RAVENNA™ GAS CONVERSION INSTRuCTIONS LP TO NG
CAT. NO. H5434, MODEL RDV-CK-LP TO NG
INSTALLATION INSTRuCTIONS FOR CONVERTING FROM PROPANE GAS (LP) TO
NATuRAL GAS (NG). FOR uSE wITH THE RAVENNA™ DIRECT VENT GAS FIREPLACE INSERTS
KIT CONTENTS (See Figure 1):
AVERTISSEMENT
1 ea. Robertshaw NG Regulator Kit (A)
1 ea. 1/8” NG main burner orifice (40,000 BTU’s) (B)
1 ea. #36 NG main burner orifice (33,000 BTU’s) (C)
1 ea. RDV 33 Sticker
Cet équipement de conversion sera installé par une
agencequalifiéedeserviceconformémentauxinstruc-
tionsdufabricantettoutesexigencesetcodesapplica-
blesdel'autorisésavoirlajuridiction. Sil'information
danscetteinstructionn'estpassuivieexactement,un
feu,explosionouproductiondeprotoxydedecarbone
peutrésulterledommagescauserdepropriété,perte
oublessurepersonnelledevie. L'agencequalifiéede
service est esponsable de l'installation propre de cet
équipment. L'installationn'estpaspropreetcompléte
jusqu'à l'opération de l'appareil converti est chéque
suivant les critères établis dans les instructions de
propriétaire provisionnées avec l'équipement.
1 ea. Instruction Sheet
TOOLS NEEDED (See Figure 2):
5/32” Allen Wrench Or T-Handle Wrench
Phillips Screwdriver
1/2” Open End Wrench
7/16” Open End Wrench
Figure 1 - Kit Contents
B
C
A
IMPORTANT CANADA
Theconversionshallbecarriedoutinaccordancewith
therequirementsoftheprovincialauthoritieshaving
jurisdictionandinaccordancewiththerequirements
of the CAN/CSA B149.1 Installation code.
IMPORTANT LE CANADA SEuLEMENT
Figure 2 - Tools Needed
La conversion devra être effectuée conformément
aux recommandations des autorités provinciales
ayant juridiction et conformément aux exigences
du code d'installation CAN/CSA B149.1 .
wARNING
This conversion kit shall be installed by a qualified
serviceagencyinaccordancewiththemanufacturer's
instructionsandallapplicablecodesandrequirements
oftheauthorityhavingjurisdiction. Iftheinformation
in these instructions is not followed exactly, a fire,
explosionorproductionofcarbonmonoxidemayresult
causing property damage, personal injury or loss of
life. The qualified service agency performing this
installationisresponsiblefortheproperinstallationof
thiskitandassumesresponsibilityforthisconversion.
The installation is not proper and complete until the
operation of the converted appliance is checked as
specified in the manufacturers instructions supplied
with the kit.
IMPORTANT
The burner orifices provided in this kit are only for
use at elevations of 0 to 2,000 feet (610 M) in the
uSA and 0 to 4,500 feet (0-1372 M) in Canada. At
higher elevations the BTu input must be de-rated
by 4% for every 1,000 feet (305 M) to maintain
the proper ratio of gas to air. If the installer must
convert the unit to adjust for varying altitudes, a
derationinformationstickermustbefilledoutbythe
installer and adhered to the appliance at the time
of the conversion. Contact your local gas supplier
for deration requirements for your area.
1
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 7.Slide the pilot orifice into the NG position by pushing it toward
the opposite side of the pilot stem. The top side of the orifice
slider should appear silver and read NG. The gas supply is now
lined up with the NG orifice. See Figure 6.
Burner Orifice
Orifice Slider
1/2” End wrench
Figure 7 - Replace Burner Orifice
Step 10.Install burner and log rack, and make sure air shutter is 1/8”
open.
Figure 6 - Adjust Orifice Slider to the NG Position
Step 8.Tighten the pilot stem by turning it clockwise, making sure the
orifice slider stays pushed into the NG position.
STEP 9.
40,000 BTu
Using a 1/2” open-end wrench, remove burner orifice. Replace
with 1/8” NG orifice that is supplied in this kit. Make sure to use
pipe sealing compound on threads of new orifice (see Figure 7).
IMPORTANT NOTE: When this appliance is installed with the 1/8”
orifice (40,000 BTU’s), increased mantel clearances are required.
See Page 8 of the Installation and Operation Manual.
Air Venturi Open
Air Shutter
Figure 8 - Adjust Air Shutter
33,000 BTu
Using a 1/2” open-end wrench, remove burner orifice. Replace
with #36 NG orifice that is supplied in this kit. Make sure to use
pipe sealing compound on threads of new orifice (see Figure 7).
NOTE: DIAGRAMS AND ILLUSTRATIONS ARE NOT TO SCALE.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 11.
Manifold Gas Supply Pressure
33,000 BTu
Fuel #
Low
High
If you are using the #36 orifice, adhere the RDV 33 sticker
(provided) in place on the safety label as shown in Figure 9.
The safety label is located in the control compartment.
Natural
Gas
(Lo) 1.7" wC/po. C.E
(0.42 kPa)
(Hi) 3.5" wC/po. C.E
(0.87 kPa)
40,000 BTu (standard from factory)
If you are using the (standard) 1/8” orifice, the label will read
RDV 40 on the safety label as shown in Figure 10. The safety
label is located in the control compartment.
Step 14.Reinstall the the log set and glass door assembly. See Pages
10 and 11 (Log Set Installation) and Page 18 (Door Assembly
Installation) in the Installation and Operation Manual.
Step 15.Lighttheapplianceperthelightinginstructionslabelonappliance
(located below glass door) or lighting instructions on Page 13
in the Installation and Operation Manual. Inspect for proper
pilot and burner flame appearances. See Figures 11 and 12
or refer to Pages 15 and 17 of the Installation and Operation
Manual.
RDV 33 Sticker
Safety Label
Figure 9 - RDV 33 If #36 Orifice is Used
RDV 40
Safety Label
Figure 10 - RDV 40 If 1/8” Orifice is Used
Figure 11 - Proper Pilot Flame Appearance
Step12. Turn on gas supply and test for gas leaks using a gas leak test
solution (see Test Procedure on Page 12 of the Installation and
Operation Manual).
Soot at
Flame Tip
Soot above
Flame Tip
No Soot at
Flame Tip
Step 13.Using a manometer, test the inlet and manifold gas pressure
per instructions in the Installation and Operation Manual (Page
12) and as shown in the following 2 tables.
Dark Orange
Flame
Semi-Transparent
Ports on Pan
Burner Assembly
Yellow Flame
No Blue Flame
Center
Blue Flame
Center
Inlet Gas Supply Pressure
PROPERLY
BuRNING FLAME
IMPROPERLY
BuRNING FLAME
Fuel #
Minimum
Maximum
Desired
Nat.
Gas
5" wC/po. C.E
(1.24 kPa)
10.5" wC/po. C.E
(2.61 kPa)
7" wC/po. C.E
(1.74 kPa)
Figure 12 - Burner Flame Appearance
NOTE: DIAGRAMS AND ILLUSTRATIONS ARE NOT TO SCALE.
Lennox reserves the right to make changes at any time, without notice, in design,
materials, specifications, prices and also to discontinue colors, styles and products.
Consult your local distributor for fireplace code information.
Printed in u.S.A. © Lennox Hearth Products 2007
P/N 775,238M REV. A 12/2007