner  
*
*
H = Clearance to each side of center line ex-  
tended above meter / regulator assembly  
3 feet (.9m) within a height 15 feet (4.5m)  
above the meter / regulator assembly  
3 feet (.9m) within a height 15 feet (4.5m)  
above the meter / regulator assembly  
I =  
Clearance to service regulator  
vent outlet  
3 feet (.9m)  
* 3 feet (.9m)  
J =  
Clearance to non-mechanical air  
supply inlet to building or the com-  
bustion air inlet to any other ap-  
pliance  
6 inches (152mm) for appliances <10,000 6 inches (152mm) for appliances <10,000  
Btuh (3kw), 9 inches (228mm) for ap-  
pliances > 10,000 Btuh (3kw) and <50,000  
Btuh (15 kw), 12 inches (305mm) for ap-  
pliances > 50,000 Btuh (15kw)  
Btuh (3kw), 12 inches (305mm) for  
appliances > 10,000 Btuh (3kw) and  
<100,000 Btuh (30kw), 36 inches (.9m)  
for appliances > 100,000 Btuh (30kw)  
K =  
L =  
Clearance to mechanical air sup-  
ply inlet  
3 feet (.9m) above if within 10 feet  
(3m) horizontally  
6 feet (1.8m)  
Clearance above paved sidewalk or  
paved driveway located on public property  
7 feet (2.1m)†  
* 7 feet (2.1m)  
M = Clearance under veranda, porch, deck or balcony  
*12 inches (305mm)‡  
12 inches (305mm)‡  
1
2
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code  
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA  
B149.1, clearance will be in accordance with local installation  
codes and the requirements of the gas supplier and these  
installation instructions.”  
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code  
† A vent shall not terminate directly above a sidewalk or paved driveway that is located  
between two single family dwellings and serves both dwellings.  
‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of  
two sides beneath the floor. Lennox recommends avoiding this location if possible.  
FIGURE 34  
Page 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Details of Intake and Exhaust Piping Terminations for  
Direct Vent Installations  
TABLE 8  
EXHAUST PIPE TERMINATION SIZE REDUCTION  
ML193UH  
MODEL  
Termination  
Pipe Size  
NOTE - In Direct Vent installations, combustion air is taken  
from outdoors and flue gases are discharged to outdoors.  
1-1/2” (38mm)  
*045 and 070  
*090  
110  
2” (51mm)  
2” (51mm)  
2” (51mm)  
NOTE - Flue gas may be slightly acidic and may adversely  
affect some building materials. If any vent termination is  
used and the flue gasses may impinge on the building ma-  
terial, a corrosion-resistant shield (minimum 24 inches  
square) should be used to protect the wall surface. If the  
optional tee is used, the protective shield is recommended.  
The shield should be constructed using wood, plastic,  
sheet metal or other suitable material. All seams, joints,  
cracks, etc. in the affected area should be sealed using an  
135  
*ML193UH-045, -070 and -090 units with the flush mount termination  
must use the 1-1/2” accelerator supplied with the kit unless a tee is used  
3”(76mm) MAX.  
SIZE TERMINATION  
Inches(mm)  
UNCONDITIONED  
ATTIC SPACE  
8” (203mm) MIN  
Intake and exhaust pipes may be routed either horizontally  
through an outside wall or vertically through the roof. In at-  
tic or closet installations, vertical termination through the  
terminations.  
12” (305mm) ABOVE  
AVERAGE SNOW  
ACCUMULATION  
1 - Intake and exhaust terminations are not required to be  
in the same pressure zone. You may exit the intake on  
one side of the structure and the exhaust on another  
side (figure 36). You may exit the exhaust out the roof  
3” (76mm) OR  
2” (51mm) PVC  
PROVIDE SUPPORT  
FOR INTAKE AND  
EXHAUST LINES  
DIRECT VENT ROOF TERMINATION KIT  
(15F75 or 44J41)  
NOTE - When venting in different pressure zones,  
maximum separation of intake and exhaust pipe DO  
NOT apply.  
FIGURE 35  
2 - Intake and exhaust pipes should be placed as close  
together as possible at termination end (refer to il-  
lustrations). Maximum separation is 3” (76mm) on roof  
terminations and 6” (152mm) on side wall termina-  
tions.  
Exiting Exhaust and Intake Vent  
(different pressure zones)  
NOTE - When venting in different pressure zones, the  
maximum separation requirement of intake and ex-  
haust pipe DOES NOT apply.  
Inlet Air  
3 - On roof terminations, the intake piping should termi-  
nate straight down using two 90° elbows (See figure  
Exhaust  
Pipe  
Furnace  
(Minimum 12 in.  
305 MM) above  
grade or snow  
accumulation  
4 - Exhaust piping must terminate straight out or up as  
shown. A reducer may be required on the exhaust pip-  
ing at the point where it exits the structure to improve  
the velocity of exhaust away from the intake piping.  
FIGURE 36  
Exiting Exhaust and Intake Vent  
(different pressure zones)  
5 - On field supplied terminations for side wall exit, ex-  
haust piping may extend a maximum of 12 inches  
(305mm) for 2” PVC and 20 inches (508mm) for 3”  
(76mm) PVC beyond the outside wall. Intake piping  
should be as short as possible.  
Roof T  
erminated  
Exhaust Pipe  
6 - On field supplied terminations, a minimum distance  
between the end of the exhaust pipe and the end of the  
intake pipe without a termination elbow is 8” and a  
minimum distance of 6” with a termination elbow.  
Inlet Air  
(Minimum 12 in.  
305 MM) above  
grade or snow  
accumulation  
Furnace  
NOTE - Care must be taken to avoid recirculation of  
FIGURE 37  
exhaust back into intake pipe.  
Page 26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
7 - If intake and exhaust piping must be run up a side wall  
to position above snow accumulation or other ob-  
structions, piping must be supported. At least one  
bracket must be used within 6” from the top of the el-  
bow and then every 24” (610mm) as shown in figure  
exhaust and intake piping must be run up an outside  
wall, the exhaust piping must be terminated with pipe  
with a 90° elbow turndown. Using turndown will add 5  
feet (1.5m) to the equivalent length of the pipe.  
8 - A multiple furnace installation may use a group of up to  
four terminations assembled together horizontally, as  
12”  
(305mm)  
5-1/2”  
(140mm)  
EXHAUST  
VENT  
5”  
(127mm)  
INTAKE  
AIR  
18” MAX.  
(457mm)  
Front View  
EXHAUST VENT  
12” (305mm) Min.  
above grade or  
average snow  
accumulation.  
Inches (mm)  
INTAKE  
AIR  
optional intake elbow  
Side View  
1 1/2” (38mm) accelerator  
provided on 71M80 & 44W92  
kits for ML193UH045P24B,  
070P24B & 070P36B  
OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT  
INSTALLATION OF DIRECT VENT WALL TERMINATION KIT  
(30G28 or 81J20)  
EXHAUST  
VENT  
FIGURE 40  
FLASHING  
12” (305mm)  
INTAKE  
AIR  
(Not Furnished)  
Minimum  
Above Average  
Snow  
2” EXTENSION FOR 2” PVC  
PIPE1” EXTENSION FOR 3”  
PVC PIPE  
Accumulation  
FURNACE  
EXHAUST  
PIPE  
4''  
FURNACE  
INTAKE  
PIPE  
SHEET METAL STRAP  
(Clamp and sheet metal strap  
must be field installed to support  
the weight of the termination kit.)  
CLAMP  
GLUE EXHAUST  
END FLUSH INTO  
TERMINATION  
FIELD-PROVIDED  
REDUCER MAY BE REQUIRED  
TO ADAPT LARGER VENT  
PIPE SIZE TO TERMINATION  
FLAT  
SIDE  
1-1/2” ACCELERATOR  
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION  
71M80, 69M29 or 60L46 (US)  
44W92 or 44W93 (Canada)  
(all -45, -070 and -090 units)  
FLUSH-MOUNT SIDE WALL TERMINATION KIT  
51W11 (US) or 51W12 (Canada)  
FIGURE 38  
FIGURE 41  
FIELD-PROVIDED  
REDUCER MAY BE REQUIRED  
TO ADAPT LARGER VENT  
PIPE SIZE TO TERMINATION  
1-1/2” (38mm) accelerator  
provided on 71M80 & 44W92  
kits for ML193UH045P24B,  
070P24B & 070P36B  
OUTSIDE  
INTAKE  
WALL  
AIR  
EXHAUST  
VENT  
EXHAUST  
VENT  
12” (305mm) Min.  
above grade or  
average snow  
accumulation.  
INTAKE  
AIR  
INTAKE  
AIR  
CLAMP  
(Not Furnished)  
GRADE  
DIRECT VENT CONCENTRIC WALL TERMINATION  
71M80, 69M29 or 60L46 (US)  
44W92 or 44W93 (Canada)  
FIGURE 39  
Page 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
FIELD FABRICATED WALL TERMINATION  
NOTE − FIELD−PROVIDED  
REDUCER MAY BE  
REQUIRED TO ADAPT  
LARGER VENT PIPE SIZE  
TO TERMINATION  
2” (51mm) 3” (76mm)  
Vent Pipe Vent Pipe  
A− Minimum clearance  
above grade or average  
snow accumulation  
12” (305 mm) 12” (305 mm)  
D
D
B− Maximum horizontal  
separation between  
intake and exhaust  
6” (152 mm)  
6” (152 mm)  
8” (203 mm)  
C1 -Minimum from end of  
exhaust to inlet of intake  
B
B
8” (203 mm)  
6” (152 mm)  
12” (305 mm)  
Intake  
Elbow  
C1  
C2  
C2 -Minimum from end of  
exhaust to inlet of intake  
A
A
6” (152 mm)  
STRAIGHT  
APPPLICATION  
D− Maximum exhaust  
20” (508 mm)  
pipe length  
E− Maximum wall support  
distance from top of each  
pipe (intake/exhaust)  
* WALL  
SUPPORT  
6” (152 mm)  
6” (152 mm)  
D
B
D
with this arrangement.  
E
E
* Use wall support every 24” (610 mm). Use two  
wall supports if extension is greater than  
B
24” (610 mm) but less than 48” (1219 mm).  
NOTE − One wall support must be within 6” (152 mm)  
from top of each pipe (intake and exhaust) to prevent  
movement in any direction.  
A
A
C1  
C2  
EXTENDED  
APPLICATION  
ALTERNATE TERMINATIONS (TEE & FORTY−FIVE DEGREE ELBOWS ONLY)  
3” (76MM)  
Vent Pipe  
2” (51MM)  
Vent Pipe  
B
D
B
A− Clearance above  
grade or average snow  
accumulation  
Exhaust  
12” (305 mm) Min. 12” (305 mm) Min.  
D
1
B− Horizontal  
separation between  
intake and exhaust  
6” (152 mm) Min.  
24” (610 mm) Max.  
6” (152 mm) Min.  
24” (610 mm) Max.  
C
3
C
Intake  
Elbow  
2
C− Minimum from  
end of exhaust to  
inlet of intake  
A
A
9” (227 mm) Min.  
9” (227 mm) Min.  
12” (305 mm) Min. 12” (305 mm) Min.  
16” (405 mm) Max. 20” (508 mm) Max.  
D− Exhaust pipe length  
Front View of  
Intake and Exhaust  
D
E− Wall support distance  
from top of each pipe  
(intake/exhaust)  
6” (152 mm) Max. 6” (152 mm) Max.  
1
E
Intake  
Exhaust  
B
12”  
1
2
The exhaust termination tee should be connected to the 2” or 3” PVC flue pipe as shown in the illustration.  
Do not use an accelerator in applications that include an exhaust termination tee.  
The accelerator is not required.  
As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent  
termination is used and flue gases will impinge on the building materials, a corrosion−resistant shield  
(24 inches square) should be used to protect the wall surface. If optional tee is used, the protective shield  
is recommended. The shield should be constructed using wood, sheet metal or other suitable material.  
All seams, joints, cracks, etc. in affected area, should be sealed using an appropriate sealant.  
Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust  
away from adjacent property. The exhaust must never be directed toward the combustion air inlet.  
C
2
A
3
FIGURE 42  
Page 28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SIZE TERMINATION  
ML193UH DIRECT VENT APPLICATION  
USING EXISTING CHIMNEY  
12” (305mm)  
ABOVE AVE.  
SNOW  
STRAIGHT-CUT OR  
ANGLE-CUT IN DIRECTION  
OF ROOF SLOPE *  
ACCUMULATION  
3”-8”  
(76mm-203mm)  
8” - 12”  
(203mm - 305mm)  
3” (76mm) OR  
2” (51mm) PVC  
UNCONDITIONED  
ATTIC SPACE  
SHOULDER OF FITTINGS  
PROVIDE SUPPORT  
OF PIPE ON TOP PLATE  
Minimum 12” (305MM)  
INTAKE PIPE  
INSULATION (optional)  
PROVIDE SUPPORT  
FOR EXHAUST LINES  
above chimney top  
plate or average snow  
accumulation  
SHEET  
METAL TOP  
PLATE  
ALTERNATE  
INTAKE PIPE  
3” - 8”  
(76mm-  
203mm)  
NON-DIRECT VENT ROOF TERMINATION KIT  
(15F75 or 44J41)  
INSULATE  
TO FORM  
SEAL  
EXTERIOR  
PORTION OF  
CHIMNEY  
FIGURE 44  
3 - If exhaust piping must be run up a side wall to position  
above snow accumulation or other obstructions, pip-  
ing must be supported every 24 inches (610mm).  
When exhaust piping must be run up an outside wall,  
any reduction in exhaust pipe size must be done after  
the final elbow.  
*SIZE TERMINATION  
NOTE - Do not discharge exhaust gases directly into any chimney or vent stack. If ver-  
tical discharge through an existing unused chimney or stack is required, insert piping  
inside chimney until the pipe open end is above top of chimney and terminate as illus-  
trated. In any exterior portion of chimney, the exhaust vent must be insulated.  
4 - Distance between exhaust pipe terminations on mul-  
tiple furnaces must meet local codes.  
FIGURE 43  
Details of Exhaust Piping Terminations for Non‐Direct  
Vent Applications  
ML193UH NON-DIRECT VENT APPLICATION  
USING EXISTING CHIMNEY  
Exhaust pipes may be routed either horizontally through an  
outside wall or vertically through the roof. In attic or closet  
installations, vertical termination through the roof is pre-  
STRAIGHT-CUT OR  
ANGLE-CUT IN DIRECTION  
OF ROOF SLOPE  
SIZE TERMINATION  
Minimum 12” (305MM)  
above chimney top  
plate or average snow  
1 - Exhaust piping must terminate straight out or up as  
shown. The termination pipe must be sized as listed in  
table 8.The specified pipe size ensures proper veloc-  
ity required to move the exhaust gases away from the  
building.  
SHOULDER OF FITTINGS  
PROVIDE SUPPORT  
OF PIPE ON TOP PLATE  
accumulation  
SHEET  
METAL TOP  
PLATE  
2 - On field supplied terminations for side wall exit, ex-  
haust piping may extend a maximum of 12 inches  
(305mm) for 2” PVC and 20 inches (508mm) for 3”  
(76mm) PVC beyond the outside wall.  
INSULATE  
TO FORM  
SEAL  
EXTERIOR  
PORTION OF  
CHIMNEY  
NOTE - Do not discharge exhaust gases directly into any chimney or vent stack. If ver-  
tical discharge through an existing unused chimney or stack is required, insert piping  
inside chimney until the pipe open end is above top of chimney and terminate as illus-  
trated. In any exterior portion of chimney, the exhaust vent must be insulated.  
FIGURE 45  
Condensate Piping  
This unit is designed for either right‐ or left‐side exit of con-  
densate piping in upflow applications. In horizontal applica-  
tions, the condensate trap must extend below the unit. An  
8” service clearance is required for the condensate trap.  
Refer to figures 46 and 48 for condensate trap locations.  
PVC.  
Page 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
NOTE - If necessary the condensate trap may be installed  
up to 5’ away from the furnace. Use PVC pipe to connect  
trap to furnace condensate outlet. Piping from furnace  
must slope down a minimum of 1/4” per ft. toward trap.  
tions the field provided vent must be a minimum 1” to a  
maximum 2” length above the condensate drain outlet  
connection. Any length above 2” may result in a  
flooded heat exchanger if the combined primary drain  
line were to become restricted.  
1 - Determine which side condensate piping will exit the  
unit, location of trap, field-provided fittings and length  
of PVC pipe required to reach available drain.  
Horizontal furnace (figure 53) - In horizontal furnace  
applications the field provided vent must be a mini-  
mum 4” to a maximum 5” length above the condensate  
drain outlet connection. Any length above 5” may re-  
sult in a flooded heat exchanger if the combined pri-  
mary drain line were to become restricted.  
2 - Use a large flat head screw driver or a 1/2” drive socket  
end header box at the appropriate location on the side  
of the unit. Install provided 3/4 NPT street elbow fitting  
into cold end header box. Use Teflon tape or appropri-  
ate pipe dope.  
NOTE - In horizontal applications it is recommended to  
install a secondary drain pan underneath the unit and  
trap assembly.  
3 - Install the cap over the clean out opening at the base  
NOTE - Appropriately sized tubing and barbed fitting  
may be used for condensate drain. Attach to the drain  
4 - Install drain trap using appropriate PVC fittings, glue  
all joints. Glue the provided drain trap as shown in fig-  
Condensate line must maintain a 1/4” downward slope  
from the furnace to the drain.  
6 - If unit will be started immediately upon completion of  
installation, prime trap per procedure outlined in Unit  
Start-Up section.  
CONDENSATE TRAP AND PLUG LOCATIONS  
(Unit shown in upflow position)  
Field Provided Drain Components  
Trap  
(same on  
right side)  
1-1/2 in.  
Elbow  
Plug  
(same on left side)  
Barbed Fitting  
Tubin  
g
Hose Clamp  
FIGURE 47  
CAUTION  
Donot use copper tubing or existing copper conden-  
sate lines for drain line.  
NOTE - In upflow applications where side return  
air filter is installed on same side as the conden-  
sate trap, filter rack must be installed beyond  
condensate trap or trap must be re-located to  
avoid interference.  
Condensate line must slope downward away from the  
trap to drain. If drain level is above condensate trap,  
condensate pump must be used. Condensate drain  
line should be routed within the conditioned space to  
avoid freezing of condensate and blockage of drain  
line. If this is not possible, a heat cable kit may be used  
on the condensate trap and line. Heating cable kit is  
available from Lennox in various lengths; 6 ft. (1.8m) -  
kit no. 26K68; 24 ft. (7.3m) - kit no. 26K69; and 50 ft.  
(15.2m) - kit no. 26K70.  
FIGURE 46  
coil using a separate drain. If necessary the conden-  
sate line from the furnace and evaporator coil can  
Upflow furnace (figure 52) - In upflow furnace applica-  
Page 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
CONDENSATE TRAP LOCA-  
(Unit shown in upflow position with remote trap)  
TIONS  
Condensate Trap With Optional Overflow Switch  
From Evaporator Coil  
Horizontal Furnace4” Min.to 5” Max. above  
condensate drain connection)  
FieldProvidedVent  
Min.1” AboveCondensate  
DrainConnection  
1” Min.  
2” Max.  
Furnace Condensate  
DrainConnection  
*5’ max.  
PVCPipeOnly  
Optional  
To Drain  
*Piping from furnace must slope down a minimum of  
1/4” per ft. toward trap.  
FIGURE 50  
FIGURE 48  
ML193UH With Evaporator  
Coil Using A Separate Drain  
Evaporator drain  
line required  
(Trap at coil is optional)  
Field Provided Vent  
(1” min. 2” max. above  
condensate connec-  
tion)  
Condensate  
DrainConnection  
FIGURE 49  
Page 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ML193UH with Evaporator Coil Using a Separate Drain  
(Unit shown in horizontal left-hand discharge position)  
Field Provided Vent  
(4” min. to 5” max. above  
condensate connection)  
Evaporator  
Coil  
4”min  
5”max  
5’ max.  
PVC Pipe Only  
Condensate  
DrainConnection  
(Trap at coil is optional)  
*Piping from furnace and evaporator coil must  
slope down a minimum 1/4” per ft. toward trap  
Drain Pan  
FIGURE 51  
.
ML193UH with Evaporator  
Coil Using a Common Drain  
IMPORTAN-  
T
Evaporator drain  
line required  
When combining the furnace and evaporator  
coil drains together, the A/C condensate drain  
outlet must be vented to relieve pressure in or-  
der for the furnace pressure switch to operate  
properly.  
(Trap at coil is optional)  
(1min. to 2” Max.above  
condensate drain connection)  
Condensate  
DrainConnection  
FIGURE 52  
ML193UH with Evaporator Coil Using a Common Drain  
(Unit shown in horizontal left−hand discharge position)  
(4min. to 5” Max.above  
condensate drain connection)  
Evaporator  
Coil  
4”min  
5”max  
5’ max.  
PVC Pipe Only  
Condensate  
DrainConnection  
(Trap at coil is optional)  
Drain Pan  
*Piping from furnace and evaporator coil must  
slope down a minimum 1/4” per ft. toward trap  
FIGURE 53  
Page 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TRAP / DRAIN ASSEMBLY USING 1/2” PVC OR 3/4” PVC  
Optional Condensate Drain Connection  
Adapter 3/4 inch slip X  
3/4 inch mpt (not furnished)  
90° Street Elbow  
3/4 inch PVC  
(not furnished)  
Adapter 3/4 inch slip X  
3/4 inch mpt (not furnished)  
Condensate Drain  
Connection In Unit  
1 (25 mm) Min.  
2 (50 mm) Max.  
Above Top Of  
Condensate Drain  
Connection In Unit  
Vent  
5 Feet  
Maximum  
Condensate Drain  
Connection In Unit  
90° Street Elbow  
3/4 inch PVC  
( furnished)  
90° Elbow 3/4 inch PVC  
(Not Furnished)  
To  
Trap  
3/4 inch PVC Pipe  
(Not Furnished)  
1/2 inch PVC Pipe  
(Not Furnished)  
OptionalDrainPipingFromTrap  
Coupling 3/4 inch slip X slip  
(Not Furnished)  
Drain Assembly for 1/2 inch Drain Pipe  
1/2 inch PVC Pipe  
(Not Furnished)  
Drain Trap  
Assembly  
(Furnished)  
90° Elbow  
1/2 inch PVC  
(Not Furnished)  
To  
Drain  
Drain Assembly for 3/4 inch Drain Pipe  
Drain Trap  
Clean Out  
90° Elbow  
90° Elbow  
3/4 inch PVC  
(Not Furnished)  
3/4 inch PVC  
(Not Furnished)  
To  
Drain  
To  
Drain  
Coupling 3/4 inch slip X slip  
(Not Furnished)  
DrainTrap Assembly with 3/4 inch Piping  
DrainTrap Assembly with 1/2 inch Piping  
1 (25 mm) Min. 2 (50 mm) Max. Above Top  
Of Condensate Drain Connection In Unit  
1 (25 mm) Min. 2 (50 mm) Max. Above Top  
Of Condensate Drain Connection In Unit  
Vent  
DrainTrapAssembly  
(Furnished)  
Vent  
3/4 inch  
1/2 inch  
7
Condensate Drain  
Connection In Unit  
Condensate Drain  
Connection In Unit  
(178)  
To  
Drain  
To  
Drain  
FIGURE 54  
Page 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4 - Piping should be sloped 1/4 inch per 15 feet (6mm per  
5.6m) upward toward the gas meter from the furnace.  
The piping must be supported at proper intervals, ev-  
ery 8 to 10 feet (2.44 to 3.05m), using suitable hangers  
or straps. Install a drip leg in vertical pipe runs to serve  
as a trap for sediment or condensate.  
Gas Piping  
CAUTION  
If a flexible gas connector is required or allowed by  
the authority that has jurisdiction, black iron pipe  
shall be installed at the gas valve and extend outside  
the furnace cabinet. The flexible connector can then  
be added between the black iron pipe and the gas  
supply line.  
5 - A 1/8” N.P.T. plugged tap or pressure post is located  
on the gas valve to facilitate test gauge connection.  
6 - In some localities, codes may require installation of a  
manual main shut‐off valve and union (furnished by in-  
staller) external to the unit. Union must be of the  
ground joint type.  
WARNING  
Do not exceed 600 in-lbs (50 ft-lbs) torque when at-  
taching the gas piping to the gas valve.  
IMPORTANT  
Compounds used on threaded joints of gas piping  
must be resistant to the actions of liquified petro-  
leum gases.  
1 - Gas piping may be routed into the unit through either  
the left‐ or right‐hand side. Supply piping enters into  
the gas valve from the side of the valve as shown in  
line enters. Ensure opposite gas line hole is plugged  
with supplied plug.  
Leak Check  
After gas piping is completed, carefully check all piping  
connections (factory- and field-installed) for gas leaks. Use  
a leak detecting solution or other preferred means.  
Never use an open flame to test for gas leaks. Check all  
connections using a commercially available soap solution  
made specifically for leak detection.  
IMPORTANT  
When converting the ML193 unit from natural gas to  
LP/propane install the field provided low pressure  
The furnace must be isolated from the gas supply system  
by closing its individual manual shut‐off valve during any  
pressure testing of the gas supply system at pressuresless  
than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).  
LOW INLET PRESSURE SWITCH  
(S145) LOCATION  
Orange  
MANUAL MAIN SHUT-OFF  
VALVE WILL NOT HOLD  
NORMAL TEST PRESSURE  
FURNACE  
ISOLATE  
GAS VALVE  
1/8” N.P.T.  
PLUGGED TAP  
White  
Orange  
CAP  
FIGURE 56  
IMPORTANT  
Yellow  
Gas Valve Shown In Off Position  
When testing pressure of gas lines, gas valve must  
valves can be damaged if subjected to pressures  
greater than 1/2 psig (3.48 kPa).  
FIGURE 55  
2 - When connecting gas supply, factors such as length of  
run, number of fittings and furnace rating must be con-  
sidered to avoid excessive pressure drop. Table 9 lists  
recommended pipe sizes for typical applications.  
WARNING  
FIRE OR EXPLOSION HAZARD  
NOTE - Use two wrenches when connecting gas pip-  
ing to avoid transferring torque to the manifold.  
Failure to follow the safety warnings exactly could  
result in serious injury, death, or property damage.  
Never use an open flame to test for gas leaks. Check  
all connections using a commercially available soap  
solution made specifically for leak detection. Some  
soaps used for leak detection are corrosive to cer-  
tain metals. Carefully rinse piping thoroughly after  
leak test has been completed.  
3 - Gas piping must not run in or through air ducts, clothes  
chutes, chimneys or gas vents, dumb waiters or eleva-  
tor shafts. Center gas line through piping hole. Gas  
Page 34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
AUTOMATIC  
GAS VALVE  
(with manual  
shut-off valve)  
Left Side Piping  
(Standard)  
Right Side Piping  
(Alternate)  
Bellows Grommet  
MANUAL  
MAIN SHUT-OFF  
VALVE  
MANUAL  
MAIN SHUT-OFF  
VALVE  
Plug  
Plug  
GROUND  
JOINT  
UNION  
GROUND  
JOINT  
UNION  
DRIP LEG  
Gas Valve  
Gas Valve  
Bellows Grommet  
DRIP LEG  
FIELD  
PROVIDED  
AND INSTALLED  
NOTE - BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET  
FIGURE 57  
Horizontal Applications  
Possible Gas Piping Configurations  
MANUAL  
MAIN SHUT-OFF  
VALVE  
Horizontal Application  
Left-Side Air Discharge  
MANUAL  
MAIN SHUT-OFF  
VALVE  
GROUND  
JOINT  
UNION  
Bellows Grommet  
GROUND  
JOINT  
UNION  
DRIP LEG  
Bellows Grommet  
DRIP LEG  
Gas Valve  
Horizontal Application  
Right-Side Air Discharge  
MANUAL  
MAIN SHUT-OFF  
VALVE  
Gas Valve  
GROUND  
JOINT  
UNION  
Bellows Grommet  
FIELD  
PROVIDED  
AND INSTALLED  
DRIP LEG  
NOTE - BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET  
Plug  
FIGURE 58  
Page 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TABLE 9  
GAS PIPE CAPACITY - FT3/HR (kL/HR)  
Length of Pipe-Feet(m)  
Nominal  
Iron Pipe Size  
-Inches(mm)  
Internal  
Diameter  
-Inches(mm)  
10  
(3.048)  
20  
(6.096)  
30  
(9.144)  
40  
50  
60  
70  
80  
90  
100  
(12.192) (15.240) (18.288) (21.336) (24.384) (27.432) (30.480)  
1/2  
(12.7)  
.622  
(17.799)  
175  
(4.96)  
120  
(3.40)  
97  
(2.75)  
82  
(2.32)  
73  
(2.07)  
66  
(1.87)  
61  
(1.73)  
57  
(1.61)  
53  
(1.50)  
50  
(1.42)  
3/4  
(19.05)  
.824  
(20.930)  
360  
(10.19)  
250  
(7.08)  
200  
(5.66)  
170  
(4.81)  
151  
(4.28)  
138  
(3.91)  
125  
(3.54)  
118  
(3.34)  
110  
(3.11)  
103  
(2.92)  
1
(25.4)  
1.049  
(26.645)  
680  
(19.25)  
465  
(13.17)  
375  
(10.62)  
320  
(9.06)  
285  
(8.07)  
260  
(7.36)  
240  
(6.80)  
220  
(6.23)  
205  
(5.80)  
195  
(5.52)  
1-1/4  
(31.75)  
1.380  
(35.052)  
1400  
(39.64)  
950  
(26.90)  
770  
(21.80)  
660  
(18.69)  
580  
(16.42)  
530  
(15.01)  
490  
(13.87)  
460  
(13.03)  
430  
(12.18)  
400  
(11.33)  
1-1/2  
(38.1)  
1.610  
(40.894)  
2100  
(59.46)  
460  
(41.34)  
1180  
(33.41)  
990  
(28.03)  
900  
(25.48)  
810  
(22.94)  
750  
(21.24)  
690  
(19.54)  
650  
(18.41)  
620  
(17.56)  
2
(50.8)  
2.067  
(52.502)  
3950  
(111.85)  
2750  
(77.87)  
2200  
(62.30)  
1900  
(53.80)  
1680  
(47.57)  
1520  
(43.04)  
1400  
(39.64)  
1300  
(36.81)  
1220  
(34.55)  
1150  
(32.56)  
2-1/2  
(63.5)  
2.469  
(67.713)  
6300  
(178.39)  
4350  
(123.17)  
3520  
(99.67)  
3000  
(84.95)  
2650  
(75.04)  
2400  
(67.96)  
2250  
(63.71)  
2050  
(58.05)  
1950  
(55.22)  
1850  
(52.38)  
3
(76.2)  
3.068  
(77.927)  
11000  
(311.48)  
7700  
(218.03)  
6250  
(176.98)  
5300  
(150.07)  
4750  
(134.50)  
4300  
(121.76)  
3900  
(110.43)  
3700  
(104.77)  
3450  
(97.69)  
3250  
(92.03)  
4
(101.6)  
4.026  
(102.260)  
23000  
(651.27)  
15800  
(447.39)  
12800  
(362.44)  
10900  
(308.64)  
9700  
(274.67)  
8800  
(249.18)  
8100  
(229.36)  
7500  
(212.37)  
7200  
(203.88)  
6700  
(189.72)  
NOTE - Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specific gravity gas.  
Removal of the Furnace from Common Vent  
3 - Close all building doors and windows and all doors be-  
tween the space in which the appliances remaining  
connected to the common venting system are located  
and other spaces of the building. Turn on clothes dry-  
ers and any appliances not connected to the common  
venting system. Turn on any exhaust fans, such as  
range hoods and bathroom exhausts, so they will oper-  
ate at maximum speed. Do not operate a summer ex-  
haust fan. Close fireplace dampers.  
In the event that an existing furnace is removed from a  
venting system commonly run with separate gas ap-  
pliances, the venting system is likely to be too large to prop-  
erly vent the remaining attached appliances.  
Conduct the following test while each appliance is operat-  
ing and the other appliances (which are not operating) re-  
main connected to the common venting system. If the vent-  
ing system has been installed improperly, you must  
correct the system as indicated in the general venting re-  
quirements section.  
4 - Follow the lighting instructions. Turn on the appliance  
that is being inspected. Adjust the thermostat so that  
the appliance operates continuously.  
5 - After the main burner has operated for 5 minutes, test  
for leaks of flue gases at the draft hood relief opening.  
Use the flame of a match or candle.  
WARNING  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow the steps outlined below for each  
appliance connected to the venting system being  
placed into operation could result in carbon mon-  
oxide poisoning or death.  
The following steps shall be followed for each ap-  
pliance connected to the venting system being  
placed into operation, while all other appliances  
connected to the venting system are not in  
operation:  
6 - After determining that each appliance connected to the  
common venting system is venting properly, (step 3)  
return all doors, widows, exhaust fans, fireplace damp-  
ers, and any other gas-burning appliances to their pre-  
vious mode of operation.  
7 - If a venting problem is found during any of the preced-  
ing tests, the common venting system must be modi-  
fied to correct the problem.  
1 - Seal any unused openings in the common venting sys-  
tem.  
Resize the common venting system to the minimum  
vent pipe size determined by using the appropriate  
tables in Appendix G. (These are in the current stan-  
dards of the National Fuel Gas Code ANSI Z223.1.  
2 - Inspect the venting system for proper size and horizon-  
tal pitch. Determine that there is no blockage, restric-  
tion, leakage, corrosion, or other deficiencies which  
could cause an unsafe condition.  
Page 36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Complete the wiring connections to the equipment. Use the  
provided unit wiring diagram and the field wiring shown in  
Class II rating for thermostat connections.  
Electrical  
ELECTROSTATIC DISCHARGE (ESD)  
Precautions and Procedures  
Electrically ground the unit according to local codes or, in  
the absence of local codes, according to the current Na-  
tional Electric Code (ANSI/NFPA No. 70) for the USA and  
current Canadian Electric Code part 1 (CSA standard  
C22.1) for Canada. A green ground wire is provided in the  
field make-up box.  
CAUTION  
Electrostatic discharge can affect elec-  
tronic components. Take precautions  
to neutralize electrostatic charge by  
touching your hand and tools to metal  
prior to handling the control.  
NOTE - The ML193UH furnace contains electronic compo-  
nents that are polarity sensitive. Make sure that the furnace  
is wired correctly and is properly grounded.  
INTERIOR MAKE-UP BOX INSTALLATION  
remove and relocate  
plug to unused  
opening on left side  
Accessory Terminals  
One line voltage “EAC” 1/4” spade terminal is provided on  
control configuration. This terminal is energized when the  
indoor blower is operating. Any accessory rated up to one  
amp can be connected to this terminal with the neutral leg  
of the circuit being connected to one of the provided neutral  
terminals. If an accessory rated at greater than one amp is  
connected to this terminal, it is necessary to use an exter-  
nal relay.  
MAKE-UP  
BOX  
Right Side  
One line voltage “HUM” 1/4” spade terminal is provided on  
control configuration. This terminal is energized in the  
heating mode when the combustion air inducer is operat-  
ing. Any humidifier rated up to one amp can be connected  
to this terminal with the neutral leg of the circuit being con-  
nected to one of the provided neutral terminals. If a humidi-  
fier rated at greater than one amp is connected to this termi-  
nal, it is necessary to use an external relay relay.  
FIGURE 59  
The unit is equipped with a field make-up box. The make-  
up box may be moved to the right side of the furnace to fa-  
cilitate installation. Seal unused openings on left side with  
plugs removed from right side. Secure the excess wire to  
the existing harness to protect it from damage.  
Thermostat  
Refer to figure 60 for schematic wiring diagram and trou-  
bleshooting.  
Install the room thermostat according to the instructions  
designations. If the furnace is being matched with a heat  
pump, refer to the FM21 installation instruction or appropri-  
ate dual fuel thermostat instructions.  
The power supply wiring must meet Class I restrictions.  
Protected by either a fuse or circuit breaker, select circuit  
protection and wire size according to unit nameplate.  
NOTE - Unit nameplate states maximum current draw.  
Maximum Over-Current Protection allowed is 15 AMP.  
Indoor Blower Speeds  
Holes are on both sides of the furnace cabinet to facilitate  
wiring.  
1 - When the thermostat is set to “FAN ON,” the indoor  
blower will run continuously on the heating speed  
when there is no cooling or heating demand.  
Install a separate (properly sized) disconnect switch near  
the furnace so that power can be turned off for servicing.  
2 - When the ML193UH is running in the heating mode,  
the indoor blower will run on the heating speed.  
Before connecting the thermostat check to make sure the  
wires will be long enough for servicing at a later date. Make  
sure that thermostat wire is long enough to facilitate future  
removal of blower for service.  
3 - When there is a cooling demand, the indoor blower will  
run on the cooling speed.  
Page 37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Generator Use - Voltage Requirements  
D The furnace integrated control requires both polarity  
and proper ground. Both polarity and proper grounding  
should be checked before attempting to operate the  
furnace on either permanent or temporary power  
D Generator should have a wave form distortion of less  
than 5% THD (total harmonic distortion).  
The following requirements must be kept in mind when  
specifying a generator for use with this equipment:  
D The furnace requires 120 volts + 10% (Range: 108  
volts to 132 volts)  
D The furnace operates at 60 Hz + 5% (Range: 57 Hz to  
63 Hz)  
TYPICAL ML193UH WIRING DIAGRAM  
FIGURE 60  
Page 38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Integrated Control  
INTEGRATED CONTROL  
(Automatic Hot Surface Ignition System)  
TERMINAL DESIGNATIONS  
Humidifier (120VAC)  
HUM  
LINE  
Input (120VAC)  
Transformer (120VAC)  
XFMR  
EAC  
Indoor Air Qality Accessory Air Cleaner (120VAC)  
Blower - Cooling Speed (120VAC)  
Blower - Heating Speed (120VAC)  
Dead terminals to park alternate spd taps  
Continuous blower  
COOL  
HEAT  
PARK  
CONT  
NEUTRALS  
Neutral terminals (120VAC)  
Twinning Terminal (24VAC)  
TWIN  
LED  
PUSH BUTTON  
TWIN  
BLOWER OFF  
DELAY JUMPER  
FIGURE 1  
Note - This control is equipped with a push button switch for  
diagnostic code recall. The control stores the last 5 fault  
codes in non-volatile memory. The most recent fault code  
is flashed first, the oldest fault code is flashed last. There is  
a 2 second pause between codes. When the push button  
switch is pressed for less than 5 seconds, the control will  
flash the stored fault codes when the switch is released.  
The fault code history may be cleared by pressing the push  
button switch for more than 5 seconds.  
Integrated Control Diagnostic Codes  
DIAGNOSTIC CODES  
LED Status  
LED Off  
LED On  
1 Flash  
DESCRIPTION  
No power to control or control harware  
fault detected.  
Normal operation.  
Flame present with gas vavle  
de-energized.  
Pressure switch closed with combustion  
air inducer de-energized.  
2 Flashes  
Pressure switch open with combus-  
tion air inducer energized.  
3 Flashes  
4 Flashes  
5 Flashes  
6 Flashes  
7 Flashes  
Primary limit switch open.  
Rollout switch open.  
Pressure switch cycle lockout.  
Lockout, burners fail to light.  
Lockout, buners lost flame too many  
times.  
8 Flashes  
9 Flashes  
Line voltage polarity incorrect.  
Page 39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
5 - Wait for the combustion air inducer to stop. Set the  
thermostat to initiate a heating demand and again al-  
low the burners to fire for approximately 3 minutes.  
6 - Adjust the thermostat to deactivate the heating de-  
mand and wait for the combustion air inducer to stop.  
At this point, the trap should be primed with sufficient  
water to ensure proper condensate drain operation.  
Unit Start-Up  
FOR YOUR SAFETY READ BEFORE OPERATING  
WARNING  
Do not use this furnace if any part has been under-  
water. A flood-damaged furnace is extremely dan-  
gerous. Attempts to use the furnace can result in fire  
or explosion. Immediately call a qualified service  
technician to inspect the furnace and to replace all  
gas controls, control system parts, and electrical  
parts that have been wet or to replace the furnace, if  
deemed necessary.  
WARNING  
If you do not follow these instructions exactly, a fire  
or explosion may result causing property damage,  
personal injury or death.  
1 - STOP! Read the safety information at the beginning of  
this section.  
WARNING  
2 - Set the thermostat to the lowest setting.  
3 - Turn off all electrical power to the unit.  
4 - This furnace is equipped with an ignition device which  
automatically lights the burners. Do not try to light the  
burners by hand.  
Danger of explosion. Can cause injury  
or product or property damage. Should  
the gas supply fail to shut off or if  
overheating occurs, shut off the gas  
valve to the furnace before shutting off  
the electrical supply.  
5 - Remove the upper access panel.  
6 - Move gas valve switch to OFF. See figure 61.  
7 - Wait five minutes to clear out any gas. If you then smell  
gas, STOP! Immediately call your gas supplier from a  
neighbor's phone. Follow the gas supplier's instruc-  
tions. If you do not smell gas go to next step.  
8 - Move gas valve switch to ON. See figure 61.  
CAUTION  
Before attempting to perform any service or mainte-  
nance, turn the electrical power to unit OFF at dis-  
connect switch.  
MANIFOLD  
PRESSURE  
OUTLET  
MANIFOLD  
PRESSURE  
ADJUSTMENT  
SCREW  
BEFORE LIGHTING the unit, smell all around the furnace  
area for gas. Be sure to smell next to the floor because  
some gas is heavier than air and will settle on the floor.  
The gas valve on the ML193UH is equipped with a gas con-  
trol switch (lever). Use only your hand to move switch. Nev-  
er use tools. If the the switch will not move by hand, do not  
try to repair it. Force or attempted repair may result in a fire  
or explosion.  
INLET  
PRESSURE  
PORT  
Placing the furnace into operation:  
ML193UH units are equipped with an automatic hot sur-  
face ignition system. Do not attempt to manually light burn-  
ers on this furnace. Each time the thermostat calls for heat,  
the burners will automatically light. The ignitor does not get  
hot when there is no call for heat on these units.  
GAS VALVE SHOWN IN ON POSITION  
FIGURE 61  
9 - Replace the upper access panel.  
10- Turn on all electrical power to to the unit.  
11- Set the thermostat to desired setting.  
Priming Condensate Trap  
NOTE - When unit is initially started, steps 1 through 11  
The condensate trap should be primed with water prior to  
start-up to ensure proper condensate drainage. Either pour  
10 fl. oz. (300 ml) of water into the trap, or follow these steps  
to prime the trap:  
may need to be repeated to purge air from gas line.  
12- If the appliance will not operate, follow the instructions  
“Turning Off Gas to Unit” and call your service techni-  
cian or gas supplier.  
1 - Follow the lighting instructions to place the unit into op-  
eration.  
Turning Off Gas to Unit  
2 - Set the thermostat to initiate a heating demand.  
1 - Set the thermostat to the lowest setting.  
3 - Allow the burners to fire for approximately 3 minutes.  
2 - Turn off all electrical power to the unit if service is to be  
performed.  
4 - Adjust the thermostat to deactivate the heating de-  
mand.  
3 - Remove the upper access panel.  
Page 40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
4 - Move gas valve switch to OFF.  
Furnace should operate at least 5 minutes before checking  
gas flow. Determine time in seconds for two revolutions of  
gas through the meter. (Two revolutions assures a more  
accurate time.) Divide by two and compare to time in table  
10 below. If manifold pressure matches table 11 and rate is  
incorrect, check gas orifices for proper size and restriction.  
Remove temporary gas meter if installed.  
5 - Replace the upper access panel.  
Failure To Operate  
If the unit fails to operate, check the following:  
1 - Is the thermostat calling for heat?  
2 - Are access panels securely in place?  
3 - Is the main disconnect switch closed?  
4 - Is there a blown fuse or tripped breaker?  
5 - Is the filter dirty or plugged? Dirty or plugged filters will  
cause the limit control to shut the unit off.  
6 - Is gas turned on at the meter?  
NOTE - To obtain accurate reading, shut off all other gas  
appliances connected to meter.  
Supply Pressure Measurement  
When testing supply gas pressure, use the 1/8” N.P.T.  
plugged tap or pressure post located on the gas valve to  
line pressure with unit firing at maximum rate. Low pres-  
sure may result in erratic operation or underfire. High pres-  
sure can result in permanent damage to gas valve or over-  
fire.  
7 - Is the manual main shut‐off valve open?  
8 - Is the internal manual shut‐off valve open?  
9 - Is the unit ignition system in lockout? If the unit locks  
out again, inspect the unit for blockages.  
Heating Sequence Of Operation  
1 - When thermostat calls for heat, combustion air inducer  
starts.  
2 - Combustion air pressure switch proves blower opera-  
tion. Switch is factory set and requires no adjustment.  
3 - After a 15-second prepurge, the hot surface ignitor en-  
ergizes.  
On multiple unit installations, each unit should be checked  
separately, with and without units operating. Supply pres-  
Manifold Pressure Measurement  
4 - After a 20-second ignitor warm-up period, the gas  
valve solenoid opens. A 4-second Trial for Ignition peri-  
od begins.”  
1 - Remove the threaded plug from the outlet side of the  
gas valve and install a field-provided barbed fitting.  
Connect to a manometer to measure manifold pres-  
sure.  
5 - Gas is ignited, flame sensor proves the flame, and the  
combustion process continues.  
6 - If flame is not detected after first ignition trial, the igni-  
tion control will repeat steps 3 and 4 four more times  
before locking out the gas valve (“WATCHGUARD”  
flame failure mode). The ignition control will then auto-  
matically repeat steps 1 through 6 after 60 minutes.  
To interrupt the 60-minute “WATCHGUARD” period,  
move thermostat from “Heat” to “OFF” then back to  
“Heat”. Heating sequence then restarts at step 1.  
2 - Start unit and allow 5 minutes for unit to reach steady  
state.  
3 - While waiting for the unit to stabilize, observe the  
flame. Flame should be stable and should not lift from  
burner. Natural gas should burn blue.  
4 - After allowing unit to stabilize for 5 minutes, record  
manifold pressure and compare to value given in table  
Gas Pressure Adjustment  
NOTE - Shut unit off and remove manometer as soon as an  
accurate reading has been obtained. Take care to remove  
barbed fitting and replace threaded plug.  
Gas Flow (Approximate)  
TABLE 10  
GAS METER CLOCKING CHART  
Seconds for One Revolution  
TABLE 11  
Supply Line and Manifold Pressure (inches w.c.)  
Natural  
LP  
ML193  
Unit  
Manifold  
Pressure  
1 cu ft  
Dial  
2 cu ft  
Dial  
1 cu ft  
Dial  
2 cu ft  
DIAL  
Unit  
Fuel  
Line Pressure  
All  
All  
Nat. Gas  
L.P. Gas  
3.5  
4.5 - 10.5  
-045  
-070  
-090  
-110  
-135  
80  
160  
110  
82  
200  
136  
102  
82  
400  
272  
204  
164  
136  
55  
10.0  
11.0 - 13.0  
41  
33  
66  
NOTE - A natural to L.P. propane gas changeover kit is  
necessary to convert this unit. Refer to the changeover kit  
installation instruction for the conversion procedure.  
27  
54  
68  
Natural-1000 btu/cu ft  
LP-2500 btu/cu ft  
Page 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Proper Combustion  
High Altitude Information  
NOTE - In Canada, certification for installations at eleva-  
tions over 4500 feet (1372 m) is the jurisdiction of local au-  
thorities.  
Furnace should operate minimum 15 minutes with correct  
manifold pressure and gas flow rate before checking com-  
bustion. Take combustion sample beyond the flue outlet  
and compare to the tables below.  
ML193UH units require no manifold pressure adjustments  
for operation at altitudes up to 10,000 feet (3048 m) above  
sea level. Units installed at altitude of 4501 - 10,000 feet  
(1373 to 3048m) require a pressure switch change which  
and pressure switch requirements at varying altitudes.  
The combustion air pressure switch is factory-set and re-  
quires no adjustment.  
TABLE 12  
ML193  
CO %  
2
CO %  
For L.P.  
For Nat  
2
Unit  
-045  
-070  
-090  
-110  
-135  
7.2 - 7.9  
8.6 - 9.3  
NOTE - A natural to LP/propane gas changeover kit is nec-  
essary to convert this unit. Refer to the changeover kit  
installation instruction for the conversion procedure.  
The maximum carbon monoxide reading should not exceed 50 ppm.  
TABLE 13  
Conversion Kit and Pressure Switch Requirements at Varying Altitudes  
High Altitude  
Natural Burner  
Orifice Kit  
LP/Propane  
to  
Natural  
High Altitude  
LP/Propane  
Burner Orifice Kit  
Natural to  
LP/Propane  
High Altitude Pressure Switch  
ML193  
Unit  
0 - 7500 ft  
(0 - 2286m)  
7501 - 10,000 ft  
(2286 - 3038m)  
0 - 7500 ft  
(0 - 2286m)  
7501 - 10,000 ft  
(2286 - 3038m)  
4501 - 7500 ft 7501 -10,000 ft  
(1373 - 2286m) (2286 - 3048m)  
-045  
-070  
-090  
-110  
-135  
*69W73  
73W37  
*73W81  
*68W68  
93W87  
93W88  
* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit.  
Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-1370 m).  
Page 42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Testing for Proper Venting and Sufficient Combustion Air for Non-Direct Vent Applications  
horizontal pitch. Determine there is no blockage or re-  
striction, leakage, corrosion, or other deficiencies  
which could cause an unsafe condition.  
WARNING  
CARBON MONOXIDE POISONING HAZARD!  
3 - To the extent that it is practical, close all building doors  
Failure to follow the steps outlined below for each  
appliance connected to the venting system being  
placed into operation could result in carbon monox-  
ide poisoning or death.  
and windows and all doors between the space in  
which the appliances connected to the venting system  
are located and other spaces of the building.  
4 - Close fireplace dampers.  
The following steps shall be followed for each ap-  
pliance connected to the venting system being  
placed into operation, while all other appliances con-  
nected to the venting system are not in operation.  
5 - Turn on clothes dryers and any appliances not con-  
nected to the venting system. Turn on any exhaust  
fans, such as range hoods and bathroom exhausts, so  
they will operate at maximum speed. Do not operate a  
summer exhaust fan.  
After the ML193UH gas furnace has been started, the fol-  
lowing test should be conducted to ensure proper venting  
and sufficient combustion air has been provided to the  
ML193UH as well as to other gas‐fired appliances which  
are separately vented.  
6 - Follow the lighting instruction to place the appliance  
being inspected into operation. Adjust thermostat so  
appliance will operate continuously.  
7 - Use the flame of match or candle to test for spillage of  
flue gases at the draft hood relief opening after 5 min-  
utes of main burner operation.  
If a ML193UH furnace replaces a Category I furnace which  
was commonly vented with another gas appliance, the size  
of the existing vent pipe for that gas appliance must be  
checked. Without the heat of the original furnace flue prod-  
ucts, the existing vent pipe is probably oversized for the  
single water heater or other appliance. The vent should be  
checked for proper draw with the remaining appliance.  
8 - If improper venting is observed during any of the  
above tests, the venting system must be corrected or  
sufficient combustion/make‐up air must be provided.  
The venting system should be re‐sized to approach  
the minimum size as determined by using the ap-  
propriate tables in appendix G in the current standards  
of the National Fuel Gas Code ANSI-Z223.1/NPFA 54  
in the U.S.A., and the appropriate Natural Gas and  
Propane appliances venting sizing tables in the cur-  
rent standard of the CSA-B149 Natural Gas and Pro-  
pane Installation Codes in Canada.  
The test should be conducted while all appliances (both in  
operation and those not in operation) are connected to the  
venting system being tested. If the venting system has  
been installed improperly, or if provisions have not been  
made for sufficient amounts of combustion air, corrections  
must be made as outlined in the previous section.  
9 - After determining that each appliance remaining con-  
nected to the common venting system properly vents  
when tested as indicated in step 3, return doors, win-  
dows, exhaust fans, fireplace dampers and any other  
gas‐burning appliance to their previous condition of  
use.  
1 - Seal any unused openings in the venting system.  
2 - Visually inspect the venting system for proper size and  
Page 43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Other Unit Adjustments  
HEAT FAN‐OFF TIME IN SECONDS  
Primary Limit.  
The primary limit is located on the heating compartment  
vestibule panel. This limit is factory set and requires no ad-  
justment.  
NO JUMPER  
Flame Rollout Switches (Two)  
To adjust fan-off timing, reposition jumper across pins to  
achieve desired setting.  
These manually reset switches are located on the front of  
the burner box.  
60 Second  
off Time  
90 Second  
off Time  
120 Second  
off Time  
180 Second  
off Time  
Pressure Switch  
The pressure switch is located in the heating compartment  
on the cold end header box. This switch checks for proper  
combustion air inducer operation before allowing ignition  
trial. The switch is factory-set and must not be adjusted.  
Temperature Rise  
After the furnace has been started and supply and return  
air temperatures have been allowed to stabilize, check the  
temperature rise. If necessary, adjust the blower speed to  
maintain the temperature rise within the range shown on  
the unit nameplate. Increase the blower speed to decrease  
the temperature. Decrease the blower speed to increase  
the temperature rise. Failure to adjust the temperature rise  
may cause erratic limit operation.  
FIGURE 62  
NOTE - Termination of any unused motor leads must be in-  
sulated.  
4 - Place unused blower speed tap on integrated control  
“PARK” terminal or insulate.  
5 - Refer to blower speed selection chart on unit wiring  
diagram for desired heating or cooling speed. See  
Product Specifications bulletin for blower perfor-  
mance tables.  
Fan Control  
The fan on time of 30 seconds is not adjustable. The fan off  
delay (amount of time that the blower operates after the  
heat demand has been satisfied) may be adjusted by  
changing the jumper position across the five pins on the  
integrated control. The unit is shipped with a factory fan off  
setting of 120 seconds. The fan off delay affects comfort  
and is adjustable to satisfy individual applications. Adjust  
the fan off delay to achieve a supply air temperature be-  
tween 90° and 110°F at the moment that the blower is  
de-energized. Longer off delay settings provide lower re-  
turn air temperatures; shorter settings provide higher re-  
6 - Connect selected speed tap at integrated control  
speed terminal.  
7 - Resecure blower access panel.  
8 - Turn on electrical power to furnace.  
9 - Recheck temperature rise.  
Electronic Ignition  
The integrated control has an added feature of an internal  
Watchguard control. The feature serves as an automatic  
reset device for integrated control lockout caused by igni-  
tion failure. This type of lockout is usually due to low gas  
line pressure. After one hour of continuous thermostat de-  
mand for heat, the Watchguard will break and remake ther-  
mostat demand to the furnace and automatically reset the  
integrated control to begin the ignition sequence.  
Electrical  
1 - Check all wiring for loose connections.  
2 - Check for the correct voltage at the furnace (furnace  
operating). Correct voltage is 120VAC + 10%  
3 - Check amp-draw on the blower motor with blower ac-  
cess panel in place.  
Exhaust and Air Intake Pipe  
Motor Nameplate__________Actual__________  
Blower Speeds  
1 - Check exhaust and air intake connections for tightness  
and to make sure there is no blockage.  
2 - Is pressure switch closed? Obstructed exhaust pipe  
will cause unit to shut off at pressure switch. Check ter-  
mination for blockages.  
Follow the steps below to change the blower speeds.  
1 - Turn off electrical power to furnace.  
2 - Remove blower access panel.  
3 - Obstructed pipe or termination may cause rollout  
switches to open. Reset manual flame rollout switches  
on burner box assembly if necessary.  
3 - Disconnect existing speed tap at integrated control  
speed terminal.  
Page 44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
between the ”C” and ”Twin” terminals of the two controls.  
The 24 VAC secondary of the two systems must be in  
phase. All thermostat connections are made to one control  
thermostats.  
Twinning the ML193UH  
The control board in this furnace is equipped with a provi-  
sion to ”twin” (interconnect) two(2) adjacent furnaces with a  
common plenum such that they operate as one (1) large  
unit.  
The twinned furnace without thermostat connections is to  
have the call for heat supplied by an external 24VAC isola-  
tion relay to prevent its rollout switch from being bypassed  
by the other twinned furnace. The coil of the isolation relay  
connects from the thermostat ”W” to 24 VAC common. The  
contacts of the relay connect ”R” to ”W” on the non-thermo-  
stat twin.  
When twinned, the circulating blower speeds are synchro-  
nized between the furnaces. If either furnace has a need to  
run the blower, both furnaces will run the blower on the  
same speed. The cooling speed has highest priority, fol-  
lowed by heating speed and fan speed.  
Field installation of twinning consists of connecting wires  
FIELD WIRING FOR TWINNING  
TWIN  
TWIN  
SINGLE STAGE THERMOSTAT  
TWO-STAGE THERMOSTAT  
R
R
Y
G
R
R
Y
G
Call For Cool  
Call For Cool  
TWIN 1  
TWIN 1  
Y
Y
Call For Fan  
Call For Fan  
G
G
Call For 1st  
Stage Heat  
Call For Heat  
W
W1  
W
C
W
Call For 2nd  
StageHeat  
W2  
C
TWIN  
TWIN  
ISOLATION  
RELAY  
ISOLATION  
RELAY  
R
R
Y
G
TWIN 2  
TWIN 2  
Y
G
W
C
W
C
FIGURE 2  
Page 45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Electrical  
Service  
1 - Check all wiring for loose connections.  
2 - Check for the correct voltage at the furnace (furnace  
operating).  
3 - Check amp-draw on the blower motor.  
Motor Nameplate__________Actual__________  
WARNING  
ELECTRICAL SHOCK, FIRE,  
OR EXPLOSION HAZARD.  
Winterizing and Condensate Trap Care  
1 - Turn off power to the furnace.  
Failure to follow safety warnings exactly could result  
in dangerous operation, serious injury, death or  
property damage.  
Improper servicing could result in dangerous opera-  
tion, serious injury, death, or property damage.  
Before servicing, disconnect all electrical power to  
furnace.  
When servicing controls, label all wires prior to dis-  
connecting. Take care to reconnect wires correctly.  
Verify proper operation after servicing.  
2 - Have a shallow pan ready to empty condensate water.  
3 - Remove the clean out cap from the condensate trap  
and empty water. Inspect the trap then reinstall the  
clean out cap.  
Cleaning the Burner Assembly  
1 - Turn off gas and electrical power to the furnace. Re-  
move heating compartment access panel.  
2 - Disconnect the gas supply line from the gas valve.  
3 - Disconnect and label wires from gas valve.  
4 - Disconnect ignitor wiring at 2 circuit plug.  
5 - Disconnect and label wires from rollout switch.  
6 - Disconnect and label flame sensor wire.  
At the beginning of each heating season, system should be  
checked as follows by a qualified service technician:  
Blower  
7 - Disconnect and label ground wire from burner/man-  
ifold assembly.  
Check the blower wheel for debris and clean if necessary.  
The blower motors are prelubricated for extended bearing  
life. No further lubrication is needed.  
8 - Remove four screws that secures burner/manifold as-  
sembly to vestibule. Remove the assembly and make  
note not to allow ignitor plate to dislodge from the as-  
sembly.  
9 - Gently clean the face of the burners using the soft  
brush attachment on a vacuum cleaner. Visually in-  
spect the inside of the burners and crossovers for any  
blockage caused by foreign matter. Remove any  
blockage  
WARNING  
The blower access panel must be securely in place  
when the blower and burners are operating. Gas  
fumes, which could contain carbon monoxide, can  
be drawn into living space resulting in personal inju-  
ry or death.  
10 - Reinstall the burner/manifold assembly using the ex-  
isting four screws. Burners are self aligning to cen-  
ter of clam shells.  
Filters  
11 - Reconnect ground wire.  
12 - Reconnect flame sensor wire.  
13 - Reconnect rollout switch wires.  
14 - Reconnect ignitor wires.  
All air filters are installed external to the unit. Filters should  
be inspected monthly. Clean or replace the filters when  
necessary to ensure proper furnace operation. Table 1 lists  
recommended filter sizes.  
15 - Reconnect gas valve wires.  
16 - Reconnect gas supply line to gas valve.  
Exhaust and air intake pipes  
17 - Refer to instructions on verifying gas and electrical  
connections when re-establishing supplies.  
Check the exhaust and air intake pipes and all connections  
for tightness and to make sure there is no blockage.  
18 - Follow instructions to place furnace in operation. Run  
furnace 5 minutes to ensure burners are clean and op-  
erating correctly.  
NOTE - After any heavy snow, ice or frozen fog event the  
furnace vent pipes may become restricted. Always check  
the vent system and remove any snow or ice that may be  
obstructing the plastic intake or exhaust pipes.  
19 - Replace heating compartment access panel.  
Page 46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Repair Parts List  
The following repair parts are available through Lennox dealers. When ordering parts, include the complete furnace model  
number listed on the CSA nameplate -- Example: ML193UH045XP36B-01. All service must be performed by a licensed  
professional installer (or equivalent), service agency, or gas supplier.  
Cabinet Parts  
Upper access panel  
Heating Parts  
Flame Sensor  
Blower access panel  
Top Cap  
Heat exchanger assembly  
Gas manifold  
Control Panel Parts  
Transformer  
Combustion air inducer  
Gas valve  
Integrated control board  
Door interlock switch  
Blower Parts  
Main burner cluster  
Main burner orifices  
Pressure switch  
Blower wheel  
Ignitor  
Motor  
Primary limit control  
Flame rollout switches  
Motor mounting frame  
Motor capacitor  
Blower housing cutoff plate  
Page 47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start-Up & Performance Check List  
UNIT SET UP  
Furnace:  
Model Number_______________  
Serial Number_________________  
SUPPLY  
AIR  
Line Voltage  
2
4
1
GAS SUPPLY  
Natural Gas  
LP Propane Gas  
3
Piping Connections Tight  
Leak Tested  
Flter  
RETURN AIR  
2
Supply Line Pressure “W.C.________  
1
Gas Supply Pressure  
DUCT SYS-  
TEM  
SUPPLY AIR DUCT  
3
1
Sealed  
Insulated (if necessary)  
RETURN DUCT  
Sealed  
2
INTAKE / EXHAUST  
PIPE  
All Joints Primed and Glued  
Filter Installed and Clean  
Terminations Installed Properly  
Grilles Unobstructed  
Horizontal Pipes Sloped (if applicable)  
Condensate Trap Primed / Line Sloped  
VOLTAGE CHECK  
4
Supply Voltage _____  
Electrical Connections Tight  
Pipes Sup-  
ported  
Heat Cable Installed and Operable (if applicable)  
Page 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT OPERATION  
HEATING MODE  
COOLING MODE  
GAS MANIFOLD PRESSURE “W.C._____  
1
2
INDOOR BLOWER  
AMPS______  
3
4
COMBUSTION SAMPLE CO % CO PPM_______  
2 ______  
TEMPERATURE DROP  
Return Duct Temperature _________  
_
INDOOR BLOWER  
AMPS______  
3
4
Supply Duct Temperature _______  
Temperature Drop = _________  
TEMPERATURE RISE  
5
TOTAL EXTERNAL STATIC (dry coil)  
Supply External Static _______  
Supply Duct Temperature ________  
_
Return Duct Temperature  
_____  
Return External Static + ______  
Total External Static = _______  
Temperature Rise = ________  
TOTAL EXTERNAL STATIC  
5
8
DRAIN LINE  
Leak Free  
Supply External Static _______  
Return External Static + ______  
Total External Static = _______  
THERMOSTAT  
6
7
9
CONDENSATE LINE  
Leak Free  
Adjusted and Programmed  
Explained Operation to Own-  
er  
VENT PIPE  
Leak Free  
Combustion CO  
2
2
7
SUPPLY  
AIR  
Thermostat  
Temperatures  
8
Gas Manifold Pressure  
9
4
1
Blower Motor Amps  
6
3
Duct Static  
5
RETURN AIR  
Contractor's: Name_________________________Telephone_____________Checklist Completed____________________  
Job Address_____-________________________________Technician's Name___________________________________  
Page 49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Requirements for Commonwealth of Massachusetts  
Modifications to NFPA-54, Chapter 10  
4 - INSPECTION. The state or local gas inspector of the  
side wall, horizontally vented, gas-fueled equipment  
shall not approve the installation unless, upon inspec-  
tion, the inspector observes carbon monoxide detec-  
tors and signage installed in accordance with the pro-  
visions of 248 CMR 5.08(2)(a) 1 through 4.  
Revise NFPA-54 section 10.8.3 to add the following re-  
quirements:  
For all side wall, horizontally vented, gas-fueled equipment  
installed in every dwelling, building or structure used in  
whole or in part for residential purposes, including those  
owned or operated by the Commonwealth and where the  
side wall exhaust vent termination is less than seven (7)  
feet above the finished grade in the area of the venting, in-  
cluding but not limited to decks and porches, the following  
requirements shall be satisfied:  
EXEMPTIONS: The following equipment is exempt  
from 24 CMR 5.08(2)(a) 1 through 4:  
1 - The equipment listed in Chapter 10 entitled “Equip-  
ment Not Required to Be Vented” in the most current  
edition of NFPA 54 as adopted by the Board; and  
2 - Product Approved side wall, horizontally vented, gas-  
fueled equipment installed in a room or structure sepa-  
rate from the dwelling, building or structure used in  
whole or in part for residential purposes.  
1 - INSTALLATION OF CARBON MONOXIDE DETEC-  
TORS. At the time of installation of the side wall, hori-  
zontally vented, gas-fueled equipment, the installing  
plumber or gasfitter shall observe that a hard-wired  
carbon monoxide detector with an alarm and battery  
backup is installed on the floor level where the gas  
equipment is to be installed. In addition, the installing  
plumber or gasfitter shall observe that a battery-oper-  
ated or hard-wired carbon monoxide detector with an  
alarm is installed on each additional level of the dwell-  
ing, building or structure served by the side wall, hori-  
zontally vented, gas-fueled equipment. It shall be the  
responsibility of the property owner to secure the ser-  
vices of qualified licensed professionals for the instal-  
lation of hard-wired carbon monoxide detectors.  
MANUFACTURER REQUIREMENTS -  
GAS EQUIPMENT VENTING SYSTEM PROVIDED.  
When the manufacturer of Product Approved side wall,  
horizontally vented, gas-fueled equipment provides a vent-  
ing system design or venting system components with the  
equipment, the instructions provided by the manufacturer  
for installation of the equipment and the venting system  
shall include:  
1 - Detailed instructions for the installation of the venting  
system design or the venting system components:  
and  
a - In the event that the side wall, horizontally vented,  
gas-fueled equipment is installed in a crawl space  
or an attic, the hard-wired carbon monoxide detec-  
tor with alarm and battery back-up may be installed  
on the next adjacent floor level.  
2 - A complete parts list for the venting system design or  
venting system.  
MANUFACTURER REQUIREMENTS -  
GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.  
b - In the event that the requirements of this subdivi-  
sion cannot be met at the time of completion of  
installation, the owner shall have a period of thirty  
(30) days to comply with the above requirements;  
provided, however, that during said thirty (30) day  
period, a battery-operated carbon monoxide detec-  
tor with an alarm shall be installed.  
When the manufacturer of Product Approved side wall,  
horizontally vented, gas-fueled equipment does not pro-  
vide the parts for venting the flue gases, but identifies “spe-  
cial venting systems,” the following requirements shall be  
satisfied by the manufacturer:  
2 - APPROVED CARBON MONOXIDE DETECTORS.  
Each carbon monoxide detector as required in accor-  
dance with the above provisions shall comply with  
NFPA 720 and be ANSI/UL 2034 listed and IAS certi-  
fied.  
1 - The referenced “special venting system” instructions  
shall be included with the appliance or equipment  
installation instructions; and  
2
The “special venting systems” shall be Product Ap-  
proved by the Board, and the instructions for that sys-  
tem shall include a parts list and detailed installation  
instructions.  
3 - SIGNAGE. A metal or plastic identification plate shall  
be permanently mounted to the exterior of the building  
at a minimum height of eight (8) feet above grade di-  
rectly in line with the exhaust vent terminal for the hori-  
zontally vented, gas-fueled heating appliance or  
equipment. The sign shall read, in print size no less  
than one-half (1/2) inch in size, “GAS VENT DIRECT-  
LY BELOW. KEEP CLEAR OF ALL OBSTRUC-  
TIONS.”  
A copy of all installation instructions for all Product  
Approved side wall, horizontally vented, gas-fueled  
equipment, all venting instructions, all parts lists for  
venting instructions, and/or all venting design instruc-  
tions shall remain with the appliance or equipment at  
the completion of the installation.  
Page 50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR THE PROVINCE OF ONTARIO, HORIZONTAL SIDEWALL VENT APPLICATIONS ONLY  
For exterior horizontal venting applications, the 2” X 1.5”  
reducer for 2” venting at the point where the exhaust pipe  
exits the structure is not required in direct or non-direct vent  
applications in the Province of Ontario. In these applica-  
tions, the vent should be oriented such that the exhaust  
plume is unobjectionable. If the installation requires more  
separation between the flue gases and the building struc-  
ture, a reducer may be installed on the exhaust pipe to in-  
crease the flue gas velocity.  
Page 51  
Download from Www.Somanuals.com. All Manuals Search And Download.  

LevelOne Switch FSW 1611TX User Manual
LG Electronics DVD Player GSA 4165B User Manual
Liebert Switch SmartSwitchTM User Manual
Linear Camera Accessories DR4 12 User Manual
Marantz Projector VP 11S1 User Manual
Mattel PDAs Smartphones R7326 User Manual
Maytag Washer W10233434 User Manual
Meade Weather Radio TE256W User Manual
Memorex Clock Radio MMG CR3810 User Manual
Microsoft Laptop W840DI User Manual