M-4109/1104 IP510, EP510, IP511, EP511 SERIES  
AIR CONNECTIONS  
SUPPLY  
Connect air supply to 1/4 NPT port marked "IN." If the above specifications are not met, possibility of internal clogging  
exists. Also see MAINTENANCE section.  
OUTPUT  
Connect output to 1/4 NPT port marked "OUT."  
GAUGE  
The plugged 1/8 NPT port in the base of the transducer is internally connected with the "OUT" port. A pressure gauge can be  
attached to this port to monitor output pressure.  
CONTENTS  
Air Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 1  
Pressure Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 2  
Mounting  
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 2  
Direct Mounting  
Mounting Kits  
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 3  
Precautions to be observed during installation  
Calibration  
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 4  
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 5  
Agency Approvals, Special Notes, and Cautions . . . . . . . . . . . . . . . . . .Page 5 & 6  
Kits  
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 7  
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 8  
WARNING  
In order to get optimal service from this transducer and ensure warranty coverage the following MUST be followed:  
The supply air quality to this instrument must be instrument quality air as defined by ISA Standard 57.0.01-1996.  
1. Dew point not higher than 35˚F.  
2. No particulates larger than 3 microns in size.  
3. Maximum oil content of 1 ppm.  
No mechanical adjustments or calibrations are necessary or allowed. All calibration MUST be done with electrical poten-  
tiometers on the enclosed circuit board only. See “CALIBRATION” section of instructions for more information.  
TABLE 1: SUPPLY PRESSURE REQUIREMENTS  
Standard Output  
Calibration  
0-2  
PSI  
0-5  
PSI  
0-30  
PSI  
0-60  
PSI  
0-100 0-120  
PSI PSI  
1-17  
PSI  
3-9  
PSI  
3-15  
PSI  
3-27  
PSI  
6-30  
PSI  
Transducer  
Supply Pressure  
20-45 20-45 50-90 80-120 110-130 130-140 30-70 20-100 20-100 35-100 35-100  
PSI PSI PSI PSI PSI PSI PSI PSI PSI PSI PSI  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
A
M-4109/1104 IP510, EP510, IP511, EP511 SERIES  
MOUNTING  
GENERAL  
NEMA 1 and NEMA 4X transducers can be mounted in any position.  
DIRECT MOUNTING  
PIPE  
Any NEMA 1 transducers may be supported by its own plumbing for air supply and output. NEMA 4X transducers may  
also be supported using 1/2" explosion proof conduit in the electrical port.  
PANEL  
NEMA 1 transducers may be mounted to a panel with two No. 10-32 screws using threaded holes in the back of a trans-  
ducer or with two to four No. 8-32 screws using threaded holes in the bottom of a transducer.  
NEMA 4X transducers may be mounted to a panel with three No. 10-32 screws using threaded holes in the back of a  
transducer or with four No. 8-32 screws using threaded holes in the bottom of a transducer. In the case of back-mount-  
ing, if the panel extends towards the screw-on cover, a 3/16-inch-thick spacer MUST be used between the back of the  
transducer and the panel in order for the panel to clear the transducer's screw-on cover.  
EP510 AND IP510  
FRONT VIEW  
SIDE VIEW  
BOTTOM VIEW  
TOP VIEW  
Drawings and dimensions are for reference only.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
A
M-4109/1104 IP510, EP510, IP511, EP511 SERIES  
ELECTRICAL CONNECTIONS  
PRECAUTIONS TO BE OBSERVED DURING INSTALLATION  
These Transducers were tested at the EMC Test Centre, Dunfermline, Fife, KY11 5LB to the Electromagnetic  
Compatibility Directive effective January 1, 1996. The relevant EMC specifications tested were the following:  
EN 50081-1 (1992) and EN 50082-2 (1992). A Technical Construction File, Serial #107 was written and  
Certificate of Conformity issued by a Competent Body.  
EN 50081-1 (1992): Test results confirmed that no precautions need to be observed during installation regarding electro-  
magnetic emissions from the 510 or 511 Series Transducers.  
EN 50082-2 (1992): The following precautions should be taken during installation to maintain the advertised accuracy speci-  
fications. The input wiring to the transducer should be isolated from other high voltage transient wiring. The momentary  
switching on and off of nearby relays, motors, or other high capacitive or inductive loads can have a minor effect on the  
accuracy specification (0.25% of Span). Any change in output pressure is minimal and momentarily, and is considered to be  
within the performance capabilities. Use of a ferrite bead collar on the input wires entering the transducer is recommended  
should installation next to high electromagnetic interference be necessary.  
WARNING: In explosive atmospheres, electrical power must be removed from the transducer before attempting to  
remove the cover and until the cover is fully reinstalled. Failure to do so may result in electrical spark or explosion.  
CAUTION: Care must be used when inserting wires into the NPT port. Wires must not enter below the circuit board  
due to sensitive mechanical components.  
DIRECTIONS  
1. Remove the cover (see WARNING above).  
2. Bring wiring to the terminal block, located on the circuit board, through 1/2 NPT electrical conduit connection. 18  
A.W.G. is recommended; 14 A.W.G. is the maximum wire size. Connect wires to the terminal block per TABLE 2. Care  
must be exercised to prevent damage to delicate internal parts when inserting wiring through the 1/2” NPT conduit  
opening.  
3. An internal grounding screw is provided on all units to facilitate separate ground when required. An external grounding  
lug is also provided on NEMA 4X enclosures.  
4. Reinstall the cover tightly using all o-rings and locking devices to insure compliance with Agency Approvals.  
TABLE 2: ELECTRICAL CONNECTIONS  
TERMINAL BLOCK  
POSITION # 1  
POSITION # 2  
POSITION # 3  
I / P TRANSDUCER MODELS  
( -- ) NEGATIVE SIGNAL  
NOT USED  
E / P TRANSDUCER MODELS  
( + ) POSITIVE SIGNAL  
COMMON GND FOR SIGNAL  
AND SUPPLY  
( + ) POSITIVE SIGNAL  
( + ) POSITIVE SUPPLY  
CALIBRATION  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
A
M-4109/1104 IP510, EP510, IP511, EP511 SERIES  
WARNING: In explosive atmospheres, electrical power must be removed from the transducer before attempting to  
remove the cover and until the cover is fully reinstalled. Failure to do so may result in electrical spark or explosion.  
CAUTION: Only attempt electrical adjustments as described below. Any mechanical adjustments made will void the  
warranty.  
1. Remove the cover to gain access to the "SPAN",(marked S), "FINE ZERO",(marked Z) and the "DAMPING", (3/4 turn low  
profile) potentiometers. The unmarked pot “COURSE ZERO”, is used only for major calibration range changes. This  
adjustment should only be attempted by factory trained personnel. For NEMA 1 enclosure, just slide open the access  
door on the top of the cover.  
2. Set electrical input signal to 0% (e.g. 4 mA or 0 VDC).  
3. FORWARD ACTING UNITS: Using "FINE ZERO" potentiometer, adjust output pressure to 0% output (e.g. 3 psi).  
4. Set electrical input signal to 100% (e.g. 20 mA or 10 VDC).  
5. FORWARD ACTING UNITS: Using "SPAN" potentiometer, adjust output pressure to 100% output (e.g. 15 psi).  
6. Repeat steps 2 through 5 until output pressures are properly set.  
NOTE: Under certain circumstances, output pressure may exhibit cycling action. To eliminate this condition, use the  
"DAMPING" potentiometer.  
7. Reinstall cover using original screws and gaskets, if equipped.  
MAINTENANCE  
When used properly, these transducers should provide more than one million cycles without failure. If a situation should  
occur in which the transducer's behavior is abnormal, the cause is usually related to a pneumatic problem.  
ELECTRICAL MAINTENANCE  
An electrical problem must be isolated by a skilled technician. The power source and all wiring should be checked first.  
Circuit board failures are very rare, and can be confirmed by the following method. Loosen the screws, or posts that hold  
the circuit board in place. Unplug the blue connector from the circuit board, and insert two small pieces of wire into the con-  
nector.  
IMPORTANT: Connect a current source with the polarity as follows. Positive to the (RED) coil wire and Negative to the  
(BROWN) coil wire of 10 mA to the connector, which powers the yellow coil. With supply pressure on, the unit should pro-  
duce an output pressure equivalent to 80% or more of the maximum output pressure. If there is little or no output, then the  
unit is clogged. Should it produce an adequate output pressure, then the circuit board is the primary suspect. The unit must  
be returned to the factory for repair.  
PNEUMATIC MAINTENANCE  
All 510 and 511 Series transducers also have an internal orifice filter, but if contaminates do invade the transducer, they can  
clog the internal orifice and block the flow, or jam open the internal supply valve. The problem can be corrected through  
replacement of the orifice (see TABLE 5: KITS) or by cleaning the internal supply valve, or both.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
A
M-4109/1104 IP510, EP510, IP511, EP511 SERIES  
REPLACING ORIFICE:  
This can be accomplished without removing the unit from its mounting or plumbing.  
1. Turn off supply pressure and unscrew the brass orifice assembly located on the side of the housing with the gauge  
port.  
NOTE: Small sealing o-ring may remain inside of the housing. If it does, remove it with a paper clip or some other small  
probe. The replacement assembly will contain this o-ring.  
2. Install the new orifice assembly making sure the o-ring is seated on the end of the screw.  
CLEANING INTERNAL SUPPLY VALVE:  
1. Turn off the supply pressure.  
2. Use a 9/16" socket or wrench to unscrew the brass plug in the bottom of the transducer.  
NOTE: Take care not to lose the supply valve spring which is retained by the bottom plug.  
3. Clean out any dirt or debris and reassemble, making sure the stem of the supply valve is nested in the supply valve  
spring.  
AGENCY APPROVALS, SPECIAL NOTES, AND CAUTIONS  
INTRINSIC SAFETY  
All 510 and 511 Series transducers are rated intrinsically safe by both FM and CSA for:  
CLASS I, DIVISION 1, GROUPS A,B,C,D HAZARDOUS LOCATIONS.  
Proper FM-approved intrinsically-safe wiring requires external FACTORY MUTUAL RESEARCH CORPORATION ENTITY-  
APPROVED SINGLE-CHANNEL barriers to be selected, based upon MAXIMUM ENTITY PARAMETERS of 510 and 511 Series  
transducers:  
ENTITY PARAMETERS:  
Vmax = 28 V, Imax = 150 mA, Ci = 0.22uF, Li = 0 mH.  
Voc and Isc of a barrier shall not exceed Vmax and Imax of the transducer.  
(Li + Lwiring) and (Ci + Cwiring) shall not exceed La and Ca of a barrier.  
NOTICE: For proper FM and CSA approved intrinsically-safe wiring, request Drawing Number 990-439-000 from the  
Factory.  
NONINCENDIVE  
All 510 and 511 Series transducers are approved as NONINCENDIVE by FM and approved as suitable by CSA for:  
CLASS I, DIVISION 2, GROUP A, B, C, D HAZARDOUS LOCATIONS.  
A barrier is not necessary when these transducers are in these locations.  
ENCLOSURES  
Compliance with NEMA 4X and CSA ENC4 enclosure ratings require that the screw-on cover has the O-ring installed. In case  
of a need for replacement parts, see TABLE 3.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
A
M-4109/1104 IP510, EP510, IP511, EP511 SERIES  
EXPLOSION & DUST-IGNITION PROOF CERTIFICATIONS  
FACTORY MUTUAL and CANADIAN STANDARDS ASSOCIATION  
WARNING: The following ratings are valid ONLY WHEN the cover is installed for FM and CSA. BOTH the cover and  
the locking device, using tamper resistant screws must be installed. Screws are to be removed and installed with a  
special driver bit (supplied). In case of a need for replacement parts, follow TABLE 4.  
EXPLOSION PROOF FOR CLASS I, DIV 1, GROUP B, C, D.  
DUST-IGNITION PROOF FOR CLASS II, DIV 1, GROUP E, F, G.  
SUITABLE FOR CLASS III LOCATIONS.  
TABLE 3: NEMA 4X, REPLACEMENT COVER O-RINGS  
PART NAME  
O-RING SEAL, VITON  
O-RING SEAL, BUNA-N  
PART NUMBER  
214-649-000-242  
214-649-000-240  
TABLE 4: NEMA 4X, REPLACEMENT PARTS FOR COVER LOCKING DEVICE  
PART NAME  
LOCKING CLAMP  
TAMPER-PROOF SCREW  
DRIVER BIT  
PART NUMBER  
224-669-000-016  
214-648-000-401  
010132-000  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
A
M-4109/1104 IP510, EP510, IP511, EP511 SERIES  
TABLE 5: KITS  
KIT NAME  
PART NUMBER  
010135-000  
010134-000  
010143-000  
010115-000  
010136-000  
010137-000  
010137-002  
010137-001  
010137-003  
010142-000  
010138-000  
010138-001  
010138-002  
010138-003  
1. Panel Mounting Kit  
2. Valve Mounting Kit  
3. 2" Pipe Mounting Kit (Valve Mounting Kit is required)  
4. DIN Rail Adapter  
5. Cover Locking Device Kit (for NEMA 4X enclosure only)  
6. Zero based outlet range orifice with Buna-N O-rings  
7. Zero based outlet range orifice with Viton O-rings  
8. Standard outlet range orifice with Buna-N O-rings  
9. Standard outlet range orifice with Viton O-rings  
10. Hirschmann Connector Kit (3-prong plug, O-ring sealed)  
11. Pressure Gauge Kit, 15 PSI  
12. Pressure Gauge Kit, 30 PSI  
13. Pressure Gauge Kit, 60 PSI  
14. Pressure Gauge Kit, 160 PSI  
EP511 AND IP511  
SIDE VIEW  
SIDE VIEW  
TOP VIEW  
TABLE 1: WIRING TERMINATION  
PWB Terminal Block  
I/P Transducer  
E/P Transducer  
Supply (+)  
Common  
Position 3  
Positive (+)  
Position 2  
No Connection  
Negative (-)  
Position 1  
Signal (+)  
Drawings and dimensions are for reference only.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
A
M-4109/1104 IP510, EP510, IP511, EP511 SERIES  
510 and 511 Series I/P AND E/P TRANSDUCER SPECIFICATIONS  
0.10% of output span, typical  
0.25% of output span, maximum  
Accuracy:  
0.01% of output span, typical  
Hysteresis:  
Dead Band:  
Repeatability:  
0.10% of output span, maximum  
Not measurable  
0.01% of output span, typical  
0.10% of output span, maximum  
0.004% of nominal span per ˚F, typical  
0.022% of nominal span per ˚F, maximum  
Ambient Temperature Effect  
Zero:  
0.013% of calibrated span per ˚F, typical  
0.022% of calibrated span per ˚F, maximum  
Span:  
Compensated Temperature Range:  
+32˚F to +122˚F  
Operating Temperature Range  
Buna-N elastomers:  
Viton elastomers:  
-20˚F to 160˚F  
0˚F to 160˚F  
Storage Temperature Range  
Buna-N elastomers:  
Viton elastomers:  
-40˚F to 200˚F  
-15˚F to 200˚F  
Less than 0.5% of SPAN per 1G,  
5-2000 Hz, 3G maximum, 3 axes  
Vibration Effect:  
Mounting Position Effect:  
Loop Load, I/P transducer:  
Not measurable  
Less than 10 VDC drop at 20 mA  
Less than 12 VDC drop at 50 mA  
Supply Voltage, E/P Transducer  
Intrinsically Safe/Nonincendive:  
General Purpose:  
9 VDC to 28 VDC, less than 20 mA  
9 VDC to 40 VDC, less than 20 mA  
Supply Voltage Effect:  
Not measurable  
Signal Impedance, E/P Transducer:  
RFI/EMI Effect (NEMA 4X):  
Supply Pressure Requirements:  
Supply Pressure Effect:  
Air Consumption:  
6000 Ohm minimum  
Less than 0.25% of SPAN, 10V/meter, 20-1000 MHz.  
See TABLE 1  
Not measurable  
6.0 SCFH maximum  
Standard Range 7 SCFM  
Forward Flow Capacity (Supply):  
Port Sizes:  
Extended Range (over 30 PSI) 12 SCFM  
Pneumatic: 1/4" NPT  
Electrical: 1/2" NPT  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARRANTY/DISCLAIMER  
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a  
period of 13 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month  
grace period to the normal one (1) year product warranty to cover handling and shipping time. This  
ensures that OMEGA’s customers receive maximum coverage on each product.  
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service  
Department will issue an Authorized Return (AR) number immediately upon phone or written request.  
Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no  
charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser,  
including but not limited to mishandling, improper interfacing, operation outside of design limits,  
improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of  
having been tampered with or shows evidence of having been damaged as a result of excessive corrosion;  
or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating  
conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not  
limited to contact points, fuses, and triacs.  
OMEGA is pleased to offer suggestions on the use of its various products. However,  
OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any  
damages that result from the use of its products in accordance with information provided by  
OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the  
company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR  
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF  
TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY  
AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF  
LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of  
OMEGA with respect to this order, whether based on contract, warranty, negligence,  
indemnification, strict liability or otherwise, shall not exceed the purchase price of the  
component upon which liability is based. In no event shall OMEGA be liable for  
consequential, incidental or special damages.  
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic  
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical  
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or  
activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility  
as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify  
OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the  
Product(s) in such a manner.  
RETURN REQUESTS/INQUIRIES  
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE  
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN  
(AR) NUMBER FROM OMEGAS CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID  
PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return  
package and on any correspondence.  
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent  
breakage in transit.  
FOR WARRANTY RETURNS, please have the  
following information available BEFORE  
contacting OMEGA:  
FOR NON-WARRANTY REPAIRS, consult OMEGA  
for current repair charges. Have the following  
information available BEFORE contacting OMEGA:  
1. Purchase Order number under which the product  
was PURCHASED,  
1. Purchase Order number to cover the COST  
of the repair,  
2. Model and serial number of the product under  
warranty, and  
3. Repair instructions and/or specific problems  
relative to the product.  
2. Model and serial number of the product, and  
3. Repair instructions and/or specific problems  
relative to the product.  
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords  
our customers the latest in technology and engineering.  
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.  
© Copyright 2009 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied,  
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the  
prior written consent of OMEGA ENGINEERING, INC.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Where Do I Find Everything I Need for  
Process Measurement and Control?  
OMEGA…Of Course!  
Shop online at omega.comSM  
TEMPERATURE  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies  
Wire: Thermocouple, RTD & Thermistor  
Calibrators & Ice Point References  
Recorders, Controllers & Process Monitors  
Infrared Pyrometers  
PRESSURE, STRAIN AND FORCE  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Transducers & Strain Gages  
Load Cells & Pressure Gages  
Displacement Transducers  
Instrumentation & Accessories  
FLOW/LEVEL  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Rotameters, Gas Mass Flowmeters & Flow Computers  
Air Velocity Indicators  
Turbine/Paddlewheel Systems  
Totalizers & Batch Controllers  
pH/CONDUCTIVITY  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
pH Electrodes, Testers & Accessories  
Benchtop/Laboratory Meters  
Controllers, Calibrators, Simulators & Pumps  
Industrial pH & Conductivity Equipment  
DATA ACQUISITION  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Data Acquisition & Engineering Software  
Communications-Based Acquisition Systems  
Plug-in Cards for Apple, IBM & Compatibles  
Data Logging Systems  
Recorders, Printers & Plotters  
HEATERS  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Heating Cable  
Cartridge & Strip Heaters  
Immersion & Band Heaters  
Flexible Heaters  
Laboratory Heaters  
ENVIRONMENTAL  
MONITORING AND CONTROL  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Metering & Control Instrumentation  
Refractometers  
Pumps & Tubing  
Air, Soil & Water Monitors  
Industrial Water & Wastewater Treatment  
pH, Conductivity & Dissolved Oxygen Instruments  
M4109/0909  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Indesit Refrigerator BAN 12 NF User Manual
Jasco Network Card 99000 User Manual
JVC Camcorder GR AX841 User Manual
JVC Car Video System KD S777R User Manual
JVC CD Player KD G441 User Manual
JVC CRT Television AV 36P903 User Manual
JVC VCR HR A230E User Manual
Kambrook Electric Cookie Press KCP100 User Manual
Kambrook Fan KFH15 User Manual
Karcher Carpet Cleaner SC 1122 User Manual