LST Smoke Alarm M400RFE AS User Manual

RF Interface  
M400RFE-AS  
• Up to 32 radio detectors can be  
controlled  
• Radio detectors can be assigned to  
2 detector zones  
• Individual detector identification  
display via 32 LEDs  
• High range of radio transmission  
• Two frequency bands (868/434MHz)  
with automatic change-over  
• Channel checked for availability  
Description  
The RF Interface M400RFE-AS serves for the connec- using built-in keys. For each radio component the recei-  
tion of up to 32 automatic or manual radio detectors. ver unit provides an individual LED indicator.  
The interface is provided with two detector zones, each  
of them having separate alarm and fault detection re- If necessary, several radio detection systems can be  
lays. Up to 16 detectors can be assigned to each zone. used in the same building, in order to integrate more  
The two zones can be reported to the fire detection than 32 radio components or to create more than 2  
control panel as collective messages, either in conven- detector zones. A unique key, based on a choice of  
tional technology or by means of auxiliary modules via several million codes, is created, which ensures the  
the ADM loop.  
unambiguous identification of the detectors.  
After an alarm activation the RF interface can be reset The RF interface comprises an integrated power unit  
by the fire detection control panel, via the remote reset and can accommodate a stand-by battery 12V/7Ah. It is  
input.  
also possible to use an external power supply.  
The detectors are programmed at the RF interface by  
Specifications  
Mains voltage  
230VAC +10/-15%, 50Hz  
12VA  
Connection power  
External supply voltage (supply through external power unit)  
10 – 30VDC  
Current consumption at 12V (supply through external power unit)  
max. 150mA  
Range of radio transmission (free air)  
Frequency band  
300m  
868MHz or 434MHz  
0°C to +40°C  
400 × 400 × 130 (mm)  
cream, RAL 9001  
6kg  
Ambient temperature  
Dimensions W × H × D (without antenna)  
Colour  
Weight (without battery)  
Approval  
VdS G204104  
249203  
Order number  
Order name  
RF Interface/4Rel M400RFE-AS  
Building Safety. Building Security.  
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27  
M400RFE-AS_DBL_LST_EN_0804.PDF • PAGE 1  
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Kyocera Printer FS 1900 User Manual
Leica Model Vehicle NCL L SP A User Manual
LG Electronics Microwave Oven LSRM2010ST User Manual
Lincoln Electric Welder 4R90 User Manual
LOREX Technology Security Camera SG7610 Series User Manual
Magnavox Flat Panel Television 20MF200V User Manual
Mattel Doll BLL48 0520G1 User Manual
MB QUART Speaker PWE354 User Manual
Melissa Hot Beverage Maker 245 023 User Manual
Middleby Marshall Oven PS314SBI User Manual