• ADM loop technology with
System Sensor/200 protocol
• 6 independent, dry relay outputs
• Status LED for each output
• Setting of module address via
decadic rotary switches
• Mounting in surface mounting box
Description
The addressable Control Module CR-6 serves for the ac- base address, i.e., the lowest one of the 6 addresses,
tuation of external devices by means of 6 independent is set by means of decadic rotary switches.
dry relay contacts, via the bidirectional communication
on the ADM loop with System Sensor/200 protocol.
The optional steel sheet Surface Mounting Box
The Control Module CR-6 occupies 6 consecutive M200SMB-MM accommodates one Monitor Module
addresses on the ADM loop. During commissioning, the IM-10 or Control Module CR-6.
Specifications
Operating voltage
Current consumption
Contact rating
Supply through loop voltage
approx. 1.5mA (quiescent)
2A/30VDC
Ambient temperature
Dimensions L × W × H
Weight
0°C to +50°C
172 × 147 × 25 (mm)
500g
Order number
249116
Order name
Control Module 6xRel.Out/Anal./200/SS CR-6
Surface Mounting Box
Ambient temperature
Dimensions L × W × H
Colour
0°C to +50°C
285 × 225 × 62 (mm)
cream
Weight
2kg
Order number
249117
Order name
Surface Mounting Box for Multimodule/SS M200SMB-MM
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
CR-6_DBL_LST_EN_0804.PDF • PAGE 1
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
Download from Www.Somanuals.com. All Manuals Search And Download.
|