• ADM loop technology with
Apollo/Discovery protocol
• For use as maximum heat or
rate-of-rise heat detector
• 5 different operating modes
selectable
• Optional connection of remote
indicator
• Sealed electronics
Description
The addressable Thermal Detector AD-58000-400 is protocol establishes a permanent communication bet-
based on the heat principle and was developed for the ween the fire detection control panel and the detector.
indoor temperature supervision in a wide range of fire That ensures a periodical function testing of the detec-
detection applications.
tor. Fires are safely detected in the control panel by
continuously analysing the measured values.
Depending on the parameter setup in the fire detection
control panel, the detector operates either as maximum The two LEDs with 360° visibility indicate the activated
heat detector with an alarm temperature of 61°C (EN condition of the detector. The detector address is se-
54-5 Class A2S) or 90°C (EN 54-5 Class CS), or as lected by means of a code card in the detector base.
rate-of-rise heat detector with a maximum temperature Therefore the detector can be changed without additi-
of 58°C (EN 54-5 Class A1R), 61°C (EN 54-5 Class A2) onal tools.
or 90°C (EN 54-5 Class CR). In Class A1R the detector
can be used up to a room height of 7.5m, in the other The detector can be attached to various bases and it
operating modes a room height of 6m is permissible.
The proven ADM loop technology with Apollo/Discovery
can be protected against theft.