Jotul Gas Heater GF 3 BV User Manual

WARNING:  
IF THE INFORMATION IN THESE INSTRUCTIONS  
ARE NOT FOLLOWED EXACTLY, A FIRE OR  
EXPLOSION MAY RESULT CAUSING PROPERTY  
DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.  
FOR YOUR SAFETY:  
DO NOT STORE OR USE GASOLINE OR OTHER  
FLAMMABLE VAPORS AND LIQUIDS IN THE  
VICINITY OF THIS OR ANY OTHER APPLIANCE.  
INSTALLATION:  
GF 3 BV  
ALLAGASH  
INSTALLATION AND SERVICE MUST BE  
PERFORMED BY A QUALIFIED INSTALLER,  
SERVICE AGENCY OR LICENSED GAS SUPPLIER.  
WHAT TO DO IF YOU SMELL GAS:  
B-Vent Gas Heater  
• DO NOT TRY TO LIGHT ANY APPLIANCE.  
• DO NOT TOUCH ANY ELECTRICAL  
SWITCHES.  
• DO NOT USE THE PHONE IN YOUR  
BUILDING. IMMEDIATELY CALL YOUR GAS  
SUPPLIER FROM A NEIGHBOR’S PHONE.  
• FOLLOW YOUR GAS SUPPLIER’S  
INSTRUCTIONS.  
• IF YOU CANNOT REACH YOUR GAS  
SUPPLIER, CALL THE FIRE DEPARTMENT.  
AVERTISSEMENT:  
ASSUREZ-VOUS DE BIEN SUIVRE LES  
INSTRUCTIONS DANS CETTE NOTICE POUR  
REDUIRE AU MINIMUM LE RISQUE D’INCENDIE  
OU POUR EVITER TOUT DOMMAGE MATERIEL,  
TOUTE BLESSURE OU MORTALIT’E.  
NE PAS ENTREPOSER NI UTILISER D’ESSENCE  
NI OU LIQUIDES INFLAMMABLES DANS LE  
VOISINAGE DE CET APPAREIL OU DE TOUT  
AUTRE APPAREIL.  
L’INSTALLATION LE SERVICE DOIVENT ETRE  
EXECUTES PAR UN INSTALLATEUR  
QUALIFIE, AGENCE DE SERVICE OU LE  
FOURNISSEUR DE GAZ.  
Installation  
and Operation  
Instructions  
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ.  
• NE PAS TENTER D’ALLUMER L’APPAREIL  
• NE TOUCHEZ A AUCUM NTERRUPTEUR.  
• NE PAS VOUS SERVIR DES TELEPHONES SE  
TROUVANT DANS LE BATIMENT OU VOUS  
VOUS TROUVEZ.  
• APPELEZIMMEDIATEMENTVOTRE  
FOURNISSEUR DE GAZ CHEZ UN VOISIN. SUIVEZ  
LESINSTRUCTIONSDUFOURNISSEUR.  
Warnock Hersey  
C
US  
• SI VOUS NE POUVEZ REJOINDRE LE  
FOURNISSEUR DE GAZ, APPELEZ LE SERVICE  
DES INCENDIES.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WELCOME TO JØTUL:  
Congratulations on the purchase of your new  
Jøtul gas stove.  
We at Jøtul are very happy you have made the  
decision to warm your hearth with a Jøtul product.  
Your new Jøtul Allagash has inherited the benefits  
learned from more than 140 years of producing  
stoves. Jøtul is the world’s largest manufacturer  
of solid fuel burning appliances and has been  
making cast iron wood and coal stoves since 1853.  
28”  
The Allagash incorporates the most advanced gas  
technology with the warm traditional style of cast  
iron. With proper care and operation, your new  
Jøtul will last many, many years.  
22 3/4”  
The Jøtul Allagash gas stove is a gravity vented  
gas fireplace heater. The Allagash B-Vent gas  
stove can only be vented vertically directly to  
the outside, using type B-vent pipe.  
HEIGHT  
OF TOP  
EXIT IS  
CENTER  
OF REAR  
EXIT IS  
23”  
27 1/2”  
The Jøtul Allagash gas stove is designed to operate  
on NATURAL GAS or PROPANE only. For  
safe and efficient operation the stove is equipped  
with a millivolt gas control valve with a piezo  
ignitor. Electrical power is only required when  
operating the OPTIONAL forced air blower, if  
installed on the stove (part # 129161).  
13 1/4”  
Input Rates  
The input rate on the Allagash gas stove is 24,000  
BTU/hr maximum input on the high setting for  
both natural gas and propane, adjusted down to  
19,000 BTU/hr minimum on the low setting, for  
both natural gas and propane.  
4”  
18 1/2”  
Natural gas  
24,000 BTU/hr. maximum input  
19,000 BTU/hr. minimum input  
Propane  
24,000 BTU/hr. maximum input  
19,000 BTU/hr. minimum input  
22 3/4”  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
STANDARDS:  
The installation must conform to local codes. Your  
local Jøtul dealer can assist you in determining  
what is required in your area for a safe and legal  
installation. Some areas require a permit to install  
a gas burning appliance. Always consult your local  
building inspector or authority having jurisdiction  
to determine what regulations apply in your area.  
This appliance complies with National Safety  
standards and is tested and listed by ITS,  
Intertek Testing Services  
Middleton, WI  
In addition, the Allagash gas stove complies with REMEMBER Your local officials have final  
and has been tested and listed as a gravity vented authority in determining if a proposed installation  
gas fieplace heater and listed to:  
is acceptable. Any requirement that is requested  
by the local authority having jurisdiction, that is  
not specifically addressed in THIS manual,  
defaults to local code. In the absence of local  
codes, the installation requirements must comply  
ANSI Z21.88-1998(NFPA 54)  
CSA 2.33-M98 for Canada.  
DO NOT ATTEMPT TO ALTER OR with the current National codes. In the U.S. these  
MODIFY THE CONSTRUCTION OF THE requirements are established in the National Fuel  
APPLIANCE OR ITS COMPONENTS. ANY Code, ANSI Z223.1.(NFPA 54). In Canada, the  
MODIFICATION OR ALTERATION WILL codes have been established in CAN/CGA B149  
VOID THE WARRANTY, CERTIFICATION Fuel Installation Code.  
AND LISTING OF THIS APPLIANCE.  
Installer l’appareil selon les codes ou reglements  
GENERAL INFORMATION:  
locaux, ou, en l’absence de tels reglements, selon  
les Codes d’installation CAN/CGA-B149.  
THIS HEATER MUST BE INSTALLED  
AND MAINTAINED BY A QUALIFIED DO NOT OPERATE THIS STOVE IF ANY  
SERVICE AGENCY. PART HAS BEEN UNDER WATER.  
The installation and repair of this appliance must Immediately call a qualified service technician  
be done by a qualified service person. Failure to inspect the heater and to replace any part of  
to properly install and maintain this heater could the control system and any gas control which has  
result in an unsafe or hazardous installation, been under water.  
which may result in a fire, explosion, property  
damage, personal injury or loss of life.  
Ne pas se servir de cet appareil s’il a ete’ plonge  
dans l’eau, completement ou en partie. Appeler  
This appliance should be inspected before use un technicien qualifie pour inspecter l’appareil et  
and at least annually. More frequent cleaning remplacer toute partie du syste’me de controle et  
may be required due to excessive lint from toute commande qui ont ete plonges dans l’eau.  
carpeting, bedding material, etc. It is imperative  
that control compartments, burners and Do not operate the Allagash gas stove with the  
circulating air passageways of the appliance be glass front removed, cracked or broken.  
kept clean.  
Replacement of the glass should be done by a  
licensed or qualified service person. Only remove  
S’assurer que le bruleur et le compartiment des glass for routine service. Always handle glass  
commandes sont propres. Voir les instructions carefully.  
d’installation et d’utilisation qui accompagnent  
l’appareil.  
Pour utilisation avec les portes en verre cerifiers  
aved l’appareil seulemend ou Ne pas utiliser avec  
des portes on verre.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hot Surfaces  
THIS APPLIANCE MUST NOT BE  
The Allagash gas stove will, during normal CONNECTED TO A CHIMNEY OR FLUE  
operation, reach high surface temperatures SERVING ANY OTHER APPLIANCE OF  
therefore:  
ANY KIND.  
·
·
Due to the high operating temperatures this LOCATION:  
appliance should be located out of traffic  
and away from furniture and draperies.  
In selecting the location, the aesthetic and  
Children and adults should be alerted to the functional use of the appliance are primary  
hazards of high surface temperatures and concerns; However, proper venting systems and  
should stay away to avoid burns or clothing access to the fuel supply are also important issues.  
ignition.  
Due to the high surface temperatures of the  
·
·
·
·
·
·
Young children should be supervised while Allagash, always consider the proximity of traffic  
they are in the same room as the Allagash ways, furniture, draperies, etc.  
gas stove.  
Clothing or other flammable materials This appliance may be located on or near  
should not be placed ON or NEAR the conventional construction materials. HOWEVER,  
Allagash gas stove.  
always maintain the proper clearances to  
Surveiller les enfants. Garder les vetements, combustibles, as this provides adequate  
les meubles, l’essence ou autres liquides a ventilation air around the appliance.  
vapeur inflammables loin de l’appareil.  
NEVER store or use gasoline or any other The following clearances and hearth requirements  
flammable vapors or liquids in the vicinity are the minimum requirements when installing  
of the Allagash gas stove.  
the Allagash gas stove near or on combustible  
Never burn any other materials in your surfaces. Always provide adequate access around  
Allagash gas stove, it is strictly designed for the appliance for servicing and proper operation.  
use with natural gas or propane fuel ONLY.  
Any safety screen, glass or guard removed A combustible surface is anything that can burn  
for servicing the appliance must be replaced (i.e. sheet rock, wall paper, wood, fabrics etc.).  
prior to operating the appliance.  
These surfaces are not limited to those that are  
visible and also include materials that are behind  
non-combustibles.  
Blower/Electrical Hazard  
When the Allagash gas stove is installed with the  
optional forced air Blower Kit (part #129161) the If you are not sure of the combustible nature of  
stove must be electrically grounded in accordance a material, consult your local fire officials.  
with local codes or, in the absence of local codes, Remember, “Fire Resistant” materials are  
with the current NFPA 70- National Electrical considered combustible: they are difficult to  
Code or CSA C22.1-Canadian Code.  
ignite, but will burn. Also, “fire-rated” sheet rock  
is considered combustible.  
The Allagash Blower Kit is already supplied with  
a three-prong (grounding) plug for protection The Allagsh B-Vent gas stove is not to be  
against shock hazard and should be plugged connected or installed using any warm air duct  
directly into a properly grounded three-prong system.  
receptacle.  
Always maintain the proper clearances to the  
DO NOT CUT OR REMOVE THE appliance for the proper flow of combustion and  
GROUNDING PRONG FROM THE PLUG.  
Always unplug the Blower when performing  
routine service to the Allagash gas stove.  
ventilation air to the stove.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
FLOOR PROTECTION:  
PARALLEL INSTALLATION  
The Allagash gas stove CANNOT be installed  
directly on carpeting, vinyl flooring, linoleum or  
Pergoã.  
2” (50mm) from  
draft hood  
If it is desired to install this appliance on any  
combustible material OTHER THAN WOOD,  
a floor pad must be installed that is either metal,  
wood or a listed hearth pad. This floor protection  
must extend the full width and depth of the  
appliance. It is not necessary to remove the  
carpeting, vinyl or linoleum from underneath the  
4”  
(102 mm)  
10”  
(255mm)  
left side  
wall  
right side  
wall  
floor protection.  
Minimum hearth protection  
under the Allagash B-Vent gas  
stove:  
CORNER INSTALLATION  
22 3/4” wide X 18 3/4” deep  
3”  
76mm  
Note: the hearth requirements are the same when  
using the optional short leg package.  
STOVE CLEARANCES:  
3”  
76mm  
Minimum clearances for the Allagash B-Vent  
gas stove are as follows:  
Rear clearance =2”(50mm)  
(measured from draft hood)  
Ceiling =18”(460mm)  
(measured from top of stove)  
Corner clearance =3”(76mm)  
(measured from rear corners)  
MANTEL, CEILING AND TRIM  
Right side clearance = 4”(102mm)  
Left side clearance = 10” (255mm)  
(for access to the lighting instructions)  
MANTEL OR  
TRIM DEPTH  
19”or greater in depth  
All venting components must be installed in  
accordance with the terms of their listing and  
manufacturer’s instructions. Refer to the pipe  
manufacturer’s instructions for proper pipe  
clearances. Any horizontal venting requires a  
2” (50mm) top clearance off top of pipe.  
6”- 18” in depth  
2”- 5” in depth  
A
B
C
1” trim only  
ALCOVE  
MINIMUM  
CLEARANCES TO TOP  
PLATE OF STOVE  
Minimum Alcove Width = 41”(1042mm)  
(minimum side clearance in an alcove becomes 8”  
on right side of stove and 10” on left side of stove).  
Maximum Alcove Depth = 24”(610mm)  
Minimum Alcove Height (off stove)= 18”(460mm)  
(minimum height off top casting of stove).  
A = 18”  
B = 12”  
C = 5”  
(460mm)  
(305mm)  
(127mm)  
1” trim = 1” (25mm)  
Pipe clearances =see manufacturer’s listing.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
• Any UNUSED flue or masonry enclosure can be  
used as a passage way for venting the Allagash:  
PROVIDED the flue is relined using Type B  
4” vent or Listed Flexible Gas Liner.  
VENTING REQUIREMENTS:  
The Allagash is specifically designed to operate  
using 4” Type B vent pipe components or a Listed  
Flexible gas liner.  
• The remaining space around the liner in a  
masonry or zero-clearance flue CANNOT be  
used to vent any other appliance.  
FOLLOW THE GUIDELINES LISTED  
BELOW FOR THE PROPER VENTING OF  
THE ALLAGASH B-VENT STOVE!  
• When terminating through the roof refer to the  
Gas Vent Rule for proper vent termination  
height. See Figure 1.  
• All venting components must be installed in  
accordance with the terms of their listing and  
manufacturer’s instructions.  
• The minimum height of a vertically terminated  
system shall be no less than 7', and the  
maximum height shall be no more than 35'.  
See diagrams page 9.  
• With steep roofs, nearby trees, and in  
predominant windy conditions, poor draft or  
down draft conditions can occur. In these cases,  
increasing the height of the vent or high wind  
termination caps may improve the situation.  
• ELBOWS: If an offset or elbow is necessary  
in the vertical rise, it is important to support  
the vent pipe every three feet, to avoid excessive  
stress on the offsets.  
Figure 1  
• Whenever possible use 45° elbows opposed to  
90° elbows. This offers less restrictions for the  
flow of flue gases.  
NO venting can terminate horizontally or  
below roof eaves.  
Maximum number of 90° elbows = three  
Maximum number of 45° elbows = four  
Passage through combustibles (walls, ceilings)  
must be with Type B venting and must  
maintain listed clearances.  
TOTAL MAXIMUM HORIZONTAL  
RUN ANYWHERE IN THE VENTING  
CONFIGURATION IS 4 FEET. The distance  
between any 45° elbows is considered a  
horizontal run. See diagrams page 9.  
It is recommended that any horizontal runs  
have an upward slope of 1/4” per foot toward  
the termination cap.  
Any Type B vent passing through a roof must  
have a flashing, storm collar, thimble and a  
Type B cap is required. See diagrams page 9.  
When venting through a thimble into a  
masonry flue any venting exposed in the room  
must be Type B venting.  
Venting on the Allagash CANNOT be less than  
Listed Flexible Gas Liners may not be exposed  
4” in diameter or greater than 4” in diameter.  
in any living space.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
• When decorative 6” pipe is installed to cover  
the venting any Listed Flexible Gas liner must  
be connected directly to the stove’s draft hood.  
Allagash B-Vent gas stove vented into a  
masonry or prefabricated fireplace.  
Listed termination  
cap required  
• Use of single wall connector pipe as a vent is  
prohibited for use with theAllagash B-Vent stove.  
Storm collar  
required  
• A firestop is required at every floor.  
Top sealing  
achor plate  
• Any venting that is exposed above the first  
floor, regardless of attic space or living space,  
must be enclosed. Always maintain the  
required clearance from all sides of the vertical  
vent system according to manufacture.  
Type B vent or  
Listed Flexible  
Gas Liner. On  
outside chimneys  
Jøtul recommends  
the use of Type B  
vent to help keep  
the gases warm and  
rising.  
• Installation of any components not  
manufactured or approved by Jøtul or failure  
to meet all clearance requirements will void  
all warranties and could result in property  
damage, bodily injury, or serious fire.  
• Never modify any venting component, or use  
any damaged venting product.  
max. height 35’  
min. height 7’  
• THE GAS APPLIANCE AND VENT  
SYSTEM MUST BE VENTED DIRECTLY  
TO THE OUTSIDE OF THE BUILDING,  
Always maintain  
the proper  
clearance to mantel  
and trim  
AND NEVER ATTACHED TO  
A
CHIMNEY SERVING A SOLID FUEL OR  
GAS BURNING APPLIANCES.  
Maximum  
offset is 4’  
• BE SURE TO MAINTAIN THE PROPER  
CLEARANCES TO COMBUSTIBLES AS  
DEFINED IN THIS MANUAL AND IN  
THE INSTRUCTIONS PROVIDED WITH  
EACH VENTING COMPONENT.  
Recommended  
damper sealing plate  
to seal flue chamber  
to prevent heat loss  
When installing at an altitude above 2000’ the  
minimum vertical rise becomes 12’ from the  
draft hood.  
Allagash B-Vent gas  
stove  
If more than two feet of venting is exposed to  
the outside, the entire exterior vent system  
must be enclosed in an insulated chase system.  
WARNING: FAILURE TO POSITION THE PARTS IN  
ACCORDANCE WITH THIS DIAGRAM OR FAILURE TO USE  
ONLY PARTS SPECIFICALLY APPROVED WITH THIS  
APPLIANCE MAY RESULT IN PROPERTY DAMAGE OR  
PERSONAL INJURY.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENTING CONFIGURATIONS FOR THE  
ALLAGASH B-VENT  
Listed B-Vent  
termination cap  
required.  
Listed B-Vent  
termination cap  
required.  
Maximum total  
horizontal  
anywhere in  
venting  
configuration  
is 4 feet.  
Maximum  
chimney height  
off draft hood  
= 35 feet.  
45° or 90°  
elbow  
Minimum  
NOTE:  
When installing  
at an altitude  
above 2000’ the  
minimum  
vertical rise  
becomes 12’  
from the draft  
hood.  
chimney height  
off draft hood  
= 7 feet.  
Minimum  
chimney height  
off draft hood  
= 7 feet.  
45° or 90°  
elbow  
NOTE:  
When installing  
at an altitude  
above 2000’ the  
minimum  
vertical rise  
becomes 12’  
from the draft  
hood.  
Minimum chimney on the Allagash  
B-Vent top vent or rear vent = 7 feet.  
Maximum horizontal offset anywhere in  
venting configuration; rear vent or top vent  
directly on the stove or further up  
45° or 90° elbows = 4 feet.  
Maximum horizontal offset anywhere in  
venting configuration; rear vent or top vent  
directly on the stove or further up  
45° or 90° elbows = 4 feet.  
Maximum # of elbows;  
90°= three  
45°=four  
Listed B-Vent termination cap always required.  
Listed B-Vent  
termination cap  
required.  
Listed B-Vent  
Maximum total  
termination cap  
horizontal offset  
required.  
anywhere in  
venting  
configuration is  
NOTE:  
When installing  
at an altitude  
45° or 90°  
elbow  
4 feet.  
above 2000’ the  
minimum  
vertical rise  
becomes 12’  
from the draft  
hood.  
Minimum  
chimney height  
off draft hood  
= 7 feet.  
45° or 90°  
Minimum  
elbow  
chimney height  
off draft hood  
= 7 feet.  
45° or 90°  
elbow  
45° or 90°  
elbow  
NOTE:  
When installing  
at an altitude  
above 2000’ the  
minimum  
vertical rise  
becomes 12’  
from the draft  
hood.  
Maximum  
horizontal  
offset  
anywhere in  
venting  
configuration  
is 4 feet.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS CONVERSION:  
Tools required:  
1/4” Nut driver, 7/16” and 1/2” open end  
The Allagash B-Vent gas stove is shipped from wrench or deep well socket, 4mm allen  
the factory equipped as a NATURAL GAS unit; wrench, Torx t20 or slotted screwdriver.  
However, the stove is shipped with the necessary  
gas conversion kit to convert the stove to burn Included in the conversion kit:  
PROPANE GAS. These kits contain all the 1 regulator tower labeled for propane  
necessary components needed to complete the 3 regulator tower screws  
task and ensure safe operation, including labeling 1 burner orifice (#54 LPG)  
that must be affixed to the stove.  
1 pilot orifice ( #30 for LPG, #51 for NG)  
Label A - to be completed and adhered to the  
back of the stove.  
WARNING:  
THE CONVERSION KIT IS TO BE INSTALLED BY  
AN AUTHORIZED JØTUL SERVICE TECHNICIAN  
Label B - to adhere to the stove’s rating plate.  
IMPORTANT:  
IN  
ACCORDANCE  
WITH  
THE  
If the forced air blower kit is installed, be sure  
to unplug blower before proceeding with this  
conversion. Any gas supply must be turned  
off and disconnected from the valve.  
MANUFACTURER’S INSTRUCTION AND ALL  
CODES AND REQUIREMENTS OF THE  
AUTHORITY HAVING JURISDICTION. FAILURE  
TO FOLLOW THESE INSTRUCTIONS COULD  
RESULT IN SERIOUS INJURY OR PROPERTY  
DAMAGE.  
THE QUALIFIED AGENCY  
Conversion instructions are also shipped in the  
stove with the conversion kit.  
PERFORMING THIS WORK ASSUMES  
RESPONSIBILTY FOR THIS CONVERSION.  
Gas Conversion Procedure  
1. Turn off gas supply to the stove.  
2. Lift off top plate (5).  
IN CANADA:  
THE CONVERSION SHALL BE CARRIED OUT IN  
ACCORDANCE WITH THE REQUIREMENTS OF  
THE PROVINCIAL AUTHORITIES HAVING  
JURISDICTION AND IN ACCORDANCE WITH  
THE REQUIREMENTS OF THE CAN1-B149.1 AND  
.2 INSTALLATION CODE.  
3. Release the glass clips atop the stove and  
slowly lift glass panel (10) up and out of track.  
Cet equipement de conversion sera installe par  
une agence qualifiee de service conformement aux  
instructions du fabricant et toutes exigences et  
codes applicables de l’autorises avoir la  
juridiction. Si l’information dans cette Instruction  
n’est pas suivie exactement, un fey, explosion ou  
production de protoxyde de carbone peut resulter  
blessure personnelle de vie. L’agence qualifiee  
de service est esponsable de l’installation n’est  
pas propre et complete jusqu’a l’operation de  
l’appareil converti est cheque suivant les criteres  
etablis dans les instructions de proprietaire  
provisionnees avec l’equipement.  
4. Remove the log set (12) using care not to  
scratch or damage logs.  
5. Lift out the log support (14). Remove the air  
divider (15) by lifting the right side and slowly  
rotating forward.  
6. Remove burner tube (13): Using a ¼” nut  
driver remove the two screws securing the  
burner tube (13) to the stove bottom. Lift out  
the burner tube.  
7. Change the main burner orifice. Using a ½”  
open end wrench or deep well socket remove  
the burner orifice and replace with the  
appropriate orifice, supplied in the kit.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. Adjust the air shutter on the burner tube to allow 11. Change the variable regulator on the valve (Hi/  
for the proper mixing of air and gas. See Figure 2.  
The correct settings: natural 1/4” open  
propane 1/4” open  
Loknob). UsingaTorx t-20screwdriver,remove  
the three specialty screws from the front of the  
valve regulator. See Figure 4.  
12. Remove the regulator tower and the gasket.  
BE SURE TO REMOVE THE BLACK  
RUBBER GASKETS FROM THE VALVE!!!  
See Figure 4.  
AIR SHUTTER  
Figure 2  
BURNER TUBE  
13. Install the new variable regulator tower with  
the new rubber gasket.  
Thoroughly tighten new  
regulator to valve body.  
ATTENTION: Air shutter should never be  
LESS than 1/8” open.  
BESURETOREMOVE  
THE BLACK RUBBER  
GASKET FROM THE  
VALVE!!!  
WHENRE-INSTALLINGTHEBURNERTUBEBESURE  
THAT THE TUBE IS PULLED FORWARD IN THE  
MOUNTING HOLES, SECURE WITH THE TWO 1/4”  
SCREWS.  
9. Change the pilot orifice. FROM WITHIN  
THE FIREBOX, PULL THE PILOT  
HOOD OFF THE PILOT ASSEMBLY.  
Using a 4mm allen wrench thread out the pilot  
orifice (counter clockwise). Replace with the  
appropriate orifice: See Figure 3.  
Figure 4.  
#51or natural gas  
#30 for propane  
Tighten orifice into the base of the pilot  
assembly. Be sure the orifice is threaded tightly  
and flush with the base.  
14. Install the identification labels to the stove so  
that they can be seen by any person that may be  
servicing the stove.  
15. Reassemble the stove, apply gas to the system  
and check for gas leaks including all stove lines  
before and after the valve.  
10. Replace pilot hood onto pilot assembly.  
NEVER USE AN OPEN FLAME TO  
CHECK FOR GAS LEAKS.  
PILOT HOOD  
ATTENTION!! ATTENTION!!  
This is very important  
Correct gas pressure is essential for efficient and  
safe operation of the Allagash B-Vent gas stove.  
It is important that the correct gas pressure be  
established at the time of the installation. For  
more details, see the Gas Pressure section of this  
manual on page 13.  
PILOT  
ORIFICE  
PILOT ORIFICE  
SCREWS INTO  
BASE  
ALWAYS REFER TO THE LIGHTING  
INSTRUCTIONS ON PAGE 23 OF THIS  
MANUAL WHEN LIGHTING YOUR  
ALLAGASH.  
Figure 3.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAKING THE GAS CONNECTION:  
Secure all joints tightly using appropriate tools  
and sealing compounds (for propane units, be sure  
to use compounds that are propane resistant).  
Turn on gas supply and test for gas leaks using a  
soapy water solution. Never use an open flame  
to check for leaks.  
NOTE: IF THE OPTIONAL FORCED BLOWER KIT  
(PART # 129161) IS TO BE INSTALLED ON THE  
STOVE AT THE TIME OF THE INSTALLATION  
OR IN THE FUTURE, THE GAS SUPPLY LINE  
SHOULD BE INSTALLED AS CLOSE TO THE  
FLOOR AS POSSIBLE.  
Leak test:  
·
·
Mix a 50-50 solution of water and dish soap.  
Light appliance- see lighting instructions on  
page 23 of this manual or on the stove’s rating  
plate.  
USE OF A 90° ELBOW DIRECTLY OFF THE VALVE  
WILL ALLOW FOR PROPER CLEARANCE FOR  
THE BLOWER.  
·
·
Brush or spray all joints and connections with  
the soapy water solution.  
If bubbles appear at any connection or seam  
or a gas odor is detected, immediately turn  
gas control knob to the OFF position.  
The gas supply line connection is made to the valve  
just inside the left rear leg. The Gas supply line  
should be a minimum of 3/8" in diameter, or  
the appropriate size to provide sufficient gas  
pressure to the valve regardless of the input  
setting.  
Tighten or reconnect the leaking joint and retest  
for any gas leaks.  
The use of Flexible Gas Appliance Connectors is  
acceptable in many areas in the U.S.; However,  
Canadian methods vary depending on local code.  
GAS PRESSURE:  
Correct gas pressure is essential for efficient and  
safe operation of the Allagash gas stove. It is  
important that the correct pressure is established  
at the time of the installation.  
ALL INSTALLATIONS MUST COMPLY  
WITH LOCAL CODE OR IN THE ABSENCE  
OF LOCAL CODE, MUST COMPLY WITH  
THE MOST RECENT EDITION OF THE  
NATIONAL FUEL GAS CODE ANSI Z223.1/  
NFPA 54 OR CAN-B149.  
Proper gas pressure provides a consistent flow of  
gas to the appliance and is instrumental in  
checking for gas leaks.The gas control valve on  
the stove is equipped with pressure test points  
for gauge connections. The gauge connections  
are located on the front of the valve under the  
On/Off/Pilot- knob. Gauge connections are  
identified by:  
All codes require: a gas shut-off valve (gas cock)  
and union, to be installed in the supply line, and  
in the same room as the appliance. This allows  
for the disconnection of the stove for servicing  
and maintenance. See Figure 5.  
E for inlet or supply pressure (the amount of  
gas coming to the valve.)  
A for manifold pressure (the amount of gas that  
is coming out of the valve to the burner.)  
Figure 5  
E A  
T-handle gas cocks are required in Massachusetts  
in compliance with code 248CMR.  
Pressure test point as located on the front of the valve.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The appliance must be isolated from the gas supply  
line by closing its individual manual gas shut-off  
valve (gas cock) during any pressure testing of  
the gas supply piping system that is equal to or  
exceeds pressures of 1/2 psig (3.5kPa).  
HIGH ALTITUDE INSTALLATIONS:  
When installing the Allagash in high altitude  
(above 2000') situations it becomes necessary to  
compensate for the thinner air (less volume of  
air per cubic foot). Higher altitudes effect the  
atmospheric pressure and heat value of gaseous  
fuels. The lower oxygen content in the air and  
the lower gas viscosity require the use of a  
different orifice to achieve efficient, clean  
combustion at the burner tube.  
NECESSARY INLET GAS PRESSURES  
(inches water column)  
MIN  
MAX  
NATURAL GAS  
PROPANE  
5.0 WC  
7.0 WC  
11.0 WC 13.5 WC  
In the U.S.  
THE DERATING KIT MUST BE INSTALLED BY  
AN AUTHORIZED SERVICE TECHNICIAN IN  
ACCORDANCE WITH THE MANUFACTURER’S  
INSTRUCTIONS AND ALL CODES AND  
REQUIREMENTS OF THE AUTHORITY HAVING  
JURISDICTION. THE INFORMATION STICKER  
MUST BE FILLED OUT BY THE INSTALLER AND  
ADHERED TO THE APPLIANCE AT THE TIME  
OF THE CONVERSION. THE QUALIFIED SERVICE  
AGENCY PERFORMING THIS WORK ASSUMES  
RESPONSIBILITY FOR THIS DERATING.  
NECESSARY MANIFOLD PRESSURES  
(inches water column)  
MIN  
MAX  
3.5 WC  
10.0 WC  
NATURAL GAS  
PROPANE  
2.2 WC  
6.5 WC  
ALWAYS TEST PRESSURES WITH VALVE  
CONTROL KNOB SET ON HIGH  
In Canada  
THIS UNIT HAS BEEN TESTED FOR  
INSTALLATION AT HIGH ALTITUDES IN  
ACCORDANCE WITH CANADIAN TEST  
STANDARD CAN/CGA-2.17.THE DERATING  
SHALL BE CARRIED OUT IN ACCORDANCE  
WITH THE REQUIREMENTS OF THE  
Symptons of incorrect gas pressure include:  
Insufficient gas pressure:  
• Small pilot flame which can result in  
insufficient millivolts.  
• Little variation in flame picture between HI  
and LO settings.  
• Insufficient gas to support more than one  
appliance causing nusance outages or gas  
surges.  
PROVINCIAL  
AUTHORITIES  
HAVING  
JURISDICTION AND IN ACCORDANCE WITH  
THE REQUIREMENTS OF THE CAN1-B-149.1  
AND .2 INSTALLATION CODE.  
For installations from 2000ft.(610m) to  
4500ft.(1370m) the orifice size for:  
natural gas is a #42  
propane gas is a #55  
SEE THE HIGH ALTITUDE ORIFICE CHART  
Excessive gas pressure:  
• Permanent damage to valve causing complete  
appliance shut down.  
• Too large a pilot flame resulting in over heating  
of the power generator causing shut down.  
• Sooting due to impingement and/or incorrect  
fuel to air mix.  
on page 14.  
For high altitude installations consult the local  
gas distributor or the authority having jurisdiction  
for proper rating methods. If the installer must  
convert the unit to adjust for varying altitudes,  
the information sticker must be filled out by the  
installer and adhered to the appliance at the time  
of the conversion. See Figure 6.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Derating procedure  
AIR SHUTTER ADJUSTMENT/FLAME  
APPEARANCE:  
1.To derate this unit, install the appropriate ori-  
fice per the High Altitude chart.  
THE ALLAGASH B-VENT GAS STOVE IS  
SHIPPED FROM THE FACTORY EQUIPPED  
AS A NATURAL GAS STOVE; THERE-  
FORE, IT WILL BE NECESSARY WHEN  
USING THE STOVEWITH PROPANE GAS  
TO ADJUST THE AIR SHUTTER ON THE  
BURNER TUBE TO ACHIEVE THE PROPER  
GAS TO AIR MIX. See Figure 6.  
ORIFICE  
SIZE  
JØTUL  
PART #  
GAS TYPE  
ELEVATION  
NATURAL  
GAS  
0-2000'  
(0-610m)  
3/32  
#54  
#42  
#55  
129114  
PROPANE  
GAS  
0-2000'  
(0-610m)  
3096145  
NATURAL  
GAS  
2001'-4500'  
(611-1170m)  
154376  
kit  
The air shutter adjustment can also help achieve  
the desired flame appearance. Generally, flame  
appearance is a matter of preference, however  
most consumers enjoy the warm yellowish flame.  
PROPANE  
GAS  
2001'-4500'  
(611-1170m)  
750305P  
kit  
2.Remove the two ¼” hex head screws that hold  
the burner tube/log support to the bottom of  
the stove.  
Closing the air shutter - will generate very long  
yellow flames resulting in soot. Sooting produces  
black deposits on the logs, on the inside walls of  
the appliance, and potentially on the exterior  
termination cap.  
3.Remove the burner tube/log support to expose  
the main burner orifice.  
4.Remove the orifice and replace with the  
appropriate one from the high altitude kit.  
Sooting is caused by incomplete combustion in  
the flames and lack of combustion air entering  
the air shutter opening.  
5.Be sure to attach the high altitude conversion  
sticker provided with the kit to the rating plate  
on the appliance.  
Opening the air shutter - will generate a flame  
that is blue and transparent, or an “anemic”  
flame. This flame is generally more efficient but  
not as pretty.  
6. It may be necessary to adjust the air shutter  
on the burner tube. See the AIR SHUTTER/  
FLAME APPEARANCE section of this  
manual for more details.  
Jøtul recommends the following settings for the  
Allagash B-Vent gas stove:  
for use with propane 1/4” open  
for use with natural 1/4” open  
This sticker (shown below) is included in all high  
altitude kits and must be adhered to the stove  
whenever it is converted for high altitude  
installations.  
AIR SHUTTER  
Figure 7  
BURNER TUBE  
ATTENTION: Air shutter should never be  
LESS than 1/8” open.  
REMEMBER: Run the stove for a minimum of  
15 to 20 minutes for an accurate representation  
of the flame appearance- this should be done  
before and between any air shutter adjustment.  
Figure 6  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To adjust the air shutter  
1.Remove the burner tube and using a phillips  
head screwdriver loosen the screw at the air  
shutter and adjust accordingly.  
2.Be sure to retighten the screw that holds the  
air shutter setting.  
3.Reassemble the stove and close the door,  
allow stove to burn 30 minutes on the HIGH  
setting, observing the flame continuously.  
4.If the flame appears weak, slow, or sooty,  
repeat the process described above until the  
flame is as desired.  
Figure 8  
WARNING:  
INSTALLING  
DECORATIVE  
PIPE  
AIR SHUTTER ADJUSTMENTS  
SHOULD ONLY BE PERFORMED BY A  
QUALIFIED PROFESSIONAL SERVICE  
TECHNICIAN.  
BRACKETS: (The use of decorative pipe is  
optional and not included with the Allagash B-  
Vent stove.)  
To install the decorative pipe brackets on the  
Allagash simply remove the four 1/4” hex head  
screws holding the 4” flue collar on the stove.  
See Figure 9.  
INSTALLING THE LOG SET:  
It is not neccessary to remove the flue collar.  
Place the “L” shaped decorative pipe brackets  
on the flue collar and align the holes on the  
brackets, flue collar, and draft hood and secure  
all three with the four 1/4” hex head screws.  
The Allagash is equipped with a one piece log set  
and is packaged in bubble wrap inside the firebox.  
The log set must be removed from the packaging  
and arranged in the unit prior to start up of the  
gas stove. Do not handle the log set with your  
bare hands. Always wear gloves to prevent skin  
irritation from the ceramic fibers.  
Black or enamel stove pipe can now rest on the  
the draft hood of the appliance while the brackets  
center the stove pipe over the draft hood.  
To install the log set, remove the packaging and  
place the log set inside the firebox, centered from  
left to right and completely against the rear wall  
of the stove. See Figure 8.  
Reminder: single wall stove pipe can never be  
used as the vent pipe on the Allagash B-Vent  
stove.  
Embers: the stove is shipped with a package of  
glowing embers. These embers should be “pea  
size” and individually spaced across the burner  
tube screen. It is best to equally space these  
embers for optimum flame appearance. NOTE:  
YOU DO NOT HAVE TO USE ALL OF THE  
EMBERS.  
THE CERAMIC FIBER LOGS AND  
GLOWING EMBERS CAN IRRITATE YOUR  
SKIN. IF THIS HAPPENS, GENTLY WASH  
HANDS WITH WARM SOAPY WATER.  
Figure 9  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connecting the blower wiring harness:  
INSTALLING THE OPTIONAL  
BLOWER:  
1. Lift off the stove top plate.  
2. Loosen (BUT DO NOT REMOVE) the 10mm bolt  
holding the switch box to the side of the stove  
(left rear corner of the stove), and lift out the  
switch box.  
3. Remove the “blank” switch from the box.  
(Hint: break the retaining tabs holding the  
switch in the box.)  
IMPORTANT: IF THE OPTIONAL FORCED AIR  
BLOWER KIT (part # 129161) IS TO BE INSTALLED  
ON THE STOVE AT THE TIME OF THE  
INSTALLATION OR IN THE FUTURE, THE GAS  
SUPPLY LINE SHOULD BE INSTALLED AS  
CLOSE TO THE FLOOR AS POSSIBLE. USE OF A  
90° ELBOW DIRECTLY OFF THE VALVE WILL  
ALLOW FOR PROPER CLEARANCE FOR THE  
BLOWER.  
4. Insert the new HI/OFF/LO switch into the  
box.  
5. Connect the insulated wires from the blower  
to three leads on the HI/OFF/LO switch.  
BLACK wire to the HI position, WHITE  
wire to the OFF position, and the RED wire  
to the LO position. See Figure 11.  
6. Retighten the switch box to the side of the  
stove. Be sure all wires are unobstructed.  
7. Replace top plate.  
Mounting the blower:  
1. Locate the reflector sheild (28) on the back of  
the stove. Remove the cover plate from the  
reflector shield to allow the blower bracket to  
slide under the stove.  
2. Locate the two raised bosses on the bottom plate  
(back) of the stove.  
3. The blower is mounted to the stove using these  
two threaded holes.  
REMINDER:  
The blower will ONLY come on when the  
switch is in the Hi or Lo position and ONLY  
when the sensor (thermodisc) is heated by the  
stove.  
(Approximately 10 - 20 minutes after the stove  
has been running).  
4. With the blower bracket and sensor facing upward  
alignthetwomiddlemountingholesonthebracket  
with the two threaded holes on the bottom of the  
stove. See Figure 10.  
5. Use the two 6mm bolts to attach the blower to  
the stove.  
6. Be sure to tighten the bolts so that the blower is  
drawn upward and tight against the stove bottom.  
7. The heat sensor (thermodisc), that is already  
attached to the blower bracket, should be inserted  
under the stove bottom and make contact with  
the firebox! See Figure 10.  
Sensor  
(thermodisc)  
Middle mounting holes.  
Use these holes to mount  
blower.  
Direction  
under the  
stove.  
Figure 11  
Figure 10  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPILL SWITCH:  
INSTALLING THE OPTIONAL  
WALL THERMOSTAT OR REMOTE:  
The Allagash B-Vent gas stove is equipped with a  
vent “SPILL SWITCH”. This switch stops gas flow  
to the main burner in the event that the appliance  
is not vented or if the venting is blocked.  
When installing a wall mounted thermostat to  
the Allagash, it must be a 750 millivolt DC two-  
wire circut thermostat. The thermostat should  
be placed in the same room as the heater, typically  
5’ off the floor. Avoid drafty areas or any area  
that may effect the accuracy of the thermostat.  
The thermostat should be connected to the  
Allagash using a minimum of 16 gauge wire with  
a maximum length of 35 feet of wire.  
The spill switch is an important safety device  
located on the draft hood of the appliance and is  
wired directly to the thermocouple (power source  
for the stove). The “spill switch” is a bimetal  
sensor that is heat sensitive. In the event that  
the venting is not carrying the exhaust up and  
out, the heat from the exhaust will trigger the  
switch and stop the electrical current to the valve;  
thereby stopping gas flow to the main burner.  
Connect the two thermostat wire leads to the two  
lower terminals on the terminal block located  
directly above the ignitor button. Do not  
overtighten the connections. IT IS NOT  
NECESSARY TO DISCONNNECT ANY  
OTHER WIRES. See Figure 12.  
Spillage: Condition of flue gases failing to exit  
the venting system properly and instead flowing  
out of the relief opening of the draft hood and  
into the dwelling. Condition calls for  
immediate examination of the appliance and  
For the thermostat to work the On/Off/T-Stat  
switch on the back of the stove must be in the  
T-stat position, and the pilot light must be running,  
as it is the power source for the thermostat.  
venting system and corrective action.  
Source: HEARTH- Gas Training Manual  
Spillage usually occurs due to incorrct vent size,  
or incorrct installation. Be sure to read all of the  
installation requirements addressed in this manual  
for the proper and safe installation of your  
Allagash B-Vent gas stove.  
Unexplained outages can be the result of the “spill  
switch”. If you experience unexplained outages,  
contact your local Jøtul dealer for assistance.  
ANY SERVICE TO THE SAFETY SPILL SWITCH  
MUST BE DONE BY A QUALIFIED SERVICE  
AGENCY.  
Figure 12  
CAUTION:  
LABEL ALL WIRES PRIOR TO DISCONNECTION  
WHEN SERVICING THE CONTROLS. WIRING  
ERRORS CAN CAUSE IMPROPER AND  
DANGEROUS OPERATION. ALWAYS VERIFY  
PROPER OPERATION AFTER SERVICING THE  
APPLIANCE.  
At the thermostat, the two wires should be  
connected to the two connections screws on the  
thermostat base plate per the manufacturer’s  
instructions.  
Remote: When using a remote, the remote  
receiver should be wired to the terminal block  
the same way the thermostat would be. See the  
instructions above.  
ATTENTION:  
AU  
MOMENT  
DE  
L’ENTRETIENDES  
COMMANDES, ETIQUETEZ TOUS LES FILS  
AVANT LE DEBRANCHEMENT. DES ERREURS  
DE CABLAGE PEUVENT ENTRAIUN  
FONCTIONNEMENT  
DAGEREUX.  
INADEQUAT  
ET  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NO SMOKE OR SOOT SHOULD BE  
PRESENT. CHECK LOG PLACEMENT IF  
ANY SOOT OR SMOKE IS DETECTED. IF  
SOOT OR SMOKE PERSIST, THE AIR  
SHUTTER MAY NEED TO BE ADJUSTED.  
CHECKING THE SYSTEM:  
1. PURGING THE GAS LINE: When lighting  
the appliance for the first time it will take a few  
moments to clear the gas line of air. Once this  
purge is complete, the appliance will operate as  
described in the lighting instructions located on  
the stove’s rating plate and the back cover of this  
manual. All subsequent lightings of the stove  
will not require such purging of the gas line.  
See Air Shutter/Flame Appearance section of this  
manual for proper air shutter settings and  
adjustments (page 14). Note: the more offsets  
on the vent system, the greater the need for an  
air shutter adjustment.  
2. PILOT FLAME: The pilot flame should be  
steady, not lifting or floating. The flame should  
be blue in color around the pilot hood, with traces  
of yellow toward the outer edges.  
CAUTION:  
DO NOT ATTEMPT TO ALTER THE  
FLAME APPEARANCE BY  
POSITIONING THE GAS VALVE IN  
ANY OTHER POSITION OTHER  
THAN THE FULL “ON” POSITION.  
It is imperative that the pilot flame engulf the  
top 3/8” of the thermopile (power generator) and  
the top 1/8” of the quick drop out thermocouple.  
The pilot flame should project out of the pilot  
hood 1” at all three ports. See Figure 13.  
1”  
(25mm)  
Pilot Hood  
Ignitor  
3”- 4”  
5”-6”  
3/8”  
(8mm)  
Min.  
1/8”  
(3mm)  
Min.  
3”- 4”  
Thermopile  
Thermocouple  
Figure 14  
Flame appearance on the high setting after  
approximately 15 to 20 minutes burning.  
Figure 13.  
3. BURNER ADJUSTMENT: The Jøtul  
Allagash gas stove is equipped with a variable  
gas control valve. This valve provides easy  
adjustment of the flame height appearance and  
heat output. To adjust the flame between the HI  
and LO setting, rotate the HI/LO knob, located  
in the center of the valve face. Flame height will  
adjust approximately 1.0” to 1.5” between the  
HI and LO settings. See Figure 14.  
Air Inlet Shutter  
Pilot Assembly  
Burner Tube  
WARNING:  
AIR SHUTTER ADJUSTMENTS  
SHOULD ONLY BE PERFORMED BY A  
QUALIFIED PROFESSIONAL SERVICE  
TECHNICIAN.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Clean the glass only when necessary. Wipe  
surface with a clean, dampened, soft cloth.  
Follow with a dry, soft towel as desired.  
Take care not to scratch the glass surface.  
OPERATION OF APPLIANCE:  
1. The Allagash B-Vent gas stove is equipped  
with an On/Off/T-stat rocker switch or can  
be controlled using an optional wall-  
mounted thermostat. A separate switch is  
provided for the optional forced air blower  
kit.  
WARNING:  
DO NOT USE ABRASIVE CLEANERS ON THE  
GLASS. NEVER CLEAN THE GLASS WHEN IT  
IS HOT.  
2. When lit for the first time, the Allagash will  
emit an odor for several hours. This odor is  
MAINTENANCE:  
the burn-off by-products of internal paints The Allagash B-Vent gas stove and its venting  
and lubricants used in the manufacturing system should be inspected before use and at least  
process.  
annually by a qualified service technician.  
IMPORTANT:  
3. Condensation may occur on the glass upon  
each lighting of the appliance. This “fog”  
will disappear as the appliance heats up.  
ALWAYS TURN OFF THE GAS SUPPLY TO THE  
STOVE AND UNPLUG THE OPTIONAL FORCED  
AIR BLOWER KIT IF INSTALLED, BEFORE ANY  
SERVICE WORK IS PERFORMED ON THE  
STOVE.  
4. Keep the controls and the area under the  
appliance free of debris, vacuum this area  
frequently. Always keep the appliance area  
clear and free from combustible materials,  
gasoline and other flammable liquids.  
General cleaning: The firebox should be  
vacuumed out annually to remove any surface  
build up. Be sure to vacuum or wipe off the pilot  
assembly and burner orifice and burner tube. Also,  
when vacuuming the log set, be sure to handle it  
carefully as it is very fragile.  
If and when a vacuum is used on any service  
for the stove, ALWAYS be sure the stove is  
cold and there are NO hot embers or sparks.  
Gasket inspection: It is important that the glass  
gasket be inspected at least annually. Examine  
the rope gasket for signs of deterioration and make  
sure the gasket has a positive seal. This is  
important to prevent combustion gases from  
escaping into the room. Replace the gasket if  
necessary, refer to the replacement parts list on  
page 21.  
5. Remember, this appliance has a continuous  
burning pilot flame. Exercise caution when  
using products with combustible vapors.  
6. CAUTION: DO NOT OPERATE THIS  
APPLIANCE WITH THE GLASS  
REMOVED CRACKED OR BROKEN.  
REPLACEMENT OF THE GLASS  
SHOULD BE DONE BY A LICENSED OR  
QUALIFIED SERVICE PERSON. USE  
To remove the glass panel or glass gasket:  
1. Lift off the stove top.  
ONLY  
REPLACEMENT  
GLASS  
PROVIDED BY YOUR AUTHORIZED  
JØTUL DEALER. NEVER USE ANY  
SUBSTITUTE MATERIALS.  
2. Release the glass clips atop the firebox.  
3. Pull the glass frame assembly straight up and out  
of the stove.  
4. Lay the asssembly on a flat surface and lift the  
metal tabs that secure the glass panel to the frame.  
5. Install the new glass panel and gasket in the glass  
frame and secure with metal tabs. Do not over  
tighten tabs as this could break the glass.  
WARNING:  
OBSERVE CAUTION NEAR THE DOOR. THE  
GLASS PANEL MAY SHATTER UNEXPECTEDLY  
IF STRUCK WITH AN OBJECT. ALWAYS  
HANDLE THEGLASSPANELWITHCARE. WHEN  
SERVICING THE STOVE ALWAYS PULL THE  
GLASS ASSEMBLY STRAIGHT UP FOR  
REMOVAL.  
ALWAYS USE JØTUL AUTHORIZED PARTS.  
NEVER USE ANY SUBSTITUE PARTS.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Always replace any damaged or broken parts on  
the Allagash with JØTUL AUTHORIZED  
PARTS ONLY. These are available through your  
Autorized Jøtul dealer. Never use any substitute  
parts on your Allagash B-Vent gas stove.  
SERVICE LOG:  
First Year  
Name of Technician__________________  
Company Name______________________  
Date of service_______________________  
Work Performed______________________  
__________________________________  
The Allagash and its venting system should be  
inspected annually or semi-annually by a qualified  
service person or agency.  
With proper care and maintenance, your appliance  
will provide you with years of enjoyment. If you  
experience any problem or inconsistency with  
your Jøtul Allagash B-Vent gas stove, contact your  
authorized Jøtul dealer for assistance.  
To expedite the proper service for your appliance  
the following information will help your dealer  
determine what you will need for parts and service.  
SERVICE LOG:  
Two Year  
RETAIN THIS MANUAL FOR REFERENCE  
AND MAKE IT AVAILABLE TO ANYONE  
USING OR SERVICING THE STOVE.  
Name of Technician__________________  
Company Name_____________________  
Date of service______________________  
Work Performed_____________________  
____________________________________  
MODEL NAME: Allagash B-Vent Stove  
SERIAL NUMBER:__________________________  
DATE OF PURCHASE:_______________________  
AUTHORIZED DEALER:_____________________  
NAME OF INSTALLER:______________________  
TYPE OF FUEL:_____________________________  
WAS STOVE CONVERTED?___________________  
NOTES:  
SERVICE LOG:  
Third Year  
Name of Technician___________________  
Company Name______________________  
Date of service_______________________  
Work Performed______________________  
___________________________________  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ALLAGASH B-VENT PARTS LIST  
Cast Iron Parts / Enamel Colors  
PART  
MATTE  
BLU/BLK  
IVORY  
GREEN  
INDIGO  
10390336  
10390436  
10390136  
103128  
1
2
3
4
5
6
7
Left Door  
Right Door  
Front Panel  
Side Panel  
Top  
10390392 10390327 10390329 10390332  
10390492 10390427 10390429 10390432  
10390192 10390127 10390129 10390132  
102967  
102033  
102246  
10203232  
10390292 10390227 10390229 10390232 10390236  
Bottom Plate 10390092 10390027 10390029 10390032  
10390036  
103123  
Legs Single  
Short Leg Set 350074  
Top Cover  
10192592 101966  
102251  
350117  
10192532  
35007432 35007465  
350075  
*
10406592 10406527 10406529 10406532 10406536  
9
Door Pins  
125960  
129135  
154337  
129113  
129124 (6ft.)  
129122  
129121  
129123  
129132  
129320  
129109  
129310  
129180  
129149  
129313  
129186  
*
ON/OFFSwitch Only  
Reflector Shield  
Valance  
129153  
129175  
129106  
154319  
154346 NG  
129128  
129152  
129471  
129116  
129472  
129473  
129446  
129447  
3094527  
129173  
129114  
3096145  
3902573  
3902576  
154915  
154916  
129129  
10  
11  
*
Glass Clips  
28  
29  
*
Glass Assembly  
Glass Panel only  
Gasket only (7/16 tadpole)  
Log Set  
Wiring Harness -On/Off Switch  
Spud Plate Assembly  
Orifice Holder  
*
30  
*
12  
13  
*
Burner Tube  
*
Jam Nut for holder  
Pilot Assembly NG  
Gasket Pilot assembly  
Pilot Orifice NG  
Pilot Orifice LP  
Embers  
*
14  
15  
16  
17  
18  
*
Log Support  
*
Air Divider  
*
Air Deflector  
*
Exhaust Baffle  
Firebox  
*
Pilot Line  
*
*
Thermocouple  
Latch Keeper  
Heat Exchanger Gasket  
Heat Exchanger  
Thermopile  
19  
20  
*
Electrode with wire  
Burner Orifice- NG 3/32  
Burner Orifice- LPG #54  
Ignitor Button  
*
*
21  
22  
23  
24  
25  
26  
*
*
*
*
Draft Hood, Lower  
Draft Hood, Upper  
Flue Starter Collar  
Cover Plate Draft Hood  
Rear Shroud  
129184  
129185  
129189  
129183  
129179  
129449  
154350  
154389  
154374  
129157  
129148  
*
*
Ignitor Bracket  
*
B-Vent Valve NG  
B-Vent Valve LP  
Brass Elbow  
*
Spill Switch  
*
Wiring Harness -Spill Switch  
Spill Switch Wire - 32 in.  
Spill Switch Wire - 35 in.  
Wire Tie  
*
Main Gas Line (complete) 154372  
Terminal Block 129154  
*
* not illustrated  
27  
Box, On/Off/T-stat  
Hardware  
Accessories  
Leg Bolts (m6x20)  
117117  
120004  
117117  
117117  
120004  
120004  
117910  
117130  
117130  
117917  
117588  
Conversion Kit to NG  
Conversion Kit to LP  
Wall Thermostat  
Blower Kit w/Rheostat  
Remote  
154375  
154348  
750003  
129161  
750002  
129174  
750304  
Washer for Leg Bolts  
Bolt- Side Wall to Front (m6x20)  
Bolt- Front to Base (m6x20)  
Washer- Side to Front  
Washer- Firebox to Base  
Nut- Firebox to Base  
Side Clips Bolts (m6x12)  
Door Clip Bolts (m6x12)  
Valance Screws (#10x1/2)  
Door Washers  
Screen  
Floor Bracket Kit  
Only use replacement parts from an Authorized Jotul Dealer.  
For the name of the dealer nearest you, call 207 797-5912  
or write to:  
Jotul North America  
400 Riverside Street  
Portland, ME 04104  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GF3 BV Allagash Illustrated Parts Breakdown  
23  
22  
20  
24  
21  
5
4
19  
26  
27  
25  
18  
17  
4
16  
28  
15  
10  
14  
6
3
9
13  
12  
11  
30  
2
1
29  
7
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIGHTING INSTRUCTIONS  
FOR YOUR SAFETY, READ BEFORE LIGHTING.  
WARNING:  
IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY  
RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE.  
A. This appliance has a pilot which must be lit  
by hand. When lighting the pilot, follow these  
instructions exactly.  
B. BEFORE LIGHTING, smell all around the  
appliance area for gas. Be sure to smell next  
to the floor because some gas is heavier than  
air and will settle to the floor.  
• If your gas supplier cannot be reached, call the  
fire department.  
C. Use only your hand to push in or turn the gas  
control knob. Never use tools. If the knob will not  
push in or turn by hand, do not try to repair it.  
Call a qualified technician. Force or attempted  
repair may result in a fire or explosion.  
WHAT TO DO IF YOU SMELL GAS:  
• Extinguish any open flame.  
• Open windows.  
D. Do not use this appliance if any part has been  
under water. Immediately call a qualified service  
technician to inspect the appliance and to  
replace any part of the control system and any  
gas control which has been under water.  
• Do not light any appliance.  
• Do not touch any electrical switches.  
• Do not use any phone in your building.  
• Immediately call your gas supplier from a  
neighbor’s phone.  
LIGHTING INSTRUCTIONS  
1. STOP!Readthesafetyinformationabove.  
2. Access the lower controls.  
3. Turn the stove ON/OFF switch to “OFF”, or set the  
thermostat to lowest setting (if used).  
4. Confirm that the gas supply line shut-off valve is open.  
5. Push in gas control knob slightly and turn clockwise  
to “OFF”.  
8. Push in control knob all the way and hold in.  
Immediately light the pilot by triggering the spark  
ignitor (push the red button repeatedly) until pilot  
lights. Continue to hold the control knob in for  
about one minute after the pilot lights. Release  
knob and it should spring back. The pilot should  
remain lit. If it goes out, repeat Steps 5 through 8.  
• If knob does not  
NOTE:KnobcannotbeturnedfromPILOTtoOFF”  
unless the knob is pushed in slightly. Do not force.  
return when released,  
stop and immediately  
Control  
Knob  
call your service  
technician or gas  
supplier.  
• If pilot will not stay  
lit after several tries,  
PILOT ASSEMBLY  
turn the control knob  
to OFF and call your service technician or gas  
supplier.  
9. Turn gas control knob counterclockwise  
to “ON”.  
10.Turn the stove ON/OFF switch to “ON”, or set  
thermostat (if used) to desired temperature.  
CONTROL VALVE  
6. Wait five (5) minutes to clear out any gas. If you then  
smell gas, STOP! Follow “B” in the safety information  
above on this page. If you do not smell gas, go to the  
next step.  
7. Push in gas control knob slightly and turn counter-  
clockwise  
toPILOT”.  
TO TURN OFF GAS TO THE APPLIANCE:  
1. Turn ON/OFF switch to” OFF”. The pilot will remain lit for  
normalservice.  
2. For complete shutdown, turn ON/OFF switch to “OFF”.  
3. Access the lower controls.  
4. Depress gas control knob slightly and turn clock-  
wise  
to “OFF”. Do not force.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Stoves and fireplaces must be installed to conform to local and national building regulations. Before preparing for the installation of  
the appliance, it is important that the instructions issued with the unit are carefully read an strictly adhered to. Jøtul pursues a policy  
of constant product development. Products supplied may therefore differ in specification, color and type of accessories for those  
illustrated and described in the brochure.  
Jøtul vise sans cesse a ameliorer ses produits. C’est pourquoi, il se reserve le droit de modifier les specifications, couleurs etequipement  
sans avis prelable.  
Jøtul ASA  
P.O. Box 1411  
N-1602 Fredrikstad, Norway  
Jøtul North America  
400 Riverside Street  
Portland, ME 04104  
December 2000.4  
129450  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Jensen Flat Panel Television JE1911 User Manual
Jensen TV Antenna ANHD20RTL12 User Manual
JVC Digital Camera LYT1366 001A User Manual
JVC DVD Player TH S7 User Manual
JVC Home Theater System SX LC33MK2 User Manual
JVC Speaker LV44498 002A User Manual
Kenmore Vacuum Cleaner 11624614 User Manual
Kettler Exercise Bike 07863 000 User Manual
Kicker Stereo Amplifier ZX4001 User Manual
Konica Minolta Drums CM 2500d User Manual