LST Smoke Alarm AOEX 55000 640 User Manual

Device
s
f
o
r
H
azardou
s
A
reas  
for the Apollo/Discovery Loop  
• ADM loop technology with  
Apollo/Discovery protocol  
• Optical smoke detector  
fig. A  
• Thermal detector  
fig. C  
• Safety barrier with galvanic isolation  
• Protocol interface for communication  
with the fire detection control panel  
fig. B  
• ATEX certified  
fig. D  
IS Optical Smoke Detector AOEX-55000-640  
The addressable Intrinsically Safe Optical Smoke De- tion of the sensing chamber to predict the likely time  
tector AOEX-55000-640 (fig. A) uses the scattered light of the next maintenance. Thus the alarm threshold is  
principle and was developed for the detection of smo- automatically adjusted within the permissible range, de-  
ke particles in hazardous areas. The smoke detector pending on the contamination. With that, the constant  
must always be connected via a safety barrier, which response sensitivity of the detector is ensured for a  
has been approved for this detector, and a protocol long time.  
interface. Furthermore, the relevant country specific  
regulations always have to be observed.  
The two LEDs with 360° visibility indicate the activated  
condition of the detector. The detector address is se-  
The proven ADM loop technology with Apollo/Discovery lected by means of a code card in the detector base.  
protocol establishes a permanent communication be- Therefore the detector can be changed without additi-  
tween the fire detection control panel and the detector. onal tools.  
That ensures a periodical function testing of the detec-  
tor. In the control panel all types of fires are detected by The detector is inserted into the IS Detector Base ASEX-  
continuously comparing fire patterns.  
45681-215 (not illustrated) and it can be protected  
Intelligent evaluation algorithms use the current condi- against theft.  
Specifications  
Ignition protection  
Ex classification  
Operating voltage  
Current consumption  
Ambient temperature  
Relative humidity  
Dimensions ø × H  
Colour  
intrinsically safe  
EEx ia IIC T5  
Supply through loop voltage  
typ. 340µA (quiescent)  
-20°C to +40°C (no condensation or icing)  
0 – 95% (no condensation)  
100 × 42 (mm)  
white  
Weight  
100g  
Building Safety. Building Security.  
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27  
Ex-ApoDisc_DBL_LST_EN_0804.PDF • PAGE 1  
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Ambient temperature  
Relative humidity  
Dimensions ø × H  
Colour  
-20°C to +60°C (no condensation or icing)  
10 – 95% (no condensation)  
100 × 15 (mm)  
white  
Weight  
50g  
Order number  
Order name  
246027  
IS Detector Base/Anal./Apo ASEX-45681-215  
Safety Barrier AES-29600-098  
The Safety Barrier AES-29600-098 (fig. C) is used for of fire detectors in hazardous areas. Due to the galvanic  
intrinsically safe electric circuits. The built-in zener bar- isolation, the earth leakage monitoring can remain acti-  
rier and the safe galvanic isolation allow the connection vated in the fire detection control panel.  
Specifications  
Ignition protection  
Ex classification  
Operating voltage  
Ambient temperature  
Colour  
intrinsically safe  
EEx ia IIC T5  
Supply through loop voltage  
-10°C to +60°C  
green  
Approval  
EECS ATEX 0073  
Order number  
Order name  
228004  
Safety Barrier/Anal./XP95/Apo AES-29600-098  
Protocol Interface API-55000-855  
The Protocol Interface API-55000-855 (fig. D) serves for hazardous areas, via an ADM loop with Apollo/Discove-  
the design of an intrinsically safe electric circuit in ADM ry protocol. The interface is always used together with  
loop technology. It allows the bidirectional data traffic the Safety Barrier AES-29600-098.  
between fire detection control panel and detectors in  
Specifications  
Ignition protection  
Ex classification  
Operating voltage  
Current consumption at 24V  
Ambient temperature  
Relative humidity  
Dimensions W × H × D  
Weight  
intrinsically safe  
EEx ia IIC T5  
Supply through loop voltage  
1mA  
-10°C to +60°C  
10 – 95% (no condensation)  
93 × 110 × 20 (mm)  
100g  
Order number  
228005  
Order name  
Protocol Interface/Anal./XP95/Apo API-55000-855  
Building Safety. Building Security.  
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27  
Ex-ApoDisc_DBL_LST_EN_0804.PDF • PAGE 3  
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED  
Download from Www.Somanuals.com. All Manuals Search And Download.  

KWC Indoor Furnishings Z535095000 User Manual
Laser MP3 Player MP3 2GA8 User Manual
Lathem Clock ATX6 User Manual
Lindy Computer Monitor 25021 User Manual
Linksys Switch PC22604 User Manual
Magnavox Portable CD Player MPC42017 User Manual
M Audio Network Card FireWire SOLO User Manual
Maytag Washer Dryer LAT5006 User Manual
Melissa Iron 641 048 User Manual
Micro Innovations Webcam 4310100 User Manual