Kraftware Corporation Garbage Disposal DS 16M2 User Manual

EMC Departmental Switches  
DS-16M2 and DS-32M2  
Installation Guide  
P/N 014003063  
REV A02  
August 1, 2002  
This document explains the power, cooling, weight, and rack placement  
requirements for the EMC departmental switches listed below. It also  
describes the kits available for mounting them in EMC and non-EMC  
racks and includes installation instructions as well.  
Device  
Device Model  
Mounting Kit Model  
Major sections are  
• Device Power, Cooling, and Weight Information................................. 2  
• Device Dimensions.................................................................................... 2  
• Device Placement Requirements............................................................. 2  
• Switch Mounting Kit (DS-16M or DS-32M)........................................... 3  
• Installing the DS-16M and DS-32M Rails............................................... 5  
• Installing the DS-16M2 and DS-32M2 Switches.................................. 17  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
Switch Mounting Kit (DS-16M or DS-32M)  
Switch Mounting Kit (DS-16M or DS-32M)  
The DS16- and DS32-CRKH kits contain the16- or 32-port standard switch  
rail mounting kits, and the DS16- and DS32-CRKL kits contain the 16- or  
32-port low protrusion rail mounting kits.  
Component  
Use  
2 mounting brackets - see illustration on page 17.  
2 per switch  
2 per switch  
2 short rail assemblies (20.5 inches to 27 inches)- see illustration on  
page 6 or page 12  
or  
2 long rail assemblies (27 inches to 34 inches)- see illustration on  
page 6 or page 12  
#10 flat washer  
M5 kep nut  
2 per rail assembly to secure adjustable  
rail to the “C” channel.  
6-32 x .31 screws  
5 thread-forming screws per bracket to  
secure bracket to switch (10)  
or  
5 non thread-forming screws per  
bracket to secure the bracket to the  
switch (10)  
Note: The kits include two (2) bags of  
6-32 x .31 screws. Be sure to check the  
labeling on the bags and the chassis  
number label located on the back and  
bottom of the chassis to ensure that you  
use the correct screws for your chassis.  
M5 x 12 mm screws  
4 per rail for DS-16M in round-hole  
channels (8)  
3 per rail for DS-32M in round-hole  
channels (6)  
Square-hole washer  
M5 x 16 mm screws  
4 per rail for DS-16M in square-hole  
channels (8)  
3 per rail for DS-32M in square-hole  
channels (6)  
M3 x 8 mm screws  
1 per bracket, used to secure brackets  
to the rails (2)  
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Switch Mounting Kit (DS-16M or DS-32M)  
Component  
Use  
#10 washers  
ball studs  
1 washer and 1 ball stud per rail to hold  
bezel (2)  
39U bezel only  
Latch brackets and keyplate spacers  
Left and right latch brackets  
2 each to secure 1U bezel for 16M  
switch in 40U cabinets  
1 left and 1 right to secure 2U bezel for  
32M switch in 40U cabinet  
1U or 2U, low-profile or standard-profile bezel (front rack panel)  
1 per switch  
Two 7-foot USA power cords, straight C13 to N5-15P straight  
Two 6-foot IEC power cords, straight C13 to C14 straight  
2 per switch  
(use the ones appropriate for your PDU)  
Tools Required for Installation  
You will need to have the following tools available to complete the  
installation of the rails and switch(es).  
# 1 Phillips head screwdriver  
1/4-in. nut driver  
5/16-in. nut driver  
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the DS-16M and DS-32M Rails  
Installing the DS-16M and DS-32M Rails  
This section describes the installation procedures for the DS-16M and  
DS-32M rails. The figures below show a front and rear view of four  
sets of rails installed in a 39U rack. Note that the rack is shown  
without the side skins.  
Front View  
Rear View  
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the DS-16M and DS-32M Rails  
DS-16M Rails Installation  
There are two different length rails: The short rails range between  
20.5 inches to 27 inches. The long rails range from 27 inches to 34  
inches. Each kit contains two different length rear rail mounts. Use  
the rail length that is appropriate for your rack/cabinet.  
Front  
Rear  
DS-16M Short Rails (for the CLARiiON Rack/Cabinet)  
DS-16M Long Rails (for 3rd Party Racks/Cabinets)  
Front  
Rear  
The front and rear flanges of the DS-16M rails have three screw holes.  
See the figure below.  
DS-16M Front Flange  
DS-16M Rear (u-shaped) Flange  
If you are installing both a DS-16M2 and DS-32M2 switch, the DS-16M2  
should be positioned at the top of the rack/cabinet, located above the  
DS-32M2 switch.  
Select the appropriate length rails, and follow the steps below to  
install them.  
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the DS-16M and DS-32M Rails  
1. Assemble the rails.  
The rails assembly consists of an adjustable rail, a C channel, and  
two washers and kep nuts. See the figure below.  
C channel  
Adjustable  
rail  
a. Insert the threaded posts on the C channel into the slot on the  
adjustable rail.  
b. Secure the adjustable rail to the C channel with two #10 flat  
washers and M5 kep nuts. Leave the nuts finger tight.  
Attach washers\nuts  
to threaded posts  
2. Determine where in the rack/cabinet you are going to locate the  
switch.  
The left/right orientation of the rails is determined by the  
location of the word “top” on the C channel. The rail is oriented  
correctly when this word “top” is up and toward the rack/cabinet  
front. See the next figure.  
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the DS-16M and DS-32M Rails  
"Top" up and to the  
rack front  
3. Adjust the length of the rail to fit between the channels in the  
rack/cabinet.  
NOTE: The rail flanges go to the inside of the channels.  
4. Once the rails are adjusted to the correct length, tighten the kep  
nuts on the rail assembly.  
NOTE: If the side skins are removed on the rack/cabinet, you can tighten  
the kep nuts after you install the rails.  
5. Align the holes of the front rail flange to the inside of the front  
channel. The top and bottom screw holes are used for the screws;  
the center screw hole is used for the ball stud or latch bracket.  
Flange to the inside  
of the channel (rack front)  
6. Secure the rail to a round-hole channel with 2 M5 x 12 mm  
pan-head screws (see the table on page 3), or secure the rail to a  
square-hole channel with 2 square-hole washers and  
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the DS-16M and DS-32M Rails  
M5 x 16 mm flat head screws (see the table on page 3). Leave the  
screws finger-tight, and tighten them after the switch is installed.  
See the figure below.  
DS-16M Round-Hole  
Channel, Rack Front  
(for example, the  
DS-16M Square-Hole  
Channel, Rack Front  
(Third-Party Rack/Cabinet)  
CLARiiON Rack/Cabinet)  
If you are installing the switch in a 40U cabinet, install a keyplate spacer on  
the outside of the channel as you secure the rail to the front channel. The  
spacer is marked such that an L or an R will be upright when correctly  
installed on the left or right channel. See the figure below.  
Switch  
Mounting Rails  
Spacer  
Screw (2)  
EMC2424  
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the DS-16M and DS-32M Rails  
7. If you are installing the switch in a 39U cabinet, position the #10  
washer and ball stud in the center hole, between the two  
M5 x 12 mm screws. Hand-tighten the ball stud.  
NOTE: The ball studs support the bezel.  
If you are installing the switch in a 40U cabinet, use an M5 x 12 mm  
screw to install the latch bracket in the center hole, over the  
keyplate spacer. See the figure below.  
Keyplate  
Spacer  
Latch  
Bracket  
Screw  
EMC2422  
8. Align the holes in the rear, u-shaped flange of the rail with the  
holes in the rear inside channel.  
Rear (u-shaped)  
flange  
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the DS-16M and DS-32M Rails  
9. Secure the rail to a round-hole rear channel with 2 M5 x 12 mm  
pan-head screws (see the table on page 3), or secure the rail to a  
square-hole rear channel with 2 square-hole washers and  
M5 x 16 mm flat-head screws (see the table on page 3). Leave the  
screws finger-tight, and tighten them after the switch is installed.  
See the figures below.  
DS-16M Round-Hole  
Channel, Rack Rear  
(for example,  
DS-16M Square-Hole  
Channel, Rack Rear  
(for example, Third Party  
Rack/Cabinet)  
CLARiiON Rack/Cabinet)  
10. Repeat steps 1 through 9 for the other rail.  
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the DS-16M and DS-32M Rails  
DS-32M Rails Installation  
There are two different length rails: the short rails range from 20.5  
inches to 27 inches. The long rails range from 27 inches to 34 inches.  
Each kit contains two different length rear rail mounts. Use the rail  
length that is appropriate for your rack/cabinet.  
Front  
DS-32M Short Rails  
(for the CLARiiON Rack/Cabinet)  
Rear  
Front  
DS-32M Long Rails  
(for 3rd Party Racks/Cabinets)  
Rear  
The front and rear flanges of the DS-32M rails have four screw holes.  
See the figure below.  
Rear Flange  
Front Flange  
NOTE: If you are installing both a DS-16M2 and DS-32M2 switch, the  
DS-16M2 should be positioned at the top of the rack/cabinet, located above  
the DS-32M2 switch.  
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the DS-16M and DS-32M Rails  
Select the appropriate length rails, and follow the steps below to  
install them.  
1. Assemble the rails.  
The rails assembly consists of an adjustable rail, a C channel, and  
two washers and nuts. See the figure below.  
C channel  
Adjustable rail  
a. Insert the threaded posts on the C channel into the slot on the  
adjustable rail.  
b. Secure the rail to the C channel with two #10 flat washers and  
M5 kep nuts. Leave the nuts finger-tight.  
2. Determine where in the rack/cabinet you are going to locate the  
switch.  
The left/right orientation of the rails is determined by the  
location of the word “top” on the C channel. The rail is oriented  
correctly when the word “top” is up and toward the rack/cabinet  
front. See the figure below.  
"Top" up and to the  
rack/cabinet  
front  
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the DS-16M and DS-32M Rails  
3. Adjust the length of the rail to fit between the channels in the  
rack/cabinet.  
NOTE: The rail flanges go to the inside of the channels.  
4. Once the rails are adjusted to the correct length, tighten the kep  
nuts.  
NOTE: If the side skins are removed on the rack/cabinet, you can tighten  
the kep nuts after you install the rails.  
5. Align two of the holes of the front rail flange to two holes on the  
inside of the front channel. The top screw hole is used for the  
screw; the bottom screw hole is used for the ball stud when  
installing in a 39U cabinet.  
Flange to the inside  
of the channel  
6. If you are installing a switch in a 39U cabinet, secure the rail to a  
round-hole channel with one M5 x 12 mm pan-head screws and  
one #10 flat washer and ball stud (see the table on page 3), or  
secure the rail to a square-hole channel with one square-hole  
washer and M5 x 16 mm screw and one #10 flat washer and ball  
stud (see the table on page 3). Leave the screw and ball stud  
finger-tight. Tighten them after the switch is installed. See the  
figures below.  
NOTE: The ball studs support the bezel.  
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the DS-16M and DS-32M Rails  
DS-32M Square-Hole  
Channel, Rack/Cabinet Front  
DS-32M Round-Hole  
Channel, Rack Front  
If you are installing the switch in a 40U cabinet, use the appropriate  
screws to install the latch bracket (instead of the ball stud) to the  
outside edge of the channel as you secure the rail. To attach the  
bottom latch bracket screw, install an M5 clip nut over the  
aligning hole in the channel. See the following figure.  
Step 1  
Step 2  
Switch  
Mounting Rail  
Switch  
Mounting Rail  
2U Bracket  
(Left)  
Screw  
(2)  
Screw  
Clip Nut  
Left Front  
Left Front  
EMC2421  
7. Align two holes in the rear, u-shaped flange of the rail with two  
holes in the rear inside channel.  
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the DS-16M and DS-32M Rails  
8. Secure the rail to a round-hole rear channel with two M5 x 12 mm  
screws (see the table on page 3), or secure the rail to a square-hole  
rear channel with two square-hole washers and M5 x 16 mm  
screws (see the table on page 3). Leave the screws finger-tight,  
and tighten them after the switch is installed. See the figure  
below.  
DS-32M Round-Hole  
Channel, Rear  
DS-32M Square-Hole  
Channel, Rear  
9. Repeat steps 1 through 8 for the other rail.  
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the DS-16M2 and DS-32M2 Switches  
Installing the DS-16M2 and DS-32M2 Switches  
This section describes the procedures for installing the DS-16M2 and  
DS-32M2 switches in a rack/cabinet, including attaching the brackets  
on the switch. Both switches are installed in the rack/cabinet the  
same way. Note, however, that the DS-16M should be positioned at  
the top of the rack/cabinet, above the DS-32M.  
Mounting Bracket Installation  
NOTE: The mounting brackets are the same for both the DS-16M2 and  
DS-32M2.  
You must attach mounting brackets to the switch before installing it  
on the rails. The mounting brackets slide into the C channel of the  
rails.  
Follow the steps below to attach the mounting brackets to the switch.  
1. Orient the L-shaped end of the bracket upward and to the fan end  
of the switch as shown in the figure below.  
At the fan end of the switch  
2. Place the bracket against the switch with the counter-sunk screw  
holes facing outward. Align the five screw holes in the bracket  
with the five screw holes on the side of the switch.  
To guarantee that all the screw holes in the bracket orient correctly with  
the screw holes in the switch, first align the bracket’s middle screw hole  
with the middle screw hole in the switch.  
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the DS-16M2 and DS-32M2 Switches  
CAUTION  
!
The kits include two (2) sets of screws. To avoid damaging the  
screw holes, be sure to check the labeling on the bags and use the  
appropriate set of screws for your chassis. The chassis product  
number is located on labels at the back and on the bottom of the  
chassis.  
Align middle hole first  
3. Secure the bracket with five 6-32 x .31 flat-head screws (see the  
table on page 3). Tighten the screws fully.  
Fan end of switch  
4. Repeat steps 1 through 3 above for the other side of the switch.  
Installing the Switch in the Rack/Cabinet  
Follow the steps below to install the switch in the rack/cabinet.  
1. Lift and orient the switch so that the fan end is to the front of the  
rack/cabinet.  
2. Align the bracket on each side of the switch with the C channel on  
each fixed rail.  
3. Push the switch about 3/4 of the way into the rack/cabinet.  
4. Tighten the rear screws securing the rails to the rear of the  
rack/cabinet.  
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
18  
Installing the DS-16M2 and DS-32M2 Switches  
5. Push the switch further into the rack/cabinet until the hole in the  
front part of each bracket (the “L”-shaped end) aligns with the  
hole on the fixed rail. See the figure below.  
C channel  
Align hole in bracket  
with hole in the fixed rail  
6. Tighten the front screws securing the rails to the front of the  
rack/cabinet.  
7. Secure the brackets to the rails with two M3 x 8 mm pan-head  
screws (see the table on page 3), one on each side, as shown  
below.  
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the DS-16M2 and DS-32M2 Switches  
Front View of 32-port Switch Installed in a 39U Rack  
Rear View of 32-port Switch Installed in a 39U Rack  
8. Install the bezel by positioning and installing the bezel stud  
receptacles on the back of the bezel over the ball studs (39U rack)  
or latch brackets (40U rack) on the rail ends.  
9. Push the bezel onto the ball studs or latch brackets until it snaps  
and locks into place. The illustration below shows an installed,  
unpainted 16-port bezel in a 39U rack.  
10. Plug one of the supplied power cords into each of the switch’s  
two power receptacles.  
11. When installing the DS-16M2 switch, run the power cords up in  
front of the units and over the top of the uppermost switch.  
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
20  
Installing the DS-16M2 and DS-32M2 Switches  
NOTE: There is a 3-inch space between the front of the switch and the back of  
the bezel. This is enough room to loop the cord up without pushing the bezel  
off.  
12. When installing the DS-32M2 switch, the 2U spacing allows you  
to run the power cords between the switches.  
13. Secure the power cords in the retainer clips, and route them down  
the trough along the edge of the rear of the rack. See the figures  
below.  
Secure cords with  
retainer clip  
Run cables  
down trough  
14. Plug the other end into available receptacles on the PDU.  
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the DS-16M2 and DS-32M2 Switches  
CAUTION  
!
If you are removing the switches from the cabinet, you must  
remove the top switch from the back of the cabinet. You can remove  
all switches below the top switch from the front.  
15. Attach the fibre-optic cables to the switch and run the cables from  
the switch to the appropriate device. Ensure each fibre-optic  
cable has a minimum bend radius of 2 inches.  
Copyright © 2002 EMC Corporation. All Rights Reserved.  
EMC believes the information in this publication is accurate as of its publication date. The information is subject to  
change without notice.  
THE INFORMATION IN THIS PUBLICATION IS PROVIDED "AS IS." EMC CORPORATION MAKES NO  
REPRESENTATIONS OR WARRANTIES OF ANY KIND WITH RESPECT TO THE INFORMATION IN THIS  
PUBLICATION, AND SPECIFICALLY DISCLAIMS IMPLIED WARRANTIES OF MERCHANTABILITY OR  
FITNESS FOR A PARTICULAR PURPOSE.  
Use, copying, and distribution of any EMC software described in this publication requires an applicable software  
license.  
Trademark Information  
EMC2, EMC, CLARiiON, and Navisphere are registered trademarks and Access Logix, SnapView and MirrorView are trademarks of EMC Corporation.  
All other trademarks mentioned herein are the property of their respective owners.  
EMC Departmental Switches DS-16M2 and DS-32M2 Installation Guide  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Integra Stereo Receiver DTR 82 User Manual
Ives Indoor Furnishings VR900 User Manual
JBL Speaker TiK Sub User Manual
JVC Car Video System KD AVX40 User Manual
JVC Home Theater System SX LC33MK2 User Manual
Kelvinator Refrigerator ER 1531T User Manual
Kenmore Sewing Machine 15243 User Manual
KitchenAid Clothes Dryer KEYS977E User Manual
KitchenAid Cooktop KECC567KBL03 User Manual
KitchenAid Ventilation Hood 883298 User Manual