• Addressable conventional technology
• Alarm temperature 90°C
• Individual detector addressing by
means of optional address module
• Optional connection of remote
indicator
• Sealed electronics
Description
The Thermal Max Detector GM-55000-137 recognises means of the optional Address Module NG60-1, each
a maximum temperature of 90°C as sign of fire. It com- detector can be addressed individually. With that, the
plies with Class CS and can be used up to a room height activated detector can also be safely identified directly
of 6m.
on the control panel.
Addressable conventional technology is used for alarm The detector can be attached to various bases and it
transmission to the fire detection control panel. By can be protected against theft.
Specifications
Operating voltage
Current consumption
Alarm temperature
Operating temperature
Ambient temperature
Relative humidity
Dimensions ø × H
Colour
Supply through the detector line voltage
typ. 45µA (quiescent)
typ. 90°C
max. +80°C (continuous operation)
-20°C to +90°C (no condensation or icing)
0 – 95% (no condensation)
100 × 42 (mm)
white
Weight
80g
Approval
VdS G200062
Order number
Order name
242027
Thermal Max Detector/Conv./65/Apo GM-55000-137
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
GM-55000-137_DBL_LST_EN_0804.PDF • PAGE 1
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
Download from Www.Somanuals.com. All Manuals Search And Download.
|